Addendum #1

advertisement
Feburary 19 , 2013
Attention:
Business and Financial Services Department
Finance Division
Telephone: 604-276-4218
Fax: 604-276-4162
To All Tenderers
Dear Bidders:
Re:
5121Q – Richmond Ice centre HVAC Upgrade 2014- Addendum #1
This Addendum includes items of clarification, forms part of the Contract Documents and shall be
read, interpreted and coordinated with all other parts. Please review and consider the following
information in the preparation of your quotation:
Delete
Attachments for Appendix A and Appendix B replace with the attached documents
Add
Part C-Requirements-1.5
f) Richmond Ice Centre- Electrical E-1
g) Richmond Ice Centre- Electrical E-2
h) Richmond Ice Centre- Electrical E-3
Documents are attached.
Yours truly,
Sharon Bentley, SCMP
Buyer 2
4158059
MECHANICAL SPECIFICATIONS
RICHMOND ICE CENTRE
14140 Triangle Rd
Richmond, BC
HVAC UPGRADE
For
City of
February 2014
File No. 1404
Consulting Mechanical Engineers
6468 Main Street, Vancouver, British Columbia V5W 2V4
Phone 604.736.6724 Facsimile 604.736.6726
RICHMOND ICE CENTRE
HVAC Upgrade
Project No. 1404
Division 15000
February 2014
TABLE of CONTENTS
Page: 1
SECTION
PAGE
SECTION
15010
15010
15011
15012
15013
15014
15015
15016
15017
15018
15019
15020
15023
15024
15025
15026
15029
15030
15031
15032
15035
15044
15045
15046
15047
15048
BASIC MECHANICAL REQUIREMENTS
Pages 1 - 7
GENERAL .............................................................................................................. 1
SCOPE................................................................................................................... 1
DISCREPANCIES, OMISSIONS, ETC. ................................................................. 1
EQUAL & ALTERNATE EQUIPMENT ................................................................... 1
CONTRACT PRICE BREAKDOWN....................................................................... 2
DRAWINGS ........................................................................................................... 2
DEFINITIONS ........................................................................................................ 3
GUARANTEE-WARRANTY ................................................................................... 3
MANDATORY SITE VISIT ..................................................................................... 4
SHUTTING DOWN OR CUTTING INTO EXISTING SERVICES .......................... 4
SEPARATE PRICES.............................................................................................. 4
CODES, PERMITS & PLAN APPROVAL .............................................................. 4
CHANGE ORDERS ............................................................................................... 5
CUTTING & PATCHING ........................................................................................ 5
RECORD DRAWINGS........................................................................................... 5
MATERIAL ............................................................................................................. 5
WORKMANSHIP.................................................................................................... 5
EXISTING EQUIPMENT ........................................................................................ 5
DISPOSITION OF SPARE PARTS........................................................................ 6
ELECTRICAL POWER CHARACTERISTICS & WIRING ..................................... 6
CLEAN UP ............................................................................................................. 6
PRIOR TESTS ....................................................................................................... 6
SUBSTANTIAL PERFORMANCE.......................................................................... 6
FINAL CONSTRUCTION REVIEW........................................................................ 6
PAINTING, FINISHING .......................................................................................... 7
SECTION
15050
15051
15060
15061
15070
15084
15094
15135
15160
15190
BASIC MECHANICAL MATERIALS & METHODS
Pages 1 - 6
DRAINS.................................................................................................................. 1
PIPING METHODS ................................................................................................ 1
PLUMBING PIPING .............................................................................................. 2
GAS PIPING ......................................................................................................... 3
FIRESTOPPING FOR MECHANICAL SYSTEMS ............................................... 3
PIPE EXPANSION, HANGERS & SUPPORTS .................................................... 5
FLOWING MEASUREMENT VALVES ................................................................. 6
CIRCULATING PUMPS ........................................................................................ 6
IDENTIFICATION & STENCILLING....................................................................... 6
SECTION
15200
15240
15243
15245
NOISE VIBRATION & SEISMIC CONTROL
Pages 1 - 4
VIBRATION ISOLATION FOR MECHANICAL EQUIPMENT................................ 1
VIBRATION ISOLATION & ASSOCIATED SEISMIC RESTRAINT....................... 3
SEISMIC RESTRAINTS......................................................................................... 3
SECTION
15250 MECHANICAL INSULATION
Pages 1
15261 PIPE INSULATION ................................................................................................ 1
SECTION
15550 HEAT GENERATION
Pages 1 - 3
15555 COMMERCIAL GAS FIRED BOILER .................................................................... 1
15575 BOILER/HOT WATER HEATER VENTING........................................................... 3
JM BEAN
& CO.
LTD
RICHMOND ICE CENTRE
HVAC Upgrade
Project No. 1404
Division 15000
February 2014
TABLE of CONTENTS
Page: 2
SECTION
15650 REFRIGERATION
Pages 1 - 2
15665 ROOF TOP HEATING & COOLING UNITS –GAS HEATING
[SEPARATE PRICE #1] ...................................................................................................... 1
SECTION
15920 CONTROLS
Pages 1
15921 GENERAL .............................................................................................................. 1
SECTION
15990
15991
15992
15996
15997
15998
TESTING ADJUSTING & BALANCING
Pages 1-6
TESTS.................................................................................................................... 1
BALANCING & TESTING ...................................................................................... 1
OPERATING INSTRUCTIONS .............................................................................. 2
EQUIPMENT MANUALS ....................................................................................... 2
COMMISSIONING ................................................................................................. 6
JM BEAN
& CO.
LTD
RICHMOND ICE CENTRE
HVAC Upgrade
Project No. 1404
Section 15010
BASIC MECHANICAL REQUIREMENTS
February 2014
Page: 1 15010 GENERAL
1.
This section shall be read in conjunction with the General Conditions and Supplementary General
Conditions of the Specifications.
2.
All work shall be performed by qualified tradesmen working for a reputable Contracting Company
experienced in this type of work and shall be strictly in accordance with the best commercial practice.
3.
Co-ordinate work with the Contractor's working schedule and co-operate to achieve the earliest
possible completion of the work.
15011 SCOPE
1.
Work covered by this Division is to provide complete systems as indicated on drawings and specified
herein.
2.
These Specifications cover information, work, equipment, accessories listed under the following
Division Sections:
15010
15050
15200
15250
15400
15550
15650
15750
15850
15880
15920
15990
3.
Basic Mechanical Requirements
Basic Mechanical Materials & Methods
Noise Vibration & Seismic Control
Mechanical Insulation
Plumbing
Heat Generation
Refrigeration
Heat Transfer
Air Handling
Air Distribution
Controls
Testing, Adjusting & Balancing
This work shall include the employment of an approved, independent Commissioning/Balancing
Firm(s) for commissioning and balancing of all air handling and heating systems installed under this
contract, to the Engineer's requirements. Reports of Commissioning and Balancing Firm(s) shall be
submitted to the Engineer prior to establishment of substantial completion. This work shall include the
preparation of equipment manuals as specified in Section 15990.
15012 DISCREPANCIES, OMISSIONS, ETC
1.
Bidders finding discrepancies in, or omissions from, Drawings, Specifications, or other documents, or
having any doubt as to the meaning or intent of any part thereof, shall at once notify the Engineer,
J.M. Bean & Co. Ltd., who will send explanatory written instructions to all bidders. Neither the
Engineer nor the Owner will be responsible for oral instructions.
2.
Addenda, corrections or drawing revisions issued during time of bidding shall be included in tender
and shall become part of Contract documents.
15013 EQUAL & ALTERNATE EQUIPMENT
1.
Equipment, other than that specified, of equal quality, will be allowed. Acceptable equipment shall be
that which has been reviewed by the Engineer five working days prior to the closing of bid depository
or tenders if bid depository is not used.
2.
Should the Mechanical Contractor propose to substitute equipment having different dimensions,
electrical wiring connections, or requiring connections or piping layout at variance with the Drawing, it
JM
BEAN & CO. LTD
RICHMOND ICE CENTRE
HVAC Upgrade
Project No. 1404
Section 15010
February 2014
BASIC MECHANICAL REQUIREMENTS
Page: 2 shall be the Mechanical Contractor's responsibility to submit a detailed drawing showing how
proposed substitute equipment is to be installed and connected in the available space. Any proposed
variations from Contract Drawings shall be specifically indicated.
3.
Equipment, other than that specified, which has been considered by the Engineer as "EQUAL" prior to
the closing of tenders may be substituted at the Mechanical Contractor's discretion provided
aforementioned conditions are met.
4.
Equipment, other than that specified, which has been considered by the Engineer as an
"ALTERNATE" prior to the closing of tenders, may be substituted by the Mechanical Contractor at the
discretion of the Engineer provided suitable adjustment of Contract Price is negotiated.
5.
The Mechanical Contractor shall be responsible for all expenses incurred in the work of other trades
made necessary because of substitution.
6.
Prior to placing orders submit to the Engineer a complete listing of sub-contractors, materials and
equipment to be used. This listing shall be submitted to the Engineer within 14 calendar days of
signing of Construction Contract.
7.
Where two or more items of equipment or materials of similar design are to be installed, they shall be
the products of one manufacturer.
15014 CONTRACT PRICE BREAKDOWN
1.
Within 48 hours after the Tender closing, provide the following price breakdown to the Engineer’s
office:
Contract Breakdown:
Cost
a.
b.
c.
d.
e.
f.
g.
h.
Heating
Refrigeration
Plumbing
Sheet Metal
Insulation
Controls
Balancing & Commissioning
Electrical
TOTAL MECHANICAL
2.
$_______
$_______
$_______
$_______
$_______
$_______
$_______
$_______
Name of Contractor
______________________________
______________________________
______________________________
______________________________
______________________________
______________________________
______________________________
______________________________
______________________________
Within 7 days of contract award, and prior to submitting shop drawings, provide a list of
manufacturers for all major equipment items for verification that proposed products are as specified
or have been reviewed as “Equal”.
15015 DRAWINGS
1.
The drawings, together with the specifications are intended to cover the complete installation of
systems to function as described. The omission of the express reference to any items of labour or
material necessary for the proper execution of the work, in accordance with present day practice shall
not relieve responsibility of supplying such additional labour or material.
2.
The drawings are mainly schematic and do not attempt to show all offsets. Make such offsets at no
additional cost to contract. Offset angles shall be as small as possible.
JM
BEAN & CO. LTD
RICHMOND ICE CENTRE
HVAC Upgrade
Project No. 1404
Section 15010
BASIC MECHANICAL REQUIREMENTS
February 2014
Page: 3 3.
4.
All figured dimensions shall have precedence over scale. Detail drawings shall have precedence over
small scale drawings; any difference between same shall be decided upon by the Engineer.
The Drawings and Specifications are the property of the Engineer and they shall be returned to him on
request.
5.
Submit shop drawings to the standard of the Mechanical Contractor's Association of B.C. for all
equipment to be installed on the job. Each shop drawing shall be submitted in the form of a "Master"
drawing 8-1/2" x 11", 8-1/2" x 14" or multiples thereof suitable for photocopying. Drawings shall be
submitted for review within 30 days of awarding of contract and bear contractors stamp indicating
project name, date and signature of a responsible person who has reviewed the drawings for the
contractor. By his review the contractor represents that he has determined and verified all field
measurements, field construction criteria, materials, catalogue numbers and similar data. In addition
he has checked and co-ordinated each shop drawing with the requirement of the work and contract
documents.
6.
This review by J.M. Bean & Co. Ltd., is for the sole purpose of ascertaining conformance with the
general design concept. This review shall not mean that J.M. Bean & Co. Ltd., approves the detail
design inherent in the shop drawings, responsibility for which shall remain with Contractor submitting
same, and such review shall not relieve the Contractor of his responsibility for errors or omissions in
the shop drawings or of his responsibility for meeting all requirements of the Contract Documents.
The Contractor is responsible for quantities and dimensions to be confirmed and correlated at the job
site, for information that pertains solely to fabrication processes or to techniques of construction and
installation and for co-ordination of the work of all sub-trades.
7.
Manufacture shall not commence until these shop drawings are reviewed. Shop drawings for fans
and pumps shall include an operating curve. See additional requirements in Clause 15245 SEISMIC
RESTRAINTS.
15016 DEFINITIONS
1.
The word "provide" shall mean "furnish and install, complete and ready for use".
2.
"Concealed" where used in connection with insulation and painting of piping, ducts and accessories,
shall mean that they are hidden from sight as in trenches, chases, furred spaces, pipe shafts or hung
ceilings: also, where they are not hidden from sight in the following locations: in partly excavated or
crawl spaces and in service spaces used solely for repairs and maintenance.
3.
"Exposed" where used in connection with insulation and painting of piping, ducts and accessories
shall mean that they are not "concealed" as defined above. Equipment rooms and fan rooms are to be
considered as "exposed" areas.
4.
"Piping" includes, in addition to pipe, fittings, valves, hangers, other accessories which comprise a
system.
15017 GUARANTEE-WARRANTY
1.
Correct promptly at own expense, defects or deficiencies in the work in accordance with the Warranty
requirements of the Contract.
2.
The Engineer shall be the judge as to whether the failure is due to defective workmanship, improper
usage or ordinary wear and tear.
3.
Make good any damage resulting from defective materials or workmanship.
4.
Rectify any deficiencies or omissions in respect to plans or Specifications which may appear during
the guarantee period even though work has been accepted as complete.
JM
BEAN & CO. LTD
RICHMOND ICE CENTRE
HVAC Upgrade
Project No. 1404
Section 15010
February 2014
BASIC MECHANICAL REQUIREMENTS
Page: 4 15018 MANDATORY SITE VISIT
1.
Before submitting prices, bidding contractors shall visit the site to familiarize themselves with working
conditions and existing constructions. Particular attention shall be paid to proposed methods of
construction and connection to existing system.
2.
Claims of lack of knowledge of existing conditions when bidding will not be acceptable as reason for
authorization of extra charges to Contract Price.
3.
During tendering period scheduled site visits will be arranged for bidders to meet with representatives
from the Owners and Engineers. Purpose of the visits will be:
a)
To advise contractors on critical aspects of construction scheduling.
b)
To demonstrate extent of demolition and routing of new piping distribution system.
c)
To familiarize contractors with working conditions, building will be occupied during
construction period.
15019 SHUTTING DOWN OR CUTTING INTO EXISTING SERVICES
1.
No active existing service pipe shall be shut down or cut into without prior arrangement with the
Owner or designated representative who will schedule the work to minimize inconvenience to Owner.
When a critical service must be shut down, this contractor shall be held responsible to meet
scheduled reactivation time. He shall provide overtime work, with no increase to the contract price if
directed by the General Contractor to do so, in order to meet agreed schedules set for service
reactivation.
15020 SEPARATE PRICES
1.
Provide separate prices for the under-mentioned items as optional extras to basic Contract price.
2.
Refer to General Specification for additional information.
3.
Separate Price #1:
Refer to Mechanical Specifications, drawings M-1 and M-2: Provide rooftop air conditioning units AC1 to AC-4 and associated electrical, gas, and controls connections.
15023 CODES, PERMITS & PLAN APPROVAL
1.
All work done under this section of the Specifications shall be in accordance with all National,
Municipal and Provincial Codes applicable.
2.
All mechanical equipment furnished shall meet all specific requirements of, and be in accordance
with, the current edition of the British Columbia Energy Efficiency Standards Regulation issued under
the British Columbia Energy Efficiency Act.
3.
Abide by all public ordinances, pay all fees, obtain all permits and give all necessary notices to
authorities having jurisdiction. The Contractor shall submit the required number of Drawings and
Specifications to all authorities having jurisdiction for approval purposes.
4.
Comply with the most stringent requirements of the B.C. Building Code and Provincial and Municipal
Regulations and By-Laws, specified standards, codes and this specification.
JM
BEAN & CO. LTD
RICHMOND ICE CENTRE
HVAC Upgrade
Project No. 1404
Section 15010
BASIC MECHANICAL REQUIREMENTS
February 2014
Page: 5 15024 CHANGE ORDERS
1.
Upon request for a price change for variations to the work specified in the contract documents, submit
to the Engineer a complete list of materials, labour, rentals, tax requirements, overhead and profit for
approval of the Owner prior to undertaking the work.
15025 CUTTING & PATCHING
1.
Provide all necessary cutting and patching required for this work.
