S&C Alduti-Rupter® Switches with Power Fuses★
Outdoor Distribution (14.4 kV through 46 kV)
Specifications
Conditions of Sale
STANDARD: Seller’s standard conditions of sale set
forth in Price Sheet 150 apply, except as modified under
“WARRANTY QUALIFICATIONS” on page 2.
SPECIAL TO THIS PRODUCT:
INCLUSIONS: S&C Alduti-Rupter Switches with Power
Fuses are available in three-pole group-operated designs
that feature pole-units mounted on individual bases for
vertical mounting. Single-Pole Style switches are also
available in vertical mounting configurations for use in
single-phase switching applications. Single-Pole Style
switches are operable using a conventional hookstick.
All three-pole Alduti-Rupter Switches with Power Fuses
are provided with an operating mechanism that includes:
• Three switch poles.
• A detailed erection drawing (ED) of the applicable
mounting arrangement.
• All required interphase and vertical pipe as specified
on the erection drawing (ED). Operating mechanism
includes three 10′-4″ (3150 mm) sections of vertical
pipe (1¼″ (32 mm) IPS for reciprocating operating
mechanisms and 1½″ (38 mm) IPS for rotating operating mechanisms).
• The appropriate set of operating-mechanism components; e.g., handle, rod guides or guide bearings, couplings, bell crank assembly, etc.
• Complete installation and maintenance instructions.
Mounting Arrangements
S&C Three-Pole Alduti-Rupter Switches with Power Fuses
are available in Standard Mounting Arrangements as
described in S&C Data Bulletin 771-80. Departures from
Standard Mounting Arrangements are also available and
fall into three categories:
1. Standard Minor Modifications of Standard Mounting
Arrangements are those which are so frequently
encountered that they are included on S&C’s basic
erection drawings (ED). Applicability of Standard
Minor Modifications are listed in the table on page 8.
The applicable Standard Minor Modifications may be
specified by adding the appropriate Catalog Number
Suffix “-S” to the erection drawing (ED) number.
2. Special Minor Modifications of Standard Mounting
Arrangements are those which include such departures
as special base drillings or special mounting brackets for
operating-mechanism components. For this category of
“special,” S&C will prepare a custom erection drawing
(ED) based on the Standard Mounting Arrangement
erection drawing (ED). Switches will be supplied with an
operating mechanism for the Special Minor Modification
of a Standard Mounting Arrangement.
3. Special Mounting Arrangements are those which
involve complete departures from the Standard
Mounting Arrangements brought about by customizing
an S&C Alduti-Rupter Switch with Power Fuses to fit the
user’s structure. Custom erection drawings (ED) will be
provided as required.
EXCLUSIONS: Alduti-Rupter Switches with Power Fuses
do not include connectors. Various connector arrangements
are available as listed in the table on page 13. Specify the
quantity and catalog number of connector arrangement
desired.
Alduti-Rupter Switches with Power Fuses do not include
holders, refill units, or fuse units.
SPECIFICATION DEVIATIONS: S&C Alduti-Rupter
Switches with Power Fuses are offered with a choice
of Cypoxy®■ or porcelain station post insulators. The
standard insulator color is gray. When switches are to be
provided with special insulators or special connectors,
consult the nearest S&C Sales Office for availability.
Switches of a given voltage rating can be furnished with
insulators of the next higher voltage rating—add suffix “-Z3”
to the catalog number.
■ Cypoxy is the S&C trademark for S&C’s cycloaliphatic epoxy resin
system. Cypoxy is nontracking, self-scouring, nonweathering . . . there’s
never a compromise of insulation integrity.
★ S&C Alduti-Rupter® Switches with Power Fuses are manufactured in accordance with a quality system certified to ISO 9001, and they are Rural
Utilities Service approved.
July 1, 2013© S&C Electric Company
Specification Bulletin 771-31
S&C Alduti-Rupter® Switches with Power Fuses
Conditions of Sale—Continued
Switches can be supplied with tin-plated terminal pads. To
specify, add suffix “-Z5” to the catalog number of the switch.
Single-, two-, and four-pole group-operated switches
are also available for Alduti-Rupter Switches with Power
Fuses.
Alduti-Rupter Switches with Power Fuses—Type SM
does not include SM Refill Units or SM Fuse Holders. The
catalog number of the holder may be obtained from the
same horizontal line in which the switch is listed.
Alduti-Rupter Switches with Power Fuses—Type SMD
do not include SMD® Fuse Units or SMU-20® Fuse Units.
In selecting a refill unit or fuse unit, watch these points:
• Alduti-Rupter Switches with Power Fuses—Type SM—
match refill unit type to holder type.
• Alduti-Rupter Switches with Power Fuses—Type
SMD—select fuse unit of the type indicated.
Refill units and fuse units are listed separately. In
selecting a refill unit or fuse unit, consider the following:
1. Description—SM-4®, SM-5®, SMD-1A, SMD-2C, or
SMU-20
2. Voltage rating
3. Ampere rating
4. Speed.
POWER OPERATION: Power operation or, if desired,
remote supervisory control may be provided for S&C AldutiRupter Switches with Power Fuses by the addition of the
appropriate S&C Switch Operator—Type AS-1A, or AS-10,
or by adding an S&C M Series® Switch Operator.
S&C Switch Operators—Types AS-1A and Type AS-10 are
for power operation of Alduti-Rupter Switches with Power
2
S&C Specification Bulletin 771-31
Fuses with rotating-type and reciprocating-type operating
mechanisms, respectively. These switch operators are
high-speed operators, with operating times not exceeding
.75 second and 1.2 seconds maximum, respectively. This
high operating speed provides sufficient moving-contact
velocity in the interrupters to ensure full interrupting
capability and long operating life.
M Series Switch Operators are available in two
versions—torsional, for rotating-type mechanisms,
and reciprocating, for reciprocating-type operating
mechanisms. Both versions operate in .5 seconds. This
high operating speed is fully compatible with the movingcontact velocity required by the interrupters to ensure full
interrupting capability for the applicable switch styles and
mounting arrangements.
Power operation is available for certain mounting
arrangements only. Consult the nearest S&C Sales Office
for availability.
For additional details concerning S&C Switch
Operators—Types AS-1A or AS-10, refer to Specification
Bulletin 769-31. For additional details concerning M Series
Switch Operators, refer to Specification Bulletin 1051-31.
WARRANTY QUALIFICATIONS: The standard warranty
contained in S&C’s standard conditions of sale, as set forth
in Price Sheet 150, does not apply when Alduti-Rupter
Switches with Power Fuses are power operated using a
switch operator other than S&C manufacture.
