Power distribution Short-circuit withstand strength to IEC Short-circuit withstand strength to IEC 60 439-1 Type testing to IEC 60 439-1 During the course of system type-testing, the following tests were conducted on the Rittal busbar systems and on representative Rittal RiLine top-mounting components: Proof of insulating properties (to IEC/EN 60 439-1, 8.2.2) Test piece: Representative system assembly Test with surge voltage 1.2/50 μs, 9.8 kV Mini-PLS busbar support Basis of test: – VDE 0660, part 500/IEC 60 439 Proof of short-circuit withstand strength (to IEC/EN 60 439-1, 8.2.3) see diagrams below Test implemented: – Rated peak withstand current Ipk Model No. SV 9600.000 40 mm bar centre distance, for Mini-PLS special busbars Rated operating voltage: up to 690 V AC Level of contamination: 3 Rated frequency: 50/60 Hz 40 Ip short-circuit current [kA] up to 250 A, 3-pole Proof of creepage distances and clearance (to IEC/EN 60 439-1, 8.2.5) Test piece: Representative system assembly 35 30 25 20 15 10 50 80 up to 800 A, 3-pole 75 60 mm bar centre distance, for busbars 15 x 5 – 30 x 10 mm. Rated operating voltage: up to 690 V AC Rated insulation voltage: 1000 V AC Rated surge voltage: 8 kV Overvoltage category: IV Level of contamination: 3 Rated frequency: 50/60 Hz Test implemented: – Rated peak withstand current Ipk – Rated short-time withstand current Icw a 65 60 b 55 50 45 c 40 d 35 55 45 40 20 Busbar mm 30 x 10 250 37.6 30 x 5 250 36.0 20 x 10 250 29.0 g 35 25 Busbar support spacing [mm] f 50 25 Icw1) kA Technical details/Power distribution/02.2014 60 20 200 250 300 350 400 450 500 550 600 e 65 30 I mm For 1 sec. l = Busbar support spacing 400 70 30 Busbar mm 1) 350 75 70 Ip peak short-circuit current [kA] Model No. SV 9340.000/SV 9340.010 300 150 250 200 Busbar support spacing [mm] 80 Ip peak short-circuit current [kA] Busbar support 100 200 250 300 350 400 450 500 550 600 Busbar support spacing [mm] Curve Busbar mm Curve 30 x 10 a 30 x 5 e 20 x 10 b 20 x 5 25 x 5 c 15 x 10 f g 15 x 5 d dri1308052en.fm – 2-105 – 1 of 7 Power distribution Short-circuit withstand strength to IEC 80 up to 800 A/1600 A, 3-pole 75 Model No. SV 9341.000/SV 9342.000 70 60 mm bar centre distance, for PLS special busbars Rated operating voltage: up to 690 V AC Rated insulation voltage: 1000 V AC Rated impulse withstand voltage: 8 kV Overvoltage category: IV Level of contamination: 3 Rated frequency: 50/60 Hz Ip peak short-circuit current [kA] PLS busbar support Model No. SV b 65 Busbar mm I mm Icw1) kA a 9341.000 PLS 800 150 25.9 b 9342.000 PLS 1600 150 37.5 I mm Icw1) kA 250 29 500 23 1) For 1 sec. I = Busbar support spacing 60 55 50 a 45 40 35 30 25 Test implemented: – Rated peak withstand current Ipk – Rated short-time withstand current Icw 20 100 150 200 250 300 350 400 450 500 Busbar support spacing [mm] 80 up to 800 A, 4-pole 75 Model No. SV 9340.004 70 60 mm bar centre distance, for 30 x 10 mm busbars Rated operating voltage: up to 690 V AC Rated insulation voltage: 1000 V AC Rated impulse withstand voltage: 8 kV Overvoltage category: IV Level of contamination: 3 Rated frequency: 50/60 Hz Ip peak short-circuit current [kA] Busbar support Test implemented: – Rated peak withstand current Ipk – Rated short-time withstand current Icw 65 Model No. SV Busbar mm 9340.004 30 x 10 1) For 1 sec. I = Busbar support spacing 60 55 50 45 40 35 30 25 20 200 250 300 350 400 450 500 Busbar support spacing [mm] PLS busbar support 115 up to 1600 A, 4-pole 110 Model No. SV 9342.004 105 60 mm bar centre distance, for PLS special busbars 100 Rated operating voltage: up to 690 V AC Rated insulation voltage: 1000 V AC Rated surge voltage: 8 kV 90 Test implemented: – Rated peak withstand current Ipk – Rated short-time withstand current Icw PLS 1600 95 I mm Icw kA 250 501) 250 532) 500 382) 1) For 3 sec. 2) For 1 sec. I = Busbar support spacing 85 Ip peak short-circuit current [kA] Overvoltage category: IV Level of contamination: 3 Rated frequency: 50/60 Hz Busbar mm 80 75 70 65 60 55 50 45 40 35 30 25 20 200 250 300 350 400 450 500 Busbar support spacing [mm] dri1308052en.fm – 2-105 – 2 of 7 Technical details/Power distribution/02.2014 Power distribution Short-circuit withstand strength to IEC Busbar support for DC use Ip peak short-circuit current [kA] 45 The figures shown in the diagram refer to a minimal bar centre distance of 60 mm. Larger centreto-centre spacings are permissible. The rated operating voltage depends on the choice of bar centre distance and the configuration of the system with top-mounting components. The rated values can be taken from the technical specifications for the components. Compliance with the creepage distances and clearance to DIN EN 60 664-1 should be checked in the final assembly or final application. 