N. S. Omar, A. A. Raj and C. K. Chakrabarty/ IJECCT 2014, Vol. 4 (2) 27 Computation of Ampacity Derating of HV and MV Multiple Circuit Crossing Nurul Syaza binti Omar1, Avinash Ashwin Raj2, Chandan Kumar Chakrabarty3 123 Department of Electronics and Communication Engineering, College of Engineering, Universiti Tenaga Nasional, Km. 7, Jalan Kajang-Puchong, 43009 Kajang, Selangor Darul Ehsan nurulsyaza.omar@gmail.com Abstract: Cable crossings may occur in substations and other installations where cable congestion may be unavoidable. When a cable carrying a high level of current crosses another cable carrying high current, additional heat is generated at the crossing point. As a result the current carrying capacity or ampacity of both cables can be reduced. To determine the ampacity, Multiphysics software from Computer Simulation Technology (CST) is used to model 2D temperature profile for the cable system in cross over configuration. The industry specific software which is Power Cable Ampacity Calculation (CYMCAP) is used to validate the CST simulation. The CST model can then be used to recommend the possible ampacity improvement actions for the cases under study. The results of this paper graphically show how the temperature of the cables at the crossing increase and then decrease as the crossing point is approached, passed and moved away from. This temperature increase will, in turn, reduce the ampacity of both cables. The reduction in ampacity can then be estimated when the temperatures of the cables are known. These data will allow the planners and engineers to optimize the lay-out of the cables to achieve the optimum configuration for the required current load on the cable. Keywords –Ampacity; cable crossing; cable laying arrangement; computer simulation technology; derating; multiple trefoil three phase cable; power cable ampacity calculation; single core cable; temperature profile I. INTRODUCTION The important thing in engineering a power plant and over its service life is to maximize the current carrying capacity of the cable system to supply the desired load. The cable needs to operate at temperatures over its lifetime that do not cause damage or excessive aging of the cable. The cable must be able to carry huge amounts of current without overheating. Cable heating is one of the major problems associated with underground lines. The rating of a power cable is dependent on its construction and also the method of installation [1]. Ampacity of electric power cables has been extensively discussed in the literature for many decades and is the subject of several international standards which are International Electrotechnical Commission (IEC) and the Institute of Electrical and Electronics Engineering (IEEE). Ampacity computations need solution of the heat transfer equations which define a functional relationship between temperature and conductor current within the cable and in its surroundings [2]. The cable ampacity calculation becomes crucial when there are multiple incoming and outgoing cable circuits at the substations which posed new challenge in determining the ampacity of the underground cables. Without proper evaluation of the ampacity of the overall underground cable system, the load transfer capability of the substation could not be optimized. However, the ampacity calculation has been accepted based on the model proposed by Neher and McGrath since the mid 1900’s. Thus it will be the reference for the cases under study [3]. The industrial software currently used for multiple circuit in parallel to determine the best cable layout is CYMCAP. This software provides temperature profile, ampacity results and other electrical specifications quite accurately. However for cable crossing layout, it can simulate only single circuit crossing. As now the need arises for determining the temperature in multiple circuit crossing because of increase in loading, therefore it has become pertinent to determine other software that can perform such type of cable layout