GLOSSARY
* Consult factory on conditions for approval acceptability
General Description
6
Introduction Guide
•Guide to Power Protection
•How various power protection devices work
•How to use power protection devices
Fuse Normal Opening (Fast-acting): Opens circuit without
deliberate time-delay.
Fuse Time-delay: Fuse that has its total clearing time
deliberately delayed in overload current range.
6600 Series
39
6700 Series
43
IAR/IUR/IER/CUR/CER
48
General Description
Max. Poles
Current and Voltage Rating
Interrupting Capacity
Approvals*
•Sub-miniature bimetal thermostat
•8-PIN DIP package configuration
•Snap-acting trip mechanism increases
operational life
•Single pole, single throw, automatic reset
•SPST
•0.50 to 16.0 amps at 240 VAC, 50/60 Hz
•0.50 to 16 amps at 50 VDC
•0.50 to 12 amps at 24 VDC (VDE)
•1000 amps
•UL recognized
•CSA certified
•VDE approved
Fuse Very Fast-acting: Fuse that opens circuit without deliberate
time delay and whose short-circuit opening time is faster than
normal opening fuse.
Instantaneous Trip (Opening): “Instantaneous” indicates delay is
not introduced purposely into action of device.
General Description
Max. Poles
Current and Voltage Rating
Interrupting Capacity
Approvals*
•Sub-miniature bimetal thermostat
•TO-220 package configuration
•Snap-acting trip mechanism increases
operational life
•Single pole, single throw, automatic reset
•VDE approved “P” version is available
•SPST
•2.5 to 20.0 amps at 240 VAC, 50/60 Hz
•2.5 to 20 amps at 50 VDC
•1000 amps
•UL recognized
•CSA certified
•TUV approved
•CE compliant
Max. Poles
•2
General Description
Current and Voltage Rating
Interrupting Capacity
Approvals*
•1U (1RU) hydraulic magnetic circuit breaker
•Low-profile design
•Auxiliary switch options available for alarm
signaling
•2 to 50 amps at 80 VDC and 250 VAC
•2 to 30 amps, 120/240VAC (2 poles)
•5000 amps, 65VDC
•5000 amps, 80VDC
•2000 amps, 250VAC
•5000 amps, 120/240VAC (2poles)
•5000 amps, 80VDC (2 poles)
•C-UL recognized
•UL1077 recognized
•UL489A listed
•TUV approved
Insulator (or Dielectric): Material that is very poor conductor of
electricity. Mica, glass, porcelain, rubber, paper, plastic, oils and
varnishes are considered good insulators.
Interrupting Capacity: Maximum short-circuit current at rated
voltage which protective device is required to interrupt under
operating duty specified and with normal frequency recovery
voltage not less than rated voltage. (See Rupture Capacity.)
Inverse-time: (See Time-inverse.)
Kilowatthour (KWH): Electrical energy expended if 1 kilowatt is
used for 1 hour.
Let-through Current: Current that actually passes through
protective device after initiation of fault.
