Metering Devices IQ 300 Technical Data Supersedes TD.17.31.T.E pages 1 – 8 dated May 2001 Description Page Metering Devices IQ 300 General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Features, Functions and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Application Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Field Wiring Connection Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2 2 3 4 5 8 TD02601006E For more information visit: www.eatonelectrical.com Technical Data Page 2 Metering Devices IQ 300 Effective: March 2004 IQ 300 Features, Functions and Benefits Control Power Input ■ All +/- 10%. Model IQ 310: ❑ 110 – 240 Vac 50/60 Hz ❑ 125 – 250 Vdc ■ Model IQ 320: ❑ 90 – 600 Vac 50/60 Hz ❑ 48 – 250 Vdc ■ Models IQ 330 and IQ 330M: ❑ 90 – 600 Vac 50/60 Hz ❑ 48 – 250 Vdc ■ Optional I/O The IQ 330 and IQ 330M models include two digital inputs and two outputs along with a single analog input. The digital inputs can be used to show the status of an external device on the meter display and via communications. Examples include breaker position, motor starter status, protective relay trip or any other device status. The analog input accepts a standard 4 to 20 mA input, is shown on the display from 0 to 100%, and is available through communications. The analog input can be used to read transformer temperature, motor speed or any analog process signal. IQ 300 General Description The IQ 300’s thin display and flexible mounting capabilities make it perfectly suited for any application where an accurate, multi-function meter is desired, such as panelboard and switchboard mains and feeders, motor control centers, and both low voltage and high voltage metal-enclosed switchgear. One IQ 300 provides an alternative to an assortment of individually wired and mounted ammeters, voltmeters, ammeter and voltmeter switches, wattmeters, varmeters, power factor meters, frequency meters, watthour and demand meters. ANSI C12 Class 10 revenue metering accuracy makes the IQ 300 an ideal choice for circuits where precise energy measurements are required. The IQ 300 can be easily programmed from the faceplate with display and keypad which features a two-line reverse mode LCD display with LED backlight. Auto scrolling function allows hand-free viewing of all voltages and currents. All measurements can be viewed from the local display. The IQ 300 can also be configured and monitored using PowerPort , free software available on the Eaton Electrical Web site, or can be used with PowerNet, the full-featured power management system software (models IQ 320 and IQ 330 only). The two digital outputs can be remotely controlled via communications or can be programmed in either of two different alarm modes. In one mode, the output will activate based upon the measured system voltage and can act as either an over- or undervoltage relay. The second mode will enable the output to alarm on a phase loss condition. Meter Sealing Display Settings Display automatically switches to power saving dim mode after 5 minutes of inactivity. User-selectable settings for: ■ ■ Application Description ■ ■ ■ ■ Meter Mounting ■ ■ Bright display with eight large numeric digits along with a 10character description of the measured value makes the IQ 300 ideal for switchgear mounting. ■ Base unit can be display mounted for simple, one-hole