D758 MiniPurge® Manual ML 434 Important Note: It is essential for safety that the installer and user of the Expo system follow these instructions. Please refer to the standard for principles and definition. These instructions apply only to the pressurizing system. it is the responsibility of the manufacturer of the pressurized enclosure to provide instructions for the enclosure. Expo Technologies reserves the right to replace any component, with one of the equivalent functionality. ML434 | v12l 23-Mar-16 Section 1: System Specification ................................................................................................1 MiniPurge® Control Unit Data...................................................................................................2 Relief Valve Unit and Purge Outlet Valve with integral spark arrestor......................................3 Section 2: Quick User Guide ......................................................................................................3 Installation ................................................................................................................................3 Operation of the System ...........................................................................................................3 Section 3: Application Suitability ..............................................................................................4 Section 4: Description and Principle of Operation ..................................................................5 Section 5: Main Components .....................................................................................................6 Air Supply Filter / Regulator......................................................................................................6 Logic Air Supply Regulator .......................................................................................................6 Minimum Pressure Sensor .......................................................................................................6 Purge Flow Sensor ...................................................................................................................6 Intermediate Sensor .................................................................................................................7 Purge Timer ..............................................................................................................................7 Purge Complete Valve..............................................................................................................7 OR Gate ...................................................................................................................................7 Alarm Only Circuit (/AO) ...........................................................................................................7 Visual Indicators .......................................................................................................................7 Power Interlock Switch .............................................................................................................8 Alarm / Pressurized Switch.......................................................................................................8 System Purging Switch (Optional)............................................................................................8 Intermediate Switch ..................................................................................................................8 Purge Valve ..............................................................................................................................8 Purge Flow Restrictor ...............................................................................................................8 CLAPS Sensor .........................................................................................................................8 CLAPS Regulator .....................................................................................................................8 Relief Valve Unit .......................................................................................................................8 /PA Terminal Box......................................................................................................................9 Section 6: Installation of the System.........................................................................................9 Relief Valve Unit .......................................................................................................................9 Air Supply Quality .....................................................................................................................9 Pipe Work ...............................................................................................................................10 Multiple Enclosures ................................................................................................................10 Provision and Installation of Alarm Devices ...........................................................................10 Power Supplies and their Isolation .........................................................................................11 Power Interlock Switch ...........................................................................................................11 Section 7: Commissioning .......................................................................................................11 Commissioning the System ....................................................................................................11 Normal Operation ...................................................................................................................13 Section 8: Maintenance of the System....................................................................................13 General maintenance .............................................................................................................13 Additional maintenance checks ..............................................................................................13 Re-calibration of the Relief Valve Unit ....................................................................................13 Re-calibration of the Pressure Sensors ..................................................................................14 Section 9: Fault Finding............................................................................................................14 General Information................................................................................................................14 System purges correctly but trips and auto re-purges at the end of the purge time. ..............15 Relief Valve opens (continuously or intermittently).................................................................15 System enters purging but purge indication does not occur...................................................16 Section 10: Recommended Spares List ..................................................................................16 Section 11: Glossary.................................................................................................................16 Section 12: Drawings and Diagrams .......................................................................................17 Section 13: Certifications .........................................................................................................17 ML434 | v12l i Section 1: System Specification 5 X LC / ss / OV / PC / PA Size 5 = MiniPurge® Purge flow rate: 6000 NI/min PA = Power and Alarm. Integral Ex e IIC T5 Gb Ex tb IIIC T100ºC Db IP66 Power and Alarm. Integral Ex e IIC T4 Gb Power = 250 Vac 4 Amp (AC15) DPNO Ex d IIC T6 Gb Ex tb IIIC T80ºC Db Alarm = 250 Vac 4 Amp (AC15) SPCO Ex d IIC T6 Gb Approval / Certification ATEX Certificate: Sira 01ATEX1295X 0518 II 2(2) GD Ex [pxb] IIC T6 Gb Ex [pxb] IIIC T85ºC Db Tamb -20ºC to +55ºC PC = Pressurized Control. Automatic leakage compensation (CLAPS) IECEx Certificate: IECEx SIR07.0027X Ex [pxb] IIC T6 Gb Ex [pxb] IIIC T85ºC Db Tamb -20ºC to +55ºC OV = Purge Outlet Valve is pneumatically operated MiniPurge® Housing ss = Stainless Steel 316L TÜV INMETRO Certificate: TÜV 12.1462X Ex [pxb] IIC T6 Gb Ex [pxb] IIIC T85ºC Db Tamb -20ºC to +55ºC Pressurization Method LC = Leakage Compensation Page 1 ML434 | v12l MiniPurge® Control Unit Data Action on Pressure Failure: Alarm and Trip (isolate power to pressurized enclosure), user adjustable Alarm Only. Type of Operation: Automatic leakage compensation using the Closed Loop Automatic Pressurization System (CLAPS System). Leakage Compensation Capacity 1000 NI/min initial maximum pressurized enclosure leakage. 1900 NI/min maximum as leakage increases. Enclosure Material: Stainless Steel 316L. Mounting Method: Wall mounting straps. Fixing holes as per drawing. Temperature Limits: -20oC to +55oC Compressed Air Supply: Clean, dry, oil free air or inert gas. Refer to Air Supply Quality section in Installation of the System. Supply Pressure: 5 to 16 barg (73 to 232 psi). Main Regulator: Set at 5 barg, 40 m automatic drain supply inlet filter. Logic Regulator and Gauge: Fitted and set to 2.3 barg (33 psi). Process Connections: Purge supply and outlet to pressurized enclosure 1” NPT female. Minimum supply line 25 mm (1”) ID tube, inlet sized appropriately for flow rate. Reference points & signals 1/8” NPT female, minimum 6 mm pipe to be used. Visual Indicators: Alarm (Red ) / Pressurized (Green System Purging (Yellow /PA Terminal Box: ). ) Stainless Steel, Ex e IIC T5 Gb / Ex tb IIIC T100ºC Db IP66 Tamb: -20ºC to +55ºC with terminals, front access cover & lower removable gland plate. Stainless Steel, Ex e IIC T4 Gb Tamb: -20ºC to +60ºC with terminals, front access cover & lower removable gland plate. Power Interlock Switch: DPNO switch, contact ratings 250 Vac 4 Amps (AC-15) / 24V DC 4A, Ex d IIC T6 Gb / Ex tb IIIC T80ºC Db. Alarm Switch: SPCO switch, contact ratings 250 VAC 4 Amps (AC-15) / 24V DC 4A, Ex d IIC T6 Gb / Ex tb IIIC T80ºC Db. Intermediate Switch: SPCO switch, contact ratings 250 VAC 4 Amps (AC-15) / 24V DC 4A, Ex d IIC T6 Gb / Ex tb IIIC T80ºC Db. System Purging Switch (Optional): SPCO switch, contact ratings 250 VAC 4 Amps (AC-15) / 24V DC 4A, Ex d IIC T6 Gb / Ex tb IIIC T80ºC Db. Minimum Pressure Sensor: Minimum: 0.5 mbarg. Maximum: 5.0 mbarg. Default Setting: 1.5 mbarg. Tolerance -0, +0.7 mbarg. Intermediate Sensor: Minimum: 2.0 mbarg. Maximum: 10 mbarg. Default Setting: 5.0 mbarg. Tolerance: -0, +10% Note: There must be a 1.5 mbarg difference between the minimum pressure and intermediate sensors. Purge Flow Sensor: ML434 | v12l Set at 6.4 mbarg (Tolerance: -0, +10%). Page 2 CLAPS Sensor: Minimum: 5.0 mbarg. Maximum:15 mbarg. Default Setting: 10 mbarg. Tolerance: -0, +10% Note: there must be a 2.5 mbarg difference between the intermediate and CLAPS sensor calibration point. For example: Minimum pressure = 5 mbarg, intermediate pressure = 6.5 mbarg, CLAPS sensor = 9 mbarg. Purge Time: User selectable, 3-off time increments available. 10, 15 or 20 Minutes (-0 + 25%). Maximum available purge time of 45 minutes. Default Setting 45 minutes. Weight: 27 kg (60lb). Relief Valve Unit and Purge Outlet Valve with integral spark arrestor Type: Bore: Relief Valve Lift-Off Pressure: Flow Rate: Material: Mounting Method: Weight: RLV104/ss/FS, Design number D758RLV. Purge Outlet Valve Ø 104 mm, Relief Valve Ø 75 mm. Minimum: 20 mbarg. Maximum: 50 mbarg. Default: 30 mbarg (+0, -20%). Range: 2000, 3000, 4000, 5000, or 6000 NI/min. Default: 2000 NI/min. Housing: Stainless steel 316L. Gasket: Silicone foam. Spark arrestor: Stainless steel mesh. Rectangular cut-out and fixing holes as per drawing. 