simulation. This paper is aimed to provide the temperature profile and ampacity of the high-voltage (HV) cable lay in the multiple circuit crossing of the cables at the substation using CST and CYMCAP. The spacing and depth of the cables buried underground in various cable laying designs is the main parameters in this paper to determine the cable ampacity. The ampacity results provided in this paper enables planners and engineers to select the optimum cable laying arrangement, depth of buried and spacing between cables that achieves the desired load. The results of ampacity calculation are divided based on different cable crossing configurations which consist of Single Core Cable Crossing and Multiple Trefoil Three Phase Cable Crossing. In order to create the model and find the ampacity of the multiple circuit crossing configuration, CST Multiphysics is used and CYMCAP to validate only the single circuit crossing due to its limitation stated earlier. II. SOFTWARE DESCRIPTION This section covers the details regarding the software used in the simulation. N. S. Omar, A. A. Raj and C. K. Chakrabarty/ IJECCT 2014, Vol. 4 (2) A. Computer Simulation Technology CST is one of the most precise and effective computational solution for electromagnetic designs. CST consists of many modules such as CST Microwave Studio, CST EM Studio, CST Particle Studio and CST Multiphysics Studio (MPS). Nevertheless, because the used of CST in this project is to determine the ampacity of underground cables for cable crossing, the suitable modules is CST MPS. CST MPS is a capable and easy-touse tool for mechanical and thermal simulation. The main function of it is to generate heat transfer and measured the temperature from the cable model created [4]. B. Power Cable Ampacity Calculation (CYMCAP) CYMCAP is dedicated to the calculation of ampacity and temperature rise for power cable installation. It addresses steady-state and transient thermal cable rating as per analytical techniques described by Neher-McGrath and the IEC287© and IEC 853© International Standards. It was developed jointly by Ontario Hydro (Hydro One), McMaster University and CYME International, under the auspices of the Canadian Electricity Association. CYMCAP also helps increase system reliability and support the proper utilization of the installed equipment [5]. III. Horizontal spacing between cables is 0.09158 meter which is 1 diameter of 132kV 800mm2 cable. The cables touch. There are also few variable parameters for multiple trefoil three phase cable crossing which are: Depth is varied from 1.5 meter to 6 meter. Horizontal spacing and the vertical spacing of the circuit is varied between 1 cable diameter and 2 cable diameter. The final section of this paper presents the temperature profile of cable crossing between 132kV 1200mm2 Cu with 33kV 800mm2 Cu cables and 132kV 1200mm2 Cu with 33kV 1600mm2 Cu cables at 90o. IV. AMPACITY GUIDELINE In this section, the types of cables used in the simulation are shown in Figure 1 to Figure 4. In the ampacity calculation, the cable layer swellable tape is not included in the modeling since the contribution of this layer to ampacity is negligible. SCOPE OF PAPER This paper only covers cables that are direct buried underground without pipe. The type of cables included in this paper are 33kV 630mm2 Copper (Cu), 132kV 800mm2 Copper (Cu), 132kV 1200mm2 Copper (Cu) and 132kV 1600mm2 Copper (Cu). It is assumed that all the cables installed in a same type of laying configuration will carry same amount of current continuously. This current is limited by the cross-linked polyethylene (XLPE) continuous operating temperature of 90oC core surface temperature. There are two types of cable crossing configuration: single core cable crossing and multiple trefoil three phase cable crossing. A. Simulation Description For single core cable crossing, the type of cable used is both the same which is 132kV 800mm2 Cu at 90o. There are three arrangements which are single crossing, double crossing and triple crossing. For multiple trefoil three phase cable crossing between 132kV 800mm2 Cu and 33kV 800mm2 Cu cables at 90o, the arrangements is the positioning of 132kV cables below of 33kV cables. The calculation of the ampacity is based on these assumptions: Ambient Temperature : 30oC Thermal resistivity: 1.2oC M/W Bonding configuration: Cross bond with equal minor section length There are fix parameters for single core cable crossing which are: Length of cable is 1 meter Depth of buried is 1.5 meter 28 Figure 1. 