55 CHAPTER 3 STATIC VAR COMPENSATOR FOR VOLTAGE SECURITY ENHANCEMENT 3.1 INTRODUCTION In the previous chapter, generation rescheduling was considered for voltage stability enhancement. This chapter explores the application of static VAr compensator (SVC) for voltage security enhancement. SVC provides fast acting dynamic reactive compensation for voltage support during contingency events which would otherwise decrease the voltage for a significant length of time. Identification of suitable location is very much essential to get the benefit of the SVC. In this work, the L-index of the load buses, explained in the previous chapter is used to identify the weak buses and hence the location of SVC. To identify the optimal setting of the control variables, the problem is formulated as a multi-objective optimization problem, with minimization of the voltage stability margin and the minimization of investment cost of the VAr sources as the objectives. MOGA is applied to solve this complex multiobjective optimization problem. 3.2 STRUCTURE AND MODELING OF STATIC VAR COMPENSATOR (SVC) SVC is a shunt connected static var generator or consumer whose output is adjusted to exchange capacitive or inductive so as to maintain or control specific parameters of electrical power system, typically, a bus voltage. The main function is to regulate the voltage at a given bus by controlling its equivalent reactance. SVC is built of reactors and capacitors, 56 controlled by thyristor controlled reactors (TCR) which are parallel with capacitor bank. Basically it consist of a fixed capacitor (FC) and a TCR. As shown in Figure 3.1 it is connected in shunt with the transmission line through a transformer. The model considers SVC as shunt variable susceptance, BSVC which is adapted automatically to achieve the voltage control. The TCR consists of a fixed reactor of inductor L and a bi-directional thyristor valve. The thyristor valves are fired symmetrically in an angle of a control range of 90o to 180o, with respect to the SVC voltage. This type of SVC can be considered as a controllable reactive admittance which, when connected to the ac system, faithfully follows (within a given frequency band and within the specified capacitive and inductive ratings) an arbitrary input (reactive admittance or current) reference signal. Figure 3.2 shows the V-I characteristics of the SVC. The V-I characteristic represents the steady state relationship. A typical V-I characteristic determines the range of inductive and capacitive current supplied by the SVC. The V-I characteristic of the SVC indicates that regulation with a given slope around the nominal voltage can be achieved in the normal operating range defined by the maximum capacitive and inductive currents of the SVC. Line voltage BSVC Control circuit FC TCR Input signals Figure 3.1 SVC employing FC - TCR 57 VT Vmax I I I LC max Capacitive 0 LL max Inductive Figure 3.2 V-I Characteristics of the SVC In the active control range, current/susceptance and reactive power is varied to regulate voltage according to a slope (droop) characteristic. The slope value depends on the desired sharing of reactive power production between various sources, and other needs of the system. The slope is typically 1-5 percent. At the capacitive limit, the SVC becomes a shunt capacitor. At the inductive limit, the SVC becomes a shunt reactor (the current or reactive power may also be limited). The TCR at a fundamental frequency can be considered to act like a variable inductance XTCR is given as: X TCR where 2( ) sin 2 (3.1) XTCR is the reactance caused by the fundamental frequency without thyristor control and is the firing angle. Hence, the total equivalent impedance of the controller can be written as X SVC XC X L XC [ 2( ) sin 2 ] X L (3.2) 58 By controlling the firing angle of of the thyristors (the angle with respect to zero crossing of the phase voltage), the device is able to control the bus voltage magnitude current. The amount of reactive power consumed by the inductor L for =90o, the inductor is fully on, whereas for =180o the inductor is off. The basic control strategy is typically to keep the transmission bus voltage within certain narrow limits defined by a controller droop and the firing angle limits (90o< < 180o). Figure 3.3 represents the equivalent steady state model of the SVC. Figure 3.3 Equivalent Steady State Model of the SVC SVC model is developed with respect to a sinusoidal voltage, and can be written as I SVC jBSVC VK (3.3) Where the variable susceptance BSVC represents the fundamental frequency equivalent susceptance of all shunt modules making up the SVC as shown in Figure 3.3 . 59 Static var compensators are used by utilities in both transmission and distribution systems. The main function of SVC is to control the voltage at weak nodes in the system. Installation of SVC in load buses used for load compensation help in containing the voltage fluctuations, improve load power factor and also voltage profile. Installation of SVC in transmission networks helps to provide dynamic reactive power injection support to maintain the bus voltage close to the nominal value under varying load conditions and also improve voltage stability. SVC also provides fast response to control the bus voltage under disturbed conditions. 