Product Description Part Winding Starting Electric Fire Pump Controllers DescriptionFiretrol® FTA1250 Part Winding Starting Fire Pump Controllers can be used where the characteristics of the power source do not permit full voltage starting. The controller monitors, displays and records fire pump system information. When the controller is actuated by the pressure switch, START pushbutton, deluge valve contact, etc., the first contactor closes, connecting one of the motor windings to the line. During starting, the motor will draw approximately 65% of its normal locked rotor current and develop approximately 42% of its normal starting torque. After a time delay, the second contactor closes, connecting the second winding in parallel with the first. The motor then draws its normal running current and develops its rated torque. ApprovalsFiretrol fire pump controllers are listed by Underwriters' Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, Standard for Industrial Control Equipment, and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA 20, Installation of Centrifugal Fire Pumps, and NFPA 70, National Electrical Code. Standard FeaturesThe following are included as standard with each controller: n Voltage surge protector n Main Disconnect Switch sized for connected motor horsepower and voltage FTA1250 n Fire pump Circuit Breaker n Motor contactor n Emergency Manual Run Mechanism to mechanically close motor contactor contacts in an emergency condition n Built-in Start and Stop push-buttons to bypass automatic start circuits n Door mounted display/interface panel featuring a 40 Character Vacuum Fluorescent Display, Membrane Type User Control Push-buttons and easy to read LED Indicators n Single handle Isolating Disconnect Switch/Circuit Breaker mechanism n POWER ON LED n PUMP RUN LED n PHASE FAILURE LED n PHASE REVERSAL LED n LOW PRESSURE LED n DELUGE OPEN LED n INTERLOCK ON LED n TRANSFER SWITCH NORMAL LED (If unit ordered with Automatic Power Transfer Switch) n TRANSFER SWITCH EMERGENCY LED (If unit ordered with Automatic Power Transfer Switch) n EMERGENCY ISOLATING SWITCH OFF LED (If unit ordered with Automatic Power Transfer Switch) n Minimum Run Timer / Off Delay Timer n Daylight Savings Time option n Weekly Test Timer n Motor Acceleration Timer n Elapsed Time Meter n Digital Pressure Display n 1.44M Floppy Disk Drive n Data Log n Event Log (3000 Events) n True RMS Metering with simultaneous 3 phase display of amps and volts n Disk Error message n Disk Near Full message n Pressure Error message n Motor Over 320% message n Local Start message n Remote Start message n Emergency Start message n Fail To Start message n Undervoltage message n Overvoltage message n Low Suction Pressure message n High Speed Open Serial Communications Port n NEMA Type 2 enclosure SPECIAL ENCLOSURES -T NEMA Type 3R (IEC IP14) -E NEMA Type 4 (IEC IP56) -F NEMA Type 4X (IEC IP56) FTA1000, 1250, 1300 FTA1350, 1500, 1800, 1900 -G NEMA Type 12 (IEC IP52) CIRCUIT BREAKER OPTION -N Intermediate withstand rating 150,000 Amps RMS Sym. -P High withstand rating 200,000 Amps RMS Sym Note: Intermediate and High withstand ratings may not be available for all horsepowers and voltages. Consult factory for availability. ANTI-CONDENSATION SPACE HEATERS -H 120 Volt Space Heater -J 120 Volt Space Heater With Thermostat -K 120 Volt Space Heater With Humidistat -L 240 Volt Space Heater -M 240 Volt Space Heater With Thermostat -N 240 Volt Space Heater With Humidistat PRESSURE TRANSDUCERS -B 0-600 psi (0-42.25 bar) Pressure Transducer for Fresh Water Service -C 0-300 psi (0-21.1 bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service -D 0-600 psi (0-42.25 bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service AUTOMATIC POWER TRANSFER SWITCHES (Refer to publication SD900-21) FTA900 - generator set emergency supply FTA901 - bypass isolation switch for generator set emergency supply FTA950 - second utility emergency supply FTA951 - bypass isolation switch for second utility emergency supply ALARMS -AC Extra contacts (normally open & normally closed) for remote indication, pump operating -AF Audible and Visible low pump room temperature alarm -AG Built-in reservoir low alarm -AH Audible low suction pressure alarm -AM Contacts for remote indication, pump fail to start -AV Contacts for remote indication, low pump room temperature PD1250-20 -AW Contacts for remote indication, reservoir low -AY Contacts for remote indication, low suction pressure -AZ Low pump room temperature switch, mounted and wired -BW Extra contacts for remote indication, phase failure/phase reversal -BY Contacts for remote indication, pump overload -COM Visible Low suction pressure alarm with manual reset push-button -DZ Weekly test timer solenoid and manual test push-button -EG Visible relief valve discharge alarm -EH Contacts for remote indication, relief valve discharge -EJ Built-in flow meter on alarm -EK Contacts for remote indication, flow meter on -P Built-in alarm system (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) -PB Built-in low system pressure visible alarm with manual reset -PE Contacts for remote indication, low system pressure -PT Built-in alarm system, 220 VAC supervisory power (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication) -HV Audible alarm device -LVA Visible pump on demand alarm -LW Audible and visible pump on demand alarm (requires (-HV)) -LY Contacts for remote indication, pump on demand (requires (-LVA) or (-LW)) MISCELLANEOUS -DZ Weekly test timer with test push-button -ED Load shed circuits -EL Series pumping, high zone controller -EM Series pumping, mid zone controller(s) -EN Series pumping, low zone controller -PY Motor space heater output contacts -S Tropicalization -ZPA Customized, annual service display message (when factory programmed or programmed by Firetrol representative during start-up) -ZPB High Quality Impact Printer with paper take-up mechanism Export packaging FTA1000, 1250, 1300 FTA1350, 1500, 1800, 1900