Thermal-Magnetic Circuit Breaker 3120-...-M1-.. Description Single or two pole rocker switch/thermal-magnetic circuit breaker with trip-free mechanism (S-type TM CBE to EN 60934). The addition of a magnetic tripping module to the type 3120 range described in catalogue section Thermal Overcurrent Circuit Breakers extends the choices available to include single pole with thermal-magnetic protection; double pole switching with thermal-magnetic protection on one pole, thermal protection on the other; double pole switching with thermal-magnetic protection on one pole only. All are offered with rocker switch or push button control - two buttons for ON/OFF or one button press-to-reset only, in designs to suit one of three different panel cut-out sizes. Illumination is optional. Approved to CBE standard EN 60934 (IEC 60934). Meets the requirements regarding fire resistance of EN 60335-1 : 2007-02 Safety of household and similar electrical appliances. Motors, machine tools, office equipment, appliances. Standard current ratings and typical internal resistance values Internal resistance per pole (Ω) thermal-magn. thermal 165 94 42.5 24 20.2 12 9.7 5.40 7.17 4.30 4.9 3 2.65 1.50 1.49 0.9 1.25 0.7 0.74 0.45 0.49 0.29 0.20 0.0785 0.14 0.0595 0.114 0.0565 0.092 0.0435 0.06 0.0325 0.043 0.0215 0.030 0.0215 0.029 0.02 0.021 0.02 < 0.02 < 0.02 < 0.02 < 0.02 < 0.02 < 0.02 < 0.02 < 0.02 Illumination voltage / Power consumption Operating voltage 12 V 24 V 48 V 115 V 230 V Issue B(300410) Y+R 2 mA 2 mA 2 mA 0.9 mA 0.9 mA 2 Technical data Typical applications Current ratings (A) 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 1.2 1.5 2 2.5 3 3.5 4 5 6 7 8 10 12 14 15 16 3120-...-M... Power consumption G 3.5 mA 3.5 mA 3.5 mA 2.8 mA 2.8 mA T 4.9 4.9 4.9 2.2 2.2 mA mA mA mA mA For further details please Voltage rating Current ratings Typical life AC 240 V: 0.1...20 A DC 50 V: 0.1...4 A 4.5...16 A DC 28 V: 4.5...20 A see chapter: Technical Information AC 240 V (50/60 Hz); DC 50 V 0.1...16 A 1-pole 30,000 operations at 1 x IN, inductive 30,000 operations at 1 x IN, inductive 30,000 operations at 1 x IN, resistive 30,000 operations at 1 x IN, inductive 2-pole AC 240 V: 0.1...16 A 50,000 operations at 1 x IN, inductive 17...20 A 30,000 operations at 1 x IN, inductive DC 50 V: 0.1...16 A 50,000 operations at 1 x IN, inductive 17...20 A 10,000 operations at 1 x IN, inductive Ambient temperature -30...+60 °C (-22...+140 °F) Insulation co-ordination rated impulse pollution (IEC 60664 and 60664 A) withstand voltage degree 2.5 kV 2 reinforced insulation in operating area Dielectric strength (IEC 60664 and 60664A) test voltage operating area AC 3,000 V current path/current path AC 1,500 V Insulation resistance > 100 MΩ (DC 500 V) 0.1...2 A 100 x IN Interrupting capacity Icn 2.5...16 A 250 A 2-pole 150 A 1-pole Interrupting capacity UN (UL 1077) IN 0.1...4 A AC 250 V 200 A 5...10 A AC 250 V 2,000 A 12...14 A AC 125 V 1,000 A Degree of protection operating area IP40 (IEC 60529/DIN 40050) (with water splash protection IP54) terminal area IP00 Vibration 8 g (57-500 Hz) ± 0.61 mm (10-57 Hz) to IEC 60068-2-6, test Fc 10 frequency cycles/axis Shock 30 g (11 ms) to IEC 60068-2-27, test Ea Corrosion 96 hours at 5 % salt mist to IEC 60068-2-11, test Ka Humidity 240 hours at 95 % RH to IEC 60068-2-78, test Cab Mass approx. 53 g (2-pole) approx. 50 g (1-pole) www.e-t-a.com 2 - 31 Thermal-Magnetic Circuit Breaker 3120-...