S&C Alduti-Rupter® Switches with Power Fuses★ Outdoor Distribution (14.4 kV through 46 kV) Specifications Conditions of Sale STANDARD: Seller’s standard conditions of sale set forth in Price Sheet 150 apply, except as modified under “WARRANTY QUALIFICATIONS” on page 2. SPECIAL TO THIS PRODUCT: INCLUSIONS: S&C Alduti-Rupter Switches with Power Fuses are available in three-pole group-operated designs that feature pole-units mounted on individual bases for vertical mounting. Single-Pole Style switches are also available in vertical mounting configurations for use in single-phase switching applications. Single-Pole Style switches are operable using a conventional hookstick. All three-pole Alduti-Rupter Switches with Power Fuses are provided with an operating mechanism that includes: • Three switch poles. • A detailed erection drawing (ED) of the applicable mounting arrangement. • All required interphase and vertical pipe as specified on the erection drawing (ED). Operating mechanism includes three 10′-4″ (3150 mm) sections of vertical pipe (1¼″ (32 mm) IPS for reciprocating operating mechanisms and 1½″ (38 mm) IPS for rotating operating mechanisms). • The appropriate set of operating-mechanism components; e.g., handle, rod guides or guide bearings, couplings, bell crank assembly, etc. • Complete installation and maintenance instructions. Mounting Arrangements S&C Three-Pole Alduti-Rupter Switches with Power Fuses are available in Standard Mounting Arrangements as described in S&C Data Bulletin 771-80. Departures from Standard Mounting Arrangements are also available and fall into three categories: 1. Standard Minor Modifications of Standard Mounting Arrangements are those which are so frequently encountered that they are included on S&C’s basic erection drawings (ED). Applicability of Standard Minor Modifications are listed in the table on page 8. The applicable Standard Minor Modifications may be specified by adding the appropriate Catalog Number Suffix “-S” to the erection drawing (ED) number. 2. Special Minor Modifications of Standard Mounting Arrangements are those which include such departures as special base drillings or special mounting brackets for operating-mechanism components. For this category of “special,” S&C will prepare a custom erection drawing (ED) based on the Standard Mounting Arrangement erection drawing (ED). Switches will be supplied with an operating mechanism for the Special Minor Modification of a Standard Mounting Arrangement. 3. Special Mounting Arrangements are those which involve complete departures from the Standard Mounting Arrangements brought about by customizing an S&C Alduti-Rupter Switch with Power Fuses to fit the user’s structure. Custom erection drawings (ED) will be provided as required. EXCLUSIONS: Alduti-Rupter Switches with Power Fuses do not include connectors. Various connector arrangements are available as listed in the table on page 13. Specify the quantity and catalog number of connector arrangement desired. Alduti-Rupter Switches with Power Fuses do not include holders, refill units, or fuse units. SPECIFICATION DEVIATIONS: S&C Alduti-Rupter Switches with Power Fuses are offered with a choice of Cypoxy®■ or porcelain station post insulators. The standard insulator color is gray. When switches are to be provided with special insulators or special connectors, consult the nearest S&C Sales Office for availability. Switches of a given voltage rating can be furnished with insulators of the next higher voltage rating—add suffix “-Z3” to the catalog number. ■ Cypoxy is the S&C trademark for S&C’s cycloaliphatic epoxy resin system. Cypoxy is nontracking, self-scouring, nonweathering . . . there’s never a compromise of insulation integrity. ★ S&C Alduti-Rupter® Switches with Power Fuses are manufactured in accordance with a quality system certified to ISO 9001, and they are Rural Utilities Service approved. July 1, 2013© S&C Electric Company Specification Bulletin 771-31 S&C Alduti-Rupter® Switches with Power Fuses Conditions of Sale—Continued Switches can be supplied with tin-plated terminal pads. To specify, add suffix “-Z5” to the catalog number of the switch. Single-, two-, and four-pole group-operated switches are also available for Alduti-Rupter Switches with Power Fuses. Alduti-Rupter Switches with Power Fuses—Type SM does not include SM Refill Units or SM Fuse Holders. The catalog number of the holder may be obtained from the same horizontal line in which the switch is listed. Alduti-Rupter Switches with Power Fuses—Type SMD do not include SMD® Fuse Units or SMU-20® Fuse Units. In selecting a refill unit or fuse unit, watch these points: • Alduti-Rupter Switches with Power Fuses—Type SM— match refill unit type to holder type. • Alduti-Rupter Switches with Power Fuses—Type SMD—select fuse unit of the type indicated. Refill units and fuse units are listed separately. In selecting a refill unit or fuse unit, consider the following: 1. Description—SM-4®, SM-5®, SMD-1A, SMD-2C, or SMU-20 2. Voltage rating 3. Ampere rating 4. Speed. POWER OPERATION: Power operation or, if desired, remote supervisory control may be provided for S&C AldutiRupter Switches