Power Quality Clean power, Efficient business Immediate Energy Efficiency with Power Factor Correction Outline Power Factor: ●Definition & Examples ●Cost Savings ●Power Factor Correction Equipment Harmonics: ●Introduction ●Harmonics and Power Factor Correction Capacitors ●IEEE 519 Standard ●Traditional Harmonic Mitigation Methods ●Active Filter Technology & Applications Schneider Electric – Global PQ – June 2013 2 What is Power Factor? Definitions: ● kW = Active Power: It does the "work" for the system - providing the motion, heat, or whatever else is required. ● kVAR = Reactive Power: It doesn't do useful "work." It simply sustains the electromagnetic field. ● kVA = Apparent Power: It is the vector addition of Working Power and Reactive Power. ● Power Factor : The ratio of Active Power (output) to Total Power (input). It is a measure of efficiency. Total Power (kVA) θ Active Power (kW) Schneider Electric – Global PQ – June 2013 Power Factor = Reactive Power (kVAR) = = Active (Real) Power Total Power kW kVA Cosine (θ) 3 Power Factor:The Beer Analogy kVAR Mug Capacity = Apparent Power (kVA) Reactive Power Foam = Reactive Power (kVAR) Beer = Real Power (kW) kVA Apparent Power kW Active Power Schneider Electric – Global PQ – June 2013 Power Factor = Beer (kW) Mug Capacity (kVA) Capacitors provide the Foam (kVAR), freeing up Mug Capacity so you don’t have to buy a bigger mug and/or so you can pay less for your beer ! 4 Why is Power Factor Important? ● Low power factor results in: ● Poor electrical efficiency ● Lower system capacity ● Higher utility bills ●Most utilities have power factor penalties to encourage power factor correction. Otherwise the utility may have to: – Build more power plants – Purchase new transformers – Use larger cables ● Power factor correction ● Reduces power cost ● Releases system capacity ● Reduces power losses ● Improves voltage Schneider Electric – Global PQ – June 2013 5 Power Factor Correction ● The easiest solution to improve power factor is to add power factor correction capacitors to your electrical distribution system. The Capacitor Supplies Reactive Current M Current that is drawn from the voltage source is then only used to do real work (kW) and not to create a magnetic field (kVAR). The source current is then minimized » The customer only pays for the capacitor » Since the utility doesn’t supply the kVAR, the customer doesn’t pay for it » In short, capacitors save money Schneider Electric – Global PQ – June 2013 6 A2 Power Factor Correction In this example, demand is reduced from 100 kVA to 80 kVA by installing a 60 kVAR capacitor. Before: PF = kW/kVA = 80% After: PF = kW/kVA = 100% Transformer loading is reduced Schneider Electric – Global PQ – June 2013 7 Benefits of Power Factor Correction ● Reduced Power Costs: lower utility bills since utility no longer supplies the reactive current. ● Released System Capacity ● Capacitors off-load transformers and cables ● Improved Voltage ● Reduced losses kW 100 kVAR 100 kVA = 141 PF = 70% Schneider Electric – Global PQ – June 2013 kW 100 kVAR 75 kVA = 125 PF = 80% kW 10 0 kVA = 100 PF = 100% 8 How do utilities charge for Power Factor? ● Example with $5.50 per demand kW Service Month 05/14/11 06/14/11 07/16/11 08/15/11 09/16/11 10/16/11 11/16/11 12/16/11 01/16/12 02/16/12 03/16/12 04/16/12 Billing Demand kW 900.0 800.0 850.0 875.0 910.0 780.0 890.0 870.0 760.0 750.0 690.0 870.0 Power Factor 0.8000 0.7950 0.7625 0.7511 0.7574 0.7722 0.7950 0.7950 0.7625 0.7511 0.7574 0.7722 Actual Actual Demand Demand kVA kW 1,000.0 800.0 888.9 706.7 944.4 720.1 972.2 730.2 1,011.1 765.8 866.7 669.2 988.9 786.2 966.7 768.5 844.4 643.9 