S&C Alduti-Rupter® Switches with Power Fuses
How to Order
Alduti-Rupter Switch with Power Fuses
1. Switch and connectors
a. Obtain the catalog number of the desired switch
from pages 6 and 7.
b. For three-pole switches, obtain the ED number of
the desired mounting arrangement from S&C Data
Bulletin 771-80.
• If a Standard Minor Modification is desired for a
three-pole switch, obtain the suffix of the desired
modification from page 8. Add the suffix to the
ED number of the switch.
c. If special minor modifications of standard mounting
arrangements or special mounting arrangements
are desired, refer to the “Mounting Arrangements”
section on page 1.
d. If specification deviations are desired, such as
switches furnished less insulators, with insulators of
the next higher or lower voltage rating, less bases,
less switch poles, or with additional switch poles,
see the “Specification Deviations” section on pages
1 and 2.
e. If connectors are desired, obtain the catalog number
of the desired connector from page 13.
2. Fuse components
a. For Type SM Power Fuses: Obtain the catalog
number of the applicable holder from the “Holder”
column on page 6, reading from the same line on
which the switch catalog number is listed, and taking care to note the number of holders required
per switch. Next, obtain the catalog number of the
desired refill unit from the tables on pages 9 and 10,
taking care to match the voltage rating of the refill
unit to that of the switch.
b. For Type SMD Power Fuses: Obtain the catalog
number of the desired fuse unit from the tables on
pages 11 and 12, taking care to match the voltage
rating of the fuse unit to that of the switch.
Handling Tools
Obtain the catalog number of the recommended handling
tool(s) from the table on page 8.
Note: If power operation or remote supervisory control
are desired, S&C Switch Operator—Type AS-1A and AS-10,
or M Series Switch Operator may be added to switches in
certain mounting arrangements. For ordering information
on S&C Switch Operator—Type AS-1A and AS-10 see
Specification Bulletin 769-31. For ordering information on M
Series Switch Operators see Specification Bulletin 1051-31.
Note: Spare or replacement parts are ordered using the
same method outlined above.
S&C Specification Bulletin 771-31
3
S&C Alduti-Rupter® Switches with Power Fuses
Application Classifications (See symbols on pages 6 and 7)
Application
Symbol
■
A
A
A
A
Three-phase transformer (or three-phase bank
of single-phase transformers) connected solidly
grounded-wye on the primary (switch) side and
delta on the secondary side
●
E
—
E
—
All other connections of three-phase
transformers (or three-phase banks of singlephase transformers)—including autotransformers
●
G
G
G
G
Single-phase transformer connected phase-toground on the primary (switch) side
●
E
—
—
—
Single-phase transformer connected phase-tophase on the primary (switch) side
●
G
G
—
—
■
A
A
A
A
Three-phase circuits with all load-side threephase transformers (or three-phase banks of
single-phase transformers) connected solidly
grounded-wye on the primary (switch) side and
delta on the secondary side, and all load-side
single-phase transformers connected phase-toground on the primary (switch) side
■
E
—
E
—
Three-phase circuits with load-side transformers
connected other than as described above
■
G
G
G
G
Single-phase circuits with all load-side transformers connected phase-to-ground on the
primary (switch) side
■
E
—
—
—
Single-phase circuits with load-side transformers
connected other than as described above
■
G
G
—
—
Line Dropping
▲
K
L
K
L
Load Splitting
■
A
A
A
A
Three-phase circuits with all load-side threephase transformers (or three-phase banks of
single-phase transformers) connected solidly
grounded-wye on the primary (switch) side and
delta on the secondary side, and all load-side
single-phase transformers connected phase-toground on the primary (switch) side
■
E
—
E
—
Three-phase circuits with load-side transformers
connected other than as described above
■
G
G
G
G
Single-phase circuits with all load-side transformers connected phase-to-ground on the
primary (switch) side
■
E
—
—
—
Single-phase circuits with load-side transformers
connected other than as described above
■
G
G
—
—
Shielded cable
▼
H
L
H
L
Load Dropping
and
Magnetizing
Current
Switching
Load Splitting
(Parallel or
Loop Switching)
Cable
Switching
Three-Pole Switch
Ungrounded
System
Qualifications
Parallel
Switching༅
Line
Switching
Single-Pole Switch
Solidly or
Effectively༄
Grounded
System
Class
Transformer
Switching
Maximum
Interrupting
Duty,༃
Amperes,
RMS
Load Dropping
Load
Dropping
Cable Dropping
(charging current)
Capacitor Bank Switching,
Single Bank Only
Solidly or
EffecUngrounded
tively༄
System
Grounded
System
▼
K
L
K
L
Grounded capacitor bank
100
H
L
H
L
Ungrounded capacitor bank
100
L
L
L
L
Unshielded cable
FOR FOOTNOTES SEE BOTTOM OF PAGE 5
4
S&C Specification Bulletin 771-31
▶
S&C Alduti-Rupter® Switches with Power Fuses
Conditional Applications (See symbols in parentheses on pages 6 and 7)
Alduti-Rupter Switch
Style
Voltage
Rating, kV
Application
Symbol
Maximum Operating Voltage
Line-to-Line, kV༃
Maximum Interrupting Duty
Over 15.5 and up through 31.7
60 amperes
Over 31.7 and up through 38.0
Line dropping only
Over 15.5 and up through 20.0
60 amperes
Over 20.0 and up through 38.0
Line dropping only
K
34.5
L
Three-Pole Double-Break
Over 15.5 and up through 31.7
60 amperes
Over 31.7 and up through 48.3
Line dropping only
Over 15.5 and up through 20.0
60 amperes
K
46
L
14.4
L
Over 20.0 and up through 48.3
Line dropping only
Over 12.0 and up through 17.0
Line dropping only
Over 15.5 and up through 22.8
60 amperes
H
Over 22.8 and up through 27.0
■
Over 15.5 and up through 19.0
Cable and line dropping only
Over 19.0 and up through 27.0
Line dropping only■
L
Over 12.0 and up through 27.0
Line dropping only
L
Over 15.5 and up through 17.0
Line dropping only
Over 15.5 and up through 22.8
60 amperes
Three-Pole Vertical-Break
25
K
14.4
H
Over 22.8 and up through 27.0
■
Over 15.5 and up through 19.0
Cable and line dropping only
Over 19.0 and up through 27.0
Line dropping only■
Over 15.5 and up through 27.0
Line dropping only
Single-Pole
25
K
L
༃ Where maximum operating voltage for a conditional application is
■ Three-Pole Vertical-Break and Single-Pole Styles may be applied for
lower than the lowest range listed, refer to “Application Classifications”
table on page 4 for applicable maximum interrupting duty values.
cable dropping (charging current) of 3 miles (4.8 km) of No. 1/0 cable or
1.2 miles (1.9 km) of 1000 kc mil cable, or equivalent, provided phase
spacing is 55 inches (1397 mm) minimum.