7 kg (15.4 lb) Section 2: Quick User Guide Installation The MiniPurge® System must be installed by a competent engineer, in accordance with relevant standards, such as IEC / EN 60079-14 and any local codes or practice. • Mount the purge system in accordance with the hook-up drawing. • Ensure the system is installed according to the full instructions in the “Installation of the System” section of this manual. • All pipings must be clean and free of dirt, condensation and debris prior to connection to the purge system or pressurized enclosure. • It is strongly recommended that a local isolation valve is installed on the air supply upstream of the purge system. Note: Most faults are due to restricted air supply, inadequate supply pipe work or drop in air supply pressure during the purge process. Operation of the System Once the system is installed correctly, turn on the air supply. Refer to Commissioning section. Indicator Colour Status Alarm / Pressurized Red Low pressure alarm (enclosure pressure too low) Page 3 ML434 | v12l Indicator Colour Status Purging Black Purge flow too low or not in purge mode The purge system commences the purge cycle: • The purge air will enter the enclosure. • The pressurized enclosure will obtain a positive pressure. • The Purge Outlet Valve will open within the Relief Valve Unit. • The air will then exit the Relief Valve Unit housing via the spark arrestor. Indicator Colour Status Alarm / Pressurized Green Pressurized (minimum enclosure pressure achieved) Purging Black Purge flow too low Open the Purge Flow Restrictor Valve until the air flow reaches the required rate; the system will initiate the timed purge cycle. Start a stopwatch when the purging indicator turns yellow. Indicator Colour Status Alarm / Pressurized Green Pressurized Purging Yellow Purge flow rate above minimum On completion of an uninterrupted purge cycle of the required length, the system will indicate purge complete. Stop the stopwatch when the purging indicator turns black. Indicator Colour Status Alarm / Pressurized Green Pressurized and in leakage compensation mode Purging Black No longer in purge mode Check stopwatch timing to verify that the actual purge time is equal to or greater than the required purge time. Note: The recorded purge time must never be less than the required purge time. The system is now operating correctly in leakage compensation mode. If the system has not performed as expected, check the installation thoroughly and ensure it has been carried out according to the instructions. If an obvious problem has not been highlighted and corrected, follow the procedures in the Fault Finding section. If all checks have been carried out and the system still does not perform as expected, contact your local distributor or Expo Technologies. Section 3: Application Suitability MiniPurge® systems are certified for use in hazardous locations, where the hazardous location is nonmining (above ground) and the hazard is caused by flammable gasses, vapours or dust. Depending on the model the systems may be used in IECEx and ATEX Zone 1(21) and/or Zone 2(22) - Categories 2 and 3 respectively. ML434 | v12l Page 4 MiniPurge® systems may be used for hazards of any gas group. Apparatus associated with the MiniPurge® system, such as intrinsically safe signalling circuits and flameproof enclosures containing switching devices may be limited in their gas group. The certification documentation supplied with any such devices must be checked to ensure their suitability. This system is primarily designed for use with compressed air. Where other inert compressed gasses are used (Nitrogen, for example) the user must take suitable precautions so that the build up of the inert gas does not present a hazard to health. Consult the Control of Substances Hazardous to Health (COSHH) data sheet for the gas used. Where a risk of asphyxiation exists, a warning label must be fitted to the pressurized enclosure. The following materials are used in the construction of MiniPurge® systems. If substances that will adversely affect any of these materials are present in the surrounding environment, please consult Expo Technologies for further guidance. Materials of Construction Stainless Steel Aluminium Acrylic Mild (Carbon) Steel Nylon Silicone Brass Polyurethane Neoprene ABS Polycarbonate Polyester (glass filled) Section 4: Description and Principle of Operation The MiniPurge® system is pneumatic in operation, with electrical interfaces. Purge and pressurization is a method of protection used in Zone 1 (21) and/or Zone 2 (22) hazardous locations to ensure that the interior of an enclosure is free of flammable gas. Addition of a MiniPurge® system allows the electrical equipment within the enclosure to be used safely in a hazardous location. The principle of purge and pressurization is as follows: • Clean compressed air or inert gas is drawn from a non-hazardous location. • The interior of the pressurized enclosure is flushed to remove any hazardous gas or dust. • This is introduced into the pressurized enclosure to keep the internal pressure at least 0.5 mbarg above the external pressure. • Whilst pressurized, flammable gas cannot enter the enclosure from the environment. Prior to switching on the power to the electrical equipment, the enclosure must be purged to remove any flammable gas that might have entered the enclosure before pressurization. Purging is the process of removal contaminated air and replacement with air (or inert gas) known to be free from flammable gas. The duration of this purge process is normally ascertained by performing a purge test. At the end of the purge cycle the system automatically switches to leakage compensation mode.The Purge Outlet Valve is closed and the airflow is reduced but remains high enough to compensate for the leakage of air from the enclosure whilst maintaining the minimum over pressure state. In the event of pressure failure within the pressurized enclosure the system will raise an alarm in the form of visual indicators and a volt free contact depending on the specification of the system. The default action on loss of pressurization is alarm and automatic disconnect of power (A&T - Alarm and Trip). This can be changed by the customer to Alarm Only (/AO), please refer to section titled Main Components. The MiniPurge® system incorporates a Closed Loop Automatic Pressurization System (CLAPS). This allows the system to detect a rise or fall of the enclosure’s internal pressure and adjust the leakage compensation rate accordingly. Pressure variations are more likely during sudden start up of large rotating electrical machines but can also be caused by changes in running temperature. This system has been specifically designed to maintain a stable internal pressure within the enclosure. Page 5 ML434 | v12l Pressure characteristics during purge and pressurization of a pressurised enclosure using a MiniPurge® system that incorporates a CLAPS system: Power Interlock switch Alarm Only Power Interlock switch Alarm &Trip Active Contacts Intermediate pressure switch Inactive Minimum pressure switch Purging Pressure Intermediate switch contacts open. Intermediate sensor sends falling pressure signal CLAPS Regulator Pressure Minimum pressure switch contacts open. Minimum pressure sensor sends a low pressure signal. Alarm indicator shows red (alarm only) Alarm indicator shows red and power is disconnected (Alarm and Trip) Intermediate Pressure Sensor Pressure Minimum Pressure Sensor Pressure Purge Time Machinery Start Normal Operation Fault Condition - loss of pressure outside of CLAPS regulation Section 5: Main Components Air Supply Filter / Regulator The unit is provided with a 40 m liquid / dust filter element as a precaution. The user of the MiniPurge® system must ensure that air supply is to the quality stated in Air Supply Quality paragraph found in the Installation of the System section. The regulator is factory set to 5 barg (73 psig) and regulates the pressure of an air supply between 5 and 16 barg (73 to 232 psig). A pressure gauge is fitted down stream of the filter; this should indicate no less than 5 barg (73 psig). During the purge cycle a pressure drop will be indicated on the gauge. Logic Air Supply Regulator This device provides the system with a stable air supply pressure to the logic system and allows consistent operation. The pressure level is factory set to 2.3 barg (33 psig) and can be verified by means of the integral pressure gauge. Minimum Pressure Sensor This monitors the pressure inside the pressurized enclosure. When the pressure is below the minimum required for safe operation, the pressure sensor causes the system to reset and the Alarm / Pressurized indicator turns Red . The sensor is factory calibrated and set to operate in falling pressure at or above the minimum specified pressure. Purge Flow Sensor The Purge Flow Sensor monitors flow through the Purge Outlet Valve. At correct purge flow rates, above the minimum specified for purging, the sensor sends a signal that activates the purge timer. This sensor is factory calibrated to operate on falling flow rate at or above the minimum specified purge flow rate. ML434 | v12l Page 6 Intermediate Sensor This sensor monitors the pressure inside the pressurized enclosure. It senses when the pressure is drops and provides early warning before the low pressure sensor trips the system. The setting on this is user selectable. Purge Timer When both the enclosure pressure and the purge flow rate are correct, the Purge Flow Sensor activates the timer to start the timing period. The purge time is set by opening/closing the pinch valve so that the sum of the open valves times equals or exceeds the required purge time. At least one valve must be open, and the screws must be at the appropriate limit of travel. Do not over tighten. The purging indicator will turn yellow during timing. Purge Complete Valve This valve receives a signal from the purge timer that indicates the completion of the purge cycle and verifies that the pressurization signal is still present. If both conditions are satisfied a signal is sent to indicate that the purge is complete. This performs two functions: to turn on the electrical supply to the pressurized enclosure and to reduce the high purge flow rate to leakage compensation mode. It also provides a hold-on signal that maintains the leakage compensation mode with the power switch on, even when the purge timer has reset ready for the next purge cycle. OR Gate This device provides the Purge Complete Valve with the hold-on function referred to previously. When either the timed-out signal or the purge complete signal is present it allows the pilot signal to be sent to the purge complete valve. Alarm Only Circuit (/AO) If the pressure in the pressurized enclosure is too low the system will normally cut off electrical power to it. In certain circumstances, where local codes of practice allow, the system can be altered to provide a holdon circuit that will maintain the electrical power supply to the pressurized enclosure while also providing a pressure failure alarm. The user must respond to the alarm and either restore the pressure to the pressurized enclosure or otherwise make the installation safe; for example, cut off the electrical supply. The decision to use the Alarm Only facility, and the allowable length of time for non-pressurized operation, is the responsibility of the user. Warning: It is potentially dangerous to energise the pressurized enclosure in an non-pressurized condition when it is known that there is potentially explosive gas or dust in the hazardous location. Visual Indicators Visual indicators are fitted to provide status information to the operator. Alarm / Pressurized Indicator Green* Pressurized Red Pressure Alarm (enclosure pressure low) System Purging Indicator Black* Purge flow too low (not in purge mode) Yellow Purging (flow above minimum) * The Green / Black combination indicates normal operation of the pressurized enclosure after the initial purging cycle has been completed. Page 7 ML434 | v12l Power Interlock Switch This flameproof power switch is activated by the signal from the Purge Complete Valve. This activation can be used to turn on the electrical supply to the pressurized enclosure. The cable from the switch is terminated in the /PA terminal box. Alarm / Pressurized Switch This flameproof switch is operated