Enclosed Circuit Breakers

advertisement
Switching Devices
Enclosed Circuit Breakers
8.2
Contents
Enclosed Circuit Breakers
Description
Page
Features, Benefits and Functions . . . . . . . . . . . . . . . . . . . . .
Standards and Certifications. . . . . . . . . . . . . . . . . . . . . . . . .
Cross-Reference. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Flex Center . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Data and Specifications. . . . . . . . . . . . . . . . . . . . .
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
106
106
107
109
111
113
114
116
8
8
8
8
8
8
8
8
8
8
Product Description
●
●
15–1200A
Enclosed device used to
open and close a circuit
8
Application Description
NEMA 1 General Purpose
Surface or Flush Mounting
15–1200A, 600 Vac, 500 Vdc
NEMA 1 enclosed breakers
are designed for indoor
use in commercial buildings,
apartment buildings and
other areas where a general
purpose enclosure is
applicable. The breaker is
front operable and is capable
of being padlocked in the
OFF position. Ratings
through 1200A are listed with
Underwriters Laboratories as
suitable for service entrance
application. Both surface and
flush mounted enclosures
are available.
8
NEMA 3R Rainproof
Surface Mounting
NEMA 4/4X, 5 Water
and Dustproof
Interchangeable Hubs (through
400A) 15–1200A, 600 Vac, 500 Vdc
This general purpose outdoor
service center employs a
circuit breaker inside a
weatherproof sheet steel
enclosure to serve as a main
disconnect and protective
device for feeder circuits.
The operating handle can
be padlocked in the OFF
position, and is interlocked
to prevent the door from
opening when the breaker
is ON. Ratings through
1200A are listed by
Underwriters Laboratories
as suitable for service
entrance application.
Stainless Steel—Type 304
Surface Mounting 15–1200A,
600 Vac, 500 Vdc
This enclosure meets NEMA
4/4X and 5 requirements
for water and dustproof
applications and has no
knockouts or other openings.
It is particularly well suited for
use in dairies, borax mines,
breweries, paper mills and
other process industries.
The operating handle can be
padlocked in the OFF position,
and is interlocked to prevent
the door from opening
when the breaker is ON.
Ratings through 1200A are
Underwriters Laboratories
listed as suitable for service
entrance application.
8
8
8
8
8
8
8
8
8
8
8
8
8
8
NEMA 1 General Purpose
8
NEMA 3R Rainproof Surface Mounting
8
8
NEMA 4/4X Water and Dustproof
Volume 2—Commercial Distribution
CA08100003E—February 2011
www.eaton.com
For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616
105
8
8.2
8
8
8
8
8
8
8
8
8
8
8
8
8
Switching Devices
Enclosed Circuit Breakers
NEMA 12 Dustproof
Surface Mounting
NEMA 7/9 Hazardous
Location
No Knockouts or Other Openings
15–1200A, 600 Vac,
500 Vdc
The Type 12 enclosure
is designed in line with
specifications for special
industry application where
unusually severe conditions
involving oil, coolant, dust and
other foreign materials exist
in the operating atmosphere.
The handle padlocks in the
OFF position and the cover is
interlocked with the handle
mechanism to prevent
opening the cover with the
circuit breaker in
the ON position. Ratings
through 1200A are listed by
Underwriters Laboratories as
suitable for service entrance
application. A NEMA 12
semi-dust-tight design
that includes knockouts
is available. These units
are rated 15–400A, 600 Vac,
500 Vdc.
Cast Aluminum, Explosion-proof
Surface Mounting 15–1200A,
600 Vac, 250 Vdc
Hazardous location, Type 7:
Class I, Groups B, C, D;
Type 9: Class II, Groups E,
F, G. This special service
cast aluminum enclosure
is supplied with a wide,
machined flanged cover
to prevent igniting outside
atmospheres by arcing from
inside the enclosure. Front
operable, the handle
padlocks in the OFF position.
Enclosures rated 600A and
above have lift-off hinges for
ease of assembly.
Features, Benefits
and Functions
●
●
●
●
●
●
Side-opening door on
NEMA 3R enclosures
Padlockable in the
OFF position
Surface or flush mounted
enclosures available
through 400A on
NEMA 1 enclosures
Interlocked handle on
NEMA 3R, 4/4X, 5 and
12 enclosures to prevent
opening when the breaker
is in the ON position
Interchangeable hubs
Numerous factory options
Note:þXFDN050B is not
Group B compliant.
Standards and
Certifications
●
●
●
UL 489
CSA 22.2
NEMA 250
NEMA 1 General Purpose
●
UL File No. E7819
●
CSA File No. LR84319
NEMA 3R Rainproof
Surface Mounting
●
UL File No. E7819
●
CSA File No. LR84319
NEMA 4/4X, 5 Water
and Dustproof
●
UL File No. E7819
●
CSA File No. LR84319
NEMA 12 Dustproof
Surface Mounting
●
UL File No. E7819
●
CSA File No. LR84319
NEMA 7/9 Hazardous Location
●
UL File No. E84577
●
CSA File No. LR42131-6
8
8
NEMA 7/9 Hazardous Location
8
8
8
8
NEMA 12 Dustproof Surface Mounting
8
8
8
8
8
8
8
8
8
8
8
106
Volume 2—Commercial Distribution
CA08100003E—February 2011
www.eaton.com
For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616
8.2
Switching Devices
Enclosed Circuit Breakers
Cross-Reference
8
8
Enclosed Circuit Breaker Competitive Catalog Numbers
Catalog Number
Square D
Siemens
8
NEMA
Rating
Eaton
General Electric
Enclosure
Breaker
Enclosure
Breaker
Enclosure
Breaker
Enclosure
Breaker
1 surface
SGDN100
GHC3100
EHB125NS
EHB34100
—
—
—
—
1 flush
—
—
EHB125NF
EHB34100
—
—
—
—
3R
RGDN100
GHC3100
EHB125NRB
EHB34100
—
—
—
—
12
JGDN100
GHC3100
—
—
—
—
—
—
12K
DGDN100
GHC3100
—
—
—
—
—
—
4/4X
WGDN100
GHC3100
—
—
—
—
—
—
1 surface
SFDN100
EHD3100L
FA100S
FAL34100
E2N1S
ED43B100
TE100S
TED134100WL
1 flush
FFDN100
EHD3100L
FA100F
FAL34100
E2N1F
ED43B100
TE100F
TED134100WL
3R
RFDN100
EHD3100L
FA100RB
FAL34100
E2N3R
ED43B100
TE100R
TED134100WL
12/3R
—
—
FA100AWK
FAL34100
—
—
—
—
12
JFDN100
EHD3100L
—
—
E2N12
ED43B100
TE100J/SE100J
TED134100WL
12K
DFDN100
EHD3100L
FA100A
FAL34100
E2N12
ED43B100
TE100D/ ______
TED134100WL
4/4X
WFDN100
EHD3100L
FA100DS
FAL34100
ED6SS4
ED43B100
TE100CS/SE100CS
TED134100WL
7/9
XFDN050
EHD3050L
FA060X
FAL34060
EA
ED43B100
—
—
9
—
—
FA060Y
FAL34060
—
—
—
—
7/9
XFDN225B FD3225L
FA100X
FAL34100
EB
ED43B100
—
—
9
—
—
FA100Y
FAL34100
—
—
—
—
1 surface
SFDN225 FDB3150L
—
—
E2N1S
ED43B125
TE150S
TED134150WL
1 flush
FFDN225 FDB3150L
—
—
E2N1F
ED43B125
TE150F
TED134150WL
3R
RFDN225 FDB3150L
—
—
E2N3R
ED43B125
TE150R
TED134150WL
12
JFDN225 FDB3150L
—
—
E2N12
ED43B125
—
—
FDB3150L
—
—
E2N12
ED43B125
—
—
FDB3150L
—
—
ED6SS4
ED43B125
—
—
12K
DFDN225
4/4X
WFDN225 7/9
XFDN225B
FDB3150L
—
—
—
—
—
—
1 surface
SFDN225 FD3225L
—
—
—
—
—
—
1 flush
FFDN225 FD3225L
—
—
—
—
—
—
3R
RFDN225 FD3225L
—
—
—
—
—
—
12
JFDN225 FD3225L
—
—
—
—
—
—
12K
DFDN225 FD3225L
—
—
—
—
—
—
4/4X
WFDN225 FD3225L
—
—
—
—
—
—
7/9
XFDN225B
1 surface
SJDN250
1 flush
3R
12/3R
12
FD3225L
—
—
—
—
—
—
JDB3250
KA225S
KAL36250
F6N1S
FXD63B250
TF225S
TFJ236225WL
FJDN250
JDB3250
KA225F
KAL36250
F6N1F
FXD63B250
TF225F
TFJ236225WL
RJDN250
JDB3250
KA225RB
KAL36250
F6N3R
FXD63B250
TF225R
TFJ236225WL
—
JDB3250
KA225AWK
KAL36250
—
—
—
—
JJDN250
JDB3250
—
—
F6N12
FXD63B250
TF225J/SF250J
TFJ236225WL
12K
DJDN250
JDB3250
KA225A
KAL36250
F6N12
FXD63B250
______ /SF250D
TFJ236225WL
4/4X
WJDN250
JDB3250
KA225DS
KAL36250
FD6SS4
FXD63B250
TF225CS/SF250CS
TFJ236225WL
7/9
XJDN250B
—
KA225X
KAL36250
EC2
FXD63B250
—
—
9
—
—
KA225Y
KAL36250
—
—
—
—
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
Notes
Maximum wire size 4/0.
