INSTALLATION INSTRUCTIONS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR EMERGENCY LIGHTING FIXTURE – N7 SERIES SAVE THESE INSTRUCTIONS IMPORTANT SAFEGUARDS: When using electrical equipment, always adhere to the basic safety precautions including the following: READ AND FOLLOW ALL SAFETY INSTRUCTIONS 1. Do not use this equipment outdoors. 2. Do not mount near gas or electric heaters. 3. Equipment should be mounted securely in locations and at heights where it will not be readily subjected to tampering by unauthorized personnel. 4. The use of accessory equipment and replacement parts not recommended by the MANUFACTURER may cause an unsafe condition. 5. Do not use this equipment for other than its intended purpose. 6. Do not let power supply cords touch hot surfaces. 7. Before wiring to power supply, turn off electricity at fuse or circuit breaker. 8. Installation and servicing should be performed by qualified personnel. 9. CAUTION: When this equipment is furnished with halogen cycle lamp, these additional safeguards apply: a. To avoid shattering, do not operate lamp in excess of rated voltage. Protect lamp against abrasion and scratches and against liquids when lamp is operating. Dispose of lamps with care. b. Halogen cycle lamps operate at a high temperature. Do not store or place flammable materials near lamps. IMPORTANT The battery in this unit may not be fully charged. After electricity is connected to unit, let battery charge for at least 168 hours, then normal operation of this unit should take effect. To check, press the TEST button. The emergency lamps should illuminate. INSTALLATION 1. Remove cover and any packing material that may have been used for shipping purposes. 2. Determine the proper location for where the sign is going to be mounted. Remove cardboard template from the box and place against the ceiling tile or area of the ceiling where exit light is going to be installed and trace a line around the template (Figure A). This will be the area that is going to be cut out. You may want to do the cutting on the ground if possible. 3. Cut the rectangular hole out of the ceiling area (Figure B). 4. Mount the recessed housing in place using the bar hangers (Figure C). 5. Make adjustments to the bar hanger holder bracket to adjust the height of the recessed housing (Figure D). The proper height is having the bottom of the recessed housing even with the finished ceiling level (shown in Figure E). 6. Extend 24-hour AC supply of rated voltage to the equipment, which is furnished with a dual voltage 120/277VAC field selectable input (see illustration). For 120V supply, connect the line wire to the black lead; for 277V supply, connect the line wire to the orange/red lead. Connect neutral wire to the white lead. Connect ground wire in accordance with local codes. A green ground lead is provided. DO NOT energize circuit at this time. CAUTION: Insulate the unused black or orange wire. Failure to insulate the unused wire will cause an unsafe condition. NOTE: If a cord set is to be installed, follow separate cord set installation instructions INSTALLATION (continued) 7. Place TRIM PLATE & LIGHTING HEADS into recessed housing by pinching together the spring clips and hooking them into the SLOTS licated on the outside of the recessed housing. 8. Connect the JUMPER CONNECTORS to connect the LAMP HEADS, SWITCH WIRES & BATTERY (Figure F). 9. Slide the trim plate/lamp head assembly up and into the recessed housing (Figure G). 10.Screw in the two screws to securely mount the trim plate to the recessed housing. And also make any adjustments to the lamp heads at this time (Figure H). 11.Energize the AC supply. The CHARGE indicator will illuminate. OPERATION 1. To test the equipment, depress the TEST switch. The CHARGE indicator will go out and the emergency lights will illuminate. 2. Release the TEST switch. The emergency lights will go out and the CHARGE indicator will illuminate. 3. The automatic charger will resume and maintain the battery in a fully charged state. NOTE: Allow the battery to charge for a minimum of 24 hours after installation or after a power failure before conducting a 90-minute test (See TESTING). CAUTION: This equipment is furnished with a sophisticated solid state transfer switch which will automatically disconnect the emergency lights from the battery if: a. The battery has been discharged to the end of its useful output. b. The output circuit is overloaded. c. The output is shorted. FIG. A FIG. B FIG. C FIG. D FIG. E FIG. F FIG. G FIG. H (Continued on back) pg 1 of 2 INSTALLATION INSTRUCTIONS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR EMERGENCY LIGHTING FIXTURE – N7 SERIES IMPORTANT SAFEGUARDS: When using electrical equipment, always adhere to the basic safety precautions including the following: MAINTENANCE CAUTION: Always turn off AC power to the equipment before servicing. Servicing should be performed only by a qualified service technician. Use only MANUFACTURER supplied or APPROVED replacement parts. 1. BATTERY: The battery supplied in this equipment requires no maintenance. However, it should be tested periodically (See TESTING) and replaced when it no longer operates the connected load for the duration of a 30-second or 90-minute test. 2. OTHER: Clean lenses and replace lamps, as required. TESTING The NFPA 101, Life Safety Code requires that all emergency lighting equipment be functionally tested every 30 days for a minimum of 30 seconds and tested yearly for a full 90-minute duration. Written records of testing are to be kept for examination by the authority having jurisdiction. TROUBLESHOOTING 1. The emergency lights do not operate a. If the charge indicator light is off, check that the circuit breaker for AC supply is on. b. If the charge indicator light is on, check that battery is properly connected. If problem persists, replace battery. 2. Emergency lights are dim - battery not fully charged. Allow battery to recharge for 168 hours and then retest. If lights are still dim, replace battery. WIRING DIAGRAM WARRANTY Juno Lighting Group warrants that its products are free from defects in material and workmanship. Juno Lighting Group’s obligation is expressly limited to repair or replacement, without charge, at Juno Lighting Group’s factory after prior written return authorization has been granted. This warranty shall not apply to products which have been altered or repaired outside of Juno Lighting Group’s factory. This warranty is in lieu of all other warranties, expressed or implied, and without limiting the generality of the foregoing phrase, excludes any implied warranty of merchantability. Also, there are no warranties which extend beyond the description of the product on the company’s literature setting forth terms of sale. Product Services Phone (888) 387-2212 1300 S. Wolf Rd • P.O. Box 5065 • Des Plaines, IL 60017-5065 • Phone: 800-323-5068 • www.junolightinggroup.com ©2016 Acuity Brands Lighting, Inc. Rev 08/05 P0066 pg 2 of 2