T/R/PP/PR/CPP/CPR/CR
( SNAPAK® )
60
AP/UP, AP-MIL
76
IPA/CPA
88
IAG/IUG/IEG/CEG/LEG
104
General Description
Max. Poles
Current and Voltage Rating
Interrupting Capacity
Approvals*
•Compact magnetic-hydraulic circuit protector
•Snap-acting trip mechanism increases
operational life
•Aesthetically pleasing for front panel mounting
•Toggle, rocker, push-pull and push-to-reset
actuation options
•2
•0.10 to 7.5 amps at 50 VDC and 250 VAC
•0.10 to 30 amps at 32 VDC
•0.10 to 30 amps at 120 VAC
•0.10 to 25 amps at 120/240 VAC (two poles)
•0.10 to 20 amps at 250 VAC
(50/60 Hz, at 500AIC)
•0.10 to 20 amps at 65 VDC
[two poles, at 500AIC]
•1000 amps
•UL recognized
•CSA certified
•TUV approved
•CE compliant
•CCC approved
General Description
Max. Poles
Current and Voltage Rating
Interrupting Capacity
Approvals*
•QPL to MIL-PRF-39019
•Sealed magnetic-hydraulic circuit protection
•Can withstand 100G shock repeatedly
•Tolerates 10G vibration from 10 to 2000 Hz
under full load
• Ideal for use in Class 1, Div. 2 Groups A, B, C
and D hazardous locations
•3
AP ratings
•0.05 to 20 amps at 50 VDC and 240 VAC
AP ratings
•500 amps, 50 VDC, 120 VAC
•300 amps, 240 VAC
•MIL-PRF-M39019
•UL recognized
(UP type only)
• FM approved
(UP type only)
General Description
Max. Poles
Current and Voltage Rating
Interrupting Capacity
Approvals*
•Compact magnetic-hydraulic circuit protection
•Quick-connect, screw, PC board mount terminals
•Auxiliary switch options
•Multi-pole options with multi or single handle
•3
•0.05 to 30 amps at 65 VDC
•0.05 to 20 amps at 80 VDC (300 AIC)
•0.05 to 25 amps at 250 VAC, 50/60 Hz
•25.1 to 30 amps at 240 VAC, 50/60 Hz
•0.10 to 15 amps at 250 VAC, 400 Hz
•0.05 to 25 amps at 65 VDC (TUV)
•0.05 to 25 amps at 250 VAC, 50/60 Hz (TUV)
•0.05 to 15 amps at 250 VAC, 400 Hz (TUV)
•1000 amps
•UL 489A listed (CPA)
•UL recognized
•CUR recognized
•TUV certified
•CE compliant
•CCC approved (pending)
UP ratings (single pole only)
•0.05 to 20 amps at 50 VDC
•0.05 to 15 amps at 120 VAC
•0.05 to 7.5 amps at 240 VAC
UP ratings
•1000 amps, 50VDC, 240 VAC
General Description
Max. Poles
Current and Voltage Rating
Interrupting Capacity
Approvals*
•IEG versions meet IEC spacing requirements for
installation in equipment that must comply with
IEC 601 and 950, and VDE 0730, 0804, and 0805
•Multi-pole options with multi or single handle
•Auxiliary switch options
•Mid-trip handle option
•Snap-in mounting option
•Dual frequency delay options
•6
•0.05 to 50 amps at 80 VDC
•0.05 to 50 amps at 240 VAC
•0.05 to 30 amps at 277 VAC, 50/60 Hz
•0.05 to 30 amps at 250 VAC, 400 Hz
•0.05 to 30 amps at 125 VAC, 50/60 Hz
•1 to 30 amps at 120/240 VAC, 50/60 Hz
•5000 amps, 240 VAC, 50/60 Hz
•1500 amps, 250 VAC, 400 Hz
•7500 amps, 80 VDC (IEG)
•5000 amps, 80 VDC (CEG)
•2000 amps, 250 VAC, 50/60 Hz (VDE)
•4000 amps, 80 VDC (VDE)
•5000 amps, 125 VAC, 50/60 Hz (LEG)
•5000 amps, 120/240 VAC, 50/60 Hz
(LEG)
•UL 489 listed (LEG)
•UL 489A listed (CEG)
•UL recognized
•CSA certified
•VDE approved (IEG, CEG, LEG)
•CE compliant
•CCC approved
•UL 1500 certified
•QPL to MIL-PRF-55629
Minimum Fusing Current: Smallest value of current that will melt
current responsive element at specified ambient temperature.
Overcurrent: Any current exceeding rated current of protective
device (exceeding maximum ultimate trip current for circuit
breakers.) This includes both overload and short-circuit currents.
Overload Current: Overcurrent in excess of current rating.
Overload range is considered to be greater than rated current
up to approximately ten times rated current.
