Power distribution

advertisement
Power distribution
Short-circuit withstand strength to IEC
Short-circuit withstand strength to IEC 60 439-1
Type testing to IEC 60 439-1
During the course of system type-testing, the
following tests were conducted on the Rittal
busbar systems and on representative Rittal
RiLine top-mounting components:
Proof of insulating properties
(to IEC/EN 60 439-1, 8.2.2)
Test piece: Representative system assembly
Test with surge voltage 1.2/50 μs, 9.8 kV
Mini-PLS busbar support
Basis of test:
– VDE 0660, part 500/IEC 60 439
Proof of short-circuit withstand strength
(to IEC/EN 60 439-1, 8.2.3)
see diagrams below
Test implemented:
– Rated peak withstand current Ipk
Model No. SV 9600.000
40 mm bar centre distance,
for Mini-PLS special busbars
Rated operating voltage: up to 690 V AC
Level of contamination: 3
Rated frequency: 50/60 Hz
40
Ip short-circuit current [kA]
up to 250 A, 3-pole
Proof of creepage distances and
clearance (to IEC/EN 60 439-1, 8.2.5)
Test piece: Representative system assembly
35
30
25
20
15
10
50
80
up to 800 A, 3-pole
75
60 mm bar centre distance,
for busbars 15 x 5 – 30 x 10 mm.
Rated operating voltage: up to 690 V AC
Rated insulation voltage: 1000 V AC
Rated surge voltage: 8 kV
Overvoltage category: IV
Level of contamination: 3
Rated frequency: 50/60 Hz
Test implemented:
– Rated peak withstand current Ipk
– Rated short-time withstand current Icw
a
65
60
b
55
50
45
c
40
d
35
55
45
40
20
Busbar
mm
30 x 10
250
37.6
30 x 5
250
36.0
20 x 10
250
29.0
g
35
25
Busbar support spacing [mm]
f
50
25
Icw1)
kA
Technical details/Power distribution/02.2014
60
20
200 250 300 350 400 450 500 550 600
e
65
30
I
mm
For 1 sec.
l = Busbar support spacing
400
70
30
Busbar
mm
1)
350
75
70
Ip peak short-circuit current [kA]
Model No. SV 9340.000/SV 9340.010
300
150
250
200
Busbar support spacing [mm]
80
Ip peak short-circuit current [kA]
Busbar support
100
200 250 300 350 400 450 500 550 600
Busbar support spacing [mm]
Curve
Busbar
mm
Curve
30 x 10
a
30 x 5
e
20 x 10
b
20 x 5
25 x 5
c
15 x 10
f
g
15 x 5
d
dri1308052en.fm – 2-105 – 1 of 7
Power distribution
Short-circuit withstand strength to IEC
80
up to 800 A/1600 A, 3-pole
75
Model No. SV 9341.000/SV 9342.000
70
60 mm bar centre distance,
for PLS special busbars
Rated operating voltage: up to 690 V AC
Rated insulation voltage: 1000 V AC
Rated impulse withstand voltage: 8 kV
Overvoltage category: IV
Level of contamination: 3
Rated frequency: 50/60 Hz
Ip peak short-circuit current [kA]
PLS busbar support
Model No.
SV
b
65
Busbar
mm
I
mm
Icw1)
kA
a 9341.000
PLS 800
150
25.9
b 9342.000
PLS 1600
150
37.5
I
mm
Icw1)
kA
250
29
500
23
1)
For 1 sec.
I = Busbar support spacing
60
55
50
a
45
40
35
30
25
Test implemented:
– Rated peak withstand current Ipk
– Rated short-time withstand current Icw
20
100 150 200 250 300 350 400 450 500
Busbar support spacing [mm]
80
up to 800 A, 4-pole
75
Model No. SV 9340.004
70
60 mm bar centre distance,
for 30 x 10 mm busbars
Rated operating voltage: up to 690 V AC
Rated insulation voltage: 1000 V AC
Rated impulse withstand voltage: 8 kV
Overvoltage category: IV
Level of contamination: 3
Rated frequency: 50/60 Hz
Ip peak short-circuit current [kA]
Busbar support
Test implemented:
– Rated peak withstand current Ipk
– Rated short-time withstand current Icw
65
Model No.
