Switching Devices Enclosed Circuit Breakers 8.2 Contents Enclosed Circuit Breakers Description Page Features, Benefits and Functions . . . . . . . . . . . . . . . . . . . . . Standards and Certifications. . . . . . . . . . . . . . . . . . . . . . . . . Cross-Reference. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Flex Center . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Data and Specifications. . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106 106 107 109 111 113 114 116 8 8 8 8 8 8 8 8 8 8 Product Description ● ● 15–1200A Enclosed device used to open and close a circuit 8 Application Description NEMA 1 General Purpose Surface or Flush Mounting 15–1200A, 600 Vac, 500 Vdc NEMA 1 enclosed breakers are designed for indoor use in commercial buildings, apartment buildings and other areas where a general purpose enclosure is applicable. The breaker is front operable and is capable of being padlocked in the OFF position. Ratings through 1200A are listed with Underwriters Laboratories as suitable for service entrance application. Both surface and flush mounted enclosures are available. 8 NEMA 3R Rainproof Surface Mounting NEMA 4/4X, 5 Water and Dustproof Interchangeable Hubs (through 400A) 15–1200A, 600 Vac, 500 Vdc This general purpose outdoor service center employs a circuit breaker inside a weatherproof sheet steel enclosure to serve as a main disconnect and protective device for feeder circuits. The operating handle can be padlocked in the OFF position, and is interlocked to prevent the door from opening when the breaker is ON. Ratings through 1200A are listed by Underwriters Laboratories as suitable for service entrance application. Stainless Steel—Type 304 Surface Mounting 15–1200A, 600 Vac, 500 Vdc This enclosure meets NEMA 4/4X and 5 requirements for water and dustproof applications and has no knockouts or other openings. It is particularly well suited for use in dairies, borax mines, breweries, paper mills and other process industries. The operating handle can be padlocked in the OFF position, and is interlocked to prevent the door from opening when the breaker is ON. Ratings through 1200A are Underwriters Laboratories listed as suitable for service entrance application. 8 8 8 8 8 8 8 8 8 8 8 8 8 8 NEMA 1 General Purpose 8 NEMA 3R Rainproof Surface Mounting 8 8 NEMA 4/4X Water and Dustproof Volume 2—Commercial Distribution CA08100003E—February 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 105 8 8.2 8 8 8 8 8 8 8 8 8 8 8 8 8 Switching Devices Enclosed Circuit Breakers NEMA 12 Dustproof Surface Mounting NEMA 7/9 Hazardous Location No Knockouts or Other Openings 15–1200A, 600 Vac, 500 Vdc The Type 12 enclosure is designed in line with specifications for special industry application where unusually severe conditions involving oil, coolant, dust and other foreign materials exist in the operating atmosphere. The handle padlocks in the OFF position and the cover is interlocked with the handle mechanism to prevent opening the cover with the circuit breaker in the ON position. Ratings through 1200A are listed by Underwriters Laboratories as suitable for service entrance application. A NEMA 12 semi-dust-tight design that includes knockouts is available. These units are rated 15–400A, 600 Vac, 500 Vdc. Cast Aluminum, Explosion-proof Surface Mounting 15–1200A, 600 Vac, 250 Vdc Hazardous location, Type 7: Class I, Groups B, C, D; Type 9: Class II, Groups E, F, G. This special service cast aluminum enclosure is supplied with a wide, machined flanged cover to prevent igniting outside atmospheres by arcing from inside the enclosure. Front operable, the handle padlocks in the OFF position. Enclosures rated 600A and above have lift-off hinges for ease of assembly. Features, Benefits and Functions ● ● ● ● ● ● Side-opening door on NEMA 3R enclosures Padlockable in the OFF position Surface or flush mounted enclosures available through 400A on NEMA 1 enclosures Interlocked handle on NEMA 3R, 4/4X, 5 and 12 enclosures to prevent opening when the breaker is in the ON position Interchangeable hubs Numerous factory options Note:þXFDN050B is not Group B compliant. Standards and Certifications ● ● ● UL 489 CSA 22.2 NEMA 250 NEMA 1 General Purpose ● UL File No. E7819 ● CSA File No. LR84319 NEMA 3R Rainproof Surface Mounting ● UL File No. E7819 ● CSA File No. LR84319 NEMA 4/4X, 5 Water and Dustproof ● UL File No. E7819 ● CSA File No. LR84319 NEMA 12 Dustproof Surface Mounting ● UL File No. E7819 ● CSA File No. LR84319 NEMA 7/9 Hazardous Location ● UL File No. E84577 ● CSA File No. LR42131-6 8 8 NEMA 7/9 Hazardous Location 8 8 8 8 NEMA 12 Dustproof Surface Mounting 8 8 8 8 8 8 8 8 8 8 8 106 Volume 2—Commercial Distribution CA08100003E—February 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 8.2 Switching Devices Enclosed Circuit Breakers Cross-Reference 8 8 Enclosed Circuit Breaker Competitive Catalog Numbers Catalog Number Square D Siemens 8 NEMA Rating Eaton General Electric Enclosure Breaker Enclosure Breaker Enclosure Breaker Enclosure Breaker 1 surface SGDN100 GHC3100 EHB125NS EHB34100 — — — — 1 flush — — EHB125NF EHB34100 — — — — 3R RGDN100 GHC3100 EHB125NRB EHB34100 — — — — 12 JGDN100 GHC3100 — — — — — — 12K DGDN100 GHC3100 — — — — — — 4/4X WGDN100 GHC3100 — — — — — — 1 surface SFDN100 EHD3100L FA100S FAL34100 E2N1S ED43B100 TE100S TED134100WL 1 flush FFDN100 EHD3100L FA100F FAL34100 E2N1F ED43B100 TE100F TED134100WL 3R RFDN100 EHD3100L FA100RB FAL34100 E2N3R ED43B100 TE100R TED134100WL 12/3R — — FA100AWK FAL34100 — — — — 12 JFDN100 EHD3100L — — E2N12 ED43B100 TE100J/SE100J TED134100WL 12K DFDN100 EHD3100L FA100A FAL34100 E2N12 ED43B100 TE100D/ ______ TED134100WL 4/4X WFDN100 EHD3100L FA100DS FAL34100 ED6SS4 ED43B100 TE100CS/SE100CS TED134100WL 7/9 XFDN050 EHD3050L FA060X FAL34060 EA ED43B100 — — 9 — — FA060Y FAL34060 — — — — 7/9 XFDN225B FD3225L FA100X FAL34100 EB ED43B100 — — 9 — — FA100Y FAL34100 — — — — 1 surface SFDN225 FDB3150L — — E2N1S ED43B125 TE150S TED134150WL 1 flush FFDN225 FDB3150L — — E2N1F ED43B125 TE150F TED134150WL 3R RFDN225 FDB3150L — — E2N3R ED43B125 TE150R TED134150WL 12 JFDN225 FDB3150L — — E2N12 ED43B125 — — FDB3150L — — E2N12 ED43B125 — — FDB3150L — — ED6SS4 ED43B125 — — 12K DFDN225 4/4X WFDN225 7/9 XFDN225B FDB3150L — — — — — — 1 surface SFDN225 FD3225L — — — — — — 1 flush FFDN225 FD3225L — — — — — — 3R RFDN225 FD3225L — — — — — — 12 JFDN225 FD3225L — — — — — — 12K DFDN225 FD3225L — — — — — — 4/4X WFDN225 FD3225L — — — — — — 7/9 XFDN225B 1 surface SJDN250 1 flush 3R 12/3R 12 FD3225L — — — — — — JDB3250 KA225S KAL36250 F6N1S FXD63B250 TF225S TFJ236225WL FJDN250 JDB3250 KA225F KAL36250 F6N1F FXD63B250 TF225F TFJ236225WL RJDN250 JDB3250 KA225RB KAL36250 F6N3R FXD63B250 TF225R TFJ236225WL — JDB3250 KA225AWK KAL36250 — — — — JJDN250 JDB3250 — — F6N12 FXD63B250 TF225J/SF250J TFJ236225WL 12K DJDN250 JDB3250 KA225A KAL36250 F6N12 FXD63B250 ______ /SF250D TFJ236225WL 4/4X WJDN250 JDB3250 KA225DS KAL36250 FD6SS4 FXD63B250 TF225CS/SF250CS TFJ236225WL 7/9 XJDN250B — KA225X KAL36250 EC2 FXD63B250 — — 9 — — KA225Y KAL36250 — — — — 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 Notes Maximum wire size 4/0. Maximum wire size 500 kcmil. 8 8 8 Volume 2—Commercial Distribution CA08100003E—February 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 107 8.2 8 8 Switching Devices Enclosed Circuit Breakers Enclosed Circuit Breaker Competitive Catalog Numbers, continued Catalog Number Eaton NEMA Rating Square D Siemens Enclosure 1 surface SKDN400 KDB3400 LA400S LAL36400 J6N1 JXD63B400 TJ400S/SG400S TJK436400WL 1 flush FKDN400 KDB3400 LA400F LAL36400 — — TJ400F/SG400F TJK436400WL 3R RKDN400 KDB3400 LA400R LAL36400 J6N3R JXD63B400 TJ400R/SG400R TJK436400WL 12/3R — — LA400AWK LAL36400 — — — — 12 JKDN400 KDB3400 — — J6N12 JXD63B400 TJ400J/SG400J TJK436400WL 8 12K DKDN400 KDB3400 — — J6N12 JXD63B400 ______ /SG400D TJK436400WL 4/4X WKDN400 KDB3400 LA400DS LAL36400 — — TJ400CS/SG400CS TJK436400WL 8 7/9 XKDN400B KDB3400 — — EE JXD63B400 — — 1 surface SLDN600 LDB3600 MA1000S MAL36600 LD6N1 LXD63B600 TJ600S/SG600S TJK636600WL 1 flush — — MA1000F MAL36600 — — TJ600F/SG600F TJK636600WL 3R RLDN600 LDB3600 — — LD6N3R LXD63B600 TJ600R/SG600R TJK636600WL 12/3R — — MA1000AWK MAL36600 — — — — 8 12 JLDN600 LDB3600 — — LD6N12 LXD63B600 TJ600J/SG600J TJK636600WL 4/4X WLDN600 LDB3600 MA1000DS MAL36600 LD6SS4 LXD63B600 TJ600CS TJK636600WL 8 7/9 XMCN800B LDB3600 — — ED6 LXD63B600 — — 1 surface SNDN1200 MDL3800 MA1000S MAL36800 LMD1 MXD63B800 TK4V1200S TKMA836800WL 1 flush — — MA1000F MAL36800 — — TK4V1200F TKMA836800WL 3R RNDN1200 MDL3800 — — LMD3R MXD63B800 TKV41200R TKMA836800WL 12/3R — — MA1000AWK MAL36800 — — — — 8 8 8 8 8 8 8 8 8 8 8 Breaker General Electric Breaker 8 Enclosure Enclosure Breaker Enclosure Breaker 12 JNDN1200 MDL3800 — — LMD12 MXD63B800 TK4V1200J/SK1200 TKMA836800WL 4/4X WNDN1200 MDL3800 MA1000DS MAL36800 — — — — 7/9 XMCN800B MDL3800 — — — — — — 1 surface SNDN1200 ND312T33W MA1000S MAL361000 — — — — 1 flush — — MA1000F MAL361000 — — — — 3R RNDN1200 ND312T33W — — — — — — 12/3R — — MA1000AWK MAL361000 — — — — 12 JNDN1200 ND312T33W — — — — — — 4/4X WNDN1200 ND312T33W MA1000DS MAL361000 — — — — 1 surface SNDN1200 ND312T33W — — MND61 NXD63B120 TK4V1200S TKMA31200WL 12 — — — — — — TK4V1200F TKMA31200WL 3R RNDN1200 ND312T33W — — MND63 NXD63B120 TKV41200R TKMA31200WL 8 1 surface — — NA1200AWK NAL361200 — — — — 12 JNDN1200 ND312T33W — — MND612 NXD63B120 TK4V1200J/SK1200 TKMA31200WL 8 4/4X WNDN1200 ND312T33W — — — — — — 7/9 XNDN1200B ND312T33W — — — — — — 8 8 8 8 Notes Maximum wire size 500 kcmil. Through-feed only. 8 8 8 8 8 8 108 Volume 2—Commercial Distribution CA08100003E—February 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Switching Devices Enclosed Circuit Breakers 8.2 Product Selection 1. Use the data on Page 120 to determine type of enclosure required. 8 3. Pages 116 through 122 include rough-in dimensional information. 8 8 2. Use the data on Page 114 and 115 to determine circuit breaker required. 8 8 Enclosure Only Breaker Frame Breaker Ampere Range 8 Enclosure NEMA Class Catalog Number 8 8 Series C Breakers GHC, GD (two- and three-pole only) GHCGFEP (single-pole only) EHD, FD, FDB, HFD 15–100 15–100 1 surface SGDN100 3R RGDN100 12 JGDN100 12K DGDN100 4/4X, 5 stainless steel WGDN100 1 surface SFDN100 1 flush FFDN100 3R RFDN100 12 JFDN100 12K DFDN100 4/4X, 5 stainless steel WFDN100 EHD, FD, FDB 15–50 7/9 cast aluminum XFDN050B HFD, FDC 60–225 7/9 cast aluminum XFDN225B FD, FDB, HFD, ED, EDH, EDC, FDC (15–225A) 125–225 1 surface SFDN225 1 flush FFDN225 3R RFDN225 12 JFDN225 12K DFDN225 4/4X, 5 stainless steel WFDN225 JD, JDB, HJD, JDC JD, JDB, HJD, JDC 125–250 125–250 1 surface SJDN250 1 flush FJDN250 3R RJDN250 12 JJDN250 12K DJDN250 4/4X, 5 stainless steel WJDN250 7/9 cast aluminum XJDN250B 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 Notes Suitable for use with single-pole breaker. Base mounting plate kit. QCCBP required. Maximum wire size: 4/0. Can be field converted to NEMA Type 3R. 8 8 8 8 8 8 8 Volume 2—Commercial Distribution CA08100003E—February 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 109 8.2 8 Switching Devices Enclosed Circuit Breakers Enclosure Only, continued 8 Breaker Frame 8 KD, KDB, HKD, KDC, DK Breaker Ampere Range Enclosure NEMA Class Catalog Number Series C Breakers, continued 125–400 1 surface SKDN400 1 flush FKDN400 3R RKDN400 8 12 JKDN400 12K DKDN400 8 4/4X, 5 stainless steel WKDN400 8 8 KD, KDB, HKD, KDC, DK 125–400 7/9 cast aluminum XKDN400B LGE, LGS, LGH 250–600 1 surface SLG630 3R RLG630 12 JLG630 4/4X, 5 stainless steel WLG630 1 surface SLDN600 3R RLDN600 12 JLDN600 4/4X, 5 stainless