33kV 630 mm2 XLPE Cu Figure 2. 132kV 800 mm2 XLPE Cu N. S. Omar, A. A. Raj and C. K. Chakrabarty/ IJECCT 2014, Vol. 4 (2) V. 29 CABLES AMPACITY FOR DIFFERENT TYPES OF CABLE CROSSING CONFIGURATION The results of the ampacity calculations are divided into two parts based on the different types of cable crossing configuration. A. Single Core Cable Crossing The purpose of this simulation is to validate the CST result with CYMCAP result. This is due to the limitation of CYMCAP software that can only simulate a single crossing. Based on the small percentage error between both the results, the CST result will be used for multiple single and trefoil three phase cable crossing. Figure 5 until Figure 7 below shows the three configurations of single core cable crossing arrangements. ‘d’ is the horizontal spacing between cables. Figure 3. 132kV 1200 mm2 XLPE Cu Figure 4. 132kV 1600 mm2 XLPE Cu Figure 5. Single Crossing A. Cables Current Carrying Capacity The cables ampacity is limited by the cable insulation material and conductor size. All the cable in this paper is XLPE insulated cables. The ampacity is limited by 90oC core surface temperature condition in continuous operation. Table 1 below shows the transformer rating and the expected current loading for the respective cables sizes. Equation (1) is used to find the expected current loading. S = 3 Io V (1) d S presents the transformer rating of the cable, Io is the current loading of the cable and V is the voltage of the cable. d Figure 6. Double Crossing Table 1. Cables Expected Current Loading No. 1 2 3 4 Type of Cable 33kV 630mm2 XLPE Cu 132kV 800mm2 XLPE Cu 132kV 1200mm2 XLPE Cu 132kV 1600mm2 XLPE Cu Transformer Rating (MVA) Expected Current Loading Io(A) 90 525 150 656 150 656 d d 240 1050 d d Figure 7. Triple Crossing N. S. Omar, A. A. Raj and C. K. Chakrabarty/ IJECCT 2014, Vol. 4 (2) Table 2 below shows the result of all cable crossing configuration. Each of the cable behaves as a heat source for neighboring one. The percentage error in the last column is the deviation of CST from CYMCAP. Table 3. Result for Top Cable 33kV 630mm2 Cu and Bottom Cable 132kV 800mm2 Cu No Depth Y(m) 1 1.5 3.0 6.0 Table 2. Result of Single Core Cable Crossing CYMCAP Ampacity(A) Type of Configuration Single Cable Crossing Double Cable Crossing Triple Cable Crossing CST Ampacity (A) error(%) 784.0 770.9 -1.7% n/a 670.3 n/a n/a 502.8 n/a CST result for the single cable crossing is hence validated by the small percentage error between both software simulations as shown in Table 2. Thus, another two simulations are done using the single crossing CST result which is 770.9A as the reference. B. Multiple Trefoil Three Phase Cable Crossing Ampacity of cables crossing are calculated to obtain the optimum horizontal spacing between each circuit, vertical spacing between top and bottom circuits and depth of buried. Figure 8 below show the cable crossing arrangements with 90° crossing which is the top three circuits are 33kV cable, bottom three circuits are 132kV cable configuration. There are two types of cable used in this section which is 33kV 630mm2 Cu and 132kV 800mm2 Cu. The horizontal spacing between each circuit, X; vertical spacing between top and bottom circuits, Z; and the depth of buried, Y; are varied for the cable crossing arrangements. X is using the cable diameter of the cable itself. For example, horizontal spacing between 33kV circuit is the cable diameter of 33kV itself. Same goes to 132kV. For Y, it is fixed with the used of 132kV cable diameter. Y 33kV X Z 132kV X Figure 8. Multiple Crossing Trefoil configuration: Top three circuits are 33kV cable, bottom three circuits are 132kV cable configuration The results of the ampacity calculations are tabulated in Table 3 below. The depth of buried and spacing between cables are varied for different cable arrangements of multiple trefoil three phase cable crossing configuration. Each of the cable behaves as a heat source for one another. 