HHV Series “Hi-Vac” Vacuum Dehydrator

advertisement
888-910-7543
www.HENEKMFG.com
HHV Series “Hi-Vac” Vacuum Dehydrator
Process used for dehydrating and degasification of electrical insulating fluids to increase and maintain
their dielectric strength
As a result of rising cost of oils,
increasing environmental
regulations, liability and disposal
cost, and new stringent vacuum
HHV-1800
requirements for manufactures
warranties to .4 Torr @ 48hours, it
is no longer economical to replace
electrical insulating oils with new
fluid. Instead, proper treatment of
these fluids with our proven Hi-Vac
Series renews dielectric strength
and lowers residual water content
by restoring oils to their original
strength through vacuum
dehydration & purification.
Improvement of the entire insulating
media of power transformers is
obtainable with our HHV series High
New Transformer
Vacuum (Hi-Vac) Oil Purifier. Our design meets the operational,
economic, and environmental needs of industry and maintains the quality
of insulating oils at the time of initial impregnation, filling at the factory,
and maintains the same quality in field operation.
Our proven Hi-Vac provides reportable dehydration, degasification, and
filtration techniques that remove even trace amounts of water to less than
5PPM and gases to less than 0.25%. An easy to read flow chart is
provided on the electric panel and is superimposed over all switches,
buttons, and indicating/warning lights. Our Hi-Vac can be used as
stationary units or manufactured within a variety of trailer configurations
to be completely portable or self contained.
HENEK. • Houston, Texas 77075 • Ph: 713-943-7543 • Fax: 713-943-3213 • www.henekmfg.com • filters@henekmanufacturing.com
888-910-7543
www.HENEKMFG.com
Specifications
•Flow rates from 30 GPH to 3,000 GPH
(higher capacities upon request)
•Vacuum pump capacity to 3,000 CFM
(higher capacities upon request)
•Maximum vacuum pressure (blank off) to
0.01MM Hg (10 micron)
•Typical operating vacuum range during oil
purification from 0.5 MM Hg to 5MM Hg
•Full range of heater capacities available
including pre and post heaters
•Available in a variety of voltages to meet
your specific operating requirements
Features & Performance
Options
•Dehydration—At minimum oil temperatures of
minimum 80°F water removal begins up from 100
PPM to less than 5PPM
• Single button shut down
• Continuous Moisture-in-Oil Monitor
• Degasification—Reduce soluble air content in a
single pass from full saturation of approximately
• Inhibitor injection system
12% to less than .25% . Other gases in solution with
oil are also removed
• Compact Programmable Logic Controller (PLC)
• Pre-filter and polishing filter options with a full range
• Variable speed driven
of heater capacities
• Gallon meters
• Removes free & emulsified (total) water to less than
10 ppm, free & dissolved air & gases to 0.25% of
• Hose reels
total gas content. Varnishes, acids, resins, and
• Built in containment
oxidized agents using unique media
• Fullers earth, activated carbon, and activated
alumina filter systems available for stripping acids
•Pre & Post filtration from 150 to 1/2 micron
and surfactants
•Moisture Meters
• Full flow hydraulic relief valves
• Available in a wide range of options & skid
configurations
• Fully pre-piped, pre-wired, factory tested and shipped
for immediate installation
• Controls designed for manual or
fully automatic operation
• Capable of full integration into
monitoring & control systems
using Programmable Logic
Controller (PLC) options
• Electrical components enclosed
in NEMA 4 weatherproof
housing or NEMA 7 explosion
proof housing
• Easy to read flow chart is on the
electrical panel, over all
switches, buttons, and
indicating/warning lights
• Nitrogen Cold Trap Option
Hi-Vac - Enclosed in container for worldwide transportation
Field Service
Small Hi-Vac
HHV130911R5
Hi-Vac on gooseneck trailer
HENEK. • Houston, Texas 77075 • Ph: 713-943-7543 • Fax: 713-943-3213 • www.henekmfg.com • filters@henekmanufacturing.com
888-910-7543
www.HENEKMFG.com
HHV Series “Hi-Vac” Trailer Mounted
Equipment mounted in open and closed trailers for portability, security, and comfort
Our HHV Series of High Vacuum (Hi-Vac)
Dehydration Systems can perform transformer
oil processing on energized transformers up to
230 KV. They have processed millions of
gallons of oil, and prolonged the life of
thousands of transformers. Our large rigs
can perform hot oil reclamation on
transformers up to 50 gallons per minute, and
HIVAC 2400
because it's energized, the customer
never has to take an outage.
