Power Factor Correction and VAR compensation Week 8-9 What is power factor: Percentage of electricity that is being useful for doing work and is defined as the ratio between the ‘active or actual power’ in kW or W, to the ‘apparent power’ expressed in volt- ampere or kilo volt-ampere πππ€ππ ππππ‘ππ = π΄ππ‘ππ£π πππ€ππ πππππ‘ππ£π πππ€ππ The apparent power also referred to as the total power supplied by the utility has two components: a- Productive component: powers the equipment and performs useful work and is given in kW or W b- Reactive power: generates magnetic field to produce flux necessary for the operation of induction devices (AC motors, transformers, induction furnaces..etc.) and is measured in kVar of Var. It produces no productive power Industrial plants introduces inefficiencies into the electrical supply network by drawing additional currents, called “inductive reactive currents”. Although these currents produce no useful power, they increase the load on the supplier’s switch gear and distribution network and on the consumer’s switchgear and cabling. Typical un-improved power factor by industry Industry Power Factor Industry Power Factor Arc welding 35-60 Paint manufacturing 65-70 clothing 35-60 Metal working 65-70 Chemical 65-75 Plastic 75-80 Cement 80-85 Office building 80-90 Calculation of the necessary reactive power: This is done using: 1. Calculations and Power factor triangle method 2. Tables 3. Curves Once the power factor πππ π1 of the installation and the power factor to be obtained πππ π2 are known, it is possible to calculate the reactive power of the capacitor bank necessary to improve the power factor as: ππ = ππΏ × tan π1 − tan π2 Load PF= πππ π1 Improved PF= πππ π2 ππΏ = OB= kW-load capacity OA=πΘ load capacity OD=πΘ reduced capacity Using tables ππ = πππ΄1 × πππ π1 , πππ΄π 1 = πππ΄1 × π πππ1 ∴ πππ΄π 1 = ππ × π‘πππ1 For correction to πππ π2 : ∴ πππ΄π 2 = ππ × π‘πππ2 Therefore, the required correction capacitors ∴ ππ = πππ΄π 1 − πππ΄π 2 ∴ ππ = ππ × π‘πππ1 − π‘πππ2 Finally, Multiplying factor found in table πππππ’ππππ = ππ × ππ’ππ‘ππππ¦πππ ππππ‘ππ Using curves: In this case, choose the initial pf value and select the current power factor curve, the value of the required capacitor is chosen from the intersection of both values in terms of the original kW load Is it that simple? Of course not!!! Power factor correction in Distribution transformer: ο± Transformers are often in constant service. It is advisable that power factor correction is carried out by keeping into account the transformer reactive power so that an average power factor equal to 0.9 on the MV side is guaranteed. ο± Generally, the compensation power ππ [kVar] in a transformer having a rated ππ [kVA], shall not exceed the reactive power absorbed under minimum reference load condition. Apparent power kVA Transformer 7.2-23 kV 24 kV 36 kV No load load No load load No load load 630 17 40.7 18.8 43.6 21.2 46 500 13.5 32.3 15.8 36.8 18 39 400 1.8 25.7 13.2 30 15.2 32 100 3.6 6.92 4.16 7.96 5.08 8.88 More than double! European standard Power factor correction in Distribution transformer: 3 phase transformer with transformation ratio of 6.6kV/ 433V or 11 kV/433 V Apparent power kVA Transformer Core losses (W) Copper losses (W) % magnetizing current 1000 1770 11820 1.2 500 1030 6860 1.53 ο± Deriving from the nameplate characteristics of the transformer the percentage no-load current πΌπ %, the percentage short-circuit voltage π’π %, the iron losses πππ and the copper losses πππ’ [kW], the required compensation power results to be about: ππ = 2 πΌπ % × ππ 100 ≈ 2 − πππ + πΎπ2 × 2 π’π % × ππ 100 2 − πππ’ πΌπ % π’π % × ππ + πΎπ2 × × ππ 100 100 Where ππΏ is the load factor, defined as the ratio between the minimum reference load and the rated power of the transformer Power factor correction in distribution transformer: πππππ 1: ππ [kVar] to be connected to the secondary winding of an ABB transformer Power factor correction in distribution transformer: USA recommendation practice: in case of use of fixed capacitor banks placed on the secondary transformer windings, capacitors should be sized to 40-67% from transformer apparent power rating Tables are available for both power transformers and distribution transformers Egyptian code Power factor correction in Three phase induction motor: Power factor versus speed performance. Better PF of 3-phase IM versus rated power output power factor is achieved at higher speed in kW (or HP). Power factor improves with higher motor power rating Power factor correction in Three phase induction motor: As the rotor is loaded an increasing resistive component is reflected from rotor to stator, increasing the power factor. Power factor improves with higher loading for the same power rating. Power factor correction in Three phase induction motor: Power factor correction capacitors can be calculated using the following: = πΎπ€ × πππ‘π’ππ % πππππππ × ππππ. ππππ‘ππ ππππππππππ¦ ππ‘ πππ‘π’ππ ππππ Correction factor: from tables % loading: actual load / full load (usually 75% from full load) Efficiency at actual load: from chart Tables for individual power factor correction for three phase induction motors How much can I save by installing power capacitors? ο Power capacitors used for power factor correction provide many benefits: ο Increase system capacity ο Reduce utility power bills ο Improve system operating characteristics (voltage gain) ο Improve system operating characteristics (reduce line losses) ο Increase system capacity: PF improvement releases system capacity and permits additional loads (motors, lighting ..etc.) to be added without overloading the system. Capacitors reduce the current drawn from the power supply, less current means less load on transformers and feeder circuits, leading to more investment in other devices such as transformers. Switched capacitor panel How much can I save by installing power capacitors? ο Reduce utility power bills: Electricity bill contains kW and kVAr of power plant. While reactive power doesn’t register on kW demand or kW hour meters, the utility’s transmission and distribution system must be large enough to provide the total power. Utilities have various ways of passing along the expense of larger generators, transformers, cables, switches..etc. Capacitors will save money no matter how the utility bills on power. Utility charges according to the kW demand and add a surcharge or adjustment for power factor. The adjustment may be a multiplier applied to kW demand. If the power factor was 0.84, the utility ππ − ππππππ ∗ 0.9 πππ€ π’π‘ππππ‘π¦ ππππ = πππ‘π’ππ πππ€ππ ππππ‘ππ would require π.