Panelboard: Single group of assembled panels which include
fuses. Assembled with or without switches and/or automatic
overcurrent protective devices for control of light, heat or power
circuits of small individual and aggregate capacity. Usually
placed in or against wall or partition and accessible only from
front.
Phase-to-phase: Voltage measured between any two “corners”
of delta connection or between any two “legs” of wye
connection.
Recovery Voltage: Voltage impressed across protective device
after circuit has been interrupted and after high frequency
transients have subsided.
Rupture Capacity: Applied to reusable protective devices. (See
Interrupting Capacity.)
Selective System: System in which protective device closest to
faulted circuit opens and isolates that circuit without disturbing
remainder of system. (See Coordination.)
Short-circuit Current (Fault Current):
Maximum current that system can produce at point of
application of protective device.
Time-delay: Qualifying term indicating that there is introduced
purposely delayed action.
Time-inverse: Time-current relationship where protective device
opening time decreases as current increases.
Total Clearing Time: Time measured from beginning of specified
overcurrent condition until permanent interruption of circuit.
Total clearing time for fuse of limiter is equal to sum of melting
item and arcing time.
Ultimate Trip Current: Minimum current which will provide a reliable
trip on the breaker (typically 115 percent of rated current.)
Voltage Drop: Fall of voltage along conductor due to its
resistance.
Voltage Drop (Distribution System): Difference at any instant
between voltages at source and utilization ends of feeder,
branch circuit or transformer.
Voltage Rating: Maximum alternating current and/or direct current
voltage at which protective device is designed to operate.
Voltage Regulation: Measure of change in voltage between no
load and full load in terms of full load voltage.
Voltage Peak: Voltage or current of AC sinusoidal wave when it
reaches its peak or maximum level twice in cycle. These peaks
are only a point of each 1/2 cycle. Direct current voltage is really
peak voltage at all times.
Watt (W or P): Unit of electrical power which represents amount
of power of circuit when current in that circuit is 1 ampere and
voLtage is 1 volt.
Protective Device: Devices which respond to harmful abnormal
conditions in electric distribution system and function to open
parts of circuit which will isolate cause of disturbances and so
permit remainder of system to function normally.
http://airpax.sensata.com/
Glossary
266
* Consult factory on conditions for approval acceptability
IAL/IUL/IEL
LEL
128
IULP/LELP/CELP
General Description
Max. Poles
Current and Voltage Rating
Interrupting Capacity
Approvals*
•IEL versions meet IEC spacing requirements for
installation in equipment that must comply with
IEC 601 and 950 and VDE 0730, 0804 and 0805
•Multi-pole options with multi or single handle
•Auxiliary switch options
•Snap-in mounting option
•Mid-trip handle option
•Various actuator options
•Dual frequency delay options
•6
•0.05 to 100 amps at 65 VDC
•0.05 to 70 amps at 80 VDC
•0.05 to 50 amps at 250VDC
•0.05 to 50 amps at 300VDC
•0.05 to 70 amps at 240 VAC, 50/60 Hz