steel WLDN600 7/9 cast aluminum XLDN600B 8 8 LD, LDB, HLD 300–600 8 8 8 8 MDL, HMDL 400–800 7/9 cast aluminum XMCN800B MDL, HMDL, ND, HND 400–1200 1 surface SNDN1200 3R RNDN1200 12 JNDN1200 4/4X, 5 stainless steel WNDN1200 — 7/9 cast aluminum XNDN1200B 15–100 1 surface SFD100E 1 flush FFD100E 3R RFDN100E 12 JFDN100E 12K DFDN100E 4/4X WFDN100E 1 surface SLG630E 3R RLG630 8 8 8 ND, HND Earth Leakage Breakers ELFD, ELHFD and ELFDC (three-pole only) 8 8 8 8 LGE, LGS, LGH used with ELLBN 250–600 8 8 8 12 JLG630 4/4X, 5 stainless steel WLG630 Notes Short-circuit ratings are limited for high interrupting rated breakers. Refer to Page 114. Can be field converted to NEMA Type 3R. 8 8 8 8 8 8 8 110 Volume 2—Commercial Distribution CA08100003E—February 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 8.2 Switching Devices Enclosed Circuit Breakers Accessories 8 Nameplates Applied Neutral Assemblies Installed Electronic Trip Options Customer must provide nameplate legend at the time of order. Ampere ratings: 100, 250, 400, 600, 800 and 1200. Frame Type Number of Poles Description KD, HKD 3 RMS 310 LS Key Interlock Systems Interlocks are used to prevent an authorized operation. Before system construction can begin, the following information must be known: 1. User—name, address and telephone number. 2. Complete lock scheme required. 8 8 Separate Ground Lug Installed RMS 310 LSI Ampere ratings: 100, 250, 400, 600 and 1200. RMS 310 LSIG RMS 310 LSG LD, HLD 3 Special Paint Finish 8 RMS 310 LS RMS 310 LSI Contact the Safety Switch Flex Center (1-888-329-9272). 8 RMS 310 LSG RMS 310 LSIG Pilot Light On NEMA 1 Enclosure 8 MDL, HMDL 3 8 RMS 310 LS 8 RMS 310 LSI Pilot light RMS 310 LSG Stainless Steel Flush Covers Frames: P, J and K. 8 RMS 310 LSIG ND 3 RMS 310 LS 8 RMS 310 LSI Assembled Enclosed Circuit Breakers RMS 310 LSG Accessories RMS 310 LSIG Auxiliary switches (specify voltage and Hz) Modifications a b Shunt trips (specify voltage and Hz) Breaker Frame Description G, F, J, K, L, M, N 1A, 1B G, F, J, K, L, M, N 2A, 2B K, L, M, N 3A, 3B R 1A, 1B G, F, J, K, L, M, N, R — RD 3 8 8 RMS 310 LS RMS 310 LSI 8 RMS 310 LSG RMS 310 LSIG 8 RMS 510 LS RMS 610 LS ST 8 RMS 810 LS a 8 RMS 910 LS Alarm switches (specify voltage and Hz) Make G, F, J, K, L, M, N 1 Make, 1 Break F, K, L, M, N 2 Make, 2 Break G, F, J, K, L, M, N, R — Break Undervoltage release (specify voltage and Hz) Notes Ground fault application not available with NEMA 7/9. Contact Eaton’s Customer Support Center. Add to the appropriate RD RMS 310 adder. 8 8 8 ST 8 8 8 8 8 8 8 8 8 8 8 Volume 2—Commercial Distribution CA08100003E—February 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 111 8.2 8 8 Switching Devices Enclosed Circuit Breakers Raintight Hubs Modifications All rainproof enclosures 30–400A are shipped with plate over cutout. Hubs are not supplied with screws on 30–400A enclosures. Use screws from plate. Allowable accessory combinations can be reviewed in Eaton’s Circuit Breaker Product Guide: PG.74.A.01.T.E. Verify final application with the Customer Support Center. 8 Special RD Modifications and Accessories Raintight Tubs Raintight Hubs 8 Hub Diameter Hubs 8 Inches mm Catalog Number For use with RGDN and RFDN 8 8 0.75 19.1 DS075H1 2500 ampere neutral assembly (aluminum) 1.00 25.4 DS100H1 1600 ampere neutral assembly (copper) 1.25 31.8 DS125H1 2000 ampere neutral assembly (copper) 1.50 38.1 DS150H1 2500 ampere neutral assembly (copper) 2.00 50.8 DS200H1 Adjustable rating plug 2.00 50.8 DS200H2 Key interlock 2.50 63.5 DS250H2 Phase failure protection (includes shunt trip) 3.00 76.2 DS300H2 Zero sequence gfp (including shunt trip and test panel) DS900AP NEMA 3R flat roof Lockoff, padlockable Large 8 For use with RJDN. RKDN has two cutouts 8 Required if using small DS hubs on RJDN and RKDN enclosures. 8 Heater package (includes cpt, heater, thermostat and disconnect) 8 8 8 8 8 Special sized enclosures Standard is 90-inch H x 30-inch W x 30-inch D (2286 x 762 x 762 mm) Breather and Drain, Hazardous Enclosures IQ metering A Universal Breather/Drain Fitting is installed in the top of an enclosure to provide ventilation to minimize condensation and in the bottom to allow drainage of accumulated condensation while maintaining explosion-proof integrity. Compliance Conduit Opening NEMA 7 NEMA 9 BD Class I, Groups C, D; Class I, Zone 1, Group IIB Class II, Groups 1/2 F, G XPBD2 DBB Class I, Groups B, C, D; Class I, Zone 1, Group IIB + Hydrogen Class II, Groups 1/2 E, F, G XPDBB50 8 Neutral Kits, Insulated and Groundable 8 Maximum Enclosure Rating (A) Main Lug Size Cu/Al Ground Lug Size Cu/Al Catalog Number 8 100 SFDN100 RFDN100 (1) 14–1/0 (1) 14–2 DH100NK 8 100 (all others) (1) 14–1/0 (1) 14–1/0 INK100 250 (1) 4–350 kcmil (1) 4–300 kcmil INK250 8 400 (1) 4–600 kcmil or (2) 1/0–250 kcmil (1) 4–300 kcmil INK400 8 600 (2) 250–500 kcmil (1) 4–300 kcmil INK600 1200 3/0–750 kcmil (1) #6–250 kcmil DS800NK 8 Non-standard terminations Catalog Number Type 8 8 1600 ampere neutral assembly (aluminum) 2000 ampere neutral assembly (aluminum) Small 8 Description 8 8 8 8 8 112 Volume 2—Commercial Distribution CA08100003E—February 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 8.2 Switching Devices Enclosed Circuit Breakers Flex Center 8 Introduction Satellite Plants The Safety Switch Flex Center is a special facility at the site of our Cleveland, Tennessee, plant that is dedicated to providing customized enclosed circuit breakers that meet customers’ challenging applications. Atlanta 7000 Highlands Parkway SE #102 Smyrna, GA 30082 Fax (770) 433-1863 Phone (678) 309-4260 Denver 14101 East 33rd Place Suite F Aurora, CO 80011 Fax (303) 371-4175 Phone (303) 371-7844 Baltimore 6671 Santa Barbara Court Suite A Elk Ridge, MD 21075 Fax (410) 796-7755 Phone (410) 796-7777 Hartford 625 Day Hill Road