Marine Module - North Shore Safety

advertisement
LineGard
NORTH SHORE SAFETY
Installation, Testing, and Operating Procedures
Ground
Fault Circuit
ELCI
MARINE
MODULE
IMPORTANT!
Please read all the information on this sheet.
SAVE THESE INSTRUCTIONS!
NOTICE
BEFORE USING READ INSTRUCTIONS COMPLETELY. TO BE
INSTALLED BY A QUALIFIED ELECTRICIAN IN ACCORDANCE
WITH NATIONAL AND LOCAL ELECTRICAL CODES AND THESE
INSTRUCTIONS.
CAUTION!
RISK OF ELECTRIC SHOCK, BURN, OR EXPLOSION.
DISCONNECT POWER BEFORE INSTALLING. NEVER WIRE
ENERGIZED ELECTRICAL COMPONENTS. FAILURE TO DO SO
MAY CAUSE SEVERE SHOCK, PERSONAL INJURY, OR DEATH.
NOTICE





ELCIs are required onboard all new manufactured boats
(per ABYC E-11) to mitigate “electric shock drowning”
associated with ground fault leakage incurred by boats
into marina waterways. (Effective 12-31-2012).
Marine ELCIs must meet the requirements as outlined in
ABYC E-11 Electrical Systems Onboard Boat (11.11) and
ABYC environmental considerations for apparatus
onboard boat (S-31) as well as requirements outlined in
UL 943 and UL 1053. Trip level is < 30mA and trip time
is < 100mS.
Unit is entirely potted and is ignition protected.
Marine Module is adaptive to marine flip-seals
produced by: Hubbell Marine or Marinco Marine.
Housing meets marine environmental considerations of
ABYC S-31 standard.
ELCI PROTECTION – WARNING!
 Equipment Leakage Circuit Interrupter is a
safety device under normal use and it is not
intended to promote activity at elevated risk.
 An ELCI is a device intended to mitigate ground
fault leakage and provide protection of
equipment (i.e. boats).
 Use only within the specified operating
parameters (failure to do so may result in
bodily injury).
 Consult a licensed electrician for assistance on
installation and repairs.
 Do not use this ELCI if it fails to function as
instructed. Never attempt to tamper with this
device.
 This ELCI does not provide protection against
shocks caused by holding both current carrying
conductors.
 This ECLI does not provide protection against
electrical shocks generated by the conductors
supplying power to the device.
Note: primary feed to ELCI is live even when ELCI
is tripped. Unit should be powered down at line
(supply) side breaker before servicing load side of
ELCI.
NORTH SHORE SAFETY’S TWO-YEAR LIMITED MANUFACTURER’S WARRANTY
North Shore Safety warrants to the consumer its offering of LineGard Ground Fault Circuit Interrupters (GFCIs) to be free from defects in materials
and workmanship under normal use and service for a period of two years from the manufacture date. North Shore Safety, at its option will repair
or replace the defective GFCIs without charge within a two year period from the date of manufacture, provided that the defect occurred during
normal use and was installed according to all published instructions. All returns must be authorized by a North Shore Safety representative. In the
event of product failure please contact a North Shore Safety representative at 1-440-205-9188 to obtain a Return Goods Authorization Number
(RGA) prior to returning any product to North Shore Safety. North Shore Safety will refuse any item if prior Return Goods Authorization has not
been granted. Defective units must be returned prepaid freight, with a description of the problem, and with an attached RGA number referenced
to the Quality Assurance Dept., North Shore Safety, Ltd., 7335 Production Drive, Mentor, OH 44060. Determination of Warranty compliance is
solely at the discretion of North Shore Safety and North Shore Safety's disposition is final.
Disclaimer
North Shore Safety will not be liable, directly or indirectly, for any cost whatsoever associated with installation or removal of any device, or for any
personal injury, property damages, or incidental, indirect, or consequential damages of any kind whatsoever as a result of any defective
device. The exclusive remedy under this Warranty is the repair or replacement of the defective device. In no case shall North Shore Safety's
liability exceed the net purchase price. This Warranty is void if the device is not properly installed, tampered with, opened, abused, or not used
according to label instructions and ratings, and/or published specifications.
7335 Production Drive
Mentor, OH 44060

Phone: 440-205-9188
Fax: 440-205-9187
sales@nssltd.com
www.nssltd.com
LineGard
NORTH SHORE SAFETY