Maximum wire size 500 kcmil.
8
8
8
Volume 2—Commercial Distribution
CA08100003E—February 2011
www.eaton.com
For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616
107
8.2
8
8
Switching Devices
Enclosed Circuit Breakers
Enclosed Circuit Breaker Competitive Catalog Numbers, continued
Catalog Number
Eaton
NEMA
Rating
Square D
Siemens
Enclosure
1 surface
SKDN400
KDB3400
LA400S
LAL36400
J6N1
JXD63B400
TJ400S/SG400S
TJK436400WL
1 flush
FKDN400 KDB3400
LA400F
LAL36400
—
—
TJ400F/SG400F
TJK436400WL
3R
RKDN400 KDB3400
LA400R
LAL36400
J6N3R
JXD63B400
TJ400R/SG400R
TJK436400WL
12/3R
—
—
LA400AWK
LAL36400
—
—
—
—
12
JKDN400 KDB3400
—
—
J6N12
JXD63B400
TJ400J/SG400J
TJK436400WL
8
12K
DKDN400 KDB3400
—
—
J6N12
JXD63B400
______ /SG400D
TJK436400WL
4/4X
WKDN400
KDB3400
LA400DS
LAL36400
—
—
TJ400CS/SG400CS
TJK436400WL
8
7/9
XKDN400B KDB3400
—
—
EE
JXD63B400
—
—
1 surface
SLDN600
LDB3600
MA1000S
MAL36600
LD6N1
LXD63B600
TJ600S/SG600S
TJK636600WL
1 flush
—
—
MA1000F
MAL36600
—
—
TJ600F/SG600F
TJK636600WL
3R
RLDN600
LDB3600
—
—
LD6N3R
LXD63B600
TJ600R/SG600R
TJK636600WL
12/3R
—
—
MA1000AWK
MAL36600
—
—
—
—
8
12
JLDN600
LDB3600
—
—
LD6N12
LXD63B600
TJ600J/SG600J
TJK636600WL
4/4X
WLDN600
LDB3600
MA1000DS
MAL36600
LD6SS4
LXD63B600
TJ600CS
TJK636600WL
8
7/9
XMCN800B
LDB3600
—
—
ED6
LXD63B600
—
—
1 surface
SNDN1200
MDL3800
MA1000S
MAL36800
LMD1
MXD63B800
TK4V1200S
TKMA836800WL
1 flush
—
—
MA1000F
MAL36800
—
—
TK4V1200F
TKMA836800WL
3R
RNDN1200
MDL3800
—
—
LMD3R
MXD63B800
TKV41200R
TKMA836800WL
12/3R
—
—
MA1000AWK
MAL36800
—
—
—
—
8
8
8
8
8
8
8
8
8
8
8
Breaker
General Electric
Breaker
8
Enclosure
Enclosure
Breaker
Enclosure
Breaker
12
JNDN1200
MDL3800
—
—
LMD12
MXD63B800
TK4V1200J/SK1200
TKMA836800WL
4/4X
WNDN1200
MDL3800
MA1000DS
MAL36800
—
—
—
—
7/9
XMCN800B
MDL3800
—
—
—
—
—
—
1 surface
SNDN1200
ND312T33W
MA1000S
MAL361000
—
—
—
—
1 flush
—
—
MA1000F
MAL361000
—
—
—
—
3R
RNDN1200
ND312T33W
—
—
—
—
—
—
12/3R
—
—
MA1000AWK
MAL361000
—
—
—
—
12
JNDN1200
ND312T33W
—
—
—
—
—
—
4/4X
WNDN1200
ND312T33W
MA1000DS
MAL361000
—
—
—
—
1 surface
SNDN1200
ND312T33W
—
—
MND61
NXD63B120
TK4V1200S
TKMA31200WL
12
—
—
—
—
—
—
TK4V1200F
TKMA31200WL
3R
RNDN1200
ND312T33W
—
—
MND63
NXD63B120
TKV41200R
TKMA31200WL
8
1 surface
—
—
NA1200AWK
NAL361200
—
—
—
—
12
JNDN1200
ND312T33W
—
—
MND612
NXD63B120
TK4V1200J/SK1200
TKMA31200WL
8
4/4X
WNDN1200
ND312T33W
—
—
—
—
—
—
7/9
XNDN1200B ND312T33W
—
—
—
—
—
—
8
8
8
8
Notes
Maximum wire size 500 kcmil.
Through-feed only.
8
8
8
8
8
8
108
Volume 2—Commercial Distribution
CA08100003E—February 2011
www.eaton.com
For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616
Switching Devices
Enclosed Circuit Breakers
8.2
Product Selection
1. Use the data on Page 120
to determine type of
enclosure required.
8
3. Pages 116 through 122
include rough-in
dimensional information.
8
8
2. Use the data on Page 114
and 115 to determine
circuit breaker required.
8
8
Enclosure Only
Breaker Frame
Breaker
Ampere Range
8
Enclosure
NEMA Class
Catalog Number
8
8
Series C Breakers
GHC, GD (two- and three-pole only)
GHCGFEP (single-pole only)
EHD, FD, FDB, HFD
15–100
15–100
1 surface
SGDN100 3R
RGDN100
12
JGDN100
12K
DGDN100
4/4X, 5 stainless steel
WGDN100
1 surface
SFDN100
1 flush
FFDN100
3R
RFDN100
12
JFDN100
12K
DFDN100
4/4X, 5 stainless steel
WFDN100
EHD, FD, FDB
15–50
7/9 cast aluminum
XFDN050B
HFD, FDC
60–225 7/9 cast aluminum
XFDN225B
FD, FDB, HFD, ED, EDH, EDC, FDC (15–225A)
125–225
1 surface
SFDN225
1 flush
FFDN225
3R
RFDN225
12
JFDN225
12K
DFDN225
4/4X, 5 stainless steel
WFDN225
JD, JDB, HJD, JDC
JD, JDB, HJD, JDC
125–250
125–250
1 surface
SJDN250
1 flush
FJDN250
3R
RJDN250
12
JJDN250
12K
DJDN250
4/4X, 5 stainless steel
WJDN250
7/9 cast aluminum
XJDN250B
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
Notes
Suitable for use with single-pole breaker. Base mounting plate kit. QCCBP required.
Maximum wire size: 4/0.
Can be field converted to NEMA Type 3R.
8
8
8
8
8
8
8
Volume 2—Commercial Distribution
CA08100003E—February 2011
www.eaton.com
For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616
109
8.2
8
Switching Devices
Enclosed Circuit Breakers
Enclosure Only, continued
8
Breaker Frame
8
KD, KDB, HKD, KDC, DK
Breaker
Ampere Range
Enclosure
NEMA Class
Catalog Number
Series C Breakers, continued
125–400
1 surface
SKDN400
1 flush
FKDN400
3R
RKDN400
8
12
JKDN400
12K
DKDN400
8
4/4X, 5 stainless steel
WKDN400
8
8
KD, KDB, HKD, KDC, DK
125–400
7/9 cast aluminum
XKDN400B
LGE, LGS, LGH
250–600
1 surface
SLG630
3R
RLG630
12
JLG630 4/4X, 5 stainless steel
WLG630
1 surface
SLDN600
3R
RLDN600
12
JLDN600
4/4X, 5 stainless steel
WLDN600
7/9 cast aluminum
XLDN600B
8
8
LD, LDB, HLD 300–600
8
8
8
8
MDL, HMDL
400–800
7/9 cast aluminum
XMCN800B
MDL, HMDL, ND, HND 400–1200
1 surface
SNDN1200
3R
RNDN1200
12
JNDN1200
4/4X, 5 stainless steel
WNDN1200
—
7/9 cast aluminum
XNDN1200B
15–100
1 surface
SFD100E
1 flush
FFD100E
3R
RFDN100E
12
JFDN100E
12K
DFDN100E
4/4X
WFDN100E
1 surface
SLG630E
3R
RLG630
8
8
8
ND, HND
Earth Leakage Breakers
ELFD, ELHFD and ELFDC (three-pole only)
8
8
8
8
LGE, LGS, LGH used with ELLBN
250–600
8
8
8
12
JLG630 4/4X, 5 stainless steel
WLG630
Notes
Short-circuit ratings are limited for high interrupting rated breakers. Refer to Page 114.
Can be field converted to NEMA Type 3R.
8
8
8
8
8
8
8
110
Volume 2—Commercial Distribution
CA08100003E—February 2011
www.eaton.com
For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616
8.2
Switching Devices
Enclosed Circuit Breakers
Accessories
8
Nameplates Applied
Neutral Assemblies Installed
Electronic Trip Options
Customer must provide
nameplate legend at the time
of order.
Ampere ratings: 100, 250,
400, 600, 800 and 1200.
Frame Type
Number of Poles
Description
KD, HKD
3
RMS 310 LS
Key Interlock Systems
Interlocks are used to prevent
an authorized operation.