833.3 625.9 766.7 580.7 966.7 746.5 0.0 0.0 Savings 2012 Possible Cost Savings $550.00 $513.33 $714.24 $796.20 $793.01 $609.18 $571.08 $558.25 $638.61 $682.46 $601.30 $679.47 Required Required % Reduction Capacitor kVAR Capacitor kVAR of Transformer for 0.92 pf for 1.0 pf kVA Load 259 600 20% 238 539 21% 304 611 24% 331 642 25% 334 660 24% 266 551 23% 265 600 21% 259 586 21% 272 546 24% 284 550 25% 253 501 24% 296 614 23% $7,707.13 Approximate cost of standard power factor correction equipment $12 to $15K === Payback about 2 years. Approximate cost of filtered power factor correction equipment $18 to $21K === Payback about 3 years. Schneider Electric – Global PQ – June 2013 9 Power Factor Correction ● Capacitors: ● Low Voltage Power Factor Correction Capacitor Banks ●Fixed ●Standard Automatic ●Detuned ●Transient Free ● Medium Voltage Power Factor Correction Capacitor Banks ●Fixed ●Standard Automatic ●Detuned ● Active Filters ● LV and MV Hybrid VAR Compensation Products Schneider Electric – Global PQ – June 2013 10 Schneider Electric – Global PQ – June 2013 11 Outline Power Factor: ●Definition & Examples ●Cost Savings ●Power Factor Correction Equipment Harmonics: ●Introduction ●Harmonics and Power Factor Correction Capacitors ●IEEE 519 Standard ●Traditional Harmonic Mitigation Methods ●Active Filter Technology & Applications Schneider Electric – Global PQ – June 2013 13 Harmonic Basics Waveform seen with oscilloscope ● What are harmonics? ● A harmonic is a component of a periodic wave with a frequency that is an integer multiple of the fundamental frequency ● Created by power semiconductor devices Fundamental rd 3 Harmonic th 7 Harmonic t1h 5 Harmonic ●Converts power (AC to DC) Harmonic Frequency Sequence 1 2 3 4 5 6 7 : 19 60Hz 120Hz 180Hz 240Hz 300Hz 360Hz 420Hz : 1140Hz Schneider Electric – Global PQ – June 2013 + 0 + 0 + + ● Characteristic harmonics are the predominate harmonics seen by the power distribution system ●Predicted by the following equation: Hc = np ± 1 – HC = characteristic harmonics to be expected – n = an integer from 1,2,3,4,5, etc. – p = number of pulses or rectifiers in circuit 14 Harmonic Filtering Schneider Electric – Global PQ – June 2013 15 Multi-pulse Converters Harmonic Orders Present Hn = np +/- 1 Hn = characteristic harmonic order present n = an integer p = number of pulses Elimination of lower orders removes largest amplitude harmonics Schneider Electric – Global PQ – June 2013 Hn 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 Harmonics present by rectifier design Type of rectifier 1 phase 2 phase 3 phase 3 phase 4-pulse 4-pulse 6-pulse 12-pulse x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x AccuSine SWP AccuSine PCS 3 phase 18-pulse x x x x 16 Harmonic Basics ● Nonlinear loads draw harmonic current from source ● Does no work Voltage: flat topping of waveform Basic PWM VFD Current: high TDD between 90-120% Inverter Converter DC bus M A B C Schneider Electric – Global PQ – June 2013 17 Harmonic Basics ●Why the concern? ● Current distortion ●Added heating = reduced capacity ●Equipment failures – Transformers – Conductors and cables – Nuisance tripping of electronic circuit breakers (thermal overloads) ●Heating proportional to harmonic order in cables & bus bars Ih Loads Vh = Ih × Zh ● Squared effect on transformers & AC motors Schneider Electric – Global PQ – June 2013 18 Harmonic Basics Voltage distortion ● Created as current harmonics flow through the system ● Interference with other electronic loads Ih ●Malfunctions to failure ● Induces harmonic currents in linear loads ●AC motor winding over heating & bearing failures Loads Vh = Ih × Zh Schneider