15026 RECORD DRAWINGS
.1
Keep a record set of drawings showing any changes made to original layout of piping, ducts,
equipment rooms, etc. Record drawings shall be continuously updated, shall be available on site for
examination, and shall be turned over to the Engineer for Owner's use upon completion. The drawings
shall indicate the inverts and dimensioned locations of all services at the property line and where they
penetrate the building perimeter. Each drawing shall be stamped “PROJECT RECORD DRAWINGS,
CERTIFIED BY THE CONTRACTOR” the current “DATE” and signed by the Contractor.
As built Cad files will be provided as part of a Cash Allowance carried by the General Contractor.
15029 MATERIAL
1.
All materials and equipment used shall be new, of the quality specified, finished and complete in every
detail.
2.
Protect all materials and equipment from damage and weather. Store all pipe off the ground on racks
and provide a weather cover. Protect all factory finished surfaces by adequate covers or other
means. Prevent the entry of foreign objects into pumps, compressors, fans, etc., by sealing all
openings with strong covers.
3.
Components with electric motors or switchgear mounted as part of an assembly shall be stored within
a dry weatherproof enclosure unless the equipment has been designed for outside installation.
Protect all finned equipment from fin damage and clean and comb all fins, if required, before putting
the system into operation.
4.
15030 WORKMANSHIP
1.
The Engineer or his authorized representative shall have the right to reject any item that in his opinion
does not conform to an acceptable standard of quality, appearance, or performance. Replace or
rectify rejected material and/or workmanship to the approval of the Engineer and at no additional cost
to the Owner.
15031 EXISTING EQUIPMENT
1.
Any existing equipment (tagged by Owner’s representative) being removed and not required to be
relocated shall remain the property of the Owner. Remove them and turn them over to the Owner.
Provide receipt verifying disposition of such equipment.
JM
BEAN & CO. LTD
RICHMOND ICE CENTRE
HVAC Upgrade
Project No. 1404
Section 15010
February 2014
BASIC MECHANICAL REQUIREMENTS
Page: 6 15032 DISPOSITION OF SPARE PARTS
1.
Where equipment spare parts or additional maintenance items such as filter media in excess of first
application requirements are specified, they shall be boxed, tagged indicating contents and applicable
job and delivered to the Owner's maintenance headquarters. Upon delivery, a receipt in quadruplicate
shall be obtained from the Owner's personnel and copies of these receipts forwarded to the Engineer
and Owner's Maintenance Engineer. Receipts shall be distributed to aforementioned people prior to
contract substantial completion date.
15035 ELECTRICAL POWER CHARACTERISTICS & WIRING
1.
All low voltage and 120 volt control wiring shall be done by Mechanical contractor.
2.
All starting and disconnect switches unless otherwise stated in this Division will be provided under
Division 16. Any additional control relays or switches required and their wiring to ensure operation of
systems as specified shall be provided under Division 15.
3.
Unless indicated differently in equipment specification clauses or equipment schedules:
Motors ½ HP and larger shall be suitable for 208/3/60 power.
Motors ⅓ HP and smaller shall be suitable for 120/1/60 power.
15044 CLEAN UP
1.
Clean up all debris resulting from the work as it progresses. At the conclusion of the work, clean and
restore all material, equipment, and fixtures to their as new condition. Remove all gummed labels.
15045 PRIOR TESTS
1.
All work which will be covered or concealed shall be tested prior to covering. Notice of tests shall be
given to the Engineer 48 hours in advance arranged to conform to the construction schedule. Test
shall be to the approval of the Engineer.
15046 SUBSTANTIAL PERFORMANCE
1.
Prior to calling for a substantial performance review, the following minimum requirements must be
satisfied:
-
All air handling systems must be operational with all controls and safety devices installed.
-
Heating systems and controls must be operational.
‐
A draft copy of the balancing report must be submitted for review to confirm system operation
is substantially as designed.
15047 FINAL CONSTRUCTION REVIEW
1.
Notify Engineer in writing when final construction review of installation may be performed. In the event
that defects or deficiencies are found during this final review, they shall be corrected to the
satisfaction of the Engineer.
2.
Engineer shall be reimbursed for time and expenses involved in subsequent reviews resulting from
deficiencies noted during final construction review.
3.
Final review mentioned above will follow after substantial performance review and correction of
deficiencies noted at that time.
JM
BEAN & CO. LTD
RICHMOND ICE CENTRE
HVAC Upgrade
Project No. 1404
Section 15010
BASIC MECHANICAL REQUIREMENTS
February 2014
Page: 7 15048 PAINTING, FINISHING
1.
Painting shall include furnishing labour, materials, and all items required to prepare, paint and finish
surfaces of work specified herein or in any of the mechanical work sections.
2.
Painting shall be applied as per manufacturer's printed application directions, by workers experienced
in use of such paint. Colours shall be selected at time of painting or as previously approved. Leave
name plates on equipment clean and free of paint.
3.
Surface Preparation of Painting:
Treat galvanized surfaces with acetic acid, sal soda or other approved solution, wash with clear water.
Scrape, wire-brush the surfaces to remove mill scale, rust; clean with solvent to remove dirt, oil
grease; where solder flux has been used, clean with benzine. After installation and before final
painting of equipment and accessories which are factory primed, clean surfaces and touch up bared
or marred spots with same finish as primer.
4.
Extent of Painting to be Done:
Any marred or scratched surfaces shall be repainted or touched up to match the equipment suppliers
finish coat. If touch up painting will not restore the equipment to as new appearance the entire
surface area shall be repainted. The mechanical contractor is to arrange with the painting contractor
and pay all costs involved in the touch up or repainting of damaged factory finish painted items.
END of SECTION 15010
JM
BEAN & CO. LTD
RICHMOND ICE CENTRE
Section 15050
HVAC Upgrade
Project No. 1404
BASIC MECHANICAL MATERIALS & METHODS
February 2014
Page: 1
15051 DRAINS
1.
Pipe all discharge from relief valves, air vents, drip pans, overflows, system drains, water columns,
and major low points in the heating system to the nearest accessible drain. No drains or overflow
shall discharge onto floor in the building.
2.
Provide 18 mm drain valves as shown on the drawings and at all low points of piping systems.
Provide 40 mm valves for pipe cleaning. Provide hose end adaptors on all drain valves. Dahl piggyback stops of Fig. 2316 hose bibbs may be used on water systems operating at less than 93°C.
3.
Chained caps are required on all drain valves.
15060 PIPING METHODS
1.
Where pipes pierce floors, walls or ceilings that are fire rated assemblies or fire separations, the
space between the pipe sleeve or adjacent construction and the pipe shall be sealed with a fire stop
system conforming to Part 3 Sub-section 3.1.9 of the 2012 BC Building Code. Such systems shall be
labelled as meeting the ULC CAN4-S115M, "Standard Method of Fire Test of Firestop Systems"
available from Hilti (Canada) Limited, 3M Fire Protection Products, Nuco Inc. or approved equal. See
Section 15084.
2.
Floor, wall and ceiling plates shall be provided on all exposed piping passing through walls, floors,
ceilings, or partitions. Plates shall be steel with polished nickel finish and securely anchored to the
pipe.
3.
Provide lateral load resistance for mechanical equipment and pipes and their anchorage as described
in Sub-Section 4.1.8 of the 2012 BC Building Code.
4.
Provide all valves shown on the drawings and as necessary for the proper control of piping and
equipment. Unless otherwise shown or specified, all valves 12mm [½"] and smaller shall be globe
pattern and all valves 20mm [3/4"] and larger shall be gate valves. All valves 65mm [2-1/2"] and
smaller shall be brass, larger valves shall be iron body bronze mounted. At the contractor’s option,
ball valve models, as specified, may be substituted for gate valves for 20mm [3/4"] and 25mm [1"]
sizes on plumbing systems and for 20mm to 50mm [3/4" to 2"] sizes, inclusive, on heating systems.
5.
Provide dedicated ball valves for isolation on supply and return piping on each hydronic heating
element.
6.
Provide hose bibbs with brass caps and chain at all low points, for drainage.
7.
Provide Miljoco CDX9 series, Trerice SX9 series Solar Thermometer, or approved equal, where
indicated on drawings and as specified herein. Thermometers shall be industrial quality with 1%
accuracy and separable socket and shall be fully interchangeable with liquid-in-glass thermometers,
complying with industrial standard dimensions, minimum 89mm [3-1/2"] length, with extension neck
for insulation as required. Thermometers shall have easy to read LCD display with switch to display
Celsius or Fahrenheit degrees and an adjustable angle stem. Thermometer shall require no external
power, needing only 35 lux of illumination to operate.
8.
Provide liquid filled pressure gauges where indicated on drawings and as specified herein. Provide on
each side of each hot water circulating pump a pressure gauge with needle type isolation valve.
Gauge calibration shall be such that instrument indicates at approximately mid scale under normal
operating conditions. Gauges shall be 100mm [4.0"] diameter face as manufactured by Miljoco,
Trerice, or approved equal. Pressure gauges shall be calibrated in S.I. metric units, or have dual
metric/imperial calibration.
9.
Provide installation of temperature control system components where required in piping system.
JM
BEAN & CO. LTD
RICHMOND ICE CENTRE
Section 15050
HVAC Upgrade
Project No. 1404
BASIC MECHANICAL MATERIALS & METHODS
February 2014
Page: 2
10.
Insulating dielectric fittings shall be installed between dissimilar metals in systems. Brass adapters
and valves are not accepted as dielectric fittings.
15061 PLUMBING PIPING
1.
Water supply piping shall be hard copper type "L" in building, with solder joints. Copper water tubing
shall be certified by Warnock Hersey or Canadian Standards Association to ensure compliance with
the B.C. Plumbing Code which references ASTM B88-83A. Water supply piping in walls shall be
encased in standard weight flexible polyethylene pipe one size larger than copper tubing. All joints to
be wrapped with Polyken tape. The use of Victaulic copper connection system is not acceptable.
2.
All copper piping shall be thoroughly cleaned of all copper shreds before installation. Joints in copper
tubing shall be made with standard fittings with 95% tin and 5% antimony solder. Tubing shall be
cleaned with steel and non-corrosive paste flux.
3.
Roof flashings shall be aluminum, as per RCABC Standards, extending at least 305mm (12") from
roof surface. Flashing shall not be turned down inside pipe.
4.
Insulating dielectric unions and flange unions shall be installed when adapting between dissimilar
metallic pipe for domestic water supply piping, and domestic water storage tanks. Unions shall be
equal to those manufactured by Epco. Elsewhere, unions and adaptors for copper piping shall be
cast brass pressure fittings.
5.
All valves of each type shall be of the same manufacture and clearly marked as to the manufacturer,
valve catalogue number and working pressure. For domestic hot water service, materials used shall
be suitable for 90°C service. Drain valves shall be provided with cap and chain. All valves 65mm
(2-1/2") and smaller shall be at least 200 psi cold working pressure rating marked and approved equal
to the following:
Globe Valves
Angle Valves
Gate Valves
Check Valves
Ball Valves
Butterfly Valves
Crane 1703
Crane 17TF
Crane 1701
Crane 1707S
Crane F9222
Victaulic No. 608
Mueller
Locxend Model 89G
Jenkins 994AJ
Jenkins 108BJ
Jenkins 992AJ
Jenkins 997AJ
Jenkins 202J
Red-White 220A
Red-White 260
Red-White 281A
Red-White 237
Red-White 5049A
Red-White 918BESL
Kitz 03
Kitz 38
Kitz 28
Kitz 23
Kitz 59
Kitz 6122E
All valves 75mm (3") and larger shall be at least 200 psi cold working pressure rating marked and
approved equal to the following:
Globe Valves
Gate Valves
Check Valves
Check Valves
Sewage Valves
ButterflyValves
(Gear Operated)
Crane 351
Crane 461 or 460
Crane 373 or 372
Crane 383
Crane 383
Victaulic No. 608
Mueller
Locxend Model 89G
Jenkins 2342J
Jenkins 451J or 452J
Jenkins 588J or 587J
Jenkins 477LJ
Red-White 400A
Red-White 415A
Red-White 435A
Red-White 435A
OL & W
Red-White
918BESL
Kitz 76
Kitz 5
Kitz 78
Kitz 78
Drain and hose valves 20mm (3/4") and smaller shall be the following or approved equal:
Drain valves
Crane F9202/Jenkins 201J c/w ball & chain
Red - White 5046Kitz 68AC
13.
Expansion compensators shall be as noted on drawings, suitable for 1034 kPa (150 psi) working
pressure. Guiding and anchoring per EJMA recommendations and guidelines.
JM
BEAN & CO. LTD
RICHMOND ICE CENTRE
Section 15050
HVAC Upgrade
Project No. 1404
BASIC MECHANICAL MATERIALS & METHODS
February 2014
Page: 3
14.
Strainers 50mm (2") and smaller shall be Red & White Bronze Fig. No. 380E. Kitz 15
Larger strainers shall be Red & White Bronze
Fig. No. 381A.
Kitz 80
or Mueller 351M
15.
All potable water system components shall conform to NSF Standard 61.
15070 GAS PIPING
1.
Gas piping within buildings shall be ASTM Standard A53 or A 106 Welded and Seamless black steel
pipe. Fittings used shall be of malleable iron or steel to comply with ANSI/ ASME Standard B16.3 for
malleable iron fittings. All materials used and work done shall comply with the regulations of the BC
Gas Inspection Department and CAN/CGA B149.1-M91 and CAN/CGA B149.2-M91 Natural Gas and
Propane Installation Codes and applicable amendments.
15084 FIRESTOPPING FOR MECHANICAL SYSTEMS
1.
Subject to compliance with through penetration firestop systems listed in U.L.C Fire Resistance Directory
– Volume III or UL Products Certified for Canada (cUL) Directory, provide products of the following
manufacturers as identified below:
1.
Hilti (Canada) Corporation, Mississauga, Ontario
1-800-363-4458/www.ca.hilti.com
2.
3M Fire Protection Products
2.
A manufacturer's authorized representative shall be on-site during initial installation of firestop systems to
verify qualifications or train appropriate contractor personnel in proper selection and installation
procedures. An acceptable Installer is one who is certified, licensed, or otherwise qualified by the
firestopping manufacturer as having been provided the necessary training to install manufacturer’s
products per specified requirements.
3.
Firestop System installation must meet requirements of CAN4-S115-M or ULC S-115-M tested
assemblies that provide a fire rating as shown below.
For penetrations through a Fire Separation wall provide a firestop system with a "F" Rating as
determined by ULC or cUL as indicated in the table:
Fire Resistance Rating
of Separation
30 minutes
45 minutes
1 hour
1.5 hours
2 hours
3 hours
4 hours
Required ULC or cUL “F” Rating
of Firestopping Assembly
20 minutes
45 minutes
45 minutes
1 hour
1.5 hours
2 hours
3 hours
For combustible pipe penetrations through a Fire Separation provide a firestop system with a “F” Rating
as determined by ULC or cUL which is equal to the fire resistance rating of the construction being
penetrated.
For penetrations through a Fire Wall or horizontal Fire Separation provide a firestop system with a “FT”
Rating as determined by ULC or cUL which is equal to the fire resistance rating of the construction being
penetrated.
JM
BEAN & CO. LTD
RICHMOND ICE CENTRE
Section 15050
HVAC Upgrade
Project No. 1404
BASIC MECHANICAL MATERIALS & METHODS
February 2014
Page: 4
4.
Submit Product Data: Manufacturer’s specifications and technical data for each material including the
composition and limitations, documentation of ULC or cUL firestop systems to be used and
manufacturer's installation instructions to comply with Section 15015.
5.
For those firestop applications that exist for which no ULC or cUL tested system is available through a
manufacturer, a manufacturer's engineering judgment derived from similar ULC or cUL system designs
or other tests will be submitted to local authorities having jurisdiction for their review and approval prior to
installation. Engineer judgment drawings must follow requirements set forth by the International Firestop
Council (September 7, 1994).
6.
Coordinate location and proper selection of cast-in-place Firestop Devices with trade responsible for the
work. Ensure device is installed before placement of concrete. Responsible trade to provide adequate
spacing of field-run pipes to allow for installation of cast-in-place firestop devices without interferences.
7.
Inspection of through-penetration firestopping shall be performed by the Manufacturer’s Authorized
Representative in accordance with ASTM E 2174, “Standard Practice for On-Site Inspection of Installed
Fire Stops” or other recognized standard. Provide a letter to certification to the Engineer indicating all fire
stopping supplied and installed for the project meets Building Code requirements and has been installed
in accordance with the Manufacturer’s installation instructions.