Before system construction
can begin, the following
information must be known:
1. User—name, address
and telephone number.
2. Complete lock scheme
required.
8
8
Separate Ground Lug
Installed
RMS 310 LSI
Ampere ratings: 100, 250,
400, 600 and 1200.
RMS 310 LSIG RMS 310 LSG LD, HLD
3
Special Paint Finish
8
RMS 310 LS
RMS 310 LSI
Contact the Safety Switch
Flex Center (1-888-329-9272).
8
RMS 310 LSG RMS 310 LSIG
Pilot Light On NEMA 1
Enclosure
8
MDL, HMDL
3
8
RMS 310 LS
8
RMS 310 LSI
Pilot light
RMS 310 LSG Stainless Steel Flush Covers
Frames: P, J and K.
8
RMS 310 LSIG ND
3
RMS 310 LS
8
RMS 310 LSI
Assembled Enclosed Circuit Breakers
RMS 310 LSG
Accessories
RMS 310 LSIG Auxiliary switches
(specify voltage and Hz)
Modifications
a
b
Shunt trips
(specify voltage and Hz)
Breaker Frame
Description
G, F, J, K, L, M, N
1A, 1B
G, F, J, K, L, M, N
2A, 2B
K, L, M, N
3A, 3B
R
1A, 1B
G, F, J, K, L, M, N, R
—
RD
3
8
8
RMS 310 LS
RMS 310 LSI
8
RMS 310 LSG
RMS 310 LSIG
8
RMS 510 LS RMS 610 LS ST
8
RMS 810 LS a
8
RMS 910 LS Alarm switches
(specify voltage and Hz)
Make
G, F, J, K, L, M, N
1 Make, 1 Break
F, K, L, M, N
2 Make, 2 Break
G, F, J, K, L, M, N, R
—
Break
Undervoltage release
(specify voltage and Hz)
Notes
Ground fault application not available with NEMA 7/9. Contact Eaton’s Customer
Support Center.
Add to the appropriate RD RMS 310 adder.
8
8
8
ST
8
8
8
8
8
8
8
8
8
8
8
Volume 2—Commercial Distribution
CA08100003E—February 2011
www.eaton.com
For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616
111
8.2
8
8
Switching Devices
Enclosed Circuit Breakers
Raintight Hubs
Modifications
All rainproof enclosures 30–400A are shipped with plate over
cutout. Hubs are not supplied with screws on 30–400A
enclosures. Use screws from plate.
Allowable accessory combinations can be reviewed in Eaton’s
Circuit Breaker Product Guide: PG.74.A.01.T.E. Verify final
application with the Customer Support Center.
8
Special RD Modifications and Accessories
Raintight Tubs
Raintight Hubs
8
Hub Diameter
Hubs
8
Inches
mm
Catalog
Number
For use with RGDN and RFDN
8
8
0.75
19.1
DS075H1
2500 ampere neutral assembly (aluminum)
1.00
25.4
DS100H1
1600 ampere neutral assembly (copper)
1.25
31.8
DS125H1
2000 ampere neutral assembly (copper)
1.50
38.1
DS150H1
2500 ampere neutral assembly (copper)
2.00
50.8
DS200H1
Adjustable rating plug
2.00
50.8
DS200H2
Key interlock
2.50
63.5
DS250H2
Phase failure protection (includes shunt trip)
3.00
76.2
DS300H2
Zero sequence gfp (including shunt trip and test panel)
DS900AP
NEMA 3R flat roof
Lockoff, padlockable
Large
8
For use with RJDN.
RKDN has two cutouts
8
Required if using small DS hubs on
RJDN and RKDN enclosures.
8
Heater package (includes cpt, heater, thermostat and disconnect)
8
8
8
8
8
Special sized enclosures
Standard is 90-inch H x 30-inch W x 30-inch D (2286 x 762 x 762 mm)
Breather and Drain, Hazardous Enclosures
IQ metering
A Universal Breather/Drain Fitting is installed in the top of an
enclosure to provide ventilation to minimize condensation and in
the bottom to allow drainage of accumulated condensation while
maintaining explosion-proof integrity.
Compliance
Conduit
Opening
NEMA 7
NEMA 9
BD
Class I, Groups C, D; Class I,
Zone 1, Group IIB
Class II, Groups 1/2
F, G
XPBD2
DBB
Class I, Groups B, C, D; Class I,
Zone 1, Group IIB + Hydrogen
Class II, Groups 1/2
E, F, G
XPDBB50
8
Neutral Kits, Insulated and Groundable
8
Maximum Enclosure
Rating (A)
Main Lug Size
Cu/Al
Ground Lug Size
Cu/Al
Catalog
Number
8
100
SFDN100
RFDN100
(1) 14–1/0
(1) 14–2
DH100NK
8
100
(all others)
(1) 14–1/0
(1) 14–1/0
INK100
250
(1) 4–350 kcmil
(1) 4–300 kcmil
INK250
8
400
(1) 4–600 kcmil or
(2) 1/0–250 kcmil
(1) 4–300 kcmil
INK400
8
600
(2) 250–500 kcmil
(1) 4–300 kcmil
INK600
1200
3/0–750 kcmil
(1) #6–250 kcmil
DS800NK
8
Non-standard terminations
Catalog
Number
Type
8
8
1600 ampere neutral assembly (aluminum)
2000 ampere neutral assembly (aluminum)
Small
8
Description
8
8
8
8
8
112
Volume 2—Commercial Distribution
CA08100003E—February 2011
www.eaton.com
For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616
8.2
Switching Devices
Enclosed Circuit Breakers
Flex Center
8
Introduction
Satellite Plants
The Safety Switch Flex
Center is a special facility
at the site of our Cleveland,
Tennessee, plant that is
dedicated to providing
customized enclosed
circuit breakers that meet
customers’ challenging
applications.
Atlanta
7000 Highlands Parkway SE
#102
Smyrna, GA 30082
Fax (770) 433-1863
Phone (678) 309-4260
Denver
14101 East 33rd Place
Suite F
Aurora, CO 80011
Fax (303) 371-4175
Phone (303) 371-7844
Baltimore
6671 Santa Barbara Court
Suite A
Elk Ridge, MD 21075
Fax (410) 796-7755
Phone (410) 796-7777
Hartford
625 Day Hill Road
Windsor, CT 06095
Fax (860) 688-4982
Phone (860) 688-5330
Phoenix
921 South Park Lane
Suite 1
Tempe, AZ 85281-5119
Fax (480) 449-4223
Phone (480) 449-4222
Houston
10810 West Little York
Suite 100
Houston, TX 77041
Fax (713) 688-3764
Phone (713) 688-8430
Raleigh
2933 S. Miami Blvd.
Suite 111
Durham, NC 27703
Fax (919) 572-9751
Phone (919) 544-7074
Los Angeles
5590 Jurupa Street
Ontario, CA 91761
Fax (909) 390-8884
Phone (909) 390-8853
St. Louis
12947 Gravois Road
St. Louis, MO 63127
Fax (314) 842-2552
Phone (314) 842-7797
New Jersey
96 Stemmers Lane
Westampton, NJ 08060
Fax (609) 835-4777
Phone (609) 835-4230
San Francisco
20923 Cabot Boulevard
Hayward, CA 94545
Fax (510) 784-8980
Phone (510) 784-8981
The Flex Center is a
solutions center that
provides real value:
●
●
●
●
●
●
A dedicated and
knowledgeable
engineering/
manufacturing/customer
service team to meet
your needs
A production facility
stocked with a full arsenal
of equipment to get the
job done
The industry’s shortest
lead-time
Easy ordering through
our distributors
Factory-installed
modifications include
(but are not limited to)
the following:
●
Special size enclosure
●
Special nameplates
●
Stainless steel flush
cover
●
Special paint
●
Lock-on provisions
●
Neutral assemblies—
factory installed
●
Equipment ground
lugs—factory installed
●
Cover control (pilot
lights, pushbuttons,
selector switches, etc.)
●
Factory-installed
G-Frame breakers
For application, availability
or pricing questions,
contact the Safety
Switch Flex Center
at 1-888-329-9272
Chicago
959 AEC Drive
Wood Dale, IL 60191
Fax (630) 860-3569
Phone (630) 860-3500
Cleveland
5565 Venture Drive
Unit B
Parma, OH 44130
Fax (216) 433-0545
Phone (216) 433-0616
Dallas
631 Westport Pkwy
Suite 100
Grapevine, TX 76051
Fax (817) 251-6249
Phone (817) 251-6797
8
Orlando
3827 St. Valentine Way
Orlando, FL 32811
Fax (407) 841-9135
Phone (407) 843-3863
8
8
8
8
8
8
8
8
8
8
8
8
8
Seattle
18657 72nd Avenue S.