with Power Fuses by the addition of the appropriate S&C Switch Operator—Type AS-1A, or AS-10, or by adding an S&C M Series® Switch Operator. S&C Switch Operators—Types AS-1A and Type AS-10 are for power operation of Alduti-Rupter Switches with Power 2 S&C Specification Bulletin 771-31 Fuses with rotating-type and reciprocating-type operating mechanisms, respectively. These switch operators are high-speed operators, with operating times not exceeding .75 second and 1.2 seconds maximum, respectively. This high operating speed provides sufficient moving-contact velocity in the interrupters to ensure full interrupting capability and long operating life. M Series Switch Operators are available in two versions—torsional, for rotating-type mechanisms, and reciprocating, for reciprocating-type operating mechanisms. Both versions operate in .5 seconds. This high operating speed is fully compatible with the movingcontact velocity required by the interrupters to ensure full interrupting capability for the applicable switch styles and mounting arrangements. Power operation is available for certain mounting arrangements only. Consult the nearest S&C Sales Office for availability. For additional details concerning S&C Switch Operators—Types AS-1A or AS-10, refer to Specification Bulletin 769-31. For additional details concerning M Series Switch Operators, refer to Specification Bulletin 1051-31. WARRANTY QUALIFICATIONS: The standard warranty contained in S&C’s standard conditions of sale, as set forth in Price Sheet 150, does not apply when Alduti-Rupter Switches with Power Fuses are power operated using a switch operator other than S&C manufacture. S&C Alduti-Rupter® Switches with Power Fuses How to Order Alduti-Rupter Switch with Power Fuses 1. Switch and connectors a. Obtain the catalog number of the desired switch from pages 6 and 7. b. For three-pole switches, obtain the ED number of the desired mounting arrangement from S&C Data Bulletin 771-80. • If a Standard Minor Modification is desired for a three-pole switch, obtain the suffix of the desired modification from page 8. Add the suffix to the ED number of the switch. c. If special minor modifications of standard mounting arrangements or special mounting arrangements are desired, refer to the “Mounting Arrangements” section on page 1. d. If specification deviations are desired, such as switches furnished less insulators, with insulators of the next higher or lower voltage rating, less bases, less switch poles, or with additional switch poles, see the “Specification Deviations” section on pages 1 and 2. e. If connectors are desired, obtain the catalog number of the desired connector from page 13. 2. Fuse components a. For Type SM Power Fuses: Obtain the catalog number of the applicable holder from the “Holder” column on page 6, reading from the same line on which the switch catalog number is listed, and taking care to note the number of holders required per switch. Next, obtain the catalog number of the desired refill unit from the tables on pages 9 and 10, taking care to match the voltage rating of the refill unit to that of the switch. b. For Type SMD Power Fuses: Obtain the catalog number of the desired fuse unit from the tables on pages 11 and 12, taking care to match the voltage rating of the fuse unit to that of the switch. Handling Tools Obtain the catalog number of the recommended handling tool(s) from the table on page 8. Note: If power operation or remote supervisory control are desired, S&C Switch Operator—Type AS-1A and AS-10, or M Series Switch Operator may be added to switches in certain mounting arrangements. For ordering information on S&C Switch Operator—Type AS-1A and AS-10 see Specification Bulletin 769-31. For ordering information on M Series Switch Operators see Specification Bulletin 1051-31. Note: Spare or replacement parts are ordered using the same method outlined above. S&C Specification Bulletin 771-31 3 S&C Alduti-Rupter® Switches with Power Fuses Application Classifications (See symbols on pages 6 and 7) Application Symbol ■ A A A A Three-phase transformer (or three-phase bank of single-phase transformers) connected solidly grounded-wye on the primary (switch) side and delta on the secondary side ● E — E — All other connections of three-phase transformers (or three-phase banks of singlephase transformers)—including autotransformers ● G G G G Single-phase transformer connected phase-toground on the primary (switch) side ● E — — — Single-phase transformer connected phase-tophase on the primary (switch) side ● G G — — ■ A A A A Three-phase circuits with all load-side threephase transformers (or three-phase banks of single-phase transformers) connected solidly grounded-wye on the primary (switch) side and delta on the secondary side, and all load-side single-phase transformers connected phase-toground on the primary (switch) side ■ E — E — Three-phase circuits with load-side transformers connected other than as described above ■ G G G G Single-phase circuits with all load-side transformers connected phase-to-ground on the primary (switch) side ■ E — — — Single-phase circuits with load-side transformers connected other than