30 15 x 5 – 25 x 10 b 25 PLS 800 20 c PLS 1600 110 Model No. SV 3073.000 100 Ip short-circuit current [kA] 105 Basis of test: – VDE 0660, part 500/IEC 60 439 30 x 10 d e Number of poles SV 9340.050 3-pole a SV 9340.030 1-pole d SV 9340.050 3-pole b SV 9340.030 1-pole c SV 9341.050 3-pole e SV 9342.050 3-pole SV 9342.030 1-pole Curve a Busbar support spacing [mm] up to 1250 A, 3-pole Rated operating voltage: up to 1000 V AC Level of contamination: 3 Rated frequency: 50/60 Hz 35 Support 200 250 300 350 400 450 500 550 Busbar support 100 mm bar centre distance, for busbars 30 x 10 – 60 x 10 mm Busbar mm a 40 a 95 b 90 Rated current up to A Curve 30 x 10 800 d 40 x 10 850 c 50 x 10 1000 b 60 x 10 1250 a Busbar E-Cu mm Rated current up to A Curve 50 x 10 1000 c 60 x 10 1250 b 80 x 10 1600 a 85 80 75 d 70 c 65 Test implemented: – Rated peak withstand current Ipk Busbar E-Cu mm 60 200 300 400 500 600 Busbar support spacing [mm] 160 up to 1600 A, 3-pole 150 Model No. SV 3052.000 185 mm bar centre distance, for busbars 50 x 10 – 80 x 10 mm Rated operating voltage: up to 1000 V AC Level of contamination: 3 Rated frequency: 50/60 Hz Basis of test: – VDE 0660, part 500/IEC 60 439 Test implemented: – Rated peak withstand current Ipk Technical details/Power distribution/02.2014 Ip short-circuit current [kA] Busbar support a 140 130 b 120 110 c 100 90 80 200 400 600 800 1000 Busbar support spacing [mm] dri1308052en.fm – 2-105 – 3 of 7 Power distribution Short-circuit withstand strength to IEC Model No. SV 3055.000 (2500 A), bar accommodation 3 x 2 x 80 x 10 mm Busbar support up to 2500 A/3000 A, 3-pole Model No. SV 3057.000 (3000 A), bar accommodation 3 x 2 x 100 x 10 mm Basis of test: – VDE 0660, part 500/IEC 60 439 Test implemented: – Rated peak withstand current Ipk 160 160 150 150 Ip short-circuit current [kA] Rated operating voltage: up to 1000 V AC Level of contamination: 3 Rated frequency: 50/60 Hz Ip short-circuit current [kA] 150 mm bar centre distance 140 130 120 110 100 90 80 150 200 130 120 110 100 90 300 400 500 600 700 Busbar support spacing [mm] dri1308052en.fm – 2-105 – 4 of 7 140 800 80 150 200 300 400 500 600 700 800 Busbar support spacing [mm] Technical details/Power distribution/02.2014 Power distribution Short-circuit withstand strength to IEC Busbar support Flat-PLS 60 1 to 4-pole Model No. SV 9676.002/SV 9676.020 160 Ip peak short-circuit current [kA] 120 mm bar centre distance, for busbars 40 x 10 – 60 x 10 mm. Population: 2, 3 or 4 bars per support Rated operating voltage: up to 690 V AC Rated insulation voltage: 1000 V AC Rated impulse withstand voltage: 8 kV Overvoltage category: IV Level of contamination: 3 Rated frequency: 50/60 Hz 140 130 110 Icw kA/1 sec. 4 x 60 x 10 450 55.0 4 x 60 x 10 900 40.0 4 x 60 x 10 450 60.0 4 x 60 x 10 900 45.0 4 x 60 x 10 450 70.0 4 x 60 x 10 900 60.0 a 100 90 80 I mm b 120 Test implemented: – Rated peak withstand current Ipk – Rated short-time withstand current Icw Busbar mm c 150 450 500 550 600 650 700 750 800 850 900 800 850 900 Busbar support spacing [mm] Curve Curve a b Design of busbar attachment a Basic version1) b With busbar claws2) c With busbar stabilisers and busbar claws2) 1) Basic version consists of system attachment with fitted busbar support 2) For version see below c I = Busbar support spacing Busbar support Flat-PLS 100 1 to 4-pole Model No. SV 9676.004/SV 9676.021 260 Ip peak short-circuit current [kA] 165 mm bar centre distance, for busbars 80 x 10 – 100 x 10 mm. Population: 2, 3 or 4 bars per support Rated operating voltage: up to 690 V AC Rated insulation voltage: 1000 V AC Rated impulse withstand voltage: 8 kV Overvoltage category: IV Level of contamination: 3 Rated frequency: 50/60 Hz 240 200 180 Busbar mm I mm Icw kA/1 sec. 4 x 100 x 10 450 75.0 4 x 100 x 10 900 52.0 4 x 100 x 10 450 81.6 4 x 100 x 10 900 55.9 4 x 100 x 10 450 110.0 4 x 100 x 10 900 78.0 b 160 140 a 120 100 Test implemented: – Rated peak withstand current Ipk – Rated short-time withstand current Icw c 220 450 500 550 600 650 700 750 Busbar support spacing [mm] Curve Curve a b Design of busbar attachment a Basic version1) b With busbar claws2) c With busbar stabilisers and busbar claws2) 1) Basic version consists of system attachment with fitted busbar support. 