◀ഩFOOTNOTES FOR TABLE ON PAGE 4
༃ Lower values may apply for “conditional applications.” Refer to
■ Same as continuous-current rating.
“Conditional Applications” table above.
● Alduti-Rupter Switches with Power Fuses will drop loads through
༄ X0 /X1 from 0 to + 3.0 and R0 /X1 from 0 to + 1.0.
༅ Applies to switching of the primary of a transformer which remains
energized from the secondary bus, or to disconnecting of a loaded secondary bus from one of two transformers supplying that bus while the
primary side of the transformer remains energized.
600 amperes, and will switch magnetizing currents associated with such
loads.
▲ Maximum length of line: 100 miles (161 km).
▼ 80 miles (129 km) of No. 1/0 cable, or 30 miles (48 km) of 1000 kc mil
cable, or equivalent.
S&C Specification Bulletin 771-31
5
S&C Alduti-Rupter® Switches with Power Fuses
Alduti-Rupter Switches wth Power Fuses—Type SM for Vertical Mounting༃༄
Rating༅
Style
Three-Pole
Double-Break
with Disconnect
180° Opening
Fuse༊
Fuse
Type and
Max Amp
Rating
SM-4
200E
Switches (less Holders)
Nom.
Max
BIL
Fuse
Interr.
Amps,
RMS,
Sym.༆
34.5
38
200
6 250
kV
Applications༇
(see pages
4 and 5)
AEGH(KL)
Cypoxy Station Porcelain Station
Post
Post
Insulators
Insulators
Catalog
Number༈༉
Catalog
Number༈༉
320704R10-E
320704R10
Holder
(Refill Units not
included)
No.
Req’d.
3
Catalog
Number
Page
Reference for
Dimensional
Information
86054
14
Three-Pole
Vertical-Break
with Disconnect
180° Opening
Fuse
Single-Pole
with Disconnect
180° Opening
Fuse
SM-5
300E
34.5
38
200
17 500
AEGH(KL)
320714R10-E
320714R10
3
86154R2
SM-4
200E
14.4
25
17.0
27
110
150
12 500
9 400
AEGHK(L)
AEG(HKL)
135302R4-E
135303R5-E
135302R4
135303R5
3
3
86052
86053
SM-5
400E■
14.4
25
17.0
27
110
150
34 000▲
20 000
AEGHK(L)
AEG(HKL)
135332R4-E
135333R5-E
135332R4
135333R5
3
3
86152R2
86153R2
SM-5
in
parallel
720E
14.4
17.0
110
25 000★
AEGHK(L)
135442R5-E
135442R5
6
86152R2
SM-4
200E
14.4
25
17.0
27
110
150
12 500
9 400
AEGHK(L)
AEG(HKL)
136302-E
136303R5-E
136302
136303R5
1
1
86052
86053
15
16
17
SM-5
400E■
14.4
25
17.0
27
110
150
34 000▲
20 000
AEGHK(L)
AEG(HKL)
༃ The switches shown include the appropriate set of operating-
mechanism components as specified on the erection drawing (ED) for
the switch. Switches do not include connectors (refer to table on page 13)
or SM Refill Units (refer to tables on pages 9 and 10).
༄ The switches are available in a variety of Standard Mounting
Arrangements, designated by erection drawing (ED) number, as
described in Data Bulletin 771-80. Specify the applicable erection drawing
(ED) number when ordering.
༅ Switches are rated 600 amperes, RMS, continuous and interrupting.
Momentary rating of the switches is 40,000 amperes, RMS, asymmetrical,
except for 14.4-kV switches with Type SM-5 Power Fuses, for which the
momentary ratings, based on limiting of the let-through current by the
fuses, are 54,000 amperes, RMS, asymmetrical at 13.8 kV and
14.4 kV, 60 hertz only, (55,000 amperes, RMS, asymmetrical on
7.2/12.47GrY-kV 60-hertz systems only). Maximum ampere ratings of
fuses are shown in second column.
༆ Symmetrical ratings assigned are based on available short-circuit
current at locations where the X/R ratio is 15. The interrupting ratings
expressed in amperes, RMS, asymmetrical are 1.6 times the symmetrical
ratings listed. Higher symmetrical ratings have been determined for these
fuses applied at lower system voltages and in locations where X/R = 10
and X/R = 5. These higher ratings as well as asymmetrical ratings are
given in S&C Descriptive Bulletin 242-30.
6
S&C Specification Bulletin 771-31
136332R2-E
136333R5-E
136332R2
136333R5
1
1
86152R2
86153R2
༇ Applications indicated by symbols in parentheses are conditional.
See “Conditional Applications” table, page 5.
༈ For a three-pole switch to be supplied less operating pipe, specify by
adding Catalog Number Suffix “-P” to the erection drawing (ED) number.
༉ Standard Minor Modifications of the Standard Mounting
Arrangement(s) for these switches are listed in the table on page 8. The
applicable Standard Minor Modifications listed therein may be specified
by adding the appropriate “-S” suffix to the erection drawing (ED) number.
Refer to page 1 for Special Minor Modifications and Special Mounting
Arrangements for these switches.
༊ Three-Pole Double-Break Style Switches with Power Fuses rated
34.5 kV and 46 kV, while provided with design features for fault closing,
are not assigned fault closing ratings or capabilities because special
mounting arrangements may deny the requisite high speed closing
behavior.
■ Maximum ampere rating at 25 kV is 300E.
▲ 60-hertz rating. For systems above 15.5 kV through 17.0 kV,
interrupting rating is 25,000 amperes, RMS, symmetrical, 50/60 hertz.
★ 60-hertz rating.
S&C Alduti-Rupter® Switches with Power Fuses
Alduti-Rupter Switches with Power Fuses—Type SMD for Vertical Mounting༃༄
Cypoxy Station
Post Insulators
Rating༅
Style
Three-Pole
Double-Break༊
Fuse
Type and
Max Amp
Rating
SMD-1A
200E
kV
Fuse
Interr.
Amps,
RMS,
Sym.༆
Porcelain Station
Post Insulators
Page Reference
Applications༇
Catalog Number Catalog Number for Dimensional
(see pages
(including
(including
Information
4 and 5)
Fuse-Unit
Fuse-Unit
End Fittings)༈༉ End Fittings)༈༉
Nom.