Windsor, CT 06095 Fax (860) 688-4982 Phone (860) 688-5330 Phoenix 921 South Park Lane Suite 1 Tempe, AZ 85281-5119 Fax (480) 449-4223 Phone (480) 449-4222 Houston 10810 West Little York Suite 100 Houston, TX 77041 Fax (713) 688-3764 Phone (713) 688-8430 Raleigh 2933 S. Miami Blvd. Suite 111 Durham, NC 27703 Fax (919) 572-9751 Phone (919) 544-7074 Los Angeles 5590 Jurupa Street Ontario, CA 91761 Fax (909) 390-8884 Phone (909) 390-8853 St. Louis 12947 Gravois Road St. Louis, MO 63127 Fax (314) 842-2552 Phone (314) 842-7797 New Jersey 96 Stemmers Lane Westampton, NJ 08060 Fax (609) 835-4777 Phone (609) 835-4230 San Francisco 20923 Cabot Boulevard Hayward, CA 94545 Fax (510) 784-8980 Phone (510) 784-8981 The Flex Center is a solutions center that provides real value: ● ● ● ● ● ● A dedicated and knowledgeable engineering/ manufacturing/customer service team to meet your needs A production facility stocked with a full arsenal of equipment to get the job done The industry’s shortest lead-time Easy ordering through our distributors Factory-installed modifications include (but are not limited to) the following: ● Special size enclosure ● Special nameplates ● Stainless steel flush cover ● Special paint ● Lock-on provisions ● Neutral assemblies— factory installed ● Equipment ground lugs—factory installed ● Cover control (pilot lights, pushbuttons, selector switches, etc.) ● Factory-installed G-Frame breakers For application, availability or pricing questions, contact the Safety Switch Flex Center at 1-888-329-9272 Chicago 959 AEC Drive Wood Dale, IL 60191 Fax (630) 860-3569 Phone (630) 860-3500 Cleveland 5565 Venture Drive Unit B Parma, OH 44130 Fax (216) 433-0545 Phone (216) 433-0616 Dallas 631 Westport Pkwy Suite 100 Grapevine, TX 76051 Fax (817) 251-6249 Phone (817) 251-6797 8 Orlando 3827 St. Valentine Way Orlando, FL 32811 Fax (407) 841-9135 Phone (407) 843-3863 8 8 8 8 8 8 8 8 8 8 8 8 8 Seattle 18657 72nd Avenue S. Kent, WA 98032 Fax (425) 251-0079 Phone (425) 251-9081 8 8 8 Satellite Service Locations 8 • 8 SEATTLE CHICAGO • • DENVER • SAN FRANCISCO CLEVELAND • • ST. LOUIS • • • 8 NE EW JERSEY 8 BALTIMORE L RALEIGH 8 SUMTER LOS ANGELES A ATLANT TA • 8 • HARTFORD • GRAND PRAIRIE PHOENIX DALLAS •★ • • ★ 8 HOUSTON • 8 OR RLANDO 8 8 8 8 Volume 2—Commercial Distribution CA08100003E—February 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 113 8.2 8 8 8 8 8 Switching Devices Enclosed Circuit Breakers Technical Data and Specifications Industrial Circuit Breaker Selection Circuit Breaker Type Continuous Ampere Rating at 40°C UL Listed Interrupting Rating rms Symmetrical Amperes Number of Poles Vac Vdc Type of Trip Federal Spec. W-C-375b Vdc Ratings Vac Ratings 120 120/240 240 277 480 600 125 250 125/250 G-Frame GHC 15–100 1 120 125 N.I.T.U. 12c, 13a 65,000 — — — — — 14,000 — — 8 GHC 15–100 2, 3 240 125/250 N.I.T.U. 13b — — 65,000 — — — — — 14,000 GHC 15–100 1 277 125 N.I.T.U. 12c, 13a — — — 14,000 — — 14,000 — — 8 GHC 15–100 2, 3 277/480 215/250 N.I.T.U. 13b — — — 14,000 14,000 — — — 14,000 GD 15–100 3 480 250 N.I.T.U. 13b — — 65,000 — 22,000 — — 10,000 — ED 100–225 2, 3 240 125 N.I.T.U. 12b — — 65,000 — — — 10,000 — — EDH 100–225 2, 3 240 125 N.I.T.U. 14b — — 100,000 — — — 10,000 — — 8 EDC 100–225 2, 3 240 125 N.I.T.U. 1 — — 200,000 — — — 10,000 — — EHD 15–100 1 277 125 N.I.T.U. 13a — — — 14,000 — — 10,000 — — 8 EHD 15–100 2, 3 480 250 N.I.T.U. 13b — — 18,000 — 14,000 — — 10,000 — 8 8 F-Frame FDB 15–150 2, 3 600 250 N.I.T.U. 18a — — 18,000 — 14,000 14,000 — 10,000 — FDB 15–150 4 600 250 N.I.T.U. — — 18,000 — 14,000 14,000 — 10,000 — FD 15–225 1 277 125 N.I.T.U. 13a — — — 25,000 — — 10,000 — — FD 15–225 2, 3 600 250 N.I.T.U. 22a — — 65,000 — 25,000 18,000 — 10,000 — 8 FD 15–225 4 600 250 N.I.T.U. — — 65,000 — 25,000 18,000 — 10,000 — HFD 15–225 1 277 125 N.I.T.U. 13a — — — 65,000 — — 10,000 — — 8 HFD 15–225 2, 3 600 250 N.I.T.U. 22a — — 100,000 — 65,000 25,000 — 20,000 — HFD 15–225 4 600 250 N.I.T.U. — — 100,000 — 65,000 25,000 — 20,000 — FDC 15–225 2, 3 600 250 N.I.T.U. 24a — — 200,000 — 100,000 35,000 — 20,000 — FDC 15–225 4 600 250 N.I.T.U. — — 200,000 — 100,000 35,000 — 20,000 — — 8 8 8 8 8 8 8 J-Frame JDB 70–250 2, 3 600 250 N.I.T.U. 22a — — 65,000 — 35,000 18,000 — 10,000 JD 70–250 2, 3, 4 600 250 I.T.U. 22a — — 65,000 — 35,000 18,000 — 10,000 — HJD 70–250 2, 3, 4 600 250 I.T.U. 22a — — 100,000 — 65,000 25,000 — 22,000 — JDC 70–250 2, 3, 4 600 250 I.T.U. 22a — — 200,000 — 100,000 35,000 — 22,000 — K-Frame 8 DK 250–400 2, 3 240 250 N.I.T.U. 14b — — 65,000 — — — — 10,000 — KDB 100–400 2, 3 600 250 N.I.T.U. 23a — — 65,000 — 35,000 25,000 — 10,000 — 8 KD 100–400 2, 3, 4 600 250 I.T.U. 23a — — 65,000 — 35,000 25,000 — 10,000 — HKD 100–400 2, 3, 4 600 250 I.T.U. 23a — — 100,000 — 65,000 35,000 — 22,000 — KDC 100–400 2, 3, 4 600 250 I.T.U. 23a — — 200,000 — 100,000 50,000 — 22,000 — LGE 250–600 3, 4 600 250 I.T.U. 23a — — 65,000 — 35,000 18,000 — 22,000 — LGS 250–600 3, 4 600 250 I.T.U. 23a — — 85,000 — 50,000 25,000 — 22,000 — LGH 250–600 3, 4 600 250 I.T.U. 23a — — 100,000 — 65,000 35,000 — 42,000 — 8 8 8 8 8 8 LG-Frame Notes N.I.T.U. is non-interchangeable trip unit and I.T.U. is interchangeable trip unit. Two-pole circuit breaker, or two poles of three-pole circuit breaker at 250 Vdc. Not defined in W-C-375b. Not suitable for use with 100A enclosures. 