•0.05 to 50 amps at 277 VAC, 50/60 Hz
•0.05 to 50 amps at 277/480 VAC, 50/60 Hz
•0.05 to 50 amps at 250 VAC, 400 Hz
•5000 amps, 240 VAC, 50/60 Hz
•1500 amps, 250 VAC, 400 Hz
•7500 amps, 80 VDC
•2000 amps, 240 VAC, 50/60 Hz (VDE)
•2000 amps, 415 VAC, 50/60 Hz (VDE)
•4000 amps, 80 VDC (VDE)
•1200 amps, 277/480 VAC, 50/60 Hz
•5000 amps, 250VDC
•1000 amps, 300VDC
•UL recognized
•CSA certified
•VDE approved (IEL)
•CE compliant (IEL)
•CCC approved
•UL 1500 certified
•QPL to MIL-PRF- 55629
General Description
Max. Poles
Current and Voltage Rating
Interrupting Capacity
Approvals*
•LEL versions meet IEC spacing requirements for
installation in equipment that must comply with
IEC 601 and 950 and VDE 0730, 0804 and 0805
•Multi-pole options with multi or single handle
•Auxiliary switch options
•Snap-in mounting option
•Mid-trip handle option
•Various actuator options
•Dual frequency delay options
•3
•0.05 to 100 amps at 80 VDC
•0.05 to 50 amps at 125 VAC, 50/60 Hz
•0.05 to 80 amps at 120/240 VAC, 50/60 Hz
•0.05 to 100 amps at 80 VDC (VDE)
•0.05 to 50 amps at 250 VAC (VDE)
•50000 amps 80 VDC
•5000 amps, 125 VAC, 120/240 VAC
50/60 Hz
•2000 amps, 80 VDC
•2000 amps, 250 VAC, 50/60 Hz (VDE)
•10000 amps, 120/240VAC, 50/60 Hz
•UL 489 listed
•CSA certified
•VDE approved
•CE compliant
•CCC approved
General Description
Max. Poles
Current and Voltage Rating
Interrupting Capacity
Approvals*
•Unique, parallel current sensing design
•Compact size, high current capacity
•Auxiliary switch options
•Mid-trip handle option
•1
•125 amps at 80 VDC†
•150 amps at 80 VDC†
•175 amps at 80 VDC†
•200 amps at 80 VDC†
•250 amps at 80 VDC†
•251 - 300 amps at 80 VDC††
•10000 amps, 80 VDC
•50000 amps, 65 VDC (up to 150 amps)
•10000 amps, 80 VDC (> 150 amps)
•UL 489 listed
•UL 489A listed
•CSA certified
† Two paralleled poles
†† Three paralleled poles
IALR/IULR/IELR
152
209/219/229/279
164
JAE/JRE/JTE/JLE
182
General Description
Max. Poles
Current and Voltage Rating
Interrupting Capacity
Approvals*
•Meets IEC spacing requirements for installation
in equipment that must comply with IEC 601
and 950, and VDE 0730, 0804 and 0805
• Designed to mount on standard 35mm DIN rails
•4
•.050 to 70 amps at 80 VDC
•.050 to 70 amps at 250 VAC, 50/60 Hz
•.100 to 50 amps at 80 VDC (VDE)
•.100 to 50 amps at 250 VAC, 50/60 Hz (VDE)
•.100 to 30 amps at 415 VAC, 50/60 Hz (VDE)
•7500 amps, 80 VDC
•5000 amps, 250 VAC, 50/60 Hz
•2000 amps, 277 VAC, 50/60 Hz
•2000 amps at 250 VAC, 50/60 Hz (VDE)
•2000 amps at 415 VAC, 50/60 Hz (VDE)
•4000 amps at 80 VDC (VDE)
•UL recognized
•CSA certified
•VDE approved (IELR)
•CE compliant
General Description
Max. Poles
Current and Voltage Rating
Interrupting Capacity
Approvals*
•Front or back connected terminal styles
•E-frame style model complies with UL 489
•249 Power Selector Breaker system is listed as
a branch circuit breaker per UL 489
•Complies with international requirements
•279 complies with UL 489A
•6
•.100 to 100 amps at 160 VDC
•.100 to 125 amps at 125 VDC
•.100 to 77 amps at 600 VAC
•.100 to 100 amps at 347/600 VAC
•.100 to 100 amps at 120, 240, 277, 480 VAC
•.100 to 100 amps, 125 VDC, 240/415 VAC
(VDE)
•5000 amps
•10000 amps
•4000 amps (VDE)
•UL 489 listed
•UL 489A listed (279)
•UL recognized
•CSA certified
•VDE approved
•UL1500 certified
•CCC approved