as described above ■ G G — — Line Dropping ▲ K L K L Load Splitting ■ A A A A Three-phase circuits with all load-side threephase transformers (or three-phase banks of single-phase transformers) connected solidly grounded-wye on the primary (switch) side and delta on the secondary side, and all load-side single-phase transformers connected phase-toground on the primary (switch) side ■ E — E — Three-phase circuits with load-side transformers connected other than as described above ■ G G G G Single-phase circuits with all load-side transformers connected phase-to-ground on the primary (switch) side ■ E — — — Single-phase circuits with load-side transformers connected other than as described above ■ G G — — Shielded cable ▼ H L H L Load Dropping and Magnetizing Current Switching Load Splitting (Parallel or Loop Switching) Cable Switching Three-Pole Switch Ungrounded System Qualifications Parallel Switching༅ Line Switching Single-Pole Switch Solidly or Effectively༄ Grounded System Class Transformer Switching Maximum Interrupting Duty,༃ Amperes, RMS Load Dropping Load Dropping Cable Dropping (charging current) Capacitor Bank Switching, Single Bank Only Solidly or EffecUngrounded tively༄ System Grounded System ▼ K L K L Grounded capacitor bank 100 H L H L Ungrounded capacitor bank 100 L L L L Unshielded cable FOR FOOTNOTES SEE BOTTOM OF PAGE 5 4 S&C Specification Bulletin 771-31 ▶ S&C Alduti-Rupter® Switches with Power Fuses Conditional Applications (See symbols in parentheses on pages 6 and 7) Alduti-Rupter Switch Style Voltage Rating, kV Application Symbol Maximum Operating Voltage Line-to-Line, kV༃ Maximum Interrupting Duty Over 15.5 and up through 31.7 60 amperes Over 31.7 and up through 38.0 Line dropping only Over 15.5 and up through 20.0 60 amperes Over 20.0 and up through 38.0 Line dropping only K 34.5 L Three-Pole Double-Break Over 15.5 and up through 31.7 60 amperes Over 31.7 and up through 48.3 Line dropping only Over 15.5 and up through 20.0 60 amperes K 46 L 14.4 L Over 20.0 and up through 48.3 Line dropping only Over 12.0 and up through 17.0 Line dropping only Over 15.5 and up through 22.8 60 amperes H Over 22.8 and up through 27.0 ■ Over 15.5 and up through 19.0 Cable and line dropping only Over 19.0 and up through 27.0 Line dropping only■ L Over 12.0 and up through 27.0 Line dropping only L Over 15.5 and up through 17.0 Line dropping only Over 15.5 and up through 22.8 60 amperes Three-Pole Vertical-Break 25 K 14.4 H Over 22.8 and up through 27.0 ■ Over 15.5 and up through 19.0 Cable and line dropping only Over 19.0 and up through 27.0 Line dropping only■ Over 15.5 and up through 27.0 Line dropping only Single-Pole 25 K L ༃ Where maximum operating voltage for a conditional application is ■ Three-Pole Vertical-Break and Single-Pole Styles may be applied for lower than the lowest range listed, refer to “Application Classifications” table on page 4 for applicable maximum interrupting duty values. cable dropping (charging current) of 3 miles (4.8 km) of No. 1/0 cable or 1.2 miles (1.9 km) of 1000 kc mil cable, or equivalent, provided phase spacing is 55 inches (1397 mm) minimum. ◀ഩFOOTNOTES FOR TABLE ON PAGE 4 ༃ Lower values may apply for “conditional applications.” Refer to ■ Same as continuous-current rating. “Conditional Applications” table above. ● Alduti-Rupter Switches with Power Fuses will drop loads through ༄ X0 /X1 from 0 to + 3.0 and R0 /X1 from 0 to + 1.0. ༅ Applies to switching of the primary of a transformer which remains energized from the secondary bus, or to disconnecting of a loaded secondary bus from one of two transformers supplying that bus while the primary side of the transformer remains energized. 600 amperes, and will switch magnetizing currents associated with such loads. ▲ Maximum length of line: 100 miles (161 km). ▼ 80 miles (129 km) of No. 1/0 cable, or 30 miles (48 km) of 1000 kc mil cable, or equivalent. S&C Specification Bulletin 771-31 5 S&C Alduti-Rupter® Switches with Power Fuses Alduti-Rupter Switches wth Power Fuses—Type SM for Vertical Mounting༃༄ Rating༅ Style Three-Pole Double-Break with Disconnect 180° Opening Fuse༊ Fuse Type and Max Amp Rating SM-4 200E Switches (less Holders) Nom. Max BIL Fuse Interr. Amps, RMS, Sym.༆ 34.5 38 200 6 250 kV Applications༇ (see pages 4 and 5) AEGH(KL) Cypoxy Station Porcelain Station Post Post Insulators Insulators Catalog Number༈༉ Catalog Number༈༉ 320704R10-E 320704R10 Holder (Refill Units not included) No. Req’d. 3 Catalog Number Page Reference for Dimensional Information 86054 14 Three-Pole Vertical-Break with Disconnect 180° Opening Fuse Single-Pole with Disconnect 180° Opening Fuse SM-5 300E 34.5 38 200 17 500 AEGH(KL) 320714R10-E 320714R10 3 86154R2 SM-4 200E 14.4 25 17.0 27 110 150 12 500 9 400 AEGHK(L) AEG(HKL) 135302R4-E 135303R5-E 135302R4 135303R5 3 3 86052 86053 SM-5 400E■ 14.4 25 17.0 27 110 150 34 000▲ 20 000 AEGHK(L) AEG(HKL) 135332R4-E 135333R5-E 135332R4 135333R5 3 3 86152R2 86153R2 SM-5 in parallel 720E 14.4 17.0 110 25 000★ AEGHK(L) 135442R5-E 135442R5 6 86152R2 SM-4 200E 14.4 25 17.0 27 110 150 12 500 9 400 AEGHK(L) AEG(HKL) 136302-E 136303R5-E 136302 136303R5 1 1 86052 86053 15 16 17 SM-5 400E■ 