advertisement
INSTALLATION INSTRUCTIONS
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
FOR EMERGENCY LIGHTING FIXTURE – N7 SERIES
SAVE THESE INSTRUCTIONS
IMPORTANT SAFEGUARDS:
When using electrical equipment, always adhere to the basic safety precautions
including the following:
READ AND FOLLOW ALL
SAFETY INSTRUCTIONS
1. Do not use this equipment outdoors.
2. Do not mount near gas or electric heaters.
3. Equipment should be mounted securely
in locations and at heights where it will
not be readily subjected to tampering by
unauthorized personnel.
4. The use of accessory equipment and
replacement parts not recommended by
the MANUFACTURER may cause an
unsafe condition.
5. Do not use this equipment for other than
its intended purpose.
6. Do not let power supply cords touch hot
surfaces.
7. Before wiring to power supply, turn off
electricity at fuse or circuit breaker.
8. Installation and servicing should be
performed by qualified personnel.
9. CAUTION: When this equipment is furnished with halogen cycle lamp, these
additional safeguards apply:
a. To avoid shattering, do not operate
lamp in excess of rated voltage. Protect
lamp against abrasion and scratches and
against liquids when lamp is operating.
Dispose of lamps with care.
b. Halogen cycle lamps operate at a high
temperature. Do not store or place flammable materials near lamps.
IMPORTANT
The battery in this unit may not be fully
charged. After electricity is connected to unit,
let battery charge for at least 168 hours, then
normal operation of this unit should take
effect. To check, press the TEST button. The
emergency lamps should illuminate.
INSTALLATION
1. Remove cover and any packing material
that may have been used for shipping
purposes.
2. Determine the proper location for where
the sign is going to be mounted. Remove
cardboard template from the box and
place against the ceiling tile or area of
the ceiling where exit light is going to
be installed and trace a line around the
template (Figure A). This will be the area
that is going to be cut out. You may
want to do the cutting on the ground
if possible.
3. Cut the rectangular hole out of the ceiling
area (Figure B).
4. Mount the recessed housing in place
using the bar hangers (Figure C).
5. Make adjustments to the bar hanger
holder bracket to adjust the height of
the recessed housing (Figure D). The
proper height is having the bottom of the
recessed housing even with the finished
ceiling level (shown in Figure E).
6. Extend 24-hour AC supply of rated
voltage to the equipment, which is
furnished with a dual voltage
120/277VAC field selectable input
(see illustration). For 120V supply,
connect the line wire to the black lead;
for 277V supply, connect the line wire
to the orange/red lead. Connect neutral
wire to the white lead. Connect ground
wire in accordance with local codes. A
green ground lead is provided. DO NOT
energize circuit at this time. CAUTION:
Insulate the unused black or orange wire.
Failure to insulate the unused wire will
cause an unsafe condition. NOTE: If a
cord set is to be installed, follow separate
cord set installation instructions
INSTALLATION (continued)
7. Place TRIM PLATE & LIGHTING HEADS
into recessed housing by pinching together the spring clips and hooking them into
the SLOTS licated on the outside of the
recessed housing.
8. Connect the JUMPER CONNECTORS
to connect the LAMP HEADS,
SWITCH WIRES & BATTERY (Figure F).
9. Slide the trim plate/lamp head assembly
up and into the recessed housing
(Figure G).
10.Screw in the two screws to securely
mount the trim plate to the recessed housing. And also make any adjustments to
the lamp heads at this time (Figure H).
11.Energize the AC supply. The CHARGE
indicator will illuminate.
OPERATION
1. To test the equipment, depress the TEST
switch. The CHARGE indicator will go out
and the emergency lights will illuminate.
2. Release the TEST switch. The emergency
lights will go out and the CHARGE indicator will illuminate.
3. The automatic charger will resume and
maintain the battery in a fully charged
state. NOTE: Allow the battery to charge
for a minimum of 24 hours after installation or after a power failure before conducting a 90-minute test (See TESTING).
CAUTION: This equipment is furnished
with a sophisticated solid state transfer
switch which will automatically disconnect
the emergency lights from the battery if:
a. The battery has been discharged to the
end of its useful output.
b. The output circuit is overloaded.
c. The output is shorted.
FIG. A
FIG. B
FIG. C
FIG. D
FIG. E
FIG. F
FIG. G
FIG. H
(Continued on back)
pg 1 of 2
INSTALLATION INSTRUCTIONS
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
FOR EMERGENCY LIGHTING FIXTURE – N7 SERIES
IMPORTANT SAFEGUARDS:
When using electrical equipment, always adhere to the basic safety precautions
including the following:
MAINTENANCE
CAUTION: Always turn off AC power to the
equipment before servicing. Servicing should
be performed only by a qualified service technician. Use only MANUFACTURER supplied
or APPROVED replacement parts.
1. BATTERY: The battery supplied in this
equipment requires no maintenance.
However, it should be tested periodically
(See TESTING) and replaced when it no
longer operates the connected load for
the duration of a 30-second or 90-minute
test.
2. OTHER: Clean lenses and replace lamps,
as required.
TESTING
The NFPA 101, Life Safety Code requires
that all emergency lighting equipment be
functionally tested every 30 days for a minimum of 30 seconds and tested yearly for a
full 90-minute duration. Written records of
testing are to be kept for examination by the
authority having jurisdiction.
TROUBLESHOOTING
1. The emergency lights do not operate a. If the charge indicator light is off, check
that the circuit breaker for AC supply is on.
b. If the charge indicator light is on, check
that battery is properly connected. If problem persists, replace battery.
2. Emergency lights are dim - battery not
fully charged. Allow battery to recharge for
168 hours and then retest.
If lights are still dim, replace battery.
WIRING DIAGRAM
WARRANTY
Juno Lighting Group warrants that its products are free from defects in material and workmanship. Juno Lighting Group’s obligation
is expressly limited to repair or replacement, without charge, at Juno Lighting Group’s factory after prior written return authorization has been
granted. This warranty shall not apply to products which have been altered or repaired outside of Juno Lighting Group’s factory. This warranty is
in lieu of all other warranties, expressed or implied, and without limiting the generality of the foregoing phrase, excludes any implied warranty of
merchantability. Also, there are no warranties which extend beyond the description of the product on the company’s literature setting forth terms
of sale.
Product Services Phone (888) 387-2212
1300 S. Wolf Rd • P.O. Box 5065 • Des Plaines, IL 60017-5065 • Phone: 800-323-5068 • www.junolightinggroup.com
©2016 Acuity Brands Lighting, Inc.
Rev 08/05
P0066
pg 2 of 2
Download