-M1-.. Ordering information 2 Ordering information Type 3120 rocker switch/circuit breaker Mounting F snap-in frame Size of frame panel thickness 3 to fit in cut-out 50.5 x 21.5 mm 1 - 6.35 mm (.039-.250 in) 5 to fit in cut-out 44.5 x 22 mm 1 - 4 mm (.039-.157 in) 6 to fit in cut-out 45 x 33.7 mm 1.2 - 2.4 mm (.047-.091 in) Number of poles 1 1-pole, thermal-magnetic protection 2 2-pole, thermal-magnetic protection on one pole, thermally protected on the other pole 5 2-pole, thermal-magnetic protection on one pole, unprotected on the other pole Mounting frame design 1 collar height 1 mm (.039 in) 3 collar height 9 mm (.354 in) (with safety frame) 4 collar height 2 mm (.079 in) with water splash protection (IP54) (not with -F6 frame) U with water splash protection and actuator guard Terminal configuration P7 blade terminals 2x2.8-0.8 mm (QC 2x.110) (terminals 12(k), 22(k), 11, 21) H7 12(k), 22(k): blade terminals 2x2.8-0.8 (QC 2x.110) 11, 21: terminal screws M3.5, blade terminals 2x2.8-0.8 (QC 2x.110) N7 as P7, but shunt terminals (12(i) and 22(i)) are blade terminals 2x2.8-0.8 (QC 2x.110) G7 as H7, but shunt terminals (12(i) and 22(i)) are blade terminals 2x2.8-0.8 (QC 2x.110) Characteristic curve M1 standard delay, therm. 1.01-1.4 x IN; magn. 4-9 x IN AC Switch style W rocker Switch colour designation OPAQUE TRANSLUCENT (for illuminated versions) 01 black 12 white 02 white 14 red 04 red 15 orange 16 sky blue 19 green Rocker markings A 0 AUS OFF B I EIN ON C D 0 AUS OFF E I EIN ON F A B C D E F X X X = without marking Rocker illumination (optional) . 12 . Y white rocker, yellow LED . 12 . T white rocker, blue LED . 14 . R red rocker, red LED . 15 . Y orange rocker, yellow LED . 16 . T blue rocker, blue LED . 19 . G green rocker, green LED Illumination voltage range (= operating voltage) 1 10 - 14 V AC/DC 2 20 - 28 V AC/DC 3 90 - 140 V AC 4 185 - 275 V AC 5 42 - 54 V AC/DC Current ratings 0.1...16 A 3120 - F 3 2 1 - N7 M1 - W 12 A Type 3120 push button switch/circuit breaker Mounting F snap-in frame Size of frame 2 special frame for fitting splash cover 3 to fit in cut-out 50.5 x 21.5 mm panel thickness 1 - 6.35 mm Number of poles 1 1-pole, thermal-magnetic protection 2 2-pole, thermal-magnetic protection on one pole, thermally protected on the other pole 5 2-pole, thermal-magnetic protection on one pole, unprotected on the other pole Mounting frame design F frame with two push buttons G frame with one push button Terminal configuration P7 blade terminals 2x2.8-0.8 mm (QC 2x.110) (terminals 12(k), 22(k), 11, 21) H7 12(k), 22(k): blade terminals 2x2.8-0.8 (QC 2x.110) 11, 21: terminal screws M3.5, blade terminals 2x2.8-0.8 (QC 2x.110) N7 as P7, but shunt terminals (12(i) and 22(i)) are blade terminals 2x2.8-0.8 (QC 2x.110) G7 as H7, but shunt terminals (12(i) and 22(i)) are blade terminals 2x2.8-0.8 (QC 2x.110) Characteristic curve M1 standard delay, therm. 1.01-1.4 x IN; magn. 4-9 x IN AC Switch style/colour D 1 push button (reset only) 01X black 04X red 12X white translucent 19X green translucent S 2 push buttons ON/OFF GRX green translucent/red WRX white translucent/red WBX white translucent/black Push button illumination (optional) G green LED, AC/DC Y yellow LED, AC/DC R red LED, AC/DC Illumination voltage range (= operating voltage) 1 10 - 14 V AC/DC 2 20 - 28 V AC/DC 3 90 - 140 V AC 4 185 - 275 V AC 5 42 - 54 V AC/DC Current ratings 0.1...16 A 3120 - F 3 2 F - N7 M1- S GRX G 4 - 10 A ordering example Approvals Authority VDE (EN 60934) CSA, UL CCC Voltage ratings AC 240 V; DC 28 V DC 50 V