Install - Bodine

advertisement
BSL36 Cold-Pak
Installation Instructions
EMERGENCY LED DRIVER
CLASS 2 OUTPUT
120Vac or 277Vac Input
! IMPORTANT SAFEGUARDS !
WHEN USING ELECTRICAL EQUIPMENT, BASIC
SAFETY PRECAUTIONS SHOULD ALWAYS BE
FOLLOWED, INCLUDING THE FOLLOWING:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. Do not join converter connector until installation is complete and AC power is supplied to the emergency driver.
2. This product is for use with an emergency LED lighting load and supplies a minimum of 6.0 W of initial power, a
maximum rated current of 0.45 A, and a maximum voltage of 52 VDC in emergency mode for a minimum of
90 minutes.
3. Make sure all connections are in accordance with the National Electrical Code, Canadian Electrical Code, and any
local regulations. Caution: The standby rating should not be used to determine the suitability of the branch
circuit.
4. To reduce the risk of electric shock, disconnect both normal and emergency power supplies and converter
connector of the emergency driver before servicing.
5.This emergency driver is suitable for both factory or field installation. For field installation, please see the
instructions on page 2. 6.This product is suitable for use in damp locations where the ambient temperature is -20ºC minimum, +55ºC
maximum. Product is also suitable for installation in sealed and gasketed fixtures. Product is not suitable for
heated air outlets and wet or hazardous locations. “Maximum allowable case temp is 63ºC. See Product Unit
Label for measurement location”.
7. An unswitched AC power source is required (120 or 277 VAC, 60 Hz).
8. Do not install near gas or electric heaters.
9. Do not attempt to service the battery. A sealed, no-maintenance battery is used that is not field
replaceable. Contact the manufacturer for information on service.
10. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
11. Do not use this product for other than intended use.
12. Servicing should be performed by qualified service personnel.
13. Equipment should be mounted in locations and at heights where it will not be subjected to tampering by unauthorized personnel.
14.For Canadian applications, the output terminals should be in compliance with the accessibility requirement of the Canadian Electric Code.
SAVE THESE INSTRUCTIONS
Ni - Cd
THIS PRODUCT CONTAINS A RECHARGEABLE NICKEL-CADMIUM BATTERY.
THE BATTERY MUST BE RECYCLED OR DISPOSED OF PROPERLY.
05/24/16
© Philips Emergency Lighting
236 Mt. Pleasant Rd. • Collierville, TN USA 38017-2752 • Tech Support 888-263-4638 • Fax 901-853-5009 • www.philips.com/bodine
70100259
INSTALLATION
CAUTION: DO NOT JOIN CONVERTER CONNECTOR UNTIL INSTALLATION IS COMPLETE AND AC POWER IS
SUPPLIED TO THE EMERGENCY DRIVER.
NOTE: Make sure the necessary branch circuit wiring is available. An unswitched source of power is
required. The emergency driver must be fed from the same branch circuit as the AC driver.
This product is suitable for field installation with certain LED loads, including LED luminaires, DC voltage driven LED replacements
for fluorescent lamps, and others. To determine if your luminaire is eligible for field installation, go to the Design Lights on
sortium website (http://www.designlights.org) and search for your LED load by model name or model number. If found in the
database, these products are pre approved to be installed together in the field or at a luminaire manufacturer. Prior to installation,
determine the system light output by doing the following:
1.Ensure the LED load’s rated power is greater than or equal to the power output of this emergency LED driver. This is to
ensure that this emergency product will not produce more power than the LED load can handle, thus ensuring that the
LED load will not be damaged when the system is in the emergency mode.
2.Verify that the forward voltage of the luminaire’s LED array is within the limits of this emergency LED driver. The forward
voltage of the LED array is commonly designated as Vf and should be found on the luminaire markings, in the luminaire
specifications, or imprinted directly on the LED arrays. If multiple LED arrays are to be driven, verify that the total forward voltage is within the limits of this product. Using a voltage meter, it may be possible to directly measure the
voltage across the LED arrays when operating from the AC driver.
