LES Series Surface Mount Edge-Lit Installation Instructions - Dual-Lite

TROUBLE SHOOTING
Exit does not light
•Check wiring connections.
•Secondary connection to LED light strip loose or missing.
RECYCLING INFORMATION
All thermoplastic parts are recyclable.
All cartons contain recycled materials.
Please recycle.
REVERSING EXIT PLAQUE ASSEMBLY
To reverse plaques on end mounted models
1. Remove end cap retaining screw
2.Slide plaque out of LED light strip extrusion
3.Rotate plaque
4. Slide plaque into LED light strip extrusion
5. Reinstall end cap
LES Series
Surface Mount Edge-Lit
LED Exit Signs
Installation Instructions
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1.Do not use outdoors.
2.Do not mount near heaters or hot surfaces.
3.Equipment should be mounted in locations and at heights where it will not readily be subjected to
tampering by unauthorized personnel.
4.The use of accessory equipment not authorized by the manufacturer may cause an unsafe condition.
5.Do not use this equipment for other than its intended purpose.
6.Service of this equipment should be performed by qualified service personnel.
Dual-Lite l www.dual-lite.com • 701 Millennium Boulevard • Greenville, SC 29607 864-678-1000 • Fax 864-678-1415
A Hubbell Lighting Inc. brand with representatives’ offices in principal cities throughout North America.
Copyright© Dual-Lite, All Rights Reserved - Specifications subject to change without notice.
Printed in U.S.A.
0601651_B 3/08
SAVE THESE INSTRUCTIONS
Liteforms LES Series LED Exit Sign Installation Instructions
FINAL ASSEMBLY
Ceiling or End Mount
1. Bring utility AC conductors (including building
ground) through center hole in universal adaptor plate
(provided).
2. Mount adaptor plate to electrical box using screws
supplied with electrical box.
3. Connect exit wires to utility conductors using installer
supplied wire nuts or other approved hardware.
For 120VAC - connect black and white leads
For 277VAC - connect red and white leads
Connect green canopy wire to building ground
IMPORTANT: Cap off unused red or black wire lead
CAUTION
Always cap off
unused red or black
lead.
FINAL ASSEMBLY
Wall Mount
4. Push all connection hardware and wiring through
center hole in adaptor plate into electrical box.
5. Secure mounting canopy to adaptor plate using
captive screws in canopy.
6. Apply utility power and check operation.
CEILING MOUNT MODELS
1. Attach pigtail leads (provided) to utility AC
conductors.
For 120VAC - connect black and white leads
For 277VAC - connect red and white leads
2. Feed all leads (including building ground) through
center hole in universal adaptor plate (provided).
3. Mount adaptor plate to electrical box using screws
supplied with electrical box.
4. Connect green canopy wire to building ground
conductor using installer supplied wire nuts or other
approved hardware. Push connector through adaptor
plate into electrical box.
5. Feed pigtail leads from electrical box through center
slot in mounting canopy.
Universal Adaptor Plate
WALL MOUNT MODELS
Quick Connector
Terminals
(2 Supplied)
Mounting Canopy
CAUTION
Always cap off unused red or black lead.
Universal Adaptor Plate
See instructions on back page for
reversing plaques (if required) on end
mounted models.
END MOUNT MODELS
6. Secure mounting canopy to adaptor plate using
captive screws in canopy.
7. Plug AC “common” exit wire (white) into one quick
connector terminal (provided). Plug AC “line” exit
wire (120VAC = black)(277VAC = red) into second
quick connector terminal (provided). Plug corresponding pigtail leads from electrical box
into exit wire quick connector terminals.
IMPORTANT: Cap off unused red or black wire lead
from exit using installer supplied wire nut or other
approved connector.
8. Push all connection hardware and wiring through
center hole in canopy into electrical box.
9. Attach exit assembly to canopy connection bracket
using hardware supplied.
10. Apply utility power and check operation.
Canopy Connection
Bracket
CAUTION
Always cap off
unused red or black
lead.
Universal Adaptor Plate
Mounting Canopy