OVR Type 1+2 surge protective devices Single pole Description Type 1 and Type 1+2 surge protective devices are designed to discharge high current surges without any destruction of the installation. These surge protective devices are characterized by their capacity to withstand impulse current with 10/350 µs wave form which simulate natural lightning current. Type 1+2 ABB surge protective devices have a high impulse current withstand capacity with ensuring a low protection level (Up). Type 1 and Type 1+2 SPDs can be installed at the entrance in the main switch board for a global protection of the electrical installation. 3 OVR T1+2 15-255-7 Ordering details Nb of Impulse Max. poles current discharge current Iimp Imax 10/350 8/20 kA kA 1 7 70 1 15 140 1 25 60 Follow current interrupting rating Ifi Voltage Nominal Max. cont. Type protection voltage operating level voltage Up Un Uc kA 15 kV 1.4 1.4 1.5 V 230/400 230/400 230/400 V 275 440 255 Follow current interrupting rating 7 kA 1 15 60 7 1.7 230/400 255 Main dimensions Order code EAN code Weight Pkg (1 pce) 3660308 OVR T1+2 7-275s P 2CTB815101R3900 513403 OVR HL 15-440s P TS 2CTB815201R0800 509802 OVR T1+2 25-255 TS 2CTB815101R0300 510884 kg 0.15 0.32 0.27 OVR T1+2 15-255-7 0.14 2CTB815101R8900 514134 mm OVR HL 15-440s P TS OVR T1+2 7-275s P 35 OVR T1+2 25-255 TS Type OVR T1+2 7-275s P OVR HL 15-440s P TS OVR T1+2 25-255 TS OVR T1+2 15-255-7 OVR T1+2 15-255-7 Width mm 17.8 35.6 35.0 17.8 inches 0.70 1.40 1.38 0.70 32 | ABB System pro M compact® 1TXH000083C0202_OVR_proM.indb 32 17/09/2012 15:57:40 OVR Type 1+2 surge protective devices Single pole General technical data Types with auxiliary contact (TS) Technology Wiring diagram OVR T1+2 7-275s P – Varistor OVR T1+2 Electrical features Standard Type / test class Protected lines Types of networks Type of current Nominal voltage Un Maximum continuous operating voltage Uc Maximum impulse current Iimp (10/350) Maximum impulse current Tot. Iimp (10/350) Maximum discharge current Imax (8/20) Nominal discharge current In (8/20) Follow current interrupting rating Ifi Voltage protection level Up at In (L-N/N-PE/L-PE) Voltage protection level Up at 3 kA (L-N/N-PE/L-PE) TOV (Temporary overvoltage) withstand Ut (L-N: 5 s / N-PE: 200 ms) Response time Residual current IPE Short-circuit withstand capability Isccr Backup protection Fuse (gG - gL) Circuit breaker (B or C curve) Pluggable cartridge Integrated thermal disconnector State indicator Safety reserve Auxiliary contact Installation Wire range (L, N, PE) Solid wire Stranded wire Stripping length (L, N, PE) Tightening torque (L, N, PE) Auxiliary contact (TS) Contact complement Minimum load Maximum load Connection cross-section Miscellaneous characteristics Stocking and operating temperature Degree of protection Fire resistance according to UL 94 Dimensions height x width x depth with auxiliary contact (TS) height x width x depth – – OVR T1+2 15-255-7 OVR HL 15-440s P TS OVR T1+2 25-255 TS – Varistor Spark-gap + varistor Spark-gap OVR HL 3 V V kA kA kA kA kA kV kV IEC 61643-1 / EN 61643-11 T1+T2 / I+II T1+T2 / I+II 1 1 TNC / TNS / TT IT / TNC / TNS / TT AC AC 230 / 400 230 / 400 275 440 7 15 7 15 70 100 7 5 – – – / – / 1.4 – / – / 1.4 – / – / 0.8 – / – / 1.2 T1+T2 / I+II 1 TNC / TNS / TT AC 230 / 400 255 25 25 60 25 15 – / – / 1.5 – / – / 1.0 T1+T2 / I+II 