•CE compliant
General Description
Max. Poles
Current and Voltage Rating
Interrupting Capacity
Approvals*
•F-frame style complies with UL 489
•Various terminal options for design flexibility
•Reduced voltage drop through the circuit
breaker compared to other protective devices
•Auxiliary switch options
•Mid-trip handle options
•6
UL489
•100 to 250 amps at 160 VDC
•100 to 250 amps at 65 VDC
•100 to 250 amps at 125/250 VDC
•100 to 250 amps at 240 VAC
•10000 amps, 160 VDC
•10000 amps, 125/250 VDC
•65000 amps, 65 VDC
•10000 amps, 240 VAC
•18000 amps, 240 VAC
•100000 amps, 65VDC
(UL489A up to 800 amps)
•UL 489 listed
•UL 489A listed
•UL recognized
•CSA certified
•VDE approved
•CCC approved
•CE compliant
UL489A
•275 to 800 amps at 160 VDC
•275 to 1200 amps at 65 VDC
* Consult factory on conditions for approval acceptability
MDS & MDS2
198
PGFM
209
General Description
Max. Poles
Current and Voltage Rating
•Modular Distribution System provides
unprecedented flexibility
•“Hot Plug” modules allow for equipment
expansion without power shutdown
•Unique alarm conductors simplify signal wiring
•Modular load terminals available with front or
rear access
•24
•Maximum load bus rating per position is
100 amps, 125VDC
General Description
Max. Poles‡
Ground Trip Current
Interrupting Capacity
Approvals*
•GFCI sensing module designed to operate in
tandem with the LEL series circuit breaker
with a shunt voltage trip and auxiliary switch
•Manufactured by North Shore Safety, Ltd., a
leader in innovative safety products
•Automatic and manual reset configurations
•Power and fault status indicators
•Double insulated user interface
•3
•4 to 6 mA
•As per rating of Airpax™ LEL series
•UL 943, Class A
or
•UL 1053 Compliant
‡
Number of
circuit breaker
poles
Trip Time, Combined Assembly
• ≤ 25 mS
Rated Voltage
• 120 VAC or 240 VAC, 50/60 Hz
Let-Go Voltage
• 60% of supply voltage
!5 Amp PGFP
Plug Series
217
General Description
Rated Current
Construction
Approvals*
•15 amp plug cordset GFCI series
•Manufactured by North Shore Safety, Ltd., a leader in innovative
safety products
•Automatic and manual reset configurations
•Available as a field wireable plug or with attached cords and outlets
•Plug assembly with power single or tri-tap outlet
•Electro-magnetically latched contacts
•Up to 15 amps at 120 VAC, 50/60 Hz
•NEMA 3R rated
•cULus 943, Class A
or
•UL recognized
Ground Trip Current
• 4 to 6 mA
Insulation Voltage
• 1500 VRMS - 1 minute
Endurance Operations
• 3000 operations
15 Amp PGFI
In-line Series
219
General Description
Rated Current
Construction
Approvals*
•15 amp in-line cordset GFCI series
•Manufactured by North Shore Safety, Ltd., a leader in innovative
safety products
•Automatic and manual reset configurations
•Available as a field wireable plug or with attached cords and outlets
•Plug assembly with power single or tri-tap outlet
•Electro-magnetically latched contacts
•Up to 15 amps at 120 VAC, 50/60 Hz
•NEMA 3R rated
•cULus 943, Class A
•cCSAus certified to
CSA-C22.2 No. 144
or
UL recognized
Ground Trip Current
• 4 to 6 mA
Insulation Voltage
• 1500 VRMS - 1 minute
Endurance Operations
• 3000 operations
20 Amp PGFI
Portable Series
221
General Description
Rated Current
Construction
Approvals*
•20 amp in-line cordset GFCI series
