- Alva Lighting

advertisement
T ECH N I CA L DOCU M EN T
Emergency Battery Back-Up for
Betty and Bob Wall Sconces
Specifications
• Fulham FireHorse Hotspot LED
Emergency back-up system
• Fully integrated Battery Back-up,
all components enclosed within
fixture
• >90 Minutes of 100% light
output in the case of a power
outage
• 24 hour recharge time
• 120-277V input voltage
• Easy to install on all types of
junction boxes, including pancake
boxes
• Test button conveniently located
on top of fixture
• Battery easily replaced in the field
after 7 year rated lifetime
• Energy Star qualified options
available
• ETL924 recognized emergency
lighting system
• ETL Damp Listed
• 5 year warranty on Fulham
components
Description
ALVA offers Fulham’s industry leading, fully integrated
emergency back-up system as an option for Betty and Bob wall
sconces. We provide 100% light output in the case of power
loss for more than 90 minutes. All electronics are fully integrated
within ALVA’s proprietary LED module.
Testing the Battery Back-Up ALVA Fixture
Press and hold down the red test switch located at the top of the
fixture, the fixture will switch to EM power. When the button is
released the fixture will return to normal mode.
Battery should be replaced when fixture no longer provides 60%
of light output at the end of 90 minutes.
Installation Instructions
See detailed instructions on page two of this document.
G
Installing your Alva light fixture with Emergency
Battery Back-up takes six easy steps:
1. Attach the crossbar to the junction box. Screw
the 1/8 IPS pipe into the cross bar.
2. Lift the back cover of the light fixture and connect
the Fulham Emergency Battery and the Fulham HotSpot
LED Driver.
3. Secure the back cover to the light fixture.
D
C
A
D
E
4. Connect the electrical wires from the junction
box to the electrical wires of the light fixture.
Please see below if using 0-10V dimming
functionality.
A. Lock-up Cap
B. Light Fixture
B
5. Place the LED light fixture over the 1/8 IPS pipe
from the universal mounting ring and carefully
slide the fixture up snug to the junction box
being careful to ensure the wires feed into the
junction box. Screw on the lock-up cap to the
1/8 IP pipe.
6. Mount shade to the light fixture using hardware
included with the shade selected for your
project.
F
C. IPS Pipe
D. Hardware
E. Crossbar
F. Junction Box
G. Reset Switch
What’s Included
• HotSpot LED Driver FHS2-UNV-36L
• HotSpot LED Battery Pack FHSBATL3-1.5
Dimming Options:
Your Betty/Bob LED wall sconce includes two dimming options as standard. You may choose either dimming option:
1. LumenSelect™ 4 level light output (100%, 75%, 50%, and 25%).
2. 0-10V Dimming
LumenSelect™
Our Betty/Bob wall sconce comes the factory set at 100% light output. You may chose at the time of install from
four settings: • 100% light output • 75% light output
• 50% light output • 25% Light output
Note that the power consumption of the fixture decreases approximately in conjuction with the light output
(ie. 50% light output consumes half the power) To select, using a standard screwdriver, turn the LumenSelect™ dial
at the end of the fixture to your desired setting. You can either set your light output prior to installing your fixture
OR you may set it after you have installed the fixture.
0-10V Dimming
Note: To use the 0-10V dimming, be sure you have set your LumenSelect™ setting to 100% light output if you
have changed it from its factory pre-setting of 100%. Your Betty/Bob LED wall sconce also provides control wires
accessible from the back of the fixture that provide 0-10V dimming. To utilize the 0-10V dimming you must provide
control wires to the junction box. At the time of installation, attach Purple (DIM+) wire from back of fixture to
DIM+ control wire from junction box. Attach Gray (DIM-) wire from back of fixture to DIM+ wire from junction box.
Compatible and Tested Dimmers: Lutron Model DVTV, Leviton Model Decora Illumatech IP710-DLZ
Instructions in detail:
1. Attaching the Cross Bar
a. Carefully unpack your new fixture and lay
all parts on a clean surface. Be careful not
to lose any small parts necessary for the
installation.
