4010-9826
120VAC Auxiliary Relay Kit
Installation Instructions
Cautions and Warnings
DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS
DAMAGED. Upon unpacking your Simplex product, inspect the contents of the
carton for shipping damage. If damage is apparent, immediately file a claim
with the carrier and notify Simplex.
ELECTRICAL HAZARD - Disconnect electrical power when making any
internal adjustments or repairs. Servicing should be performed by qualified
Simplex Representatives.
STATIC HAZARD - Static electricity can damage components. Therefore,
handle as follows:
1. Ground yourself before opening or installing components (use the 553-484
Static Control Kit).
2. Keep uninstalled component wrapped in anti-static material at all times.
Overview
This publication shows how to wire and install the 4010-9826 120VAC
Auxiliary Relay Kit into a 4010 Fire Alarm Control Panel (FACP). Refer to the
4010 — Fire Alarm-Installing, Operating, and Programming Instructions
(574-052) for configuration information. Refer to the 842-058 Field Wiring
Diagram for additional wiring information.
Introduction
The 4010-9826 Auxiliary Relay Kit is comprised of an in-line fuse and a
terminal block cover. The kit is used when connecting 120VAC to a 4010 SFI/O
board’s (565-737 or 565-738) auxiliary relays (TB6, AUX 1 or TB7, AUX 2).
The circuit rating is 0.5 Amp at 120VAC.
Installing the Fuse
Refer to Steps 1 through 5 and Figure 1 to install the in-line fuse (Buss, Type
HLQ Fuseholder; Type GLQ-1 Fuse: 1A, 300V) into the 4010 FACP.
1.
2.
3.
4.
5.
Disconnect the power to the Auxiliary Relay Contacts and the 4010 FACP.
Wire 120VAC HOT through the in-line fuse. DO NOT fuse the neutral leg.
DO NOT wire 240VAC or voltages greater than 120VAC to the system.
Connect the other in-line fuse end to the Auxiliary Relay Terminal block
(TB6 or TB7) Normally Open (NO) or Normally Closed (NC).
Connect the Auxiliary Relay Terminal Block (TB6 or TB7) Common (C) to
the LOAD.
Connect 120VAC NEUTRAL directly to the LOAD.
IMPORTANT: Route 120V in accordance with power-limited
requirements. Keep 1/4-inch distance from all powerlimited circuits.
Figure 1. Installing the Fuse
 1998 Simplex Time Recorder Co., Gardner, MA 01441-0001 USA
All specifications and other information shown were current as of publication, and are subject to change without notice.
Technical Manuals Online! - http://www.tech-man.com
574-471
Rev. A
Mounting the Terminal Block
Cover
To mount the terminal block cover onto the 4010 FACP refer to Figure 2 and
Steps 1 through 4.
1.
2.
3.
4.
Locate the bottom two screws of the Keyboard Mounting Plate Assembly of
the 4010 FACP.
Partially unscrew the two screws (approximately 1/16-inch).
Slide the terminal block cover so that the top slots of the cover hook on to
the screws.
With the terminal block cover in place, retighten the two screws.
4010 FACP
Bottom Screw (2) of
Keyboard Mounting
Plate Assembly
Slide Slot (2)
under screws
Terminal Block
Cover
Figure 2. Mounting the Terminal Block Cover
574-471
Rev. A