installation. ■ Base unit can be mounted up to 10 feet (3 m) away from display and has three mounting options. Ratings ■ Application to 200 kV, no PTs to 600 V. CT ratios selectable from 5 to 8,000 A. ■ Three-phase, 3- or 4-wire. ■ For more information visit: www.eatonelectrical.com Monitoring of electrical parameters. Can be used on both low voltage and medium voltage assemblies. Metered/Monitored Parameters ■ The IQ 330 and IQ 330M models have a hardware seal that prohibits the changing of settings or the resetting of values. The base module can be display mounted, panel mounted, DIN-rail mounted or side-mounted. The display only requires 1.50 inches (38.1 mm) behind the panel it is mounted in, including display to base cable. Auto scroll time-out. Contrast. ■ ■ ■ ■ ■ Phase currents. Voltage, L-L, L-N. Power: real, reactive, apparent. Energy: watthours, varhours, and VA hours. Frequency. Power factor. Minimum/maximum values. System demand. KYZ energy pulse output. Note: Models IQ 320 and IQ 330 only. ■ ANSI C12.16 revenue metering accuracy (1%). Communications The IQ 320 and IQ 330 models have interface capability to computer network for data collection, storage and/or printout via the Cutler-Hammer PowerNet system. The IQ 330M model has an industry standard RS-485 multi-drop serial interface with the Modbus RTU communication protocol built-in. This interface can be used to connect the IQ 330M to a wide variety of Building Management Systems, Programmable Logic Controllers and other systems utilizing this communication network. TD02601006E Metering Devices IQ 300 Technical Data Effective: March 2004 Physical Characteristics ■ ■ ■ ■ ■ ■ ■ ■ Two-line reverse mode LED back-lit LCD display with helpful icons. Standard IQ meter cutout. Display height: 10.25 inches (260.4 mm). Display width: 6.72 inches (170.7 mm). Display depth (behind panel): 0.75 inches (19.1 mm). Membrane faceplate designed and tested to meet NEMA 12, 3R and IP 52. Base unit can be mounted on the rear of the display. Three separate base mounting options. Listings/Certifications UL and CUL listed under UL 3111 ■ CSA C22.2 # 1010.1. ■ Meets IEC 1010-1. ■ CE mark for applications where European compliance is required. ■ Specifications Compatible with the following systems: Digital Inputs Note: Models IQ 330 and IQ 330M only. Input voltage rating: 12 – 48 Vdc. ■ Maximum current rating: 96 mA. Digital Outputs Note: Models IQ 330 and IQ 330M only. ■ Maximum voltage: 125 Vac/175 Vdc. Maximum current: 96 mA. ■ Isolation rating: 3750 Vrms. ■ Note: Models IQ 330 and IQ 330M only. ■ ■ ■ ■ ■ Current Input (Each Channel) ■ ■ ■ ■ ■ Nominal full scale current: 5 amperes ac. Current range: two times nominal. Overload withstand: ❑ 10 amperes ac continuous ❑ 50 amperes ac 1 second Input impedance: 0.01 ohms. Burden: 0.025 VA. Voltage Input (Each Channel) ■ Voltage range (nominal): 90 – 600 Vac. ■ Overload withstand: ❑ 660 Vac continuous ❑ 800 Vac 1 second ■ Input impedance: 2 megaohms. Models IQ 320, IQ 330/330M: Maximum voltage: 240 Vac/300 Vdc, 125 Vac/175 Vdc. ■ Maximum current: 96 mA 96 mA. ■ Isolation rating: 3750 Vrms 3750 Vrms. TD02601006E Select from 256 ratios ranging from 5:5 to 5:8,000. PT (Primary) Settings ■ Select from 256 ratios ranging from 1.0:1 to 1690:1. Table 1. Environmental Conditions Base Display Operating Temperature -20 – 50°C 0 – 50°C Storage Temperature -30 – 85°C -20 – 70°C Maximum Relative Humidity 80% up to 31°C decreasing linearly 50% at 50°C. Frequency Range ■ 50/60 Hz. Communication Speed ■ INCOM: 1200 or 9600 baud. Note: Models IQ 320 and IQ 330 only. ■ RS-485: ❑ 9600 or 19,200 baud ❑ Half duplex Note: Model IQ 330M only. KYZ Output ■ Value displayed: 0 – 100%. Minimum resolution: 1%. Nominal current rating: 4 – 20 mA, 30 mA. Maximum current input: 30 mA. Maximum voltage input: 6.8 V. Input impedance: 231 ohms. CT (Primary) Settings ■ ■ IEC 1010-1 Incl. Amend. 1 and 2. EN61010-1. ■ CSA C22.2 Number 1010.0. ■ UL 3111. ■ EMC Emissions ■ ■ ■ Analog Input ■ Three-phase, 3-wire. ■ Three-phase, 4-wire. Safety ■ ■ Page 3 ■ ■ ■ ■ ■ FCC Part 15 Class A. CISPR 11/EN55011. Group 1 Class A. Immunity. Electrostatic Discharge. EN61000-4-2/EN50082-2. 4 kV Contact Discharge. 8 kV Air Discharge. Electrical Fast Transient ■ EN61000-4-4/EN50082-2. 2 kV power lines. ■ 2 kV signal lines. ■ Radiated Immunity ■ ■ EN61000-4-3/EN50082-2. 10 V/m. Conducted Immunity ■ ■ EN61000-4-6/EN50082-2. 10 V/m. Power Frequency Magnetic Field ■ ■ EN61000-4-8. 30 A/m. Table 2. Metered Values (Based on Full Scale up to 5 A, Reading >5 A) Metered Parameter Accuracy ac Ampere Phase Voltage +/- 0.5% +/- 0.5% Watts Vars VA +/- 1.0% +/- 1.0% +/- 1.0% kW Hours kvar Hours kVA Hours +/- 1.0% +/- 1.0% +/- 1.0% Power Factor Frequency Demand +/- 2.0% +/- 0.1% +/- 1.0% Table 3. Control Power Input Input IQ 310 Vac 110 – 240 ±10% 90 – 600 ±10% 50/60 Hz ±10% 50/60 Hz ±10% Electrical Standards Frequency Range ■ ac Burden 180 mA ■ Vdc 125 – 250 ±10% dc Burden 7W UL, CUL and CSA listed. UL File Number E185559. ■ CE mark for applications where European compliance is required. For more information visit: www.eatonelectrical.com IQ 320/330 180 mA 48 – 250 ±10% 7W Technical Data Page 4 Metering Devices IQ 300 Effective: March 2004 Field Wiring Connection Diagrams 3-Phase, 3-Wire (Up to 600 Volts) Proper CT polarity is critical to the proper operation of the meter. LOAD LINE 3-Phase, 4-Wire (Up to 600 Volts) Proper CT polarity is critical to the proper operation of the meter. LOAD LINE L3 N L2 L3 L1 L2 L1 H2A H1A H2B H1B H2C H2A H1C H1A Case ground must be connected for proper operation. IQ 300 VA VB VC NEU PS1 PS2 FUSE H2B H1B H2C H1C IQ 300 VA VB VC NEU PS1 PS2 IQ 320/330 90 – 600 Vac 48 – 250 Vdc IQ 310 110 – 240 Vac 125 – 250 Vdc Control Power Case ground must be connected for proper operation. FUSE Control Power Figure 1. 3-Phase, 3-Wire (Up to 600 Volts) IQ 310 110 – 240 Vac 125 – 250 Vdc Figure 3. 3-Phase, 4-Wire (Up to 600 Volts) 3-Phase, 3-Wire (Above 600 Volts) Proper CT polarity is critical to the proper operation of the meter. LINE LOAD 3-Phase, 4-Wire (Above 600 Volts) Proper CT polarity is critical to the proper operation of the meter. LINE L3 N L2 L3 L1 LOAD L2 FUSE L1 H2A Open Delta PT Connection IQ 320/330 90 – 600 Vac 48 – 250 Vdc H1A H2B H1B FUSE H2C H1C H2A IQ 300 VA VB VC NEU PS1 PS2 Case ground must be connected for proper operation. FUSE Control Power H1A H2B H1B H2C H1C WYE Connection IQ 300 VA VB VC NEU PS1 PS2 IQ 320/330 90 – 600 Vac 48 – 250 Vdc IQ 310 110 – 240 Vac 125 – 250 Vdc FUSE Control Power Figure 2. 3-Phase, 3-Wire (Above 600 Volts) Case ground must be connected for proper operation. IQ 320/330 90 – 600 Vac 48 – 250 Vdc IQ 310 110 – 240 Vac 125 – 250 Vdc Figure 4. 