Kent, WA 98032
Fax (425) 251-0079
Phone (425) 251-9081
8
8
8
Satellite Service Locations
8
•
8
SEATTLE
CHICAGO
•
•
DENVER
•
SAN FRANCISCO
CLEVELAND
•
•
ST. LOUIS
•
•
•
8
NE
EW JERSEY
8
BALTIMORE
L
RALEIGH
8
SUMTER
LOS ANGELES
A
ATLANT
TA
•
8
•
HARTFORD
•
GRAND PRAIRIE
PHOENIX
DALLAS
•★
•
•
★
8
HOUSTON
•
8
OR
RLANDO
8
8
8
8
Volume 2—Commercial Distribution
CA08100003E—February 2011
www.eaton.com
For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616
113
8.2
8
8
8
8
8
Switching Devices
Enclosed Circuit Breakers
Technical Data and Specifications
Industrial Circuit Breaker Selection
Circuit
Breaker
Type
Continuous
Ampere
Rating
at 40°C
UL Listed Interrupting Rating rms Symmetrical Amperes
Number
of
Poles
Vac
Vdc
Type of
Trip Federal
Spec.
W-C-375b
Vdc Ratings Vac Ratings
120
120/240
240
277
480
600
125
250
125/250
G-Frame
GHC
15–100
1
120
125
N.I.T.U.
12c, 13a
65,000
—
—
—
—
—
14,000
—
—
8
GHC
15–100
2, 3
240
125/250
N.I.T.U.
13b
—
—
65,000
—
—
—
—
—
14,000
GHC
15–100
1
277
125
N.I.T.U.
12c, 13a
—
—
—
14,000
—
—
14,000
—
—
8
GHC
15–100
2, 3
277/480
215/250
N.I.T.U.
13b
—
—
—
14,000
14,000
—
—
—
14,000
GD
15–100
3
480
250
N.I.T.U.
13b
—
—
65,000
—
22,000
—
—
10,000
—
ED
100–225
2, 3
240
125
N.I.T.U.
12b
—
—
65,000
—
—
—
10,000
—
—
EDH
100–225
2, 3
240
125
N.I.T.U.
14b
—
—
100,000
—
—
—
10,000
—
—
8
EDC
100–225
2, 3
240
125
N.I.T.U.
1
—
—
200,000
—
—
—
10,000
—
—
EHD
15–100
1
277
125
N.I.T.U.
13a
—
—
—
14,000
—
—
10,000
—
—
8
EHD
15–100
2, 3
480
250
N.I.T.U.
13b
—
—
18,000
—
14,000
—
—
10,000
—
8
8
F-Frame
FDB
15–150
2, 3
600
250
N.I.T.U.
18a
—
—
18,000
—
14,000
14,000
—
10,000
—
FDB
15–150
4
600
250
N.I.T.U.
—
—
18,000
—
14,000
14,000
—
10,000
—
FD
15–225
1
277
125
N.I.T.U.
13a
—
—
—
25,000
—
—
10,000
—
—
FD
15–225
2, 3
600
250
N.I.T.U.
22a
—
—
65,000
—
25,000
18,000
—
10,000
—
8
FD
15–225
4
600
250
N.I.T.U.
—
—
65,000
—
25,000
18,000
—
10,000
—
HFD
15–225
1
277
125
N.I.T.U.
13a
—
—
—
65,000
—
—
10,000
—
—
8
HFD
15–225
2, 3
600
250
N.I.T.U.
22a
—
—
100,000
—
65,000
25,000
—
20,000
—
HFD
15–225
4
600
250
N.I.T.U.
—
—
100,000
—
65,000
25,000
—
20,000
—
FDC
15–225 2, 3
600
250
N.I.T.U.
24a
—
—
200,000
—
100,000
35,000
—
20,000
—
FDC
15–225
4
600
250
N.I.T.U.
—
—
200,000
—
100,000
35,000
—
20,000
—
—
8
8
8
8
8
8
8
J-Frame
JDB
70–250
2, 3
600
250
N.I.T.U.
22a
—
—
65,000
—
35,000
18,000
—
10,000
JD
70–250
2, 3, 4
600
250
I.T.U.
22a
—
—
65,000
—
35,000
18,000
—
10,000
—
HJD
70–250
2, 3, 4
600
250
I.T.U.
22a
—
—
100,000
—
65,000
25,000
—
22,000
—
JDC
70–250
2, 3, 4
600
250
I.T.U.
22a
—
—
200,000
—
100,000
35,000
—
22,000
—
K-Frame
8
DK
250–400
2, 3
240
250
N.I.T.U.
14b
—
—
65,000
—
—
—
—
10,000
—
KDB
100–400
2, 3
600
250
N.I.T.U.
23a
—
—
65,000
—
35,000
25,000
—
10,000
—
8
KD
100–400
2, 3, 4
600
250
I.T.U.
23a
—
—
65,000
—
35,000
25,000
—
10,000
—
HKD
100–400
2, 3, 4
600
250
I.T.U.
23a
—
—
100,000
—
65,000
35,000
—
22,000
—
KDC
100–400
2, 3, 4
600
250
I.T.U.
23a
—
—
200,000
—
100,000
50,000
—
22,000
—
LGE
250–600
3, 4
600
250
I.T.U.
23a
—
—
65,000
—
35,000
18,000
—
22,000
—
LGS
250–600
3, 4
600
250
I.T.U.
23a
—
—
85,000
—
50,000
25,000
—
22,000
—
LGH
250–600
3, 4
600
250
I.T.U.
23a
—
—
100,000
—
65,000
35,000
—
42,000
—
8
8
8
8
8
8
LG-Frame
Notes
N.I.T.U. is non-interchangeable trip unit and I.T.U. is interchangeable trip unit.
Two-pole circuit breaker, or two poles of three-pole circuit breaker at 250 Vdc.
Not defined in W-C-375b.
Not suitable for use with 100A enclosures.
8
8
114
Volume 2—Commercial Distribution
CA08100003E—February 2011
www.eaton.com
For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616
8.2
Switching Devices
Enclosed Circuit Breakers
Industrial Circuit Breaker Selection, continued
Circuit
Breaker
Type
Continuous
Ampere
Rating
at 40°C
Number
of
Poles
Vac
Vdc
300–600
2, 3
600
300–600
2, 3, 4
300–600
2, 3, 4
8
UL Listed Interrupting Rating rms Symmetrical Amperes
Type of
Trip Federal
Spec.
W-C-375b
Vac Ratings
120
120/240
240
277
480
600
125
250
125/250
250
N.I.T.U.
23a
—
—
65,000
—
35,000
25,000
—
22,000
—
600
250
I.T.U.
23a
—
—
65,000
—
35,000
25,000
—
22,000
—
600
250
I.T.U.
23a
—
—
100,000
—
65,000
35,000
—
25,000
—
8
8
Vdc Ratings
8
L-Frame
LDB
LD
HLD
8
M-Frame
MDL
300–800
2, 3
600
250
I.T.U.
23a
—
—
65,000
—
50,000
25,000
—
22,000
—
HMDL 300–800
2, 3
600
250
I.T.U.
23a
—
—
100,000
—
65,000
35,000
—
25,000
—
ND
600–1200
3, 4
600
—
N.I.T.U.
23a
—
—
65,000
—
50,000
25,000
—
—
HND 600–1200
3, 4
600
—
N.I.T.U.
23a
—
—
100,000
—
65,000
35,000
—
—
800–2500
3, 4
600
—
N.I.T.U.
24a
—
—
125,000
—
65,000
35,000
—
—
8
N-Frame
8
R-Frame
RD
8
8
—
8
Notes
N.I.T.U. is non-interchangeable trip unit and I.T.U. is interchangeable trip unit.
Two-pole circuit breaker, or two poles of three-pole circuit breaker at 250 Vdc.
HLD: NEMA 1 enclosed: 240 Vac = 100 kA, 480 Vac = 65 kA, 600 Vac = 35 kA, 250 Vdc = 20 kA, 500 Vdc = 25 kA.
NEMA 3R enclosed: 240 Vac = 65 kA, 480 Vac = 50 kA, 600 Vac = 25 kA, 250 Vdc = 20 kA, 500 Vdc = 25 kA.
HMDL and HND: NEMA 1 and 3R enclosed: 240 Vac = 100 kA, 480 Vac = 65 kA, 600 Vac = 35 kA, 250 Vdc = 30 kA, 500 Vdc = 30 kA.
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
Volume 2—Commercial Distribution
CA08100003E—February 2011
www.eaton.com
For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616
115
8.2
Switching Devices
Enclosed Circuit Breakers
8
Dimensions
8
NEMA 1, 12, 12K, 3R
8
Approximate Dimensions in Inches (mm)
Note:þNot to be used for construction purposes unless approved.
