Metering Devices IQ 300
Technical Data
Supersedes TD.17.31.T.E
pages 1 – 8 dated May 2001
Description
Page
Metering Devices IQ 300
General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Features, Functions and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Application Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Field Wiring Connection Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
2
2
3
4
5
8
TD02601006E
For more information visit: www.eatonelectrical.com
Technical Data
Page 2
Metering Devices IQ 300
Effective: March 2004
IQ 300
Features, Functions
and Benefits
Control Power Input
■
All +/- 10%.
Model IQ 310:
❑ 110 – 240 Vac 50/60 Hz
❑ 125 – 250 Vdc
■ Model IQ 320:
❑ 90 – 600 Vac 50/60 Hz
❑ 48 – 250 Vdc
■ Models IQ 330 and IQ 330M:
❑ 90 – 600 Vac 50/60 Hz
❑ 48 – 250 Vdc
■
Optional I/O
The IQ 330 and IQ 330M models include
two digital inputs and two outputs
along with a single analog input. The
digital inputs can be used to show the
status of an external device on the
meter display and via communications.
Examples include breaker position,
motor starter status, protective relay
trip or any other device status. The
analog input accepts a standard 4 to
20 mA input, is shown on the display
from 0 to 100%, and is available
through communications. The analog
input can be used to read transformer
temperature, motor speed or any
analog process signal.
IQ 300
General Description
The IQ 300’s thin display and flexible
mounting capabilities make it perfectly
suited for any application where an
accurate, multi-function meter is
desired, such as panelboard and
switchboard mains and feeders, motor
control centers, and both low voltage
and high voltage metal-enclosed
switchgear.
One IQ 300 provides an alternative
to an assortment of individually wired
and mounted ammeters, voltmeters,
ammeter and voltmeter switches,
wattmeters, varmeters, power factor
meters, frequency meters, watthour
and demand meters. ANSI C12 Class
10 revenue metering accuracy makes
the IQ 300 an ideal choice for circuits
where precise energy measurements
are required.
The IQ 300 can be easily programmed
from the faceplate with display and
keypad which features a two-line
reverse mode LCD display with LED
backlight. Auto scrolling function
allows hand-free viewing of all voltages and currents. All measurements
can be viewed from the local display.
The IQ 300 can also be configured
and monitored using PowerPort ,
free software available on the Eaton
Electrical Web site, or can be used
with PowerNet, the full-featured
power management system software
(models IQ 320 and IQ 330 only).
The two digital outputs can be remotely
controlled via communications or can
be programmed in either of two different
alarm modes. In one mode, the output
will activate based upon the measured
system voltage and can act as either
an over- or undervoltage relay. The
second mode will enable the output
to alarm on a phase loss condition.
Meter Sealing
Display Settings
Display automatically switches to power
saving dim mode after 5 minutes of
inactivity. User-selectable settings for:
■
■
Application Description
■
■
■
■
Meter Mounting
■
■
Bright display with eight large
numeric digits along with a 10character description of the measured value makes the IQ 300 ideal
for switchgear mounting.
■ Base unit can be display mounted
for simple, one-hole installation.
■ Base unit can be mounted up to
10 feet (3 m) away from display and
has three mounting options.
Ratings
■
Application to 200 kV, no PTs to 600 V.
CT ratios selectable from 5 to 8,000 A.
■ Three-phase, 3- or 4-wire.
■
For more information visit: www.eatonelectrical.com
Monitoring of electrical parameters.
Can be used on both low voltage
and medium voltage assemblies.
Metered/Monitored Parameters
■
The IQ 330 and IQ 330M models have
a hardware seal that prohibits the
changing of settings or the resetting
of values.
The base module can be display
mounted, panel mounted, DIN-rail
mounted or side-mounted. The display
only requires 1.50 inches (38.1 mm)
behind the panel it is mounted in,
including display to base cable.
Auto scroll time-out.
Contrast.
■
■
■
■
■
Phase currents.
Voltage, L-L, L-N.
Power: real, reactive, apparent.
Energy: watthours, varhours,
and VA hours.
Frequency.
Power factor.
Minimum/maximum values.
System demand.
KYZ energy pulse output.