8.
Avoid cutting or penetrating of existing firestop systems already installed by other trades. If unavoidable,
especially in renovations, remove existing material and provide new fire stopping system to complete the
installation in accordance with this specification.
9.
Install a warning card that is clearly visible adjacent to all large and medium openings that may be repenetrated. This card should contain the following information:
1.
2.
3.
4.
5.
Warning that the opening has being fire stop protected
Indicate the fire stop system used (ULC or cUL)
F rating or FT rating
Fire stop product(s) used
Contact phone number or HELP line
15090 PIPE SLEEVES
1.
Except where otherwise specified, construct sleeves of galvanized sheet steel with lock seam joints,
of the following minimum gauges:
a.
b.
c.
24 gauge for 75mm [3"] and smaller.
22 gauge for 100mm to 150mm [4" to 6"] inclusive.
20 gauge for sizes over 150mm [6"].
2.
Make sleeves of galvanized steel or wrought iron pipe when they are located in concrete beams or
concrete fireproofing; in outside walls, foundations, footings, waterproofed floors; in other locations
where sleeve is extended above finished floor or where space between pipe and sleeve is to be lead
caulked.
3.
Extra heavy cast-iron soil pipe may be used in place of steel or wrought iron pipe for sleeves in walls
below grade.
4.
Where pipe motion due to expansion and contraction will occur, make sleeves of sufficient diameter to
permit free movement of pipe. Where pipes are insulated, make sleeves of sufficient diameter to pass
pipe insulation. Check floor and wall construction and finishes to determine the proper length of
sleeves for various locations; make actual length to suit following:
JM
BEAN & CO. LTD
RICHMOND ICE CENTRE
Section 15050
HVAC Upgrade
Project No. 1404
BASIC MECHANICAL MATERIALS & METHODS
February 2014
Page: 5
a.
b.
c.
d.
Terminate sleeves flush with walls, partitions, ceilings.
In areas where pipes are concealed as in chases, terminate sleeves flush with floor.
In finished areas where pipes are exposed, extend sleeves 6mm [1/4"] above finished floor,
except in kitchens, toilets, equipment rooms, other areas where water may accumulate on
floor, extend 38m [1-1/2"].
In sprinklered areas, extend sleeves as recommended in NFPA Pamphlet 13.
15094 PIPE EXPANSION, HANGERS & SUPPORTS
1.
Equipment, duct and piping shall be supported and restrained in accordance with Clause 15245. All
piping shall be so installed that it will in no way be strained or distorted by expansion and contraction.
Anchors shall be provided wherever necessary to protect equipment and control direction of pipe
movement. Pipe guides shall be provided at each side of each expansion joint.
2.
Provide all hangers, anchors, brackets and miscellaneous supports as required for the installation of
ductwork, piping and equipment. Supports, hangers, and brackets shall be attached to walls, ceilings
and floors in an approved substantial manner. All hanger supports for equipment shall be set in
structural members of the building to the Architect's approval. Pipe hangers shall be Grinnell Fig. 260,
adjustable wrought clevis, Fig. 101 adjustable swivel ring, solid ring Type or Fig. 237 steel band and
bolt. Perforated band iron, wire or chain hangers will not be approved. All hangers for copper pipe
shall be copper, copper clad or use plastic-tape wrapped pipe at hanger. Inserts shall be Grinnell Fig.
152.
3.
All hangers shall be capable of vertical adjustment after pipe is erected. Pipe shall not be hung from
other pipe.
4.
All insulated pipe 50mm [2"] and larger shall be fitted with insulation protection saddles, or insulation
protection shields.
5.
On all pipe with vapour-seal insulation the hanger shall fit outside the insulation. Provide Fig. 167
insulation protection shields on all insulated cold piping such as domestic water, chilled water and rain
water leaders so that hanger rod and pipe hanger will not penetrate insulation vapour barrier.
6.
Pipe hanger rods shall be continuously threaded, cadmium plated and shall be sized and spaced as
follows:
MAXIMUM HANGER SPACING
PIPE DIA
(inches)
HANGER
ROD DIA.
(inches)
STEEL
SCH.40
(feet)
COPPER
DWV,L,K
(feet)
1/2"
1/4"
6'
6'
4'
3/4" & 1"
1/4"
8'
6'
4'
1¼"
3/8"
10'
6'
4'
1½"
3/8"
10'
6'
10'
4'
2"
3/8"
10'
10'
10'
4'
2½", 3 & 4"
1/2"
10'
10'
10'
8'
4'
5", 6" & 8"
5/8"
10'
10'
10'
8'
4'
JM
CAST.I
STD.
(feet)
BEAN & CO. LTD
GLASS
(feet)
PLASTIC
DWV,SCH.40
(feet)
RICHMOND ICE CENTRE
Section 15050
HVAC Upgrade
Project No. 1404
BASIC MECHANICAL MATERIALS & METHODS
February 2014
Page: 6
15135 FLOW MEASUREMENT VALVES
1.
Provide Bell & Gossett lead-free Circuit Setter Plus, or approved equal, conforming to NSF Standard
61. All valves to be of Lead-Free Brass** body/SS ball construction with glass and carbon filled TFE
seat rings. Valves to have differential pressure read-out ports across valve seat area. Read-out ports
to be fitted with internal EPT inserts/check valves. Valve bodies to have 1/4” NPT tapped drain/purge
port. Valves to have memory stop feature to allow valve to be closed for service and then reopened to
set point without disturbing balance position. All valves to have calibrated nameplates to assure
specific valve settings. Valves shall be designed for positive shut-off. Valves shall be rated for 2,069
kPa [400 psig] at 121°C [250ºF].
15160 CIRCULATING PUMPS
1.
Provide circulating pumps where indicated, designed for quiet operation and guaranteed by the
manufacturer for the intended operation. All pumps shall be lead-free bronze or stainless construction
conforming to NSF Standard 61.
2.
Refer to Section 15200 for vibration isolation and seismic restraint requirements.
15190 IDENTIFICATION & STENCILLING
1.
Provide means of identifying the contents of pipes as follows:
Use basic colour schemes for identity band on covered and as finish painting of uncovered pipes as
listed in the following schedule. Paint identifying band of colour listed in Schedule near each valve
and fitting, on both sides of pipes passing through walls and on long pipe runs (approximately every
9.1m [30'] or closer when directed). Stencil on pipe identity band, near each valve, name of pipe
contents in an abbreviated form as listed in the Schedule under the heading "Legend". Stencil the
size of pipe adjacent to each Legend. Paint arrow next to Legend indicating direction of flow in the
pipe. Place stencil legend in location so that it can be easily read from the floor. The size of the
stencil letters shall vary with the size of pipe, as per ASA.A.13 Standard.
2.
Schedule of Piping Systems Identification:
SERVICE
BASIC COLOUR
Water, Cold
Water, Domestic Hot
Gas
3.
Dark Green
Yellow
Yellow
LEGEND
C.W.
D.H.W.
Gas
Equipment Identification:
Identify each equipment unit, valve, controls, dampers, temperature and pressure tubing for controls
dampers, temperature and pressure tubing for controls and other parts of mechanical systems by
means of rectangular "Lamicoid" tags with brass "S" hooks, chains or adhesive.
4.
Commercially available pipe markers and direction arrows, Brady B-946 film material or approved
equal, will be permitted at the contractor's option. Labels shall be suitable for continuous operating
temperatures between -40°C and 120°C [104°F and 248°F] and shall be applied in accordance with
manufacturer's recommendations by this contractor. Labels shall have 50mm [2"] high letters for pipe
sizes, 75mm [3"] and larger and 20mm [3/4"] high letters for smaller sizes.
Locate nameplates, so that they are easily read. Do not insulate or paint over plates.
END of SECTION 15050
JM
BEAN & CO. LTD
RICHMOND ICE CENTRE
Mechanical Upgrade
Project No. 1404
Section 15200
February 2014
NOISE VIBRATION & SEISMIC CONTROL
Page: 1
15240 VIBRATION ISOLATION FOR MECHANICAL EQUIPMENT
1.
GENERAL
1.1
1.2
Related Work
1.
This section of the Specification forms part of the Contract Documents and is to
be read, interpreted and coordinated with all other parts.
2.
Seismic restraint of vibration isolated equipment is covered in Clause 15243 of
this Section.
3.
Seismic restraint of pipes, ducts, and other non-vibration-isolated equipment is
covered in Clause 15245 of this Section.
Shop Drawings, Qualifications and Submittals
1.
All equipment shall be of a type tested in an independent testing laboratory, or
certified by a registered professional engineer, demonstrating that the equipment,
including attachment details, meets the requirements of this section. Submit
such tests or certification on request.
2.
Obtain all relevant equipment information and provide shop and placement
drawings for all vibration isolation elements, steel bases, concrete inertia base
frames and seismic restraining devices for review, before materials are ordered.
Shop drawings are to include ALL of the following information:
Projected static deflection of each vibration isolator under installed conditions.
Specified static deflection for each vibration isolator from Table 1.
Load/deflection curves for all elastomeric elements.
Attachment details to equipment and structure.
Location and height of centre of gravity for each machine.
Shop drawings not including this information will be rejected without review.
1.3
3.
Provide attachment to both the equipment and structure meeting the specified
forces involved. Attachment details to the structure to be reviewed by the
structural consultant for the project.
4.
Provide a written warranty guaranteeing the work of this section from any defects
from the use of the improper of defective materials, or by reason of poor
workmanship, for a period of one (1) year from the date of acceptance of the
work. Make good all such defects which impair the function of the work of this
section to the Consultant’s approval and satisfaction, at no expense to the
Owner.
1.
Where imperial units have been indicated in brackets () following the
requirements in SI units, the conversion is approximate and provided for
convenience. The SI units shall govern.
Scope
JM BEAN
& CO.
LTD
RICHMOND ICE CENTRE
Mechanical Upgrade
Project No. 1404
2.
February 2014
NOISE VIBRATION & SEISMIC CONTROL
Page: 2
Provide seismic restraint for all vibration isolated equipment according to the
applicable sections of the B.C. Building Code and other requirements of the
project specification.
2.0
PRODUCTS
2.1
Isolators - General
2.5
Section 15200
1.
Supply all of the vibration isolation equipment by one approved supplier with the
exception of isolators which are factory installed and are standard equipment
with the machinery.
2.
Select isolators at the supplier's optimum recommended loading, and do not load
beyond the limit specified in the manufacturer's literature.
3.
Select isolators for motor driven fans of less than 0.35 kW for a minimum static
deflection of 3 mm.
4.
Provide steel spring isolators for deflections of 12mm and over.
5.
Provide neoprene isolators for deflections 6 mm and under.
6.
Provide either neoprene of steel spring isolators for deflections between 6mm
and 12mm.
7.
Provide adjustable limit stops for spring isolation mounts on equipment with
operating weights substantially different from the installed weights, such as
cooling towers, etc.
Hanger Mounts
1.
Satisfy requirements of this section for steel spring or neoprene isolators.
2.
Provide housings which incorporate a minimum 6 mm thick sound pad sized for a
minimum static deflection of 1 mm.
Provide hangers capable of a 10o misalignment (+10o) without binding.
3.
EXECUTION
3.1
Installation
1.
Execute the work in accordance with the specification and, where applicable, in
accordance with the manufacturer's instructions and only by workers experienced
in this type of work.
2.
Provide a minimum clearance of 50 mm to other structures, piping, equipment,
etc. for all equipment mounted on vibration isolators.
3.
Before bolting isolators to the structure, start equipment and balance the systems
so that the isolators can be adjusted to the correct operating position before
installing (seismically rated) drilled inserts.
4.
After installation and adjustment of isolators, verify deflection under load to
ensure loading is within specified range and isolation is being obtained.
JM BEAN
& CO.
LTD
RICHMOND ICE CENTRE
Mechanical Upgrade
Project No. 1404
5.
Section 15200
February 2014
NOISE VIBRATION & SEISMIC CONTROL
Page: 3
Install flexible duct connections so that duct size is not reduced by the deflection
of the flexible connector.
15243 VIBRATION ISOLATION & ASSOCIATED SEISMIC RESTRAINT
1.
Provide seismic restraint for vibration isolated items as indicated or as specified herein.
2.
Design shall be by manufacturer specializing in vibration isolation materials and devices. Seismic
restraints shall be located as close as possible to the isolators or incorporated in the isolator.
Isolated, suspended equipment shall be restrained by slack cable. Restraints shall withstand
loads imposed by a 2 g earthquake acceleration of the isolated equipment. Shop drawings shall
demonstrate compliance with the Code and bear the seal of a Professional Engineer.
15245 SEISMIC RESTRAINTS
1.
Provide seismic restraint systems, complying with 2012 BC Building Code section 4.1.8, for nonstructural components and equipment, including ductwork, piping, floor-mounted equipment,
suspended equipment (terminal boxes, ceiling cabinet fans, fan coils, etc.).
2.
Where slack cable is used as seismic restraints for suspended equipment with vibration isolators,
provide sufficient slack to avoid short circuiting.
3.
All unbraced suspended piping and equipment shall be installed with a minimum 152mm [6”]
clearance to vertical ceiling hanger wires.
4.
The spacing of transverse and longitudinal bracings for piping shall be designed to meet the
requirements of 2012 BC Building Code section 4.1.8.
5.
Seismic restraints for piping shall be designed and installed in accordance to 2012 BC Building
Code. Shop drawings must be sealed by a B.C. registered Professional Engineer and include the
following:
●
Seismic data for the building site.
●
Seismic restraints (e.g. rod size, restraint type, size and spacing, etc.) for various
sizes of duct and pipe in tabulated format.
6.
Provide seismic restraints for equipment as manufactured by Mason Industries Inc. or approved
equal. Shop drawings must clearly indicate recommended method of installation and points of
attachment of hangers and supports to provide the necessary seismic restraint and be sealed by
a B.C. Registered Professional Engineer. Shop drawings shall include statements detailing:
●
●
●
●
●
Operating weight from equipment shop drawing.
Zonal velocity ratio for the building site.
Calculated lateral force value Vp.
Number of foundation bolts required and shear force on bolts.
Tension force on anchorages from sum of moments for overturning.
The vibration isolation/seismic restraint vendor shall provide all seismic restraint related hardware for
fastening equipment, from point of attachment to equipment through to and including attachment
to structure.
Note: vibration isolation/seismic restraint of the internal components of equipment are responsibilities of
equipment manufacturer.
7.
Use seismic data for Richmond, B.C. from the 2012 BC Building Code.
8.
Provide the services of the Professional Engineer(s) who designed the restraint systems for
JM BEAN
& CO.
LTD
RICHMOND ICE CENTRE
Mechanical Upgrade
Project No. 1404
Section 15200
February 2014
NOISE VIBRATION & SEISMIC CONTROL
Page: 4
"Field Review" of the installed components, and submit the following to the Engineer:
-
Assurance commitment letter, signed and sealed; provided at the commencement of the
project.
-
Signed and sealed shop drawings of seismic restraints for equipment, piping and
ductwork as described in Paragraphs 9 and 10; provided prior to installation.
-
Typewritten inspection reports; provided during the construction period.
-
Schedule C-B, signed and sealed; provided after performing “Field Review”.
END of SECTION 15200
JM BEAN
& CO.
LTD
RICHMOND ICE CENTRE
HVAC Upgrade
Project No. 1404
Section 15250
February 2014
MECHANICAL INSULATION
Page: 1
15261 PIPE INSULATION
1.
The B.C. Insulation Contractors Association Standards Manual for mechanical insulation, latest
edition together with authorized additions and amendments shall be used as a reference standard and
shall form part of the Specification. Provide pipe insulation on the following:
-
All new piping under this contract
2.
Provide and apply in accordance with BCICA Specification 1501 Piping, as hereinafter specified
and/or modified a heavy density pre-formed, mineral fibre pipe insulation suitable for a temperature
range of 0°C. to +455°C [32°F to +850°F] for hot water piping including domestic hot water and hot
water recirculation. For piping sized 50mm [2"] and larger, include insulation on valve bodies,
strainers, and flanges in accordance with Specification 1501H. Abrasions and cuts in insulation shall
be sealed with vapour-proof mastic. Finish exposed raw pipe insulation bevels and ends with
finishing jacket or Robson’s Mastic.
3.