14.4 25 17.0 27 110 150 34 000▲ 20 000 AEGHK(L) AEG(HKL) ༃ The switches shown include the appropriate set of operating- mechanism components as specified on the erection drawing (ED) for the switch. Switches do not include connectors (refer to table on page 13) or SM Refill Units (refer to tables on pages 9 and 10). ༄ The switches are available in a variety of Standard Mounting Arrangements, designated by erection drawing (ED) number, as described in Data Bulletin 771-80. Specify the applicable erection drawing (ED) number when ordering. ༅ Switches are rated 600 amperes, RMS, continuous and interrupting. Momentary rating of the switches is 40,000 amperes, RMS, asymmetrical, except for 14.4-kV switches with Type SM-5 Power Fuses, for which the momentary ratings, based on limiting of the let-through current by the fuses, are 54,000 amperes, RMS, asymmetrical at 13.8 kV and 14.4 kV, 60 hertz only, (55,000 amperes, RMS, asymmetrical on 7.2/12.47GrY-kV 60-hertz systems only). Maximum ampere ratings of fuses are shown in second column. ༆ Symmetrical ratings assigned are based on available short-circuit current at locations where the X/R ratio is 15. The interrupting ratings expressed in amperes, RMS, asymmetrical are 1.6 times the symmetrical ratings listed. Higher symmetrical ratings have been determined for these fuses applied at lower system voltages and in locations where X/R = 10 and X/R = 5. These higher ratings as well as asymmetrical ratings are given in S&C Descriptive Bulletin 242-30. 6 S&C Specification Bulletin 771-31 136332R2-E 136333R5-E 136332R2 136333R5 1 1 86152R2 86153R2 ༇ Applications indicated by symbols in parentheses are conditional. See “Conditional Applications” table, page 5. ༈ For a three-pole switch to be supplied less operating pipe, specify by adding Catalog Number Suffix “-P” to the erection drawing (ED) number. ༉ Standard Minor Modifications of the Standard Mounting Arrangement(s) for these switches are listed in the table on page 8. The applicable Standard Minor Modifications listed therein may be specified by adding the appropriate “-S” suffix to the erection drawing (ED) number. Refer to page 1 for Special Minor Modifications and Special Mounting Arrangements for these switches. ༊ Three-Pole Double-Break Style Switches with Power Fuses rated 34.5 kV and 46 kV, while provided with design features for fault closing, are not assigned fault closing ratings or capabilities because special mounting arrangements may deny the requisite high speed closing behavior. ■ Maximum ampere rating at 25 kV is 300E. ▲ 60-hertz rating. For systems above 15.5 kV through 17.0 kV, interrupting rating is 25,000 amperes, RMS, symmetrical, 50/60 hertz. ★ 60-hertz rating. S&C Alduti-Rupter® Switches with Power Fuses Alduti-Rupter Switches with Power Fuses—Type SMD for Vertical Mounting༃༄ Cypoxy Station Post Insulators Rating༅ Style Three-Pole Double-Break༊ Fuse Type and Max Amp Rating SMD-1A 200E kV Fuse Interr. Amps, RMS, Sym.༆ Porcelain Station Post Insulators Page Reference Applications༇ Catalog Number Catalog Number for Dimensional (see pages (including (including Information 4 and 5) Fuse-Unit Fuse-Unit End Fittings)༈༉ End Fittings)༈༉ Nom. Max BIL 34.5 38 200 17 500 AEGH(KL) 145814R10-E 145814R10 46 48.3 250 13 100 AEG(KL) 145815R10-E 145815R10 18 SMD-2C 300E SMD-20■ 34.5 38 200 33 500 AEGH(KL) 145824R10-E 145824R10 46 48.3 250 31 500 AEG(KL) 145825R10-E 145825R10 34.5 38 200 10 000★ AEGH(KL) 145844R1-E 145844R1 14.4 17.0 110 14 000★ AEGHK(L) 135552R1-E 135552R1 25 27 150 12 500★ AEG(HKL) 135553R5-E 135553R5 200E 19 Three-Pole Vertical-Break SMD-20■ 200E 20 ༃ The switches shown include the appropriate set of operating- ༇ Applications indicated by symbols in parentheses are conditional. mechanism components as specified by the erection drawing (ED) for the switch. Switches do not include connectors (refer to table on page 13), SMD Fuse Units (refer to table on page 11), or SMU-20 Fuse Units (refer to table on page 12). ༈ For a three-pole switch to be supplied less operating pipe, specify by ༄ Switches are available in a variety of Standard Mounting Arrangements, designated by erection drawing (ED) number, as described in Data Bulletin 771-80. Specify the applicable erection drawing (ED) number when ordering. ༅ Switches are rated 600 amperes, RMS, continuous and interrupting. Momentary rating of the switches is 40,000 amperes, RMS, asymmetrical, except for switches with Type SMD-2C Power Fuses, for which the momentary ratings, based on limiting of the let-through current by the fuses, are 53,500 amperes, RMS, asymmetrical for models rated 34.5 kV and 50,500 amperes, RMS, asymmetrical for models rated 46 kV. Maximum ampere ratings of fuses are shown in second column. ༆ Symmetrical ratings assigned are based on available short-circuit current at locations where the X/R ratio is 15. The interrupting ratings expressed in amperes, RMS, asymmetrical are 1.6 times the symmetrical ratings listed. Higher symmetrical ratings have been determined for these fuses applied at lower system voltages and in locations where X/R = 10 and X/R = 5. These higher ratings as well as asymmetrical ratings are