DC 50 V AC 250 V AC 125 V AC 250 V; DC 50 V Current ratings 0.1...16 A 0.1...16 A double pole 0.1...10 A single pole 0.1...10 A 0.1...16 A 0.1...20 A R 4 - 10 A rdering example The exact part number required can be built up from the table of choices shown above. Ordering references for optional features should be omitted if not required. All dimensions without tolerances are for reference only. In the interest of improved design, performance and cost effectiveness the right to make changes in these specifications without notice is reserved.Product markings may not be exactly as the ordering codes. Errors and omissions excepted. 2 - 32 www.e-t-a.com Issue B(300410) Thermal-Magnetic Circuit Breaker 3120-...-M1-.. Mounting frame variants Mounting style -F3.1, with rocker – Collar height 1 mm optional illumination in ON position 54 2.13 Mounting style F3.3 with rocker collar height 9 mm (.354 in.) 18 .709 21 .827 41 1.61 14 .551 flat-head screw M3.5x5 ISO 1580 (H7 / G7) tightening torque max.0.8 Nm blade terminal DIN 46244-C-Ms-S (QC 2x.110) 30 1.18 10 .394 30 1.18 9 .354 15.5 .610 blade terminals DIN 46244-C-Ms-S (QC 2 x.110) 54 2.13 35 1.38 35 1.38 33 1.30 10 .394 35 1.38 33 1.30 3.5 .138 flat-head screw M3.5x5 ISO 1580 tightening torque max. 0.8 Nm 25 .984 19.5 .768 3.5 .138 15.5 .610 21 .827 18 .709 41 1.61 Installation drawing 14 .551 9 .354 OFF position 9 7 .276 25 .984 16 .630 .354 Dimensions Mounting style F3.4 with rocker collar height 2 mm (.079 in.), with water splash protection Required safety distances for rocker and push button 27 1.06 19.5 .768 10 .394 . When installing the circuit breaker apply pressure on bezel only. 15.5 .610 3.8 .150 10 .394 operating area Mounting style F3.F-…-S-… with 2 push buttons mounting area 7 .276 7 .276 8 .315 7 .276 56 2.21 35 1.38 optional illumination in ON position 10 .394 • 25 .984 16.2 .638 54 2.13 14.2 .559 15 .591 Cut-out dimensions OFF position panel thickness max. R2 max .079 ±0.05 ±.002 ±0.05 ±.002 “A” max. R0.3 max .012 Mounting style F3.G-…-D-… with 1 push button optional illumination in ON position 25 .984 16.2 .638 Cut-out for mounting style -F5 - 0.4 with rocker -.016 max. R1.5 max .059 ±0.05 ±.002 44.5+0.2 1.75+.008 +0.4 panel mm 1.2 thickness inch .047+.016 +0,2 dimension mm 45 - 0.05 “A” inch 1.77+.008 - .002 1.6 +0.8 2.4 +1 .063 +.031 .094 +.039 +2.2 45 +1.1 - 0.05 45 - 0.05 +.087 1.77 +.043 1.77 - .002 - .002 max. R0.3 max .012 Edges of working parts: ISO 13715 Issue B(300410) 54 2.13 14.2 .559 10 .394 min. 2 min .079 22+0.3 .866+.012 1-4 mm .039-.157 in. - 0.2 -.008 OFF position 15 .591 +0.2 min. 2 min .079 max. R1.5 max .059 max. R0.3 max .012 33.7 - 0.05 50.5+0.3 1.99+.012 - 0.4 -.016 - 0.2 -.008 1.33 +.008 - .002 1-6.35 21.5+0.2 min. 2.5 min .098 .846+.008 .039-.250 - 0.4 -.016 - 0.2 -.008 Cut-out for mounting style -F6 with rocker 10 .394 Cut-out for mounting style -F3 with rocker and push button For mounting styles -F2.., -F5.., -F6.. please see section Thermal Overcurrent Circuit Breakers. This is a metric design and millimeter dimensions take precedence ( mm ) inch www.e-t-a.com 2 - 33 2 Thermal-Magnetic Circuit Breaker 3120-...-M1-.. Internal connection diagrams therm.-magn. protection on one pole thermally protected on the other pole 11 therm.