In concealed areas, a jacket equal to Manville Micro-Lok c/w APT 2000 jacket, Manson
APT/Fibreglass ASJ self sealing edged will be acceptable. In the equipment rooms, basements and
elsewhere where covering is exposed in finished areas, finish with Alpha Maritex #3451-RW
pre-pasted, pre-sized glass fibre jacket or U.L. listed Flamex FR Canvas, Thermo canvas, or
Approved Equal jacket, in accordance with manufacturer's specification for installation. Jacket shall be
neatly pasted in place with an approved insulation adhesive. Approved preformed PVC fitting covers
secured in placed with staples and colour matched pressure sensitive tape may also be used.
Otherwise, fittings and elbows shall be neatly rounded and given a skim coat of finishing cement and
finished with the canvas jacket to match.
4.
Insulation thickness shall be as selected from the following table for the appropriate pipes sizes and
operating temperatures. Boiler operating temperature shall be assumed as 93°C [200°F], domestic
hot and cold water piping shall be assumed as 52°C and 7°C [125°F and 45°F] respectively.
5.
For exposed and concealed cold pumps, meters, couplings, and cold pipe surfaces, where insulation
is not otherwise specified, apply No Sweat-FX as per Robson Thermal Manufacturing Ltd.’s
recommendations to prevent condensation.
6.
For exposed and hot pumps, meters, couplings, and hot pipe surfaces over 60°C (140°F) and where
insulation is not otherwise specified, apply ThermaLite as per manufacturer’s recommendations to
prevent skin burns.
7.
Pipe insulation adhesives and coatings shall be non-toxic as defined by W.C.B. Regulations.
Imperial Minimum Pipe Insulation Thickness (in.)
Fluid Design
Operating
Temperature
Range °F
Insulation Conductivity
Nominal Pipe Diameter (in.)
Conductivity
Range Btuin./hr.ft.3 °F
Mean Rating
Temperature
°F
1" and
less
1½"
to 2"
2½"
to 4
0.25 - 0.29
125
1.5
1.5
1.5
ALL Systems
141 - 200
END of SECTION 15250
JM
BEAN & CO. LTD
RICHMOND ICE CENTRE
HVAC Upgrade
Project No. 1404
Section 15550
HEAT GENERATION
February 2014
Page: 1
15555 COMMERCIAL GAS FIRED BOILER
1. The work to be performed consists of providing all labor, equipment, materials, etc. to furnish and install
new factory assembled, hot water boilers/heaters as described in the specifications herein. All of the
contractor's work shall be performed in a workmanlike manner, by experienced workmen previously engaged
in boiler plant construction and shall be under the supervision of a qualified installation supervisor. Install
equipment in strict compliance with manufacturer's installation instructions. Maintain manufacturer's
recommended clearances around sides and over top of equipment. Install components that were removed
from equipment for shipping purposes. Install components that were furnished loose with equipment for field
installation.
2. Provide 2 [two] gas fired boilers as manufactured by Laars or approved equal. Boilers shall be model
NeoTherm NTV500 SS water heater c/w pump, rated at the 500MBH input and 483MBH output
[96.7% Thermal Efficiency].
3. The boiler shall modulate 20-100% of full fire. The units shall be design-certified to comply with the
current edition of the Harmonized ANSI Z21.13 / CSA 4.9 Standard for GasFired Low Pressure Steam
and Hot Water Boilers. The unit(s) shall be designed and constructed in accordance with the ASME
Boiler & Pressure Vessel Code, Section IV requirements for 160 psi (1103 kPa) maximum working
pressure, and shall bear the ASME "H" Stamp and be listed by the National Board. The unit(s) shall
be constructed to comply with the efficiency requirements of the latest edition of ASHRAE Standard
90.1.
4. The boiler shall be equipped with an ASME certified pressure relief valve set at 125psi (861 kPa).
Provide manual reset low water-cut off. Provide neutralization tank and limestone rocks as required and
shown on drawings.
5. The boiler shall be listed with AHRI (Air Conditioning, Heating and Refrigeration Institute). The boiler
shall have a minimum thermal efficiency of 95%, and a minimum combustion efficiency of 95%.
6. The water tube heat exchanger shall be stainless steel, rated for 160 psi (1103 kPa) working
pressure. The heat exchanger shall be a low water volume design, welded construction, with no
gaskets, o-rings or bolts in the header. Heat exchanger shall be accessible for visual inspection and
cleaning of all internal surfaces. The boiler shall be fully condensing design with built-in condensate
drain and trap. The heat exchanger shall have a limited twelve-year warranty.
7. Each boiler shall be fully test fired, (with water, gas, and venting connected), and all safety
components tested, at the factory. The boiler shall be sealed combustion, and removal of jacket
panels shall not affect the combustion seal. The boiler jacket shall be a unitized shell finished with
acrylic thermo-set paint baked at not less than 325°F (163°C). The frame shall be constructed of
galvanized steel for strength and protection. Chamber shall include a sight glass for viewing flame.
Boiler shall be certified for zero clearance to combustible surfaces.
8. All water, gas, vent and air connections shall be on the top of the boiler, and the top jacket panels
shall be split, such that they are removable without disconnecting the water, gas, vent or air pipes.
9. The boiler shall be shipped with a pump and a conduit. The wiring and terminals shall be wired to the
pump. The boiler shall have a flanged inlet water connection that allows the pump to be connected
directly to the top of the boiler in the field. The pump shall be capable of serving the boiler's heat
exchanger and 30 feet of piping that is the same size as the boiler's water connections, with a normal
number of pipe fittings.
10. Boiler shall operate on 4-13" w.c. gas pressure. The boiler shall use a premix burner with a stainless
steel woven metal fiber wrap, and a negative pressure gas valve to burn cleanly, with NOx emissions
not exceeding 10ppm. The boiler shall meet the emissions requirements of SCAQMD 2012. The
JM
BEAN & CO. LTD
RICHMOND ICE CENTRE
HVAC Upgrade
Project No. 1404
Section 15550
HEAT GENERATION
February 2014
Page: 2
boiler shall be designed for vertical or horizontal Category IV venting, up to 100 equivalent feet with
4" diameter. Combustion air shall be ducted directly to the boiler using single wall Aluminum pipe.
Flue vent shall be stainless steel AL29-4C.
11. Unit shall be 120VAC, single phase, less than 6 Amps (including mounted pump) for connection to a 15A
breaker. The control circuit shall be 24VAC.
12. The boiler control shall be an integrated electronic PID temperature and ignition control with LCD and
touchpad and shall control the boiler operation and firing rate. The control shall have three menu
structures for user mode, set-up mode, and diagnostic model. The boiler display shall be visible without
the removal of any jacket panels or control panels. When a display or control is field-replaced, the device
shall have the ability to read parameter setpoints from the original set-up, so the system does not have to
be re-programmed.
13. The control shall have the ability to control the boiler pump, system pump, and indirect domestic water
pump, each with delay features. The control shall be able to cascade and lead-lag with other NeoTherm
controllers, without additional system controllers. An optional display that is full-color, high definition LCD
with touch-screen shall be available, to allow for additional communication ports.
14. The control shall have the ability to accept a 4-20mA or 0-10VDC input connection from an external
control or building automation system, to modulate the flame. The control shall have dry alarm contacts
for ignition failure. The control shall monitor flue gas temperature and shall stop the boiler from firing if
temperature is excessive. The control shall have a display button that allows a user to choose one of six
menus, including: Login; Display Setup; Quick Start; Advanced Setup; Test; Diagnostics. The display
button shall be active at all times, regardless of what menu the control is showing. Login shall allow an
installer to adjust password-protected parameters. A Display Setup menu shall allow the user to adjust the
LCD contrast, and to customize the display’s homescreen. The user shall be able to choose five of the
following parameters to display on the homescreen – system setpoint, operating temperature, outlet
temperature, outlet temperature, inlet temperature, outdoor temperature, boiler temperature rise (delta T),
lead-lag operating temperature, lead-lag system setpoint, fan speed, flame signal, firing rate, domestic
water temperature, stack temperature, and 4-20mA input level. The homescreen shall also indicate the
boiler name, what firing state the boiler is in, if there is a demand on the boiler, if the system is in
password-level status, and shall show any holds, alerts, or lockouts that are present. The homescreen
shall be accessible at any time by pressing a homescreen button on the display.
15. The Advanced Setup menu shall give the installer access to all adjustable parameters, for more complex
installations, including; all lead-lag set up parameters, boiler high limit, boiler temperature setpoint and
on/off differentials, domestic water temperature setpoint and on/off differentials, domestic water priority
time, boiler stack temperature limit, pump delay and exercise values for all pumps controlled, PID
parameters, anti-shortcycle feature adjustment, and °F or °C display.
16. The control shall have a Test menu that allows the user to force the boiler into minimum or maximum firing
rate for 10 minutes, for set-up purposes. The test menu shall also allow the burner to be turned on or off,
and the pumps to be set to on or auto, for testing purposes. The control shall show a count-down timer,
enabling the user to see how much time is left for the test segment.
17. A Diagnostics menu shall allow the user to see analog inputs, digital inputs, and the history of alerts and
lockouts. Analog inputs shall include – outlet temperature, inlet temperature, temperature rise (delta T),
domestic water temperature, stack temperature, outdoor temperature, fan speed, flame signal, firing rate,
4-20mA input level, and system sensor temperature. Digital inputs shall include – main valve state, alarm
status, demand status, safety chain status, and interlock status. The control shall display information
about holds, alerts, and errors in both text form, and with codes numbers for further analysis.
JM
BEAN & CO. LTD
RICHMOND ICE CENTRE
HVAC Upgrade
Project No. 1404
Section 15550
HEAT GENERATION
February 2014
Page: 3
18. Boilers shall have:• Built-in condensate trap • Vent temperature cutoff • ASME “H” stamp • Water flow
switch • Temperature and pressure gauge • Drain valve • Direct spark ignition • On/Off toggle switch •
Manual reset high limit • Burner site glass • Flue gas temperature cutoff • Zero clearance to combustible
surfaces • 12-year limited warranty
19. Start and adjust unit to deliver 145°F supply to system and perform required tests. Start up shall be carried
out by factory authorized representative. Provide copy of start up report indicating all readings taken.
20. Instruct assigned personnel to operate and service equipment. Provide three copies of manufacturer's
instruction manual for operating and maintaining unit and its integral equipment.
21. Provide full sized gas vent, complete with roof jack, storm collar, bird-proof top and other accessories as
required.
22. Refer to Section 15200 for seismic restraint requirements.
15575 BOILER/HOT WATER HEATER VENTING
1.
The boiler shall operate under a positive pressure condition and shall be connected with a Saf-T
CI double wall vent system, certified to ULS636, with AL29-4C inner conduit rated to +/- 3 in. w.g.
pressure rating, or Approved Equal. Provide inlet and outlet caps as shown on drawings. The
location of the inlet and outlet terminals and the maximum length of venting and fittings shall be in
strict accordance with the manufacturer’s installation instructions. Combustion air intake venting
shall be single wall aluminium pipe. Provide screened intake.
2.
Refer to Section 15200 for seismic restraint requirements.
END OF SECTION 15550
JM
BEAN & CO. LTD
RICHMOND ICE CENTRE
HVAC Upgrade
Project No. 1404
Section 15650
REFRIGERATION
February 2014
Page: 1
15665 ROOF TOP HEATING & COOLING UNITS - GAS HEATING
[SEPARATE PRICE #1]
1.
Provide 4 replacement Lennox, packaged air conditioning units. Units shall be LG Series R-410A
High Efficiency models with capacities as scheduled incorporating direct expansion cooling and gas
heating, with accessories as specified herein. The equipment shall be CSA/CGA approved and
shipped pre-charged, piped and wired internally ready for field connections. Unit shall be complete
with PVC coated condenser coil guards, economizer section with modulating damper motor, outdoor
air and return air dampers, and pressure relief damper. Existing units are Lennox Model GCS16.
Provide an adaptor curb instead of the roof mounting frame so that the existing roof curb and duct
connections can be re-used as is.
2.
Heat exchanger shall be constructed of aluminised steel with a limited 10 year warranty. Inshot
burners shall be individually removable for servicing. Gas controls to have intermittent spark ignition,
electronic flame safety, automatic dual stage gas valves, manual shut off, pressure regulator, induced
draft fan, air proving switch, and manual reset flame roll out switch and fan limit switches and to
protect heating system from abnormal operating temperatures. Unit shall have 2 stages of heating.
3.
Refrigeration circuit shall be factory sealed with full operating charges of oil and R-410A refrigerant
and shall be complete with liquid line strainer, suction and liquid line service gauge ports, manual
reset high pressure switch, low pressure switch, drier, freezestat and thermostatic expansion valve.
Controls shall include dual pressure switch, compressor relay and overload protection. Hermetic,
scroll type compressor shall be warranted for five years, suction cooled and equipped with suction
and liquid line valves, overload protection and effective slugging protection. Compressor shall be
equipped with crankcase heaters. The entire running gear shall be spring mounted within the sealed
unit and the entire compressor shall be mounted on rubber vibration isolators. Unit shall be capable of
low ambient operation down to 0°F (-18°C) and have 2 stages of cooling.
4.
Condenser fan shall be and axial flow type, with overload protection, and permanently lubricated
bearings. Supply air fan shall be belt drive with adjustable pulley, forward curved, centrifugal type.
Condenser and evaporator coils shall be aluminum fin on copper tube.
5.
Cabinet shall be hot dipped galvanized steel with baked on enamel finish with hinged access doors
and fibreglass insulation. All panels shall have seals and quarter turn latching handles to provide a
tight air and water seal. Provide an adaptor curb for weatherproof duct connection and entry into
conditioned area.
6.
Provide disposable 50mm (2") thick type pleated MERV 7 filters with the unit.
7.
The unit shall be complete with a factory wired solid state microprocessor based control board,
Integrated Modular Control (IMC) consisting of standard operating and safety controls for the heating
and mechanical cooling control systems as well as a terminal strip suitable for connection of low
voltage controls. The IMC unit controller shall display temperature readings from return air, supply air
and outside air sensors that are furnished as standard equipment. The IMC shall display detailed
diagnostic information and diagnostic codes to identify any problems. All codes shall be listed inside
control access panel for easy reference. Provide contacts for unit connection to existing DDC system.
8.
The unit shall have a fully modulating economiser section complete with outdoor air hood and
pressure relief dampers (and hood). The economiser controls shall use the add-on IMC control board
with the sensible control. Economizer shall be factory installed. The assembly shall include fully
modulating 0-100 percent motor and dampers, barometric relief, minimum position setting, preset
linkage, wiring harness with plug. The outdoor air damper shall return to a minimum position when
outdoor temperature or relative humidity is too high for proper cooling. An adjustable minimum
position damper switch shall position the outdoor air damper.
JM
BEAN & CO. LTD
RICHMOND ICE CENTRE
HVAC Upgrade
Project No. 1404
9.
Section 15650
REFRIGERATION
February 2014
Page: 2
10.
Assemble units on roof; provide duct connections and accessories as indicated. Provide control
wiring to the existing DDC System.
Manufacturer or authorized representative shall provide field starting service for the units. Startup air
conditioning units in accordance with manufacturer’s startup instructions. Test controls and
demonstrate compliance with requirements. Provide startup reports.
11.
Refer to Section 15200 for seismic restraint requirements.
END OF SECTION 15650
JM
BEAN & CO. LTD
RICHMOND ICE CENTRE
HVAC Upgrade
Project No. 1404
Section 15920
February 2014
CONTROLS
Page: 1
15921 GENERAL
1.
The Control System disconnect from existing equipment and reconnection to new shall be provided by
the ESC Automation but as an integral part of the Mechanical Sub-contract. All work shall be by
certified journeymen, electricians and registered electrical apprentices regularly employed by the
Control Contractor.
2.
Existing DDC Control system is Delta as installed by ESC Automation.
3.
The system shall be tested, completely calibrated and adjusted prior to final inspection by the
Engineer.
4.
All instrument calibrations and readouts shall include SI metric units, temperatures shall be in Celsius.
5.
Provide electronic copies of updated schematic control diagrams and maintenance manuals. Control
drawings shall incorporate a typed plain English "sequence" of operation for each system installed.
6.
Maintenance and repair of existing control components other than those specified for replacements
are excluded from the contract. All new and existing control components shall be calibrated and a
status report on condition of re-used existing components provided to Engineer and Owner.
7.
Refer to Separate Price #1 for AC-1 to AC-4 DDC system controls requirements.