3-Phase, 4-Wire (Above 600 Volts) For more information visit: www.eatonelectrical.com TD02601006E Metering Devices IQ 300 Technical Data Effective: March 2004 Dimensions .50 (12.7) 6.72 (170.7) .39 (9.9) Normal Program IQ 300 10.25 (260.4) Menu Scroll Enter .35 (8.9) Figure 5. Dimensions for the IQ 300 Display Module (Only) TD02601006E For more information visit: www.eatonelectrical.com Page 5 Metering Devices IQ 300 Technical Data Page 6 Effective: March 2004 6.72 (170.7) 4.01 (101.9) .50 (12.7) Normal Program IQ 300 IQ 220/IQ 320 10.25 (260.4) Menu Scroll E18559 Enter Figure 6. Dimensions for the IQ 300 Display Module with Base (All Models) For more information visit: www.eatonelectrical.com TD02601006E Metering Devices IQ 300 Technical Data Effective: March 2004 .78 (19.8) 3.55 (90.2) 2.00 (50.8) .25 (6.4) Page 7 5.38 (136.7) 2.69 (68.3) 8.90 (226.1) Slot Size 0.125 Rad. (4 places) 9.38 (238.3) 6.68 (169.7) 4.55 (115.6) 5.05 (128.3) 4.45 (113.0) 4.69 (119.1) .06 (1.5) R 4 Places 2.23 (Optional) (56.6) 2.53 (64.3) 5.06 (128.5) Figure 7. IQ 300 Base Mounting Hole Pattern DIN Clip Figure 9. IQ 300 Display Mounting Hole Pattern IQ 300 Base Module DIN Rail L-Bracket Figure 8. IQ 300 Optional Base Mounting TD02601006E For more information visit: www.eatonelectrical.com .218 (5.5) Diameter 10 Places Technical Data Page 8 Metering Devices IQ 300 Effective: March 2004 Product Selection Table 4. IQ 300 Features Feature Table 5. Ordering Information IQ 300 Meter Catalog Number IQ310 IQ320 IQ330 IQ330M Voltage Sensing Range 0 – 600 Vac 0 – 600 Vac 0 – 600 Vac 0 – 600 Vac ANSI C12 Accuracy Yes Yes Yes Yes Power Supply 110 – 240 Vac 90 – 600 Vac 90 – 600 Vac 90 – 600 Vac 125 – 250 Vdc 48 – 250 Vdc 48 – 250 Vdc 48 – 250 Vdc Communications No INCOM INCOM Modbus RTU KYZ Output No Yes Yes Yes Digital Inputs No No 2 2 Digital Outputs No No 2 2 Analog Input No No 1 1 Anti-Tamper Seal No No Yes Yes Description Catalog Number IQ 310 Complete Meter with Base Module, Display, and 14-inch (355.6 mm) Cable — no communications, no pulse output IQ310 IQ 320 Complete Meter with Base Module, Display, and 14-inch (355.6 mm) Cable — with INCOM communications and pulse output IQ320 IQ 330 Complete Meter with Base Module, Display, and 14-inch (355.6 mm) Cable — with INCOM communications, pulse output, 2 contact outputs, 2 digital inputs, 1 analog input and anti-tamper seal IQ330 IQ 330M Complete Meter with Base Module, Display, and 14-inch (355.6 mm) Cable — with RS-485 Modbus communications, pulse output, 2 contact outputs, 2 digital inputs, 1 analog input and anti-tamper seal IQ330M IQ 300D Display Module Only IQ300D 3 feet (0.9 m) Long CAT 5 Cable 6 feet (1.8 m) Long CAT 5 Cable 10 feet (3.0 m) Long CAT 5 Cable IQ23CABLE IQ26CABLE IQ210CABLE CSA is a registered trademark of the Canadian Standards Association. Modbus is a registered trademark of Modicon, a division of Schneider Electric Industries SA. NEMA is the registered trademark and service mark of the National Electrical Manufacturers Association. UL and CUL are federally registered trademarks of Underwriters Laboratories Inc. Eaton Electrical 1000 Cherrington Parkway Moon Township, PA 15108-4312 USA tel: 1-800-525-2000 www.eatonelectrical.com © 2004 Eaton Corporation All Rights Reserved Printed in USA Publication No. TD02601006E / Z-2347 March 2004