-magn. protection on one pole unprotected on the other pole 21 11 line Insulated cover Y 303 068 01 2.5 .098 21 12(i) 22(i) 12(i) 12(k) 22(k) 12(k) I> 20 .787 I> Spacer for 3120-F3... Y 303 675 01/02 Spacer for 3120-F5... Y 303 676 01 58 2.28 50.5 1.99 52 2.05 44.5 1.75 Typical time/current characteristics at +23°C/+73.4°F 0.1…2 A 22 .866 28 1.10 Single or double pole load AC/DC 1) 1 .039 22.5 .886 28 1.10 12 12 0.8 .031 * 1 .039 10000 sharp-edged 2.5 .098 1000 100 * Y 303 675 01 suitable for panel thickness < 2 mm (.079 in) * Y 303 675 02 suitable for panel thickness < 4 mm (.157 in) 10 Blanking piece in -F3… size mounting frame Y 303 885 31 1 54 2.13 31 1.22 1 .039 Trip time in seconds without bends 0.1 matt finish 25 .984 16.5 .650 33 1.30 36 1.42 0.01 0.001 1 2 4 6 8 10 20 40 60 80 100 … times rated current AC/DC 1) 2.5…16 A 41 1.61 10000 1000 21 .827 Separate water splash cover, transparent (IP66) for use with -F5.. size mounting frames X 221 619 01 100 48 1.89 10 25 .984 Trip time in seconds 1 ø8 .315 16.5 .650 0.1 0.01 3.4 .134 ø4.4 .173 0.001 1 1) 2 4 6 8 10 20 40 60 80 100 … times rated current 35 1.38 2 22(i) 0.9 .035 9 .354 line Accessories Magnetic tripping currents are increased by 25% on DC supplies. 60 2.36 73 2.87 The time/current characteristic curve depends on the ambient temperature prevailing. In order to eliminate nuisance tripping, please multiply the circuit breaker current ratings by the derating factor shown below. See also section Technical information. Ambient temperature °F -22 -4 +14 +32 +73.4 +104 +122 +140 °C -30 -20 -10 0 +23 +40 +50 +60 Derating factor 0.8 0.76 0.84 0.92 1 1.08 1.16 1.24 This is a metric design and millimeter dimensions take precedence ( mm ) inch 2 - 34 www.e-t-a.com Issue B(300410) Thermal-Magnetic Circuit Breaker 3120-...-M1-.. Description Single or two pole rocker switch/thermal-magnetic circuit breaker with trip-free mechanism (S-type TM CBE to EN 60934). The addition of a magnetic tripping module to the type 3120 range described in catalogue section Thermal Overcurrent Circuit Breakers extends the choices available to include single pole with thermal-magnetic protection; double pole switching with thermal-magnetic protection on one pole, thermal protection on the other; double pole switching with thermal-magnetic protection on one pole only. All are offered with rocker switch actuation. Illumination is optional. Approved to CBE standard EN 60934 (IEC 60934). Meets the requirements regarding fire resistance of EN 60335-1 : 2007-02 Safety of household and similar electrical appliances. 3120-F7..-M1.. 2 Typical applications Technical data Motors, machine tools, office equipment, appliances. Standard current ratings and typical internal resistance values Current ratings (A) 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 1.2 1.5 2 2.5 3 3.5 4 5 6 7 8 10 12 14 15 16 Internal resistance per pole (Ω) thermal-magn. thermal 165 94 42.5 24 20.2 12 9.7 5.40 7.17 4.30 4.9 3 2.65 1.50 1.49 0.9 1.25 0.7 0.74 0.45 0.49 0.29 0.20 0.0785 0.14 0.0595 0.114 0.0565 0.092 0.0435 0.06 0.0325 0.043 0.0215 0.030 0.0215 0.029 0.02 0.021 0.02 < 0.02 < 0.02 < 0.02 < 0.02 < 0.02 < 0.02 < 0.02 < 0.02 Illumination voltage / Power consumption Operating voltage 12 V 24 V 48 V 115 V 230 V Issue B(300410) Y+R 2 mA 2 mA 2 mA 0.9 mA 0.9 mA Power consumption G 3.5 mA 3.5 mA 3.5 mA 2.8 mA 2.8 mA T 4.9 4.9 4.9 2.2 2.2 mA mA mA mA mA For further details please Voltage rating Current ratings Typical life AC 240 V: 0.1...20 A DC 50 V: 0.1...4 A 4.5...16 A DC 28 V: 4.5...20 A see chapter: Technical Information AC 240 V, 50/60 Hz; DC 50 V 0.1...16 A 1-pole 30,000 operations at 1 x IN, inductive 30,000 operations at 1 x IN, inductive 30,000 operations at 1 x IN, resistive 30,000 operations at 1 x IN, inductive 2-pole AC 240 V: 0.1...16 A 50,000 operations at 1 x IN, inductive 17...20 A 30,000 operations at 1 x IN, inductive DC 50 V: 0.1...16 A 50,000 operations at 1 x IN, inductive 17...20 A 10,000 operations at 1 x IN, inductive Ambient temperature -30...