END of SECTION 15920
JM BEAN
& CO.
LTD
RICHMOND ICE CENTRE
HVAC Upgrade
Project No. 1404
Section 15990
TESTING, ADJUSTING, AND BALANCING
February 2014
Page: 1 15991 TESTS
1.
At completion, provide all instruments and personnel and make tests of all equipment as required by
these Specifications to demonstrate that all are in perfect working order. Present to the Engineer a
typewritten report detailing methods used to obtain balance in air and heating systems and listing all
final instrument readings taken by the Contractor at the site.
2.
Tests on plumbing systems shall consist of pressure tests. All leaks shall be corrected by remaking
the joints. The system shall be retested until no leaks are present. Tests shall be as follows:
 Domestic water - Hydraulic, 1034 kPa [150 psig]. for 8 hours.
3.
Test hydrostatically, before painting or covering piping for all services except air to 1 1/2 times the
maximum working pressure, but in no case less than 345 kPa [50 psi.], for at least 4 consecutive
hours, during which time the pressure shall remain constant without pumping. Subject welded joints to
a hammer test while under hydrostatic pressure. Test piping which will be concealed in sections as
approved, in manner which will not leave any pipe or joint untested.
4.
If, upon testing, leaks develop or the installation fails to function properly, make all necessary
corrections and new tests until all defects or deficiencies have been remedied. Corrections necessary
for the proper functioning of the installation shall be made to the satisfaction of the Owner before final
acceptance of the system.
15992 BALANCING & TESTING
.1
General:
Balancing and adjusting of air handling and water systems shall be carried out by a firm such as MDT
Systems Ltd., Western Mechanical Services Ltd., or other approved by Consulting Mechanical
Engineer. A copy of the balancing report shall be sent to the Engineer for record purposes.
.2
Air Handling Systems:
All air handling systems shall be balanced for satisfactory performance. Balancing results shall be
tabulated and include the following:
-
Single line drawing with outlets numbered corresponding to outlet summary sheets.
Outlet summary sheets listing outlet number, outlet make, model, area factor, required
velocity/quantity, actual velocity/quantity.
Fan air volume.
Fan speed.
Fan motor current, and rated motor current.
Entering and leaving air temperatures for each heating coil.
-
Where required adjustment is beyond the range of the sheave supplied, the sheave replacement will
be treated as an extra cost to the balancing contract.
1.
Water Systems:
Water circulating systems shall be balanced by means of balancing fittings and tabulated results shall
include the following:


Differential head across all circulating pumps.
Flow and water supply temperature.
JM BEAN
& CO. LTD
RICHMOND ICE CENTRE
HVAC Upgrade
Project No. 1404
Section 15990
TESTING, ADJUSTING, AND BALANCING
February 2014
Page: 2 
Water temperature supplied to and returning from each system element [boilers, storage
tanks, heat exchangers].
15996 OPERATING INSTRUCTIONS
1)
During "substantial performance" review of the work the Mechanical Contractor, together with the
Engineer, Control Sub-contractor, and other Sub-contractors designated by the Engineer, shall
instruct the Owner's operating personnel in the proper operation and maintenance of all systems and
equipment installed under the contract.
2)
It shall be the Mechanical Contractor's responsibility to have the specified equipment manuals
prepared, previously approved by the Engineer, and ready for presentation to the Owner at this
meeting.
3)
Convene the meeting with the aforementioned parties at the time called for in the substantial
performance review. The arrangements shall include written notices to all the parties concerned.
Should the equipment manuals, or system installation not be complete and operable at the proper
time, he shall then convene the operating instruction meeting at a later date and pay any additional
costs including time and travelling expenses for the personnel involved which are attributable to the
delay.
15997 EQUIPMENT MANUALS
.1
Provide two hard covered, durable plastic bound, loose leaf equipment manuals with index page and
tabs.
.2
Equipment manuals shall contain the system description, manufacturer's descriptive literature,
installation instructions and maintenance recommendations relative to methods and frequency
requirements for lubrication, filter cleaning, belt adjustment and other items.
Specific
recommendations of the manufacturer relative to lubricants, adhesives, etc. will be required. Where
literature furnished covers several models of the equipment, all data except that pertaining to the
model installed shall be neatly "ruled" out.
.3
For each fan installed, provide performance data in "Curve" or multi rating table.
.4
For each plumbing fixture, floor and roof drain installed, provide manufacturer's "cut" of that item and
"cuts" of associated brass goods.
.5
Copies of extended guarantees and warranties for equipment items such as hot water tanks and heat
exchangers shall be included in a separate section of the manual.
.6
A draft copy of the system description shall be sent to the Engineer for review and a final copy sent for
record files.
.7
The Mechanical Contractor shall furnish sufficient copies of equipment manufacturer's literature to
meet the above requirements.
.8
Hard Copy Requirements:
Hard copies shall be placed in D-ring binders with clear overlay on front and spine with labels inserted
on front cover and spine. Labels shall include the following information:
Front cover label shall include the project name, project location, owner, mechanical consultant,
general contractor, mechanical contractor, firm preparing the manuals, and the month and year that
the manuals were prepared. It shall also bear the label
‘Operating & Maintenance Manual For Mechanical Systems”.
JM BEAN
& CO. LTD
RICHMOND ICE CENTRE
HVAC Upgrade
Project No. 1404
Section 15990
TESTING, ADJUSTING, AND BALANCING
February 2014
Page: 3 Spine label shall include the project name, project location, and the year that the manuals were
prepared. It shall also bear the label “Operating & Maintenance Manual For Mechanical Systems”.
Insert a Title page and Table of Contents in clear plastic covers. Title page shall include the project
name, project location, as well as the name, address, phone number of the owner, architect,
mechanical consultant, general contractor, mechanical contractor, firm preparing the manuals, and
the month and year that the manuals were prepared. It shall also bear the label “Operating &
Maintenance Manual For Mechanical Systems”.
Index the binder according to the following system:
Tab 1.1
Mechanical Drawing Schedule
Tab 1.2
Description of Systems
Provide a schematic drawing and component description for each major mechanical
system including air handling systems, boiler and hot water heating piping
distribution systems and (where applicable) water chillers and chilled water
distribution systems. The schematic drawing shall identify each component with a
letter designation corresponding to a description briefly explaining the purpose of
each component and how it relates to the other components, and be presented in a
current version of AutoCAD or similar computer aided drafting program.
The component description shall be clearly written in a language that may be easily
understood by the building operators and maintainers who will be using them.
Tab 1.3
Operating Division
Provide the following:
Specific operating instructions for each major item of equipment, including air
handling systems, etc.
Trouble Shooting Procedure Guide in spreadsheet form with the most likely causes
and recommended actions for all foreseeable problems. Trouble Shooting
Procedure guides are required for all the major items of equipment including air
handling systems, exhaust fans, circulating pumps, mechanical cooling equipment,
etc.
Mechanical Equipment Starting Procedures
Tab 1.4
Maintenance and Lubrication Division
Tab 1.5
Equipment Supplier and Contractor Schedule
Provide a list of Equipment Suppliers and Contractors and include their address,
telephone number.
Provide the Equipment Make/Manufacturer
Tab 2.0
Guarantees, Certificates and Reports
Tab 3.0
Equipment Shop Drawings and Maintenance Data
JM BEAN
& CO. LTD
RICHMOND ICE CENTRE
HVAC Upgrade
Project No. 1404
Section 15990
February 2014
TESTING, ADJUSTING, AND BALANCING
Page: 4 Organize this section into numbered tabs.
Insert final shop drawings that have been reviewed and as-built control
schematics.
For each fan installed, provide performance curves indicating the design point of
intersection and the actual operating point.
In addition to the shop drawings provided for the various items of mechanical
equipment, this section shall also include the Manufacturers’ Literature on:
Tab 4.0
Operating and maintenance instructions
Spare parts lists
Trouble Shooting information
Balancing Report
The divider tabs shall be custom laminated mylar plastic and shall be in accordance
with the following colour scheme:
Tabs 1.1 to 1.5 Orange
Tabs 2.0 to 2.3 Green
Tab 3.0 Yellow
A preliminary copy of the manual shall be sent to the engineer for review. Final copies shall
incorporate all of the consultant’s review comments.
The Mechanical Trade shall furnish sufficient copies of equipment manufacturer’s literature, a set of
drawings, and a Division 15 Specification to the company preparing the manuals to meet the above
requirements.
.9
Digital Manual Requirements
The digital version of the manuals and the hard cover version shall be prepared by the same
company.
In addition to the operating and maintenance manuals provided in hard covered binders, two copies of
all information shall be provided in digital format as follows:
The information shall be organized into sections in a user-friendly format to make it easy to search for
specific information. An indexing system shall be included that remains on an expandable portion of
the screen that allows the end user to scroll through the manual information that appears on the main
portion of the screen. The digital version content and organization for each manual shall be arranged
in a manner identical to the hard copy version. The specific requirements are listed below:
-
Utilize Adobe Acrobat X (or later) Portable Document Format (PDF). The entire Manual shall
be contained within one Adobe Acrobat PDF file for every 650 MB of file size.
-
If there is more than one volume of manual, indicate “Volume X of Y” for each volume.
-
Include a copy of Adobe Acrobat Reader X (or later).
-
The final Digital copies are to be copied to CDR with a custom CDR label. The custom CDR
label shall include: Project Name, Location of Project, Date of Assembly, name of
Mechanical Consultant, and shall be titled “Operating & Maintenance Manual for Mechanical
Systems”.
JM BEAN
& CO. LTD
RICHMOND ICE CENTRE
HVAC Upgrade
Project No. 1404
Section 15990
February 2014
TESTING, ADJUSTING, AND BALANCING
Page: 5 -
The Digital Manual shall be enhanced with the following features: Bookmarks, Thumbnails,
Internet Links, Internal Document Links and Optical Character Recognition (OCR). Refer to
Scanning Requirements and Organizational Requirements listed below.
Scanning Requirements:
-
All pages contained within the hard copy manual are to be scanned and/or digitized
to Adobe Acrobat 5.0 (or later) PDF.
Provide a minimum 300 DPI for all scanned pages.
-
All scanned shop drawings may be searched for text with minimum 75% Optical
Character Recognition (OCR).
-
All shop drawings are to be scanned to a minimum 8.5” x 11” size. If the original
page size is 11” x 17”, the digital copy shall also be 11” x 17”. Page sizes exceeding
11” x 17” may be shrunk down to 11” x 17”.
-
Rotation of scanned page images/texts shall be displayed within +/- 20 degrees.
Organizational Requirements:
-
Digital Manual shall be organized in the same manner as the approved Hard Copy
Manual. (e.g. Tabs 1.1, 1.2, 1.3, 1.4, 1.5, 2.0, 3.0, 4.0, etc).
-
Bookmark all major tabs and subsections.
-
Bookmark each set of shop drawings (Section 3.0).
-
Link the Table of Contents page to the referenced sections.
-
Insert an introduction/summary page for Sections 1.2, 1.3, 1.4, and 3.0 indicating
major subsections. Link these pages to their referenced sections.
-
Link the system descriptions to the referenced schematic drawings contained in
section 1.2.
-
Insert Internet Links and Internal Document Links from Section 1.5 to Mechanical
Equipment Manufacturers/Suppliers/Contractors official websites.
-
Mechanical Equipment Shop Drawings located in Section 3.0.
Use the following colour code for links contained in Sections 1.2, 1.3, 1.4, and 1.5.:
-
Internet Links (light blue with underline).
Internal Document Link (dark blue) (excludes AutoCAD schematic links).
Insert a title page for each major piece of equipment located in Section 3.0. The title page
shall include the Shop Drawing name, and a link (dark blue in colour) to Section 1.5.
It is the responsibility of the Mechanical Trade to provide high quality documentation for
scanning.
Digital Manual shall be reviewed by the Mechanical Consultant for content and layout prior to
final submission.
JM BEAN
& CO. LTD
RICHMOND ICE CENTRE
HVAC Upgrade
Project No. 1404
Section 15990
TESTING, ADJUSTING, AND BALANCING
February 2014
Page: 6 15998 COMMISSIONING
3.
Commissioning of the mechanical systemsshall be carried out by the balancing and testing contractor
or an independent commissioning contractor acceptable to the Engineer with technicians specifically
trained in commissioning procedures. The Commissioning Report will be forwarded to the Engineer
for review. The completed report shall form part of the Operating and Maintenance Manuals; provide
sufficient copies.
4.
Acceptable Balancing/Commissioning Contractors:
MDT Systems Ltd.
Western Mechanical Services
or other approved by Consulting Mechanical Engineer.
5.
The Commissioning Contractor shall advise the Contractor in writing, of any installation defects or
performance deficiencies encountered during the field checks and tests. A copy of this advice shall
be forwarded to the Engineer. As part of the final commissioning report, submit a Certificate stating
that the commissioning procedures have been completed, that complete factual reports have been
distributed and that directions have been given to the Contractor to correct faults and omissions and
finally, that follow-up testing, after the correction of faults and omissions has been completed and
recorded.
6.
All HVAC systems shall be commissioned in accordance with "The Code of Practice for
Commissioning Mechanical Systems in Buildings" issued by the Standing Committee of Consulting
Engineers and Mechanical Contractors in British Columbia or other approved, except that the
commissioning team shall include additional members as mentioned above.
7.
Check all Mechanical equipment for suitability to run prior to the initial startup. Provide assistance
to contractors and manufacturer's representatives, of each piece of equipment and verify equipment
operating characteristics and function. Maintain a log of key operating parameters, problems
encountered, solutions employed and verification of effectiveness. Findings/deficiencies during start
up to be noted on check lists and preliminary lists distributed to design authority and other parties
involved. Review the log of key operating parameters.
END of SECTION 15990
JM BEAN
& CO. LTD
1
1
1
WP
3
2
WP
4
WP
5
2
2
-
1
no.
UPPER ROOF PLAN - ELECTRICAL
0
4
8
12
16
20
2014/02/18 ISSUED FOR TENDER
24
date
remarks
revision
1/8"=1'-0"
2nd Floor, 1330 Granville St.
Vancouver, B.C. V6Z 1M7
tel : 604 569 6500
fax : 604 569 6501
Vancouver Victoria
MECHANICAL EQUIPMENT SCHEDULE
www.appliedengineering.ca
DRAWING KEY NOTES:
1
DISCONNECT EXISTING AC UNIT FOR REMOVAL BY OTHERS.
2
RECONNECT NEW UNIT IN SAME LOCATION AS REMOVED UNIT.
PROVIDE SEPARATE 120 VOLT CONNECTION TO INTEGRAL
DUPLEX RECEPTACLE. CONNECT TO PANEL K. PROVIDE
15A-1POLE BREAKER.
SINGLE POINT POWER
TO ROOFTOP UNIT
18.0 MCA
575V
3
PANEL A
MAG
M
M
M
M
M
M
C
M
M
M
SINGLE POINT POWER
TO ROOFTOP UNIT
18.0 MCA
575V
3
PANEL A
MAG
M
M
M
M
M
M
C
M
M
M
SINGLE POINT POWER
TO ROOFTOP UNIT
18.0 MCA
575V
3
PANEL A
MAG
M
M
M
M
M
M
C
M
M
M
SINGLE POINT POWER
TO ROOFTOP UNIT
18.0 MCA
575V
3
PANEL A
MAG
M
M
M
M
M
M
C
M
M
M
8.0 AMPS
115V
1
PANEL D
MAG
M
M
M
E
M
M
C
M
M
M
8.0 AMPS
115V
1
PANEL D
MAG
M
M
M
E
M
M
C
M
M
M
1/3 HP
115V
1
PANEL D
MAG
M
M
M
-
M
M
C
M
M
M
1/3 HP
115V
1
PANEL D
MAG
M
M
M
-
M
M
C
M
M
M
1/3 HP
115V
1
PANEL D
HOA
E
M
M
E
M
M
C
M
M
M
WP
7
3
AC-1 CHANGE BREAKER IN PANEL A FROM 30A-3P TO
20AMP-3P.
4
AC-2 CHANGE BREAKER IN PANEL A FROM 20A-3P TO 15A-3P
BREAKER.
5
AC-3 EXISTING 15A-3POLE BREAKER IN PANEL A SHALL REMAIN
IN USE.
6
1
6
7
AC-4 EXISTING 15A-3POLE BREAKER IN PANEL SHALL REMAIN
IN USE.