3.3 PLACEMENT OF SVC To improve the voltage stability level of the system, SVC has to be placed at the proper locations. To determine the best location, L-index is calculated as explained in the previous chapter. The bus with maximum Lindex value is the most vulnerable bus in the given system and there the compensator devices have to be placed. Weak buses are identified based on the L-index values of the load buses. The buses with high values of Lmax are the weak buses of the system from the voltage stability point of view. The Lindices are calculated for the system by running the power flow analysis. Computing L-index value for load buses (including the generator buses treated as PQ bus), it is found that the L-index values are higher at each bus by repeating the power flow with only one generator bus and other generator buses as PQ buses. Hence it is concluded that the number of buses makes a significant change in the L-indices results. If we take SVC bus as generator bus and compute the L-indices, we get L-index values reduced significantly compared to the SVC bus treated as load bus. With same compensation as obtained for maintaining the same voltage as in previous output, obtain the Lindices. These L-indices are higher at each bus compared to previous case when SVC bus was assumed as PV bus. This gives indication that while 60 computing L-indices, it is reasonable to treat SVC bus as load bus than generator bus. 3.4 PROBLEM FORMULATION With the increasing size of power system, there is a thrust on finding the solution to maximize the utilization of existing system and to provide adequate voltage support. VAr devices if placed optimally can be effective in providing voltage support, controlling power flow and in turn resulting into lower losses. The problem of voltage security enhancement is formulated as a multi-objective optimization problem. The objectives considered here are minimization of VAr cost and maximization of voltage stability margin. This is achieved by proper adjustment of real power generation, generator voltage magnitude, SVC reactive power generation of capacitor bank and transformer tap setting. Power flow equations are the equality constraints of the problems, while the inequality constraints include the limits on real and reactive power generation, bus voltage magnitudes, transformer tap positions and line flows. The expression representing the objective functions and the constraints are given below: 3.4.1 Objective functions The voltage security problem is to optimize the steady state performance of a power system in terms of one or more objective functions while satisfying several equality and inequality constraints. The objective functions considered in this work are given below: 3.4.1.1 Minimization of SVC devices cost Investment costs of SVC devices are broken into two components: fixed and variable cost. The fixed cost is comprised of the physical installation and additional equipment costs (such as switchgear and breakers). 61 The variable component is the procurement cost which depends on the amount of nominal reactive power installed at a system bus. Mathematically, this is stated as, NC (C fi Minimize F C C ci | Q ci | ) $ / hr (3.4) i 1 where Cfi is the fixed installation cost of the reactive power sources at the ith bus($) Cci is the cost of the SVC compensation devices at the ith bus ($/MVAr) Qci is the reactive compensation at the ith bus (MVAr) Nc is the number of possible buses for the installation of the compensation devices. 3.4.1.2 Voltage stability margin Minimize L max (3.5) This is presented in the previous chapter in section 2.2. Using equation (2.3) L-index values are calculated for all the load buses. The maximum of the L- indices give the proximity of the system to voltage collapse. 3.4.2 Problem constraints The minimization problem is subject to the equality constraints of the equations (2.6, 2.7) and the inequality constraints of the equations (2.8, 2.9) and (2.10, 2.11) of the previous chapter in section 2.3.2 and in section 62 2.3.3. In addition the SVC reactive power generation constraint is represented as follows: SVC reactive power generation limit min Q svc Q svc max Q svc ;i Nc (3.6) Aggregating the objectives and constraints, the problem can be mathematically formulated as a non- linear constrained multi-objective problem as follows: Minimize F T [ F C , Lmax ] (3.7) subject to the above constraints. Multi-objective Genetic Algorithm explained in the previous chapter is applied to solve the multi-objective security enhancement problem. 3.5 SIMULATION RESULTS To demonstrate the effectiveness of the proposed approach IEEE 30-bus system is considered. Case (i): Voltage security constrained OPF (VSCOPF) using GA Contingency analysis was conducted on the system by simulating single line outages to identify the critical contingencies. From the contingency analysis, it is found that the line outage 1-2 is the most severe one from the voltage security point of view and the system reached a maximum Lmax value of 0.2910 during this contingency state. The Lmax value of contingency 1-2 is included in the objective function of the OPF problem along with the base case fuel cost and the GA- based algorithm was applied to solve this voltage security constraint optimal power flow problem. Figure 3.4 shows the convergence diagram. The optimal control variable setting obtained in this case is tabulated in Table 3.1 along with the Lmax value. 