Note: Models IQ 320 and IQ 330 only.
■
ANSI C12.16 revenue metering
accuracy (1%).
Communications
The IQ 320 and IQ 330 models have
interface capability to computer network for data collection, storage and/or
printout via the Cutler-Hammer
PowerNet system.
The IQ 330M model has an industry
standard RS-485 multi-drop serial
interface with the Modbus RTU
communication protocol built-in. This
interface can be used to connect the
IQ 330M to a wide variety of Building
Management Systems, Programmable
Logic Controllers and other systems
utilizing this communication network.
TD02601006E
Metering Devices IQ 300
Technical Data
Effective: March 2004
Physical Characteristics
■
■
■
■
■
■
■
■
Two-line reverse mode LED back-lit
LCD display with helpful icons.
Standard IQ meter cutout.
Display height: 10.25 inches
(260.4 mm).
Display width: 6.72 inches
(170.7 mm).
Display depth (behind panel):
0.75 inches (19.1 mm).
Membrane faceplate designed and
tested to meet NEMA 12, 3R and
IP 52.
Base unit can be mounted on the
rear of the display.
Three separate base mounting
options.
Listings/Certifications
UL and CUL listed under UL 3111
■ CSA C22.2 # 1010.1.
■ Meets IEC 1010-1.
■ CE mark for applications where
European compliance is required.
■
Specifications
Compatible with the following systems:
Digital Inputs
Note: Models IQ 330 and IQ 330M only.
Input voltage rating: 12 – 48 Vdc.
■ Maximum current rating: 96 mA.
Digital Outputs
Note: Models IQ 330 and IQ 330M only.
■
Maximum voltage: 125 Vac/175 Vdc.
Maximum current: 96 mA.
■ Isolation rating: 3750 Vrms.
■
Note: Models IQ 330 and IQ 330M only.
■
■
■
■
■
Current Input (Each Channel)
■
■
■
■
■
Nominal full scale current:
5 amperes ac.
Current range: two times nominal.
Overload withstand:
❑ 10 amperes ac continuous
❑ 50 amperes ac 1 second
Input impedance: 0.01 ohms.
Burden: 0.025 VA.
Voltage Input (Each Channel)
■
Voltage range (nominal):
90 – 600 Vac.
■ Overload withstand:
❑ 660 Vac continuous
❑ 800 Vac 1 second
■ Input impedance: 2 megaohms.
Models IQ 320, IQ 330/330M:
Maximum voltage:
240 Vac/300 Vdc, 125 Vac/175 Vdc.
■ Maximum current:
96 mA 96 mA.
■ Isolation rating:
3750 Vrms 3750 Vrms.
TD02601006E
Select from 256 ratios ranging
from 5:5 to 5:8,000.
PT (Primary) Settings
■
Select from 256 ratios ranging
from 1.0:1 to 1690:1.
Table 1. Environmental Conditions
Base
Display
Operating Temperature
-20 – 50°C
0 – 50°C
Storage Temperature
-30 – 85°C
-20 – 70°C
Maximum Relative Humidity
80% up to 31°C decreasing linearly 50% at
50°C.
Frequency Range
■
50/60 Hz.
Communication Speed
■
INCOM: 1200 or 9600 baud.
Note: Models IQ 320 and IQ 330 only.
■
RS-485:
❑ 9600 or 19,200 baud
❑ Half duplex
Note: Model IQ 330M only.
KYZ Output
■
Value displayed: 0 – 100%.
Minimum resolution: 1%.
Nominal current rating:
4 – 20 mA, 30 mA.
Maximum current input: 30 mA.
Maximum voltage input: 6.8 V.
Input impedance: 231 ohms.
CT (Primary) Settings
■
■
IEC 1010-1 Incl. Amend. 1 and 2.
EN61010-1.
■ CSA C22.2 Number 1010.0.
■ UL 3111.
■
EMC
Emissions
■
■
■
Analog Input
■
Three-phase, 3-wire.
■ Three-phase, 4-wire.
Safety
■
■
Page 3
■
■
■
■
■
FCC Part 15 Class A.
CISPR 11/EN55011.
Group 1 Class A.
Immunity.
