SECTION 262816 – ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 1.1 1.5 Product Data: For each product specified including disconnect switches, enclosed circuit breakers, fuses, and accessories. QUALITY ASSURANCE A. Source Limitations: Obtain disconnect switches and enclosed circuit breakers from one source and by a single manufacturer. B. Listing and Labeling: Provide products specified in this Section that are listed and labeled. The Terms "Listed" and "Labeled" shall be as defined in the NFPA 70, Article 100, by a testing agency acceptable to the authorities having jurisdiction and marked for the intended use. C. Standards: Comply with applicable NEMA and UL Standards. COORDINATION A. PART 2 2.1 This Section includes individually mounted safety switches and enclosed circuit breakers used for the service disconnect switches, feeder and equipment disconnect switches, feeder and branch-circuit protection, and motor disconnect switches. SUBMITTALS A. 1.4 Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections apply to this Section. SUMMARY A. 1.3 GENERAL RELATED DOCUMENTS A. 1.2 262816/1 Coordinate layout and installation of safety switches, enclosed circuit breakers, and components with other construction that penetrates walls or is supported by them, including electrical and other types of equipment, raceways, piping, and encumbrances to workspace clearance requirements. PRODUCTS MANUFACTURERS A. Manufacturers: Subject to compliance with requirements, provide disconnect switches and fuses by one of the following: 1. Fusible Switches: a. Eaton Corp.; Cutler-Hammer Products. b. General Electric Co.; Electrical Distribution and Control Division. c. Siemens Energy & Automation, Inc. d. Square D Corp.; Groupe Schneider FRED HAAS TOYOTA WORLD JJA, INC. PROJECT NO. 3916037.010 SECTION 262816 – ENCLOSED SWITCHES AND CIRCUIT BREAKERS 2. 3. 2.2 2.3 2.4 262816/2 Fuses: a. Bussmann b. Gould-Shawmut c. Littlefuse Enclosed Circuit Breakers: a. Eaton Corp.; Cutler-Hammer Products b. General Electric Co.; Electrical Distribution and Control Division. c. Siemens Energy & Automation, Inc. d. Square D Corp.; Groupe Schneider DISCONNECT SWITCHES A. Enclosed, Fusible Switch: NEMA Type HD clips to accommodate specified fuses, enclosure consistent with environment where located. B. Disconnect Switch Features and Accessories: Standard frame sizes, trip ratings, and number of poles. 1. Handle: Lockable with two padlocks and interlocked with cover in CLOSED position. 2. Lugs: Mechanical style suitable for number, size, trip ratings, and material of conductors. FUSES A. Motor and Transformer Branch Circuits: Class RK1, time delay. B. Other Branch Circuits: Class RK5, non-time delay. ENCLOSED CIRCUIT BREAKERS A. Molded-Case Circuit Breaker: NEMA AB 1 with interrupting capacity to meet available fault currents and lockable with two padlocks. Molded-case circuit breakers shall be thermal-magnetic with inverse time-current element for low-level overloads, and instantaneous magnetic trip element for short circuits. Adjustable magnetic trip setting for circuit-breaker frame sizes 200 amperes and larger. B. Molded-Case Circuit Breaker Features and Accessories: Standard frame sizes, trip ratings, and number of poles. 1. Lugs: Mechanical style suitable for number, size, trip ratings, and material of conductors. 2. Shunt Trip: 120 V trip coil energized from separate circuit. 3. Auxiliary Switch: One single-pole-double-throw (SPDT) switch with “a” and “b” contacts; “a” contacts mimic circuit breaker contacts, “b” contacts operate in reverse of circuit breaker contacts. FRED HAAS TOYOTA WORLD JJA, INC. PROJECT NO. 3916037.010 SECTION 262816 – ENCLOSED SWITCHES AND CIRCUIT BREAKERS 2.5 ENCLOSURES A. PART 3 3.1 3.2 Applicable NEMA standards to meet environmental conditions of installed location. 1. Indoor Locations: NEMA, Type 1 2. Outdoor Locations: NEMA, Type 3R. 3. Other Wet or Damp Indoor Locations: NEMA, Type 4. 4. Hazardous Areas: NEMA, Type suitable for the Division, Class, and Group of the hazardous environment. EXECUTION INSTALLATION A. Install disconnect switches and circuit breakers level and plumb in locations as indicated, according to manufacturer's written instructions, and with proper working clearances. B. Connect disconnect switches circuit breakers, and components to wiring system and to ground as indicated and instructed by manufacturer. Tighten electrical connectors and terminals according to manufacturer's published torque-tightening values. Where manufacturer's torque values are not indicated, use those specified in applicable UL Standards. C. Identify each disconnect switch or enclosed circuit breaker according to requirements specified in other Division 26 Specification Sections. D. Install fuses in fusible devices as indicated. Arrange fuses so fuse ratings are readable without removing fuse. E. Install typewritten labels on the inside door of each fused switch to indicate fuse replacement information including fuse classification, ampacity, and manufacturer’s part number. CLEANING A. 3.3 262816/3 After completing system installation, including outlet fittings and devices, inspect exposed finish. Remove burrs, dirt, and construction debris and repair damaged finish including chips, scratches, and abrasions. ACCESSORIES A. Spare Fuses: Furnish quantity equal to 20 percent of each fuse type and size installed, but not less than 1 set of 3 of each type and size. B. Cabinet: Wall-mounted, 0.05-inch thick steel unit with full-length, recessed piano-hinged door with key-coded cam lock and pull. 1. Size: Adequate for orderly storage of spare fuses specified with 15 percent spare capacity minimum. 2. Finish: Gray, baked enamel. FRED HAAS TOYOTA WORLD JJA, INC. PROJECT NO. 3916037.010 SECTION 262816 – ENCLOSED SWITCHES AND CIRCUIT BREAKERS C. 262816/4 3. Identification: Stencil legend "SPARE FUSES" in 1-1/2-inch letters on door. 4. Fuse Pullers: For each size fuse. Chart: Furnish a fuse chart affixed to the inside of the spare fuse cabinet indicating the fuse classification, ampacity, and manufacturer’s part number of the fusing for each piece of equipment. END OF SECTION 262816 FRED HAAS TOYOTA WORLD JJA, INC. PROJECT NO. 3916037.010