8 8 114 Volume 2—Commercial Distribution CA08100003E—February 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 8.2 Switching Devices Enclosed Circuit Breakers Industrial Circuit Breaker Selection, continued Circuit Breaker Type Continuous Ampere Rating at 40°C Number of Poles Vac Vdc 300–600 2, 3 600 300–600 2, 3, 4 300–600 2, 3, 4 8 UL Listed Interrupting Rating rms Symmetrical Amperes Type of Trip Federal Spec. W-C-375b Vac Ratings 120 120/240 240 277 480 600 125 250 125/250 250 N.I.T.U. 23a — — 65,000 — 35,000 25,000 — 22,000 — 600 250 I.T.U. 23a — — 65,000 — 35,000 25,000 — 22,000 — 600 250 I.T.U. 23a — — 100,000 — 65,000 35,000 — 25,000 — 8 8 Vdc Ratings 8 L-Frame LDB LD HLD 8 M-Frame MDL 300–800 2, 3 600 250 I.T.U. 23a — — 65,000 — 50,000 25,000 — 22,000 — HMDL 300–800 2, 3 600 250 I.T.U. 23a — — 100,000 — 65,000 35,000 — 25,000 — ND 600–1200 3, 4 600 — N.I.T.U. 23a — — 65,000 — 50,000 25,000 — — HND 600–1200 3, 4 600 — N.I.T.U. 23a — — 100,000 — 65,000 35,000 — — 800–2500 3, 4 600 — N.I.T.U. 24a — — 125,000 — 65,000 35,000 — — 8 N-Frame 8 R-Frame RD 8 8 — 8 Notes N.I.T.U. is non-interchangeable trip unit and I.T.U. is interchangeable trip unit. Two-pole circuit breaker, or two poles of three-pole circuit breaker at 250 Vdc. HLD: NEMA 1 enclosed: 240 Vac = 100 kA, 480 Vac = 65 kA, 600 Vac = 35 kA, 250 Vdc = 20 kA, 500 Vdc = 25 kA. NEMA 3R enclosed: 240 Vac = 65 kA, 480 Vac = 50 kA, 600 Vac = 25 kA, 250 Vdc = 20 kA, 500 Vdc = 25 kA. HMDL and HND: NEMA 1 and 3R enclosed: 240 Vac = 100 kA, 480 Vac = 65 kA, 600 Vac = 35 kA, 250 Vdc = 30 kA, 500 Vdc = 30 kA. 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 Volume 2—Commercial Distribution CA08100003E—February 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 115 8.2 Switching Devices Enclosed Circuit Breakers 8 Dimensions 8 NEMA 1, 12, 12K, 3R 8 Approximate Dimensions in Inches (mm) Note:þNot to be used for construction purposes unless approved. 8 NEMA 1 Surface Mounted 8 Frame Maximum Amperes A G 100 17.50 (444.5) 8.56 (217.4) 6.28 (159.5) 13.03 (331.0) F 100 19.13 (485.9) 9.13 (231.9) 5.20 (132.1) 17.00 (431.8) 8 Earth leakage 100 23.25 (590.6) 8.56 (217.4) 6.28 (159.5) 18.75 (476.3) F 225 23.25 (590.6) 8.56 (217.4) 6.28 (159.5) 8 J 250 34.70 (881.4) 10.92 (277.4) 7.20 (182.9) K 400 38.81 (985.8) 11.06 (280.9) 10.94 (277.9) LG 600 51.06 (1296.9) 21.87 (555.5) Earth leakage 600 51.06 (1296.9) 21.87 (555.5) 8 8 8 B F Approximate Weight in Lbs (kg) 1.20 (30.5) 17.19 (436.6) 12 (5) N/A 18.81 (477.8) 13 (6) 1.20 (30.5) 22.94 (582.7) 15 (7) 18.75 (476.3) 1.20 (30.5) 22.94 (582.7) 15 (7) 30.00 (762.0) 1.88 (47.8) 34.39 (873.5) 31 (14) 34.00 (863.6) 9.28 (235.7) 38.50 (977.9) 53 (24) 9.96 (253.0) 51.63 (1311.5) 1.94 (49.3) 50.13 (1273.3) 90 (41) 9.96 (253.0) 51.63 (1311.5) 1.94 (49.3) 50.13 (1273.3) 90 (41) C D E L 600 45.88 (1165.4) 14.31 (363.5) 12.38 (314.5) 46.56 (1182.6) 1.91 (48.5) 45.56 (1157.2) 81 (37) 8 M, N 1200 61.22 (1555.0) 21.44 (544.6) 15.41 (391.4) 61.84 (1570.7) 1.97 (50.0) 60.91 (1547.1) 178 (81) 8 NEMA 1 Surface Mounted E 8 C B 8 8 8 D A F 8 8 8 8 8 Notes SFDN100 Series “B” released 9/15/01. Maximum wire size: 4/0. Total width, including door clip is 9.95 inches (253 mm). Single centered mounting hole provided. Maximum wire size: 500 kcmil. 8 8 8 8 8 8 8 8 8 116 Volume 2—Commercial Distribution CA08100003E—February 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 8.2 Switching Devices Enclosed Circuit Breakers Approximate Dimensions in Inches (mm) 8 NEMA 1 Flush Mounted Frame Maximum Amperes A B C D E F Approximate Weight in Lbs (kg) F 100 18.81 (477.8) 9.72 (246.9) 6.28 (159.5) 13.03 (331.0) 1.86 (47.2) 18.50 (469.9) 12 (5) Earth leakage 100 24.56 (623.8) 9.72 (246.9) 6.28 (159.5) 18.75 (476.3) 1.86 (47.2) 24.25 (616.0) 15 (7) F 225 24.56 (623.8) 9.72 (246.9) 6.28 (159.5) 18.75 (476.3) 1.86 (47.2) 24.25 (616.0) 15 (7) J 250 36.02 (914.9) 12.23 (310.6) 7.20 (182.9) 30.00 (762.0) 1.88 (47.8) 35.70 (906.8) 32 (15) K 400 40.13 (1019.3) 12.38 (314.5) 10.94 (277.9) 34.00 (863.6) 2.94 (74.7) 39.81 (1011.2) 53 (24) 8 8 8 8 8 NEMA 1 Flush Mounted 8 E 8 C B 8 8 F A D 8 8 8 8 NEMA 1 Surface Mounted SFDN100 Series “B” 8 8 9.95 (252.7) NEED ART 1.84 (46.7) 1.78 (45.2) 9.13 (232.0) DWG...95-1562 18.81 (478.0) 0.71 (18.0) 2.13 (54.1) 1.91 (48.5) FROM 17.00 MARK SCHMIDT (431.8) 1.91 (48.5) 0.27 (6.8) Diameter 3 Mounting Holes 1.78 (45.2) 4.23 (107.4) 5.20 (132.0) 0.81 (20.6) 7.25 (184.1) 8 1.84 (46.7) 19.12 (485.6) 1.84 (46.7) 8 0.38 (9.7) 8 Concentric Knockouts for 1, 1-1/4, 1-1/2 (25.4, 31.8, 38.1) 2 Conduit Quantity: 10 8 8 8 1.84 (46.7) 8 3.50 (89.0) 1.91 (48.5) 8 0.69 (17.5) 8.82 (224.0) 8 0.281 (7.1) Diameter Knockout Quantity: 2 8 Notes Maximum wire size: 4/0. Maximum wire size: 500 kcmil. 8 8 8 8 Volume 2—Commercial Distribution CA08100003E—February 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 117 8.2 Switching Devices Enclosed Circuit Breakers 8 Approximate Dimensions in Inches (mm) 8 NEMA 12, 12K Dustproof 8 Maximum Amperes Frame A B C D E Approximate Weight in Lbs (kg) G, F 100 19.91 (505.7) 9.16 (232.7) 9.31 (236.5) 18.53 (470.7) 1.70 (43.2) 16 (7) 8 Earth leakage 100 19.91 (505.7) 9.16 (232.7) 9.31 (236.5) 18.53 (470.7) 1.70 (43.2) 19 (9) FBP, FCL 100 25.66 (651.8) 9.16 (232.7) 9.31 (236.5) 24.28 (616.7) 1.70 (43.2) 19 (9) 8 F 225 25.66 (651.8) 9.16 (232.7) 9.31 (236.5) 24.28 (616.7) 1.70 (43.2) 19 (9) J 250 37.53 (953.3) 11.88 (301.8) 10.22 (259.6) 35.77 (908.6) 1.94 (49.3) 37 (17) 8 K 400 41.69 (1058.9) 12.31 (312.7) 14.06 (357.1) 39.94 (1014.5) 1.97 (50.0) 58 (26) 8 LG 600 53.37 (1355.6) 23.06 (585.7) 14.10 (358.1) 51.63 (1311.4) 1.94 (49.3) 94 (43) Earth leakage 600 53.37 (1355.6) 23.06 (585.7) 14.10 (358.1) 51.63 (1311.4) 1.94 (49.3) 94 (43) 8 L 600 48.31 (1227.1) 15.56 (395.2) 15.50 (393.7) 46.56 (1182.6) 1.92 (48.8) 84 (38) NBP 800 63.59 (1615.2) 22.63 (574.8) 17.63 (447.8) — — 110 (50) M, N 1200 63.59 (1615.2) 22.63 (574.8) 17.63 (447.8) 61.84 (1570.7) 1.97 (50.0) 175 (80) 8 8 G, F 100 19.91 (505.7) 9.16 (232.7) 9.31 (236.5) — — 16 (7) Earth leakage 100 19.91 (505.7) 9.16 (232.7) 9.31 (236.5) — — 19 (9) 8 FBP, FCL 100 25.66 (651.8) 9.16 (232.7) 9.31 (236.5) — — 19 (9) F 225 25.66 (651.8) 9.16 (232.7) 9.31 (236.5) — — 19 (9) 8 J 250 37.53 (953.3) 11.88 (301.8) 10.22 (259.6) — — 37 (17) K 400 41.69 (1058.9) 12.31 (312.7) 14.06 (357.1) — — 58 (26) 8 8 NEMA 12, 12K Dustproof C 8 8 8 A D 8 8 8 Notes Maximum wire size: 4/0. Maximum wire size: 500 kcmil. 