8
NEMA 1 Surface Mounted
8
Frame
Maximum
Amperes
A
G
100
17.50 (444.5)
8.56 (217.4)
6.28 (159.5)
13.03 (331.0)
F
100
19.13 (485.9)
9.13 (231.9) 5.20 (132.1)
17.00 (431.8)
8
Earth leakage
100
23.25 (590.6)
8.56 (217.4)
6.28 (159.5)
18.75 (476.3)
F
225
23.25 (590.6)
8.56 (217.4)
6.28 (159.5)
8
J
250
34.70 (881.4)
10.92 (277.4)
7.20 (182.9)
K
400
38.81 (985.8)
11.06 (280.9)
10.94 (277.9)
LG
600
51.06 (1296.9)
21.87 (555.5)
Earth leakage
600
51.06 (1296.9)
21.87 (555.5)
8
8
8
B
F
Approximate Weight
in Lbs (kg)
1.20 (30.5)
17.19 (436.6)
12 (5)
N/A 18.81 (477.8)
13 (6)
1.20 (30.5)
22.94 (582.7)
15 (7)
18.75 (476.3)
1.20 (30.5)
22.94 (582.7)
15 (7)
30.00 (762.0)
1.88 (47.8)
34.39 (873.5)
31 (14)
34.00 (863.6)
9.28 (235.7)
38.50 (977.9)
53 (24)
9.96 (253.0)
51.63 (1311.5)
1.94 (49.3)
50.13 (1273.3)
90 (41)
9.96 (253.0)
51.63 (1311.5)
1.94 (49.3)
50.13 (1273.3)
90 (41)
C
D
E
L
600
45.88 (1165.4)
14.31 (363.5)
12.38 (314.5)
46.56 (1182.6)
1.91 (48.5)
45.56 (1157.2)
81 (37)
8
M, N
1200
61.22 (1555.0)
21.44 (544.6)
15.41 (391.4)
61.84 (1570.7)
1.97 (50.0)
60.91 (1547.1)
178 (81)
8
NEMA 1 Surface Mounted
E
8
C
B
8
8
8
D
A
F
8
8
8
8
8
Notes
SFDN100 Series “B” released 9/15/01.
Maximum wire size: 4/0.
Total width, including door clip is 9.95 inches (253 mm).
Single centered mounting hole provided.
Maximum wire size: 500 kcmil.
8
8
8
8
8
8
8
8
8
116
Volume 2—Commercial Distribution
CA08100003E—February 2011
www.eaton.com
For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616
8.2
Switching Devices
Enclosed Circuit Breakers
Approximate Dimensions in Inches (mm)
8
NEMA 1 Flush Mounted
Frame
Maximum
Amperes
A
B
C
D
E
F
Approximate Weight
in Lbs (kg)
F
100
18.81 (477.8)
9.72 (246.9)
6.28 (159.5)
13.03 (331.0)
1.86 (47.2)
18.50 (469.9)
12 (5)
Earth leakage
100
24.56 (623.8)
9.72 (246.9)
6.28 (159.5)
18.75 (476.3)
1.86 (47.2)
24.25 (616.0)
15 (7)
F
225
24.56 (623.8)
9.72 (246.9)
6.28 (159.5)
18.75 (476.3)
1.86 (47.2)
24.25 (616.0)
15 (7)
J
250
36.02 (914.9)
12.23 (310.6)
7.20 (182.9)
30.00 (762.0)
1.88 (47.8)
35.70 (906.8)
32 (15)
K
400
40.13 (1019.3)
12.38 (314.5)
10.94 (277.9)
34.00 (863.6)
2.94 (74.7)
39.81 (1011.2)
53 (24)
8
8
8
8
8
NEMA 1 Flush Mounted
8
E
8
C
B
8
8
F
A
D
8
8
8
8
NEMA 1 Surface Mounted SFDN100 Series “B”
8
8
9.95 (252.7)
NEED ART
1.84
(46.7)
1.78
(45.2)
9.13 (232.0)
DWG...95-1562
18.81
(478.0)
0.71
(18.0)
2.13
(54.1)
1.91
(48.5)
FROM
17.00
MARK SCHMIDT
(431.8)
1.91
(48.5)
0.27 (6.8) Diameter
3 Mounting Holes
1.78
(45.2)
4.23
(107.4)
5.20
(132.0)
0.81
(20.6)
7.25
(184.1)
8
1.84
(46.7)
19.12
(485.6)
1.84
(46.7)
8
0.38
(9.7)
8
Concentric Knockouts
for 1, 1-1/4, 1-1/2
(25.4, 31.8, 38.1)
2 Conduit
Quantity: 10
8
8
8
1.84
(46.7)
8
3.50 (89.0)
1.91
(48.5)
8
0.69
(17.5)
8.82
(224.0)
8
0.281 (7.1) Diameter
Knockout Quantity: 2
8
Notes
Maximum wire size: 4/0.
Maximum wire size: 500 kcmil.
8
8
8
8
Volume 2—Commercial Distribution
CA08100003E—February 2011
www.eaton.com
For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616
117
8.2
Switching Devices
Enclosed Circuit Breakers
8
Approximate Dimensions in Inches (mm)
8
NEMA 12, 12K Dustproof
8
Maximum
Amperes
Frame
A
B
C
D
E
Approximate Weight
in Lbs (kg)
G, F
100
19.91 (505.7)
9.16 (232.7)
9.31 (236.5)
18.53 (470.7)
1.70 (43.2)
16 (7)
8
Earth leakage
100
19.91 (505.7)
9.16 (232.7)
9.31 (236.5)
18.53 (470.7)
1.70 (43.2)
19 (9)
FBP, FCL
100
25.66 (651.8)
9.16 (232.7)
9.31 (236.5)
24.28 (616.7)
1.70 (43.2)
19 (9)
8
F
225
25.66 (651.8)
9.16 (232.7)
9.31 (236.5)
24.28 (616.7)
1.70 (43.2)
19 (9)
J
250
37.53 (953.3)
11.88 (301.8)
10.22 (259.6)
35.77 (908.6)
1.94 (49.3)
37 (17)
8
K
400
41.69 (1058.9)
12.31 (312.7)
14.06 (357.1)
39.94 (1014.5)
1.97 (50.0)
58 (26)
8
LG
600
53.37 (1355.6)
23.06 (585.7)
14.10 (358.1)
51.63 (1311.4)
1.94 (49.3)
94 (43)
Earth leakage
600
53.37 (1355.6)
23.06 (585.7)
14.10 (358.1)
51.63 (1311.4)
1.94 (49.3)
94 (43)
8
L
600
48.31 (1227.1)
15.56 (395.2)
15.50 (393.7)
46.56 (1182.6)
1.92 (48.8)
84 (38)
NBP
800
63.59 (1615.2)
22.63 (574.8)
17.63 (447.8)
—
—
110 (50)
M, N
1200
63.59 (1615.2)
22.63 (574.8)
17.63 (447.8)
61.84 (1570.7)
1.97 (50.0)
175 (80)
8
8
G, F
100
19.91 (505.7)
9.16 (232.7)
9.31 (236.5)
—
—
16 (7)
Earth leakage
100
19.91 (505.7)
9.16 (232.7)
9.31 (236.5)
—
—
19 (9)
8
FBP, FCL
100
25.66 (651.8)
9.16 (232.7)
9.31 (236.5)
—
—
19 (9)
F
225
25.66 (651.8)
9.16 (232.7)
9.31 (236.5)
—
—
19 (9)
8
J
250
37.53 (953.3)
11.88 (301.8)
10.22 (259.6)
—
—
37 (17)
K
400
41.69 (1058.9)
12.31 (312.7)
14.06 (357.1)
—
—
58 (26)
8
8
NEMA 12, 12K Dustproof
C
8
8
8
A D
8
8
8
Notes
Maximum wire size: 4/0.
Maximum wire size: 500 kcmil.
8
8
8
8
8
8
8
8
8
8
118
Volume 2—Commercial Distribution
CA08100003E—February 2011
www.eaton.com
For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616
8.2
Switching Devices
Enclosed Circuit Breakers
Approximate Dimensions in Inches (mm)
8
NEMA 3R Rainproof
Frame
Maximum
Amperes
A
B
C
D
E
Approximate Weight
in Lbs (kg)
G, F 100
19.91 (505.7)
9.16 (232.7)
9.31 (236.5)
18.53 (470.7)
1.70 (43.2) 16 (7)
Earth leakage
100
19.91 (505.7)
9.19 (232.7)
9.31 (236.5)
18.53 (470.7)
1.70 (43.2)
19 (9)
FBP, FCL
100
25.66 (651.8)
9.16 (232.7)
9.31 (236.5)
24.28 (616.7)
1.70 (43.2)
19 (9)
F
225
25.66 (651.8)
9.16 (232.7)
9.31 (236.5)
24.28 (616.7)
1.70 (43.2)
19 (9)
J
250
37.50 (952.5)
11.88 (301.8)
10.22 (259.6)
35.77 (908.6)
1.94 (49.3)
37 (17)
K
400
41.69 (1058.9)
12.31 (312.7)
14.06 (357.1)
39.94 (1014.5)
1.97 (50.0)
58 (26)
LG
600
53.37 (1355.6)
23.06 (585.7)
14.10 (358.1)
51.63 (1311.4)
1.94 (49.3)
94 (43)
Earth leakage
600
53.37 (1355.6)
23.06 (585.7)
14.10 (358.1)
51.63 (1311.4)
1.94 (49.3)
94 (43)
L
600
48.31 (1227.1)
15.56 (395.2)
15.50 (393.7)
46.56 (1182.6)
1.92 (48.8)
84 (38)
M, N
1200
63.59 (1615.2)
22.63 (574.8)
17.63 (447.8)
61.84 (1570.7)
1.97 (50.0)
175 (80)
8
8
8
8
8
8
8
8
NEMA 3R Rainproof
E
8
C
8
8
ON
A
D
OFF
F
8
8
B
8
NEMA 3R Rainproof RFDN100 Series “B”
8
8
NEED ART
8
9.95 (252.7)
0.71
(18.0)
DWG...95-1562
8
FROM
17.00
MARK SCHMIDT
(431.8)
8
9.13 (232.0)
18.81
(478.0)
1.84
(46.7)
1.91
(48.5)
1.78
(45.2)
0.81
(20.6)
4.23
(107.4)
5.20
(132.0)
0.27 (6.8) Diameter
3 Mounting Holes
7.25
(184.0)
0.38
(9.7)
8
Concentric Knockouts
for 1, 1-1/4, 1-1/2
(25.4, 31.8, 38.1)
2 Conduit
Quantity: 5
19.12
(485.6)
19.27
(489.4)
8
8
1.91
(48.5)
8
1.84
(46.7)
8
3.50 (89.0)
8
1.91
(48.5)
0.69
(17.5)
8.82
(224.0)
8
0.281 (7.1) Diameter
Knockout Quantity: 2
8
Notes
RFDN100 Series “B” released 9/15/01.