Max
BIL
34.5
38
200
17 500
AEGH(KL)
145814R10-E
145814R10
46
48.3
250
13 100
AEG(KL)
145815R10-E
145815R10
18
SMD-2C
300E
SMD-20■
34.5
38
200
33 500
AEGH(KL)
145824R10-E
145824R10
46
48.3
250
31 500
AEG(KL)
145825R10-E
145825R10
34.5
38
200
10 000★
AEGH(KL)
145844R1-E
145844R1
14.4
17.0
110
14 000★
AEGHK(L)
135552R1-E
135552R1
25
27
150
12 500★
AEG(HKL)
135553R5-E
135553R5
200E
19
Three-Pole
Vertical-Break
SMD-20■
200E
20
༃ The switches shown include the appropriate set of operating-
༇ Applications indicated by symbols in parentheses are conditional.
mechanism components as specified by the erection drawing (ED) for the
switch. Switches do not include connectors (refer to table on page 13),
SMD Fuse Units (refer to table on page 11), or SMU-20 Fuse Units (refer
to table on page 12).
༈ For a three-pole switch to be supplied less operating pipe, specify by
༄ Switches are available in a variety of Standard Mounting Arrangements,
designated by erection drawing (ED) number, as described in Data
Bulletin 771-80. Specify the applicable erection drawing (ED) number
when ordering.
༅ Switches are rated 600 amperes, RMS, continuous and interrupting.
Momentary rating of the switches is 40,000 amperes, RMS, asymmetrical,
except for switches with Type SMD-2C Power Fuses, for which the
momentary ratings, based on limiting of the let-through current by
the fuses, are 53,500 amperes, RMS, asymmetrical for models rated
34.5 kV and 50,500 amperes, RMS, asymmetrical for models rated 46 kV.
Maximum ampere ratings of fuses are shown in second column.
༆ Symmetrical ratings assigned are based on available short-circuit
current at locations where the X/R ratio is 15. The interrupting ratings
expressed in amperes, RMS, asymmetrical are 1.6 times the symmetrical
ratings listed. Higher symmetrical ratings have been determined for these
fuses applied at lower system voltages and in locations where X/R = 10
and X/R = 5. These higher ratings as well as asymmetrical ratings are
given in S&C Descriptive Bulletins 212-30 and 242-32, as applicable.
See “Conditional Applications” table, page 5.
adding Catalog Number Suffix “-P” to the erection drawing (ED) number.
༉ Standard
Minor Modifications of the Standard Mounting
Arrangement(s) for these switches are listed in the table on page 8 of
this specification bulletin. The applicable Standard Minor Modifications
listed therein may be specified by adding the appropriate “-S” suffix to
the erection drawing (ED) number. Refer to page 1 for Special Minor
Modifications and Special Mounting Arrangements for these switches.
༊ Three-Pole Double-Break Style Switches with Power Fuses rated
34.5 kV and 46 kV, while provided with design features for fault closing,
are not assigned fault closing ratings or capabilities because special
mounting arrangements may deny the requisite high-speed closing
behavior.
■ SMD-20 Power Fuses accommodate SMU-20 Fuse Units in ratings
through 200K amperes as well as 200E amperes.
★ 60-hertz rating.
S&C Specification Bulletin 771-31
7
S&C Alduti-Rupter® Switches with Power Fuses
Parts
For Use on Alduti-Rupter Switches
Style
kV
Catalog
Number
Three-Pole Vertical-Break and
Single-Pole
7.2
SA-30817R2
14.4 or 25
SA-30818R4
Three-Pole Double-Break༃
All
SDA-10175
Spare End Fittings for SMD-1A Fuse Unit
Three-Pole Double-Break
All
3004R1
Spare End Fittings for SMD-2C Fuse Unit
Three-Pole Double-Break
All
3032R1
Spare End Fittings for SMU-20 Fuse Unit
Three-Pole Double-Break and
Three-Pole Vertical-Break
All
3095
Item
Spare or Replacement Interrupter
Spare or Replacement Interrupter with integral mounting bracket
and muffler
༃ Previous designs of Three-Pole Double-Break Switches with Power
Fuses require catalog number 4559R1 Interrupter.
Handling Tools
For Removal and Installation of
Catalog Number
Large Round Socket
Item
SMD-2C Fuse Unit
4407R4
Small Round Socket
SMD-1A Fuse Unit
4408R4
All
4402R2
Station Prong
Universal Pole◆
◆ Select to match height of installation. Refer to Specification Bulletin
851-31.
Standard Minor Modifications—For Three-Pole Mounting Styles
Applicable to Three-Pole
Mounting Styles
Item
Suffix to be
Added to Erection
Drawing Number
2⅝″ (67 mm) Diameter Tubular Fiberglass Insulating Section in vertical operating shaft
All
-S1
One Cypoxy Insulator Unit in vertical operating shaft
All
-S2
Insulated Interphase Sections and One Fiberglass Insulating Section in vertical operating
shaft
All
-S3■
Insulated Interphase Sections and One Cypoxy Insulator Unit in vertical operating shaft
All
-S4■
2″ (51 mm) IPS Pipe—required for rotating-type operating-mechanism vertical shaft when
such shaft exceeds three 10′– 4″ (3150 mm) sections
All
-S5
One extra pipe section, 2″ (51 mm) pipe
All rotating
operating mechanisms
-S5A
Two extra pipe sections, 2″ (51 mm) pipe
All rotating
operating mechanisms
-S5B
Refer to ED drawing
-S5C
Three extra pipe sections, 2″ (51 mm) pipe
Key Interlock—single lock for “locked-open” application
All
-S6
Auxiliary contact switch with 4 NO & 4 NC contacts (600 VAC, 20 Amperes)
All
-S7
Provision for power operation of pole-mounted switches by S&C Switch Operator—Type
AS-1A or AS-10
All
-S8▲
Provision for power operation of steel-structure or pedestal-mounted switches by S&C Switch
Operator—Type AS-1A or AS-10
All
-S9▲
All rated
14.4-kV & 25-kV༃
-S16▲
Provision for power operation of pole-mounted switches by M Series Switch Operator—
Torsional and Reciprocating
One extra pipe section, 1¼″ (32 mm) pipe
All reciprocating operating
mechanisms
-V1
Two extra pipe sections, 1¼″ (32 mm) pipe
All reciprocating operating
mechanisms
-V2
༃ Switches at 34.5 kV and 46 kV may be suitable for use with M-Series
▲ Not all mounting arrangements are suitable for power operation,
Switch Operators. Contact the nearest S&C Sales Office for availability.
contact the nearest S&C Sales Office for availability.