+60 °C (-22...+140 °F) Insulation co-ordination rated impulse pollution (IEC 60664 and 60664 A) withstand voltage degree 2.5 kV 2 reinforced insulation in operating area Dielectric strength (IEC 60664 and 60664A) test voltage operating area AC 3,000 V current path/current path AC 1,500 V Insulation resistance > 100 MΩ (DC 500 V) 0.1...2 A 100 x IN Interrupting capacity Icn 2.5...16 A 250 A 2-pole 150 A 1-pole Interrupting capacity UN (UL 1077) IN 0.1...4 A AC 250 V 200 A 5...10 A AC 250 V 2,000 A 12...14 A AC 125 V 1,000 A Degree of protection operating area IP40 (IEC 60529/DIN 40050) (with water splash protection IP54) terminal area IP00 Vibration 8 g (57-500 Hz) ± 0.61 mm (10-57 Hz) to IEC 60068-2-6, test Fc 10 frequency cycles/axis Shock 30 g (11 ms) to IEC 60068-2-27, test Ea Corrosion 96 hours at 5 % salt mist to IEC 60068-2-11, test Ka Humidity 240 hours at 95 % RH to IEC 60068-2-78, test Cab Mass approx. 53 g (2-pole) approx. 50 g (1-pole) www.e-t-a.com 2 - 35 Thermal-Magnetic Circuit Breaker 3120-...-M1-.. Ordering information 25 .984 15.5 .610 3 .118 48±0.2 1.89±.008 44.2-0.2 1.74-.008 33 1.30 8.9 .350 Mounting style -F7.N and -F7.R 15.5 .610 9 .354 3.5 .138 LINE 11 12(k) 10 30 .394 1.18 12(i) 21 .827 blade terminals DIN 46244-C-Ms-S (QC 2 x .110) flat head screw ISO1580 M3.5x5-MS tightening torque max. 0.8 Nm 14 .551 18 .709 41 1.61 34 1.34 18.8 .740 15.5 .610 60 2.36 44.2-0,2 1.74-.008 5.9 .232 8.9 .350 Mounting style -F7.P and -F7.S 33 1.30 LINE LINE 11 12(k) 3.5 .138 30 1.18 10 .394 12(i) 15.5 .610 21 .827 blade terminals DIN 46244-C-Ms-S (QC 2 x .110) flat head screw ISO1580 M3.5x5-MS tightening torque max. 0.8 Nm I 0 9 .354 Type 3120 rocker switch/circuit breaker Mounting F snap-in frame Size of frame panel thickness 7 to fit in cut-out 44.5 x 22 mm 1 - 4 mm (.039-.157 in) Number of poles 1 1-pole, thermal-magnetic protection 2 2-pole, thermal-magnetic protection on one pole, thermally protected on the other pole 5 2-pole, thermal-magnetic protection on one pole, unprotected on the other pole Mounting frame design N new design, grey P snap-on actuator guard grey Q snap-on splash cover grey R new design, black S snap-on actuator guard black T snap-on splash cover black Terminal configuration P7 blade terminals 2x2.8-0.8 mm (QC 2x.110) (terminals 12(k), 22(k), 11, 21) H7 12(k), 22(k): blade terminals 2x2.8-0.8 (QC 2x.110) 11, 21: terminal screws M3.5, blade terminals 2x2.8-0.8 (QC 2x.110) N7 as P7, but shunt terminals (12(i) and 22(i)) are blade terminals 2x2.8-0.8 (QC 2x.110) G7 as H7, but shunt terminals (12(i) and 22(i)) are blade terminals 2x2.8-0.8 (QC 2x.110) Characteristic curve M1 standard delay, therm. 