given in S&C Descriptive Bulletins 212-30 and 242-32, as applicable. See “Conditional Applications” table, page 5. adding Catalog Number Suffix “-P” to the erection drawing (ED) number. ༉ Standard Minor Modifications of the Standard Mounting Arrangement(s) for these switches are listed in the table on page 8 of this specification bulletin. The applicable Standard Minor Modifications listed therein may be specified by adding the appropriate “-S” suffix to the erection drawing (ED) number. Refer to page 1 for Special Minor Modifications and Special Mounting Arrangements for these switches. ༊ Three-Pole Double-Break Style Switches with Power Fuses rated 34.5 kV and 46 kV, while provided with design features for fault closing, are not assigned fault closing ratings or capabilities because special mounting arrangements may deny the requisite high-speed closing behavior. ■ SMD-20 Power Fuses accommodate SMU-20 Fuse Units in ratings through 200K amperes as well as 200E amperes. ★ 60-hertz rating. S&C Specification Bulletin 771-31 7 S&C Alduti-Rupter® Switches with Power Fuses Parts For Use on Alduti-Rupter Switches Style kV Catalog Number Three-Pole Vertical-Break and Single-Pole 7.2 SA-30817R2 14.4 or 25 SA-30818R4 Three-Pole Double-Break༃ All SDA-10175 Spare End Fittings for SMD-1A Fuse Unit Three-Pole Double-Break All 3004R1 Spare End Fittings for SMD-2C Fuse Unit Three-Pole Double-Break All 3032R1 Spare End Fittings for SMU-20 Fuse Unit Three-Pole Double-Break and Three-Pole Vertical-Break All 3095 Item Spare or Replacement Interrupter Spare or Replacement Interrupter with integral mounting bracket and muffler ༃ Previous designs of Three-Pole Double-Break Switches with Power Fuses require catalog number 4559R1 Interrupter. Handling Tools For Removal and Installation of Catalog Number Large Round Socket Item SMD-2C Fuse Unit 4407R4 Small Round Socket SMD-1A Fuse Unit 4408R4 All 4402R2 Station Prong Universal Pole◆ ◆ Select to match height of installation. Refer to Specification Bulletin 851-31. Standard Minor Modifications—For Three-Pole Mounting Styles Applicable to Three-Pole Mounting Styles Item Suffix to be Added to Erection Drawing Number 2⅝″ (67 mm) Diameter Tubular Fiberglass Insulating Section in vertical operating shaft All -S1 One Cypoxy Insulator Unit in vertical operating shaft All -S2 Insulated Interphase Sections and One Fiberglass Insulating Section in vertical operating shaft All -S3■ Insulated Interphase Sections and One Cypoxy Insulator Unit in vertical operating shaft All -S4■ 2″ (51 mm) IPS Pipe—required for rotating-type operating-mechanism vertical shaft when such shaft exceeds three 10′– 4″ (3150 mm) sections All -S5 One extra pipe section, 2″ (51 mm) pipe All rotating operating mechanisms -S5A Two extra pipe sections, 2″ (51 mm) pipe All rotating operating mechanisms -S5B Refer to ED drawing -S5C Three extra pipe sections, 2″ (51 mm) pipe Key Interlock—single lock for “locked-open” application All -S6 Auxiliary contact switch with 4 NO & 4 NC contacts (600 VAC, 20 Amperes) All -S7 Provision for power operation of pole-mounted switches by S&C Switch Operator—Type AS-1A or AS-10 All -S8▲ Provision for power operation of steel-structure or pedestal-mounted switches by S&C Switch Operator—Type AS-1A or AS-10 All -S9▲ All rated 14.4-kV & 25-kV༃ -S16▲ Provision for power operation of pole-mounted switches by M Series Switch Operator— Torsional and Reciprocating One extra pipe section, 1¼″ (32 mm) pipe All reciprocating operating mechanisms -V1 Two extra pipe sections, 1¼″ (32 mm) pipe All reciprocating operating mechanisms -V2 ༃ Switches at 34.5 kV and 46 kV may be suitable for use with M-Series ▲ Not all mounting arrangements are suitable for power operation, Switch Operators. Contact the nearest S&C Sales Office for availability. contact the nearest S&C Sales Office for availability. ■ Not available for power-operated switches. 8 S&C Specification Bulletin 771-31 S&C Alduti-Rupter® Switches with Power Fuses SM-4® Refill Units (For Use in SM-4 Holders) Rating, Amperes Speed 1 2 3E 5E 7E 10E 13E 15E 20E 25E 30E 40E 50E 65E 80E 100E 125E 150E 175E 200E 210 25 kV Nominal, 27 kV Max Catalog Number Catalog Number S&C Std. TCC 115-4 S&C Std. TCC 115-4 122001R4 122002R4 123001R4 123002R4 S&C Std. TCC 153-4 Speed 14.4 kV Nominal, 17.0 kV Max 122005R4 122007R4 122010R4 122015R4 122020R4 122025R4 122030R4 122040R4 122050R4 122060R4 122075R4 122100R4 122125R4 122150R4 122200R4 122250R4 122275R4 122300R4 S&C Slow TCC 119-4 S&C Coord. TCC 179-4 252025R4 252030R4 252040R4 252050R4 252060R4 252075R4 252100R4 252125R4 252150R4 252200R4 252250R4 252275R4 252300R4 S&C Std. TCC 153-4 S&C Slow TCC 119-4 123005R4 123007R4 123010R4 123015R4 123020R4 123025R4 123030R4 123040R4 123050R4 123060R4 123075R4 123100R4 123125R4 123150R4 123200R4 123250R4 123275R4 123300R4 253025R4 253030R4 253040R4 253050R4 253060R4 253075R4 253100R4 253125R4 253150R4 253200R4 253250R4 253275R4 253300R4 382210R4■ 34.5 kV Nominal, 38 kV Max Rating, Amperes Catalog Number S&C Std. TCC 115-4 Speed 1 2 Speed 3E 5E 7E 10E 13E 15E 20E 25E 30E 40E 50E 65E 80E 100E 125E 150E 175E 200E 124001R4 124002R4 S&C Std. S&C Std. TCC 