3
UL Classified Emergency products can be paired with LED luminaires or retrofit kits if found in the Design Lights
Consortium database. Go to the Design Lights Consortium website (http://www.designlights.org) and search for your LED
system by model name or model number. If found in the database, these products are pre approved by UL to be installed
together in the field or at a luminaire manufacturer, provided steps are taken to ensure there will be sufficient light output in the end application.
You can estimate the egress lighting illumination levels by doing the following:
a. Find the efficacy of the LED load, which will be found in the Design Lights Consortium database. This number will be given in lumens per watt (lm/w).
b. Lumens can be calculated by multiplying the output power of the emergency LED driver by the efficacy of the LED load. In many cases the actual lumen output in emergency mode will be greater than this calculation gives, however it will provide a good estimate for beginning the lighting design of the system.
c. Using the results of this calculation and industry standard lighting design tools, calculate the anticipated illumination levels in the path of egress.
Lumens In Emergency Mode = Lumens per Watt of Fixture X Output Power of Choosen Product
________________(Lumens) = __________________(lm/W) X 6 (W)
NOTE: This product has been designed to reliably interface with a wide selection of LED loads and is electrically compatible
with every simple LED array that meets criteria 1 and 2 above. However, compatibility cannot be guaranteed with all current and
future LED systems. Compatibility testing of the end-use system is suggested. Please contact the factory with any questions.
After installation, it will be necessary to measure the egress lighting illumination levels to ensure it complies with national,
state, and local code requirements.
Installation of this emergency LED driver will vary based on
the luminaire type, however, generally follow these steps.
STEP #1
INSTALLING THE EMERGENCY DRIVER
> Disconnect AC power from the LED luminaire.
>Mount the emergency LED driver by the mounting tabs using the supplied screws. The luminaire’s installation
instructions may provide guidance on the recommended mounting location.
>The emergency LED driver may be remote mounted from the luminaire. If used in conjunction with an AC driver, this
distance is up to half the distance the AC driver manufacturer recommends remote mounting the AC driver from the LED
Load. If used without an AC driver, please contact the factory.
> Mounting Height: This product meets or exceeds the NFPA minimum light requirements with all loads, down to the
smallest rated lamp load, at heights up to 7.17ft (2.2m). Many factors influence emergency illumination levels, such as
the lamp load selected, luminare design, and environmental factors therefore end use verification is necessary. For field
installations, when the attached luminaire is mounted at heights greater than 7.17ft (2.2m), the level of illumination
must be measured in the end application to ensure the requirements of NFPA 101 and local codes are satisfied.
2
STEP #2a
Fixture or
Test/Monitor Plate
INSTALLING THE 2W-ITS ON FIXTURE SURFACE
>Mount the supplied 2W-ITS (2 wire illuminated test switch) in a location that is
visible and accessible by maintenance personnel. The 2W-ITS mounts through a
½” hole which may need to be made in the luminaire or could come pre-punched
by the luminaire supplier.
2 Wire
Illuminated
Test Switch
Hex Nut
Violet
Brown
>Wire the test switch per wiring diagrams provided on these instructions.
>If wired correctly, the 2W-ITS indicator light should be ON when AC power is
supplied to the fixture and the converter connector is closed, indicating that the
emergency inverter battery is charging. After installing, mark with the "PUSH TO
TEST" and "CHARGING INDICATOR LIGHT" labels.
Drill or Punch
a 1/2” Hole
2W-IP67 Test Switch
Fixture
Note: The BSL36 Cold-Pak can also be supplied with an IP67 rated test switch intended for mounting on the fixture surface.
Illuminated
Test Switch
Push to Test
STEP #2b
INSTALLING THE 2W-ITS ON A BALLAST CHANNEL COVER
> Drill or punch a 7/8 inch hole in the ballast channel cover. Insert the large
flanged bushing included with the parts kit. Insert the plastic tube into the
large flanged bushing. Slide the 2W-ITS tube up or down to adjust the height
and visibility of the charging indicator light.
