mcPhilben CXX Series Xtest INSTRUCTION MANUAL p/n: 787625458 THERMOPLASTIC EMERGENCY LIGHTING PRODUCTS Self-Testing / Self-Dianostic EXIT PANEL CANOPY LED STRIP BACK PANEL Simple snap-out Chevrons PLUG CHEVRON CHEVRON Circuit Assembly Code X 1 Std Emergency Backup X 2 Flash on Battery X 3 FireAlarm Interface PCA - Electronics BATTERY PACK Flexible conduit only 2C Two Circuit Input ADC Alt. DC Source No rigid conduit IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS + + + + + + + + Do not use outdoors. Do not mount near gas or electric heaters. Do not let power supply wires touch hot surfaces. Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel. The use of accessory equipment not authorized by the manufacturer may cause an unsafe condition. Do not use this equipment for other than its intended purpose. Service of this equipment should be performed by qualified service personnel. No rigid conduit. SAVE THESE INSTRUCTIONS INSTALLATION Transformer Inputs: ================= BLACK - 120V WHITE - Common RED - 277V TO OPEN EXIT SIGN: 2 1 DO NOT FEED IMPORTANT NOTE: REMOVE THE INPUT POWER IMMEDIATELY IF ALL RED LED’S ON THE OP-PANEL FLASH: This indicates that the input power is incorrectly wired, and needs to be corrected. IF 277 is applied to the 120 tap for more than 7/sec, then the fusable-link may open requiring the transformer to be replaced. Note that this condition is not covered by warranty. WALL / CEILING / FLAG INSTALLATION: > WALL MOUNT) Always verify the input voltage source. Open front cover as shown above. Route the required transformer input wires (BLACK=120V, WHITE=common, RED=277V) though the read center K/O and make input connection in the box. Simply use the Box pattern K/O’s in the back panel as needed to mount to wall box and secure unit to the wall. If the unit is shipped with the battery disconnected, connect/verify it at this time to the BAT location on the main PCA. Remove the snap-out chevrons in the EXIT panels as needed, replace the EXIT panel(s) back on to the sign, and then proceed to Power-Up Sequence... > CEILING/FLAG MOUNT) Remove the two snap-out plugs at the desired locations for the canopy to fit. Route the proper two transformer input wires (BLACK=120V, WHITE=common, RED=277V) out through the hole in the body for the canopy snap that is labeled “<< INPUT FEED ACCESS”. Then snap the canopy in to the body with the wires threaded. Align the metal adapter plate for mount direction and mount it to the j-box with the input wires out through the center hole. Now make the input connections and then push them in through the center hole in the metal adapter plate, and mount the canopy/exit-sign to the metal adapter. Remove the snap-out chevrons in the EXIT panels as needed, replace the EXIT panel(s) back on to the sign, and then proceed to Power-Up Sequence... Normal Power-Up Sequence APPLY INPUT POWER IMPORTANT NOTE: ~0/sec ARE ALL RED DIAG LED’S FLASHING Y REMOVE INPUT POWER IMMEDIATELY Y VERIFY BATTERY CONNECTED REMOVE THE INPUT POWER IMMEDIATELY IF ALL RED LED’S ON THE OP-PANEL FLASH. This indicates that the input power is incorrectly wired, and needs to be corrected. IF 277 is applied to the 120 tap for more than 7/sec, then the fusable-link may open requiring the transformer to be replaced. Note that this condition is not covered by warranty. N IS THE BATTERY LED FLASHING BATTERY LED FLASHING AFTER POWER-UP: > > 1) Most likely the battery is not connected; verify that it is connected to the BAT location of the main PCA. 2) If the battery is connected, then it is faulty and needs to be replaced. N ~7/sec WITHIN ~7/sec GREEN STATUS - ON EXIT SIGN - ON ANY OF THE (6) EXIT LED’S NOT OPERATING AT POWER-UP SEQUENCE: VERIFY ALL (6) EXIT-LED’s ARE OPERATING ~30/sec > Y CORRECT EXIT STRIP PROBLEM > N WITHIN ~25/sec IT PERFORMS 5/sec AUTO-DIAG TEST AUTO-DIAG TESTING: > > > TO NORMAL OPERATION > > > > > 1) If some of the (6) LED’s are on and some are off, the the EXIT strip needs to be replaced. 