153-4 TCC 119-4 124005R4 124007R4 124010R4 124015R4 124020R4 124025R4 124030R4 124040R4 124050R4 124060R4 124075R4 124100R4 124125R4 124150R4 124200R4 124250R4 124275R4 124300R4 254025R4 254030R4 254040R4 254050R4 254060R4 254075R4 254100R4 254125R4 254150R4 254200R4 254250R4 254275R4 254300R4 ■ This S&C Coordinating Speed refill unit should be applied where the maximum continuous load current does not exceed 200 amperes and where all fault currents below 1000 amperes will be cleared by another fuse. S&C Specification Bulletin 771-31 9 S&C Alduti-Rupter® Switches with Power Fuses SM-5® Refill Units (For Use in SM-5 Holders) Rating, Amperes Speed 1 2 Speed 3E 5E 7E 10E 13E 15E 20E 25E 30E 40E 50E 65E 80E 100E 125E 150E 175E 200E 250E 300E 400E 410E 420E 14.4 kV Nominal, 17.0 kV Max 25 kV Nominal, 27 kV Max Catalog Number Catalog Number Catalog Number S&C Std. TCC 115-4 S&C Std. TCC 115-4 S&C Std. TCC 115-4 132001R4 132002R4 133001R4 133002R4 134001R4 134002R4 S&C Std. TCC 153-4 132005R4 132007R4 132010R4 132015R4 132020R4 132025R4 132030R4 132040R4 132050R4 132060R4 132075R4 132100R4 132125R4 132150R4 132200R4 132250R4 132275R4 132300R4 132400R4 132500R4 132600R4 S&C Slow TCC 119-4 S&C Coord. TCC 173-4 S&C Std. TCC 153-4 133005R4 133007R4 133010R4 133015R4 133020R4 133025R4 133030R4 133040R4 133050R4 133060R4 133075R4 133100R4 133125R4 133150R4 133200R4 133250R4 133275R4 133300R4 133400R4 133500R4 262025R4 262030R4 262040R4 262050R4 262060R4 262075R4 262100R4 262125R4 262150R4 262200R4 262250R4 262275R4 262300R4 262400R4 262500R4 262600R4 382410R4 ■ 382420R4 ■ ■ These S&C Coordinating Speed refill units should be applied where the maximum continuous load current does not exceed 400 amperes and where all fault currents below 3000 amperes for Catalog Numbers 381410R4 and 382410R4 and 4000 amperes for Catalog Numbers 381420R4 and 382420R4 will be cleared by another fuse. 10 34.5 kV Nominal, 38 kV Max S&C Specification Bulletin 771-31 S&C Slow TCC 119-4 S&C Std. TCC 153-4 S&C Slow TCC 119-4 263025R4 263030R4 263040R4 263050R4 263060R4 263075R4 263100R4 263125R4 263150R4 263200R4 263250R4 263275R4 263300R4 263400R4 263500R4 134005R4 134007R4 134010R4 134015R4 134020R4 134025R4 134030R4 134040R4 134050R4 134060R4 134075R4 134100R4 134125R4 134150R4 134200R4 134250R4 134275R4 134300R4 134400R4 134500R4 264025R4 264030R4 264040R4 264050R4 264060R4 264075R4 264100R4 264125R4 264150R4 264200R4 264250R4 264275R4 264300R4 264400R4 264500R4 S&C Alduti-Rupter® Switches with Power Fuses SMD-1A Fuse Units 34.5 kV Nominal, 38 kV Max Rating, Amperes 46 kV Nominal, 48.3 kV Max Catalog Number Catalog Number S&C Std. TCC 115-1 Speed 1 444001R1 S&C Std. TCC 153-1 Speed 3E 5E 7E 10E 13E 15E 20E 25E 30E 40E 50E 65E 80E 100E 125E 150E 175E 200E S&C Std. TCC 115-1 444003R2 444005R1 444007R1 444010R1 444013R1 444015R1 444020R1 444025R1 444030R1 444040R1 444050R1 444065R1 444080R1 444100R1 444125R1 444150R1 444175R1 444200R1 445001R1 S&C Slow TCC 119-1 S&C Very Slow TCC 176-1 S&C Std. TCC 153-1 S&C Slow TCC 119-1 S&C Coord. TCC 176-1 564050 564065 564080 564100 564125 564150 564175 564200 445003R2 445005R1 445007R1 445010R1 445013R1 445015R1 445020R1 445025R1 445030R1 445040R1 445050R1 445065R1 445080R1 445100R1 445125R1 445150R1 445175R1 445200R1 455015R1 455020R1 455025R1 455030R1 455040R1 455050R1 455065R1 455080R1 455100R1 455125R1 455150R1 455175R1 455200R1 565050 565065 565080 565100 565125 565150 565175 565200 454015R1 454020R1 454025R1 454030R1 454040R1 454050R1 454065R1 454080R1 454100R1 454125R1 454150R1 454175R1 454200R1 SMD-2C Fuse Units 34.5 kV Nominal, 38 kV Max Rating, Amperes 46 kV Nominal, 48.3 kV Max Catalog Number Catalog Number S&C Std. TCC 115-1 Speed 1 Speed 3E 5E 7E 10E 13E 15E 20E 25E 30E 40E 50E 65E 80E 100E 125E 150E 175E 200E 250E 300E S&C Std. TCC 115-1 464001R3 S&C Std. TCC 153-1 464003R3 464005R3 464007R3 464010R3 464013R3 464015R3 464020R3 464025R3 464030R3 464040R3 464050R3 464065R3 464080R3 464100R3 464125R3 464150R3 464175R3 464200R3 464250R3 464300R3 465001R3 S&C Slow TCC 119-1 484015R3 484020R3 484025R3 484030R3 484040R3 484050R3 484065R3 484080R3 484100R3 484125R3 484150R3 484175R3 484200R3 484250R3 484300R3 S&C Very Slow TCC 176-1 574050R3 574065R3 574080R3 574100R3 574125R3 574150R3 574175R3 574200R3 574250R3 S&C Std. TCC 153-1 S&C Slow TCC 119-1 465003R3 465005R3 465007R3 465010R3 465013R3 465015R3 465020R3 465025R3 465030R3 465040R3 465050R3 465065R3 465080R3 465100R3 465125R3 465150R3 465175R3 465200R3 465250R3 465300R3 485015R3 485020R3 485025R3 485030R3 485040R3 485050R3 485065R3 485080R3 485100R3 485125R3 485150R3 485175R3 485200R3 485250R3 485300R3 S&C Coord. TCC 176-1 575050R3 575065R3 575080R3 575100R3 575125R3 575150R3 575175R3 575200R3 575250R3 S&C Specification Bulletin 771-31 11 S&C Alduti-Rupter® Switches with Power Fuses SMU-20® Fuse Units 14.4 kV Nominal, 17.0 kV Max “K” Ratings Rating, Amperes Speed “E” Ratings Catalog Number S&C “K” TCC 165-2 Rating, Amperes Speed 1 Speed 3K 6K 8K 10K 12K 15K 20K 25K 30K 40K 50K 65K 80K 100K 140K 200K 25 kV Nominal, 27 kV Max 702003 702006 702008 702010 702012 702015 702020 702025 702030 702040 702050 702065 702080 702100 702140 