■ Not available for power-operated switches.
8
S&C Specification Bulletin 771-31
S&C Alduti-Rupter® Switches with Power Fuses
SM-4® Refill Units (For Use in SM-4 Holders)
Rating,
Amperes
Speed
1
2
3E
5E
7E
10E
13E
15E
20E
25E
30E
40E
50E
65E
80E
100E
125E
150E
175E
200E
210
25 kV Nominal, 27 kV Max
Catalog Number
Catalog Number
S&C Std.
TCC 115-4
S&C Std.
TCC 115-4
122001R4
122002R4
123001R4
123002R4
S&C Std.
TCC 153-4
Speed
14.4 kV Nominal, 17.0 kV Max
122005R4
122007R4
122010R4
122015R4
122020R4
122025R4
122030R4
122040R4
122050R4
122060R4
122075R4
122100R4
122125R4
122150R4
122200R4
122250R4
122275R4
122300R4
S&C Slow
TCC 119-4
S&C Coord.
TCC 179-4
252025R4
252030R4
252040R4
252050R4
252060R4
252075R4
252100R4
252125R4
252150R4
252200R4
252250R4
252275R4
252300R4
S&C Std.
TCC 153-4
S&C Slow
TCC 119-4
123005R4
123007R4
123010R4
123015R4
123020R4
123025R4
123030R4
123040R4
123050R4
123060R4
123075R4
123100R4
123125R4
123150R4
123200R4
123250R4
123275R4
123300R4
253025R4
253030R4
253040R4
253050R4
253060R4
253075R4
253100R4
253125R4
253150R4
253200R4
253250R4
253275R4
253300R4
382210R4■
34.5 kV Nominal, 38 kV Max
Rating,
Amperes
Catalog Number
S&C Std.
TCC 115-4
Speed
1
2
Speed
3E
5E
7E
10E
13E
15E
20E
25E
30E
40E
50E
65E
80E
100E
125E
150E
175E
200E
124001R4
124002R4
S&C Std.
S&C Std.
TCC 153-4
TCC 119-4
124005R4
124007R4
124010R4
124015R4
124020R4
124025R4
124030R4
124040R4
124050R4
124060R4
124075R4
124100R4
124125R4
124150R4
124200R4
124250R4
124275R4
124300R4
254025R4
254030R4
254040R4
254050R4
254060R4
254075R4
254100R4
254125R4
254150R4
254200R4
254250R4
254275R4
254300R4
■ This S&C Coordinating Speed refill unit should be applied where the
maximum continuous load current does not exceed 200 amperes and
where all fault currents below 1000 amperes will be cleared by another
fuse.
S&C Specification Bulletin 771-31
9
S&C Alduti-Rupter® Switches with Power Fuses
SM-5® Refill Units (For Use in SM-5 Holders)
Rating,
Amperes
Speed
1
2
Speed
3E
5E
7E
10E
13E
15E
20E
25E
30E
40E
50E
65E
80E
100E
125E
150E
175E
200E
250E
300E
400E
410E
420E
14.4 kV Nominal, 17.0 kV Max
25 kV Nominal, 27 kV Max
Catalog Number
Catalog Number
Catalog Number
S&C Std.
TCC 115-4
S&C Std.
TCC 115-4
S&C Std.
TCC 115-4
132001R4
132002R4
133001R4
133002R4
134001R4
134002R4
S&C Std.
TCC 153-4
132005R4
132007R4
132010R4
132015R4
132020R4
132025R4
132030R4
132040R4
132050R4
132060R4
132075R4
132100R4
132125R4
132150R4
132200R4
132250R4
132275R4
132300R4
132400R4
132500R4
132600R4
S&C Slow
TCC 119-4
S&C Coord.
TCC 173-4
S&C Std.
TCC 153-4
133005R4
133007R4
133010R4
133015R4
133020R4
133025R4
133030R4
133040R4
133050R4
133060R4
133075R4
133100R4
133125R4
133150R4
133200R4
133250R4
133275R4
133300R4
133400R4
133500R4
262025R4
262030R4
262040R4
262050R4
262060R4
262075R4
262100R4
262125R4
262150R4
262200R4
262250R4
262275R4
262300R4
262400R4
262500R4
262600R4
382410R4 ■
382420R4 ■
■ These S&C Coordinating Speed refill units should be applied where
the maximum continuous load current does not exceed 400 amperes
and where all fault currents below 3000 amperes for Catalog Numbers
381410R4 and 382410R4 and 4000 amperes for Catalog Numbers
381420R4 and 382420R4 will be cleared by another fuse.
10
34.5 kV Nominal, 38 kV Max
S&C Specification Bulletin 771-31
S&C Slow
TCC 119-4
S&C Std.
TCC 153-4
S&C Slow
TCC 119-4
263025R4
263030R4
263040R4
263050R4
263060R4
263075R4
263100R4
263125R4
263150R4
263200R4
263250R4
263275R4
263300R4
263400R4
263500R4
134005R4
134007R4
134010R4
134015R4
134020R4
134025R4
134030R4
134040R4
134050R4
134060R4
134075R4
134100R4
134125R4
134150R4
134200R4
134250R4
134275R4
134300R4
134400R4
134500R4
264025R4
264030R4
264040R4
264050R4
264060R4
264075R4
264100R4
264125R4
264150R4
264200R4
264250R4
264275R4
264300R4
264400R4
264500R4
S&C Alduti-Rupter® Switches with Power Fuses
SMD-1A Fuse Units
34.5 kV Nominal, 38 kV Max
Rating,
Amperes
46 kV Nominal, 48.3 kV Max
Catalog Number
Catalog Number
S&C Std.
TCC 115-1
Speed
1
444001R1
S&C Std.
TCC 153-1
Speed
3E
5E
7E
10E
13E
15E
20E
25E
30E
40E
50E
65E
80E
100E
125E
150E
175E
200E
S&C Std.
TCC 115-1
444003R2
444005R1
444007R1
444010R1
444013R1
444015R1
444020R1
444025R1
444030R1
444040R1
444050R1
444065R1
444080R1
444100R1
444125R1
444150R1
444175R1
444200R1
445001R1
S&C Slow
TCC 119-1
S&C Very Slow
TCC 176-1
S&C Std.
TCC 153-1
S&C Slow
TCC 119-1
S&C Coord.