π π.ππ = π. ππ kW –normal demand or 7% increase in utility billing How much can I save by installing power capacitors? ο Improve system operating characteristics (voltage gain): Good PF provides “stiffer” voltage, typically a 1-2% voltage rise can be expected when PF is brought to ±0.95. Excessive voltage drop make your motors sluggish, and cause them to overheat. Low voltage also interferes with lighting, the proper application of motor controls and electrical and electronic instruments. An estimation of the voltage rise from the improved power factor with the installation of power capacitors can be made using the following: % π£πππ‘πππ πππ π = πππ΄π ππ πππππππ‘πππ × % π‘ππππ ππππππ πππππππππ π‘ππππ ππππππ − πππ΄ How much can I save by installing power capacitors? ο Improve system operating characteristics (reduce line losses): Improving PF at the load point shall relieve the system of transmitting reactive current. Less current shall mean lower losses in the distribution system of the facility since losses are proportional to the square of the current. Therefore, the fewer kW-hr needed to be purchased from the utility An estimation of the power losses can be made using the following: ππππππππ ππΉ % ππππ’ππ‘πππ ππ πππ€ππ πππ π ππ = 1 − ππππππ£ππ ππΉ 2 × 100 Types of power factor compensation: 1. Individual correction 2. Group compensation 3. Centralized compensation 4. Combined compensation 5. Automatic compensation ο Individual correction ο± Applied directly at the terminals of the load which demand reactive power. ο± Simple, capacitor and load can use the same protective devices against over current and are connected and disconnected simultaneously. ο± Advisable in the case of large equipment with constant load and continuous operation ο± Used with motors and lamps ο Individual correction ο± In case of direct connection (diagram 1 and 2), after the motor disconnection from the supply, the motor will continue to rotate (residual KE) and self excite with the reactive energy drawn from the capacitor and may turn into an asynchronous generator and might damage with over voltage ο± With this type of correction the network on the supply side of the load works with a high power factor, on the other hand, this solution is costly ο± Delta connected capacitors for 3rd harmonic cancellation ο Group correction ο± Improving locally the power factor of groups of loads having similar functioning characteristics by installing a dedicated capacitor bank. ο± Power factor is improved only by upstream the point where the capacitor bank is located. ο± The capacitor requires its own switching device. ο Centralized correction ο± System with permanently changing loads, several compensation units are usually installed centrally in the main distribution switchboard. ο± Switched ON and OFF by a controller depending on the respective reactive power demand. ο± Rated for the highest load, thus the total compensation power installed is lower than for the other types of compensation. However, the load on the distribution system is not reduced, and there must be enough room for all capacitor units in the main distribution panel. ο Combined PF Compensation ο± Derives from a compromise between the two solutions of individual and centralized power factor correction and it exploits the advantages they offer. ο± In this case, distributed compensation is used for high power electrical equipment and the centralized modality for the remaining part. ο± Combined solution is used in installations where large equipment only are frequently used, in such circumstances their power factor is corrected individually, whereas the PF of small equipment is corrected by the centralized modality. ο Automatic PF Compensation ο± Automatic correction is used in installations with variable absorption of reactive power. This system monitors the installation and automatically switches different capacitor banks. ο± This system required sensors, intelligent system comparing measured and desired operation to connect/disconnect capacitors, and electric power boards with switches and protective devices. Power factor correction: Common Problems 1- Harmonic and Resonance: • Capacitors connected to induction motors increase the chance of resonance between the power factor capacitors and the motor’s inductive reactance. • This issue makes the selection and filters design even more difficult. • For these reason, NEMA standards (NEMA MG 1-1993 section 14.43.4) have recommended not to use individual correction technique in presence of large number of induction motors. ππππ = 1 2π πΏπΆ Increasing C means that the square root increases so that the resonant frequency reduces and could approach the 50 Hz. Non linear loads introduce currents of harmonic ferq. 150-300 Hz so it even becomes nearer to the boundaries of resonance Power factor correction: Common Problems 2- Self Excitation: • Capacitors are connected in parallel to motors where both are fed/disconnected from the same source together. • Motors store energy in their rotating mass while capacitors stores energy in their electric field. • When motors are disconnected (with capacitors) Capacitor and motor magnetization from the power source, the motor will continue to rotate due to the energy stored in its inertia. At this point energy is being exchanged between the capacitor and the motor. • Current will pass in the circuit between the motor and capacitors and this current depends on the voltage difference between both. curve for self excitation Power factor correction: Common Problems ο assume motor terminal voltage is 460 v and that the capacitors used are 6 kVAr represented by the straight line shown. The intersection point between the capacitor load line and the magnetizing curve shows that when the motor is disconnected both the motor and capacitor will have the same voltage. ο Assume another capacitor is used of 14.4 kVAr. At 460 volts, motor draws reactive current of 8 A while capacitor draws 18 A. ο When both are disconnected from source, the motor terminal voltage will rise suddenly to 680 V. Leading to that the capacitor tries to discharge this “unbalanced” energy between capacitor and motor leading to rise in motor terminal voltage.