30 2 1.5 3.0 6.0 3 1.5 3.0 6.0 4 1.5 3.0 6.0 Horizontal Spacing X(m) 1 cable diameter 2 cable diameter Vertical Spacing Z(m) 1 cable diameter 132kV cable 2 cable diameter 132kV cable 1 cable diameter 132kV cable 2 cable diameter 132kV cable Current 33kV 630mm2 In(A) 324.7 320.1 Current 132kV 800mm2 In(A) 453.0 442.5 315.5 432.1 336.2 320.1 484.2 473.8 313.2 458.2 333.9 330.4 489.4 484.2 324.7 473.8 331.6 329.3 317.8 502.4 492.0 486.8 The optimum spacing and depth of cables buried underground shall be selected to obtain the required current carrying capacity of the cables. Based on Table 3 above, the optimum depth of buried chosen is 1.5 meter. This is because, the cable is laid progressively deeper under the ground the heat dissipation becomes correspondingly more difficult. Hence, as the depth of laying increases, the current carrying capacity also decreases. In order to find the optimum spacing, the percent of derating is calculated by using (2). Derating % Io I n / Io 100% (2) From the calculation done, the lowest percent of derating is 27.3% for 33kV cable and 12.3% for 132kV cable which the optimum horizontal spacing and optimum vertical spacing is 2 cable diameters. Reference [6] showed this percent of derating which the author claims the derating factor can be greater than 10% even if the heat source is perpendicular to the rated cable. The temperature influence on the external heat source on the rated cable will depend on both the crossing angle and the distance between the circuits. The vertical distance between the circuits plays a smaller role as far as the variation in the temperature is concerned. The influence temperature can be high at the point of intersection, even for a perpendicular crossing [7][8]. However, this paper only considered the angle of 90o only. VI. TEMPERATURE PROFILE Electric cables transmitting capacity were mainly restricted to its heat insulation level. To ensure the safe operation of the cable, mastering the temperature of the cable ontology was needed. Therefore, this section shows two results of the computed core temperature for cable crossing. Figure 9 shows the arrangement of cable crossing for 33kV 630mm2 cable with 132kV cable. The computed temperature for 33kV 630mm2 cable with 132kV N. S. Omar, A. A. Raj and C. K. Chakrabarty/ IJECCT 2014, Vol. 4 (2) 31 1200mm2 cable and 33kV 630mm2 cable with 132kV 1600mm2 cable are listed in Table 5 and Table 6. Figure 10 and Figure 11 show the profiles of temperature at the point of crossing. The temperature is from the point of crossing up to +/- 20 centimeters. This trend of results can be extended to other cables. The ampacity calculation is according to the following parameters as shown in Table 4. Table 4. Parameters of Ampacity Calculation No. 1 2 3 4 Parameters Type of Buried Bonding Arrangement Ambient Temperature Thermal Resistivity Conditions Direct Buried Cross Bonded 30oC o 1.2 C M/W Table 6. The Result for Computed Core Temperature between 33kV 630mm2 and 132kV 1600mm2 33kV 132kV Figure 9. Top circuit is 33kV cable, bottom circuit is 132kV cable configuration Table 5. Result for Computed Core Temperature between 33kV 630mm2 and 132kV 1200mm2 Distance along 132 kV 1200mm2 cables (cm) 20 18 16 14 12 10 8 6 4 2 0 -2 -4 -6 -8 -10 -12 -14 -16 -18 -20 Core Temperature (oC) 118.4 119.1 119.4 119.8 120.4 121.2 121.8 122.5 122.9 123.2 123.8 123.9 123.4 123.1 122.3 122.1 121.7 121.4 120.7 120.1 119.6 Distance along 33kV 630mm2 cables (cm) 20 18 16 14 12 10 8 6 4 2 0 -2 -4 -6 -8 -10 -12 -14 -16 -18 -20 Figure 10. Graph of Core