702200 5E 7E 10E 13E 15E 20E 25E 30E 40E 50E 65E 80E 100E 125E 150E 175E 200E “K” Ratings Catalog Number S&C Std. TCC 115-2 Speed Rating, Amperes Speed Catalog Number S&C “K” TCC 165-2 Speed 1 Speed 3K 6K 8K 10K 12K 15K 20K 25K 30K 40K 50K 65K 80K 100K 140K 200K 12 704003 704006 704008 704010 704012 704015 704020 704025 704030 704040 704050 704065 704080 704100 704140 704200 5E 7E 10E 13E 15E 20E 25E 30E 40E 50E 65E 80E 100E 125E 150E 175E 200E S&C “K” TCC 165-2 612005 612007 612010 612013 612015 612020 612025 612030 612040 612050 612065 612080 612100 612125 612150 612175 612200 712015 712020 712025 712030 712040 712050 712065 712080 712100 712125 712150 712175 712200 602050 602065 602080 602100 602125 602150 602175 602200 Catalog Number S&C Std. TCC 115-2 704001 S&C Std. TCC 153-2 614005 614007 614010 614013 614015 614020 614025 614030 614040 614050 614065 614080 614100 614125 614150 614175 614200 S&C Specification Bulletin 771-31 “E” Ratings Rating, Amperes Speed 1 S&C S&C S&C Std. Slow Very Slow TCC 153-2 TCC 119-2 TCC 176-2 “E” Ratings Rating, Amperes Catalog Number 702001 34.5 kV Nominal, 38 kV Max “K” Ratings Rating, Amperes S&C S&C Slow Very Slow TCC 119-2 TCC 176-2 714015 714020 714025 714030 714040 714050 714065 714080 714100 714125 714150 714175 714200 604050 604065 604080 604100 604125 604150 604175 604200 Speed 3K 6K 8K 10K 12K 15K 20K 25K 30K 40K 50K 65K 80K 100K 140K 200K 703003 703006 703008 703010 703012 703015 703020 703025 703030 703040 703050 703065 703080 703100 703140 703200 5E 7E 10E 13E 15E 20E 25E 30E 40E 50E 65E 80E 100E 125E 150E 175E 200E Catalog Number S&C Std. TCC 115-2 703001 S&C S&C Std. S&C Slow Very Slow TCC 153-2 TCC 119-2 TCC 176-2 613005 613007 613010 613013 613015 613020 613025 613030 613040 613050 613065 613080 613100 613125 613150 613175 613200 713015 713020 713025 713030 713040 713050 713065 713080 713100 713125 713150 713175 713200 603125 603150 603175 603200 S&C Alduti-Rupter® Switches with Power Fuses Connectors Illustration Description Accommodating Conductor Catalog Number Bronze Body, Tin Plated. Includes one ½ –13×2½ Galvanized Steel Bolt No. 2 solid (33.6 mm2) through 500 kc mil (335 mm2) stranded copper or aluminum Bronze Body, Tin Plated. Includes one ½ –13×2¼ Galvanized Steel Bolt No. 2 solid (33.6 mm2) through 500 kc mil (335 mm2) stranded copper or aluminum 5394▲ Aluminum-Alloy Body, Tin Plated. Includes two ½ –13×2½ Galvanized Steel Bolts No. 2 solid (33.6 mm2) through 500 kc mil (335 mm2) stranded copper or aluminum 4744■★ Aluminum-Alloy Body, Tin Plated. Includes two ½ –13×2¼ Galvanized Steel Bolts No. 2 solid (33.6 mm2) through 500 kc mil (335 mm2) stranded copper or aluminum 4746▲ No. 6 solid (53.5 mm2) through 250 kc mil (168 mm2) copper or aluminum 4564R1-B 1/0 solid (53.5 mm2) through 500 kc mil (335 mm2) copper or aluminum 4565R1-B 2/0 stranded (89 mm2) through 800 kc mil (539 mm2) copper or aluminum 4567R1-B Standard Bronze Pad Terminal, Four-Bolt, Tin Plated. Includes two ½ –13″×2½ Galvanized Steel Bolts for attachment to terminal pads of switches ■ Not suitable for use at fuse terminal pads of Alduti-Rupter Switches with Power Fuses—Type SM. 4740R1■ ★ Mechanical interference with blade prevents use on single-pole style Alduti-Rupter Switches with Power Fuses. ▲ Suitable only for use at fuse terminal pads of Alduti-Rupter Switches with Power Fuses—Type SM. S&C Specification Bulletin 771-31 13 S&C Alduti-Rupter® Switches with Power Fuses Type SM for Vertical Mounting Three-Pole Double-Break Style with Disconnect 180° Opening Fuse Dimensions in inches 10 29³⁄₈ 8¹⁄₄ 6 ⁹⁄₁₆ DIA. HOLES (2) 3 ⁹⁄₁₆ DIA. HOLES (6) 21¹⁄₂ 1³⁄₄ 2 18 2⁷⁄₈ 1¹⁄₂ OPERATING PIPE MAY BE FURNISHED IN THIS POSITION 1 19 1 20¹⁄₄ 39¹⁄₂ 1⁵⁄₈ 19 HORIZONTAL OPERATING PIPE 82 1 1³⁄₄ FOR SM-4 4¹⁄₁₆ FOR SM-5 39¹⁄₂ ⁄ 2¹⁄₄ ¹⁄₂ –13 TAPPED HOLES (2) EACH SIDE 32 1 6 1³⁄₄ 21³⁄₄ ⁹⁄₁₆⫻1⁹⁄₁₆ SLOTS (4) ⁹⁄₁₆ 1 32 53⁷⁄₈ – FOR SM-4 57 – FOR SM-5 1 TERMINAL PAD DRILLING Rating Fuse Type and Max Amp Rating kV Catalog Number Fuse Interr. Amps, RMS, Sym. Applications (see pages 4 and 5) Cypoxy Station Post Insulators Porcelain Station Post Insulators Holder (Refill Units not Included) Cypoxy Station Porcelain Station Post Insulators Post Insulators Nom. Max BIL SM-4 200E 34.5 38 200 6 250 AEGH(KL) 320704R10-E 320704R10 86054 280 362 SM-5 300E 34.5 38 200 17 500 AEGH(KL) 320714R10-E 320714R10 86154R2 308 380 ༃ Includes weight of fuse holder. 14 Net Wt. per Pole, Lbs.༃ Switches (less Holders) S&C Specification Bulletin 771-31 S&C Alduti-Rupter® Switches with Power Fuses Type SM for Vertical Mounting Three-Pole Vertical-Break Style with Disconnect 180° Opening Fuse Dimensions in inches 38⅜ (14.4 kV) 47 (25 kV) 26⅝ (14.4 kV) 30⅝ (25 kV) 63 (14.4 kV) 71¼ (25 kV) 9∕16×19∕16 SLOTS (2) Fuse Type kV and Max Amp Rating Nom. Max Rating Catalog Number Fuse Interr. Amps, RMS Sym. Applications (see pages 4 and 5) SM-4 14.4 17.0 110 200E 25 27 150 12 500 9 400 AEGHK(L) AEG(HKL) 135302R4-E 135303R5-E 135302R4 86052 135303R5 86053 SM-5 14.4 17.0 110 400E 25 27 150 34 000 20 000 AEGHK(L) AEG(HKL) 135332R4-E 135333R5-E BIL Dimensions in Inches (to nearest ⅛″) Net Wt. per Pole, Lbs.