Plastic Tube
2W-ITS
Assembly
Components
Tie Wrap
White
Bushing
> Slide the plastic tube up or down to adjust the height and visibility of the
charging indicator light. If the tube is too long, cut the plastic tubing to
necessary length.
2 Wire Illuminated Test Switch
> After cutting the tube to the proper length, assemble the 2W-ITS.
To assemble the 2W-ITS Assembly:
• Feed the 2W-ITS leads through the plastic tubing.
• Insert the white bushing in the opposite end of tube from the 2W-ITS body.
• Pull switch leads and use provided tie wrap to secure leads snug against
white bushing.
• Unscrew hex nut to apply tension to leads.
> Wire the test switch per wiring diagrams provided on these instructions.
> If wired correctly, the 2W-ITS indicator light should be ON when AC power is
supplied to the fixture and the converter connector is closed, indicating that
the emergency inverter battery is charging. After installing, mark with the
"PUSH TO TEST" and "CHARGING INDICATOR LIGHT" labels.
STEP #3
PUSH TO TEST
PUSH TO TEST
WIRING THE EMERGENCY DRIVER
> Use the wiring diagram of page 4 to connect the emergency driver to the AC driver and LED load. Make sure all connections are in accordance with the National Electrical Code and any local regulations.
> After installation is complete, supply AC power to the emergency driver and join the converter connector.
> At this point, power should be connected to both the AC driver and the emergency driver, and the Charging Indicator Light should illuminate indicating the battery is charging.
> A short-term discharge test may be conducted after the emergency driver has been charged for one hour. Charge for 24 hours before conducting a long-term discharge test. Refer to OPERATION.
> In a readily visible location, attach the label "CAUTION - This Unit Has More Than One Power Connection Point.
To Reduce The Risk Of Electric Shock, Disconnect Both The Branch Circuit-Breakers Or Fuses And Emergency
Power Supplies Before Servicing."
3
OPERATION
During normal operation AC power is applied and the converter connector is closed, the charging indicator light is
illuminated, indicating that the battery is being charged. When power fails, the emergency LED driver automatically
switches to emergency power (internal battery), operating the LED load for a minimum of 90 minutes. When AC power is
restored, the emergency driver returns to the charging mode.
MAINTENANCE
Although no routine maintenance is required to keep the emergency driver functional, it should be checked periodically to
ensure that it is working. The following schedule is recommended:
1. Visually inspect the charging indicator light monthly. It should be illuminated.
2. Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds. The LED load should operate at reduced illumination.
3. Conduct a 90-minute discharge test once a year. The LED load should operate at reduced illumination for at least 90 minutes.
! REFER ANY SERVICING INDICATED BY THESE CHECKS TO QUALIFIED PERSONNEL !
2-Wire Illuminated Test Switch (2W-ITS)
Wiring Specification
The 2W-ITS may be remotely mounted up to 200 ft
from the BSL36 Cold-Pak Emergency Driver with wire
of 24 AWG or heavier
EMERGENCY DRIVER AND AC DRIVER MUST BE FED FROM THE SAME BRANCH CIRCUIT
TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER DRIVERS. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAM.
WIRING DIAGRAM
HOT
WALL SWITCH
~120 or ~277V
WHITE
COMMON
BLACK
AC Driver
LED (-)
LED (+)
WHITE
WHT/RED
SW Line IN
ORN/BLK
2W-ITS
VIOLET
VIOLET (+)
BROWN
BROWN (-)
CONVERTER
CONNECTOR
RED
WHITE
Cold-Pak
Emergency
LED
Driver
WHT/BLK
SW Line OUT
BLUE
AC Driver (+)
YELLOW
LED (+)OUT
YEL/BLK
LED (-) and AC Driver (-)
4
(+)
(-)
LEDLoad
Download