PROVIDE 120V DEDICATED CONNECTION TO INEGRAL DUPLEX
RECEPTACLE. UTILIZE CCT. B42.
PROVIDE 15AMP-1POLE BREAKER.
CITY OF
RICHMOND
MECHANICAL EQUIPMENT NOTES
THE CONTRACTOR SHALL CONFIRM ALL EQUIPMENT
LOADS, CIRCUIT SIZES AND MOUNTING HEIGHTS PRIOR TO
ROUGH-IN. COORDINATE WITH MECHANICAL CONTRACTOR
ON SITE.
THE ELECTRICAL CONTRACTOR MUST CONFIRM THE
MAXIMUM OVER-CURRENT PROTECTION BREAKER
ELECTRICAL REQUIREMENTS FOR ALL UNITS PRIOR TO
ORDERING BREAKERS. BREAKER SIZES ON UNIT
NAMEPLATES ARE NOT TO BE EXCEEDED AS PER C.E.C.
RICHMOND ICE
CENTRE
UPPER & LOWER
ROOF PLAN
ELECTRICAL
PROVIDE DISCONNECT SWITCH C/W RELAYS FOR
CONNECTION TO DUCT SENSOR AS REQUIRED.
TIMECLOCKS TO BE PROGRAMMABLE 24 HOUR/7 DAY.
APPROVED MANUFACTURERS TORKS OR PARAGON.
2
LOWER ROOF PLAN - ELECTRICAL
0
4
8
12
16
20
24
1/8"=1'-0"
ELECTRICAL DRAWING LIST:
E1 UPPER & LOWER ROOF PLAN ELECTRICAL
E2 PARTIAL FLOOR PLAN ELECTRICAL DEMOLITION
E3 ELECTRICAL SPECIFICATIONS
drawn
checked
date
scale
issued
project
drawing number
revision
E1
3
-
EXISTING ELECTRICAL
EQUIPMENT
EXISTING
PANEL D
EXISTING
MCC
SDC1
MDC
1
UNIT SUB
STATION
2
SEE DETAIL BELOW
1
PARTIAL FLOOR PLAN - ELECTRICAL DEMOLITION
0
4
8
12
16
20
24
1/8"=1'-0"
-
2014/02/18 ISSUED FOR TENDER
no.
date
remarks
revision
2nd Floor, 1330 Granville St.
Vancouver, B.C. V6Z 1M7
tel : 604 569 6500
fax : 604 569 6501
Vancouver Victoria
www.appliedengineering.ca
DRAWING KEY NOTES:
1
DISCONNECT EXISTING BOILER AND ASSOCIATED EQUIPMENT
FOR REMOVAL BY OTHER.
2
DISCONNECT AND REMOVE EXISTING KILL SWITCH.
3
PROVIDE WIREMOLD BOX ON EXISTING KILL SWITCH BOX.
INSTALL NEW RED MUSHROOM TYPE KILL SWITCH. LOCATE
BEYOND SWING OF DOOR. UTILIZE SURFACE RACEWAY AND
WIREMOLD BOX. CONNECT KILL SWITCH TO NEW BOILER TO
KILL POWER TO BOILERS WHEN ACTIVATED.
4
CONNECT NEW BOILER/PUMP TO PANEL D IN ELECTRICAL ROOM.
UTILIZE EXISTING CIRCUIT D09.
5
CONNECT NEW BOILER / PUMP TO PANEL D IN ELECTRICAL
ROOM. UTILIZE CIRCUIT D13. PROVIDE 15AMP-1POLE BREAKER.
6
DISCONNECT EXISTING RECIRC. PUMP. RECONNECT NEW PUMP
CP007 TO SAME CIRCUIT CD11. CONFIRM CIRCUIT ON SITE.
4
6
5
3
CITY OF
RICHMOND
3
2
EXISTING BOILER ROOM - ELECTRICAL WORK
0
4
8
12
16
20
24
1/8"=1'-0"
RICHMOND ICE
CENTRE
PARTIAL FLOOR
PLAN ELECTRICAL
DEMOLITION
drawn
checked
date
scale
issued
project
drawing number
revision
E2
3
-
ELECTRICAL SPECIFICATION:
1.
GENERAL
.1
.2
.3
.4
.4
GENERAL REQUIREMENTS, INSTRUCTIONS TO BIDDERS, THIS SPECIFICATION AND ANY ADDENDA
HERETO FORM PART OF THE CONTRACT DOCUMENTS AND SHALL BE READ IN CONJUNCTION WITH
THEM. WORK TO INCLUDE THE FURNISHING OF ALL LABOR AND MATERIALS, UNLESS SPECIFIED
OTHERWISE, TO COMPLETE AND PUT INTO OPERATING CONDITION ALL ELECTRICAL SYSTEMS AS
INDICATED ON THE DRAWINGS AND SPECIFIED HEREIN.
IT IS THE INTENT OF THE WORK TO PROVIDE COMPLETE, NEATLY FINISHED, AND OPERATIONAL
SYSTEMS. ANY LABOR, MATERIAL, PERMITS, LICENSES, APPROVALS AND INSPECTIONS REQUIRED
FOR COMPLETION OF THE WORK, WHETHER SPECIFICALLY MENTIONED IN THE DRAWINGS OR
SPECIFICATIONS OR NOT, ARE TO BE INCLUDED IN THE TENDERED PRICE.
RESPONSIBILITY AS TO WHICH TRADE PROVIDES REQUIRED ARTICLES OR MATERIALS RESTS
SOLELY WITH THE GENERAL CONTRACT TRADE. EXTRAS WILL NOT BE CONSIDERED BASED ON
GROUNDS OF DIFFERENCE OF INTERPRETATION OF SPECIFICATIONS AS TO WHICH TRADE
INVOLVED SHALL PROVIDE CERTAIN SPECIALTIES OR MATERIALS.
THE DRAWINGS AND SPECIFICATIONS FOR THE COMPLETE WORKS, INCLUDING ALL OF THOSE
RELATED TO OTHER TRADES ARE TO BE EXAMINED BEFORE SUBMITTING TENDERS. ALL
ELECTRICAL AND COMMUNICATIONS REQUIREMENTS INDICATED ARE TO BE INCLUDED IN THE
SCOPE OF THE WORK.
10.
CLEAN UP AND REMOVE ALL UNUSED WIRING AND CONDUITS.
.6
REMOVE AND REINSTALL EXISTING DEVICES TO FACILITATE CONSTRUCTION AS REQUIRED.
.7
CONFIRM OUTLET LOCATIONS AND MOUNTING HEIGHT WITH PROJECT COORDINATOR ON SITE
PRIOR TO INSTALLATION.
.8
FIRE PROOF ALL FIRE RATED PENETRATIONS AFTER INSTALLATION TO COMPLY WITH CODES AND
TO PROVIDE EQUAL FIRE SEPARATION RATINGS.
11.
12.
.2
.7
ALLOW FOR OVERTIME WORK AS REQUIRED AND COORDINATE WITH OWNER/OCCUPANTS IF
APPLICABLE.
.4
RACEWAYS ARE TO BE INSTALLED FREE FROM DENTS AND BRUISES AND SHALL HAVE
THEIR ENDS CAPPED, PLUGGED, OR SEALED AS NECESSARY TO PREVENT ENTRANCE
OF DIRT OR MOISTURE.
.8
CONTRACTOR TO COORDINATE ANY INTERRUPTIONS TO ADJOINING OCCUPANTS IN ORDER
TO AVOID ANY INCONVENIENCES TO SAID OCCUPANTS. IF NECESSARY CONTRACTOR TO DO
ANY REQUIRED CONNECTIONS DURING "OFF" HOURS
.5
IN ALL AREAS SUBJECT TO MOISTURE, WATERTIGHT FITTINGS MUST BE USED.
.6
ALL RACEWAY, EXCEPT WHERE OTHERWISE INDICATED, SHALL BE
ACCORDANCE WITH THE CANADIAN ELECTRICAL CODE, CURRENT EDITION.
.7
TECK90 OR SEAL TIGHT FLEXIBLE CONDUIT IS BE UTILIZED FOR CONNECTIONS TO
MOTORS AND MOTOR CONTROLLERS.
.8
ALL UNDERGROUND CONDUIT SYSTEMS ARE TO BE OF APPROVED PVC SCHEDULE 40
CONDUIT, COMPLETE WITH INSTALLED BONDING CONDUCTOR, AND INSTALLED AT OR
BELOW THE DEPTH REQUIRED BY CODE. PROVIDE 150mm CLEAN SAND BEDDING ABOVE
AND 75mm BELOW CONDUITS AND CONTINUOUS MARKING TAPE 300mm BELOW GRADE.
PROVIDE SUITABLE BACKFILL AND COMPACTION.
EXAMINATION OF THE SITE
CUTTING AND PATCHING
DRAWINGS AND SPECIFICATIONS ARE COMPLEMENTARY TO EACH OTHER AND WHAT IS CALLED
FOR BY ONE IS TO BE BINDING AS IF CALLED FOR BY BOTH.
.1
SHOULD ANY DISCREPANCY APPEAR BETWEEN DRAWINGS AND SPECIFICATIONS THAT LEAVES THE
ELECTRICAL TRADE IN DOUBT AS TO TRUE INTENT AND MEANING, OBTAIN RULING FROM THE
ENGINEER BEFORE SUBMITTING TENDER, OR ALLOW FOR THE MOST EXPENSIVE ALTERNATIVE.
ALL PENETRATIONS SHALL BE SEALED WITH APPROVED FIRE STOP MATERIAL.
.9
SIZED
31. SEISMIC PROTECTION
.1 THE ELECTRICAL TRADE SHALL PROVIDE SEISMIC RESTRAINT AND ANCHORAGE FOR ALL
EQUIPMENT AND SERVICES IN ACCORDANCE WITH THE CURRENT EDITION OF THE B.C. BUILDING
CODE, AND ALL APPLICABLE BUILDING BYLAWS.
IN
THE ELECTRICAL CONTRACTOR IS TO EXAMINE CAREFULLY STRUCTURAL, ARCHITECTURAL AND
MECHANICAL DRAWINGS, AND THE WORK OF OTHER TRADES AND SATISFY HIMSELF THAT THE
WORK UNDER THIS CONTRACT CAN BE SATISFACTORILY CARRIED OUT WITHOUT CHANGES TO THE
BUILDING AS SHOWN ON THE PLANS. SHOULD ANY DIFFICULTY ARISE SHOWING CONFLICT WITH, OR
REQUIRING ADDITIONAL WORK BEYOND THE WORK OF THESE DRAWINGS, BRING THIS MATTER TO
THE ATTENTION OF THE ENGINEER BEFORE SUBMITTING TENDER.
DURING CONSTRUCTION THE ELECTRICAL TRADE AND HIS SUBTRADES ARE TO KEEP THE
SITE FREE OF DEBRIS, BOXES, PACKING, AND OTHER MATERIALS ASSOCIATED WITH THE
WORK OF THIS TRADE. ALL WASTE MATERIAL IS TO BE DISPOSED OF IN A SAFE AND
ENVIRONMENTALLY RESPONSIBLE MANNER.
13.
.2
THE NUMBER OF ACCESS DOORS SHALL BE KEPT TO A MINIMUM.
.3
THE ELECTRICAL TRADE SHALL PROVIDE ACCESS PANELS IN THE DRYWALL CEILINGS FOR
ALL ELECTRICAL JUNCTION BOXES AND EQUIPMENT IN ACCORDANCE WITH APPLICABLE
CODES.
ALL MATERIALS ARE TO BE NEW AND OF THE QUALITY SPECIFIED, AND SHALL BE APPROVED BY
CSA OR EQUIVALENT AGENCY RECOGNIZED IN BRITISH COLUMBIA.
14.
CODES, PERMITS AND INSPECTION
.1
.2
ALL WORK SHALL BE EXECUTED IN A NEAT AND WORKMANLIKE MANNER BY QUALIFIED
TRADESMEN. THE ELECTRICAL CONTRACTOR SHALL KEEP A COMPETENT FOREMAN AND
NECESSARY ASSISTANTS ON THE SITE DURING THE PROGRESS OF THE WORK.
.2
.3
ALL MATERIAL AND INSTALLATION SHALL MATCH BUILDING STANDARD UNLESS IT IS NOTED
OTHERWISE ON THE DRAWINGS.
THE ELECTRICAL TRADE IS TO OBTAIN ALL PERMITS REQUIRED FOR EACH STAGE OF WORK,
AND AFTER COMPLETION OF THE ENTIRE INSTALLATION FURNISH TO THE ENGINEER A
CERTIFICATE OF FINAL INSPECTION AND APPROVAL FROM THE ELECTRICAL INSPECTION
DEPARTMENT.
15.
.2
THE ENGINEER WILL FURNISH TO THE ELECTRICAL TRADE ONE SET OF DRAWINGS TO BE USED FOR
RECORD PURPOSES. THE ELECTRICAL TRADE IS TO ACCURATELY RECORD ON THESE PRINTS ALL
REVISIONS TO THE ORIGINAL PLANS THAT ARE MADE ON SITE DURING CONSTRUCTION.
.1
.2
ALL BUILDING WIRING IS TO BE COPPER, EXCEPT WHERE NOTED OTHERWISE.
A MINIMUM CONDUCTOR SIZE OF #12 AWG COPPER IS TO BE USED, EXCEPT WHERE
NOTED OTHERWISE.
.3 ALL CONDUCTORS ARE TO BE COLOR CODED THROUGHOUT THE INSTALLATION AS
FOLLOWS:
- EQUIPMENT GROUNDING CONDUCTOR - GREEN
- NEUTRAL CONDUCTOR - WHITE
- 120/208V PHASE WIRES - RED, BLACK, AND BLUE
- 347/600V PHASE WIRES - COLOUR TO MATCH EXISTING
.4 ALL WIRING #12 AND HIGHER SHALL BE STRANDED
.1
ALIGN ALL DEVICES AND PLATES PLUMB AND LEVEL WITH BUILDING STRUCTURAL LINES.
.2
ALL OUTLET BOXES ARE TO BE FLUSH MOUNTED EXCEPT WHERE SPECIFIED
OTHERWISE.
THE ELECTRICAL TRADE IS TO PRODUCE AT HIS OWN EXPENSE A SET OF AUTOCAD 2007 (OR
LATER) DRAWINGS, INCLUDING ALL CHANGES TO THE ORIGINAL TENDER DRAWINGS COVERED BY
ADDENDA, CHANGE ORDERS, FIELD CHANGES, AND JOB CONDITIONS, AND TURN THESE OVER TO
THE ENGINEER IN ELECTRONIC AND HARD COPY FORM. COMPLETED RECORD DRAWINGS ARE TO
BE CLEARLY MARKED "RECORD DRAWINGS". ENGINEER IS AVAILABLE TO PROVIDE CHANGE TO THE
AUTOCAD FILES. ALLOW $350 / DRAWING FOR THIS WORK.
.2
SHOP DRAWINGS
.1
.2
.3
THE ELECTRICAL CONTRACTOR IS TO SUBMIT TO THE ENGINEER, FOR REVIEW, SHOP DRAWINGS
OF MAJOR ELECTRICAL EQUIPMENT. SUCH EQUIPMENT SHALL INCLUDE, BUT NOT BE LIMITED TO
SWITCHGEAR, PANELBOARDS, SERIES-RATED BREAKER COMBINATIONS, FIXTURES AND FITTINGS
NOT PROVIDED BY THE OWNER.
.3
ALL DRAWINGS ARE TO BE SUBMITTED IN TRIPLICATE AND TWO COPIES WILL BE RETURNED TO THE
ELECTRICAL TRADE. SUBMIT ADDITIONAL COPIES FOR APPROVAL AS MAY BE REQUIRED.
THE ENGINEER'S REVIEW OF SHOP DRAWINGS IS TO BE FOR GENERAL DESIGN ONLY AND WILL NOT
RELIEVE THE ELECTRICAL TRADE OR SUPPLIERS FROM RESPONSIBILITY FOR ERRORS, PROPER
FITTING, CONSTRUCTION OF WORK, AND FURNISHING OF MATERIALS. REVIEW WILL NOT BE
CONSTRUED AS APPROVING DEPARTURES FROM CONTRACT DOCUMENT REQUIREMENTS IF SUCH
DEPARTURES ARE NOT SPECIFICALLY NOTED. THE ELECTRICAL TRADE IS RESPONSIBLE FOR
VERIFYING ALL DIMENSIONS.