SV
Busbar
mm
9340.004
30 x 10
1)
For 1 sec.
I = Busbar support spacing
60
55
50
45
40
35
30
25
20
200 250 300 350 400 450 500
Busbar support spacing [mm]
PLS busbar support
115
up to 1600 A, 4-pole
110
Model No. SV 9342.004
105
60 mm bar centre distance,
for PLS special busbars
100
Rated operating voltage: up to 690 V AC
Rated insulation voltage: 1000 V AC
Rated surge voltage: 8 kV
90
Test implemented:
– Rated peak withstand current Ipk
– Rated short-time withstand current Icw
PLS 1600
95
I
mm
Icw
kA
250
501)
250
532)
500
382)
1)
For 3 sec.
2) For 1 sec.
I = Busbar support spacing
85
Ip peak short-circuit current [kA]
Overvoltage category: IV
Level of contamination: 3
Rated frequency: 50/60 Hz
Busbar
mm
80
75
70
65
60
55
50
45
40
35
30
25
20
200 250 300 350 400 450 500
Busbar support spacing [mm]
dri1308052en.fm – 2-105 – 2 of 7
Technical details/Power distribution/02.2014
Power distribution
Short-circuit withstand strength to IEC
Busbar support for DC use
Ip peak short-circuit current [kA]
45
The figures shown in the diagram refer to a minimal bar centre distance of 60 mm. Larger centreto-centre spacings are permissible. The rated
operating voltage depends on the choice of bar
centre distance and the configuration of the
system with top-mounting components. The
rated values can be taken from the technical
specifications for the components. Compliance
with the creepage distances and clearance to
DIN EN 60 664-1 should be checked in the final
assembly or final application.
30
15 x 5 – 25 x 10
b
25
PLS 800
20
c
PLS 1600
110
Model No. SV 3073.000
100
Ip short-circuit current [kA]
105
Basis of test:
– VDE 0660, part 500/IEC 60 439
30 x 10
d
e
Number of
poles
SV 9340.050
3-pole
a
SV 9340.030
1-pole
d
SV 9340.050
3-pole
b
SV 9340.030
1-pole
c
SV 9341.050
3-pole
e
SV 9342.050
3-pole
SV 9342.030
1-pole
Curve
a
Busbar support spacing [mm]
up to 1250 A, 3-pole
Rated operating voltage: up to 1000 V AC
Level of contamination: 3
Rated frequency: 50/60 Hz
35
Support
200 250 300 350 400 450 500 550
Busbar support
100 mm bar centre distance,
for busbars 30 x 10 – 60 x 10 mm
Busbar
mm
a
40
a
95
b
90
Rated current
up to A
Curve
30 x 10
800
d
40 x 10
850
c
50 x 10
1000
b
60 x 10
1250
a
Busbar
E-Cu mm
Rated current
up to A
Curve
50 x 10
1000
c
60 x 10
1250
b
80 x 10
1600
a
85
80
75
d
70
c
65
Test implemented:
– Rated peak withstand current Ipk
Busbar
E-Cu mm
60
200
300
400
500
600
Busbar support spacing [mm]
160
up to 1600 A, 3-pole
150
Model No. SV 3052.000
185 mm bar centre distance,
for busbars 50 x 10 – 80 x 10 mm
Rated operating voltage: up to 1000 V AC
Level of contamination: 3
Rated frequency: 50/60 Hz
Basis of test:
– VDE 0660, part 500/IEC 60 439
Test implemented:
– Rated peak withstand current Ipk
Technical details/Power distribution/02.2014
Ip short-circuit current [kA]
Busbar support
a
140
130
b
120
110
c
100
90
80
200
400
600
800
1000
Busbar support spacing [mm]
dri1308052en.fm – 2-105 – 3 of 7
Power distribution
Short-circuit withstand strength to IEC
Model No. SV 3055.000 (2500 A),
bar accommodation
3 x 2 x 80 x 10 mm
Busbar support
up to 2500 A/3000 A, 3-pole
Model No. SV 3057.000 (3000 A),
bar accommodation
3 x 2 x 100 x 10 mm
Basis of test:
– VDE 0660, part 500/IEC 60 439
Test implemented:
– Rated peak withstand current Ipk
160
160
150
150
Ip short-circuit current [kA]
Rated operating voltage: up to 1000 V AC
Level of contamination: 3
Rated frequency: 50/60 Hz
Ip short-circuit current [kA]
150 mm bar centre distance
140
130
120
110
100
90
80
150 200
130
120
110
100
90
300
400
500
600
700
Busbar support spacing [mm]
dri1308052en.fm – 2-105 – 4 of 7
140
800
80
150 200
300
400
500
600
700
800
Busbar support spacing [mm]
Technical details/Power distribution/02.2014
Power distribution
Short-circuit withstand strength to IEC
Busbar support Flat-PLS 60
1 to 4-pole
Model No. SV 9676.002/SV 9676.020
160
Ip peak short-circuit current [kA]
120 mm bar centre distance,
for busbars 40 x 10 – 60 x 10 mm.