Single centered mounting hole provided on RFDN100, Series “B.”
Maximum wire size: 4/0.
Maximum wire size: 500 kcmil.
Volume 2—Commercial Distribution
8
8
CA08100003E—February 2011
www.eaton.com
For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616
119
8.2
8
8
8
8
8
8
8
8
8
8
8
Switching Devices
Enclosed Circuit Breakers
Approximate Dimensions in Inches (mm)
NEMA 4/4X, 5, 7/9
Note:þNot to be used for construction purposes unless approved.
NEMA 4/4X, 5 Stainless Steel
Maximum
Amperes
Frame
A
B
C
D
E
Approximate Weight
in Lbs (kg)
16 (7)
G, F
100
19.91 (505.7)
8.84 (224.5)
9.31 (236.5)
18.53 (470.7)
1.70 (43.2)
Earth leakage
100
19.91 (505.7)
8.84 (224.5)
9.31 (236.5)
18.53 (470.7)
1.70 (43.2)
20 (9)
FBP, FCL
100
25.66 (651.8)
8.84 (224.5)
9.31 (236.5)
24.28 (616.7)
1.70 (43.2)
20 (9)
20 (9)
F
225
25.66 (651.8)
8.84 (224.5)
9.31 (236.5)
24.28 (616.7)
1.70 (43.2)
J
250
37.50 (952.5)
11.56 (293.6)
10.22 (259.6)
35.77 (908.6)
1.94 (49.3)
39 (18)
K
400
41.69 (1058.9)
11.75 (298.5)
14.06 (357.1)
39.94 (1014.5)
1.97 (50.0)
60 (27)
96 (44)
LG
600
53.38 (1355.9)
23.06 (585.7)
14.11 (358.4)
51.64 (1311.7)
1.94 (49.3)
Earth leakage
600
53.38 (1355.9)
23.06 (585.7)
14.11 (358.4)
51.64 (1311.7)
1.94 (49.3)
96 (44)
L
600
48.31 (1227.1)
14.91 (378.7)
15.50 (393.7)
46.56 (1182.6)
1.92 (48.8)
88 (40)
M, N
1200
63.59 (1615.2)
22.00 (558.8)
17.63 (447.8)
61.84 (1570.7)
1.97 (50.0)
185 (84)
NEMA 4/4X, 5 Stainless Steel
8
E
B
8
C
8
8
D
A
ON
OFF
8
8
8
8
Notes
Maximum wire size: 4/0.
Maximum wire size: 500 kcmil.
8
8
8
8
8
8
8
8
8
8
8
120
Volume 2—Commercial Distribution
CA08100003E—February 2011
www.eaton.com
For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616
8.2
Switching Devices
Enclosed Circuit Breakers
Approximate Dimensions in Inches (mm)
8
NEMA 7/9 Cast Aluminum with Weather-Resistant Seals—15–250A
Breaker
Size
Amperes
Number
of
Outlets
F
XFDN050B
15–50
F
XFDN100B
Mounting Inside Outside Standard
Conduit
Size Approximate
Weight in
Lbs (kg)
A
B
J
C
D
E
F
G
H
K
Dim
4
5.50
(139.7)
13.13
(333.5)
14.13
(358.9)
6.13
(155.7)
10.75
(273.1)
5.25
(133.4)
10.63
(270.0)
15.25
(387.4)
8.88
(225.6)
2.00
(50.8)
1.50
(38.1)
38 (17)
60–100
4
6.00
(152.4)
18.00
(457.2)
19.00
(482.6)
6.50
(165.1)
16.00
(406.4)
5.50
(139.7)
11.00
(279.4)
20.50
(520.7)
9.00
(228.6)
2.31
(58.7)
2.00
(50.8)
57 (26)
F
XFDN225B
125–225
4
10.25
(260.4)
22.63
(574.8)
—
11.38
(289.1)
20.00
(508.0)
6.38
(162.1)
16.38
(416.1)
25.13
(638.3)
9.63
(244.6)
3.50
(88.9)
2.50
(63.5)
104 (47)
J
XJDN225B
70–225
4
8.50
(215.9)
27.13
(689.1)
—
11.25
(285.8)
29.88
(759.0)
7.38
(187.5)
16.00
(406.4)
29.50
(749.3)
12.31
(312.7)
4.00
(101.6)
3.00
(76.2)
145 (66)
J
XJDN250B
250
4
9.50
(241.3)
27.25
(692.2)
—
11.25
(285.8)
29.88
(759.0)
8.06
(204.7)
16.38
(416.1)
35.00
(889.0)
12.38
(314.5)
4.19
(106.4)
4.00
(101.6)
170 (77)
Breaker
Frame
8
8
8
8
8
8
8
8
NEMA 7/9 Cast Aluminum with Weather-Resistant Seals—Dual Three- and Four-Point Mounting
Available as Standard on F-Frame 100A and Below
8
8
8
8
8
8
8
8
Note
Maximum wire size: 4/0.
8
8
8
8
8
8
8
8
8
8
8
8
8
Volume 2—Commercial Distribution
CA08100003E—February 2011
www.eaton.com
For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616
121
8.2
Switching Devices
Enclosed Circuit Breakers
8
Approximate Dimensions in Inches (mm)
8
7/9 Cast Aluminum with Weather-Resistant Seals—400–1200A
Breaker
Size
Amperes
Overall Enclosure
A
B
C
D
E
F
G
H
Enclosure Mounting
Conduit
Hinged Cover
Standard Conduit
I
J
Size
Location
8
Breaker
Frame
8
K
XKDN400B
400
35.00
(889.0)
16.38
(416.1)
12.63
(320.8)
7.13
(181.1)
9.50
(241.3)
27.25
(692.2)
.50
(12.7)
3.00
(76.2)
4.19
(106.4)
5.50
(139.7)
4.00
(101.6)
1, 3 and
6, 8
170 (77)
L
XLDN600B
600
37.88
(962.2)
23.88
(606.6)
14.25
(362.0)
8.25
(209.6)
16.00
(406.4)
45.38
(1152.7)
.50
(12.7)
4.00
(101.6)
5.00
(127.0)
6.00
(152.4)
4.00
(101.6)
1, 3 and
6, 8
419 (190)
M
XMCN800B
800
47.88
(1216.2)
13.63
(346.2)
12.81
(325.4)
6.81
(173.0)
16.13
(409.7)
40.75
(1035.1)
.50
(12.7)
4.00
(101.6)
4.00
(101.6)
6.00
(152.4)
4.00
(101.6)
1, 3 and
6, 8
228 (104)
N
XNDN1200B
1200
64.00
(1625.6)
26.00
(660.4)
21.38
(543.1)
14.38
(365.3)
27.56
(700.0)
38.63
(981.2)
.50
(12.7)
6.50
(165.1)
4.38
(111.3)
7.00
(177.8)
4.00
(101.6)
1, 3 and
6, 8
567 (257)
8
8
8
8
NEMA 7/9 Cast Aluminum with Weather-Resistant Seals
8
CONDUIT POSITION NO.
1
8
2 3
G-MTG.
HOLES (4)
J
8
B
F-MTG.
A
8
8
I
D
C
8
H H
8
8
8
8
8
8
8
8
Weight
Lbs (kg)
7 6
Conduit Openings
Refer to outline dimensions for size and location of standard
conduit openings. In addition, 1/2-inch (12.7 mm) openings are
drilled and tapped for breather and drain. Unless ordered with
breather and drain, these openings are plugged. Refer to Eaton
for price of breather and drain.
Notes
Maximum wire size: 500 kcmil.
Power cables must enter and leave from opposite ends (through-feed).
