GH Phipps Construction Co. 496 Nevada Mesa View Colorado Springs CO 80907-4347 Request For Information RFI-14J2029-0155 Printed On: Subject: T6 Fixture in Corridor Leading to MDF Room Will Not Work Date: Project: CSU Pueblo-General Classroom Building Job: Address: 2200 Bonforte Blvd Required: Pueblo CO 81001 Pueblo County Phone: 01/20/2015 Page 1 of 1 01/20/2015 14J2029 01/27/2015 Est.Cost Impact: $ Fax: Est. Days Impact: To: Gwen Gilley SlaterPaull Architects Inc From: GH Phipps Construction Co. Co-Author: Ryan Cooley Contact: Co-Author RFI Number: Reference: Drawing: A-121 Detail: N/A Spec Section: N/A Page: N/A Discipline: All Request Please reference sheet A-121 and T6 fixture cut sheets. On sheet A-121, First Floor Reflected Ceiling Plan, the corridor leading to the MDF room has no ceiling in it. For this hallway, three T6 fixtures are shown to be in place according to the first floor lighting plan. However, on the attached T6 cut sheets, there's a note that says "integrates with the ceiling..." Furthermore, on the dimensional data section of the cut sheet, it shows all three options (trimless mud-in, non-drywall hard surface and trim flange), all which require either a ceiling or drywall for mounting. Finally, on the section page of the T6 cut sheet, the "Mudin Trimless, pre-set for 5/8" drywall" is boxed in indicating that this fixture is the on that has been ordered and furthermore requires a ceiling for mounting which is not provided in the aforementioned corridor. Please advise on how to proceed. Suggestion Answer Accept Suggestion Per discussion with CSUP facilities team at yesterday's OAC it is acceptable to retrofit the existing T6 fixtures so that they can be suspended by chains from floor structure above. Gwen Gilley Answered By: Signed: 01.22.2015 Date: Distribution: Subcontractors/Suppliers - Please respond back to GH Phipps Construction Co. within 7 calendar days from date of receipt regarding any cost or schedule impacts that are a result of this RFI. pm3010 1 5 4 3 2 6 SLATERPAULL RCP GENERAL NOTES RCP LEGEND AND SYMBOLS ARCHITECTS C1 1. EXPOSED STRUCTURE; PAINT ALL CEILING ELEVATIONS DIMENSIONED FROM FINISH FLOOR BELOW UNLESS NOTED OTHERWISE 2. CENTER ALL DEVICES, SPRINKLER HEADS, ETC. IN CEILING TILE C2 2' x 4' ACOUSTICAL CEILING TILE; BASIS OF DESIGN ARMSTRONG OPTIMA C3 SUSPENDED GYP BOARD SOFFIT - PAINTED REFER TO FINISH LEGEND C4 2' x 2' ACOUSTICAL CEILING TILE; BASIS OF DESIGN ARMSTRONG OPTIMA 3. ALL CEILING PAINT TO BE PT7 UNLESS NOTED OTHERWISE 1331 Nineteenth Street Denver, CO. 80202 P 303.607.0977 www.slaterpaull.com E CONSULTANT: RCP KEYNOTES WOOD CEILING SYSTEM; ALTERNATE #02 BASE BID, GYP C5 ACOUSTIC CEILING CLOUDS C6 2' x 4' ACOUSTICAL CEILING TILE; BASIS OF DESIGN ARMSTRONG MESA C7 2' x 2' ACOUSTICAL CEILING TILE; BASIS OF DESIGN ARMSTRONG MESA C8 1 ALUMINUM SUNSHADES, ADD ALTERNATE #11 2 GYPSUM BOARD CONTROL JOINT 3 ALIGN SOFFIT TO WALL 4 ALIGN ACOUSTIC CEILING TILE GRID 5 PREMANUFACTURED METAL PANEL SOFFIT 6 PROJECTION SCREEN 7 WOOD CEILING SYSTEM, ADD ALTERNATE #2 1 HOUR FIRE RATED SUSPENDED GYP BOARD SOFFIT - PAINTED REFER TO FINISH LEGEND C9 D A3 A-301 A2 A-124 9" 2' - 6" 2' - 6" 5 A B C6 C6 C6 5 PROJECT: C6 C6 5 CSU PUEBLO GENERAL CLASSROOM BUILDING COFFEE LOUNGE 101 A1 C3 11' - 4" 33 ASI #14 A-312 12 COB #03 A4 STAIR A 112 A-526 C3 14' - 0" FROM 96'-6" A-525 C3 9' - 8" FROM 96'-6" 16'-10" A5 A3 A-525 A-526 FROM 96'-6" STORAGE 112A 1' - 4" 4' - 0" 