Population: 2, 3 or 4 bars per support
Rated operating voltage: up to 690 V AC
Rated insulation voltage: 1000 V AC
Rated impulse withstand voltage: 8 kV
Overvoltage category: IV
Level of contamination: 3
Rated frequency: 50/60 Hz
140
130
110
Icw
kA/1 sec.
4 x 60 x 10
450
55.0
4 x 60 x 10
900
40.0
4 x 60 x 10
450
60.0
4 x 60 x 10
900
45.0
4 x 60 x 10
450
70.0
4 x 60 x 10
900
60.0
a
100
90
80
I
mm
b
120
Test implemented:
– Rated peak withstand current Ipk
– Rated short-time withstand current Icw
Busbar
mm
c
150
450
500
550
600
650
700
750
800
850
900
800
850
900
Busbar support spacing [mm]
Curve
Curve
a
b
Design of busbar attachment
a
Basic version1)
b
With busbar claws2)
c
With busbar stabilisers and busbar claws2)
1)
Basic version consists of system attachment with fitted busbar support
2) For version see below
c
I = Busbar support spacing
Busbar support Flat-PLS 100
1 to 4-pole
Model No. SV 9676.004/SV 9676.021
260
Ip peak short-circuit current [kA]
165 mm bar centre distance,
for busbars 80 x 10 – 100 x 10 mm.
Population: 2, 3 or 4 bars per support
Rated operating voltage: up to 690 V AC
Rated insulation voltage: 1000 V AC
Rated impulse withstand voltage: 8 kV
Overvoltage category: IV
Level of contamination: 3
Rated frequency: 50/60 Hz
240
200
180
Busbar
mm
I
mm
Icw
kA/1 sec.
4 x 100 x 10
450
75.0
4 x 100 x 10
900
52.0
4 x 100 x 10
450
81.6
4 x 100 x 10
900
55.9
4 x 100 x 10
450
110.0
4 x 100 x 10
900
78.0
b
160
140
a
120
100
Test implemented:
– Rated peak withstand current Ipk
– Rated short-time withstand current Icw
c
220
450
500
550
600
650
700
750
Busbar support spacing [mm]
Curve
Curve
a
b
Design of busbar attachment
a
Basic version1)
b
With busbar claws2)
c
With busbar stabilisers and busbar claws2)
1)
Basic version consists of system attachment with fitted busbar support.
2) For version see below
c
I = Busbar support spacing
Busbar claws
Max. distance
Model No. SV 9676.017/SV 9676.019
Busbar claw – Busbar claw
Supplementary information on Flat-PLS
short-circuit protection diagrams
Mounting distance of busbar claws:
In order to achieve the cited short-circuit protection,
the busbar claws must be fitted at a spacing of
300 mm. If there is a busbar support, a contact
maker or a longitudinal connector located within this
300 mm, there is no need to fit a claw at this point.