1 TNC / TNS / TT AC 230 / 400 255 15 15 60 15 7 – / – / 1.7 – / – / 0.9 V ns µA kA 334 / – ≤ 25 50 50 440 / – ≤ 25 50 50 334 / – ≤ 100 10 50 650 / – ≤ 100 1000 50 ≤ 50 ≤ 50 Yes Yes Yes Yes No ≤ 50 ≤ 50 Yes Yes Yes Yes Yes ≤ 125 ≤ 125 No Yes Yes No Yes ≤ 125 ≤ 125 No – Yes No No 2.5…25 2.5…16 12.5 2 2.5…50 2.5…35 15 3.5 2.5…50 2.5…35 15 3.5 2.5…50 2.5…35 15 3.5 1 NO - 1 NC 12 V DC - 10 mA 250 VAC - 1 A 1.5 1 NO - 1 NC 12 V DC - 10 mA 250 VAC - 1 A 1.5 – – – – -40 to +80 IP20 V0 -40 to +80 IP20 V0 -40 to +80 IP20 V0 -40 to +80 IP20 V0 mm inches 85 x 17.8 x 64.8 3.35 x 0.70 x 2.55 – – – – 85 x 17.8 x 70.8 3.35 x 0.70 x 2.79 mm inches – – 90 x 35.6 x 65 3.54 x 1.40 x 2.56 93 x 35 x 58 3.66 x 1.38 x 2.28 – – A A mm² mm² mm Nm – – – mm² – °C ABB System pro M compact® | 33 1TXH000083C0202_OVR_proM.indb 33 17/09/2012 15:57:41 OVR Type 1+2 surge protective devices TNC 230 V networks Description Type 1 and Type 1+2 surge protective devices are designed to discharge high current surges without any destruction of the installation. These surge protective devices are characterized by their capacity to withstand impulse current with 10/350 µs wave form which simulate natural lightning current. Type 1+2 ABB surge protective devices have a high impulse current withstand capacity with ensuring a low protection level (Up). Type 1 and Type 1+2 SPDs can be installed at the entrance in the main switch board for a global protection of the electrical installation. 3 Ordering details OVR HL 3L 15-440s P TS Nb of poles 3 3 Impulse Max. current discharge current Iimp Imax 10/350 8/20 kA kA 15 100 7 70 Main dimensions Voltage Nominal Max. Type protection voltage cont. level operating voltage Up Un Uc kV 1.4 1.4 V V 230/400 440 230/400 275 OVR HL 3L 15-440s P TS OVR T1+2 3L 7-275s P EAN code Weight Pkg (1 pce) OVR HL 3L 15-440s P TS 2CTB815401R0400 OVR T1+2 3L 7-275s P 2CTB815101R4000 3660308 509833 513410 kg 0.94 0.48 mm OVR HL 3L 15-440s P TS Type Order code Width mm 106.8 53.4 OVR T1+2 3L 7-275s P inches 4.2 2.1 34 | ABB System pro M compact® 1TXH000083C0202_OVR_proM.indb 34 17/09/2012 15:57:43 OVR Type 1+2 surge protective devices TNC 230 V networks General technical data Types with auxiliary contact (TS) Technology Wiring diagram – OVR HL 3L 15-440s P TS Varistor OVR T1+2 3L 7-275s P – Varistor OVR T1+2 OVR T1+2 OVR T1+2 OVR HL 3 Electrical features Standard Type / test class Protected lines Types of networks Type of current Nominal voltage Un Maximum continuous operating voltage Uc Maximum impulse current Iimp (10/350) Maximum impulse current Tot. Iimp (10/350) Maximum discharge current Imax (8/20) Nominal discharge current In (8/20) Follow current interrupting rating Ifi Voltage protection level Up at In (L-N/N-PE/L-PE) Voltage protection level Up at 3 kA (L-N/N-PE/L-PE) TOV (Temporary overvoltage) withstand Ut (L-N: 5 s / N-PE: 200 ms) Response time Residual current IPE Short-circuit withstand capability Isccr Backup protection Fuse (gG - gL) Circuit breaker (B or C curve) Pluggable cartridge Integrated thermal disconnector State indicator Safety reserve Auxiliary contact Installation Wire range (L, N, PE) Solid wire Stranded wire Stripping length (L, N, PE) Tightening torque (L, N, PE) Auxiliary contact (TS) Contact complement Minimum load Maximum load Connection cross-section Miscellaneous characteristics Stocking