Electric – Global PQ – June 2013 19 Harmonics and Standard Capacitors ●Capacitors absorb harmonics ● Overheating of PFC capacitors ● Tripping of PF protection devices ● Reduced life expectancy ●Magnification of harmonics by resonance Utility M M Schneider Electric – Global PQ – June 2013 M VFD ● Amplification of current between capacitor and transformer ● Current distortion rises ● Voltage distortion rises ● Main transformer &/or capacitor fuses blow ● Equipment damage 20 Capacitor Resonance Schneider Electric – Global PQ – June 2013 21 Detuned Capacitors Schneider Electric – Global PQ – June 2013 22 Conventional Switch Structure L1 HRC Fuses Contactors Optional De-tuned Inductor Schneider Electric – Global PQ – June 2013 L2 L3 Electromechanical switching elements (contactors) are used to connect a capacitor group. 23 IEEE 519-1992 ● Defines current distortion as TDD (Total Demand Distortion) ● Largest amplitude of harmonic current occurs at maximum load of nonlinear device – if electrical system can handle this it can handle all lower levels of amplitudes ● Always referenced to full load current ● Effective meaning for current distortion ● Defines voltage distortion as THD ● Total harmonic voltage distortion ● Does not use THD(I) ● Total harmonic current distortion ● Instrument measurement (instantaneous values) ● Uses measured load current to calculate THD(I) THDv = 2 V ∑ h Vf Schneider Electric – Global PQ – June 2013 TDD = 2 I ∑h If ( FLA ) THDi = 2 I ∑h If 24 IEEE 519-1992 ● Issues addressed: ● THD(V) delivered by utility to user (Chapter 11) ●THD(V) must be < 5% [< 69 KV systems] ● Defines the amount of TDD a user can cause (Chapter 10) ●Based upon size of user in relation to power source ●Table 10.3 for systems < 69 kV ● Defines limits for voltage notches caused by SCR rectifiers – Table 10.2 ● Defines PCC (point of common coupling) Schneider Electric – Global PQ – June 2013 25 IEEE 519-1992 • TDD and THD(I) are not the same except at 100% load • As load decreases, TDD decreases while THD(I) increases. • Example: Total I, rms Full load Schneider Electric – Global PQ – June 2013 936.68 836.70 767.68 592.63 424.53 246.58 111.80 Measured Fund I, Harm I, rms rms 936.00 836.00 767.00 592.00 424.00 246.00 111.00 35.57 34.28 32.21 27.23 21.20 16.97 13.32 THD(I) 3.8% 4.1% 4.2% 4.6% 5.0% 6.9% 12.0% TDD 3.8% 3.7% 3.4% 2.9% 2.3% 1.8% 1.4% 26 IEEE 519-1992 Table 10.3 Current Distortion Limits for General Distribution Systems (<69 kV) Isc/Iload <20 20<50 50<100 100<1000 >1000 <11 4.0% 7.0% 10.0% 12.0% 15.0% 11<=h<17 17<=h<23 23<=h<35 2.0% 1.5% 0.6% 3.5% 2.5% 1.0% 4.5% 4.0% 1.5% 5.5% 5.0% 0.2% 7.0% 6.0% 2.5% h>=35 0.3% 0.5% 0.7% 1.0% 1.4% TDD 5.0% 8.0% 12.0% 15.0% 20.0% Isc = short circuit current capacity of source Iload = demand load current (fundamental) TDD = Total Demand Distortion (TDD = Total harmonic current distortion measured against fundamental current at demand load.) Schneider Electric – Global PQ – June 2013 27 Harmonic Standards •Designed to protect utility •Most harmonic problems are not at PCC with utility •Occur inside the plant •Occur where nonlinear loads are concentrated •Occur with generators & UPS (high probability of problems) •Need to protect the user from self by moving the PCC to where harmonic loads are located. •Apply principals of IEEE 519-1992 Table 10.3 inside the plant •Assures trouble free operations •Assures compliance to standard •We have the products to meet 5% TDD inside the plant Schneider Electric – Global PQ – June 2013 28 Harmonic mitigation methods - (Applied per VFD) Typical % Typical Price Solution Advantage Disadvantage TDD Multiplier* Dependent upon