4' - 5 3/4" C3 11' - 4" 4' - 11 3/4" 3' - 2" C1 PC 4' - 8" 2' - 10" PT2 C3 11' - 0" OPEN ABOVE 2' - 11 1/2"4' - 0" A4 37' - 8 3/8" FROM 96'-6" C P GYP @ UNDERSIDE OF STAIR PT4 C4 11' - 4" C3 10' - 8" C3 11' - 4" C4 A-526 OPEN ABOVE VESTIBULE 102 P COLORADO STATE UNIVERSITY PUEBLO 5 C3 11' - 4" 6' - 6" 1' - 0 1/2" OWNER: A-301 A-122 4' - 0" 4' - 4 1/4" 5' - 10 1/2" C6 LOBBY 100 A4 P P C3 TOILET 10' - 0" 105 ELEV 106 A-524 2200 BONFORTE BOULEVARD PUEBLO, COLORADO 81001 A-311 STOR. 104 C1 J 13' - 0" J MEN'S TOILET ROOM 107 C3 13' - 6" FROM 96'-6" C9 PUEBLO, COLORADO C1 E1 8' - 1" FROM 96'-6" C6 5 3/4" C3 9' - 8" A-312 C3 COFFEE 11' - 4" SHOP 101A 4' - 6 1/4" 5' - 10 1/2" FACP 4' - 0" C4 14' - 0" 7' - 6" 10' - 5" A5 17' - 11 1/4" 2' - 0" C6 A-310 12' - 5 1/4" 5 20' - 7" C 6' - 4" 5' - 9 1/4" 2' - 7 3/4" 3' - 0" 4' - 0" 3 3/4" 36' - 9 1/8" 4' - 0" 1' - 7 1/4" A1 C3 10' - 0" 27' - 5 1/4" A-301 STORAGE 103A P C9 STAIR B 103 6' - 4 3/4" ISSUE: D 1' - 0" 05.30.2014 ISSUE FOR BID PACKAGE 04 07.29.2014 ISSUE FOR CONSTRUCTION 12 29 33 45 9'-8" REFERENCED T6 FIXTURES C3 P 45 COB #26 LECTURE CLASSROOM 111 A1 45 COB #26 LECTURE CLASSROOM 110 10' - 0" STORAGE 109G C3 7" 5' - 10" 6 C2 13' - 6" FROM 96'-6" 5' - 10" 7" 13'-6" 1' - 7" A-526 A-300 C3 10' - 0" 111' - 4" F MECHANICAL 109F C1 A5 A2 A-311 D1 A-514 A-525 4' - 3" 6 5 14'-10" FROM 96'-6" SERVICE YARD 100 13' - 9" P A-312 C1 EM. ELEC. 109D P 6 A2 COB #03 ASI #13 ASI #14 COB #26 C1 C1 C2 10' - 6" C2 10' - 0" FROM 96'-6" E A4 C3 10' - 0" 10' - 6" A-525 B WOMEN'S TOILET ROOM 108 C1 P CUST 109H FROM 96'-6" 7/28/14 10/24/14 11/5/14 12/29/14 FIRE PUMP 109B C1 C3 10' - 0" 6' - 3" C1 4' - 3" 6' - 0" A-524 ELEC. 109C 10' - 0" C1 MDF 109E C3 14' - 10" FROM 96'-6" A1 P C3 11' - 4" 2' - 6" A-300 G DRAWING INFORMATION: 11366.000 PROJECT NO: H 9" 10' - 2 3/4" DRAWN BY: Author CHECKED BY: Checker A1 APPROVED BY: A-312 Approver SHEET TITLE: FIRST FLOOR REFLECTED CEILING PLAN A 12/24/2014 1:24:15 PM C:\Revit Local Files\CSU_Pueblo_Central 2014_ggilley.rvt C3 14' - 10" FROM 96'-6" 13'-6" FROM 96'-6" C1 1 2 3 4 5 6 6.2 7 8 9 10 11 12 13 A-121 FLOOR REFLECTED CEILING PLAN A1 FIRST 1/8" = 1'-0" SHEET 1 2 3 4 5 6 OF Submitting Agency: Description: FSM4 FL 2T8 1C 277 S XF2 LP835 WH 4' Project: Notes: CSU PUEBLO GENERAL CLASSROOM Type: T6 CONTRACTOR TO VERIFY: drywall/hard ceiling seem 4 ® Voltage: Row Information: Colors/ Finishes: Switching Options: Ceiling Type: Suspension Lengths: Specific Dimming Ballasts (if required): Other: features Narrow 4" aperture slot fluorescent luminaire that integrates with the ceiling for a clean unobtrusive aesthetic. Frosted acrylic flush lens provides even illumination, high performance lens available for increased efficiency. Parabolic louver also available. Allows for individual and continuous row mount in trimless or flanged drywall applications. Available in 1 lamp T5, T5HO or T8 and 2 lamp T5 or T8 configurations, Seem 4 provides continuous illumination by TYPE combining 3’ and 4’ staggered lamps. Specify 1 lamp for even appearance and minimal lamp image, or 2 lamps when higher light levels are required. dimensional data non-drywall hard surface 4.00" 101.6mm 7.53" 191.3mm 4.88" 124.0mm 5.53" 140.5mm 4.88" 124.0mm 5.53" 140.5mm trim options THE LIGHTING AGENCY 4.00" 101.6mm 7.30" 185.4mm note: 0.375"min - 2.125"max ceiling thickness trimless mud-in louver companion luminaires note: 0.375"min - 2.125"max ceiling thickness wall to