Installation, Testing, and Operating Procedures
Ground
Fault Circuit
ELCI
MARINE
MODULE
DANGER: HAZARD OF ELECTRICAL SHOCK, BURN, OR EXPLOSION. Disconnect power at main power feed before the
start of installation. Failure to do so may cause severe shock, personal injury, or death
Ø1.96
Ø1.50
.710 DIA. LARGE ENOUGH
FOR (3) 6GA. WIRES
0.007
2.79
NEUTRAL OR L2 (WHITE OR RED) TO BREAKER LINE SIDE NEUTRAL OR L2
HOT (BLACK) TO BREAKER LINE SIDE HOT OR L1
SHUNT (YELLOW) TO BREAKER AUXILIARY SWITCH
DIA.
2.66
DIA.
Ø0.15
(2) PLACES
1.85
0.66
RECOMMENDED PANEL CUT-OUT
1.85
1.32
M3.0 X .5 THREADED
BRASS INSERTS FOR
MOUNTING (2) PLACES
2.35
MODULE CONTROL CONDUCTORS
NEUTRAL (WHITE) TO BREAKER LINE SIDE NEUTRAL
HOT (BLACK) TO BREAKER LINE SIDE HOT
SHUNT (YELLOW) TO BREAKER AUXILIARY SWITCH
120 VAC APPLICATIONS: (H,N,G)
LINE: FROM POWER
SUPPLY (SOURCE)
}
NEUTRAL (WHITE)
NEUTRAL (WHITE)
HOT (BLACK)
HOT (BLACK)
TO BREAKER
LINE INPUT
USED IN CONJUNCTION
WITH A SENSATA LEL
SERIES 2 POLE BREAKER
MODULE CONTROL CONDUCTORS
240 VAC APPLICATIONS: (L1,L2,G)
(L1,N,G) EUROPE - ELEVATED
240VAC
LINE: FROM POWER
SUPPLY (SOURCE)
L1 (BLACK) TO BREAKER LINE SIDE L1
L2 (RED) TO BREAKER LINE SIDE L2
SHUNT (YELLOW) TO BREAKER AUXILIARY SWITCH
L1 (BLACK)
L1 (BLACK)
L2 (RED)
N (EUROPE)
L2 (RED)
N (EUROPE
}
TO BREAKER
LINE INPUT
USED IN CONJUNCTION
WITH A SENSATA LEL
SERIES 2 POLE BREAKER
MODULE CONTROL CONDUCTORS
L1 (BLACK) TO BREAKER LINE SIDE L1
NEUTRAL (WHITE) TO BREAKER LINE SIDE NEUTRAL
SHUNT (YELLOW) TO BREAKER AUXILIARY SWITCH
120/240 VAC APPLICATIONS:
(L1,L2,N,G)
LINE: FROM POWER
SUPPLY (SOURCE)
L1 (BLACK)
L2 (RED)
L2 (RED)
NEUTRAL
SYSTEM NEUTRAL- MAY OR MAY
NOT REQUIRE A BREAKER POLE
CONTACT: CONSULT FACTORY FOR
DETERMINATION
USED IN CONJUNCTION
WITH A SENSATA LEL
SERIES 2 OR 3 POLE
BREAKER
NOTES:
1. CIRCUIT BREAKER LINE / LOAD MAY BE AT OPPOSITE ENDS.
2. L1 (BLACK WIRE) SHALL ALWAYS BE CONNECTED TO THE AUX SWITCH AND SHUNT POLE.
3. SAFETY GROUND IS NOT FED THROUGH SENSING CORE BUT IS BYPASSED TO BOAT SYSTEM SAFETY GROUNDING POINT.
IMPORTANT:
1.
2.
3.
4.
5.
6.
7.
READ ALL THE INSTRUCTIONS IN THIS LEAFLET AND ON THE DEVICE LABEL.
IDENTIFY ALL THE FEATURES AND WIRES (SEE DRAWINGS).
IDENTIFY MODULE WIRES.
VERIFY THAT THE RATINGS ON THE DEVICE INCLUDING BREAKER MATCH YOUR FIELD LINE
RATINGS.
STRIP WIRES TO 3/8”, OR AS RECOMMENDED FOR YOUR CONNECTIONS: (MODULE MAY
INCLUDE FIELD TERMINATIONS). MODULE SUPPLY MUST BE TERMINATED IN CONJUNCTION
WITH AND IN COMPLIANCE OF ABYC E-11 AND INSTRUCTIONS PROVIDED BY SENSATA
BREAKER INSTRUCTIONS.
CHOOSE THE RIGHT WIRING APPLICATION (120VAC, 240VAC USA, 240VAC EUROPE, OR SPLIT
PHASE 120/240VAC) AND CONNECT WIRES ACCORDING TO THE DRAWINGS.
PLACE SUPPLIED TEST INSTRUCTION LABEL IN CLOSE PROXIMITY TO.