•Manufactured by North Shore Safety, Ltd., a leader in innovative
safety products
•Automatic and manual reset configurations
•Available with locking connectors / plugs or flying leads
•Electro-magnetically latched contacts
•Up to 20 amps
•NEMA 4X wet location rated
•cULus 943, Class A
•cCSAus certified to
CSA-C22.2 No. 144
Rated Voltage
• 120 VAC, 208 VAC, 240 VAC, 277 VAC
Operating Voltage Range
• 85% to 110% of rating
Ground Trip Current
• 4 to 6 mA
30 Amp PGFI
Portable Series
223
General Description
Rated Current
Construction
Approvals*
•30 amp in-line cordset GFCI series
•Manufactured by North Shore Safety, Ltd., a leader in innovative
safety products
•Automatic and manual reset configurations
•Available with locking connectors / plugs or flying leads
•Electro-magnetically latched contacts
•Up to 30 amps
•NEMA 4X and 6P wet location rated
•cULus 943, Class A
•cCSAus certified to
CSA-C22.2 No. 144
Rated Voltage
• 120 VAC, 208 VAC, 240 VAC, 277 VAC
Operating Voltage Range
• 85% to 110% of rating
Ground Trip Current
• 4 to 6 mA
* Consult factory on conditions for approval acceptability
30 Amp PGFI
Portable Series,
Multi-Phase
225
General Description
Rated Current
Construction
Approvals*
•30 amp multi-phase cordset GFCI series
•Manufactured by North Shore Safety, Ltd., a leader in innovative
safety products
•Automatic and manual reset configurations
•Dual indication lights displaying power and fault status
•Grounded and open neutral protected
•Electro-magnetically latched contacts
•Up to 30 amps
•NEMA 4X and 6P wet location rated
•cULus 943, Class A
Rated Voltage
•cCSAus certified to
CSA-C22.2 No. 144
• 120/240 VAC dual voltage,
120/208 VAC 3Ø, 240 VAC 3Ø, 208 VAC 3Ø, 277 VAC 3Ø (non-UL or CSA)
Operating Voltage Range
• 85% to 110% of rating
Ground Trip Current
• 4 to 6 mA
40, 50 & 60 Amp
PGFI Portable Series
227
General Description
Rated Current
Construction
Approvals*
•40, 50 & 60 amp in-line ELCI series
•Manufactured by North Shore Safety, Ltd., a leader in innovative
safety products
•Automatic and manual reset key switch selector
•Fault theshold key switch selector
•Available with locking connectors/ plugs or flying leads
•Electro-magnetically latched contacts
•40, 50 or 60 amps
•NEMA 4X wet location rated
•UL 1053 compliant
Rated Voltage
• 120 VAC, 240 VAC, 208 VAC, 277 VAC, 120/240 VAC, 3Ø 240 VAC, 3Ø 208 VAC, 3Ø 277 VAC, 3Ø 480 VAC, 3Ø 600 VAC
Operating Voltage Range
• 85% to 110% of rating
Ground Trip Current Threshold
• Key switch selectable: 6, 10 and 30mA
30 Amp PGFS
Permanent Series
229
General Description
Rated Current
Construction
Approvals*
•30 amp splice-in GFCI series
•Manufactured by North Shore Safety, Ltd., a leader in innovative
safety products
•Automatic and manual reset configurations
•Fault output options available
•Grounded and open neutral protected
• Electro-magnetically latched contacts
•Up to 30 amps
•NEMA 4X and 6P wet location rated
•cULus 943, Class A
Rated Voltage
•cCSAus certified to
CSA-C22.2 No. 144
• 120 VAC, 208 VAC, 240 VAC, 120/240 VAC
277 VAC (non-UL)
Operating Voltage Range
• 85% to 110% of rating
Ground Trip Current
• 4 to 6 mA
30 Amp PGFS
Permanent Series,
Multi-Phase
231
General Description
Rated Current
Construction
Approvals*
•30 amp multi-phase splice-in GFCI series