8 8 8 8 8 8 8 8 8 8 118 Volume 2—Commercial Distribution CA08100003E—February 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 8.2 Switching Devices Enclosed Circuit Breakers Approximate Dimensions in Inches (mm) 8 NEMA 3R Rainproof Frame Maximum Amperes A B C D E Approximate Weight in Lbs (kg) G, F 100 19.91 (505.7) 9.16 (232.7) 9.31 (236.5) 18.53 (470.7) 1.70 (43.2) 16 (7) Earth leakage 100 19.91 (505.7) 9.19 (232.7) 9.31 (236.5) 18.53 (470.7) 1.70 (43.2) 19 (9) FBP, FCL 100 25.66 (651.8) 9.16 (232.7) 9.31 (236.5) 24.28 (616.7) 1.70 (43.2) 19 (9) F 225 25.66 (651.8) 9.16 (232.7) 9.31 (236.5) 24.28 (616.7) 1.70 (43.2) 19 (9) J 250 37.50 (952.5) 11.88 (301.8) 10.22 (259.6) 35.77 (908.6) 1.94 (49.3) 37 (17) K 400 41.69 (1058.9) 12.31 (312.7) 14.06 (357.1) 39.94 (1014.5) 1.97 (50.0) 58 (26) LG 600 53.37 (1355.6) 23.06 (585.7) 14.10 (358.1) 51.63 (1311.4) 1.94 (49.3) 94 (43) Earth leakage 600 53.37 (1355.6) 23.06 (585.7) 14.10 (358.1) 51.63 (1311.4) 1.94 (49.3) 94 (43) L 600 48.31 (1227.1) 15.56 (395.2) 15.50 (393.7) 46.56 (1182.6) 1.92 (48.8) 84 (38) M, N 1200 63.59 (1615.2) 22.63 (574.8) 17.63 (447.8) 61.84 (1570.7) 1.97 (50.0) 175 (80) 8 8 8 8 8 8 8 8 NEMA 3R Rainproof E 8 C 8 8 ON A D OFF F 8 8 B 8 NEMA 3R Rainproof RFDN100 Series “B” 8 8 NEED ART 8 9.95 (252.7) 0.71 (18.0) DWG...95-1562 8 FROM 17.00 MARK SCHMIDT (431.8) 8 9.13 (232.0) 18.81 (478.0) 1.84 (46.7) 1.91 (48.5) 1.78 (45.2) 0.81 (20.6) 4.23 (107.4) 5.20 (132.0) 0.27 (6.8) Diameter 3 Mounting Holes 7.25 (184.0) 0.38 (9.7) 8 Concentric Knockouts for 1, 1-1/4, 1-1/2 (25.4, 31.8, 38.1) 2 Conduit Quantity: 5 19.12 (485.6) 19.27 (489.4) 8 8 1.91 (48.5) 8 1.84 (46.7) 8 3.50 (89.0) 8 1.91 (48.5) 0.69 (17.5) 8.82 (224.0) 8 0.281 (7.1) Diameter Knockout Quantity: 2 8 Notes RFDN100 Series “B” released 9/15/01. Single centered mounting hole provided on RFDN100, Series “B.” Maximum wire size: 4/0. Maximum wire size: 500 kcmil. Volume 2—Commercial Distribution 8 8 CA08100003E—February 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 119 8.2 8 8 8 8 8 8 8 8 8 8 8 Switching Devices Enclosed Circuit Breakers Approximate Dimensions in Inches (mm) NEMA 4/4X, 5, 7/9 Note:þNot to be used for construction purposes unless approved. NEMA 4/4X, 5 Stainless Steel Maximum Amperes Frame A B C D E Approximate Weight in Lbs (kg) 16 (7) G, F 100 19.91 (505.7) 8.84 (224.5) 9.31 (236.5) 18.53 (470.7) 1.70 (43.2) Earth leakage 100 19.91 (505.7) 8.84 (224.5) 9.31 (236.5) 18.53 (470.7) 1.70 (43.2) 20 (9) FBP, FCL 100 25.66 (651.8) 8.84 (224.5) 9.31 (236.5) 24.28 (616.7) 1.70 (43.2) 20 (9) 20 (9) F 225 25.66 (651.8) 8.84 (224.5) 9.31 (236.5) 24.28 (616.7) 1.70 (43.2) J 250 37.50 (952.5) 11.56 (293.6) 10.22 (259.6) 35.77 (908.6) 1.94 (49.3) 39 (18) K 400 41.69 (1058.9) 11.75 (298.5) 14.06 (357.1) 39.94 (1014.5) 1.97 (50.0) 60 (27) 96 (44) LG 600 53.38 (1355.9) 23.06 (585.7) 14.11 (358.4) 51.64 (1311.7) 1.94 (49.3) Earth leakage 600 53.38 (1355.9) 23.06 (585.7) 14.11 (358.4) 51.64 (1311.7) 1.94 (49.3) 96 (44) L 600 48.31 (1227.1) 14.91 (378.7) 15.50 (393.7) 46.56 (1182.6) 1.92 (48.8) 88 (40) M, N 1200 63.59 (1615.2) 22.00 (558.8) 17.63 (447.8) 61.84 (1570.7) 1.97 (50.0) 185 (84) NEMA 4/4X, 5 Stainless Steel 8 E B 8 C 8 8 D A ON OFF 8 8 8 8 Notes Maximum wire size: 4/0. Maximum wire size: 500 kcmil. 8 8 8 8 8 8 8 8 8 8 8 120 Volume 2—Commercial Distribution CA08100003E—February 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 8.2 Switching Devices Enclosed Circuit Breakers Approximate Dimensions in Inches (mm) 8 NEMA 7/9 Cast Aluminum with Weather-Resistant Seals—15–250A Breaker Size Amperes Number of Outlets F XFDN050B 15–50 F XFDN100B Mounting Inside Outside Standard Conduit Size Approximate Weight in Lbs (kg) A B J C D E F G H K Dim 4 5.50 (139.7) 13.13 (333.5) 14.13 (358.9) 6.13 (155.7) 10.75 (273.1) 5.25 (133.4) 10.63 (270.0) 15.25 (387.4) 8.88 (225.6) 2.00 (50.8) 1.50 (38.1) 38 (17) 60–100 4 6.00 (152.4) 18.00 (457.2) 19.00 (482.6) 6.50 (165.1) 16.00 (406.4) 5.50 (139.7) 11.00 (279.4) 20.50 (520.7) 9.00 (228.6) 2.31 (58.7) 2.00 (50.8) 57 (26) F XFDN225B 125–225 4 10.25 (260.4) 22.63 (574.8) — 11.38 (289.1) 20.00 (508.0) 6.38 (162.1) 16.38 (416.1) 25.13 (638.3) 9.63 (244.6) 3.50 (88.9) 2.50 (63.5) 104 (47) J XJDN225B 70–225 4 8.50 (215.9) 27.13 (689.1) — 11.25 (285.8) 29.88 (759.0) 7.38 (187.5) 16.00 (406.4) 29.50 (749.3) 12.31 (312.7) 4.00 (101.6) 3.00 (76.2) 145 (66) J XJDN250B 250 4 9.50 (241.3) 27.25 (692.2) — 11.25 (285.8) 29.88 (759.0) 8.06 (204.7) 16.38 (416.1) 35.00 (889.0) 12.38 (314.5) 4.19 (106.4) 4.00 (101.6) 170 (77) Breaker Frame 8 8 8 8 8 8 8 8 NEMA 7/9 Cast Aluminum with Weather-Resistant Seals—Dual Three- and Four-Point Mounting Available as Standard on F-Frame 100A and Below 8 8 8 8 8 8 8 8 Note Maximum wire size: 4/0. 8 8 8 8 8 8 8 8 8 8 8 8 8 Volume 2—Commercial Distribution CA08100003E—February 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 121 8.2 Switching Devices Enclosed Circuit Breakers 8 Approximate Dimensions in Inches (mm) 8 7/9 Cast Aluminum with Weather-Resistant Seals—400–1200A Breaker Size Amperes Overall Enclosure A B C D E F G H Enclosure Mounting Conduit Hinged Cover Standard Conduit I J Size Location 8 Breaker Frame 8 K XKDN400B 400 35.00 (889.0) 16.38 (416.1) 12.63 (320.8) 7.13 (181.1) 9.50 (241.3) 27.25 (692.2) .50 (12.7) 3.00 (76.2) 4.19 (106.4) 5.50 (139.7) 4.00 (101.6) 1, 3 and 6, 8 170 (77) L XLDN600B 600 37.88 (962.2) 23.88 (606.6) 14.25 (362.0) 8.25 (209.6) 16.00 (406.4) 45.38 (1152.7) .50 (12.7) 4.00 (101.6) 5.00 (127.0) 6.00 (152.4) 4.00 (101.6) 1, 3 and 6, 8 419 (190) M XMCN800B 800 47.88 (1216.2) 13.63 (346.2) 12.81 (325.4) 6.81 (173.0) 16.13 (409.7) 40.75 (1035.1) .50 (12.7) 4.00 (101.6) 4.00 (101.6) 6.00 (152.4) 4.00 (101.6) 1, 3 and 6, 8 228 (104) N XNDN1200B 1200 64.00 (1625.6) 26.00 (660.4) 21.38 (543.1) 14.38 (365.3) 27.56 (700.0) 38.63 (981.2) .50 (12.7) 6.50 (165.1) 4.38 (111.3) 7.00 (177.8) 4.00 (101.6) 1, 3 and 6, 8 567 (257) 8 8 8 8 NEMA 7/9 Cast Aluminum with Weather-Resistant Seals 8 CONDUIT POSITION NO. 1 8 2 3 G-MTG. HOLES (4) J 8 B F-MTG. A 8 8 I D C 8 H H 8 8 8 8 8 8 8 8 Weight Lbs (kg) 7 6 Conduit Openings Refer to outline dimensions for size and location of standard conduit openings. In addition, 1/2-inch (12.7 mm) openings are drilled and tapped for breather and drain. Unless ordered with breather and drain, these openings are plugged. Refer to Eaton for price of breather and drain. Notes Maximum wire size: 500 kcmil. Power cables must enter and leave from opposite ends (through-feed). 