by the pressurized signal. It allows a remote electrical system status indicator to show either pressurized or a pressure failure alarm. The cable from the switch is terminated in the /PA terminal box. System Purging Switch (Optional) This switch is operated by the purge flow signal that allows a remote electrical system status indicator to signal that the system is purging; sometimes referred to as purge in progress. The cable from the switch is terminated in the /PA terminal box. Intermediate Switch This is a flameproof switch which is activated by the signal from the Intermediate Sensor. The cable from the switch is terminated in the /PA terminal box. Purge Valve This changeover valve selects between purge air flow or leakage compensation. It is sized to allow sufficient air into the enclosure during purging based on: the specified air supply pressure range, the minimum specified purging outlet flow rate +10% and the expected leakage rate from the pressurized enclosure. At the end of the purge cycle, the purge valve closes in response to the “Purge Complete” signal; it remains in the closed position until the next purge cycle is initiated. Purge Flow Restrictor This valve restricts the purge flow to the minimum required flow rate. The Purge Flow Restrictor must be readjusted during commissioning. CLAPS Sensor This sensor monitors the pressure within the pressurized enclosure and sends a control signal to the CLAPS Regulator. The normal running pressure must be determined prior to system start-up so that the CLAPS Sensor may be set to the level required to control the CLAPS Regulator. CLAPS Regulator This is the regulator that controls the leakage compensation air flow into the enclosure after the purging is complete. It either increases or decreases the air flow into the enclosure as appropriate to maintain a stable running pressure.The CLAPS Regulator must be set at the time of commissioning. Relief Valve Unit The Relief Valve Unit allows the purge air to exit the enclosure safely via a built-in spark arrestor. This spark arrestor is designed to prevent the emission of arcs, sparks and incandescent particles produced within the pressurized enclosure. Purge air passes through the Relief Valve Unit; the preset pressure differential across the appropriate orifice ensures that the purge flow sensor is activated once the selected purge flow has been attained. During the purge cycle a pneumatic cylinder operates the Purge Outlet Valve that lets the air from inside the enclosure exhaust through the Relief Valve Unit. When the system changes to leakage compensation mode, the Purge Outlet Valve is closed and the enclosure sealed. ML434 | v12l Page 8 The Relief Valve Unit has an in-built relief valve.This is sized to ensure that, if the air supply pressure rises up from the specified maximum, the internal enclosure pressure will not exceed the specified maximum working pressure of the pressurized enclosure. /PA Terminal Box Increased Safety Ex e IIC T5 Gb Ex tb IIIC T100ºC Db IP66 Tamb -20ºC to +55ºC Ex e IIC T4 Gb Tamb -20ºC to +60ºC The Terminal Box is increased safety (Ex e) certified and incorporates the terminal connection points for the alarm and interlock switches. All contacts provided are volt free (dry). Cable entry methods (for example conduit or cable glands) must be certified to IECEx, ATEX or INMETRO standards. The main requirement is that IP66 (or better) ingress protection must be provided by use of seals or washers. Section 6: Installation of the System The MiniPurge® is designed for use under normal industrial conditions of ambient temperature, humidity and vibration. Please consult Expo before installing this equipment in conditions that may cause stresses beyond normal industrial conditions.The MiniPurge® system must be installed by a competent person in accordance with relevant standards, such as IEC / EN 60079-14, and any local codes of practice. The MiniPurge® control unit should be installed either directly on, or close to the pressurized enclosure. It should be installed such that the system indicators and certification labels are in view. All parts of the system carry a common serial number. If installing more than one system, ensure that this commonality is maintained within each system installed. Relief Valve Unit To achieve effective purging, the points where air enters and exits the pressurized enclosure should normally be at opposite ends of the enclosure. The RLV unit must be mounted vertically and there should be a minimum clearance of 300 mm (12") around the spark arrestor (purge outlet). It is important that the interior and exterior of the spark arrestor is kept clean and debris is not allowed to accumulate; this might affect the calibration of the device. In particular the exterior of the spark arrestor should not be painted or blocked in any way. Air Supply Quality The MiniPurge® system should be connected to a protective gas supply, which is suitable for purging and pressurization. The supply pipe connection to the MiniPurge® must be appropriate for the maximum input flow rate for the application. The air supply must be regulated at a pressure less than the maximum stated inlet pressure. The air supply must be: clean, non-flammable and from a non-hazardous location. The air should be of Instrument Air Quality. Although the purge control system will operate with lower air quality, its operational life will be adversely affected. The equipment that is being protected by the MiniPurge® may also suffer because of poor air quality. With reference to BS ISO 8573-1: 2010, Instrument Air is typically specified as: Particle Class 1 Page 9 ML434 | v12l In each cubic metre of compressed air, the particulate count should not exceed 20,000 particles in the 0.1 to 0.5 micron size range, 400 particles in the 0.5 to 1 micron size range and 10 particles in the 1 to 5 micron size range. Humidity or pressure dew point The dew point, at line pressure, shall be at least 10 °C below the minimum local recorded ambient temperature at the plant site. In no case, should the dew point at line pressure exceed +3 °C. Oil Class 2 In each cubic metre of compressed air, not more than 0.1mg of oil is allowed. This is a total level for liquid oil, oil aerosol and oil vapour. When an inert gas is being used to supply the purge system, risk of asphyxiation exists. Refer to Application Suitability section. Before connection of the air supply to the purge system, the supply pipe work should be flushed through with instrument quality air to remove any debris that may remain in the pipes. This must be carried out for at least 10 seconds for every meter of supply pipe. Unless a supply shut-off valve has been fitted to the MiniPurge® system, an external shut-off valve with the same, or larger, thread size as the Control Unit inlet fitting should be fitted by the installer to prevent any restriction of purge flow. The purge air from the MiniPurge® Control Unit should be piped within the pressurized enclosure to ensure purging of potential dead air spots. The purge system is fitted with an internal regulator factory set to 3 bar feeding the logic. Pipe Work If the MiniPurge® is not connected directly to the pressurized enclosure, pipe work and fittings used to connect the Control Unit to the pressurized enclosure should be either metallic or appropriate to the environment into which the system is installed. No valve may be fitted in any signal pipe connecting the Control Unit to the pressurized enclosure. This pipe work must be fitted in accordance with local codes of practice where relevant. Multiple Enclosures This system is suitable for the purge and pressurization of the primary pressurized enclosure and its associated terminal boxes. Provision and Installation of Alarm Devices When the pressure inside the pressurized enclosure is above the minimum, the Minimum Pressure Sensor returns a positive (pressurized) signal causing the alarm indicator on the control unit to change from red to green. When the pressure falls below the minimum permissible the positive (pressurized) signal is removed. This absence of signal indicates a low pressure alarm condition and causes the alarm indicator on the control unit to go from green to red. There are volt free (dry) contacts available within the terminal box for remote usage. The user must make use of this alarm facility in accordance with the local code of practice for Action on Pressure or Flow Failure. Most codes include the following recommendations: • Zone 1 Installations: Alarm and Automatic Trip of Power. • Zone 2 Installations: Alarm Only on pressure or flow failure with power being removed manually. ML434 | v12l Page 10 Power Supplies and their Isolation All power entering the pressurized enclosure should have a means of isolation. This requirement also applies to any external power sources that are connected to the equipment such as volt-free (dry) contacts within the pressurized enclosure. This is commonly achieved using the Power Interlock Switch. Power Interlock Switch This switch is a Double Pole Normally Open, double-break switch: it provides two independent contacts that should be connected in series and used to isolate the power. This can be achieved using switchgear or other suitable switching device. These contacts are terminated and accessible to the user in the Ex e terminal box. It is the responsibility of the user to ensure that the switch is only operated within appropriate technical limits. The switch must be replaced after any short circuit that occurs within the main circuit; the switch is a piece of encapsulated equipment and as such it is not possible to check the state of the contacts. Technical modifications to the switch are not permitted. Prior to commissioning, check that the Ex e terminal box is clean, the connections have been made properly, the cables laid correctly and all screws in the terminals are secure. In all cases the application and isolation of power must be controlled by the MiniPurge® system using the power interlock signal. No switches are permitted between the power switch and the MiniPurge® system other than an authorized manual override circuit. The safe use of this switch is the responsibility of the user, all electrical installations must conform to local codes of practice. Exception Power to apparatus that is already suitable for use in hazardous locations need not be isolated by the MiniPurge® system. Section 7: Commissioning Commissioning the System Note: The steps 11 and 15 to 21 represent detailed commissioning tests The following equipment is needed for this process: • Continuity meter • Gauge manometer (0 to 200 mbarg) • Differential manometer If, after commissioning, the system does not perform as expected, refer to the Fault Finding Section. Follow the steps as outlined: 1. Check all connections and that the Relief Valve Unit is fitted correctly with an unobstructed path to the purge exhaust. 2. Close the Purge Flow Restrictor Valve. 3. Fully open external supply shut-off valve where fitted. 4. Check that the internal logic pressure gauge reads 2.3 barg / 33 psi / 230 kPag. 5. Check that the pressure gauge on main air supply reads 5 barg / 73 psi / 500 kPag. 6. Check that the Pressure Relief Valve is correctly set by disconnecting the minimum pressure sensing pipe at the bulkhead fitting on the input to the MiniPurge®. This will disable all of the pressure sensors. Page 11 ML434 | v12l • Using a 4 mm nylon tube, connect a manometer to the bulkhead fitting from which the minimum pressure sensing pipe was removed. • Open the Purge Flow Restrictor Valve very slowly, until the Pressure Relief Valve opens • Check the opening pressure is within calibration limits. • This test can be carried out several times to ensure repeatability and compliance. Refer to the Maintenance of the System section if the Relief Valve needs recalibrating. 7. Close the Purge Flow Restrictor Valve. 8. Remove the manometer and reconnect the minimum pressure sensing pipe to the bulkhead fitting. 9. Remove red plug from the top of the Minimum Pressure Sensor and connect a gauge manometer. 