•Manufactured by North Shore Safety, Ltd., a leader in innovative
safety products
•Automatic and manual reset configurations
•Dual indication lights displaying power and fault status
•Grounded and open neutral protected
•Electro-magnetically latched contacts
•Up to 30 amps
•NEMA 4X and 6P wet location rated
•cULus 943, Class A
Rated Voltage
•cCSAus certified to
CSA-C22.2 No. 144
• 120/240 VAC dual voltage,
120/208 VAC 3Ø, 240 VAC 3Ø,
208 VAC 3Ø, 277 VAC 3Ø (non-UL or CSA)
Operating Voltage Range
• 85% to 110% of rating
Ground Trip Current
• 4 to 6 mA
40, 50 & 60 Amp
PGFS Permanent Series
233
General Description
Rated Current
Construction
Approvals*
•40, 50 & 60 amp splice-in ELCI series
•Manufactured by North Shore Safety, Ltd., a leader in innovative
safety products
•Automatic / manual reset key switch
•Fault trip level key switch
•Keyed power switch •Dual indication lights displaying power and fault status
•Grounded and open neutral protected
•Electro-magnetically latched contacts
•40, 50 or 60 amps
•NEMA 4X wet location rated
•UL 1053 compliant
Rated Voltage
• 120 VAC, 240 VAC, 208 VAC, 277 VAC, 120/240 VAC, 3Ø 240 VAC, 3Ø 208 VAC, 3Ø 277 VAC, 3Ø 480 VAC, 3Ø 600 VAC
Operating Voltage Range
• 85% to 110% of rating
Ground Trip Current
• 6 mA, 10 mA and 30mA
PGFR Duplex
Receptacle Series
235
General Description
Rated Current
Approvals*
•15 / 20 amp duplex receptacle GFCI series •PGFR model - standard wall receptacle
•Model has:
Standard power indicator light
Manual reset configuration
TEST and RESET buttons
•15 / 20 amps
•UL recognized for
use under
cULus 943, Class A
Rated Voltage
• 120 VAC
Operating Voltage Range
• 85% to 110% of rating
Ground Trip Current
• 4 to 6 mA
•cCSAus certified to
CSA-C22.2 No. 144
* Consult factory on conditions for approval acceptability
SAS/SUS/SES
237
SAR/SUR/SER
QAS/QAL/QFS/QFL
241
HVS
245
SARPV
General Description
Max. Poles
Current and Voltage Rating
Interrupting Capacity
Approvals*
•Ultra-compact and ultra-light hydraulic-
magnetic circuit protector
•Trip-free function
•Wiping-action, self-cleaning contacts
•Slide actuator
•PCB terminals
•1
•0.100 to 15.0 amps at 125 VAC, 50/60 Hz
•0.100 to 15 amps at 250 VAC, 50/60 Hz
•0.100 to 15 amps at 32 VDC
•0.100 to 15 amps at 50 VDC
•500 amps
•UL recognized
•CSA certified
•VDE approved
General Description
Max. Poles
Current and Voltage Rating
Interrupting Capacity
Approvals*
•Ultra-compact and ultra-light hydraulic-
magnetic circuit protector
• Trip-free function
• Wiping-action, self-cleaning contacts
• Rocker actuator
• .250” quick-connect or PCB terminals
•2
•0.100 to 20.0 amps at 125 VAC, 50/60 Hz
•0.100 to 15 amps at 250 VAC, 50/60 Hz
•0.100 to 15 amps at 32 VDC
•0.100 to 30 amps at 50 VDC**
•500 amps
•UL recognized
•CSA certified
•VDE approved
General Description
Current and Voltage Rating
Interrupting Capacity
Approvals*
•Silver-link quick-action fuses
•L-type terminals construction for easy installation
•Resistive to repetitive currents
•Low power loss
•Excellent current-limiting characteristics
•Available options include fuse holder indicator fuse, microswitch
QAS25
•20 to 100 amps at 250VAC, 300VDC
QAS25
•10KA at 250VAC, 300VDC
•QFS25: CSA certified
UL recognized, TUV
QAL25
•75 to 300 amps at 250VAC, 300VDC
QAL25
•10KA at 250VAC, 300VDC
QAS60
•20 to 75 amps at 600VAC, 500VDC