8
8
8
8
8
8
8
8
8
122
Volume 2—Commercial Distribution
CA08100003E—February 2011
www.eaton.com
For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616
Index
A
above, 2
ABreaker, 18
Accessories, 1, 7-8
accessory, 8
accumulated, 8
Add, 7
adder, 7
addition, 18
address, 7
Adjustable, 8
AEC, 9
akecify, 7
Al, 8
Alarm, 7
all, 8
allow, 8
Allowable, 8
Aluminum, 2, 17-18
aluminum, 2, 5-6, 8
Ampere, 5-7, 10-11
ampere, 8
Amperes, 11-18
AmperesCircuit, 10
an, 7-8
and, 1-2, 5-11, 17-18
ANGELES, 9
Angeles, 9
apartment, 1
applicable, 1
Application, 1
application, 1-2, 7-9
applications, 1, 9
Applied, 7
appropriate, 7
approved, 12, 16
Approxi, 13
Approximat, 15
Approximate, 12-18
APRJDN, 8
arcing, 2
are, 1-2, 6-9, 18
areas, 1
ARK, 15
arsenal, 9
ART, 15
as, 1-2, 17
Assembled, 7
Assemblies, 7
assemblies, 9
assembly, 2, 8
at, 1-18
ATLANTA, 9
Atlanta, 9
atmosphere, 2
atmospheres, 2
Aurora, 9
authorized, 7
Auxiliary, 7
availability, 9
Available, 17
available, 1-2, 7
Avenue, 9
AWK, 3-4
AZ, 9
Index
B
Baltimore, 9
BALTIMORErame, 9
Barbara, 9
Base, 5
BD, 8
be, 1, 5-8, 12, 16
Before, 7
begin, 7
being, 1
Below, 17
Benefits, 1-2
Blvd, 9
borax, 1
Both, 1
bottom, 8
Boulevard, 9
Break, 7
Breake, 17
Breaker, 3-8, 10-11, 17-18
breaker, 1-2, 5, 10-11
Breakers, 1-18
breakers, 1, 6, 9
BreakersELFD, 6
Breather, 8
breather, 18
breweries, 1
buildings, 1
but, 9
by, 1-2
C
CA, 1-18
cables, 18
Cabot, 9
call, 1-18
Can, 5-6
can, 1, 7-8
capable, 1
Cast, 2, 17-18
cast, 2, 5-6
Catalog, 3-6, 8
CatalogRating, 8
Center, 1, 7-9
center, 1, 9
centered, 12, 15
Certifications, 1-2
challenging, 9
CHICAGO, 9
Chicago, 9
Circuit, 1-18
circuit, 1-2, 5-6, 9-11
circuits, 1
Class, 2, 5-6, 8
CLEVELAND, 9
Cleveland, 9
clip, 12
close, 1
CO, 9
com, 1-18
combinations, 8
Commercial, 1-18
commercial, 1
Competitive, 3-4
Complete, 7
Compliance, 8
compliant, 2
Concentric, 13, 15
condensation, 8
conditions, 2
CONDUIT, 18
Conduit, 8, 13, 15, 17-18
conduit, 18
construction, 7, 12, 16
Contact, 7
contact, 9
Contents, 1
continued, 6, 11
continuedCatalog, 4
Continuo, 11
Continuous, 10
control, 9
converted, 5-6
coolant, 2
copper, 8
Court, 9
Cover, 9, 18
cover, 2, 9
Covers, 7
cpt, 8
Cross, 1, 3
CS, 3-4
CSA, 2
CT, 9
Cu, 8
Customer, 7-8
customer, 9
Index
customers, 9
customized, 9
cutout, 8
cutouts, 8
D
DA, 16
dairies, 1
Dale, 9
DALLAS, 9
Dallas, 9
Data, 1, 10
data, 5
Day, 9
DBB, 8
dedicated, 9
defined, 10
Delivery, 1-18
DENVER, 9
Denver, 9
Description, 1, 7
Descriptionameter, 8
design, 2
designed, 1-2
determine, 5
device, 1
Devices, 1-18
DFDN, 3, 5-6
DGDN, 3, 5
DH, 8
Di, 8
Diameter, 13, 15
Dim, 17
dimensional, 5
Dimensions, 1, 12-18
dimensions, 18
DimensionsApproximate, 12
disconnect, 1, 8
Distribution, 1-18
distributors, 9
DJDN, 3, 5
DK, 6, 10
DKDN, 4, 6
done, 9
door, 1-2, 12
Drain, 8
drain, 18
drainage, 8
Dri, 9
drilled, 18
Drive, 9
DS, 3-4, 8
Dual, 17
Durham, 9
dust, 2
Dustproof, 1-2, 14
dustproof, 1
DWG, 13, 15
E
EA, 3
Ea, 15
Earth, 6, 12-16
ease, 2
East, 9
Easy, 9
Eaton, 3-4, 7-8, 18
eaton, 1-18
EB, 3
EC, 3
ED, 3-5, 10
EDC, 5, 10
EDH, 5, 10
EE, 4
EHB, 3
EHD, 3, 5, 10
Electric, 3
ElectricRating, 4
Electronic, 7
ELFDC, 6
ELHFD, 6
Elk, 9
ELLBN, 6
employs, 1
Encl, 2
Enclosed, 1-18
enclosed, 1, 9, 11
Enclosure, 3-8, 18
enclosure, 1-2, 5, 8-9
Enclosures, 8
enclosures, 1-2, 8, 10
enclosuresStandard, 8
ends, 18
engineering, 9
Index
enter, 18
entrance, 1-2
Equipment, 9
equipment, 9
etc, 9
exist, 2
Explosion, 2
explosion, 8
F
FA, 3
facility, 9
Factory, 9
factory, 2, 9
failure, 8
FAL, 3
fault, 7
Fax, 9
FBP, 14-16
FCL, 14-16
FD, 3, 5, 10
FDB, 3, 5, 10
FDC, 5, 10
Features, 1-2
February, 1-18
Federal, 10-11
feed, 4, 18
feeder, 1
FFD, 6
FFDN, 3, 5
field, 5-6
File, 2
final, 8
Finish, 7
Fitting, 8
FJDN, 3, 5
FKDN, 4, 6
FL, 9
flanged, 2
flat, 8
Flex, 1, 7, 9
Flush, 1, 7, 13
flush, 1-6, 9
following, 7, 9
For, 1-18
for, 1-2, 5-6, 10, 12-13, 15-16, 18
foreign, 2
Four, 17
Frame, 5-7, 10-11, 13-17
FrameLGE, 10
Frames, 7
FRANCISCO, 9
Francisco, 9
FROM, 13, 15
from, 1-2, 8, 18
Front, 2
front, 1
full, 9
Functions, 1-2
FXD, 3
G
GA, 9
GD, 5, 10
General, 1-4
general, 1
get, 9
gfp, 8
GHC, 3, 5, 10
GHCGFEP, 5
GRAND, 9
Grapevine, 9
Gravois, 9
Ground, 7-8
ground, 9
Groundable, 8
Group, 2, 8
Groups, 2, 8
Guide, 8
H
handle, 1-2
HARTFORD, 9
Hartford, 9
has, 1, 8
have, 2
Hayward, 9
Hazardous, 2, 8
Heater, 8
Index
heater, 8
HFD, 5, 10
high, 6
Highlands, 9
Hill, 9
Hinged, 18
hinges, 2
HJD, 5, 10
HKD, 6-7, 10
HLD, 6-7, 11
HMDL, 6-7, 11
HND, 6, 11
hole, 12, 15
HOLES, 18
Holes, 13, 15
HOUSTON, 9
Houston, 9
Hub, 8
Hubs, 1, 8
hubs, 8
hubsmechanism, 2
Hydrogen, 8
Hz, 7
inside, 1-2
Installed, 7
installed, 8-9
Insulated, 8
integrity, 8
Interchangeable, 1-2
interchangeable, 10-11
Interlock, 7
interlock, 8
Interlocked, 2
interlocked, 1-2
Interlocks, 7
Interrupting, 10-11
interrupting, 6
Introduction, 9
involving, 2
IQ, 8
is, 1-2, 8-12
It, 1
J
I
IDT, 13, 15
if, 8
igniting, 2
II, 2, 8
IIB, 8
IL, 9
Immediate, 1-18
In, 18
in, 1-2, 5, 8, 10, 12-18
inch, 8, 18
Inches, 8, 12-18
inches, 12
include, 5, 9
includes, 2, 8
including, 8, 12
indoor, 1
Industrial, 10-11
industries, 1
industry, 2, 9
information, 5, 7
INK, 8
Inside, 17
JD, 5, 10
JDB, 3, 5, 10
JDC, 5, 10
JERSEY, 9
Jersey, 9
JFDN, 3, 5-6
JGDN, 3, 5
JJDN, 3, 5
JKDN, 4, 6
JLDN, 4, 6
JLG, 6
JNDN, 4, 6
Jurupa, 9
JXD, 4
K
KA, 3
kA, 11
KAL, 3
kcmil, 3-4, 8, 12-16, 18
KD, 6-7, 10
Index
KDB, 4, 6, 10
KDC, 6, 10
Kent, 9
Key, 7-8
kg, 12-18
kit, 5
Kits, 8
KMParts, 1-18
kn, 9
Knockout, 13, 15
Knockouts, 13, 15
knockouts, 1-2