and operating temperature Degree of protection Fire resistance according to UL 94 Dimensions height x width x depth with auxiliary contact (TS) height x width x depth V V kA kA kA kA kA kV kV IEC 61643-1 / EN 61643-11 T1+T2 / I+II 3 IT / TNC AC 230 / 400 440 15 45 100 5 – – / – / 1.4 – / – / 1.2 T1+T2 / I+II 3 TNC AC 230 / 400 275 7 20 70 7 – – / – / 1.4 – / – / 0.8 V ns µA kA 440 / – ≤ 25 150 50 334 / – ≤ 25 150 50 ≤ 50 ≤ 50 Yes Yes Yes Yes Yes ≤ 50 ≤ 50 Yes Yes Yes Yes No 2.5…50 2.5…35 15 3.5 2.5…25 2.5…16 12.5 2 A A mm² mm² mm Nm 1 NO - 1 NC 12 V DC - 10 mA 250 V AC - 1 A mm² 1.5 – – – – -40 to +80 IP20 V0 -40 to +80 IP20 V0 mm inches – – 85 x 53.4 x 64.8 3.35 x 2.10 x 2.55 mm inches 90 x 106.8 x 65 3.54 x 4.20 x 2.56 – – °C ABB System pro M compact® | 35 1TXH000083C0202_OVR_proM.indb 35 17/09/2012 15:57:43 OVR Type 1+2 surge protective devices TNS/TT 230 V 1Ph+N and 3Ph+N networks Description Type 1 and Type 1+2 surge protective devices are designed to discharge high current surges without any destruction of the installation. These surge protective devices are characterized by their capacity to withstand impulse current with 10/350 µs wave form which simulate natural lightning current. Type 1+2 ABB surge protective devices have a high impulse current withstand capacity with ensuring a low protection level (Up). Type 1 and Type 1+2 SPDs can be installed at the entrance in the main switch board for a global protection of the electrical installation. 3 Ordering details OVR T1+2 1N 7-275s P Nb of Impulse Max. poles current discharge current Iimp Imax 10/350 8/20 kA kA 1+1 7 70 3+1 7 70 4 7 70 4 15 100 Follow current interrupting rating Ifi Voltage Nominal Max. Type protection voltage cont. level operating voltage Up Un Uc kA - kV 1.4 1.4 0.9 1.4 V 230/400 230/400 230/400 230/400 V 275 275 275 440 Order code OVR T1+2 1N 7-275s P OVR T1+2 3N 7-275s P OVR T1+2 4L 7-275s P OVR HL 4L 15-440s P TS OVR T1+2 3N 7-275s P kg 0.32 0.63 0.60 1.20 2CTB815101R9000 514141 0.84 Width mm 35.0 71.2 71.2 142.4 89.0 OVR T1+2 4L 7-275s P OVR T1+2 3N 15-255-7 OVR HL 4L15-440s P TS OVR T1+2 1N 7-275s P OVR T1+2 3N 7-275s P OVR T1+2 4L 7-275s P OVR HL 4L15-440s P TS OVR T1+2 3N 15-255-7 3660308 515728 515735 513427 509840 2CTB815302R1000 2CTB815502R1000 2CTB815101R4100 2CTB815503R0400 mm OVR T1+2 1N 7-275s P Type Weight Pkg (1 pce) Follow current interrupting rating 7 kA - 2 poles (1Ph+N) 3+1 15 60 7 1.7 230/400 255 OVR T1+2 3N 15-255-7 Main dimensions EAN code inches 1.38 2.80 2.80 5.60 3.50 36 | ABB System pro M compact ® 1TXH000083C0202_OVR_proM.indb 36 17/09/2012 15:57:44 OVR Type 1+2 surge protective devices TNS/TT 230 V 1Ph+N and 3Ph+N networks General technical data Types with auxiliary contact (TS) Technology Wiring diagram OVR T1+2 1N 7-275s P – Varistor OVR T1+2 OVR T1+2 OVR T1+2 3N 7-275s P – Varistor OVR T1+2 OVR T1+2 OVR T1+2 OVR T1+2 OVR T1+2 4L 7-275s P – Varistor OVR T1+2 OVR T1+2 OVR T1+2 – OVR T1+2 3N 15-255-7 OVR HL 4L 15-440s P TS – Varistor Spark-gap OVR T1+2 OVR T1+2 OVR HL 3 Electrical features Standard IEC 61643-1 / EN 61643-11 Type / test class T1+T2 / I+II T1+T2 / I+II Protected lines 1+1 3+1 Types of networks TNS / TT TNS / TT Type of current AC AC V 230 / 400 Nominal voltage Un 230 / 400 V 275 Maximum continuous operating voltage Uc 275 kA 7 Maximum impulse current Iimp (10/350) 7 kA 15 