.4
16.
.1
THE ELECTRICAL TRADE SHALL FURNISH A WRITTEN WARRANTY, SIGNED BY AUTHORIZED
PERSONNEL, STATING:
.1
.2
.3
THAT ALL WORK EXECUTED UNDER THIS CONTRACT WILL BE FREE FROM DEFECTS OF
MATERIAL AND WORKMANSHIP FOR A PERIOD OF 1 YEAR FROM DATE OF FINAL ACCEPTANCE.
THE ABOVE PARTIES FURTHER AGREE TO, AT THEIR OWN EXPENSE, REPAIR AND REPLACE ALL
SUCH DEFECTIVE WORK, AND OTHER WORK DAMAGED THEREBY, WHICH FAILS OR BECOMES
DEFECTIVE DURING THE TERM OF THE WARRANTY PROVIDED THAT SUCH FAILURE IS NOT DUE
TO IMPROPER USAGE.
THE PERIOD OF THE WARRANTY SPECIFIED WILL IN NO WAY SUPPLANT ANY OTHER WARRANTY
OF A LONGER PERIOD BUT BE BINDING ON WORK NOT OTHERWISE COVERED.
17.
.1
.2
.3
THE ELECTRICAL TRADE IS RESPONSIBLE FOR CORRECTING ALL WORK COMPLETED CONTRARY TO
THE INTENT OF DRAWINGS AND SPECIFICATIONS AND SHALL BEAR ALL COSTS INVOLVED IN MAKING
THE CORRECTIONS. WHERE INTENT OF DRAWINGS AND SPECIFICATIONS IS NOT CLEAR, OBTAIN
CLARIFICATION FROM THE ENGINEER BEFORE PROCEEDING WITH WORK.
THE ELECTRICAL TRADE IS TO GIVE WORK HIS PERSONAL SUPERVISION, LAY OUT HIS OWN WORK,
DO ALL NECESSARY LEVELING AND MEASURING OR EMPLOY A COMPETENT ENGINEER TO DO SO.
FIGURES, FULL SIZE AND DETAIL DRAWINGS TO TAKE PRECEDENCE OVER SCALE MEASUREMENTS.
THE ELECTRICAL TRADE SHALL BE RESPONSIBLE FOR ANY DAMAGE CAUSED TO THE OWNER OR
ANY OTHER TRADE BY IMPROPER LOCATION OR CARRYING OUT OF HIS WORK.
MECHANICAL AND CONTROL EQUIPMENT IS SHOWN DIAGRAMMATICALLY ON THE DRAWINGS.
ELECTRICAL CONTRACTOR SHALL COORDINATE LOCATION WITH MECHANICAL TRADE PRIOR
TO ROUGH-IN.
UPON PROJECT COMPLETION, AND IMMEDIATELY PRIOR TO FINAL INSPECTION AND
TAKEOVER, THE ELECTRICAL TRADE SHALL CHECK THE LOAD BALANCE ON ALL FEEDERS AND
AT DISTRIBUTION CENTRES, LOAD CENTRES, AND PANELS. THESE CHECKS ARE TO BE
CARRIED OUT BY TURNING ON ALL LOADS AND CHECKING LOAD CURRENT BALANCE. IF LOAD
UNBALANCE EXCEEDS 15 %, THE CIRCUITS ARE TO BE RECONFIGURED AS NECESSARY TO
BALANCE THE LOADS.
.3
.4
.2
.3
.4
.5
40
41
CONTRACTOR TO PROVIDE DEMOLITION OF EXISTING ELECTRICAL SERVICES IN
WORK AREA. CONTRACTOR TO TURN OVER TO BUILDING OWNER MATERIAL AS
NOTED.
IN AREAS WHERE DEMOLITION OCCURS AND EXISTING ELECTRICAL SERVICES
ARE SHOWN TO REMAIN OR ARE REQUIRED FOR SERVICING OF ADJACENT
AREAS, CONTRACTOR TO REROUTE AND REFEED AS REQUIRED TO RECONNECT.
CLEAN UP AND REMOVE ALL UNUSED WIRING AND SURFACE CONDUITS BACK TO
SOURCE.
REWIRE EXISTING LIGHTING AND POWER THAT ARE AFFECTED BY THIS
CONSTRUCTION.
THE RAISED FLOOR IS USED AS AN AIR PLENUM. ANY WIRING AND CONDUIT
PENETRATING WALLS, SHEET METAL PLENUMS WITHIN RAISED FLOOR AND
FLOOR TILES TO BE SEALED AIR TIGHT.
.1.1
.1.2
EXECUTION
.3.1
INSTALLATION
.3.1.2 ENSURE CORRECT FUSES AND OVERLOAD DEVICES ELEMENTS INSTALLED.
.3.2
FIELD QUALITY CONTROL
.3.2.1 PERFORM TESTS IN ACCORDANCE WITH SECTION 26 05 00 - COMMON
WORK RESULTS - ELECTRICAL AND MANUFACTURE'S INSTRUCTION.
.3.2.2 OPERATES SWITCHES, CONTACTORS TO VERIFY CORRECT FUNCTIONING.
.3.2.4 CHECK THAT SQUENCE CONTROLS, INTERLOCKING WITH OTHER SEPARATE
RELATED STARTERS, EQUIPMENT, CONTROL DEVICES, OPERATE AS INDICATED.
42
SHOP DRAWINGS AND PRODUCT DATA
-
2014/02/18 ISSUED FOR TENDER
FIRE STOPPING
.1 FIRE STOPPING
.1.1
SEAL ALL OPENINGS FOR CONDUIT OR SLEEVE PENETRATIONS IN FIRE RATED AN
SMOKE RATED SEPARATIONS USING APPROVED MATERIALS.
.1.2
ALL BLOCK OUTS AND ACCESS SLOTS TO BE SEALED USING APPROVED FIRE
STOPPING ASSEMBLY. PROVIDE FULL DETAILS FOR ALL FIRE STOPPING
APPLICATIONS AS THEY RELATE TO EACH APPLICATION.
.1.3
PROVIDE SHOP DRAWINGS FOR ALL FIRE STOPPING PRODUCTS, INCLUDING
ASSEMBLY DETAILS AS IT RELATES TO EACH APPLICATION. PRODUCTS SHALL BE
ULC APPROVED AS AN ASSEMBLY.
.1.4
RETAIN THE SERVICES OF A PROFESSIONAL ENGINEER REGISTERED IN THE
PROVINCE OF BRITISH COLUMBIA TO INSPECT EACH AND EVERY FIRE STOPPING
INSTALLATION AND TO PROVIDE A REPORT ON ALL INSTALLATIONS.
.1.5
ALLOW FOR THE DESTRUCTIVE TESTING OF 10%%% OF FIRE STOPPING APPLICATIONS.
SHOULD INSTALLATIONS NOT CONFIRM TO MANUFACTURE'S DETAILS, AN ADDITIONAL 25%
OF INSTALLATION WILL BE DESTRUCTIVELY TESTED AND SHOULD THERE BE MORE
FAILURES, THE CONTRACTOR WILL BE RESPONSIBLE TO REMOVE ALL FIRE STOPPING
PRODUCTS AND REINSTALL PRODUCTS CORRECTLY, AT NO ADDITIONAL COST TO OWNER.
no.
date
remarks
revision
2nd Floor, 1330 Granville St.
Vancouver, B.C. V6Z 1M7
tel : 604 569 6500
fax : 604 569 6501
Vancouver Victoria
www.appliedengineering.ca
.1.2.1 SUBMIT SHOP DRAWINGS IN ACCORDANCE WITH SECTION 01 33 00 SUBMITTAL PROCEDURES.
.1.2.2 INDICATE:
- MOUNTING METHOD AND DIMENSIONS.
- STARTER SIZE AND TYPE.
- LAYOUT OF IDENTIFIED INTERNAL AND FRONT PANEL COMPONENTS.
- ENCLOSURE TYPES.
- WIRING DIAGRAM FOR EACH TYPE OF STARTER.
- INTERCONNECTION DIAGRAMS.
.7 WEATHERPROOF PLATES: COST METAL GASKETTED COVERPLATES FOR RECEPTACLES, SPRING
LOADED COST GASKETTED DOORS. DOUBLE DOORS FOR STANDARD DUPLEX RECEPTACLES.
COVERPLATES TO FASTEN TO THE BOX WITH 4 SCREWS.
25. SUPPORTS
.1.3
.1 ALL CONDUIT, RACEWAYS, AND OTHER ELECTRICAL EQUIPMENT SHALL BE SECURELY AND
ADEQUATELY
SUPPORTED, IN ACCORDANCE WITH THE CANADIAN ELECTRICAL CODE.
.1.3.2 AT MINIMUM, PROVIDE THE FOLLOWING SPARE PARTS FOR EACH
DIFFERENT SIZE AND TYPE OF STARTER:
- 3 CONTACTS, STATIONARY
- 3 CONTACTS, MOVABLE
- 1 CONTACT, AUXILIARY
- 1 CONTROL TRANSFORMER
- 1 OPERATING COIL
- 2 FUSES
- 10% INDICATING LAMP BULB USED.
.2
27. PANELS
.1 THE MAJORITY OF PANELBOARDS ARE EXISTING. PROVIDE NEW BREAKERS AS INDICATED ON
THE DRAWINGS.
.2 NEW BREAKERS SHALL MATCH EXISTING AND BE OF SAME TYPE AND MANUFACTURE AS
EQUIPMENT EXISTING WITHIN THE BUILDING THEY ARE BEING INSTALLED IN. BREAKERS SHALL
BE FULL SIZE (25mm) AND SHALL BE BOLT ON TYPE. MINIMUM PANEL FAULT RATING SHALL
BE 10000 AMP SYMMETRICAL. NEW PANELS SHALL HAVE HINGED DOOR WITH LOCK.
CITY OF
RICHMOND
PRODUCTS
.2.1
MATERIAL
.2.1.1 STARTERS: TO IEC 647-4 WITH AC4 UTILIZATION CATEGORY.
.2.2
.3 A SEPARATE GROUND CONDUCTOR SHALL BE INSTALLED IN ALL RACEWAY FEEDER RUNS,
FLEXIBLE CONDUIT, AND IN CONDUIT INSTALLED IN SLAB OR UNDERGROUND.
EXTRA MATERIAL
.1.3.1 PROVIDE MAINTENANCE MATERIALS IN ACCORDANCE WITH MANUFACTURE'S
RECOMMENDATIONS.
.2 WHERE INSERTS ARE REQUIRED IN CONCRETE, EXPANSION INSERTS, LEAD INSERTS OR
PLASTIC INSERTS ARE
TO BE USED IN DRILLED HOLES. SHOT DRIVEN PINS MAY BE USED IN STRUCTURAL CONCRETE
ONLY WITH
THE PERMISSION OF THE ENGINEER.
.2 ALL METAL PARTS NOT CARRYING CURRENT, INCLUDING BUT NOT LIMITED TO, SECONDARY
FEEDER CIRCUITS, EQUIPMENT AND PANELBOARD ENCLOSURES, METAL RACEWAYS, PULL AND
JUNCTION BOXES, SHALL BE PROPERLY GROUNDED. METAL RACEWAYS SHALL UTILIZE DOUBLE
LOCKNUTS AND OTHER FITTINGS WHERE NECESSARY TO PROVIDE GROUND CONTINUITY.
IN
.3
REFERENCES
.1.1.1 INTERNATIONAL ELECTROTECHNICAL COMMISSION (IEC)
IEC 647-4-1-LATEST EDITION, PART 4: CONTACTORS AND
MOTOR-STARTERS.
.5 STANDARD RECEPTACLES TO BE MATCH COLOUR OF ADJACENT DEVICES IN SAME BUILDING.
HUBBELL 5252-1 OR EQUAL.
ALL PANELS ARE TO BE FACTORY-FINISHED WITH SPRAY-ON AIR DRY ENAMEL. ALL ENAMEL
TO BE APPLIED OVER CORROSION-RESISTANT PRIMER. MATTE OR FLAT TYPE FINISH PAINT
WILL NOT BE ACCEPTED. ALL PANELS OR SIMILAR FACTORY-FINISHED UNITS THAT ARE
SCRATCHED OR MARKED DURING INSTALLATION ARE TO BE TOUCHED UP WITH MATCHING
SPRAY-ON AIR DRY LACQUER AND, IF REQUIRED TO PROVIDE A SATISFACTORY JOB, TO BE
COMPLETELY REFINISHED.
BE FURNISHED
.2.7.1 PROVIDE EQUIPMENT IDENTIFICATION IN ACCORDANCE WITH SECTION 33.
MOTOR STARTERS TO 600 VOLTS
.2 PROVIDE P-TOUCH LABELS FOR ALL RECEPTACLE LABELS.
.1 A COMPLETE GROUNDING AND BONDING SYSTEM SHALL BE SUPPLIED AND INSTALLED IN
ACCORDANCE WITH THE CANADIAN ELECTRICAL CODE AND THE ELECTRICAL INSPECTION
DEPARTMENT.
ETC. SHALL
EQUIPMENT IDENTIFICATION
MOTOR CONTROL CENTERS. (NOT USED)
.1 GENERAL
ALL ELECTRICAL FITTINGS, SUPPORTS, HANGER RODS, PULLBOXES, CHANNEL FRAMES,
CONDUIT RACKS, OUTLET BOXES, BRACKETS, AND CLAMPS ARE TO HAVE A GALVANIZED
FINISH OR A PAINT FINISH OVER CORROSION-RESISTANT PRIMER.
PULLBOXES, JUNCTION BOXES, TERMINAL PANELS,
ACCORDANCE WITH EXISTING BUILDING STANDARDS.
.1
26. GROUNDING AND BONDING
ALL 347/600V AND 120/208V PANELBOARDS, PULLBOXES, AND OTHER ELECTRICAL CABINETS
AND BOXES ARE TO BE FINISHED IN GREY ENAMEL.
2.7
39. DEMOLITION
.6 PLATES FOR ALL FLUSH MOUNTED DEVICES TO BE STAINLESS STEEL, HEAVY
CONSTRUCTION.
PAINTING AND FINISHES
.2
BOXES: HOT DIP GALVANIZED, CONFORMING TO CSA REQUIREMENTS.
BOXES FOR CEILING, NO 54151 BOX, OTHERWISE NO. 52171 OR NO. 72171 BOX
AS PER CODE REQUIREMENTS.
BOXES FOR INDOOR SURFACE MOUNTED EQUIPMENT, USE 4 IN. SQUARE C/W
COVER.
NO SECTIONAL OR HANDY BOXES ALLOWED.
FINISHES
.2.6.1 APPLY FINISHES TO ENCLOSURE IN ACCORDANCE WITH SECTION 26 05
00 - COMMON WORK RESULTS - ELECTRICAL.
38. RAISED FLOOR PEDESTAL GROUNDING (NOT USED)
24. SWITCHES AND RECEPTACLES
.3 FOR ALL RECEPTACLE OTHER THAN STANDARD 15A DUPLEX RECEPTACLES, PROVIDE
LAMICOID NAMETAGS GIVING AMP RATING, PHASE AND VOLTAGE.
.4 PROVIDE LOW VOLTAGE SWITCHES PROM THE SAME MANUFACTURE OF EXISTING LV.
LIGHTING CONTROL SYSTEM.
BEFORE ENERGIZING ANY PORTION OF THE ELECTRICAL SYSTEM, THE ELECTRICAL TRADE
SHALL PERFORM MEGGER TESTS ON ALL FEEDERS AND BRANCH CIRCUITS. ANY PROBLEMS
DISCOVERED BY SUCH TESTING ARE TO BE CORRECTED BY THE ELECTRICAL TRADE AND THE
CIRCUITS IN QUESTION RETESTED. THE RESULTS OF ALL FINAL TESTING SHALL BE PROVIDED
TO THE ENGINEER IN REPORT FORM.
SETTING OUT OF THE WORK
THE ELECTRICAL TRADE SHALL SUPPLY AND INSTALL PULLBOXES AS REQUIRED TO SUIT
JOB CONDITIONS. PULLBOXES SHALL CONFORM TO CANADIAN ELECTRICAL CODE
REQUIREMENTS. PULLBOXES TO BE BE FINISHED IN ENAMEL OVER
CORROSION-RESISTANT PRIMER WITH SCREW-ON OR HINGED COVER. IN REMOVABLE
CEILING AREAS, PULLBOXES ARE TO BE INSTALLED ABOVE THE CEILING.