TEST INSTRUCTIONS
THE EQUIPMENT LEAKAGE SENSING MODULE MOUNTING AS SHOWN BELOW:
ELCI SENSING MODULE
TEST BEFORE EACH USE
NORMAL OPERATING STATE – SENSING
DEVICE GREEN LED IS “ON” AND CIRCUIT
BREAKER IS AT “ON” POSITION
STEP 1: PRESS “TEST” BUTTON: GREEN LED
SHOULD GO “OUT” AND RED LED
SHOULD START “BLINKING”. CIRCUIT
BREAKER SHOULD TRIGGER TO “OFF”
POSITION
STEP 2: IF SENSING DEVICE LED OR BREAKER
DOES NOT TRIP OR CHANGE STATE:
“DO NOT USE” CONSULT AN
ELECTRICIAN FOR ASSISTANCE
STEP 3: PRESS “RESET” BUTTON: RED LED
SHOULD TURN “OFF” AND GREEN LED
SHOULD TURN ON.
STEP 4:MANUALLY RESET (SWITCH) CIRCUIT
BREAKER TO “ON” POSITION TO
RESTORE CIRCUIT POWER
:
WARNING!
IF ABOVE TESTS FAILS, DO NOT USE THIS
ELCI. CONSULT A QUALIFIED ELECTRICIAN
FOR REPAIR OR REPLACEMENT.
7335 Production Drive
}
L1 (BLACK)
Mentor, OH 44060
Phone: 440-205-9188
TO BREAKER
LINE INPUT
TESTING AND TROUBLESHOOTING
NORMAL OPERATING STATE – SENSING MODULE DEVICE GREEN LED IS “ON” AND CIRCUIT BREAKER IS
AT “ON” POSITION.
STEP 1: PRESS “TEST” BUTTON: GREEN LED SHOULD GO “OUT” AND RED LED
SHOULD START “BLINKING”. CIRCUIT BREAKER SHOULD TRIGGER TO
“OFF” POSITION.
STEP 2: IF SENSING DEVICE LED OR BREAKER DOES NOT TRIP OR CHANGE
STATE: “DO NOT USE” CONSULT AN ELECTRICIAN FOR ASSISTANCE OR REPLACEMENT.
STEP 3: PRESS “RESET” BUTTON: RED LED SHOULD TURN “OFF” AND GREEN
LED SHOULD TURN ON.
STEP 4: MANUALLY RESET (SWITCH) CIRCUIT BREAKER TO “ON” POSITION TO
RESTORE CIRCUIT POWER.
WARNING:
IF ABOVE TESTS FAILS, DO NOT USE THIS ELCI.
CONSULT AN ELECTRICIAN FOR ASSITANCE OR REPLACEMENT.
Fax: 440-205-9187
sales@nssltd.com
www.nssltd.com
LineGard
NORTH SHORE SAFETY
Installation, Testing, and Operating Procedures
Ground
Fault Circuit
ELCI
MARINE
MODULE
TYPICAL WIRING DIAGRAMS
CIRCUIT
BREAKER
LOAD
PART #
PGFM-111-B-A1-188
ORANGE SHUNT
JUMPER
(PROVIDED IN
ASSEMBLY KIT)
120VAC ELCI
SENSING MODULE
LINE
H
N
WHITE
BLACK
YELLOW (SHUNT)
SINGLE PHASE 120VAC (HOT, NEUTRAL, GRND)
GRND
CIRCUIT
BREAKER
LOAD
ORANGE SHUNT
JUMPER
(PROVIDED IN
ASSEMBLY KIT)
PART #
PGFM-211-B-A1-188
240VAC ELCI
SENSING MODULE
LINE
L1
L2
RED
BLACK
YELLOW (SHUNT)
SINGLE PHASE 240VAC (L1, L2, GRND)
GRND
CIRCUIT
BREAKER
LOAD
ORANGE SHUNT
JUMPER
(PROVIDED IN
ASSEMBLY KIT)
PART #
PGFM-111-B-A1-188
120VAC ELCI
SENSING MODULE
LINE
L1
L2
N
WHITE
BLACK
YELLOW (SHUNT
SPLIT PHASE 120/240VAC BREAKING NEUTRAL (L1, L2, N, GRND)
GRND
NOTES:
1. CIRCUIT BREAKER LINE/LOAD MAY BE AT OPPOSITE ENDS.
2. L1 (BLACK WIRE) WILL ALWAYS BE CONNECTED TO THE SAME POLE AS THE SHUNT COIL AND AUXILIARY SWITCH.
3. SAFETY GROUND IS NOT FED THROUGH SENSING CORE BUT IS BYPASSED TO BOAT SAFETY GROUNDING POINT.
7335 Production Drive

Mentor, OH 44060
Phone: 440-205-9188
Fax: 440-205-9187
sales@nssltd.com
www.nssltd.com