QAS60
•100KA at 600VAC,10KA at 500VDC
QAL60
•100 to 300 amps at 600VAC, 500VDC
QAL60
•100KA at 600VAC,10KA at 500VDC
QFS25
•10 to 100 amps at 250VAC, 400VDC
QFS25
•10KA at 250VAC, 400VDC
QFL25
•75 to 300 amps at 250VAC, 400VDC
QFL25
•10KA at 250VAC, 400VDC
General Description
Max. Poles
Current and Voltage Rating
•High voltage DC switch
•Compact design
•Available options include remote signal
disconnect and auxiliary switch
•3
•Up to 30 amps at 300VDC, open voltage 450VDC
•> 5000cycles at 2x per minute, at nominal current
General Description
Max. Poles
Current and Voltage Rating
•High voltage DC power switch
•Compact design
•Available options include remote signal
disconnect and auxiliary switch
•2
•Up to 10 amps at 300VDC, open voltage 450VDC
•> 5000cycles at 2x per minute, at nominal current
General Description
248
ADDITIONAL
PRODUCTS
258
DIMENSIONS™
DC TO AC INVERTERS
•AIRPAX™ & KLIXON™ Bimetal Thermostats
•KLIXON™ Air Flow Sensors
•AIRPAX™ Temperature Sensors
•KLIXON™ Aircraft Circuit Breakers
•KLIXON™ Thermal Circuit Breakers
General Description
•AIRPAX™ APG/UPG Series
•AIRPAX™ APL/UPL/205 Series
•AIRPAX™ 203 Series
General Description
262
EXISTING-DESIGN
PRODUCTS
** Agency Approvals Pending
•Mobile AC Power
•International Standby Power
•Traffic Signal Backup
•Industrial (High Voltage)
•Military
This document is generated from the AIRPAX™ full-line catalog #2455005000 printed in USA, January 2011
BUSINESS CENTERS
Sensata Technologies
807 Woods Road
Cambridge, MD 21613, USA
Phone: +1 410-228-1500
Brands: Airpax™
Sensata Technologies Holland B.V.
Kolthofsingel 8
7602 EM Almelo, The Netherslands
Phone: +31 546 87 95 55
Brands: Klixon™, Sensata Technologies™
Sensata Technologies Inc.
529 Pleasant Street
Attleboro, MA 02703, USA
Phone: +1 508-236-3287
Brands: Klixon™, Sensata Technologies™
Sensata Technologies China Co., Ltd.
Novel Plaza, 8th Floor
128 Nanjing Road West
Shaghai, 20003
People’s Republic of China
Phone: +86 21 23061500
Brands: Klixon™, Sensata Technologies™
Sensata Technologies
4467 White Bear Lake Parkway
St. Paul, MN 55110, USA
Phone: +1 800-553-6418
Brands: Dimensions™
Sensata Technologies Japan Ltd.
305, Tanagashira
Oyama-cho, Sunto-gun, Shizuoka-ken
Japan, 410-1396
Phone: +81 550 78 1211
Brands: Klixon™, Sensata Technologies™
Sensata Technologies Nihon-Airpax
6-3, Chi Yoda 5 Chome
Saitama-Ken
Japan, 350-0214
Phone: +81 492 83 7575
Brands: Airpax™
Sensata Technologies Korea Ltd.
29F, Trade Tower
159-1 SamSung-Dong, KangNam-Ku, Seoul
135-729, Korea
Phone: +81-2-551-2918
Brands: Klixon™, Sensata Technologies™
Important Notice: Sensata Technologies (Sensata) reserves the right to make changes to or discontinue any
product or service identified in this publication without notice. Sensata advises its customers to obtain the
latest version of the relevant information to verify, before placing any orders, that the information being
relied upon is current. Sensata assumes no responsibility for infringement of patents or rights of others
based on Sensata applications assistance or product specifications since Sensata does not possess full
access concerning the use or application of customers’ products. Sensata also assumes no responsibility for
customers’ product designs.
http://airpax.sensata.com/
Download