Maximum impulse current Tot. Iimp (10/350) 30 kA 70 Maximum discharge current Imax (8/20) 70 kA 7 Nominal discharge current In (8/20) 7 kA – Follow current interrupting rating Ifi – kV 0.9 / 1.4 / 1.4 Voltage protection level Up at In (L-N/N-PE/L-PE) 0.9 / 1.4 / 1.4 kV 0.8 / 0.8 / 0.8 Voltage protection level Up at 3 kA (L-N/N-PE/L-PE) 0.8 / 0.8 / 0.8 TOV (Temporary overvoltage) withstand Ut V 334 / 1200 (L-N: 5 s / N-PE: 200 ms) 334 / 1200 ns ≤ 25 Response time ≤ 25 µA 10 Residual current IPE 10 kA 50 Short-circuit withstand capability Isccr 50 Backup protection A ≤ 50 Fuse (gG - gL) ≤ 50 A ≤ 50 Circuit breaker (B or C curve) ≤ 50 Pluggable cartridge Yes Yes Integrated thermal disconnector Yes Yes State indicator Yes Yes Safety reserve Yes Yes Auxiliary contact No No Installation Wire range (L, N, PE) mm² 2.5…25 Solid wire 2.5…25 mm² 2.5…16 Stranded wire 2.5…16 mm 12.5 Stripping length (L, N, PE) 12.5 Nm 2 Tightening torque (L, N, PE) 2 Auxiliary contact (TS) Contact complement – – Minimum load – – Maximum load – – mm² – Connection cross-section – Miscellaneous characteristics °C -40 to +80 Stocking and operating temperature -40 to +80 Degree of protection IP20 IP20 Fire resistance according to UL 94 V0 V0 Dimensions mm 85 x 35 x 64.8 height x width x depth 85 x 71.2 x 64.8 inches 3.35 x 1.38 x 2.55 3.35 x 2.80 x 2.55 with auxiliary contact (TS) mm – height x width x depth – inches – – T1+T2 / I+II 4 TNS AC 230 / 400 275 7 30 70 7 – - / - / 1.4 - / - / 0.8 T1+T2 / I+II 4 TNS AC 230 / 400 440 15 60 100 5 – - / - / 1.4 - / - / 1.2 T1+T2 / I+II 3+1 TNS / TT AC 230 / 400 255 15 50 60 15 7 1.7 / 1.5 / 1.7 0.9 / 0.9 / 0.9 334 / ≤ 25 200 50 440 / ≤ 25 200 50 650 / 1200 ≤ 100 1000 50 ≤ 50 ≤ 50 Yes Yes Yes Yes No ≤ 50 ≤ 50 Yes Yes Yes Yes Yes ≤ 125 ≤ 125 No Yes No No 2.5…25 2.5…16 12.5 2 2.5…50 2.5…35 15 3.5 2.5…50 2.5…35 15 3.5 – – – – 1 NO - 1 NC 12 V DC - 10 mA 250 V AC - 1 A 1.5 – – – – -40 to +80 IP20 V0 -40 to +80 IP20 V0 -40 to +80 IP20 V0 85 x 71.2 x 64.8 3.35 x 2.80 x 2.55 – – 85 x 89 x 70.8 3.35 x 3.50 x 2.79 – – 90 x 142.4 x 65 3.54 x 5.60 x 2.56 – – ABB System pro M compact® | 37 1TXH000083C0202_OVR_proM.indb 37 17/09/2012 15:57:45 OVR Type 2 surge protective devices Single pole 57 V networks Description Type 2 surge protective devices are designed to protect electric installations and sensitive equipment against indirect surges with ensuring a low protection level (Up). They are characterized by their capacity to safely discharge current with 8/20 µs wave form. Ordering details Nb of poles 3 OVR T2 15-75 P Type 1 1 2 2 Max. discharge current Imax 8/20 kA Nominal discharge current Voltage Nominal Max. Type protection voltage cont. level operating voltage Up Un Uc kV V V In kA 2 pluggable - Uc 75 V 15 5 0.3 15 5 0.3 15 5 0.3 15 5 0.3 Main dimensions 57 57 57 57 75 75 75 75 OVR T2 15-75 P OVR T2 15-75 P TS OVR T2 2L 15-75 P OVR T2 2L 15-75 P TS OVR T2 2L 15-75 P OVR T2 15-75 P TS OVR T2 2L 15-75 P TS OVR T2 15-75 P OVR T2 15-75 P TS OVR T2 2L 15-75 P OVR T2 2L 15-75 P TS EAN code Weight Pkg (1 pce) 2CTB803851R2800 2CTB803851R2700 2CTB803852R1700 2CTB803852R1600 3660308 kg 518446 518453 518484 518477 0.12 0.12 0.23 0.23 mm OVR T2 15-75 P Type Order code Width mm 17.8 17.8 35.6 35.6 inches 0.70 0.70 1.40 1.40 38 | ABB System pro M compact ® 1TXH000083C0202_OVR_proM.indb 38 17/09/2012 15:57:46