G
b. Pull the electrical wires part way out of the
junction box for easier access.
c. Attach your light fixture’s cross bar to the
electrical junction box.
2. Setting up the Fulham system.
D
C
A
D
E
a. Carefully lift the back cover of the fixture.
b. Connect the cable plug from the Fulham
Emergency Battery into the Fulham HotSpot
LED Driver.
c. At this point the light fixture will turn on.
F
A. Lock-up Cap
B. Light Fixture
B
C. IPS Pipe
D. Hardware
E. Crossbar
3.
Securing the back cover to the light fixture.
a.
Using the hardware provided, screw the back
cover to the fixture. Make sure that the back
cover is aligned correctly.
4. Connecting the Electrical Wires
a. Connect the light fixture wires to the wires
of the junction box. White to white, black
to black and ground to ground. If there is
no ground wire from the junction box,
connect the fixture ground wire (green or
yellow/green, or copper) to the mounting
bar with the green screw provided. Be
certain that all connections are tight and
NO bare wire is visible. (note: ground wire,
if unshielded copper, will show bare wire).
b. Tuck the wires into the junction box.
c.
When the installation area’s power is reinstated
the fixture will stop relying on the battery as a
power source automatically
F. Junction Box
G. Reset Switch
5. Securing the Light Fixture to the Cross Bar.
a. Slide the fixture over the 1/8 IPS pipe and
gently push the fixture up until snug to
the wall. Screw down the lock-up cap to
secure the fixture to the wall.
6. Attaching the Diffuser to Your Light Fixture.
a. Position the shade/diffuser on the light
fixture and using the shade/diffuser
hardware, attach the shade/diffuser to
the light fixture.
GENERAL INSTALLATION GUIDELINES FOR
LED EMERGENCY DRIVER MODEL : FHS2-UNV-36L
IMPORTANT SAFE PRACTICES
When using electrical equipment and this lighting device basic
safety precaution should be followed at all times including but not
limited to the following:
PLEASE READ CAREFULLY AND FOLLOW ALL INSTRUCTIONS
FOR YOUR OWN SAFETY
IMPORTANT: An un-switched AC power source of 100VAC to
277VAC is required.
This device is designed for use in fixtures listed for damp locations.
CAUTION: Make sure all electrical connections conform to the
National Electrical Code and all applicable local regulations.
CAUTION: Do not let power supply cords touch hot surfaces.
CAUTION: Do not mount near gas or electric heaters.
CAUTION: Battery is rechargeable Ni-Cad or LiFePO4 type and
must be recycled or disposed of properly.
Do not use this emergency driver with accessory equipment other
than recommended by manufacturer; failure to follow this may
cause an unsafe condition. Servicing should only be performed by
qualified service personnel.
Do not use this emergency driver for other than intended use.
Equipment should be mounted in locations and at heights where it
will not readily be subjected to tampering by unauthorized
personnel.
IMPORTANT: Indicator (LED light) illuminated indicates battery in
charge mode when AC power is applied. It is recommended and
required by applicable code to test emergency ballast to ensure
proper function of the system; push the test switch for thirty (30)
seconds every 30 days to ensure the emergency driver is
functioning as LED light source illuminated. Conduct a ninety
minute (90) discharge test one time (1) per year; LED light source
should be illuminated for a minimum of ninety minutes (90).
ASSEMBLY and FIELD INSTALLATION WIRING: WARNING: AC
power must be off before proceeding with assembly or installation
of emergency driver.
TESTING SYSTEM: The emergency battery requires a charge
minimum of one (1) hour before testing the circuit. A full charge
requires twenty four (24) or thirty six (36) or forty eight (48) hours,
depending upon battery pack. Please refer to battery chart for
charging time.
LED-BASED ARCHITECTURAL LIGHTING
2150 ALLSTON WAY, SUITE 400, BERKELEY, CA 94704
P: 408.394.3054
WWW.ALVALIGHT.COM
EBB-2014-07