10.Connect a differential manometer to the test points on the flow sensor. 11.To check sensor calibration • The internal pressure in the pressurized enclosure must be below Relief Valve lift off pressure and above the CLAPS pressure • At this time the pressurized indicator should be green. • gradually open Purge Flow Restrictor Valve until purging indicator turns yellow. Note: For large volumes it may take a long time for the purge flow to start. • very slowly close Purge Flow Restrictor Valve until the purging indicator turns back to black. • Take a reading from pressure gauge. 12.To set the purge flow rate: • Turn on the compressed air to the MiniPurge®. • Gradually open the Purge Flow Restrictor Valve until the black / yellow indicator changes to yellow. • The yellow indicator confirms the correct flow rate. • The differential pressure should be greater than 6.4 mbarg. • The relief valve is supplied with different orifice plates for the specified flow rate. This orifice plate is held in position by two M3 screws and can easily be changed by removing the large cover plate from over the outlet valve assembly and screws. Warning: When opening the Purge Flow Restrictor Valve, ensure the over pressure within the pressurized enclosure does not exceed the pressure relief valve setting. 13.The purge timer will start as soon as the Purging Indicator turns yellow. Check that the time delay between the indicator turning to yellow and returning to black is not less than the minimum time required for complete purging of the pressurized enclosure. Times in excess of minimum are permitted. 14.After the purge has been completed, the Purge Valve will close and the air flow into the pressurized enclosure will be controlled by the CLAPS Regulator. The initial setting may be too high or too low. 15.Gradually turn the CLAPS Regulator anti-clockwise to reduce enclosure pressure. 16.Reduce regulator until intermediate sensor causes contacts to open. 17.Check the manometer on the minimum pressure sensor. 18.Continue to reduce the CLAPS Regulator to test the minimum pressure sensor. 19.To check operation of Minimum Pressure Sensor, check readings on manometer as system will automatically re-purge when it reaches minimum pressure. 20.While the system re-purges, return the CLAPS Regulator to the initial setting. 21.If minimum pressure is below the set point, refer to the Recalibration section 22.If the setting is too high, continual rising and falling of the enclosure pressure will be seen as the CLAPS Regulator automatically shuts off and reinstates the flow. The CLAPS Regulator should be adjusted to reduce the flow into the pressurized enclosure by turning the adjuster screw anti-clockwise. ML434 | v12l Page 12 23.If the initial setting is too low the CLAPS Regulator may not provide enough air flow causing a gradual decline in enclosure pressure. To increase the flow into the pressurized enclosure, adjust the CLAPS Regulator Relief Valve unit by turning the adjuster screw clockwise. 24.To test the CLAPS settings, create a leak in the system by removing a bolt or losening a gland plate in order to create a 15mm hole. Remember to replace bolt or retighten gland plate after testing. 25.The setting of the CLAPS Sensor is factory calibrated to the normal working pressure expected in the pressurized enclosure, typically 10 mbarg. The pressure in the pressurized enclosure should be stabilized as close as possible to this figure. This can be checked by a manometer attached to the minimum pressure sensor. 26.Remove the air supply to the system, remove all test equipment and replace all plugs. Normal Operation For normal operation of the system, after commissioning has been carried out it is possible to turn the air supply valve on or off to start or stop the system. After this, the purge and pressurization sequence is automatic. Section 8: Maintenance of the System General maintenance The maintenance of the system outlined in this manual should be supplemented with any additional requirements set out in appropriate local codes of practice. The following checks should be carried out every 6 – 36 months dependent on environment according to IEC / EN 60079-17 • Tests outlined in the Detailed Commissioning section. • Ensure that the Relief Valve Unit is free from contamination prior to making any adjustment. To do this: • Remove large cover plate using a 8 mm spanner (wrench). • Check that the interior and all components are clean and free from contamination. • Replace large cover plate. • Check the condition of the air supply filter element. Clean or replace as necessary. Additional maintenance checks The following additional checks are recommended at least every 3 years: Check that: • Apparatus is suitable for use in the hazardous location. • There are no unauthorised modifications. • The air supply is uncontaminated. • The interlocks and alarms function correctly. • Approval labels are legible and undamaged. • Adequate spares are carried. • The action on pressure failure is correct. Re-calibration of the Relief Valve Unit Warning Incorrect adjustment of the Relief Valve Unit can lead to significant over pressure and result in damage to the enclosure. If maximum pressure setting is reached, stop adjustment and reduce the pressure. To perform the following adjustments, an 8 mm spanner (wrench) and a 2.5 mm hex key will be required. Page 13 ML434 | v12l Ensure that the Relief Valve Unit is free from contamination prior to making any adjustment. To do this: • Remove large cover plate using a 8 mm spanner (wrench). • Check that the interior and all components are clean and free from contamination. • Replace large cover plate To adjust the lift off pressure of the Relief Valve: • Attach test equipment as described in the Commissioning Section. • Remove small cover plate. • Whilst holding the central adjustment screw in position using the hex key, loosen the retaining nut. • Adjust the hex key clockwise to increase, or anti-clockwise to reduce the lift off pressure. • Before testing, retighten the locking nut whilst holding the adjustment screw in place. • Carry out the commissioning tests to check the correct setting of the relief valve after adjustment. • The adjustment is sensitive and it is recommended that a 1/4 turn (maximum) adjustments are applied between tests. A llen Sc rew & Lock N UT Rem ov ing t he sm a ll cov er pl a te t o set t he RL V o penin g pressur e Orific e P la te Re-calibration of the Pressure Sensors The brass nozzle on the sensor is sealed into position using Loctite thread sealant. If the thread has seized up, remove to a safe area and heat slightly to soften prior to making any adjustment. This prevents potential damage to the brass of the nozzle. • Disconnect pipe work from the sensor, including pipe located below the sensor. • Remove sensor by unscrewing anti-clockwise. • The nozzle is located under the sensor. • The adjustment is sensitive, turn the nozzle in 1/8 of a turn steps. • Turn clockwise to reduce the pressure setting and anti-clockwise to increase. • Replace sensor, screwing clockwise. • Reconnect all pipe work. Section 9: Fault Finding General Information If you are having problems that cannot be corrected using one of the methods described, please call Expo or your supplier for further assistance. If the system is less than 12 months old, parts under warranty should be returned to Expo for investigation. A full report of the fault and the system serial number should accompany the parts. It is common for problems with the MiniPurge® system to be caused by contamination of the air supply with oil, water or dirt. To prevent these problems, the air supply must contain a dust filter and a water filter. This ML434 | v12l Page 14 will ensure that the air is instrument quality and protect both the purge system and the equipment being purged. This filtration system is not provided by Expo and must be sourced separately. Contamination can enter the system from a number of sources. To prevent this, it is essential that the procedures described in the Installation section are carried out prior to first use of the system. These procedures should also be carried out following any disconnection and re-connection of the pipe work. Failure to perform these procedures may cause damage to the system that will not be covered by the warranty. The system has been designed for ease of fault finding and many of the components fitted are plug-in or chassis mounted. Check components by substitution only after establishing that such action is necessary. Before carrying out the fault finding procedures, ensure that: • Both the main air pressure to the system and for Motor Purge Systems, the regulated pressure to the logic manifold are as specified on the settings sheet. • Air pressure does not drop below the minimum supply pressure during purging; the majority of faults reported are due to insufficient air supply during the purge cycle. System purges correctly but trips and auto re-purges at the end of the purge time. This is a result of the pressure within the pressurized enclosure being below the minimum pressure sensor setting. The pressure can be checked using a manometer. The most common causes of this problem are outlined below: Fault Location Pressurised Enclosure CLAPS Regulator MiniPurge® Control Unit Cause There is debris on the face of the Relief Valve disk held in place by the magnet. Enclosure leaking excessively. Pressure sensing tube damaged. The CLAPS Regulator setting is too low. the Minimum Pressure Sensor setting has drifted above the CLAPS setting Solution • Remove debris and ensure RLV disk is clean. • Ensure all doors and covers are closed and that all conduit and cable glands are properly sealed. • Seal any other leaks. • Replace tubing. • Increase the setting of the CLAPS regulator to raise the pressure in the pressurised enclosure after purging. • To do this, turn clockwise. The Minimum Pressure Sensor needs re-calibrating. • Refer to Re-calibration of Pressure Sensors in the Maintenance section Relief Valve opens (continuously or intermittently) Fault Location Cause Solution Pressurised Enclosure Enclosure pressure is too high due to CLAPS Regulator being open to far. Adjust the CLAPS Regulator. Relief Valve Unit Debris on the Relief Valve disk allowing air to leak from the valve. Remove Relief Valve cover and clean the valve disk. Page 15 ML434 | v12l System enters purging but purge indication does not occur. Fault Location Air Supply Cause Insufficient flow rate due to inadequate air supply pressure. Often due to pressure drop in the supply pipe. Pressurized Enclosure Excessive leakage from the pressurized enclosure. Pipe Work Tubing from Relief Valve flow sensing point not air tight. Relief Valve Unit Relief Valve opening during purge MiniPurge Control Unit Flow sensor setting incorrect Solution Static pressure of 5 barg must be maintained during purge • Check air supply pressure at the inlet to the control unit. • Ensure that the supply pipe bore is suitable for the flow rate • Check around the enclosure while purging is taking place. • Total leakage at purge outlet valve should not exceed 10% of purge flow sensor setting. • Check for leakage down cables and conduit. • Ensure fitting nuts are tightened. • Check for tube damage. • Repair as necessary. • Check enclosure pressure on start up is less than Relief Valve lift off pressure. • Check the pressure is correct on the flow sensor. Section 10: Recommended Spares List Part Number Description KFL-AO1N-001 Filter Kit for S0015/275 filter / regulator S0030/606 Purge flow sensor factory set to 6.4 mbarg S0030/016 Minimum Pressure sensor, must be factory set to the value as stated on the Customer Test and Inspection Sheet S0030/478 Intermediate pressure sensor S0030/588 CLAPS Sensor must be factory set to the value as stated on the Customer Test and Inspection Sheet S0015/018 Pressure gauge (Air Supply Pressure), 0 - 10 barg S0015/135 Miniature gauge (Logic Pressure), 0-4 barg Note. The system’s Pneumatic Timer may be replaced with the Expo Electronic Timer. Please contact Expo Technologies’ Sales Team for further details. Section 11: Glossary Acronym Definition A&T Alarm and Trip AO Alarm Only CLAPS Closed Loop Automatic Pressurization System CU Control Unit ML434 | v12l Page 16 Acronym Definition ET Electronic Timer FCV Flow Control Valve IS Intrinsically Safe LC Leakage Compensation PA Power and Alarm RLV Relief Valve Unit Section 12: Drawings and Diagrams Title Drawing Number Number of Sheets D758 Control Unit - Pneumatic Timer D758MOTORSYS-P 2 Typical D758 Hook Up D758-HU 1 D758-3 P and I Diagram D758-PI 1 D758 Circuit Diagram - Pneumatic Timer AGM-PA00-029 1 D758 Ex e Terminal Box Layout AGE-WC00154 1 Manual Override Switch Hook Up AGE-WC00-117 1 Size 5 MOTORPURGE RLV XBR-RTD0-009 1 MiniPurge® XBR-7TD0-040 1 TP-518-058-wd 1 X LC Sequence Diagram System Status Indication Section 13: Certifications Download the certificates at www.expoworldwide.com/downloads. Component Certificate Number Purge System ATEX Certificate SIRA 01ATEX1295X IECEx Certificate IECEx SIR07.0027X INMETRO/TÜV Certificate TÜV 12.1462X ATEX Certificate ITS 10ATEX37092X IECEx Certificate IECEx ITS 10.0003X INMETRO/TÜV Certificate TÜV 12.1463 Ex d limit switch IECEx EPS 14.0092X Ex d limit switch EPS 14 ATEX 1766 X MIU/e Ex e Terminal Box Electronic Switches Page 17 ML434 | v12l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age 18 ,1&/8',1**$6.