RFI 155

advertisement
GH Phipps Construction Co.
496 Nevada Mesa View
Colorado Springs CO 80907-4347
Request For Information
RFI-14J2029-0155
Printed On:
Subject: T6 Fixture in Corridor Leading to MDF Room Will Not Work
Date:
Project: CSU Pueblo-General Classroom Building
Job:
Address: 2200 Bonforte Blvd
Required:
Pueblo CO 81001 Pueblo County
Phone:
01/20/2015
Page 1 of 1
01/20/2015
14J2029
01/27/2015
Est.Cost Impact: $
Fax:
Est. Days Impact:
To: Gwen Gilley
SlaterPaull Architects Inc
From: GH Phipps Construction Co.
Co-Author:
Ryan Cooley
Contact:
Co-Author RFI Number:
Reference:
Drawing:
A-121
Detail:
N/A
Spec Section:
N/A
Page:
N/A
Discipline:
All
Request
Please reference sheet A-121 and T6 fixture cut sheets.
On sheet A-121, First Floor Reflected Ceiling Plan, the corridor leading to the MDF room has no ceiling in it. For
this hallway, three T6 fixtures are shown to be in place according to the first floor lighting plan. However, on the
attached T6 cut sheets, there's a note that says "integrates with the ceiling..." Furthermore, on the dimensional
data section of the cut sheet, it shows all three options (trimless mud-in, non-drywall hard surface and trim flange),
all which require either a ceiling or drywall for mounting. Finally, on the section page of the T6 cut sheet, the "Mudin Trimless, pre-set for 5/8" drywall" is boxed in indicating that this fixture is the on that has been ordered and
furthermore requires a ceiling for mounting which is not provided in the aforementioned corridor.
Please advise on how to proceed.
Suggestion
Answer
Accept Suggestion
Per discussion with CSUP facilities team at yesterday's OAC it is acceptable to retrofit the
existing T6 fixtures so that they can be suspended by chains from floor structure above.
Gwen Gilley
Answered By:
Signed:
01.22.2015
Date:
Distribution:
Subcontractors/Suppliers - Please respond back to GH Phipps Construction Co. within 7 calendar days from date
of receipt regarding any cost or schedule impacts that are a result of this RFI.
pm3010
1
5
4
3
2
6
SLATERPAULL
RCP GENERAL NOTES
RCP LEGEND AND SYMBOLS
ARCHITECTS
C1
1.
EXPOSED STRUCTURE; PAINT
ALL CEILING ELEVATIONS DIMENSIONED FROM FINISH FLOOR BELOW
UNLESS NOTED OTHERWISE
2.
CENTER ALL DEVICES, SPRINKLER HEADS, ETC. IN CEILING TILE
C2
2' x 4' ACOUSTICAL CEILING TILE;
BASIS OF DESIGN ARMSTRONG OPTIMA
C3
SUSPENDED GYP BOARD SOFFIT - PAINTED
REFER TO FINISH LEGEND
C4
2' x 2' ACOUSTICAL CEILING TILE;
BASIS OF DESIGN ARMSTRONG OPTIMA
3.
ALL CEILING PAINT TO BE PT7 UNLESS NOTED OTHERWISE
1331 Nineteenth Street
Denver, CO. 80202
P 303.607.0977
www.slaterpaull.com
E
CONSULTANT:
RCP KEYNOTES
WOOD CEILING SYSTEM; ALTERNATE #02
BASE BID, GYP
C5
ACOUSTIC CEILING CLOUDS
C6
2' x 4' ACOUSTICAL CEILING TILE;
BASIS OF DESIGN ARMSTRONG MESA
C7
2' x 2' ACOUSTICAL CEILING TILE;
BASIS OF DESIGN ARMSTRONG MESA
C8
1
ALUMINUM SUNSHADES, ADD ALTERNATE #11
2
GYPSUM BOARD CONTROL JOINT
3
ALIGN SOFFIT TO WALL
4
ALIGN ACOUSTIC CEILING TILE GRID
5
PREMANUFACTURED METAL PANEL SOFFIT
6
PROJECTION SCREEN
7
WOOD CEILING SYSTEM, ADD ALTERNATE #2
1 HOUR FIRE RATED SUSPENDED GYP BOARD SOFFIT - PAINTED
REFER TO FINISH LEGEND
C9
D
A3
A-301
A2
A-124
9"
2' - 6"
2' - 6"
5
A
B
C6
C6
C6
5
PROJECT:
C6
C6
5
CSU PUEBLO
GENERAL
CLASSROOM
BUILDING
COFFEE
LOUNGE
101
A1
C3
11' - 4"
33
ASI #14
A-312
12
COB #03
A4
STAIR A
112
A-526
C3
14' - 0"
FROM 96'-6"
A-525
C3
9' - 8"
FROM 96'-6"
16'-10"
A5
A3
A-525
A-526
FROM 96'-6"
STORAGE
112A
1' - 4"
4' - 0"
4' - 5 3/4"
C3
11' - 4"
4' - 11 3/4"
3' - 2"
C1
PC
4' - 8"
2' - 10"
PT2
C3
11' - 0"
OPEN
ABOVE
2' - 11 1/2"4' - 0"
A4
37' - 8 3/8"
FROM 96'-6"
C
P
GYP @ UNDERSIDE
OF STAIR
PT4
C4
11' - 4"
C3
10' - 8"
C3
11' - 4"
C4
A-526 OPEN
ABOVE
VESTIBULE
102
P
COLORADO STATE
UNIVERSITY PUEBLO
5
C3
11' - 4"
6' - 6"
1' - 0 1/2"
OWNER:
A-301
A-122
4' - 0" 4' - 4 1/4" 5' - 10 1/2"
C6
LOBBY
100
A4
P
P
C3
TOILET
10' - 0"
105
ELEV
106
A-524
2200 BONFORTE BOULEVARD
PUEBLO, COLORADO 81001
A-311
STOR.