1.01-1.4 x IN; magn. 4-9 x IN AC Betätigungselement A Switch style Switch colour designation OPAQUE TRANSLUCENT (for illuminated versions) 01 black 12 white 02 white 14 red 04 red 15 orange 09 green 19 greeen 20 blue 30 blue 26 sky blue 36 sky blue Rocker markings 14 .551 18 .709 41 1.61 Q 3120 - F 7 2 N - N7 M1- A 30 Q T 4 - 10 A Mounting style -F7.Q and -F7.T 60 2.36 44.8 1.76 11.5 .453 34 1.34 18.6 .732 3.5 .138 ordering example 21 .827 blade terminals DIN 46244-C-Ms-S (QC 2 x .110) flat head screw ISO1580 M3.5x5-MS tightening torque max. 0.8 Nm LINE 11 12(k) 10 30 .394 1.18 12(i) 15.5 .610 9 .354 12 14 15 19 30 36 Q „I“ and „0“ moulded in Push button illumination (optional) Q T white wocker, blue LED Q R red rocker, red LED Q Y orange rocker, yellow LED Q G green rocker, green LED Q G blue rocker, green LED Q T sky blue rocker, blue LED Illumination voltage range (= operating voltage) 1 10 - 14 V 2 20 - 28 V 3 90 - 140 V 4 185 - 275 V 5 42 - 54 V AC/DC Current ratings 0.1...16 A 33 1.30 2 Dimensions 18 .709 14 .551 41 1.61 This is a metric design and millimeter dimensions take precedence ( mm ) inch 2 - 36 www.e-t-a.com Issue B(300410) Thermal-Magnetic Circuit Breaker 3120-...-M1-.. Installation drawing Internal connection diagrams When installing the circuit breaker apply pressure on bezel only. therm.-magn. protection on one pole thermally protected on the other pole therm.-magn. protection on one pole unprotected on the other pole operating area 12(i) LINE 11 12(k) line 21 11 12(i) 22(i) 12(k) 22(k) .276 8 .315 7 .276 22(i) 12(k) I> 12 12 7 .276 21 12(i) I> 7 line 15.5 .610 10 .394 11 Typical time/current characteristics at +23°C/+73.4°F 10 .394 mounting area Single or double pole load 0.1…2 A AC/DC 1) Cut-out dimensions 10000 22+0.3 1- 4 .866+.012 .039 - .157 -0,4 -.016 -0,2 -.008 ±0,05 ±.002 Trip time in seconds 1000 min. 2 min .079 max. R1.5 max .059 44.5+0.4 1.75+.016 max. R0.3 max .012 100 10 1 0.1 0.01 Edges of working parts: ISO 13715 0.001 1 CCC 10000 Voltage ratings AC 240 V; DC 28 V DC 50 V DC 50 V AC 250 V AC 125 V AC 250 V; DC 50 V Current ratings 0.1...16 A 0.1...16 A double pole 0.1...10 A single pole 0.1...10 A 0.1...16 A 0.1...20 A 1000 Trip time in seconds CSA, UL 4 6 8 10 20 40 60 80 100 … times rated current AC/DC 1) 2.5…16 A Approvals Authority VDE (EN 60934) 2 100 10 1 0.1 0.01 0.001 1 1) 2 4 6 8 10 20 40 60 80 100 … times rated current Magnetic tripping currents are increased by 25% on DC supplies. The time/current characteristic curve depends on the ambient temperature prevailing. In order to eliminate nuisance tripping, please multiply the circuit breaker current ratings by the derating factor shown below. See also section Technical information. Ambient temperature °F -22 -4 +14 +32 +73.4 +104 +122 +140 °C -30 -20 -10 0 +23 +40 +50 +60 Derating factor 0.8 0.76 0.84 0.92 1 1.08 1.16 1.24 This is a metric design and millimeter dimensions take precedence ( mm ) inch Issue B(300410) www.e-t-a.com 2 - 37 2 Thermal-Magnetic Circuit Breaker 3120-...-M1-.. Accessories Insulated cover Y 303 068 01 20 .787 Spacer for 3120-F7... Y 303 676 01 52 2.05 44.5 1.75 1 .039 22.5 .886 28 1.10 1 .039 0.8 .031 2.5 .098 sharp-edged without bends Translucent water splash cover (IP54) X 222 143 01 Consisting of - Y 307 097 01 snap-on frame with actuator guard - Y 307 096 01 soft plastic cover 18.8 .740 60 2.36 11.5 .453 34 1.34 10.1 .398 Snap-on frame with actuator guard (can be snapped on as switch-on protection or switch-off protection) Y 307 097 01 18.8 .740 5.9 .232 60 2.36 2 0.9 .035 9 .354 2.5 .098 34 1.34 10.1 .398 This is a metric design and millimeter dimensions take precedence ( mm ) inch All dimensions without tolerances are for reference only. In the interest of improved design, performance and cost effectiveness the right to make changes in these specifications without notice is reserved.Product markings may not be exactly as the ordering codes. Errors and omissions excepted. 2 - 38 www.e-t-a.com Issue B(300410)