(7 ML434 | v12l Page 19 ML434 | v12l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| v12l Page 20 DR'WN CHK'D APP'D D R A W IN G S T A T U S : APPROVED: DAT E: MO D. No: IS S U E : 3rd A N G L E P R O JE C T IO N D I M E N S I O N S IN m m F IN IS H M A T E R IA L PURGE AIR DISTRIBUTION AS REQUIRED M OTOR MINIPURGE JOB No: T IT L E C U S T O ME R : S U R R E Y K T 7 0R H U N IT E D K IN G D O M S H E ET N o. OF See drawing A G M - P A 00 - 02 1 D R A W IN G N o . SC ALE SYSTEM PURGING contacts ALARM / PRESSURIZED contacts INTERMEDIATE PRESSURE contacts POWER INTERLOCK contacts Measuring point for minimum pressure Air inlet Measuring point for flow of purge air Ensure outlet is not obstructed Expo Technologies Limited B O O S T A IR CONTROL UNIT Air outlet R E LI E F V A LV E U N I T The contents of this drawing / docum ent are Copyright ¤ Expo Technologies Lim ited. They are to be treated as confidential and are returnable upon request. They are not to be copied or com m unicated in part or in whole without written consent from Expo Technologies Lim ited, neither are they to be used in any way against our interests. PURGE OUTLET VALVE open signal UNS P E CIFIE D T O LERANCES N O D E C P LA C E ± 0 . 5 1 D E C P LA C E ± 0 . 2 2 D E C P L A C E ± 0 .1 F LA T N E S S T O B E LE S S T H A N 0. 4m m O V E R A N Y 10 0m m LE N G T H M O T O R CO O LE R D O N O T SC ALE Page 21 ML434 | v12l DR'WN CHK'D APP'D D I M E N S I O N S IN m m IS S U E : D R A W IN G S T A T U S : APPROVED: DAT E: MO D. No: UNS P E CIFIE D T O LERANCES M I N IP U R G E C O N TR O L LO G I C XI XC M A N U ALLY SE T PU RG E B OO S T FLO W C O N TR O L VA LVE H F IN IS H M A T E R IA L PI B O O S T A I R C O N T R O L U N I T ( O P T I O N A L) A U TO M A TI C LE A KA G E C O M P E N S A T IO N V A LV E H M AN UA LLY S E T PU RG E FLO W C O N T RO L VA LVE H PI PUR GIN G / PU RG E C O M PLE T E LO W P RES SU R E P A L A LA R M M I N I P U R G E S Y S T E M E N C LO S U R E 1/ 2" N PT C O N N E C T T O E IT H E R A OR B A B * 1 " [ 2 5 m m ] I.D . M IN I M U M * 1 / 4 " [ 6 m m ] I.D . JOB No: T IT L E 1/8" N PT 1/8" N PT R E LI E F V A LV E AS SE M BLY 1 /8 " N PT C U S T O ME R : S U R R E Y K T 7 0R H U N IT E D K IN G D O M O PTI O N A L S H E ET N o. D R A W IN G N o . SC ALE E L E C T R I C A L S I G N A L V I A E E x e J U N C T IO N B O X R E C O M M E N D E D M IN IM U M S IZ E FO R P U R G E A I R D I S T R IB U T IO N PIPEW OR K M O T O R E N C LO S U R E Expo Technologies Limited 1" N P T O P E N P U R G E O U T L E T V A L V E C O N T R O L S IG N A L 1/8" NP T 1 / 4 " [ 6 m m ] I.D . 1 /8 " N PT TE ST PO I N T N O RM A LLY PLU GG E D D . P . L O F R O M R E LI E F V A L V E D . P . H I F R O M R E LI E F V A L V E 1/8" NP T 1/8" NP T M O T O R IN T E R L O C K I N TE R M E DI ATE PRE S SUR E A L A R M / P R E S S U R IZ E D 1 / 4 " [ 6 m m ] I.D . OF The contents of this drawing / docum ent are Copyright ¤ Expo Technologies Lim ited. They are to be treated as confidential and are returnable upon request. They are not to be copied or com m unicated in part or in whole without written consent from Expo Technologies Lim ited, neither are they to be used in any way against our interests. S Y S T E M P U R G IN G ( O P T I O N A L ) N O D E C P LA C E ± 0 . 5 1 D E C P LA C E ± 0 . 2 2 D E C P L A C E ± 0 .1 F LA T N E S S T O B E LE S S T H A N 0. 4m m O V E R A N Y 10 0m m LE N G T H 1/ 2" N PT 1" N P T D O N O T SC ALE S U P P LY 5 - 1 6 b a r g ( 7 3 - 2 3 0 p si ) I N S TRUM E N T AI R /I N E R T G A S 1 " [ 2 5 m m ] I. D. M IN I M U M 3rd A N G L E P R O JE C T IO N ML434 | v12l Page 22 DR'WN CHK'D APP'D 22 DRAWING STATUS: APPROVED: DATE: MOD. No: ISSUE: 23 3rd ANGLE PROJECTION DIMENSIONS IN mm 16 18 2 15 19 DO NOT SCALE 28 1 21 29 FINISH MATERIAL 12 5 6 2 14 7 13 17 4 26 24 JOB No: CUSTOMER: Expo Technologies Limited 8 SURREY KT7 0RH UNITED KINGDOM 3 1 25 9 SHEET No. DRAWING No. SCALE 27 OF The contents of this drawing / document are Copyright ã Expo Technologies Limited. They are to be treated as confidential and are returnable upon request. They are not to be copied or communicated in part or in whole without written consent from Expo Technologies Limited, neither are they to be used in any way against our interests. TITLE UNSPECIFIED NO DEC PLACE ±0.5 TOLERANCES 1 DEC PLACE ±0.2 2 DEC PLACE ±0.1 FLATNESS TO BE LESS THAN 0.4mm OVER ANY 100mm LENGTH DR'WN CHK'D APP'D IS S U E : D R A W IN G S T A T U S : APPROVED: DAT E: MO D. No: 10 2 1 01 A LA R M / P RE SS U RI S E D C O N T A CT S 1 02 10 1 I N T ER M ED I A T E PR E SS U R E CO N T A C T S S EE CI R CU I T D I A G R A M 105 10 3 1 06 PO W E R I N T E RL OC K CO N T A C T S 107 1 08 1 04 1 05 10 6 POW ER I N T ER LO C K CO N TA CTS S EE CI R CU I T D I A G R A M 104 I N T E RM E DI A T E PR ES S U RE CO N TA CTS 1 03 B LA C K B LA C K AL A RM / PR ES S U R I S E D CO N T A C T S U N S P E C I F IE D T O LERANCES N O D E C P LA C E ± 0 . 5 1 D E C P LA C E ± 0 . 2 2 D E C P L A C E ± 0 .1 F LA T N E S S T O B E LE S S T H A N 0. 4m m O V E R A N Y 10 0m m LE N G T H G REY G REY B LA C K B LA C K B RO W N B RO W N G REY G REY G REY 10 9 F IN IS H JOB No: T IT L E C U S T O ME R : Expo Technologies Limited S U R R E Y K T 7 0R H U N IT E D K IN G D O M M A XI M UM PER T ER MI N A L A T 5 5 ° C : 2 5 0 V 4 A (A C -1 5 ) M A T E R IA L D O UB LE LI N ES S H OW T HE PO S I T I O N O F T E RM I N A L E N D PLA T ES 4 1 13 3 11 2 A L L T E R M I N A L S M U S T B E E x e CE R T I F IE D K E M A 9 8 A T E X 1 6 8 3 U , I E C E x U L D 0 5 .0 0 0 8 U . 1 11 T ER M I N A L L A Y OU T F OR SYSTEM FITTED WITH "SYSTEM PURGING" CONTACTS TERMINAL LAYOUT 2 110 S Y S T EM PU RG I N G C O N T A CT S 11 0 1 N OT ES 10 8 1 09 S H E ET N o. D R A W IN G N o . SC ALE OF The contents of this drawing / docum ent are Copyright ¤ Expo Technologies Lim ited. They are to be treated as confidential and are returnable upon request. They are not to be copied or com m unicated in part or in whole without written consent from Expo Technologies Lim ited, neither are they to be used in any way against our interests. E X T R A T E R M IN A L S M A Y B E F I T T E D . T H E N U M B E R O F T E R M I N A L S M U S T N O T E X CE E D T H E M A X I M U M S P EC I F I ED I N T H E T ER M I N A L B O X C E R T I F I CA T E - C O N S U L T E X P O T E CH N O L O G I ES . 1 07 G REY B RO W N B RO W N BLUE BLUE B LA C K B LA C K B RO W N B RO W N D I M E N S I O N S IN m m B RO W N D O N O T SC ALE B LA C K 3rd A N G L E P R O JE C T IO N G REY Page 23 ML434 | v12l ML434 | v12l Page 24 DR'WN CHK'D APP'D D R A W IN G S T A T U S : APPROVED: DAT E: MO D. No: IS S U E : 3rd A N G L E P R O JE C T IO N D I M E N S I O N S IN m m D O N O T SC ALE F IN IS H M A T E R IA L JOB No: T IT L E C U S T O ME R : Expo Technologies Limited * TERMINAL NUMBER ACCORDING TO MOTOR SYSTEM CABLE GLANDS ARE NOT SUPPLIED. GLAND PLATE IN PURGE SYSTEM IS UNDRILLED. S U R R E Y K T 7 0R H U N IT E D K IN G D O M S H E ET N o. D R A W IN G N o . SC ALE OF The contents of this drawing / docum ent are Copyright ¤ Expo Technologies Lim ited. They are to be treated as confidential and are returnable upon request. They are not to be copied or com m unicated in part or in whole without written consent from Expo Technologies Lim ited, neither are they to be used in any way against our interests. MANUAL OVERRIDE SWITCH SUPPLIED LOOSE. N O D E C P LA C E ± 0 . 5 1 D E C P LA C E ± 0 . 2 2 D E C P L A C E ± 0 .1 F LA T N E S S T O B E LE S S T H A N 0. 4m m O V E R A N Y 10 0m m LE N G T H UNS P E CIFIE D T O LERANCES 280 MOD NUMBER DRAWN 4666 4793 REV. 01 02 03 ML434 | v12l 16/10/2009 17/04/2009 20/02/2009 APPROVED DATE JPdB JPdB JPdB APPROVED 274 202 330 306 CRS 240 CRS EXCHANGEABLE ORIFICE PLATE 10-OFF FIXING POINTS TO SUIT M8 DR'WN NAH CHK'D NRB APP'D JPdB Controlled FINISH 88 NOTES PURGE AIR OUTLET 43 DIFFERENTIAL FLOW SIGNAL LOW PRESSURE OPEN PURGE OUTLET VALVE SIGNAL DIFFERENTIAL FLOW SIGNAL HIGH PRESSURE MOTOR ENCLOSURE TEST POINT (PLUGGED) NROB STAINLESS STEEL 316L 1.6mm THK JOB No: TITLE CUSTOMER: SIZE 5 MOTORPURGE RLV SURREY KT7 0RH MOUNTING DETAILS Expo Technologies LimitedUNITED KINGDOM 5. ON INSTALLATION ENSURE THAT FIXING BOLTS ARE EVENLY TIGHTENED TO A TORQUE OF 5 Nm (44 lbf/in) 4. PART CODE: ARV-1048-107 3. WEIGHT IS APPROXIMATELY 7 kg 2. THE RELIEF VALVE MUST BE MOUNTED IN THE ORIENTATION SHOWN. 9.4 = 240 = 10.8 = 274 = 12.0 = 306 = 1:5 03 REV: SHEET No. 1 OF 1 XBR-RTD0-009 DRAWING No. SCALE 10 FIXING POINTS TO SUIT M8 LARGE COVER PLATE FOR CHANGING THE ORIFICE PLATE INSPECTION COVER The contents of this drawing / document are Copyright © Expo Technologies Limited. They are to be treated as confidential and are returnable upon request. They are not to be copied or communicated in part or in whole without written consent from Expo Technologies Limited, neither are they to be used in any way against our interests. 1. RELIEF VALVE SUPPLIED WITH USER SELECTABLE ORIFICE PLATES TO SET THE FLOW RATE. 11/02/2009 MATERIAL DRAWING STATUS: DRAWN DATE: MOTOR ENCLOSURE OVER PRESSURE RELIEF VALVE ASSEMBLY PURGE AIR OUTLET SPARK ARRESTOR MUST NOT BE OBSTRUCTED 120 CRS DO NOT SCALE 30 256 CRS 136 60 NO DEC PLACE ±0.5 1 DEC PLACE ±0.2 2 DEC PLACE ±0.1 FLATNESS TO BE LESS THAN 0.4mm OVER ANY 100mm LENGTH 10.1 = 256 = UNSPECIFIED TOLERANCES 8.9 = 225 = DIMENSIONS IN mm 4.7 = 120 = 3rd ANGLE PROJECTION 95 Page 25 ML434 | v12l Page 26 MOD NUMBER DRAWN 5434 REV. 01 02 No No No 20/12/2011 23/06/2010 APPROVED DATE Purge timer resets 3rd ANGLE PROJECTION JPdB JPdB APPROVED "Purging" Indicator Purge flow falls below minimum Purging Indicator turns Black as DR'WN BRD CHK'D PSC APP'D JPdB Controlled FINISH "Pressurized" signal absent i.e. "Alarm" ON Red = Pressure Low PRESSURIZED INDICATOR SURREY KT7 0RH CUSTOMER: 1:1 02 REV: SHEET No. 1 OF 1 XBR-7TD0-040 DRAWING No. SCALE THE RELEVANT EXPO CERTIFICATION DRAWING IS EP99-2-3 Optional operation (User decision) Automatic operation by the system Manual operation by the user Key to functions MINIPURGE X LC SEQUENCE DIAGRAM JOB No: TITLE "Purge Complete" signal to electrical Power Switch Black = Purge flow too low Yellow = Purge flow OK Power turned off automatically without delay Minimum Pressure sensor turns off Expo Technologies Limited UNITED KINGDOM Alarm and delayed trip "Pressurized" signal to remote alarm switch include:- Alarm and/or Trip Green = Pressure OK depends upon the user. Actions Action taken on pressure failure Enclosure door opened, or excessive leakage Enclosure pressure falls below the minimum Pressurizing air or inert gas turned off The contents of this drawing / document are Copyright © Expo Technologies Limited. They are to be treated as confidential and are