known, 7
Locations, 9
Lock, 9
lock, 7
Lockoff, 8
LOS, 9
Los, 9
LOUIS, 9
Louis, 9
LR, 2
LS, 7
LSG, 7
LSI, 7
LSIG, 7
LSSeparate, 7
Lug, 7-8
lugs, 9
LXD, 4
L
LA, 4
Laboratories, 1-2
LAL, 4
Lane, 9
Large, 8
Lbs, 12-18
LD, 4, 6-7, 11
LDB, 4, 6, 11
lead, 9
Leakage, 6
leakage, 12-16
leave, 18
legend, 7
LG, 10, 12, 14-16
LGE, 6
LGH, 6, 10
LGS, 6, 10
Li, 11
li, 9
lift, 2
Light, 7
light, 7
lights, 9
limited, 6
line, 2
Listed, 10
listed, 1-2
Little, 9
LMD, 4
Location, 2, 18
location, 2, 18
Locationare, 2
M
MA, 4
Ma, 13
machined, 2
Main, 8
main, 1
maintaining, 8
Make, 7
MAL, 4
manufacturing, 9
MARK, 13
mate, 13
materials, 2
Maxi, 15
Maximum, 3-5, 8, 12-18
MD, 9
MDL, 4, 6-7, 11
meet, 9
meets, 1
meteringA, 8
Miami, 9
mills, 1
mines, 1
minimize, 8
mited, 9
mm, 8, 12-18
MND, 4
MO, 9
Modifications, 7-8
Index
modifications, 9
ModificationsAll, 8
Mounted, 12-13
mounted, 1-2
Mounting, 1-2, 13, 15, 17-18
mounting, 5, 12, 15
MTG, 18
mum, 15
must, 7, 18
MXD, 4
N
NA, 4
NAL, 4
name, 7
nameplate, 7
Nameplates, 7
nameplates, 9
NBP, 14
NC, 9
ND, 4, 6-7, 11
nd, 9
NEED, 13, 15
needs, 9
NEMA, 1-8, 11-18
Neutral, 7-9
neutral, 8
NEW, 9
New, 9
NF, 3
NJ, 9
NK, 8
NKRFDN, 8
NO, 18
No, 2
no, 1
nockouts, 2
Non, 8
non, 10-11
Not, 10
not, 2, 7-9
Note, 2, 12, 16-17
Notes, 3-7, 10-16, 18
NRB, 3
NS, 3
Number, 3-8, 10-11, 17
number, 7
Numbers, 3-4
Numerous, 2
NXD, 4
O
ob, 9
of, 1-2, 5, 7-11, 17-18
OFF, 1-2, 15-16
off, 2
OH, 9
oil, 2
ON, 1-2, 15-16
On, 7
on, 2, 5, 8-9, 15, 17
Only, 5-6
only, 4-6
Ontario, 9
open, 1
Opening, 8
opening, 1-2
Openings, 2, 18
openings, 1, 18
operable, 1-2
operating, 1-2
operation, 7
opposite, 18
Options, 7
options, 2
or, 1-18
order, 7
ordered, 18
ordering, 9
ORLANDO, 9
Orlando, 9
osures, 2
Other, 2
other, 1-2
others, 8
our, 9
outdoor, 1
Outlets, 17
outline, 18
Outside, 17
outside, 2
over, 8
Overall, 18
owledgeable, 9
Index
P
package, 8
Padlockable, 2
padlockable, 8
padlocked, 1
padlocks, 2
Page, 1, 5-6
Pages, 5
Paint, 7
paint, 9
panel, 8
paper, 1
Park, 9
Parkway, 9
Parma, 9
particularly, 1
PG, 8
Phase, 8
PHOENIX, 9
Phoenix, 9
Phone, 9
Pilot, 7
pilot, 9
Pkwy, 9
Place, 9
plant, 9
Plants, 9
plate, 5, 8
plug, 8
plugged, 18
Point, 17
pole, 5-6, 10-11
Poles, 7, 10-11
poles, 10-11
POSITION, 18
position, 1-2
Power, 18
PRAIRIE, 9
prevent, 1-2, 7
price, 18
pricing, 9
process, 1
Product, 1, 5, 8
production, 9
proof, 2, 8
protection, 8
protective, 1
provide, 7-8
provided, 12, 15
provides, 9
providing, 9
provisions, 9
Purpose, 1-2
purpose, 1
purposes, 12, 16
pushbuttons, 9
Q
QCCBP, 5
Quantity, 13, 15
questions, 9
R
Rainproof, 1-2, 15
rainproof, 8
Raintight, 8
RALEIGH, 9
Raleigh, 9
Range, 5-6
rated, 2, 6
Rating, 3, 10-11
rating, 8
Ratings, 1-2, 10-11
ratings, 6-7
RB, 3
RD, 7-8, 11
rd, 9
real, 9
Refer, 6, 18
Reference, 1, 3
release, 7
released, 12, 15
Required, 8
required, 5, 7
requirements, 1
Resistant, 17-18
reviewed, 8
RFDN, 3, 5-6, 8, 15
RGDN, 3, 5, 8
Ridge, 9
RJDN, 3, 5, 8
Index
RKDN, 4, 6, 8
RLDN, 4, 6
RLG, 6
RMS, 7
rms, 10-11
RNDN, 4, 6
Road, 9
roof, 8
rough, 5
RT, 13
rth, 15
S
Safety, 7, 9
SAN, 9
San, 9
Santa, 9
Satellite, 9
SCH, 13, 15
scheme, 7
screws, 8
SE, 3, 9
Seals, 17-18
SEATTLE, 9
Seattle, 9
Selection, 1, 5, 10-11
selector, 9
semi, 2
sequence, 8
Series, 5-6, 12-13, 15
serve, 1
Service, 9
service, 1-2, 9
severe, 2
SF, 3
SFD, 6
SFDN, 3, 5, 8, 12-13
SG, 4
SGDN, 3, 5
sheet, 1
shipped, 8
Short, 6
shortest, 9
Shunt, 7
shunt, 8
Side, 2
Siemens, 3-4
Single, 12, 15
single, 5
site, 9
Size, 8, 17-18
size, 3-5, 9, 12-18
sized, 8
SJDN, 3, 5
SK, 4
SKDN, 4, 6
SLDN, 4, 6
SLG, 6
Small, 8
small, 8
Smyrna, 9
SNDN, 4, 6
solutions, 9
South, 9
spe, 7
Spec, 10-11
Special, 7-9
special, 2, 9
Specifications, 1, 10
specifications, 2
specify, 7
Square, 3-4
SS, 3-4
ST, 7, 9
St, 9
Stainless, 1, 7, 9, 16
stainless, 5-6
Standard, 17-18
standard, 8, 18
Standards, 1-2
sted, 11
Steel, 1, 7, 16
steel, 1, 5-6, 9
Stemmers, 9
stocked, 9
Street, 9
Suitable, 5
suitable, 1-2, 10
Suite, 9
suited, 1
SUMTER, 9
supplied, 2, 8
Support, 1-18
Surface, 1-2, 12-13
surface, 1, 3-6
Switch, 7, 9
switches, 7, 9
Switching, 1-18
Symmetrical, 10-11
system, 7
Index
Systems, 7
U
T
tapped, 18
TE, 3
team, 9
Tech, 1-18
Technical, 1, 10
TED, 3
telephone, 7
Tempe, 9
Tennessee, 9
terminations, 8
test, 8
TF, 3
TFJ, 3
Th, 9
that, 2, 9
The, 1-2, 9
the, 1-2, 5, 7-9
thermostat, 8
These, 2
these, 18
This, 1-2
Three, 17
three, 5-6, 10-11
Through, 4
through, 1-2, 5, 9, 18
tight, 2
time, 7, 9
TJ, 4
TJK, 4
TK, 4
TKMA, 4
TKV, 4
to, 1-2, 5-9, 12, 16, 18
top, 8
Total, 12
Trip, 7, 10-11
trip, 7-8, 10-11
Tubs, 8
Two, 10-11
two, 5, 8, 10-11
TX, 9
Type, 1-2, 5-8, 10-11
type, 5
UL, 2, 10-11
Undervoltage, 7
Underwriters, 1-2
Unit, 9
unit, 10-11
units, 2
Universal, 8
Unless, 18
unless, 12, 16
unusually, 2
urface, 3
us, 11
Use, 5, 8
use, 1, 5, 8, 10
used, 1, 6-7, 12, 16
User, 7
using, 8
V
Vac, 1-2, 10-11
Valentine, 9
value, 9
Vdc, 1-2, 10-11
ve, 9
ventilation, 8
Venture, 9
Verify, 8
voltage, 7
Volume, 1-18
W
WA, 9
Water, 1-2
water, 1
Way, 9
Weather, 17-18
weatherproof, 1
Index
Weight, 13-17
WeightFrame, 12, 18
well, 1
West, 9
Westampton, 9
Westport, 9
WFDN, 3, 5-6
WGDN, 3, 5
when, 1-2
where, 1-2
while, 8
wide, 2
width, 12
Windsor, 9
wire, 3-5, 12-18
witch, 9
with, 1-2, 5-10, 17-18
WJDN, 3, 5
WKDN, 4, 6
WL, 3-4
WLDN, 4, 6
WLG, 6
WNDN, 4, 6
Wood, 9
www, 1-18
X
XFDN, 3, 5, 17
ximu, 13
XJDN, 3, 5, 17
XKDN, 4, 6, 18
XLDN, 6, 18
XMCN, 4, 6, 18
XNDN, 4, 6, 18
XPBD, 8
XPDBB, 8
Y
York, 9
your, 9
Z
Zero, 8
Zone, 8
Þ
þNot, 12, 16
þXFDN, 2
Download