2) For version see below c I = Busbar support spacing Busbar claws Max. distance Model No. SV 9676.017/SV 9676.019 Busbar claw – Busbar claw Supplementary information on Flat-PLS short-circuit protection diagrams Mounting distance of busbar claws: In order to achieve the cited short-circuit protection, the busbar claws must be fitted at a spacing of 300 mm. If there is a busbar support, a contact maker or a longitudinal connector located within this 300 mm, there is no need to fit a claw at this point. Busbar claw – Busbar support ≤ 300 Busbar claw – Contact maker ≤ 300 Busbar claw – Longitudinal connector ≤ 300 Technical details/Power distribution/02.2014 mm ≤ 300 dri1308052en.fm – 2-105 – 5 of 7 Power distribution Short-circuit withstand strength to UL 508 The short-circuit withstand strength of RiLine has been extensively tested. Short-circuit withstand strength to UL criteria is assessed via the root-mean-square value of the shortcircuit current (IRMS), which must be applied for at least 3 periods (60 ms). During the course of testing, the test equipment has been adjusted to the respective root-mean-square values (IRMS). The resultant peak short-circuit currents Ip are shown in the diagrams below. Busbar support Settings IRMS (Ieff.) of the test equipment without pre-fuse: 60 mm bar centre distance, for busbars 15 x 5 – 30 x 10 mm Note: SV 9340.050 with E-Cu 30 x 5/10 mm The following short-circuit value can be achieved with a pre-fuse: – Support spacing: 350 mm – Fuse: Class L 800 A – IRMS: 50 kA Support spacing mm IRMS kA Support spacing mm IRMS kA 250 35 250 30 500 25 500 22 Ip peak short-circuit current [kA] SV 9340.050 with 30 x 5/10 mm SV 9340.050 with 25 x 5 mm 20 x 5/10 mm 15 x 5/10 mm 80 80 75 75 70 70 65 65 Ip peak short-circuit current [kA] for feeder circuits 700 A, 3-pole 60 55 50 45 40 35 60 55 50 45 40 35 30 30 25 25 20 20 200 250 300 350 400 450 500 550 600 200 250 300 350 400 450 500 550 600 Busbar support spacing [mm] for feeder circuits 700 A (PLS 800)/1400 A (PLS 1600), 3-pole Settings IRMS (Ieff.) of the test equipment without pre-fuse: 60 mm bar centre distance, for PLS special busbars Note: SV 9342.050 (PLS 1600) The following short-circuit value can be achieved with a pre-fuse: – Support spacing: 250 mm – Fuse: Class L 1400 A – IRMS: 65 kA Support spacing mm IRMS kA Support spacing mm IRMS kA 200 22 150 35 500 14 500 25 Ip peak short-circuit current [kA] SV 9341.050 (PLS 800) 80 80 75 75 70 70 65 65 60 55 50 45 40 35 60 55 50 45 40 35 30 30 25 25 20 20 150 200 250 300 350 400 450 500 550 Busbar support spacing [mm] dri1308052en.fm – 2-105 – 6 of 7 SV 9342.050 (PLS 1600) Ip peak short-circuit current [kA] Busbar support Busbar support spacing [mm] 150 200 250 300 350 400 450 500 550 Busbar support spacing [mm] Technical details/Power distribution/02.2014 Power distribution Short-circuit withstand strength to UL 508 80 for feeder circuits up to 700 A, 4-pole 75 Model No. SV 9340.004 70 60 mm bar centre distance Ip peak short-circuit current [kA] Busbar support Settings IRMS (Ieff.) of the test equipment without pre-fuse: Busbar mm 65 60 15 x 5 – 30 x 10 55 Support spacing mm IRMS 250 30 500 22 50 45 40 35 30 25 20 200 250 300 350 400 450 500 Busbar support spacing [mm] 80 for feeder circuits up to 1400 A, 4-pole 75 Model No. SV 9342.004 70 60 mm bar centre distance, for PLS special busbars 65 Ip peak short-circuit current [kA] Busbar support Settings IRMS (Ieff.) of the test equipment without pre-fuse: Busbar mm 60 PLS 1600 55 Support spacing mm RMS kA 150 35 500 25 50 45 40 35 30 25 20 150 200 250 300 350 400 450 500 550 Busbar support spacing [mm] Technical details/Power distribution/02.2014 dri1308052en.fm – 2-105 – 7 of 7