returnable upon request. They are not to be copied or communicated in part or in whole without written consent from Expo Technologies Limited, neither are they to be used in any way against our interests. PRESSURIZED INDICATOR "Pressurized" signal absent i.e. "Alarm" ON 23/06/2010 MATERIAL DRAWING STATUS: DRAWN DATE: Power on - Normal operation Leakage Compensation starts Purge flow ceases; Relief Valve closes Purge valve closes; Power Sw. signal ON Purge timer times out Yes Outlet flow still above the minimum? Purge timer starts automatically Purge Flow Sensor turns on Yes Purge Outlet flow above the minimum? Relief Valve opens Purge flow starts Minimum Pressure sensor turns on Yes Is the PE pressure above the minimum? Air enters the PE Turn Pressurizing air or inert gas on Red = Pressure Low PRESSURIZED INDICATOR UNSPECIFIED TOLERANCES NO DEC PLACE ±0.5 1 DEC PLACE ±0.2 2 DEC PLACE ±0.1 FLATNESS TO BE LESS THAN 0.4mm OVER ANY 100mm LENGTH Pressurized Enclosure door closed DO NOT SCALE DIMENSIONS IN mm 3rd ANGLE PROJECTION DR'WN BRD CHK'D PSC JPdB Controlled APP'D DRAWING STATUS: FINISH 19/03/2009 MATERIAL MOTOR LOW PRESSURE SHUTDOWN INTERMEDIATE OR PRE-ALARM PURGE COMPLETE NORMAL OPERATION DURING PURGE SYSTEM STATUS DRAWN DATE: DO NOT SCALE RED GREEN GREEN GREEN BLACK BLACK BLACK YELLOW INDICATORS 101 102 103 101 102 103 101 102 103 104 105 106 104 105 106 104 105 106 107 108 109 110 107 108 109 110 107 108 109 110 JOB No: ML434 | v12l CUSTOMER: SYSTEM STATUS INDICATION SURREY KT7 0RH 107 108 109 110 Expo Technologies LimitedUNITED KINGDOM 101 102 103 104 105 106 SYSTEM PURIGING OPTION The contents of this drawing / document are Copyright © Expo Technologies Limited. They are to be treated as confidential and are returnable upon request. They are not to be copied or communicated in part or in whole without written consent from Expo Technologies Limited, neither are they to be used in any way against our interests. TITLE NO DEC PLACE ±0.5 1 DEC PLACE ±0.2 2 DEC PLACE ±0.1 FLATNESS TO BE LESS THAN 0.4mm OVER ANY 100mm LENGTH BLACK BLACK BLACK BLACK UNSPECIFIED TOLERANCES GREY GREY GREY GREY DIMENSIONS IN mm BROWN BROWN BROWN BROWN GREY GREY GREY GREY BROWN BROWN BLACK BLACK BLACK BLACK BLACK BLACK BROWN BROWN GREY GREY GREY GREY BROWN BROWN BLUE BLUE BLUE BLUE 111 112 113 111 112 113 111 112 113 BLACK 1:1 05 REV: SHEET No. 2 OF 2 TP-518-058-WD DRAWING No. SCALE 111 112 113 BLACK BLACK BLACK GREY GREY GREY GREY BROWN BROWN BLACK BLACK BROWN BROWN BROWN BROWN Page 27 ML434 | v12l Page 28 This equipment and any acceptable variation thereto is specified in the schedule to this certificate and the documents therein referred to. Sira Certification Service, notified body number 0518 in accordance with Article 9 of Directive 94/9/EC of 23 March 1994, certifies that this equipment has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of equipment intended for use in potentially explosive atmospheres given in Annex II to the Directive. 7 8 EN 60079-2:2014 70012182 Form 9400 Issue 1 This certificate and its schedules may only be reproduced in its entirety and without change. Project Number II 2(2) GD Ex [pxb] ia IIC T6 Gb Ex [pxb] ia IIIC T95°C Db (Ta –20°C to +55°C) II 2(2) GD Ex [pxb] IIC T6 Gb Ex [pxb] IIIC T85°C Db (Ta –20°C to +55°C) Standard/ET versions: Page 1 of 7 II 2(2) GD Ex [pxb] d e m ia IIC T3 Gb Ex [pxb] d e m ia IIC T4 Gb Ex [pxb] ia IIIC T200°C Db Ex [pxb] ia IIIC T135°C Db (Ta –60°C to +55°C) Tel: Fax: Email: Web: +44 (0) 1244 670 900 +44 (0) 1244 539 301 ukinfo@csagroup.org www.csagroupuk.org Unit 6, Hawarden Industrial Park, Hawarden, CH5 3US, United Kingdom Sira Certification Service C Ellaby Deputy Certification Manager II 2(2) GD Ex [pxb] d e m ia IIC T3 Gb Ex [pxb] d e m ia IIC T4 Gb Ex [pxb] ia IIIC T200°C Db Ex [pxb] ia IIIC T135°C Db (Ta –60°C to +55°C) II 2(3) GD Ex [pzc] IIC T6 Gb Ex [pzc] IIIC T85°C Db (Ta –20°C to +55°C) Low temperature/ET versions The marking of the equipment shall include the following: 11 II 2(2) GD Ex [pyb] IIC T6 Gb Ex [pyb] IIIC T85°C Db Ta –20°C to +55°C) Low temperature versions: This EC type-examination certificate relates only to the design and construction of the specified equipment. If applicable, further requirements of this Directive apply to the manufacture and supply of this equipment. 11 Standard versions: If the sign ‘X’ is placed after the certificate number, it indicates that the equipment is subject to special conditions for safe use specified in the schedule to this certificate. The above list of documents may detail standards that do not appear on the UKAS Scope of Accreditation, but have been added through Sira’s flexible scope of accreditation, which is available on request. EN 60079-0:2012 Compliance with the Essential Health and Safety Requirements, with the exception of those listed in the schedule to this certificate, has been assured by compliance with the following documents: 10 9 The examination and test results are recorded in the confidential reports listed in Section 14.2. Equipment intended for use in Potentially Explosive Atmospheres Directive 94/9/EC Certificate Number: Sira 01ATEX1295X Issue: 9 Equipment: Purge Controllers: Sub-MiniPurge, MiniPurge, Super-MiniPurge, Super-MiniPurge 1800/3500/7000/7000X Applicant: EXPO Technologies Limited Address: Unit 2, The Summit, Hanworth Road, Sunbury on Thames, Surrey TW16 5DB UK 2 3 4 5 6 EC TYPE-EXAMINATION CERTIFICATE 1 Sira 01ATEX1295X Issue 9 Metal foam Tortuous path with at least 4 x 90°or 2 x 180° bends Multi-layer stainless steel mesh Knitted mesh Threaded Orifices e.g. ¼″ NPT or 2″ BSP with a built in spark arrester. These are selected to maintain a desired back pressure within the Ex p protected apparatus when used with the Continuous Flow options. The designation of each outlet orifice indicates the nominal inlet diameter. The designations are as follows: SA3, SA6, SA9, SA12, SA19, SA25, SA32, SA38 and SA50. Plain holes in the Relief Valve disk, sized according to the flow rate required. Replaceable orifice type SAU**. • • Form 9400 Issue1 Page 2 of 7 Tel: Fax: Email: Web: +44 (0) 1244 670 900 +44 (0) 1244 539 301 ukinfo@csagroup.org www.csagroupuk.org Unit 6, Hawarden Industrial Park, Hawarden, CH5 3US, United Kingdom Sira Certification Service Pneumatically Operated Outlet Valve - The pneumatically operated outlet valve is used to positively open or close the outlet of the purged enclosure by means of a spring return pneumatic cylinder. Systems fitted with the Pneumatically Operated Outlet Valve will carry the option OV. High Pressure Sensor for LC Systems (HP code) - If the pressure in the pressurized enclosure rises above the setting of the High Pressure sensor, the purge gas flow is isolated from the pressurised enclosure. The valve isolates both the leakage compensation and the purge streams. On detecting the overpressure, an optional facility is available for the generation of an alarm or indicator. On systems with a High Pressure sensor, the relief valve may be omitted. High Pressure Sensor for CF Systems (HP code) - If the pressure in the pressurized enclosure rises above the setting of the High Pressure sensor, the controller resets cutting the power to the enclosure. On detecting the overpressure an optional facility is available for the generation of an alarm or indicator. On systems with a High Pressure sensor, the relief valve may be omitted. • • • Outlet Orifice - Three types of orifice are used: • • The outlet of each relief valve is fitted with a spark arrestor, of which there are four optional types: RLV3, RLV6, RLV9, RLV12, RLV19, RLV25, RLV26, RLV52, RLV36, RLV75, RLV104, RLV125, RLV150 and RLV200. Relief Valve - The MiniPurge controller is supplied with an optional overpressure relief valve, which is to be fitted to the Ex p protected apparatus to prevent an internal overpressure above the maximum overpressure rating of the apparatus. There are 14 models of relief valve; the designation of each relief valve refers to its nominal bore in mm, as follows: The MiniPurge option pD is for use in combustible dust The MiniPurge control unit may be supplied within a heated enclosure to permit the use of the system within an ambient temperature down to –50oC. LC-Leakage compensation only after initial high purge CF-Continuous flow (same flow rate during and after purging) CF2-Two flow CF system with initial high purge rate only at one orifice CFHP-Continuous (lower) flow after initial high purge The Purge Controllers are pneumatically operated devices, which are intended to provide a given flow rate of purging gas for a predetermined time to unspecified Ex p protected electrical equipment. The MiniPurge Control Units provide one of the following four methods of purge operation. DESCRIPTION OF EQUIPMENT This certificate and its schedules may only be reproduced in its entirety and without change. 13 EC TYPE-EXAMINATION CERTIFICATE SCHEDULE Page 29 ML434 | v12l Sira 01ATEX1295X Issue 9 Form 9400 Issue1 This certificate and its schedules may only be reproduced in its entirety and without change. Page 3 of 7 Tel: Fax: Email: Web: +44 (0) 1244 670 900 +44 (0) 1244 539 301 ukinfo@csagroup.org www.csagroupuk.org Unit 6, Hawarden Industrial Park, Hawarden, CH5 3US, United Kingdom Sira Certification Service a Size or Capacity 1 Sub-MiniPurge Model Number: 2 MiniPurge 3 Super-MiniPurge 1 X LC cs DS SS AA MO FM OA TW 4 Super-MiniPurge 1800 Key: 5 Super-MiniPurge 3500 a b cc mm Example option codes 6 Super-MiniPurge 7000 7 Super-MiniPurge xxxx b Pressurization Type X X Pressurization Y Y Pressurization Z Z Pressurization cc Action after initial purging LC Leakage Compensation only after initial High Purge CF Continuous Flow (same flow rate during and after purging) CF2 Two Flow CF system with initial High Purge rate but only one orifice CFHP Continuous (lower) Flow after initial High Purge DP Dust Protection (pressurization only) mm Material of the Control Unit Enclosure al Aluminium alloy cs Mild steel, painted ss Stainless steel bp Back Plate only co Chassis only pm Panel mounting nm Non-Metallic Option codes (Added only if used) AA Active Alarm output fitted. AC Alarm cancellation circuit. AO "Alarm Only" Action on Pressure or Flow Failure. AS Alarm "Action on Pressure or Flow failure", Selector valve. CS Containment System Monitor. DS Door switch Power Interlock fitted. DT Delayed Trip after Pressure or Flow failure. DXXX Special design for specific flow rates ET Electronic Timer FM Flow Meter(s) fitted. HP System LC or CF with High Pressure Sensor IS Internal Switches suitable for Ex i circuits. MO Manual Override fitted. MT Mechanical Timer. OA On/Off switch controlling Protective gas and logic supply. OB On/Off switch controlling logic supply only. OC On/Off switch controlling Protective gas supply only. OS Outlet (Orifice) Selector valve. OV Outlet valve, pneumatically operated. PA "Ex" switch(es) built-in, with/without "Ex" junction box. PC PE Pressure Control Leakage Compensation Valve (CLAPS System.) PO Pneumatic Output signals for Power and Alarm control. SP Secondary Pressurization supply options. SS Separate Supply for Protective gas and Logic air. TW Twin (or more) outputs for two or more separate pressurized enclosures purged in paralle LS Local Sensing for internal overpressure monitoring EC TYPE-EXAMINATION CERTIFICATE SCHEDULE Model Number Designation for ATEX approved MiniPurge systems Old Name: Expo Telektron Safety System Limited New name: Expo Technologies Limited A change of the Applicant’s name on the certificate and the substitution of the new name for the old name on the approved label affixed to the purge controllers: Any suitably ATEX, Category 2 approved cable gland may be used, if it can be used with the ambient temperature range. An Ex e terminal box is provided within the main enclosure for connection of the heater leads. This polyester box is manufactured by Bartec and coded Ex e II T6 under BAS 98ATEX3008X. Other alternative ATEX terminal boxes may be used as a replacement if they are suitably certified, carry the same or greater ambient temperature range, occupy the same or smaller