ceiling corner trim flange trim flange NOTES shielding november 2013 K trimless mud-in CATALOG NUMBER suspended wall mount 5.00" 127.0mm 5.63" 143.0mm 4.00" 101.6mm 5.30" 134.6mm performance 1-Lamp T5 High Performance Lens 77% Efficiency 999 cd @ 0˚ TYPE 1-Lamp T5 Flush Satin Lens 56% Efficiency 595 cd @ 0˚ CATALOG NUMBER NOTES THE LIGHTING AGENCY Visit focalpointlights.com for complete photometric data. www.focalpointlights.com | 1.773.247.9494 Submitting Agency: Description: FSM4 FL 2T8 1C 277 S XF2 LP835 WH 4' Project: Notes: CSU PUEBLO GENERAL CLASSROOM Type: T6 fixture: project: ordering ordering XXX FSM4 ordering luminaire header series ordering Seem text 4 XXX FSM4 ordering fine print FL shielding Flush Satin Lens High Performance Flush Lens (lamp image may be visible) Parabolic Louver FL FLXP PL 2T8 lamping One Lamp T8 Two Lamp T8 One Lamp T5 Two Lamp T5 One Lamp T5HO 1T8 2T8 1T5 2T5 1T5HO 1C circuits Single Circuit Dual Circuit (2-lamp luminaires only) 1C 2C 277 voltage 120 Volt 277 Volt 347 Volt ballast construction One piece, .07" thick housing of 6063-T5 extruded aluminum. 20 Ga. steel end caps. Luminaires include trimless aluminum flange. Lengths 6' and longer configured with staggered lamps: 1-lamp T8: 2-lamp T8: 1-lamp T5/T5HO: 2-lamp T5: 4.47" 9.35" 4.35" 2.00" 18 24 30 36 2' 3' 4' 5' unit unit unit unit weight: weight: weight: weight: overlap overlap overlap overlap lbs. lbs. lbs. lbs. Some configurations available for wood/IC applications, consult factory for details. optic Reflectors fabricated of 22 Ga. steel finished in High Reflectance White powder coat. Flush satin lens: extruded acrylic lens .07" thick with opal satin finish. High performance flush lens: extruded acrylic lens .07" thick with increased light transmission. Parabolic Louver: 0.75"H x 1.5" frequency fabricated of low iridescent semi-specular premium grade aluminum. electrical Luminaires are pre–wired with factory installed branch circuit wiring and over-molded quick connects. Electronic fluorescent ballasts are thermally protected and have a Class “P" rating. Optional dimming ballasts available. UL and cUL listed. finish Electronic Instant Start (T8 only) (maximum <20% THD) S E Electronic Program Start <10% THD S Electronic Dimming Ballast* D XF2 mounting Trim Flange Drywall Mud-in Trimless, pre-set for 1/2" Drywall Mud-in Trimless, pre-set for 5/8" Drywall Mud-in Trimless, set thickness in field TF XF1 XF2 XFF Non-Drywall Hard Surface XFN (mounting equipment assembled in field) (not intended for combustible materials) (consult factory for wood/IC applications) factory options Chicago Plenum CP Emergency Circuit* EC Emergency Battery Pack* EM Flex Whip* FW HLR/GLR Fuse FU Include 3000K lamp L830 Include 3500K lamp L835 Include 4100K lamp L841 WH finish Matte White L835 WH luminaire length 4' (lengths are nominal) Specify luminaire/row length in 1' increments X' (lengths 6' and longer configured with staggered lamps. 6' 2-lamp T8 configured with non-staggered lamps.) Polyester powder coat applied over a 5-stage pre–treatment. Focal Point LLC | 4141 S. Pulaski Rd, Chicago, IL 60632 | T: 773.247.9494 | F: 773.247.8484 | info@focalpointlights.com | www.focalpointlights.com. Focal Point LLC reserves the right to change specifications for product improvement without notification. specifications 120 277 347 * for more information see Reference section. * for more information see Reference section. recessed 363