Electrostatic Discharge.
EN61000-4-2/EN50082-2.
4 kV Contact Discharge.
8 kV Air Discharge.
Electrical Fast Transient
■
EN61000-4-4/EN50082-2.
2 kV power lines.
■ 2 kV signal lines.
■
Radiated Immunity
■
■
EN61000-4-3/EN50082-2.
10 V/m.
Conducted Immunity
■
■
EN61000-4-6/EN50082-2.
10 V/m.
Power Frequency Magnetic Field
■
■
EN61000-4-8.
30 A/m.
Table 2. Metered Values
(Based on Full Scale up to 5 A, Reading >5 A)
Metered Parameter
Accuracy
ac Ampere Phase
Voltage
+/- 0.5%
+/- 0.5%
Watts
Vars
VA
+/- 1.0%
+/- 1.0%
+/- 1.0%
kW Hours
kvar Hours
kVA Hours
+/- 1.0%
+/- 1.0%
+/- 1.0%
Power Factor
Frequency
Demand
+/- 2.0%
+/- 0.1%
+/- 1.0%
Table 3. Control Power Input
Input
IQ 310
Vac
110 – 240 ±10%
90 – 600 ±10%
50/60 Hz ±10%
50/60 Hz ±10%
Electrical Standards
Frequency
Range
■
ac Burden
180 mA
■
Vdc
125 – 250 ±10%
dc Burden
7W
UL, CUL and CSA listed.
UL File Number E185559.
■ CE mark for applications where
European compliance is required.
For more information visit: www.eatonelectrical.com
IQ 320/330
180 mA
48 – 250 ±10%
7W
Technical Data
Page 4
Metering Devices IQ 300
Effective: March 2004
Field Wiring Connection Diagrams
3-Phase, 3-Wire (Up to 600 Volts)
Proper CT polarity is critical to the proper operation of the meter.
LOAD
LINE
3-Phase, 4-Wire (Up to 600 Volts)
Proper CT polarity is critical to the proper operation of the meter.
LOAD
LINE
L3
N
L2
L3
L1
L2
L1
H2A
H1A
H2B
H1B
H2C
H2A
H1C
H1A
Case ground
must be
connected for
proper operation.
IQ 300
VA VB VC NEU PS1 PS2
FUSE
H2B
H1B
H2C
H1C
IQ 300
VA VB VC NEU PS1 PS2
IQ 320/330
90 – 600 Vac
48 – 250 Vdc
IQ 310
110 – 240 Vac
125 – 250 Vdc
Control Power
Case ground
must be
connected for
proper operation.
FUSE
Control Power
Figure 1. 3-Phase, 3-Wire (Up to 600 Volts)
IQ 310
110 – 240 Vac
125 – 250 Vdc
Figure 3. 3-Phase, 4-Wire (Up to 600 Volts)
3-Phase, 3-Wire (Above 600 Volts)
Proper CT polarity is critical to the proper operation of the meter.
LINE
LOAD
3-Phase, 4-Wire (Above 600 Volts)
Proper CT polarity is critical to the proper operation of the meter.
LINE
L3
N
L2
L3
L1
LOAD
L2
FUSE
L1
H2A
Open Delta
PT
Connection
IQ 320/330
90 – 600 Vac
48 – 250 Vdc
H1A
H2B
H1B
FUSE
H2C
H1C
H2A
IQ 300
VA VB VC NEU PS1 PS2
Case ground
must be
connected for
proper operation.
FUSE
Control Power
H1A
H2B
H1B
H2C
H1C
WYE
Connection
IQ 300
VA VB VC NEU PS1 PS2
IQ 320/330
90 – 600 Vac
48 – 250 Vdc
IQ 310
110 – 240 Vac
125 – 250 Vdc
FUSE
Control Power
Figure 2. 3-Phase, 3-Wire (Above 600 Volts)
Case ground
must be
connected for
proper operation.