104
C1
J
13' - 0"
J
MEN'S
TOILET
ROOM
107
C3
13' - 6"
FROM 96'-6"
C9
PUEBLO, COLORADO
C1
E1
8' - 1"
FROM 96'-6"
C6
5 3/4"
C3
9' - 8"
A-312
C3 COFFEE
11' - 4" SHOP
101A
4' - 6 1/4" 5' - 10 1/2"
FACP
4' - 0"
C4
14' - 0"
7' - 6"
10' - 5"
A5
17' - 11 1/4"
2' - 0"
C6
A-310
12' - 5 1/4"
5
20' - 7"
C
6' - 4"
5' - 9 1/4"
2' - 7 3/4"
3' - 0"
4' - 0"
3 3/4"
36' - 9 1/8"
4' - 0"
1' - 7 1/4"
A1
C3
10' - 0"
27' - 5 1/4"
A-301
STORAGE
103A
P
C9
STAIR B
103
6' - 4 3/4"
ISSUE:
D
1' - 0"
05.30.2014 ISSUE FOR BID PACKAGE 04
07.29.2014 ISSUE FOR CONSTRUCTION
12
29
33
45
9'-8"
REFERENCED T6
FIXTURES
C3
P
45
COB #26
LECTURE
CLASSROOM
111
A1
45
COB #26
LECTURE
CLASSROOM
110
10' - 0"
STORAGE
109G
C3
7"
5' - 10"
6
C2
13' - 6" FROM 96'-6"
5' - 10"
7"
13'-6"
1' - 7"
A-526
A-300
C3
10' - 0"
111' - 4"
F
MECHANICAL
109F
C1
A5
A2
A-311
D1
A-514
A-525
4' - 3"
6
5
14'-10"
FROM 96'-6"
SERVICE
YARD
100
13' - 9"
P
A-312
C1
EM. ELEC.
109D
P
6
A2
COB #03
ASI #13
ASI #14
COB #26
C1
C1
C2
10' - 6"
C2
10' - 0"
FROM 96'-6"
E
A4
C3
10' - 0"
10' - 6"
A-525
B
WOMEN'S
TOILET
ROOM
108
C1
P
CUST
109H
FROM 96'-6"
7/28/14
10/24/14
11/5/14
12/29/14
FIRE
PUMP
109B
C1
C3
10' - 0"
6' - 3"
C1
4' - 3"
6' - 0"
A-524
ELEC.
109C
10' - 0"
C1
MDF
109E
C3
14' - 10" FROM 96'-6"
A1
P
C3
11' - 4"
2' - 6"
A-300
G
DRAWING INFORMATION:
11366.000
PROJECT NO:
H
9"
10' - 2 3/4"
DRAWN BY:
Author
CHECKED BY:
Checker
A1
APPROVED BY:
A-312
Approver
SHEET TITLE:
FIRST FLOOR
REFLECTED CEILING
PLAN
A
12/24/2014 1:24:15 PM
C:\Revit Local Files\CSU_Pueblo_Central 2014_ggilley.rvt
C3
14' - 10"
FROM 96'-6"
13'-6"
FROM 96'-6"
C1
1
2
3
4
5
6
6.2
7
8
9
10
11
12
13
A-121
FLOOR REFLECTED CEILING PLAN
A1 FIRST
1/8" = 1'-0"
SHEET
1
2
3
4
5
6
OF
Submitting Agency:
Description:
FSM4 FL 2T8 1C 277 S XF2 LP835 WH 4'
Project:
Notes:
CSU PUEBLO GENERAL CLASSROOM
Type:
T6
CONTRACTOR TO VERIFY:
drywall/hard ceiling
seem 4
®
Voltage:
Row Information:
Colors/ Finishes:
Switching Options:
Ceiling Type:
Suspension Lengths:
Specific Dimming Ballasts
(if required):
Other:
features
Narrow 4" aperture slot fluorescent
luminaire that integrates with the ceiling
for a clean unobtrusive aesthetic.
Frosted acrylic flush lens provides even
illumination, high performance lens available
for increased efficiency. Parabolic louver
also available.
Allows for individual and continuous
row mount in trimless or flanged drywall
applications.