TCC 176-1
564050
564065
564080
564100
564125
564150
564175
564200
445003R2
445005R1
445007R1
445010R1
445013R1
445015R1
445020R1
445025R1
445030R1
445040R1
445050R1
445065R1
445080R1
445100R1
445125R1
445150R1
445175R1
445200R1
455015R1
455020R1
455025R1
455030R1
455040R1
455050R1
455065R1
455080R1
455100R1
455125R1
455150R1
455175R1
455200R1
565050
565065
565080
565100
565125
565150
565175
565200
454015R1
454020R1
454025R1
454030R1
454040R1
454050R1
454065R1
454080R1
454100R1
454125R1
454150R1
454175R1
454200R1
SMD-2C Fuse Units
34.5 kV Nominal, 38 kV Max
Rating,
Amperes
46 kV Nominal, 48.3 kV Max
Catalog Number
Catalog Number
S&C Std.
TCC 115-1
Speed
1
Speed
3E
5E
7E
10E
13E
15E
20E
25E
30E
40E
50E
65E
80E
100E
125E
150E
175E
200E
250E
300E
S&C Std.
TCC 115-1
464001R3
S&C Std.
TCC 153-1
464003R3
464005R3
464007R3
464010R3
464013R3
464015R3
464020R3
464025R3
464030R3
464040R3
464050R3
464065R3
464080R3
464100R3
464125R3
464150R3
464175R3
464200R3
464250R3
464300R3
465001R3
S&C Slow
TCC 119-1
484015R3
484020R3
484025R3
484030R3
484040R3
484050R3
484065R3
484080R3
484100R3
484125R3
484150R3
484175R3
484200R3
484250R3
484300R3
S&C Very Slow
TCC 176-1
574050R3
574065R3
574080R3
574100R3
574125R3
574150R3
574175R3
574200R3
574250R3
S&C Std.
TCC 153-1
S&C Slow
TCC 119-1
465003R3
465005R3
465007R3
465010R3
465013R3
465015R3
465020R3
465025R3
465030R3
465040R3
465050R3
465065R3
465080R3
465100R3
465125R3
465150R3
465175R3
465200R3
465250R3
465300R3
485015R3
485020R3
485025R3
485030R3
485040R3
485050R3
485065R3
485080R3
485100R3
485125R3
485150R3
485175R3
485200R3
485250R3
485300R3
S&C Coord.
TCC 176-1
575050R3
575065R3
575080R3
575100R3
575125R3
575150R3
575175R3
575200R3
575250R3
S&C Specification Bulletin 771-31
11
S&C Alduti-Rupter® Switches with Power Fuses
SMU-20® Fuse Units
14.4 kV Nominal, 17.0 kV Max
“K” Ratings
Rating,
Amperes
Speed
“E” Ratings
Catalog
Number
S&C “K”
TCC 165-2
Rating,
Amperes
Speed
1
Speed
3K
6K
8K
10K
12K
15K
20K
25K
30K
40K
50K
65K
80K
100K
140K
200K
25 kV Nominal, 27 kV Max
702003
702006
702008
702010
702012
702015
702020
702025
702030
702040
702050
702065
702080
702100
702140
702200
5E
7E
10E
13E
15E
20E
25E
30E
40E
50E
65E
80E
100E
125E
150E
175E
200E
“K” Ratings
Catalog Number
S&C Std.
TCC 115-2
Speed
Rating,
Amperes
Speed
Catalog
Number
S&C “K”
TCC 165-2
Speed
1
Speed
3K
6K
8K
10K
12K
15K
20K
25K
30K
40K
50K
65K
80K
100K
140K
200K
12
704003
704006
704008
704010
704012
704015
704020
704025
704030
704040
704050
704065
704080
704100
704140
704200
5E
7E
10E
13E
15E
20E
25E
30E
40E
50E
65E
80E
100E
125E
150E
175E
200E
S&C “K”
TCC 165-2
612005
612007
612010
612013
612015
612020
612025
612030
612040
612050
612065
612080
612100
612125
612150
612175
612200
712015
712020
712025
712030
712040
712050
712065
712080
712100
712125
712150
712175
712200
602050
602065
602080
602100
602125
602150
602175
602200
Catalog Number
S&C Std.
TCC 115-2
704001
S&C Std.
TCC 153-2
614005
614007
614010
614013
614015
614020
614025
614030
614040
614050
614065
614080
614100
614125
614150
614175
614200
S&C Specification Bulletin 771-31
“E” Ratings
Rating,
Amperes
Speed
1
S&C
S&C
S&C Std.
Slow
Very Slow
TCC 153-2
TCC 119-2 TCC 176-2
“E” Ratings
Rating,
Amperes
Catalog
Number
702001
34.5 kV Nominal, 38 kV Max
“K” Ratings
Rating,
Amperes
S&C
S&C
Slow
Very Slow
TCC 119-2 TCC 176-2
714015
714020
714025
714030
714040
714050
714065
714080
714100
714125
714150
714175
714200
604050
604065
604080
604100
604125
604150
604175
604200
Speed
3K
6K
8K
10K
12K
15K
20K
25K
30K
40K
50K
65K
80K
100K
140K
200K
703003
703006
703008
703010
703012
703015
703020
703025
703030
703040
703050
703065
703080
703100
703140
703200
5E
7E
10E
13E
15E
20E
25E
30E
40E
50E
65E
80E
100E
125E
150E
175E
200E
Catalog Number
S&C Std.
TCC 115-2
703001
S&C
S&C Std. S&C Slow
Very Slow
TCC 153-2 TCC 119-2
TCC 176-2
613005
613007
613010
613013
613015
613020
613025
613030
613040
613050
613065
613080
613100
613125
613150
613175
613200
713015
713020
713025
713030
713040
713050
713065
713080
713100
713125
713150
713175
713200
603125
603150
603175
603200
S&C Alduti-Rupter® Switches with Power Fuses
Connectors
Illustration
Description
Accommodating Conductor
Catalog
Number
Bronze Body, Tin Plated.
Includes one ½ –13×2½
Galvanized Steel Bolt
No. 2 solid (33.6 mm2) through 500 kc mil
(335 mm2) stranded copper or aluminum
Bronze Body, Tin Plated.
Includes one ½ –13×2¼
Galvanized Steel Bolt
No. 2 solid (33.6 mm2) through 500 kc mil
(335 mm2) stranded copper or aluminum
5394▲
Aluminum-Alloy Body, Tin Plated.
Includes two ½ –13×2½
Galvanized Steel Bolts
No. 2 solid (33.6 mm2) through 500 kc mil
(335 mm2) stranded copper or aluminum
4744■★
Aluminum-Alloy Body, Tin Plated.