63 Figure 3.4 Convergence curves of the VSCOPF Table 3.1 Result of VSCOPF Algorithm (IEEE 30-bus system) Control variables P1 P2 P5 P8 P11 P13 V1 V2 V5 V8 V11 V13 T11 T12 T15 T36 QC10 QC12 QC15 Variable setting 68.9229 MW 77.1429 MW 41.6667 MW 35.0000 MW 29.0476 MW 36.8889 MW 1.0500 P.U 1.0310 P.U 1.0262 P.U 1.0167 P.U 1.1 P.U 1.0238 P.U 0.9 0.9571 1.1 0.9857 4.2857 MVAr 5.0 MVAr 1.4286 MVAr 64 Table 3.1 (Continued) QC17 QC20 QC21 QC23 QC24 QC29 Cost Lmax 2.8571 5.0 5.0 5.0 5.0 2.8571 822.2797 0.1034 MVAr MVAr MVAr MVAr MVAr MVAr $/hr To assess the voltage security of the system, contingency analysis was conducted using the variable setting obtained in the base case and voltage stability constraint OPF. The maximum Lmax values corresponding to the four critical contingencies are given in Table 3.2. From the result it is observed that the Lmax index value has reduced appreciably for all contingencies in the voltage stability constraint OPF. This shows that the proposed algorithm has helped to improve the voltage security of the system. Table 3.2 Lmax under contingency state No Contingency Lmax(base case) Lmax(VSCOPF) 1 1-2 0.2910 0.1311 2 9-10 0.2176 0.1672 3 4-12 0.2152 0.1712 4 4-6 0.1932 0.1506 65 Case (ii) Multi-objective optimal power flow for voltage security enhancement Contingency analysis Next, the proposed MOGA approach was applied for solving the voltage security enhancement to IEEE 30-bus test system. L-index method is adopted here to identify the weak buses. The buses having high values of Lmax are the weak buses, which require reactive power support. For each contingency, L-index values are computed. According to the values, the most severe contingencies were the outages of lines (1-2), (4-12), (9-10), (6-7) and (28-27). L-indices are evaluated for the above severe contingencies and the first five buses with high values of L-index are identified for reactive power compensation. They are tabulated in Table 3.3. Finally, the common buses among the identified weak buses are selected for placing the SVC. From the weak bus identified, the candidate locations for placement of SVC are buses 30, 29,25,12,19. The main purpose of identifying the weak buses is to maintain control of voltages at these buses in particular to prevent voltage collapse. Here identifying weak buses can also give correct information to determine which buses are most severe and need to have new reactive power sources installed. The algorithm was run with minimization of SVC investment cost and Lmax value as the objectives. The initial population was randomly generated between the variable’s lower and upper limits. Fitness proportionate selection was applied to select the members of the new population. Blend crossover and non uniform mutation were applied on the selected individuals. The performance of MOGA for various crossover and mutation probabilities in the range 0.6-0.9 and 0.001-0.01 respectively was therefore evaluated. It was applied by considering several sets of parameters in order to prove its capability to provide acceptable trade-offs close to the 66 Pareto optimal front The optimal settings of the MOGA were obtained by the following parameters are given below: Generations : 50 Population size : 50 Crossover rate : 0.85 Mutation rate : 0.01 Figure 3.5 represents the Pareto-optimal front curve. It is worth mentioning that the proposed approach produces nearly 21 Pareto optimal solutions in a single run that have satisfactory diversity characteristics and span over the entire Pareto optimal front. From the Pareto front, two optimal solutions which are the extreme points to represent the minimum SVC investment cost and maximum voltage stability margin are noted. The optimal values of the control variable are given in Table: 3.4. This shows the effectiveness of the proposed approach in solving the optimal power flow problem. Table 3.3 Identification of weak buses Line outage Weak buses 1-2 3,30,29,12,25,27 4-12 12,14,19,29,30 9-10 25,30,27,26,24 6-7 12,19,30,9,29 28-27 30,29,25,24,21 67 Figure 3.5 Pareto Optimal Front Table 3.4 Control variables for IEEE 30- bus system Extreme Solutions Control variables Minimum installation cost solution P1 (MW) 29.9654 P2 (MW) 95.7833 P5 (MW) 48.9274 P8 (MW) 33.9137 P11 (MW) 24.2062 P13 (MW) 54.5317 V1 (P.U) 1.0479 V2 (P.U) 1.0749 V5 (P.U) 1.0852 V8 (P.U) 1.0665 V11 (P.U) 1.0931 V13 (P.U) 1.0959 T11 1.0750 T12 0.9750 T15 1.0750 T36 1.0250 SVC1(MVAr) 0.9750 SVC2(MVAr) 2.3796 SVC3(MVAr) 0.8512 SVC4(MVAr) 1.4825 SVC5(MVAr) 2.8413 Installation Cost($/hr) 515 Lmax 0.115 Maximum voltage stability margin solution 53.5209 88.1262 49.4162 34.9039 24.3695 41.8188 1.0704 1.0295 1.0188 0.9898 1.0776 1.0705 1.0968 0.9 0.9750 1.1 2.4912 0.8512 1.4829 2.8413 2.3731 550 0.0729 68 Thus the problem is formulated as a bi-objective optimization considering the minimization of SVC cost and the maximization of voltage stability margin as the conflicting objectives. MOGA has been applied to solve this multi-objective optimization problem. The results of MOGA are presented in the above Table 3.4.From this table it is observed that the cost obtained with maximization of voltage margin as objective is 550$/hr, whereas the cost of the pareto solutions with SVC cost as one of the objectives (multi-objective case) is less than this value. It is also observed that the non-dominated solutions are diverse and well distributed over the Pareto-front. 3.6 CONCLUSIONS This chapter has presented a MOGA algorithm approach to obtain the optimum values of the optimal power flow including the voltage security enhancement. It is considered as an optimization criterion, the minimization of SVC investment cost and the maximum voltage security enhancement. It is evaluated by L-index value. The effectiveness of the proposed method is demonstrated on IEEE 30-bus system with promising results. The performance of the proposed algorithm is performed well when it was used to characterize Pareto optimal front of the multi-objective power flow problem.