༃ Switches (less Holders) Cypoxy Station Post Insulators Holder (Refill Units Porcelain not Station Post Included) Insulators B F L1 15⅝ 16½ 19⅝ 20½ 10 14 18½ 22½ 26 30 135332R4 86152R2 15⅝ 16½ 135333R5 86153R2 19⅝ 20½ 10 14 18½ 22½ 26 30 A1 A2 L2 M1 M2 Cypoxy Station Post Insulators Porcelain Station Post Insulators 32 32 19⅜ 36¼ 44¼ 23¾ 165 206 193 260 32 40⅝ 24 36¼ 49⅛ 27 194 242 222 296 ༃ Includes weight of fuse holder. S&C Specification Bulletin 771-31 15 S&C Alduti-Rupter® Switches with Power Fuses Type SM for Vertical Mounting Three-Pole Vertical-Break Style with Disconnect 180° Opening Fuse Dimensions in inches 9∕16 × 19∕16 SLOTS (2) Rating Fuse Type and Max Amp Rating SM-5 in Parallel 720E kV Nom. Max BIL 14.4 17.0 110 Catalog Number Fuse Interr. Amps, RMS, Sym. Applications (see pages 4 and 5) 25 000 AEGHK(L) ༃ Includes weight of fuse holder. 16 S&C Specification Bulletin 771-31 Net Wt. per Pole, Lbs.༃ Switches (less Holders) Cypoxy Station Post Insulators Porcelain Station Post Insulators 135442R5-E 135442R5 Holder (Refill Units not Included) 86152R2 Cypoxy Station Porcelain Station Post Insulators Post Insulators 242 270 S&C Alduti-Rupter® Switches with Power Fuses Type SM for Vertical Mounting Single-Pole Style with Disconnect 180° Opening Fuse Dimensions in inches 40¾ (14.4 kV) 47 (25 kV) 23⅝ (14.4 kV) 27¾(25 kV) 48 (14.4 kV) 54¼ (25 kV) 9∕16 × 19∕16 SLOTS (2) Fuse Type kV and Max Amp Rating Nom. Max Rating Dimensions in Inches (to nearest ⅛″) Catalog Number Net Wt. per Pole, Lbs.༃ Fuse Interr. Amps, RMS, Sym. Applications (see pages 4 and 5) SM-4 14.4 17.0 110 200E 14.4 27 150 12 500 9 400 AEGHK(L) AEG(HKL) 136302-E 136303R5-E 136302 136303R5 86052 86053 12⅝ 13½ 16⅝ 17½ 10 14 18½ 45 34⅜ 19½ 20½ 51¼ 42⅝ 23¾ 101 135 122 176 SM-5 14.4 17.0 110 400E 25 27 150 34 000 20 000 AEGHK(L) AEG(HKL) 136332R2-E 136333R5-E 136332R2 136333R5 86152R2 86153R2 12⅝ 13¾ 16⅝ 17¾ 10 14 18½ 45 36¼ 23⅝ 20½ 54¼ 44½ 27⅞ 130 175 151 216 BIL Switches (less Holders) Cypoxy Station Post Insulators Holder (Refill Units Porcelain not Station Post Included) Insulators A1 A2 B F L M1 M2 Cypoxy Porcelain Station Post Station Post Insulators Insulators ༃ Includes weight of fuse holder. S&C Specification Bulletin 771-31 17 S&C Alduti-Rupter® Switches with Power Fuses Type SMD for Vertical Mounting Three-Pole Double-Break Style Dimensions in inches 10 8¹⁄₄ R ⁹⁄₁₆ DIA. HOLES (6) 6 1 2 A₁ 1³⁄₄ 2⁷⁄₈ B HORIZONTAL OPERATING PIPE 1 ⁹⁄₁₆ DIA. HOLES (2) F₁ 20¹⁄₄ FOR 34.5 KV 23¹⁄₄ FOR 46 KV F₁ OPERATING PIPE MAY BE FURNISHED IN THIS POSITION L 1⁵⁄₈ 1 90 ⁹⁄₁₆ ⫻ 1⁹⁄₁₆ SLOTS (4) 2¹⁄₄ F₂ L 1 5¹⁄₈ ⁹⁄₁₆ DIA. HOLES (2) EACH SIDE– 1³⁄₄ APART 1¹⁄₂ A₂ M₁ Catalog Number (including Rating Fuse Fuse-Unit End Fittings) Type Applications Fuse and kV Interr. (see pages Cypoxy Porcelain Max 4 and 5) Amps, Station Post Station Post Amp Insulators Insulators Rating Nom. Max BIL RMS, Sym. M₂ Net Wt. per Pole, Lbs. Dimensions in Inches (to nearest ⅛″) A1 A2 B C F1 F2 L M1 M2 R Cypoxy Porcelain Station Station Post Post Insulators Insulators SMD-1A 34.5 200E 46 38 200 17 500 48.3 250 13 100 AEGH(KL) AEG(KL) 145814R10-E 145815R10-E 145814R10 145815R10 21¾ 22⅝ 18 90 19 41¾ 43½ 62⅞ 36¼ 29⅝ 25¾ 26⅝ 22 100 22 45¾ 48½ 70⅞ 40¼ 33⅝ 307 386 364 443 SMD-2C 34.5 300E 46 38 200 33 500 48.3 250 31 500 AEGH(KL) AEG(KL) 145824R10-E 145825R10-E 145824R10 145825R10 21¾ 22⅝ 18 90 19 41¾ 43½ 62⅞ 36¼ 29⅝ 25¾ 26⅝ 22 100 22 45¾ 48½ 71⅛ 40¼ 33⅝ 318 397 375 454 18 S&C Specification Bulletin 771-31 S&C Alduti-Rupter® Switches with Power Fuses Type SMD for Vertical Mounting Three-Pole Double-Break Style Dimensions in inches 29³⁄₈ 6 10 2156O 856M 6 6QEDIA. HOLES (2) 156O 2 6M 1³⁄₄ 18 2⁷⁄₈ 6QEDIA. HOLES (6) 1 256M OPERATING PIPE MAY BE FURNISHED IN THIS POSITION 1 19 2056M 4356O 16 19 HORIZONTAL OPERATING PIPE 1 836 34 36(6 1³⁄₄ 1 5(6 ⁹⁄₁₆ ⫻ ¹¹⁄₁₆ SLOTS (2) EACH SIDE – 1³⁄₄ APART 2256 ⁹⁄₁₆ ⫻ 1⁹⁄₁₆ SLOTS (4) 27(6 54 Rating Fuse Type and Max Amp Rating SMD-20 200E kV Nom. Max BIL Fuse Interr. Amps, RMS, Sym. 34.5 38 200 10 000 Applications (see pages 4 and 5) AEGH(KL) Catalog Number (including Fuse-Unit End Fittings) Net Wt. per Pole, Lbs. Cypoxy Station Post Insulators Porcelain Station Post Insulators Cypoxy Station Post Insulators Porcelain Station Post Insulators 145844R1-E 145844R1 336 412 S&C Specification Bulletin 771-31 19 S&C Alduti-Rupter® Switches with Power Fuses Type SMD for Vertical Mounting Three-Pole Vertical-Break Style Dimensions in inches 39¾ (14.4 kV) 49¼ (25 kV) 27½ (14.4 kV) 33 (25 kV) 65½ (14.4 kV) 73 (25 kV) 9∕16 × 11∕16 SLOTS (2) EACH SIDE— 1¾ APART 9∕16 × 19∕16 SLOTS (2) SMD-20 14.4 17.0 200E 25 27 20 BIL 110 150 Fuse Interr. Amps, RMS, Sym. Applications (see pages 4 and 5) 14 000 12 500 AEGHK(L) AEG(HKL) S&C Specification Bulletin 771-31 Dimensions in Inches (to nearest ⅛″) Catalog Number (including Fuse-Unit End Fittings) Cypoxy Station Post Insulators 135552R1-E 135553R5-E Porcelain Station Post Insulators Net Wt. per Pole, Lbs. A1 A2 135552R1 16⅜ 14½ 135553R5 21⅞ 18½ B 10 14 F L1 18½ 26 22½ 30 L2 M1 M2 34½ 36⅜ 18⅜ 38 38⅞ 21⅞ Cypoxy Porcelain Station Post Station Post Insulators Insulators 193 219 221 273 Printed in U.S.A. Rating Fuse Type kV and Max Amp Nom. Max Rating