IQ 320/330
90 – 600 Vac
48 – 250 Vdc
IQ 310
110 – 240 Vac
125 – 250 Vdc
Figure 4. 3-Phase, 4-Wire (Above 600 Volts)
For more information visit: www.eatonelectrical.com
TD02601006E
Metering Devices IQ 300
Technical Data
Effective: March 2004
Dimensions
.50
(12.7)
6.72
(170.7)
.39
(9.9)
Normal
Program
IQ 300
10.25
(260.4)
Menu
Scroll
Enter
.35
(8.9)
Figure 5. Dimensions for the IQ 300 Display Module (Only)
TD02601006E
For more information visit: www.eatonelectrical.com
Page 5
Metering Devices IQ 300
Technical Data
Page 6
Effective: March 2004
6.72
(170.7)
4.01
(101.9)
.50
(12.7)
Normal
Program
IQ 300
IQ 220/IQ 320
10.25
(260.4)
Menu
Scroll
E18559
Enter
Figure 6. Dimensions for the IQ 300 Display Module with Base (All Models)
For more information visit: www.eatonelectrical.com
TD02601006E
Metering Devices IQ 300
Technical Data
Effective: March 2004
.78
(19.8)
3.55
(90.2)
2.00
(50.8)
.25
(6.4)
Page 7
5.38
(136.7)
2.69
(68.3)
8.90
(226.1)
Slot Size
0.125 Rad.
(4 places)
9.38
(238.3)
6.68
(169.7)
4.55
(115.6)
5.05
(128.3)
4.45
(113.0)
4.69
(119.1)
.06 (1.5) R
4 Places
2.23 (Optional)
(56.6)
2.53
(64.3)
5.06
(128.5)
Figure 7. IQ 300 Base Mounting Hole Pattern
DIN Clip
Figure 9. IQ 300 Display Mounting Hole Pattern
IQ 300
Base Module
DIN Rail
L-Bracket
Figure 8. IQ 300 Optional Base Mounting
TD02601006E
For more information visit: www.eatonelectrical.com
.218 (5.5) Diameter
10 Places
Technical Data
Page 8
Metering Devices IQ 300
Effective: March 2004
Product Selection
Table 4. IQ 300 Features
Feature
Table 5. Ordering Information
IQ 300 Meter Catalog Number
IQ310
IQ320
IQ330
IQ330M
Voltage Sensing
Range
0 – 600 Vac
0 – 600 Vac
0 – 600 Vac
0 – 600 Vac
ANSI C12
Accuracy
Yes
Yes
Yes
Yes
Power Supply
110 – 240 Vac 90 – 600 Vac 90 – 600 Vac 90 – 600 Vac
125 – 250 Vdc 48 – 250 Vdc 48 – 250 Vdc 48 – 250 Vdc
Communications No
INCOM
INCOM
Modbus RTU
KYZ Output
No
Yes
Yes
Yes
Digital Inputs
No
No
2
2
Digital Outputs
No
No
2
2
Analog Input
No
No
1
1
Anti-Tamper
Seal
No
No
Yes
Yes
Description
Catalog
Number
IQ 310 Complete Meter with Base Module,
Display, and 14-inch (355.6 mm) Cable —
no communications, no pulse output
IQ310
IQ 320 Complete Meter with Base Module,
Display, and 14-inch (355.6 mm) Cable —
with INCOM communications and pulse output
IQ320
IQ 330 Complete Meter with Base Module,
Display, and 14-inch (355.6 mm) Cable —
with INCOM communications, pulse output,
2 contact outputs, 2 digital inputs, 1 analog
input and anti-tamper seal
IQ330
IQ 330M Complete Meter with Base Module,
Display, and 14-inch (355.6 mm) Cable —
with RS-485 Modbus communications, pulse output,
2 contact outputs, 2 digital inputs,
1 analog input and anti-tamper seal
IQ330M
IQ 300D Display Module Only
IQ300D
3 feet (0.9 m) Long CAT 5 Cable
6 feet (1.8 m) Long CAT 5 Cable
10 feet (3.0 m) Long CAT 5 Cable
IQ23CABLE
IQ26CABLE
IQ210CABLE
CSA is a registered trademark of the Canadian Standards
Association. Modbus is a registered trademark of Modicon,
a division of Schneider Electric Industries SA. NEMA is the
registered trademark and service mark of the National Electrical
Manufacturers Association. UL and CUL are federally registered