Vaisala INTERCAP® Humidity and Temperature Transmitter Series HMW80 INSTALLATION 1. Find a suitable mounting location for the transmitter. The conditions at the location should represent well the area of interest. NOTE Do not install the transmitter on the ceiling. Avoid placing the transmitter near heat sources, ventilation, and direct sunlight. 2. 3. 4. Use the mounting holes to attach the mounting base securely. Use at least two screws (not included). The arrow on the mounting base must point straight up after installation. Proper orientation is important, so that air will flow through the vents on the bottom and top. Connect the wiring to the screw terminals on the mounting base. The supply voltage and terminal assignments are model-specific; see Wiring on page 2. After completing the wiring, connect the cover over the mounting base. Dimensions (in mm) 81 76.9 9 5 59 32.4 20 Ø4.4 123.7 127.3 Ø4.4 77.9 5.5 60.3 24 M211328EN-C _______________________________________________________________________ 1 Quick Guide ____________________________________________________________________ HMW80 WIRING HMW82 -T +T -RH +RH mA 4...20 mA (0 ... 100% RH) mA 4...20 mA (-5 ... +55 ºC) Power supply 10 ... 28 VDC RL = 0 ... 500 Ω Power supply 10 ... 28 VDC RL = 0 ... 500 Ω You must connect the RH channel of the HMW82, even if you only want to measure temperature. Connecting the T channel is optional. HMW82P100 2 Pt100 1 1 t+ -T +T -RH +RH mA 4...20 mA (0 ... 100% RH) mA 4...20 mA (-5 ... +55ºC) Power supply 10 ... 28 VDC RL = 0 ... 500 Ω HMW82P100 Includes a passive Pt100 temperature sensor (Class F 0.1 IEC 60751) with a 3-wire connection. Power supply 10 ... 28 VDC RL = 0 ... 500 Ω TMW82 -T +T mA Power supply 10 ... 28 VDC RL = 0 ... 500 Ω Leave the two terminals on the left unconnected. 4...20 mA (-5 ... +55 ºC) © Vaisala 2016. All rights reserved. _______________________________________________________ 2 Quick Guide ____________________________________________________________________ HMW80 HMW83 -RH +RH -T +T -VS +VS V 0...10 V (0...100 %RH) Power supply 15 ... 35 VDC or 24 VAC ±20% RL = 10 kΩ min. -RH +RH -T +T -VS +VS V 0...10 V V V 0...10 V (-5...+55 ºC) Power supply 15 ... 35 VDC or 24 VAC ±20% RL = 10 kΩ min. 0...10 V Recommended wiring for long cables. 3-wire connection with -VS as common ground. Not recommended if cable resistance is more than 2.5 Ω. TMW83 -T +T -VS +VS Power supply 15 ... 35 VDC or 24 VAC ±20% RL = 10 kΩ min. V 0...10 V (-5 ... +55 ºC) Recommended wiring for long cables. -T +T -VS +VS V 0...10 V Power supply 15 ... 35 VDC or 24 VAC ±20% RL = 10 kΩ min. 3-wire connection with -VS as common ground. Not recommended if cable resistance is more than 2.5 Ω. © Vaisala 2016. All rights reserved. _______________________________________________________ 3