Includes two ½ –13×2¼
Galvanized Steel Bolts
No. 2 solid (33.6 mm2) through 500 kc mil
(335 mm2) stranded copper or aluminum
4746▲
No. 6 solid (53.5 mm2) through 250 kc mil
(168 mm2) copper or aluminum
4564R1-B
1/0 solid (53.5 mm2) through 500 kc mil (335 mm2)
copper or aluminum
4565R1-B
2/0 stranded (89 mm2) through 800 kc mil
(539 mm2) copper or aluminum
4567R1-B
Standard Bronze Pad Terminal,
Four-Bolt, Tin Plated. Includes
two ½ –13″×2½ Galvanized Steel Bolts
for attachment to terminal pads of
switches
■ Not suitable for use at fuse terminal pads of Alduti-Rupter Switches
with Power Fuses—Type SM.
4740R1■
★ Mechanical interference with blade prevents use on single-pole style
Alduti-Rupter Switches with Power Fuses.
▲ Suitable only for use at fuse terminal pads of Alduti-Rupter Switches
with Power Fuses—Type SM.
S&C Specification Bulletin 771-31
13
S&C Alduti-Rupter® Switches with Power Fuses
Type SM for Vertical Mounting
Three-Pole Double-Break Style with Disconnect
180° Opening Fuse
Dimensions in inches
10
29³⁄₈
8¹⁄₄
6
⁹⁄₁₆ DIA.
HOLES (2)
3
⁹⁄₁₆ DIA.
HOLES (6)
21¹⁄₂
1³⁄₄
2
18
2⁷⁄₈
1¹⁄₂
OPERATING PIPE MAY BE
FURNISHED IN THIS POSITION
1
19
1
20¹⁄₄
39¹⁄₂
1⁵⁄₈
19
HORIZONTAL
OPERATING PIPE
82
1
1³⁄₄ FOR SM-4
4¹⁄₁₆ FOR SM-5
39¹⁄₂
⁄
2¹⁄₄
¹⁄₂ –13 TAPPED
HOLES
(2) EACH SIDE
32
1
6
1³⁄₄
21³⁄₄
⁹⁄₁₆⫻1⁹⁄₁₆ SLOTS (4)
⁹⁄₁₆
1
32
53⁷⁄₈ – FOR SM-4
57 – FOR SM-5
1
TERMINAL PAD
DRILLING
Rating
Fuse Type
and
Max Amp
Rating
kV
Catalog Number
Fuse
Interr.
Amps,
RMS,
Sym.
Applications
(see pages
4 and 5)
Cypoxy
Station Post
Insulators
Porcelain
Station Post
Insulators
Holder
(Refill Units
not Included)
Cypoxy Station Porcelain Station
Post Insulators Post Insulators
Nom.
Max
BIL
SM-4
200E
34.5
38
200
6 250
AEGH(KL)
320704R10-E
320704R10
86054
280
362
SM-5
300E
34.5
38
200
17 500
AEGH(KL)
320714R10-E
320714R10
86154R2
308
380
༃ Includes weight of fuse holder.
14
Net Wt. per Pole, Lbs.༃
Switches (less Holders)
S&C Specification Bulletin 771-31
S&C Alduti-Rupter® Switches with Power Fuses
Type SM for Vertical Mounting
Three-Pole Vertical-Break Style with Disconnect
180° Opening Fuse
Dimensions in inches
38⅜ (14.4 kV)
47 (25 kV)
26⅝ (14.4 kV)
30⅝ (25 kV)
63 (14.4 kV)
71¼ (25 kV)
9∕16×19∕16 SLOTS (2)
Fuse
Type
kV
and
Max
Amp
Rating Nom. Max
Rating
Catalog Number
Fuse
Interr.
Amps,
RMS
Sym.
Applications
(see pages
4 and 5)
SM-4 14.4 17.0 110
200E 25 27
150
12 500
9 400
AEGHK(L)
AEG(HKL)
135302R4-E
135303R5-E
135302R4 86052
135303R5 86053
SM-5 14.4 17.0 110
400E 25 27
150
34 000
20 000
AEGHK(L)
AEG(HKL)
135332R4-E
135333R5-E
BIL
Dimensions in Inches (to nearest ⅛″)
Net Wt. per Pole, Lbs.༃
Switches (less Holders)
Cypoxy
Station Post
Insulators
Holder
(Refill Units
Porcelain
not
Station Post
Included)
Insulators
B
F
L1
15⅝ 16½
19⅝ 20½
10
14
18½
22½
26
30
135332R4 86152R2 15⅝ 16½
135333R5 86153R2 19⅝ 20½
10
14
18½
22½
26
30
A1
A2
L2
M1
M2
Cypoxy
Station Post
Insulators
Porcelain
Station Post
Insulators
32 32 19⅜
36¼ 44¼ 23¾
165
206
193
260
32 40⅝ 24
36¼ 49⅛ 27
194
242
222
296
༃ Includes weight of fuse holder.
S&C Specification Bulletin 771-31
15
S&C Alduti-Rupter® Switches with Power Fuses
Type SM for Vertical Mounting
Three-Pole Vertical-Break Style with Disconnect
180° Opening Fuse
Dimensions in inches
9∕16 × 19∕16 SLOTS (2)
Rating
Fuse Type
and
Max Amp
Rating
SM-5
in Parallel
720E
kV
Nom.
Max
BIL
14.4
17.0
110
Catalog Number
Fuse
Interr.
Amps,
RMS,
Sym.
Applications
(see pages
4 and 5)
25 000
AEGHK(L)
༃ Includes weight of fuse holder.
16
S&C Specification Bulletin 771-31
Net Wt. per Pole, Lbs.༃
Switches (less Holders)
Cypoxy
Station Post
Insulators
Porcelain
Station Post
Insulators
135442R5-E
135442R5
Holder
(Refill Units
not Included)
86152R2
Cypoxy Station Porcelain Station
Post Insulators Post Insulators
242
270
S&C Alduti-Rupter® Switches with Power Fuses
Type SM for Vertical Mounting
Single-Pole Style with Disconnect
180° Opening Fuse
Dimensions in inches
40¾ (14.4 kV)
47 (25 kV)
23⅝ (14.4 kV)
27¾(25 kV)
48 (14.4 kV)
54¼ (25 kV)
9∕16 × 19∕16 SLOTS (2)
Fuse
Type
kV
and
Max
Amp
Rating Nom. Max
Rating
Dimensions in Inches (to nearest ⅛″)
Catalog Number
Net Wt. per Pole, Lbs.༃
Fuse
Interr.