Auxiliary Equipment
• Roadworthy trailers in open or closed
construction up to 53ft long
• Trailer lighting
• Heating, A/C & Ventilation
• Operator’s quarters with work space,
lab, and furnishings
Control Room
• Fire Suppression System
• Under body storage
• Oil and vacuum hoses, quick couplings
• Multiple exits for safety
• Aluminum stairs with safety rails (hinged to
flip up in trailer for storage)
• Containment built in for environmental
safety
• Convenience outlets throughout trailer
• Diesel-Driven generator set for auxiliary
power
• Jib-Crane for hoisting
HENEK. • Houston, Texas 77075 • Ph: 713-943-7543 • Fax: 713-943-3213 • www.henekmfg.com • filters@henekmanufacturing.com
HENEK
HHV SERIES CHART
STANDARD SPECIFICATIONS
MODEL NO. & FLOW GPH
HHV-60
HHV-120
HHV-360
HHV-600
HHV-900
HHV-1200
HHV-1800
HHV-2400
Flow GPM
1GPM
2GPM
6GPM
10GPM
15GPM
20GPM
30GPM
40GPM
Heater capacity KW
6
12
16
32
48
64
96
128
Motor, HP, Oil Discharge Pump
1/3
1/3
1
1
2
2
3
3
Quantity Coaslecers HC-3135
1
2
5
10
12
14
20
24
Oil Discharge Pressure Range
Adjustable
Standard
Unit Range
—————
—————
—————
—————
—————-
 All Power calculations are for 480 Volts, 3 Phase, 50/60 HZ.
 Each Unit is equipped with an Internal Transformer to supply 120V Single Phase control voltage.
WEIGHTS AND DIMENSIONS
MODEL NO.
HHV-60
HHV-120
HHV-360
HHV-600
HHV-900
HHV-1200
HHV-1800
HHV-2400
Oil Inlet size NPT
1/2”
3/4”
1”
1 1/2”
1 1/2”
1 1/2”
2”
2”
Oil Outlet Size NPT
1/2”
1/2”
3/4”
1”
1 1/2”
1 1/2”
2”
2”
Vacuum Line Size (Main)
1- 1/2”
1-1/2”
3”
3”
4”
4”
6”
6”
Vacuum Line Size (Aux)
1-1/2”
1-1/2”
2”
2”
4”
4”
4”
4”
Approximate Height
66”
66”
84”
84”
84”
84”
90”
90”
Approximate Length
60”
72”
96”
96”
120”
120”
144”
168”
Approximate Width
48”
48”
60”
60”
60”
60”
72”
72”
Approximate Weight (lbs)
1550
1850
4050
4150
4550
4850
Call Factory
Call Factory
Skid Sizes Vary with Options
SIGNIFICANT NUMBERING SYSTEM - Notes


The Model Number identifies the major “Characteristics” and separates them with a dash mark for clarity.
Use the chart below to identify your specific HENEK Low Vacuum Purifier
HHV - Series Major Characteristics Identification
Product Series -
Flow (US GPH) -
HHV
600
See Chart
Vacuum System - Electrical Enclosure - Heat (KW) - Options - Options - Options
C
W
32
C= Vacuum Pump
W= Weather Proof
See Chart
L=Liquid Ring
Vacuum Pump
X = Explosion Proof
XX
-
XX
-
XX
List Options Alphabetically
HHV130911R5
HENEK. • Houston, Texas 77075 • Ph: 713-943-7543 • Fax: 713-943-3213 • www.henekmfg.com • filters@henekmanufacturing.com
888-910-7543
www.HENEKMFG.com
Cold Trap
Oil Wetness Determination Under Transformer Blank Off Conditions
During certain phases of transformer restoration it is of critical importance that
as much moisture as possible be removed from its internal sections. This
phase is called the “dry out” phase. The task is accomplished by attaching the
transformer to a vacuum pump/blower system at the auxiliary connection.
Functionality
When all leaks on the transformer are sealed to the lowest possible point,
vacuum can be pulled on the transformer internals. This is normally the area
of ½ to 1 torr (1/2 – 1 micron), the only flow that may enter the vacuum pump
must come from the transformer and pass through the cold trap. Any water in
the transformer will turn to a vapor (steam) under these low vacuum conditions
and freeze as it passes in the cold trap (temperature -80°F to -40°F). It should
also be noted that any other liquid contaminants in the transformer that can
boil at temperatures equal to or below water may also vaporize and pass
through the vacuum system and finally return to a liquid state and move into
the atmosphere or the vacuum pump oil.
When charged with liquid nitrogen and nitrogen gas, the cold trap is self
Skid mounted with containment
contained. It is electrically and pneumatically controlled by a single
temperature sensing device on the chiller side and is automated to reduce
liquid nitrogen consumption during the chilling
operation.
To thaw the collected water for measurement, the
cold trap is equipped with a hot water/glycol
solution tank that is heated by a manually activated
emersion heater. When activated, the heater
increases the temperature of the glycol solution to
a preset point before it cuts out and recycles. The
glycol tank is equipped with a circulating pump that
can be turned on manually to distribute the hot
glycol throughout the heating coils (approximately
Built into service vehicle
Nitrogen Purge Discharge
170°F). The ice is thawed and contained in the cold trap until it can be
measured.
HHV130911R5
HENEK. • Houston, Texas 77075 • Ph: 713-943-7543 • Fax: 713-943-3213 • www.henekmfg.com • filters@henekmanufacturing.com
Download