8 8 8 8 8 8 8 8 8 122 Volume 2—Commercial Distribution CA08100003E—February 2011 www.eaton.com For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616 Index A above, 2 ABreaker, 18 Accessories, 1, 7-8 accessory, 8 accumulated, 8 Add, 7 adder, 7 addition, 18 address, 7 Adjustable, 8 AEC, 9 akecify, 7 Al, 8 Alarm, 7 all, 8 allow, 8 Allowable, 8 Aluminum, 2, 17-18 aluminum, 2, 5-6, 8 Ampere, 5-7, 10-11 ampere, 8 Amperes, 11-18 AmperesCircuit, 10 an, 7-8 and, 1-2, 5-11, 17-18 ANGELES, 9 Angeles, 9 apartment, 1 applicable, 1 Application, 1 application, 1-2, 7-9 applications, 1, 9 Applied, 7 appropriate, 7 approved, 12, 16 Approxi, 13 Approximat, 15 Approximate, 12-18 APRJDN, 8 arcing, 2 are, 1-2, 6-9, 18 areas, 1 ARK, 15 arsenal, 9 ART, 15 as, 1-2, 17 Assembled, 7 Assemblies, 7 assemblies, 9 assembly, 2, 8 at, 1-18 ATLANTA, 9 Atlanta, 9 atmosphere, 2 atmospheres, 2 Aurora, 9 authorized, 7 Auxiliary, 7 availability, 9 Available, 17 available, 1-2, 7 Avenue, 9 AWK, 3-4 AZ, 9 Index B Baltimore, 9 BALTIMORErame, 9 Barbara, 9 Base, 5 BD, 8 be, 1, 5-8, 12, 16 Before, 7 begin, 7 being, 1 Below, 17 Benefits, 1-2 Blvd, 9 borax, 1 Both, 1 bottom, 8 Boulevard, 9 Break, 7 Breake, 17 Breaker, 3-8, 10-11, 17-18 breaker, 1-2, 5, 10-11 Breakers, 1-18 breakers, 1, 6, 9 BreakersELFD, 6 Breather, 8 breather, 18 breweries, 1 buildings, 1 but, 9 by, 1-2 C CA, 1-18 cables, 18 Cabot, 9 call, 1-18 Can, 5-6 can, 1, 7-8 capable, 1 Cast, 2, 17-18 cast, 2, 5-6 Catalog, 3-6, 8 CatalogRating, 8 Center, 1, 7-9 center, 1, 9 centered, 12, 15 Certifications, 1-2 challenging, 9 CHICAGO, 9 Chicago, 9 Circuit, 1-18 circuit, 1-2, 5-6, 9-11 circuits, 1 Class, 2, 5-6, 8 CLEVELAND, 9 Cleveland, 9 clip, 12 close, 1 CO, 9 com, 1-18 combinations, 8 Commercial, 1-18 commercial, 1 Competitive, 3-4 Complete, 7 Compliance, 8 compliant, 2 Concentric, 13, 15 condensation, 8 conditions, 2 CONDUIT, 18 Conduit, 8, 13, 15, 17-18 conduit, 18 construction, 7, 12, 16 Contact, 7 contact, 9 Contents, 1 continued, 6, 11 continuedCatalog, 4 Continuo, 11 Continuous, 10 control, 9 converted, 5-6 coolant, 2 copper, 8 Court, 9 Cover, 9, 18 cover, 2, 9 Covers, 7 cpt, 8 Cross, 1, 3 CS, 3-4 CSA, 2 CT, 9 Cu, 8 Customer, 7-8 customer, 9 Index customers, 9 customized, 9 cutout, 8 cutouts, 8 D DA, 16 dairies, 1 Dale, 9 DALLAS, 9 Dallas, 9 Data, 1, 10 data, 5 Day, 9 DBB, 8 dedicated, 9 defined, 10 Delivery, 1-18 DENVER, 9 Denver, 9 Description, 1, 7 Descriptionameter, 8 design, 2 designed, 1-2 determine, 5 device, 1 Devices, 1-18 DFDN, 3, 5-6 DGDN, 3, 5 DH, 8 Di, 8 Diameter, 13, 15 Dim, 17 dimensional, 5 Dimensions, 1, 12-18 dimensions, 18 DimensionsApproximate, 12 disconnect, 1, 8 Distribution, 1-18 distributors, 9 DJDN, 3, 5 DK, 6, 10 DKDN, 4, 6 done, 9 door, 1-2, 12 Drain, 8 drain, 18 drainage, 8 Dri, 9 drilled, 18 Drive, 9 DS, 3-4, 8 Dual, 17 Durham, 9 dust, 2 Dustproof, 1-2, 14 dustproof, 1 DWG, 13, 15 E EA, 3 Ea, 15 Earth, 6, 12-16 ease, 2 East, 9 Easy, 9 Eaton, 3-4, 7-8, 18 eaton, 1-18 EB, 3 EC, 3 ED, 3-5, 10 EDC, 5, 10 EDH, 5, 10 EE, 4 EHB, 3 EHD, 3, 5, 10 Electric, 3 ElectricRating, 4 Electronic, 7 ELFDC, 6 ELHFD, 6 Elk, 9 ELLBN, 6 employs, 1 Encl, 2 Enclosed, 1-18 enclosed, 1, 9, 11 Enclosure, 3-8, 18 enclosure, 1-2, 5, 8-9 Enclosures, 8 enclosures, 1-2, 8, 10 enclosuresStandard, 8 ends, 18 engineering, 9 Index enter, 18 entrance, 1-2 Equipment, 9 equipment, 9 etc, 9 exist, 2 Explosion, 2 explosion, 8 F FA, 3 facility, 9 Factory, 9 factory, 2, 9 failure, 8 FAL, 3 fault, 7 Fax, 9 FBP, 14-16 FCL, 14-16 FD, 3, 5, 10 FDB, 3, 5, 10 FDC, 5, 10 Features, 1-2 February, 1-18 Federal, 10-11 feed, 4, 18 feeder, 1 FFD, 6 FFDN, 3, 5 field, 5-6 File, 2 final, 8 Finish, 7 Fitting, 8 FJDN, 3, 5 FKDN, 4, 6 FL, 9 flanged, 2 flat, 8 Flex, 1, 7, 9 Flush, 1, 7, 13 flush, 1-6, 9 following, 7, 9 For, 1-18 for, 1-2, 5-6, 10, 12-13, 15-16, 18 foreign, 2 Four, 17 Frame, 5-7, 10-11, 13-17 FrameLGE, 10 Frames, 7 FRANCISCO, 9 Francisco, 9 FROM, 13, 15 from, 1-2, 8, 18 Front, 2 front, 1 full, 9 Functions, 1-2 FXD, 3 G GA, 9 GD, 5, 10 General, 1-4 general, 1 get, 9 gfp, 8 GHC, 3, 5, 10 GHCGFEP, 5 GRAND, 9 Grapevine, 9 Gravois, 9 Ground, 7-8 ground, 9 Groundable, 8 Group, 2, 8 Groups, 2, 8 Guide, 8 H handle, 1-2 HARTFORD, 9 Hartford, 9 has, 1, 8 have, 2 Hayward, 9 Hazardous, 2, 8 Heater, 8 Index heater, 8 HFD, 5, 10 high, 6 Highlands, 9 Hill, 9 Hinged, 18 hinges, 2 HJD, 5, 10 HKD, 6-7, 10 HLD, 6-7, 11 HMDL, 6-7, 11 HND, 6, 11 hole, 12, 15 HOLES, 18 Holes, 13, 15 HOUSTON, 9 Houston, 9 Hub, 8 Hubs, 1, 8 hubs, 8 hubsmechanism, 2 Hydrogen, 8 Hz, 7 inside, 1-2 Installed, 7 installed, 8-9 Insulated, 8 integrity, 8 Interchangeable, 1-2 interchangeable, 10-11 Interlock, 7 interlock, 8 Interlocked, 2 interlocked, 1-2 Interlocks, 7 Interrupting, 10-11 interrupting, 6 Introduction, 9 involving, 2 IQ, 8 is, 1-2, 8-12 It, 1 J I IDT, 13, 15 if, 8 igniting, 2 II, 2, 8 IIB, 8 IL, 9 Immediate, 1-18 In, 18 in, 1-2, 5, 8, 10, 12-18 inch, 8, 18 Inches, 8, 12-18 inches, 12 include, 5, 9 includes, 2, 8 including, 8, 12 indoor, 1 Industrial, 10-11 