SCR*** Cost of transformer and installation change out Increase short circuit capacity Reduces THD(V) ●Increases TDD ●Not likely to occur** C-Less Technology ●Lower TDD ●Simplified design ●Less cost ●Compliance is limited ●Application limited ●Size limited 30 - 50% TDD 0.90 - 0.95 Impedance (3% LR or 3% DC choke) ●Low cost adder ●Simple ●Compliance difficult 30 - 40% TDD 1.05 - 1.15 5th Harmonic filter Reduces 5th & total TDD ●Does not meet harmonic levels at higher orders^ 18 - 22% TDD 1.20 - 1.45 Broadband filter Reduces TDD (thru 13th) ●Large heat losses ●Application limited 8 - 15% TDD 1.25 - 1.50 12-pulse rectifiers ●Reduces TDD ●Reliable ●Large footprint/heavy ●Good for >100 HP 8 - 15 % TDD 1.65 - 1.85 18-pulse rectifiers ●Reduces TDD ●Reliable ●Large footprint/heavy ●Good for >100 HP 5 - 8% TDD 1.65 - 1.85 Active front end converter ●Very good TDD ●Regeneration possible ●Large footprint/heavy ●Very high cost per unit ●High heat losses < 5% TDD 2.0 - 2.5 * Price compared to a standard 6-pulse VFD. ** Utilities and users are not likely to change their distribution systems. *** Increasing short circuit capacity (lower impedance source or larger KVA capacity) raises TDD but lowers THD(V). ^ Can be said for all methods listed. Active Filter Concept Load(s) Source XFMR SOURCE Sense LOAD Sense Is Il Ia •Parallel connected Is + Ia = Il Optional CT location • Ia includes 2nd to 50th harmonic current • Is <5% TDD Schneider Electric – Global PQ – June 2013 30 Harmonic Mitigation Solutions System solution Comparison of 18-P VFD to AccuSine PCS + standard VFD ●Price (first cost) ●Footprint required ●Heat losses ●Cost to operate ●Site cooling required ●Net Present Value (NPV) Schneider Electric – Global PQ – June 2013 31 Solutions by AccuSine Model Schneider Electric – Global PQ – June 2013 32 Schneider Electric Offer ●AccuSine SWP ● 20-120 Amps ● 400 VAC ● Neutral correction ●AccuSine PCS ● 50-300 Amps ● 208-480 VAC/600 VAC/690 VAC ●AccuSine PFV ● 50-300 Amps ● 208-480 VAC/600 VAC/690 VAC ● No harmonics ●Use customized transformers for higher voltages (to 15 kV for harmonics & 35 kV for non-harmonic modes) Schneider Electric – Global PQ – June 2013 33 AccuSine SWP ● The Schneider Electric solution for harmonic filtering in buildings. Schneider Electric – Global PQ – June 2013 34 AccuSine PCS ● The Schneider Electric solution for active harmonic filtering in industrial installations. ● Most common – VFD sites ● Centrifugal pumps and fans ●Pumping Stations – Potable – Wastewater ●Wastewater Plants ●Water Purification (potable) Schneider Electric – Global PQ – June 2013 35 AccuSine® PCS/PFV Power Diagram IGBT Module C Pre-charge Contactor C E S1 C E S3 E S5 DC Bus Capacitors Fuse AC Lines Fuse Line Inductor + C Fuse Inductor C Filter Board E S2 Schneider Electric – Global PQ – June 2013 C C E S4 E S6 36 AccuSine® PCS Performance Summary - Harmonics ● Discrete Spectrum Logic (DSL) ● TDD <= 5%, if loads have =>3% Z installed ● 2nd to 50th orders, discrete ● <2 cycle response ● Resonance avoidance logic ● Adjustable trip limits per harmonic order ● On-board commissioning program ●Phase rotation (clockwise required) ●Automatic CT orientation (phase rotation/polarity/calibration) ●Run lockout if not possible to re-orient ● Oscilloscope feature built into HMI ● Load/source bar graphs ● Load balancing ● Can parallel up to 99 units of each size and mix sizes Schneider Electric – Global PQ – June 2013 37 System Solution AccuSine® PCS Sizing Example ● A 125 HP variable torque 6-pulse VFD with 3% LR ● Required AHF filtering capability = 47.5 amperes ● Two 125 HP VT 6-pulse VFD w/3% LR ● Required AHF size = 