Busbar claw – Busbar support
≤ 300
Busbar claw – Contact maker
≤ 300
Busbar claw – Longitudinal connector
≤ 300
Technical details/Power distribution/02.2014
mm
≤ 300
dri1308052en.fm – 2-105 – 5 of 7
Power distribution
Short-circuit withstand strength to UL 508
The short-circuit withstand strength of RiLine
has been extensively tested. Short-circuit
withstand strength to UL criteria is assessed
via the root-mean-square value of the shortcircuit current (IRMS), which must be applied for
at least 3 periods (60 ms).
During the course of testing, the test equipment has been adjusted to the respective
root-mean-square values (IRMS). The resultant
peak short-circuit currents Ip are shown in the
diagrams below.
Busbar support
Settings IRMS (Ieff.) of the test equipment
without pre-fuse:
60 mm bar centre distance,
for busbars 15 x 5 – 30 x 10 mm
Note:
SV 9340.050 with E-Cu 30 x 5/10 mm
The following short-circuit value can be
achieved with a pre-fuse:
– Support spacing: 350 mm
– Fuse: Class L 800 A
– IRMS: 50 kA
Support spacing
mm
IRMS
kA
Support spacing
mm
IRMS
kA
250
35
250
30
500
25
500
22
Ip peak short-circuit current [kA]
SV 9340.050 with
30 x 5/10 mm
SV 9340.050
with 25 x 5 mm
20 x 5/10 mm
15 x 5/10 mm
80
80
75
75
70
70
65
65
Ip peak short-circuit current [kA]
for feeder circuits 700 A, 3-pole
60
55
50
45
40
35
60
55
50
45
40
35
30
30
25
25
20
20
200 250 300 350 400 450 500 550 600
200 250 300 350 400 450 500 550 600
Busbar support spacing [mm]
for feeder circuits
700 A (PLS 800)/1400 A (PLS 1600),
3-pole
Settings IRMS (Ieff.) of the test equipment
without pre-fuse:
60 mm bar centre distance,
for PLS special busbars
Note:
SV 9342.050 (PLS 1600)
The following short-circuit value can be
achieved with a pre-fuse:
– Support spacing: 250 mm
– Fuse: Class L 1400 A
– IRMS: 65 kA
Support spacing
mm
IRMS
kA
Support spacing
mm
IRMS
kA
200
22
150
35
500
14
500
25
Ip peak short-circuit current [kA]
SV 9341.050 (PLS 800)
80
80
75
75
70
70
65
65
60
55
50
45
40
35
60
55
50
45
40
35
30
30
25
25
20
20
150 200 250 300 350 400 450 500 550
Busbar support spacing [mm]
dri1308052en.fm – 2-105 – 6 of 7
SV 9342.050 (PLS 1600)
Ip peak short-circuit current [kA]
Busbar support
Busbar support spacing [mm]
150 200 250 300 350 400 450 500 550
Busbar support spacing [mm]
Technical details/Power distribution/02.2014
Power distribution
Short-circuit withstand strength to UL 508
80
for feeder circuits up to 700 A, 4-pole
75
Model No. SV 9340.004
70
60 mm bar centre distance
Ip peak short-circuit current [kA]
Busbar support
Settings IRMS (Ieff.) of the test equipment
without pre-fuse:
Busbar
mm
65
60
15 x 5 – 30 x 10
55
Support
spacing
mm
IRMS
250
30
500
22
50
45
40
35
30
25
20
200 250 300 350 400 450 500
Busbar support spacing [mm]
80
for feeder circuits up to 1400 A, 4-pole
75
Model No. SV 9342.004
70
60 mm bar centre distance,
for PLS special busbars
65
Ip peak short-circuit current [kA]
Busbar support
Settings IRMS (Ieff.) of the test equipment
without pre-fuse:
Busbar
mm
60
PLS 1600
55
Support
spacing
mm
RMS
kA
150
35
500
25
50
45
40
35
30
25
20
150 200 250 300 350 400 450 500 550
Busbar support spacing [mm]
Technical details/Power distribution/02.2014
dri1308052en.fm – 2-105 – 7 of 7