Amps,
RMS,
Sym.
Applications
(see pages
4 and 5)
SM-4 14.4 17.0 110
200E 14.4 27
150
12 500
9 400
AEGHK(L)
AEG(HKL)
136302-E
136303R5-E
136302
136303R5
86052
86053
12⅝ 13½
16⅝ 17½
10
14
18½ 45
34⅜ 19½
20½ 51¼ 42⅝ 23¾
101
135
122
176
SM-5 14.4 17.0 110
400E 25 27
150
34 000
20 000
AEGHK(L)
AEG(HKL)
136332R2-E
136333R5-E
136332R2
136333R5
86152R2
86153R2
12⅝ 13¾
16⅝ 17¾
10
14
18½ 45
36¼ 23⅝
20½ 54¼ 44½ 27⅞
130
175
151
216
BIL
Switches (less Holders)
Cypoxy
Station Post
Insulators
Holder
(Refill Units
Porcelain
not
Station Post
Included)
Insulators
A1
A2
B
F
L
M1
M2
Cypoxy
Porcelain
Station Post Station Post
Insulators
Insulators
༃ Includes weight of fuse holder.
S&C Specification Bulletin 771-31
17
S&C Alduti-Rupter® Switches with Power Fuses
Type SMD for Vertical Mounting
Three-Pole Double-Break Style
Dimensions in inches
10
8¹⁄₄
R
⁹⁄₁₆ DIA.
HOLES (6)
6
1
2
A₁
1³⁄₄
2⁷⁄₈
B
HORIZONTAL
OPERATING PIPE
1
⁹⁄₁₆ DIA.
HOLES (2)
F₁
20¹⁄₄ FOR 34.5 KV
23¹⁄₄ FOR 46 KV
F₁
OPERATING PIPE MAY
BE FURNISHED IN
THIS POSITION
L
1⁵⁄₈
1
90
⁹⁄₁₆ ⫻ 1⁹⁄₁₆
SLOTS (4)
2¹⁄₄
F₂
L
1
5¹⁄₈
⁹⁄₁₆ DIA. HOLES (2)
EACH SIDE–
1³⁄₄ APART
1¹⁄₂
A₂
M₁
Catalog Number (including
Rating
Fuse
Fuse-Unit End Fittings)
Type
Applications
Fuse
and
kV
Interr. (see pages
Cypoxy
Porcelain
Max
4 and 5)
Amps,
Station Post Station Post
Amp
Insulators
Insulators
Rating Nom. Max BIL RMS,
Sym.
M₂
Net Wt. per Pole,
Lbs.
Dimensions in Inches (to nearest ⅛″)
A1
A2
B
C
F1
F2
L
M1
M2
R
Cypoxy Porcelain
Station
Station
Post
Post
Insulators Insulators
SMD-1A 34.5
200E 46
38
200 17 500
48.3 250 13 100
AEGH(KL)
AEG(KL)
145814R10-E
145815R10-E
145814R10
145815R10
21¾ 22⅝ 18 90 19 41¾ 43½ 62⅞ 36¼ 29⅝
25¾ 26⅝ 22 100 22 45¾ 48½ 70⅞ 40¼ 33⅝
307
386
364
443
SMD-2C 34.5
300E 46
38
200 33 500
48.3 250 31 500
AEGH(KL)
AEG(KL)
145824R10-E
145825R10-E
145824R10
145825R10
21¾ 22⅝ 18 90 19 41¾ 43½ 62⅞ 36¼ 29⅝
25¾ 26⅝ 22 100 22 45¾ 48½ 71⅛ 40¼ 33⅝
318
397
375
454
18
S&C Specification Bulletin 771-31
S&C Alduti-Rupter® Switches with Power Fuses
Type SMD for Vertical Mounting
Three-Pole Double-Break Style
Dimensions in inches
29³⁄₈
6 10
2156O
856M
6
6QEDIA.
HOLES (2)
156O
2
6M
1³⁄₄
18
2⁷⁄₈
6QEDIA.
HOLES (6)
1
256M
OPERATING PIPE MAY
BE FURNISHED IN
THIS POSITION
1
19
2056M
4356O
16
19
HORIZONTAL
OPERATING PIPE
1
836
34
36(6
1³⁄₄
1
5(6
⁹⁄₁₆ ⫻ ¹¹⁄₁₆ SLOTS (2)
EACH SIDE – 1³⁄₄ APART
2256
⁹⁄₁₆ ⫻ 1⁹⁄₁₆
SLOTS (4)
27(6
54
Rating
Fuse Type
and
Max Amp
Rating
SMD-20
200E
kV
Nom.
Max
BIL
Fuse Interr.
Amps, RMS,
Sym.
34.5
38
200
10 000
Applications
(see pages
4 and 5)
AEGH(KL)
Catalog Number (including
Fuse-Unit End Fittings)
Net Wt. per Pole, Lbs.
Cypoxy
Station Post
Insulators
Porcelain
Station Post
Insulators
Cypoxy
Station Post
Insulators
Porcelain
Station Post
Insulators
145844R1-E
145844R1
336
412
S&C Specification Bulletin 771-31
19
S&C Alduti-Rupter® Switches with Power Fuses
Type SMD for Vertical Mounting
Three-Pole Vertical-Break Style
Dimensions in inches
39¾ (14.4 kV)
49¼ (25 kV)
27½ (14.4 kV)
33 (25 kV)
65½ (14.4 kV)
73 (25 kV)
9∕16 × 11∕16 SLOTS
(2) EACH SIDE—
1¾ APART
9∕16 × 19∕16 SLOTS (2)
SMD-20 14.4 17.0
200E 25
27
20
BIL
110
150
Fuse
Interr.
Amps,
RMS,
Sym.
Applications
(see pages
4 and 5)
14 000
12 500
AEGHK(L)
AEG(HKL)
S&C Specification Bulletin 771-31
Dimensions in Inches (to nearest ⅛″)
Catalog Number
(including Fuse-Unit
End Fittings)
Cypoxy
Station
Post
Insulators
135552R1-E
135553R5-E
Porcelain
Station
Post
Insulators
Net Wt. per Pole, Lbs.
A1
A2
135552R1 16⅜ 14½
135553R5 21⅞ 18½
B
10
14
F
L1
18½ 26
22½ 30
L2
M1
M2
34½ 36⅜ 18⅜
38
38⅞ 21⅞
Cypoxy
Porcelain
Station Post Station Post
Insulators
Insulators
193
219
221
273