industries, 1 industry, 2, 9 information, 5, 7 INK, 8 Inside, 17 JD, 5, 10 JDB, 3, 5, 10 JDC, 5, 10 JERSEY, 9 Jersey, 9 JFDN, 3, 5-6 JGDN, 3, 5 JJDN, 3, 5 JKDN, 4, 6 JLDN, 4, 6 JLG, 6 JNDN, 4, 6 Jurupa, 9 JXD, 4 K KA, 3 kA, 11 KAL, 3 kcmil, 3-4, 8, 12-16, 18 KD, 6-7, 10 Index KDB, 4, 6, 10 KDC, 6, 10 Kent, 9 Key, 7-8 kg, 12-18 kit, 5 Kits, 8 KMParts, 1-18 kn, 9 Knockout, 13, 15 Knockouts, 13, 15 knockouts, 1-2 known, 7 Locations, 9 Lock, 9 lock, 7 Lockoff, 8 LOS, 9 Los, 9 LOUIS, 9 Louis, 9 LR, 2 LS, 7 LSG, 7 LSI, 7 LSIG, 7 LSSeparate, 7 Lug, 7-8 lugs, 9 LXD, 4 L LA, 4 Laboratories, 1-2 LAL, 4 Lane, 9 Large, 8 Lbs, 12-18 LD, 4, 6-7, 11 LDB, 4, 6, 11 lead, 9 Leakage, 6 leakage, 12-16 leave, 18 legend, 7 LG, 10, 12, 14-16 LGE, 6 LGH, 6, 10 LGS, 6, 10 Li, 11 li, 9 lift, 2 Light, 7 light, 7 lights, 9 limited, 6 line, 2 Listed, 10 listed, 1-2 Little, 9 LMD, 4 Location, 2, 18 location, 2, 18 Locationare, 2 M MA, 4 Ma, 13 machined, 2 Main, 8 main, 1 maintaining, 8 Make, 7 MAL, 4 manufacturing, 9 MARK, 13 mate, 13 materials, 2 Maxi, 15 Maximum, 3-5, 8, 12-18 MD, 9 MDL, 4, 6-7, 11 meet, 9 meets, 1 meteringA, 8 Miami, 9 mills, 1 mines, 1 minimize, 8 mited, 9 mm, 8, 12-18 MND, 4 MO, 9 Modifications, 7-8 Index modifications, 9 ModificationsAll, 8 Mounted, 12-13 mounted, 1-2 Mounting, 1-2, 13, 15, 17-18 mounting, 5, 12, 15 MTG, 18 mum, 15 must, 7, 18 MXD, 4 N NA, 4 NAL, 4 name, 7 nameplate, 7 Nameplates, 7 nameplates, 9 NBP, 14 NC, 9 ND, 4, 6-7, 11 nd, 9 NEED, 13, 15 needs, 9 NEMA, 1-8, 11-18 Neutral, 7-9 neutral, 8 NEW, 9 New, 9 NF, 3 NJ, 9 NK, 8 NKRFDN, 8 NO, 18 No, 2 no, 1 nockouts, 2 Non, 8 non, 10-11 Not, 10 not, 2, 7-9 Note, 2, 12, 16-17 Notes, 3-7, 10-16, 18 NRB, 3 NS, 3 Number, 3-8, 10-11, 17 number, 7 Numbers, 3-4 Numerous, 2 NXD, 4 O ob, 9 of, 1-2, 5, 7-11, 17-18 OFF, 1-2, 15-16 off, 2 OH, 9 oil, 2 ON, 1-2, 15-16 On, 7 on, 2, 5, 8-9, 15, 17 Only, 5-6 only, 4-6 Ontario, 9 open, 1 Opening, 8 opening, 1-2 Openings, 2, 18 openings, 1, 18 operable, 1-2 operating, 1-2 operation, 7 opposite, 18 Options, 7 options, 2 or, 1-18 order, 7 ordered, 18 ordering, 9 ORLANDO, 9 Orlando, 9 osures, 2 Other, 2 other, 1-2 others, 8 our, 9 outdoor, 1 Outlets, 17 outline, 18 Outside, 17 outside, 2 over, 8 Overall, 18 owledgeable, 9 Index P package, 8 Padlockable, 2 padlockable, 8 padlocked, 1 padlocks, 2 Page, 1, 5-6 Pages, 5 Paint, 7 paint, 9 panel, 8 paper, 1 Park, 9 Parkway, 9 Parma, 9 particularly, 1 PG, 8 Phase, 8 PHOENIX, 9 Phoenix, 9 Phone, 9 Pilot, 7 pilot, 9 Pkwy, 9 Place, 9 plant, 9 Plants, 9 plate, 5, 8 plug, 8 plugged, 18 Point, 17 pole, 5-6, 10-11 Poles, 7, 10-11 poles, 10-11 POSITION, 18 position, 1-2 Power, 18 PRAIRIE, 9 prevent, 1-2, 7 price, 18 pricing, 9 process, 1 Product, 1, 5, 8 production, 9 proof, 2, 8 protection, 8 protective, 1 provide, 7-8 provided, 12, 15 provides, 9 providing, 9 provisions, 9 Purpose, 1-2 purpose, 1 purposes, 12, 16 pushbuttons, 9 Q QCCBP, 5 Quantity, 13, 15 questions, 9 R Rainproof, 1-2, 15 rainproof, 8 Raintight, 8 RALEIGH, 9 Raleigh, 9 Range, 5-6 rated, 2, 6 Rating, 3, 10-11 rating, 8 Ratings, 1-2, 10-11 ratings, 6-7 RB, 3 RD, 7-8, 11 rd, 9 real, 9 Refer, 6, 18 Reference, 1, 3 release, 7 released, 12, 15 Required, 8 required, 5, 7 requirements, 1 Resistant, 17-18 reviewed, 8 RFDN, 3, 5-6, 8, 15 RGDN, 3, 5, 8 Ridge, 9 RJDN, 3, 5, 8 Index RKDN, 4, 6, 8 RLDN, 4, 6 RLG, 6 RMS, 7 rms, 10-11 RNDN, 4, 6 Road, 9 roof, 8 rough, 5 RT, 13 rth, 15 S Safety, 7, 9 SAN, 9 San, 9 Santa, 9 Satellite, 9 SCH, 13, 15 scheme, 7 screws, 8 SE, 3, 9 Seals, 17-18 SEATTLE, 9 Seattle, 9 Selection, 1, 5, 10-11 selector, 9 semi, 2 sequence, 8 Series, 5-6, 12-13, 15 serve, 1 Service, 9 service, 1-2, 9 severe, 2 SF, 3 SFD, 6 SFDN, 3, 5, 8, 12-13 SG, 4 SGDN, 3, 5 sheet, 1 shipped, 8 Short, 6 shortest, 9 Shunt, 7 shunt, 8 Side, 2 Siemens, 3-4 Single, 12, 15 single, 5 site, 9 Size, 8, 17-18 size, 3-5, 9, 12-18 sized, 8 SJDN, 3, 5 SK, 4 SKDN, 4, 6 SLDN, 4, 6 SLG, 6 Small, 8 small, 8 Smyrna, 9 SNDN, 4, 6 solutions, 9 South, 9 spe, 7 Spec, 10-11 Special, 7-9 special, 2, 9 Specifications, 1, 10 specifications, 2 specify, 7 Square, 3-4 SS, 3-4 ST, 7, 9 St, 9 Stainless, 1, 7, 9, 16 stainless, 5-6 Standard, 17-18 standard, 8, 18 Standards, 1-2 sted, 11 Steel, 1, 7, 16 steel, 1, 5-6, 9 Stemmers, 9 stocked, 9 Street, 9 Suitable, 5 suitable, 1-2, 10 Suite, 9 suited, 1 SUMTER, 9 supplied, 2, 8 Support, 1-18 Surface, 1-2, 12-13 surface, 1, 3-6 Switch, 7, 9 switches, 7, 9 Switching, 1-18 Symmetrical, 10-11 system, 7 Index Systems, 7 U T tapped, 18 TE, 3 team, 9 Tech, 1-18 Technical, 1, 10 TED, 3 telephone, 7 Tempe, 9 Tennessee, 9 terminations, 8 test, 8 TF, 3 TFJ, 3 Th, 9 that, 2, 9 The, 1-2, 9 the, 1-2, 5, 7-9 thermostat, 8 These, 2 these, 18 This, 1-2 Three, 17 three, 5-6, 10-11 Through, 4 through, 1-2, 5, 9, 18 tight, 2 time, 7, 9 TJ, 4 TJK, 4 TK, 4 TKMA, 4 TKV, 4 to, 1-2, 5-9, 12, 16, 18 top, 8 Total, 12 Trip, 7, 10-11 trip, 7-8, 10-11 Tubs, 8 Two, 10-11 two, 5, 8, 10-11 TX, 9 Type, 1-2, 5-8, 10-11 type, 5 UL, 2, 10-11 Undervoltage, 7 Underwriters, 1-2 Unit, 9 unit, 10-11 units, 2 Universal, 8 Unless, 18 unless, 12, 16 unusually, 2 urface, 3 us, 11 Use, 5, 8 use, 1, 5, 8, 10 used, 1, 6-7, 12, 16 User, 7 using, 8 V Vac, 1-2, 10-11 Valentine, 9 value, 9 Vdc, 1-2, 10-11 ve, 9 ventilation, 8 Venture, 9 Verify, 8 voltage, 7 Volume, 1-18 W WA, 9 Water, 1-2 water, 1 Way, 9 Weather, 17-18 weatherproof, 1 Index Weight, 13-17 WeightFrame, 12, 18 well, 1 West, 9 Westampton, 9 Westport, 9 WFDN, 3, 5-6 WGDN, 3, 5 when, 1-2 where, 1-2 while, 8 wide, 2 width, 12 Windsor, 9 wire, 3-5, 12-18 witch, 9 with, 1-2, 5-10, 17-18 WJDN, 3, 5 WKDN, 4, 6 WL, 3-4 WLDN, 4, 6 WLG, 6 WNDN, 4, 6 Wood, 9 www, 1-18 X XFDN, 3, 5, 17 ximu, 13 XJDN, 3, 5, 17 XKDN, 4, 6, 18 XLDN, 6, 18 XMCN, 4, 6, 18 XNDN, 4, 6, 18 XPBD, 8 XPDBB, 8 Y York, 9 your, 9 Z Zero, 8 Zone, 8 Þ þNot, 12, 16 þXFDN, 2