2) Verify that the cable to the EXIT strip is connected to the EXIT location of the main PCA, and to the EXIT strip INPUT location. NOTE: It is very important that all of the (6) LEDs of the strip are operating during the first 24 hours after installation. Otherwise the system LED detection circuit may not properly detect the LED strip. > The unit automatically performs diag testing at all power-up’s, and randomly each 30/days. The system is capable of detecting a single LED failure of the EXIT sign. This is only possible if at installation, you verify that all (6) LED’s of the EXIT sign are lighted. If they are not all operating, the system will not properly learn the units thresholds causing the system to improperly detect LED failures. The system also constantly monitors and controls all functions, the charging circuit, the EXIT LED’s, operator manual tests. The charge circuit is computer controlled by an algorithm that is monitoring the environment, the levels of the battery, and the curves associated to each. The system literally learns these parameters and then remembers them to better provide for the best life of the unit and its’ battery. It is normal for the CHARGER LED to goON solid right after the power-up sequence from installation. This indicates the battery is charging, and the LED will go out when the battery is at full charge, this usually occurs within 24-96 hours after installation. The charger LED may cycle from off to on solid as the system charging algorithm dictates. This is normal. Allow the system to fully charge until the CHARGER LED is off before initiating tests. NORMAL OPERATION / MANUAL TESTS OP-PANEL INDICATORS / OPERATION: > > > > > > > > > > GREEN - Status: Solid indicates system normal and charging current from the input source is available. NOTE: Pressing the button during any test will cancel the test and return to normal. 1 Press: performs a 5/sec brief test, all lamps operating from battery only. 2 Press: performs a 1/min test, all lamps operating from battery only. 3 Press: performs a 30/min long run discharge test, all lamps operating from battery only. The system locks out to allow only one 30/min test ea 24/hr period. CONTINUOS MONITORING: The system monitors the battery for proper levels and performs periodic low-level exercising. Constant LAMP/EXIT checking, should a LAMP/EXIT LED fail, the system will flash the LAMPS indicator until repaired. The charger is fully checked once per day for a internally disconnected integrity check, at this time the battery is also completely isolated and then check for proper capacity levels. OPTIONAL FACTORY EQUIPPED ITEMS: FireAlarm Interface: Unit will be supplied with a connector at the FAFI location and a interface cable to connect to the building system (per wiring diagram). Flashing EM: Unit will flash the EXIT sign when operating from the battery only. Remote Control: Use typical laser pen to operated unit from the floor level just as if you were pushing the button as the laser passes across the sensor. TROUBLE INDICATIONS / TROUBLESHOOTING OP-PANEL INDICATORS: SELF-TEST / DIAGNOSTIC CHARGER > GREEN - Status: Solid indicates system normal and flashes during any manual/auto test cycle. BATTERY LAMPS > RED - CHARGER FLASHING: a charger failure requires the main system PCA to be replaced. > RED - BATTERY FLASHING: battery may be disconnected or if it is connected replacement is needed. > RED - LAMPS FLASHING: on EXIT products, it indicates that a EXIT LED is failed. Even one LED can be detected. CHG - TEST REMOTE SENSOR (IF EQUIPPED) WIRING INFORMATION PCA Configuration CODE (see front page for the table of codes) Transformer Inputs: ================= BLACK - 120V WHITE - Common RED - 277V FIRE ALARM (IF EQUIPPED) X1 TRANSFORMER CABLE EXIT LED’s Factory Cable: YELLOW - Signal from system BLACK - Return line from system BATTERY PACK mcPhilben / Day-Brite 776 S.Green Street - Tupelo, Ms 38804 - ph: 662.842.7212 - fx: 662.680.6619