Temperature versus Distance of Core Along the 33kV 630mm2 cable and 132kV 1200mm2 cable Core Temperature (oC) 116.8 117.5 117.9 117.9 118.2 118.4 118.6 118.9 119.2 119.7 120.4 119.8 119.5 119.1 118.9 118.6 118.2 117.7 117.5 117.2 117.0 Distance along 132 kV 1600mm2 cables (cm) 20 18 16 14 12 10 8 6 4 2 0 -2 -4 -6 -8 -10 -12 -14 -16 -18 -20 Core Temperature (oC) 122.2 122.8 123.5 123.7 123.9 124.1 124.2 124.4 124.5 124.8 124.9 124.9 124.7 124.3 124.1 123.5 123.0 122.6 122.3 122.1 121.7 Distance along 33kV 630mm2 cables (cm) 20 18 16 14 12 10 8 6 4 2 0 -2 -4 -6 -8 -10 -12 -14 -16 -18 -20 Core Temperature (oC) 121.2 121.6 122.1 122.2 122.5 122.8 123.2 123.4 123.6 123.9 124.2 123.8 123.7 123.3 123.1 122.8 122.5 122.2 122.0 121.7 121.4 Figure 11. Graph of Core Temperature versus Distance of Core along the 33kV 630mm2 cable and 132kV 1600mm2 cable N. S. Omar, A. A. Raj and C. K. Chakrabarty/ IJECCT 2014, Vol. 4 (2) Both cable loadings were not derated and the loading used was taken based on independent simulation of single circuit’s buried 1.5m to achieve a 90°C temperature at core. At 0cm, both cables obtain its highest temperature at core because that is the touching point of both crossings. The 132kV 1600mm2 cable temperature at this point is 124.9°C and the 33kV 630mm2 cable temperature is 124.2°C. The temperature decreases linearly as the length increases away from the point of intersection. From the results, the extent of cable crossing is an important factor that is going to determine the amount of derating during continuous operation and as such cable installers can now find ways to mitigate this by using different materials between the cables layer at only point of intersection [9]. VII. CONCLUSIONS The objective of this paper which is to use CST in finding the ampacity is achieved. CST Multiphysics is able to simulate and determine the ampacity and derating of single core multiple crossing and multiple trefoil three phase cable crossing. The simulations have shown that when a cable crosses each other, derating of its current carrying capacity or ampacity is required in determining the optimum cable laying arrangement. Furthermore, the angle of crossing might be one of the main parameters in determining the cable ampacity; which may dictate the bottleneck of the whole cable system. In addition, Figure 10 and Figure 11 prove that cable has its highest 32 temperature at 0cm which is the touching point of both crossing. REFERENCES [1] [2] [3] [4] [5] [6] [7] [8] [9] George J. Anders, “Rating of Electric Power Cables: Ampacity Computations for Transmission, Distribution, and Industrial Applications,” New York, McGraw-Hill, 1997. George J. Anders, “Rating of Electric Power Cables In Unfavourable Thermal Environment,” Canada, McGraw-Hill, 2005. Pascal Vaucheret, R. A. Hartlein, Senior Member, IEEE, & W. Z. Black, Fellow, IEEE, “Ampacity Derating Factors for Cables Buried in Short Segments of Conduit,” IEEE Trans. Power Delivery, vol. 20, no. 2, pp. 560-565, Apr. 2005. CST – Computer Simulation Technology available at: http://www.cst.com, retrieved on 10 August 2013. CYME – Power Engineering Software and Solutions available at: http://www.cyme.com, retrieved on 10 August 2013. George J. Anders, Fellow, IEEE, and Eric Dorison, “Derating Factor for Cable Crossings With Consideration of Longitudinal Heat Flow in Cable Screen,” IEEE Trans. Power Delivery, vol. 19, no. 3, pp. 926-932, Jul. 2004. George J. Anders and Heinrich Brakelmann, “Cable Crossings Derating Considerations Part I - Derivation of Derating Equations,” IEEE Trans. Power Delivery, vol. 14, no. 3, pp. 709-714, Jul. 1999. George J. Anders and Heinrich Brakelmann, “Cable Crossings Derating Considerations Part II – Example of Derivation of Derating Curves,” IEEE Trans. Power Delivery, vol. 14, no. 3, pp. 715-720, Jul. 1999. George J. Anders and Heinrich Brakelmann, “Ampacity Reduction Factors for Cables Crossing Thermally Unfavorable Regions,” IEEE Trans. Power Delivery, vol. 16, no. 4, pp. 444-448, Oct. 2001.