Available in 1 lamp T5, T5HO or T8 and
2 lamp T5 or T8 configurations, Seem
4 provides continuous illumination by
TYPE
combining 3’ and 4’ staggered lamps.
Specify 1 lamp for even appearance and
minimal lamp image, or 2 lamps when
higher light levels are required.
dimensional data
non-drywall hard surface
4.00"
101.6mm
7.53"
191.3mm
4.88"
124.0mm
5.53"
140.5mm
4.88"
124.0mm
5.53"
140.5mm
trim options THE LIGHTING AGENCY
4.00"
101.6mm
7.30"
185.4mm
note: 0.375"min - 2.125"max ceiling thickness
trimless mud-in
louver
companion luminaires
note: 0.375"min - 2.125"max ceiling thickness
wall to ceiling
corner
trim flange
trim flange
NOTES
shielding
november 2013 K
trimless mud-in
CATALOG NUMBER
suspended
wall mount
5.00"
127.0mm
5.63"
143.0mm
4.00"
101.6mm
5.30"
134.6mm
performance
1-Lamp T5
High Performance
Lens
77% Efficiency
999 cd @ 0˚
TYPE
1-Lamp T5
Flush Satin Lens
56% Efficiency
595 cd @ 0˚
CATALOG NUMBER
NOTES
THE LIGHTING AGENCY
Visit focalpointlights.com for
complete photometric data.
www.focalpointlights.com | 1.773.247.9494
Submitting Agency:
Description:
FSM4 FL 2T8 1C 277 S XF2 LP835 WH 4'
Project:
Notes:
CSU PUEBLO GENERAL CLASSROOM
Type:
T6
fixture:
project:
ordering
ordering
XXX
FSM4
ordering
luminaire
header
series
ordering Seem
text 4 XXX
FSM4
ordering fine print
FL
shielding
Flush Satin Lens
High Performance Flush Lens
(lamp image may be visible)
Parabolic Louver
FL
FLXP
PL
2T8
lamping
One Lamp T8
Two Lamp T8
One Lamp T5
Two Lamp T5
One Lamp T5HO
1T8
2T8
1T5
2T5
1T5HO
1C
circuits
Single Circuit
Dual Circuit
(2-lamp luminaires only)
1C
2C
277
voltage
120 Volt
277 Volt
347 Volt
ballast
construction
One piece, .07" thick housing of 6063-T5 extruded aluminum.
20 Ga. steel end caps.
Luminaires include trimless aluminum flange.
Lengths 6' and longer configured with staggered lamps:
1-lamp T8:
2-lamp T8:
1-lamp T5/T5HO:
2-lamp T5:
4.47"
9.35"
4.35"
2.00"
18
24
30
36
2'
3'
4'
5'
unit
unit
unit
unit
weight:
weight:
weight:
weight:
overlap
overlap
overlap
overlap
lbs.
lbs.
lbs.
lbs.
Some configurations available for wood/IC applications, consult factory for details.
optic
Reflectors fabricated of 22 Ga. steel finished in High Reflectance White
powder coat.
Flush satin lens: extruded acrylic lens .07" thick with opal satin finish.
High performance flush lens: extruded acrylic lens .07" thick with increased light
transmission.
Parabolic Louver: 0.75"H x 1.5" frequency fabricated of low iridescent
semi-specular premium grade aluminum.
electrical
Luminaires are pre–wired with factory installed branch circuit wiring and
over-molded quick connects.
Electronic fluorescent ballasts are thermally protected and have a Class “P" rating.
Optional dimming ballasts available.
UL and cUL listed.
finish
Electronic Instant Start
(T8 only)
(maximum <20% THD)
S
E
Electronic Program Start <10% THD S
Electronic Dimming Ballast* D
XF2
mounting
Trim Flange Drywall
Mud-in Trimless, pre-set for 1/2" Drywall
Mud-in Trimless, pre-set for 5/8" Drywall
Mud-in Trimless, set thickness in field
TF
XF1
XF2
XFF
Non-Drywall Hard Surface
XFN
(mounting equipment assembled in field)
(not intended for combustible materials)
(consult factory for wood/IC applications)
factory options
Chicago Plenum CP
Emergency Circuit* EC
Emergency Battery Pack* EM
Flex Whip* FW
HLR/GLR Fuse FU
Include 3000K lamp
L830
Include 3500K lamp
L835
Include 4100K lamp
L841
WH
finish
Matte White
L835
WH
luminaire length
4'
(lengths are nominal)
Specify luminaire/row length
in 1' increments
X'
(lengths 6' and longer configured
with staggered lamps. 6' 2-lamp T8
configured with non-staggered lamps.)
Polyester powder coat applied over a 5-stage pre–treatment.
Focal Point LLC | 4141 S. Pulaski Rd, Chicago, IL 60632 | T: 773.247.9494 | F: 773.247.8484 | info@focalpointlights.com | www.focalpointlights.com.
Focal Point LLC reserves the right to change specifications for product improvement without notification.
specifications
120
277
347
* for more information see Reference section.
* for more information see Reference section.
recessed
363
Download