physical space, have the same certification code and have the same Temperature Class. RTDs are fitted to the air inlet pipe-work and inside the purge controller enclosure. The enclosure is made from 1.5mm or 2.5 mm thick stainless or mild steel painted and the lid is made from 1.5 mm thick stainless steel, lined with 38 mm thick insulation, or other materials with equivalent insulating properties. The purge inlet, purge outlet and pressure sensing lines are similarly insulated. The door may optionally be hinged with quick release catches, these will be fitted with a padlock. An enclosure breather tube is fitted to help prevent condensation. A plastic clear viewing window may optionally be fitted to the door. The heater (500 W maximum) is manufactured by Intertec-Hess GmbH and coded Ex d m IIC T3 (max) under PTB 02ATEX1041X. If the outer enclosure is reduced in size the power of the heater may be reduced in proportion to the reduction in surface area. Other alternative heaters may be used as a replacement if they are suitably certified, carry the same or greater ambient temperature range, occupy the same or smaller physical space, have the same certification code and have the same or more restrictive Temperature Class. Form 9400 Issue1 II 2(2) G D Page 4 of 7 The ATEX coding is modified to: [Ex pD] II T200°C 21 (Ta = -20°C to +55°C) [Ex pD] II T85°C 21 (Ta = -20°C to +55°C) - Tel: Fax: Email: Web: +44 (0) 1244 670 900 +44 (0) 1244 539 301 ukinfo@csagroup.org www.csagroupuk.org Unit 6, Hawarden Industrial Park, Hawarden, CH5 3US, United Kingdom Sira Certification Service (used with the low temperature versions) (used with the standard temperature versions) To permit the pressurisation of enclosures for the exclusion of combustible dusts in accordance with IEC61241-4:2001 and modification of the marking to include one of the following: This certificate and its schedules may only be reproduced in its entirety and without change. i. Sira 01ATEX1295X Issue 9 The purge controller to be fitted inside an additional, heated, stainless steel enclosure that allows it to be used down to -50oC. Variation 2 This variation introduced the following change: ii. i. Variation 1 This variation introduced the following changes: EC TYPE-EXAMINATION CERTIFICATE SCHEDULE ML434 | v12l Page 30 To permit the inclusion of the following coding for the Low Temperature MiniPurge Enclosure: Ex [p] dem IIC T4 Ex pD II 21 T135°C (Ta –50oC to +55oC) The introduction of the /ET version, an alternative to the pneumatic or mechanical timer system, this incorporates an Electronic Timer Module ETM-IS**-*** in the Mini Purge, the certification includes ‘ia’ marking when the ETM is fitted. The dust marking was changed to be consistent with the marking for gases and vapours. The introduction of a high pressure sensor for the LC option. Following appropriate re-assessment to demonstrate compliance with the requirements of the latest EN 60079 series of standards, the documents previously listed in section 9, EN 60079-0: 2006 and EN 60079-2: 2004 were replaced by those currently listed (EN 61241-0: 2006 was removed as this is incorporated into the current version of 60079-0), the markings in section 12 were updated accordingly and a new condition of certification was added. The recognition of the Applicant’s address change from Summer Road, Thames Ditton, Surrey KT7 0RH to Unit 2, The Summit, Hanworth Road, Sunbury on Thames, Surrey TW16 5DB. Form 9400 Issue1 Page 5 of 7 Tel: Fax: Email: Web: +44 (0) 1244 670 900 +44 (0) 1244 539 301 ukinfo@csagroup.org www.csagroupuk.org Unit 6, Hawarden Industrial Park, Hawarden, CH5 3US, United Kingdom Sira Certification Service The inlet air temperature sensing system was changed; as a consequence, a Special Condition For Safe Use was amended. A Local Sensing (LS) option was introduce. The RLV configuration was changed to show an optional alternative position of the flow sensing connection. The recognition of minor drawing modifications; the addition of notes and the clarification of the markings etc., these amendments are administrative that do not affect the aspects of the product that are relevant to explosion safety. The minimum ambient temperature limit for the Low Temperature and Low Temperature/ET versions was lowered from -50°C to -60°C. Following appropriate assessment to demonstrate compliance with the latest technical knowledge, Following appropriate assessment to demonstrate compliance with the latest technical knowledge, EN 60079-0:2012, EN 60079-2:2007, IEC 61241-4:2001 Edition 1 and EN 61241-4:2006 were replaced by EN 60079-0:2012 and EN 60079-2:2014, the markings in section 12 were updated accordingly. This certificate and its schedules may only be reproduced in its entirety and without change. vi. v. iv. ii. iii. i. Variation 8 - This variation introduced the following changes: i. Variation 7 - This variation introduced the following change: i. Variation 6 - This variation introduced the following change: ii. iii. i. Variation 5 - This variation introduced the following changes: i. Sira 01ATEX1295X Issue 9 Following appropriate re-assessment to demonstrate compliance with the requirements of the EN 60079 series of standards, the documents originally listed in section 9, EN 50014:1997 (amendments A1 to A2) and EN 50016:1995 were replaced by EN 60079-0:2006, EN 60079-1:2004, EN 61241-0:2006 and EN 61241-1:2006, the markings in section 12 were updated accordingly. The removal of special conditions for safe use that were not specifically associated with the equipment covered by this certificate. Variation 4 - This variation introduced the following change: ii. i. Variation 3 This variation introduced the following changes: EC TYPE-EXAMINATION CERTIFICATE SCHEDULE This MiniPurge Control Unit shall be incorporated into equipment and the appropriate Conformity Assessment Procedures applied to the combination as defined by Directive 94/9/EC. This certificate does not cover the combination. The purge controller, low temperature version, shall be protected by a safety related system that ensures that it cannot be energised if the temperature of the controller logic air or purge controller falls below -20°C. This system shall utilise the RTDs that are fitted to the purge controller to provide the appropriate level of system integrity, i.e. a level of operational safety of Cat 3 according to EN 954-1 for ATEX Category 2 (Zone 1) applications; note that these RTDs have not been assessed as a safety related device in accordance with EHSR 1.5 of Directive 94/9/EC. 15.4 15.5 Form 9400 Issue1 Page 6 of 7 The values of the safety parameters shall be set in accordance with the equipment certificate that covers the combination of the pressurised enclosure(s) and MiniPurge Control Unit. 15.3 Tel: Fax: Email: Web: +44 (0) 1244 670 900 +44 (0) 1244 539 301 ukinfo@csagroup.org www.csagroupuk.org Unit 6, Hawarden Industrial Park, Hawarden, CH5 3US, United Kingdom Sira Certification Service The installer/user shall ensure that the MiniPurge Control Unit is installed in accordance with the equipment certificate that covers the combination of the pressurised enclosure(s) and MiniPurge Control Unit. 15.2 This certificate and its schedules may only be reproduced in its entirety and without change. When using the AO, AS and DT options, the recommendations for the additional requirements of Ex p apparatus contained within EN 60079-14 shall be applied. R25983A/00 R29097A/00 R70012182A Comment The release of prime certificate. The introduction of Variation 1. The introduction of Variation 2. The re-issue of Variation 2 to include the changes described in report number R51A15629A. This Issue covers the following changes: • All previously issued certification was rationalised into a single certificate, Issue 4, Issues 0 to 3 referenced above are only intended to reflect the history of the previous certification and have not been issued as documents in this format. • The introduction of Variation 3. The introduction of Variation 4. This Issue covers the following changes: • This certificate history was modified to recognise that that Variation 2 was re-issued, subsequent Variations have therefore been re-numbered. • The introduction of Variation 5. The introduction of Variation 6. The introduction of Variation 7. The introduction of Variation 8. SPECIAL CONDITIONS FOR SAFE USE (denoted by X after the certificate number) 07 December 2011 05 October 2012 10 July 2015 R51L19695A R23665A/00 R51L15966B Report no. R53A7169A R53V11342A R51A11080A R51A15629A 15 7 8 9 18 February 2009 22 December 2010 7 June 2007 4 5 6 Date 3 July 2002 29 March 2004 30 September 2004 19 September 2006 Issue 0 1 2 3 Associated Sira Reports and Certificate History Refer to Certificate Annexe. Drawings DESCRIPTIVE DOCUMENTS Sira 01ATEX1295X Issue 9 15.1 14.2 14.1 14 EC TYPE-EXAMINATION CERTIFICATE SCHEDULE Page 31 ML434 | v12l The use of this certificate is subject to the Regulations Applicable to Holders of Sira Certificates. Holders of Type Examination Certificates are required to comply with the production control requirements defined in Article 8 of directive 94/9/EC. The switches incorporated in the PA option shall be suitably certified for Category 2. The following routine tests shall be performed by the manufacturer: 17.2 17.3 17.4 Form 9400 Issue1 Page 7 of 7 The Purge Controllers: Sub-MiniPurge, MiniPurge, Super-MiniPurge, Super-MiniPurge 1800/3500/7000/7000X shall not be marked as suitable for use in explosive dust atmospheres when a non-metallic or painted housing is used. 17.7 Tel: Fax: Email: Web: +44 (0) 1244 670 900 +44 (0) 1244 539 301 ukinfo@csagroup.org www.csagroupuk.org Unit 6, Hawarden Industrial Park, Hawarden, CH5 3US, United Kingdom Sira Certification Service The certification code that is appropriate to Purge Controllers low temperature version shall appear in the product marking applied to outer stainless steel enclosure. 17.6 This certificate and its schedules may only be reproduced in its entirety and without change. The products covered by this certificate incorporate previously certified devices, it is therefore the responsibility of the manufacturer to continually monitor the status of the certification associated with these devices, and the manufacturer shall inform Sira of any modifications of the devices that may impinge upon the explosion safety design of the products. 