84.4 amps ● Three 125 HP VT 6-pulse VFD w/3% LR ● Required AHF size = 113.5 amps ● Six 125 HP VT VFD w/3% LR ● Required AHF size = 157.6 amps ● (not 6 x 47.5 = 285 amps) Schneider Electric – Global PQ – June 2013 38 AccuSine® PCS/PFV Product Package ● Standard (UL/CSA, ABS) ● Three current ratings ● Enclosed – NEMA 1/IP20 ● 50 amp – 52”(1321mm) x 21”(533mm) x 19”(483mm) ●Weight – 250#(114 K\kg) ● 100 amp – 69”(1753mm) x 21”(533mm) x 19”(483mm) ●Weight – 350#(159 kg) ● 300 amp – 75”(1905mm) x 32”(813mm) x 20”(508mm) ●Weight – 775#(352 kg) ● Wall mount – 50 & 100 amp ● Free standing – 300 amp with disconnect Schneider Electric – Global PQ – June 2013 39 AccuSine® PCS/PFV Product Package ● Other enclosures (380 - 480VAC) ● NEMA 12, IP30, IP54 ●50 amp – 75”(1905mm) x 31.5”(800mm) x 23.62”(600mm) – Weight – 661Ib(300 kg) ●100 amp – 75”(1905mm) x 31.5”(800mm) x 23.62”(600mm) – Weight – 771Ib(350 kg) ●300 amp – 75”(1905mm) x 39.37”(1000mm) x 31.5”(800mm) – Weight – 1012Ib(460 kg) ● Free standing with door interlocked disconnect ● CE Certified, C-Tick, ABS, UL, CUL Schneider Electric – Global PQ – June 2013 40 AccuSine PCS 600/690 VAC ● Includes autotransformer & input fused disconnect ● Simple installation ● 600 VAC: UL/cUL/CE ● 690 VAC: CE ● Ratings: PCS 600V 690V 50 A 39 A 33 A 100 A 78 A 67 A 300 A 235 A 200 A Schneider Electric – Global PQ – June 2013 Height 300A 1000 mm 800 mm Height 1900 mm Depth 800 mm 50/100A 800 mm 600 mm 1972 mm 600 mm 41 AccuSine Performance At VFD Terminals AccuSine injection Source current Schneider Electric – Global PQ – June 2013 Order Fund 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 TDD AS off AS on % I fund % I fund 100.000%100.000% 0.038% 0.478% 31.660% 0.674% 11.480% 0.679% 0.435% 0.297% 7.068% 0.710% 4.267% 0.521% 0.367% 0.052% 3.438% 0.464% 2.904% 0.639% 0.284% 0.263% 2.042% 0.409% 2.177% 0.489% 0.293% 0.170% 1.238% 0.397% 1.740% 0.243% 0.261% 0.325% 0.800% 0.279% 1.420% 0.815% 0.282% 0.240% 0.588% 0.120% 1.281% 0.337% 0.259% 0.347% 0.427% 0.769% 1.348% 0.590% 35.28% 2.67% 42 700 HP Drive – AccuSine ON – OFF Schneider Electric – Global PQ – June 2013 43 700 HP Drive – AccuSine ON – OFF Schneider Electric – Global PQ – June 2013 44 700 HP Drive – AccuSine ON – OFF Schneider Electric – Global PQ – June 2013 45 AccuSine® PCS Dual Mode Operation ● Assignment of capacity ● Assign priority to Harmonic or PF/LB (fundamental) modes ● Use % of harmonic mode to set split ●100% means capacity utilized for harmonic correction, then left over can be used for PF/LB ●0% assigns fundamental (PF correction/LB) current as primary mode, left over used for harmonic correction ●Can split to limit harmonic mode capacity, left over to PF correction/LB Schneider Electric – Global PQ – June 2013 I as = I h + I f 2 2 Ias = rms output current of AccuSine PCS Ih = rms harmonic current If = rms fundamental current Ias 100.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 Examples Ih 10.0 20.0 30.0 40.0 50.0 60.0 70.0 80.0 90.0 95.0 If 99.5 98.0 95.4 91.7 86.6 80.0 71.4 60.0 43.6 31.2 46 AccuSine® PFV Power Factor & VAR Compensation ●HVC (AccuSine PFV + PF caps) ● Larger systems approach ●HVC is Hybrid VAR Control – Combines AccuSine PFV with PF caps – Caps on line all the time ● AccuSine adjusts fundamental current to attain unity DPF ● Cycle-by-cycle response ● Voltages to 33 kV (6.6 kV shredder in France, 12.47 kV in US automotive, 13.8 kV steel mill in Colombia) ● Fundamental current balancing (optional since 1 Nov 10)) ●Sometimes critical – i.e. two phase loads Schneider Electric – Global PQ – June 2013 47 Thank You Questions? Schneider Electric – Global PQ – June 2013 48