THE ELECTRICAL CONTRACTOR IS TO CONFIRM MOTOR (OR OTHER EQUIPMENT) LOCATION
AND SIZES WITH THE TRADE SUPPLYING THE MOTOR (OR OTHER EQUIPMENT) BEFORE
COMMENCING ANY ASSOCIATED ELECTRICAL WORK.
.2
.1
.1
.2.6
.3.1.1 INSTALL STARTERS, CONNECT POWER AND CONTROL AS INDICATED.
23. PULL BOXES
.1 ALL SWITCHES AND RECEPTACLES SHALL BE SPECIFICATION GRADE TO MATCH EXISTING
UNLESS OTHERWISE NOTED.
ALL PORTIONS OF ELECTRICAL WORK ARE TO BE TESTED FOR SATISFACTORY OPERATION.
.3
.4
THE ENGINEER RESERVES THE RIGHT TO CHANGE THE LOCATION OF OUTLETS TO
WITHIN 3 M OF THE LOCATION INDICATED ON PLANS WITHOUT EXTRA CHARGE,
PROVIDED THE ELECTRICAL CONTRACTOR IS ADVISED BEFORE INSTALLATION IS MADE.
THE ELECTRICAL EQUIPMENT MAY INCLUDE BUT NOT BE LIMITED TO SUCH ITEMS AS PUMP
MOTORS AND INTERLOCKS, STARTING DEVICES, MOTOR CONTROLLERS, FLOAT SWITCHES,
ALARM DEVICES OR SYSTEMS, PUSH BUTTONS, EXHAUST FANS, DATA SYSTEMS.
.1
WARRANTY
.1
UNLESS SPECIFIED OTHERWISE, THE ELECTRICAL CONTRACTOR IS TO SUPPLY AND INSTALL
ALL REQUIRED CONDUIT, WIRING, ELECTRICAL FITTINGS AND CONNECTIONS FOR ALL
MOTORS AND OTHER ELECTRICAL EQUIPMENT, EVEN THOUGH SUCH MOTORS AND OTHER
ELECTRICAL EQUIPMENT MAY BE SUPPLIED BY OTHERS. WHERE REQUIRED BY THE
DRAWINGS OR APPLICABLE REGULATIONS, DISCONNECT SWITCHES, STARTERS, OVERLOAD
RELAYS AND OTHER NECESSARY PROTECTIVE DEVICES ARE TO BE SUPPLIED AND INSTALLED
BY THE ELECTRICAL CONTRACTOR. MOTORS AND CONTROLS SHALL BE FURNISHED BY THE
SUPPLIER OF THE DRIVEN EQUIPMENT. THE ELECTRICAL CONTRACTOR SHALL INCLUDE ALL
WORK AND CONNECTIONS REQUIRED TO MAKE THE SYSTEM COMPLETE AND OPERATIONAL.
TESTS
.4 ELECTRONIC COPIES OF SHOP DRAWINGS WILL BE ACCEPTABLE.
.3
22. LOCATION OF OUTLETS
MECHANICAL EQUIPMENT
.1
.2.5.2 SIZE CONTROL TRANSFORMER FOR CONTROL CIRCUIT LOAD PLUS 20%
SPARE CAPACITY.
37. OUTLET BOXES
.1
.2
CONTROL TRANSFORMERS
.2.5.1 SINGLE PHASE, DRY TYPE, CONTROL TRANSFORMERS WITH PRIMARY
VOLTAGE AS INDICATED AND 120V SECONDARY, COMPLETE WITH
SECONDARY FUSE, INSTALLED IN WITH STARTER AS INDICATED.
36. INTERCOM SYSTEM (NOT USED)
RECORD DRAWINGS
.1
.2.5
34. COMMUNICATION CABLING (NOT USED)
21. WIRING DEVICES & OUTLET BOXES
THE ENTIRE INSTALLATION, INCLUSIVE OF MATERIAL AND LABOR, IS TO COMPLY WITH ALL THE
REQUIREMENTS OF ALL BUILDING CODES AND AUTHORITIES HAVING JURISDICTION, THE
CANADIAN ELECTRICAL CODE, AND REGULATIONS OF THE LOCAL INSPECTION DEPARTMENT.
.2.4.2 ACCESSORIES
- SELECTOR SWITCHES: STANDARD LABELED AS INDICATED.
- INDICATING LIGHTS: STANDARD TYPE AND COLOR AS INDICATED.
- AUXILIARY CONTROL DEVICES AS INDICATED.
35. SECURITY SYSTEMS (NOT USED)
WHERE CONDUITS ARE INSTALLED IN CONCRETE SLABS OR CROSS STRUCTURAL
EXPANSION JOINTS, AN APPROVED EXPANSION FITTING COMPLETE WITH BONDING
JUMPER AND CLAMPS SHALL BE INSTALLED, EXPANSION JOINTS TO BE CROUSE HINDS
XJ SERIES OR OZ TYP AX SERIES.
FULL VOLTAGE REVERSING MAGNETIC STARTERS
.2.4.1 FULL VOLTAGE REVERSING MAGNETIC STARTERS OF SIZE, TYPE, RATING
AND ENCLOSURE TYPE AS INDICATED WITH COMPONENTS AS FOLLOWS:
- TWO-3 POLE MAGNETIC CONTACTORS MOUNTED ON COMMON BASE.
- MECHANICAL AND ELECTRICAL INTERLOCKS TO PREVENT BOTH
CONTACTORS FROM OPERATING AT SAME TIME.
.1 IDENTIFY ALL MAJOR PIECES OF EQUIPMENT, INCLUDING BUT NOT LIMITED TO PANELBOARDS,
ELECTRICAL CABINETS, AND BREAKERS IN PANELBOARDS WITH ENGRAVED LAMACOID LABELS,
BLACK LETTERING ON WHITE BACKGROUND.
.2 PROVIDE TYPEWRITTEN DIRECTORIES IN ALL PANELS.
.3 PROVIDE LAMACOID NAMEPLATE ON EACH PANEL COVER TO IDENTIFY PANEL NAME, NUMBER
OF PHASES, VOLTAGE, CURRENT RATING AND SOURCE OF FEEDER.
.4 IDENTIFY BRANCH CIRCUIT WIRES TO MEET CODE REQUIREMENTS.
.5 FIRE ALARM BREAKER TO BE RED AND CLEARLY IDENTIFIED.
20. WIRE AND CABLE
UNLESS OTHERWISE SPECIFIED, UNIFORMITY OF MANUFACTURE IS TO BE MAINTAINED FOR ANY
PARTICULAR ITEM THROUGHOUT.
.2.3.3 ACCESSORIES:
- SELECTOR SWITCHES: STANDARD LABELED AS INDICATED.
- INDICATING LIGHTS: STANDARD TYPE AND COLOR AS INDICATED.
- 1-N/O AND 1-N/C SPARE AUXILIARY CONTACTS UNLESS OTHERWISE
INDICATED.
19. EXPANSION JOINTS
UPON COMPLETION OF WORK, THE ELECTRICAL INSTALLATION SHALL BE LEFT IN A CLEAN
AND FINISHED CONDITION TO THE SATISFACTION OF THE ENGINEER.
THE ELECTRICAL TRADE IS TO SUPPLY AND INSTALL ACCESS DOORS AS REQUIRED FOR
PROPER SERVICING OF ALL ELECTRICAL WORK. ACCESS DOORS SHALL BE COMPLETE WITH
NECESSARY FRAMES AND HINGED DOORS HELD CLOSED WITH CAPTIVE STUDS. ACCESS
PANEL TO BE OF NOT LESS THAN 14 GAUGE STEEL, PRIME COAT FINISHED AND PAINTED ON
THE JOB TO MATCH THE WALL OR CEILING FINISH.
.3 INCLUDE IN THE TENDERED PRICE ALL SERVICES OF THE PROFESSIONAL ENGINEER
INCLUDING BUT NOT LIMITED TO PROVIDING LETTERS OF ASSURANCE FOR THE PROJECT IN
RESPECT OF THE SEISMIC RESTRAINT OF ALL ELECTRICAL MATERIALS AND EQUIPMENT,
CONDUCTING THE NECESSARY SITE REVIEWS AND PROVIDING A LETTER AT THE CONCLUSION
OF THE PROJECT, CONFIRMING THAT ALL SEISMIC RESTRAINTS FOR THE ELECTRICAL WORKS
HAVE BEEN INSTALLED IN ACCORDANCE WITH THE ENGINEER'S INSTRUCTIONS.
33. IDENTIFICATION
ACCESS DOORS
.1
.2.3.2 COMBINATION TYPE STARTERS TO INCLUDE MOTOR CIRCUIT INTERRUPTER
OR CIRCUIT BREAKER WITH OPERATING LEVER ON OUTSIDE OF
ENCLOSURE, AND PROVISION FOR:
- LOCKING IN "OFF" POSITION WITH UP TO 3 PADLOCKS.
- INDEPENDENT LOCKING OF ENCLOSURE DOOR.
- PROVISION FOR PREVENTING SWITCHING TO "ON" POSITION WHILE
ENCLOSURE DOOR OPEN.
.2.4
CONDUIT TO BE ELECTRIC METALLIC TUBING. UTILIZE RIGID GALVANIZED STEEL
CONDUIT FOR ALL EXPOSED RUNS BELOW 7 FEET OF FLOOR. WHERE IN JUDGEMENT BY
THE ELECTRICAL INSPECTION AUTHORITY IS SUBJECT TO MECHANICAL DAMAGE.
.11 AC90 (BX) CABLE MAY BE USED FOR FIXTURE DROPS IN SUSPENDED CEILINGS, AND
FROM CEILING JUNCTION BOX TO RECEPTACLES IN PARTITION WALL. NO DAISY
CHAINING OF OUTLETS IN PARTITION WALL. EACH DROP NOT TO EXCEED 15 FEET.
.2 PROVIDE CERTIFIED PROFESSIONALLY SEALED SHOP AND PLACEMENT DRAWINGS WHERE
APPLICABLE FOR ALL ELECTRICAL EQUIPMENT AND EQUIPMENT ASSEMBLIES SHOWING THE
METHODS OF ATTACHMENT TO THE PARTICULAR STRUCTURE FOR EACH PIECE OF EQUIPMENT
AND ASSEMBLY AND PROVIDE ANCHORAGE/ATTACHMENT DETAILS APPROVED AND SEALED BY A
B.C. REGISTERED PROFESSIONAL ENGINEER. ELECTRICAL CONTRACTOR SHALL ENGAGE THIS
PROFESSIONAL ENGINEER..
32. COMMUNICATIONS (DATA) ROUGH-IN (NOT USED)
.10 FLEXIBLE CONDUIT CONNECTIONS TO MOTORS, CONTROL, ETC., TO BE FLEXIBLE
PLASTIC JACKETED, SEAL TIGHT OR APPROVED EQUAL. FLEXIBLE CONDUIT
CONNECTIONS ARE REQUIRED TO ALL MOTORS FROM STUB-UPS OR JUNCTION BOXES.
.1
STANDARDS OF MATERIAL AND WORKMANSHIP
.1
9.
WHERE WORK DONE BY THE ELECTRICAL TRADE DAMAGES THE WORK OF OTHER TRADES,
THE ELECTRICAL TRADE SHALL REPAIR AND MAKE GOOD SUCH DAMAGE TO THE
SATISFACTION OF EACH TRADE CONCERNED AND THE ENGINEER.
UNIFORMITY OF EQUIPMENT
.1
8.
THE GENERAL TRADE WILL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING REQUIRED
FOR ELECTRICAL INSTALLATION. STRUCTURAL MEMBERS MUST NOT BE CUT WITHOUT
CONSENT OF THE ENGINEER.
CLEANUP
EXAMINATION OF OTHER DRAWINGS
.1
7.
30. FIRE ALARM SYSTEM(NOT USED)
SURFACE MOUNTED CONDUIT AND EMT ARE TO BE INSTALLED PARALLEL TO
STRUCTURAL LINES, AND, WHERE BENDS OCCUR IN PARALLEL RUNS, THEY SHALL BE
CONCENTRIC.
.2
6.
UNLESS OTHERWISE NOTED, CONDUIT AND EMT ARE TO BE CONCEALED IN ALL
FINISHED AREAS. IN SERVICE AREAS, CONDUIT AND EMT SHALL BE RUN ON SURFACE
UNLESS INDICATED OTHERWISE.
FULL VOLTAGE MAGNETIC STARTERS
.2.3.1 MAGNETIC AND COMBINATION MAGNETIC STARTERS OF SIZE, TYPE, RATING
AND ENCLOSURE TYPE AS INDICATED AND COMPONENTS AS FOLLOWS:
- CONTACTOR SOLENOID OPERATED, RAPID ACTION TYPE.
- MOTOR OVERLOAD PROTECTIVE DEVICE IN EACH PHASE, MANUALLY
RESET FROM OUTSIDE ENCLOSURE..
- WIRING AND SCHEMATIC DIAGRAM INSIDE STARTER ENCLOSURE IN
VISIBLE LOCATION.
- IDENTIFY EACH WIRING AND TERMINAL FOR EXTERNAL CONNECTIONS,
WITHIN STARTER, WITH PERMANENT NUMBER MARKING IDENTICAL TO DIAGRAM.
29. EXIT LIGHTING AND EMERGENCY LIGHTING (NOT USED)
DRAWINGS AND SPECIFICATIONS
.1
5.
.2
.3
.3
4.
WHERE REQUIRED BY THE CANADIAN ELECTRICAL CODE, ALL WIRE AND CABLE IS TO BE
INSTALLED IN CONDUIT OR EMT. WHERE APPROVED, AC90 OR TECK90 MAY BE USED.
WHERE OUTLET BOXES OCCUR IN EXTERIOR WALLS, THE ELECTRICAL TRADE IS TO ENSURE
THAT THERE IS INSULATION BEHIND THE OUTLET BOXES TO PREVENT CONDENSATION
THROUGH THE BOXES.
.2
3.
.1
.6
PRIOR TO SUBMITTING TENDER, THE ELECTRICAL TRADE SHALL CAREFULLY EXAMINE THE
SITE AND ASCERTAIN ALL CONDITIONS WHICH MAY AFFECT HIS TRADE. NO ADDITIONAL
MONEY WILL BE ALLOWED FOR WORK RESULTING FROM CONDITIONS THAT SHOULD HAVE
BEEN NOTICED AND ACCOUNTED FOR DURING A THOROUGH EXAMINATION OF THE SITE.
.2.3
28. LIGHTING LUMINAIRES AND LIGHTING CONTROLS (NOT USED)
THE ELECTRICAL TRADE SHALL CONFIRM OUTLET LOCATIONS AND MOUNTING HEIGHTS WITH
THE PROJECT COORDINATOR ON SITE PRIOR TO INSTALLATION.
.1
2.
18. CONDUIT AND EMT
.5
.1
.5
THE ELECTRICAL TRADE, IN THE SETTING OUT OF HIS WORK, IS TO MAKE REFERENCE TO
MECHANICAL DRAWINGS. HE SHALL CONSULT WITH ALL RELEVANT TRADES IN SETTING OUT
LOCATIONS FOR CONDUIT RUNS, LIGHTING FIXTURES, PANEL ASSEMBLIES, AND ALL OTHER
ELECTRICAL EQUIPMENT, SO THAT CONFLICTS ARE AVOIDED AND SYMMETRICAL SPACING IS
MAINTAINED.
MANUAL MOTOR STARTERS
.2.2.1 SINGLE AND THREE PHASE MANUAL MOTOR STARTERS OF SIZE, TYPE,
RATING, AND ENCLOSURE TYPE AS INDICATED, WITH COMPONENTS AS
FOLLOWS:
- SWITCHING MECHANISM, QUICK MAKE AND BREAK.
- ONE OR THREE OVERLOAD HEATERS AS REQUIRED, MANUAL RESET,
TRIP INDICATING HANDLE.
.2.2.2 ACCESSORIES:
- PUSHBUTTON: STANDARD LABELED AS INDICATED.
- INDICATING LIGHT: STANDARD TYPE AND COLOR AS INDICATED.
- LOCKING TAB TO PERMIT PADLOCKING IN "ON" OR "OFF" POSITION.
RICHMOND ICE
CENTRE
ELECTRICAL
SPECIFICATIONS
drawn
checked
date
scale
issued
project
drawing number
revision
E3
3
-
Download