17.5 Where the HP is specified an overpressure shall be simulated whilst the MiniPurge Control Unit is cycling, it shall be verified that the controller provides the appropriate output and resets. Verification of Purging Overpressure protection An air supply failure shall be simulated whilst the MiniPurge Control Unit is cycling, it shall be verified that the controller provides the appropriate output and resets. Verification of Air Supply Failure Protection A purge failure shall be simulated whilst the MiniPurge Control Unit is cycling, it shall be verified that the controller provides the appropriate output and resets. Verification of Purge Failure Protection An overpressure loss shall be simulated whilst the MiniPurge Control Unit is cycling, it shall be verified that the controller provides the appropriate output and resets. Verification of Minimum Overpressure Cut Off CONDITIONS OF CERTIFICATION 17.1 The relevant EHSRs that are not addressed by the standards listed in this certificate have been identified and individually assessed reports listed in Section 14.2. ESSENTIAL HEALTH AND SAFETY REQUIREMENTS (EHSRs) Sira 01ATEX1295X Issue 9 17 16 EC TYPE-EXAMINATION CERTIFICATE SCHEDULE Purge Controllers Sub-MiniPurge, MiniPurge, Super-MiniPurge, Super-MiniPurge 1800/3500/7000/7000X EXPO Technologies Limited Equipment: Applicant: Sheet 1 to 4 1 to 2 1 of 1 1 of 1 1 of 1 Rev. 3 2 1 1 1 Date 02 Jul 02 21 May 01 21 Sep 00 21 Sep 00 21 Sep 00 Description MiniPurge ATEX Certification Labelling MiniPurge ATEX Certification Type Numbering Scheme MiniPurge, Continuous Flow with /HP Sensor –Schematic diagram RLV, outlet orifice Outlet Valve Control Circuit Diagram Sheet 1 of 1 Rev. 3 Date Description 22 March 04 Low Temperature Housing - General Arrangement Description Certification label Low temperature housing wiring certification drawing. Sheet 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 to 2 1 to 2 Sheet 1 to 5 Rev. 02 03 02 02 02 02 02 03 03 02 02 02 02 01 01 01 01 02 01 04 06 03 Rev. 5 Date 15 Mar 07 09 Jul 07 15 Mar 07 15 Mar 07 15 Mar 07 15 Mar 07 15 Mar 07 15 Mar 07 15 Mar 07 15 Mar 07 15 Mar 07 15 Mar 07 15 Mar 07 15 Mar 07 15 Mar 07 18 Apr 07 27 Mar 07 15 Mar 07 25 Apr 07 15 Mar 07 20 Feb 07 20 Feb 07 Date 30 Aug 06 Form 9400 Issue 1 This certificate and its schedules may only be reproduced in its entirety and without change. Number EP99-3-1 EP99-2-1 EP99-2-3 EP99-2-2 EP99-2-7 EP99-2-8 EP99-2-9 EP99-2-10 EP99-2-11 EP99-2-12 EP99-2-14 EP99-2-17 EP99-2-16 SD7533 SD7535 SD7536 SD7538 SD7449 SD7500 SD7448 SD7281 SD7282 Issue 4 Number SD7281 Page 1 of 2 Tel: Fax: Email: Web: +44 (0) 1244 670 900 +44 (0) 1244 539 301 ukinfo@csagroup.org www.csagroupuk.org Unit 6, Hawarden Industrial Park, Hawarden, CH5 3US, United Kingdom Sira Certification Service Description Minipurge Control Unit – General Assembly Schematic - Type x Leakage Compensation Sequence Diagram - Type x Leakage Compensation Schematic - Type x Continuous Flow Schematic – Separate Supply and Mechanical Timer Schematic – Delay Before Trip and On/Off Schematic – Twin Output and Manual Override Schematic – Pressure Control Leakage Compensation Internal “IS” Switches Schematic – Containment System and Secondary pressurisation Schematic – Continuous Flow with 2 Flow Rates Schematic – Continuous Flow with High Pressure Schematic – Outlet Valve Control Schematic – Dust Protection Spark Arrestor Differential Flow Monitor Continuous Flow Outlet Orifice Wiring Diagram – Low temperature Outlet Orifice Closing Device Low Temperature Housing Certification Label Details MiniPurge Data Sheet Description Certification label Issue 3 (The drawings associated with this issue were replaced by those listed in Issue 4) Number Sheet Rev. Date SD7281* 1 to 5 4 17 Dec 03 SD7449 1 of 1 1 18 Dec 03 * Modified by Sira 30 September 2004 Issue 2 (The drawings associated with this issue were replaced by those listed in Issue 4) Number SD7448 Issue 1 (The drawings associated with this issue were replaced by those listed in Issue 4) Number SD7281 SD7282 EP/99-2-17 EP99-7-7 EP99-7-9 Issue 0 (The drawings associated with this issue were replaced by those listed in Issue 4) Sira 01ATEX1295X Certificate Number: Certificate Annexe ML434 | v12l Page 32 Sheets 1 to 3 1 to 3 1 to 2 1 to 7 1 of 1 1 of 1 Sheets 1 to 3 Sheets 1 of 1 1&2 1 to 3 1 of 1 Sheets 1 to 2 1 to 2 1 of 1 1 of 1 Sheets 1 to 2 1 of 1 Rev. 10 11 6 1 8 2 Rev. 10 Rev. 6 5 9 2 Rev. 8 4 2 2 Rev. 7 05 Date (Sira stamp) 22 Jun 15 22 Jun 15 22 Jun 15 22 Jun 15 22 Jun 15 22 Jun 15 Date (Sira stamp) 05 Oct 12 Date (Sira stamp) 23 Nov 11 23 Nov 11 23 Nov 11 23 Nov 11 Date (Sira stamp) 23 Dec 10 21 Dec 10 21 Dec 10 21 Dec 10 Form 9400 Issue 1 Page 2 of 2 Title Low Temperature Housing MiniPurge Certification Label MiniPurge Data Sheets MiniPurge Manual Extracts Low Temperature Wiring Local Sensing Option Title Minipurge Certification Label Tel: Fax: Email: Web: +44 (0) 1244 670 900 +44 (0) 1244 539 301 ukinfo@csagroup.org www.csagroupuk.org Unit 6, Hawarden Industrial Park, Hawarden, CH5 3US, United Kingdom Sira Certification Service Description Minipurge Low Temperature Housing Minipurge Data Sheets Minipurge ATEX/IECEx Certification Label Minipurge Dust Protection Schematic Description Minipurge ATEX/IECEx Certification Label MiniPurge Data Sheet MiniPurge electronic timer MiniPurge HP sensor Description Minipurge ATEX/IECEx Certification Label Minipurge Low temperature Housing Description Fault Evaluation Outlet Valve Circuit N/O Outlet Control Valve N/C Schematic – Type Z or Y leakage compensation Schematic Type Z or Y Continuous Flow Sequence Diagram – Type X Continuous Flow Schematic – Alarm only and Alarm Action Selector Schematic – Door Switch Active Alarm and Alarm Cancel RLV Configurations Alternative Z&Y LC System Alternative Z&Y LC System Date (Sira stamp) 12 Feb 09 12 Feb 09 Date 20 Feb 07 15 Mar 07 15 Mar 07 09 Jul 07 15 Mar 07 15 Mar 07 15 Mar 07 15 Mar 07 05 Jul 07 09 Jul 07 09 Jul 07 This certificate and its schedules may only be reproduced in its entirety and without change. Number SD7448 SD7281 SD7282 SD8196 SD7449 SD8158 Issue 9 Number SD7281 Issue 8 Number SD7448 SD7282 SD7281 SD7533 Issue 7 Number SD7281 SD7282 SD7913 SD7914 Issue 6 Number SD7281 SD7448 Issue 5 Rev. 01 02 01 02 01 02 02 02 01 01 01 EXPO Technologies Limited Applicant: Number SD7537 EP99-7-9 EP99-7-9 SD7531 SD7532 EP99-2-4 EP99-2-5 EP99-2-6 SD7555 SD7556 SD7556 Purge Controllers Sub-MiniPurge, MiniPurge, Super-MiniPurge, Super-MiniPurge 1800/3500/7000/7000X Sira 01ATEX1295X Equipment: Sheet 1 to 3 1 of 2 2 of 2 1 of 1 1 of 1 1 of 1 1 of 1 1 of 1 1 to 4 1 of 2 2 of 2 Certificate Number: Certificate Annexe Page 33 ML434 | v12l ML434 | v12l Page 34 Page 35 ML434 | v12l ML434 | v12l Page 36 Page 37 ML434 | v12l ML434 | v12l Page 38 MiniPurge Interface Unit MIU/e User Instruction Manual Manufacturer: Model Type & Rating: Certificates: Hazardous Area Marking Code: Expo Technologies Ltd, Unit 2 The Summit, Sunbury on Thames. UK. MIU/e1 MIU/e2 MIU/e1/MO 400V / 7A 400V / 7A 400 V / 2A IECEx ITS10.0003X Ex e IIC T5 Gb Ex tb IIIC T100°C Db IP66 Tamb -20°C to +55°C Ex e IIC T4 Gb Tamb -20ºC to +60ºC ITS 10ATEX37092X II 2 G D Ex e IIC T5 Gb Ex tb IIIC T100°C Db IP66 Tamb -20°C to +55°C II 2 G D Ex e IIC T4 Gb Tamb -20°C to +60°C TUV 12.1463 Ex e IIC T5 Gb Ex tb IIIC T100ºC Db IP66 Tamb -20°C to +55°C Ex e IIC T4 Gb Tamb -20°C to +60°C APPLICATION SUITABILITY The MiniPurge Interface Units – MIU/e are certified for use in Hazardous Areas where the Hazardous Area is non-mining (i.e. above ground) and the hazard is caused by flammable gasses or vapours. The systems may be used in ATEX/IECEx Gas Zones 1 & 2, Gas Groups IIA, IIB & IIC and in Dust Zones 21 & 22, Dust Groups IIIA, IIIB & IIIC. The following materials are used in the construction of MIU/e: Stainless Steel, Steel, Brass, Copper, Polyamide, Silicone. If substances that will adversely affect any of these materials are present in the surrounding environment, please consult Expo Technologies for further guidance. This equipment is designed for use under normal industrial conditions of ambient temperature, humidity and vibration. Please consult Expo Technologies before installing this equipment in conditions that may cause stresses beyond normal industrial conditions. WARNING - Only install, commission, inspect, maintain or fault find when safe to do so. INSTALLATION The MIU/e shall be installed in accordance with relevant standards, such as EN 60079-14 and any local codes of practice that are in force. Cable glands or other cable entry devices shall be appropriately certified and suitable for the cable and the conditions of use and be installed in accordance with the manufacturer’s instructions. The MIU/e shall be connected to the Purge and Pressurization system in accordance with the instructions given in the handbook supplied with the pressurization system. The external earth connection of the MIU/e shall be connected to earth using minimum 4mm2 conductor. TERMINALS MIU/e may be fitted with a combination of: WDU2.5 terminals certified to KEMA 98ATEX1683U & IECEx ULD05.0008U SAK2.5 terminals certified to KEMA 98ATEX1798U & IECEx KEM06.0014U WPE2.5 Earth terminals certified to KEMA 98ATEX1683U & IECEx ULD05.0008U For all type of terminals: Tightening torque range: 0.4 to 0.8 Nm (WDU & WPE) & 0.4 to 0.6 Nm (SAK) Conductor cross section maximum 2.5 mm2, minimum 1.5 mm2 Type of connection is screwed - Solid copper conductors to be used. Stripping length shall be 10 mm. Only one conductor is allowed at each side of a terminal. Multiple conductors shall be crimped together before screwed into the terminal. Maximum number of terminals: For Model MIU/e1 – Up to 18 current carrying terminals For Model MIU/e2 – Up to 33 current carrying terminals For Model MIU/e1/MO – Up to 13 current carrying terminals COMMISSIONING The installation of the cable glands, electrical and earth connections shall be inspected for correct installation before the unit is put into service. The lid shall be correctly fitted. MAINTENANCE The condition of enclosure and associated cable glands shall be inspected for damage every six months. The terminals shall be inspected for tightness and gaskets inspected for damage. FAULT FINDING When wiring or signal fault occurs, check each terminated wire, terminals for tightness and gaskets for damage. External faults such as broken switches within the Control Unit may also require investigation. ML358 v7 Page 1 of 1 Page 39 18-Feb-16 ML434 | v12l ML434 | v12l Page 40 Page 41 ML434 | v12l ML434 | v12l Page 42 Page 43 ML434 | v12l 2 ML434 | v12l Page 44 Page 45 ML434 | v12l 2 ML434 | v12l Page 46 Page 47 ML434 | v12l &%68)'+QF, 0MQMXW[MXGL8]TI 4SWMXMSRW[MXGL8]TI %TTPMGERX %TTEVEXYW 1E\r' 8E r'8 1E\r' 8E r'8 X]TIHITIRHMRKZEPYIW 8LIGPEWWMJMGEXMSRSJEWTIGMJMGXIQTIVEXYVIGPEWWHITIRHWSREQFMIRXXIQTIVEXYVIGYVVIRXPSEHGEFPIX]TIERH GVSWWWIGXMSR8LIWIHEXEEVIHIJMRIHSRXLIQEVOMRKTPEXIERHXLI]EVIEPWSTVSZMHIHF]XLIQERYJEGXYVIV[MXLMR XLIXIGLRMGEPHSGYQIRXWERHMRWXVYGXMSRQERYEP ! QQtYTXSQQt %QFMIRXXIQTIVEXYVIVERKI SV 2YQFIVSJLSWIGEFPIW : (': ('% % %': (': ('% %': %'% %'% QE\ 6EXIHZSPXEKI QE\ 6EXIHGYVVIRX 'VSWWWIGXMSR 8]TI 8IGLRMGEPHEXE -)')\)47<MWWYI2S %RRI\XS ML434 | v12l Page 48 Page 49 ML434 | v12l With European Directives EC-Declaration of Conformity Expo Technologies Ltd Unit 2, The Summit, Hanworth Road Sunbury on Thames TW16 5DB, UK This is to declare that Purge Controllers Type “MiniPurge” are manufactured in conformity with the following European Directives and standards: Electromagnetic Compatibility Directive 2004/108/EG MiniPurge Systems with a /PO suffix in the type number are non-electrical and are outside the scope of the EMC Directive. MiniPurge Systems with suffices /PA or /IS incorporate one or more volt-free (“dry”) contacts which work in circuits specified by others. In normal operation these circuits are “benign” and no CE mark is appropriate. MiniPurge Systems with Electronic Timer (Option /ET) are designed to conform to the EMC Directive, in compliance with EN 61000-6-4:2007 and EN 61000-6-2:2005 (Intertek Report EM10048000). Low Voltage Directive 2006/95/EC MiniPurge Systems are intended for use in potentially explosive atmospheres (Hazardous Areas) and are therefore excluded from the Low Voltage Directive. Pressure Equipment Directive 97/23/EC MiniPurge Systems are classified as not higher than category I under Article 9 of this Directive and intended for use in potentially explosive atmospheres (Hazardous Areas) and are therefore excluded from the Pressure Equipment Directive. ATEX Directive 94/9/EC MiniPurge Systems are designed to conform to the ATEX Directive, in compliance with: EN 60079-0 : 2012 + A11:2013 EN 60079-2 : 2014 MiniPurge Systems are certified by SIRA Certification Service, Rake Lane, Eccleston, Chester CH4 9JN, England, under EC Type-Examination Certificate SIRA 01ATEX1295X, in compliance with: EN 60079-0 : 2012 EN 60079-2 : 2014 According to the model, MiniPurge Systems are rated and shall be marked as follows: MiniPurge, X & Y models MiniPurge, Z models Group II Category 2G & 2D Group II Category 3G & 3D II 2(2) GD II 2(3) GD MiniPurge systems are manufactured under Production Quality Assurance Notification SIRA 99 ATEX M043, issued by SIRA Certification Service, Notified Body No 0518. John Paul de Beer Managing Director Date 25/09/2015 Confidential Assessment file reference SC004 S:\Files\QA\CERTS\C-OF-C\Minipurge CE SC004 Issue7.doc ML434 | v12l Page 50 Expo Technologies Ltd. Unit 2 The Summit Hanworth Road Sunbury on Thames TW16 5DB UK Expo Technologies Inc. 9140 Ravenna Road Unit #3 Twinsburg OH 44087 USA Tel: Fax: E-mail: +44(0)20 8398 8011 +44(0)20 8398 8014 sales@expoworldwide.com Tel: Fax: E-mail: +1 (440) 247 5314 +1 (330) 487 0611 sales.na@expoworldwide.com www.expoworldwide.com