® Heat Link SSP106RS SSP / SST Series SS Manifold Pump / Mixing Panel Installation, Operation, and Maintenance Manual SST106RS ™ MECHANICAL ROOM IN A BOX SSP106RL SST106RL L6SSPSST ® Heat Link www.heatlink.com Installation, Operation, and Maintenance SSP / SST – SS Manifold Pump / Mixing Panels Table Of Contents Warnings........................................................................................................................3 Tools Needed ...............................................................................................................3 Function .........................................................................................................................4 Unpacking.....................................................................................................................5 Panel Components ....................................................................................................6-7 Specifications ...............................................................................................................8 Panel Component Specifications .........................................................................9-16 Valve Adjustments (SST Series only)....................................................................11 Manifold Balancing ....................................................................................................12 Mounting.......................................................................................................................17-18 Piping Hookup ............................................................................................................19-20 Fill and Purge ...............................................................................................................21 Panel Wiring .................................................................................................................22 Panel Control Sequence & Wiring.........................................................................23 Troubleshooting .........................................................................................................24 Maintenance ................................................................................................................25 Application Drawings ...............................................................................................26-27 2 ® Installation, Operation, and Maintenance SSP / SST – SS Manifold Pump / Mixing Panels Heat Link www.heatlink.com Warnings The zone control panel is for indoor use only and must be installed by a qualified installer/service technician. This product must be installed and operated in strict accordance with the terms set out in this manual and in accordance with the relevant requirements of the Local Authority Having Jurisdiction. Failure to comply will result in a void of warranty, and may also result in property damage, serious injury, or death. Servicing Prior to commencing installation of this panel it is necessary to read and understand all sections of this manual. The symbols below are used throughout this document to ensure proper operation of the panel, and your safety. Please pay attention to these symbols. Warning Possible Hazard Warning Live Power Warning Hot Pipes Warning Treated Water In order to avoid injury or death, switch off the power to the panel prior to inspecting or making connections to the terminal strip. Disclaimer HeatLink Group Inc. shall not be responsible for errors in its brochures or printed materials. HeatLink Group Inc. reserves the right to alter its products at any time without notice, provided that alterations to products already on order shall not require material changes in specifications previously agreed upon HeatLink Group Inc. and the Purchaser. All trademarks in this material are property of the respective companies. HeatLink and the HeatLink logotype are trademarks of HeatLink Group Inc. All rights reserved. Tools For Installation • Level • Screwdriver or power drill • Flat head bit • Phillips head bit # 2 • 2 adjustable wrenches (or 2× 30mm wrenches and 2× 40mm wrenches) • O-ring Lubricant (#79951 or #79952) 3 ® Heat Link www.heatlink.com Installation, Operation, and Maintenance SSP / SST – SS Manifold Pump / Mixing Panels Function This panel can provide mixing (SST series only), distribution, and zoning for a wide variety of hydronic heating applications. The effectiveness of the system is dependant on the system being designed and installed correctly. Proper consideration of factors such as BTU loads, outdoor design temperature, indoor design temperature, room set-point temperature(s), differential fluid temperatures, head loss, flow rates, and transfer capacities of the heat emitters is critical. Once these factors have been considered and the system requirements determined, these can then be evaluated and compared to the zone control panel capabilities (refer to pages 6-11). Note: 4 This panel does not regulate or monitor the operating safety limit temperatures of the fluid leaving the heat source. ® Heat Link www.heatlink.com Installation, Operation, and Maintenance SSP / SST – SS Manifold Pump / Mixing Panels Unpacking Step 1 Examine carton for any damage that may have occurred during shipping. If damage is visible notify your courier and supplier immediately. Step 2 Open the carton by removing the strapping. Step 3 Remove the cardboard spacers from the carton, then remove the panel from the carton. Lift the panel by the enclosure, not the cover. This panel is heavy; 2-3 person lift required. Step 4 Remove the cover from the panel by unlocking the coin/screwdriver locks. Lift the top of the cover upwards to disengage the tongues from the slots at the bottom of the panel and then pull the cover off. Step 5 Verify the following items: Small pump • (2) 3⁄4" MBSP x 1" FNPT adapters • (4) 3⁄4" rubber washers (2 spares) • (1) 1" rubber washers (1 spares) Large pump • (2) 1" MBSP x 1" FNPT adapters • (6) 1" rubber washers (4 spares) 5 ® Installation, Operation, and Maintenance SSP / SST – SS Manifold Pump / Mixing Panels Heat Link www.heatlink.com Panel Components Part Number # Component SSP1xxRS SSP1xxRL SST1xxRS SST1xxRL 1 Primary Pump PUMP1558 PUMP2699 PUMP1558 PUMP2699 2 Power Box PWRB1R2 PWRB1R2 PWRB1R2 PWRB1R2 3 Stainless Steel Manifold 76100 series 76100 series 76100 series 76100 series Flow Meter Valve Insert (supply) (0-1.5 US gpm lock nut) 76916 76916 76916 76916 Zone Valve Insert (return) 76911 76911 76911 76911 4 3-way Mixing Valve n/a n/a 63716 63725 5 Automatic Air Vent 79932 79932 79932 79932 6 Thermometer 76940 76940 76940 76940 7 SS Manifold Port Caps 77100 77100 77100 77100 8 Hose Bib – – – – 9 Isolation Ball Valve – – – – 10 Enclosure – – – – 11 Cover – – – – 12 Accessory Pack ACCSSSML ACCSSLRG ACCSSSML ACCSSLRG ⁄4" Washer WHTWSH34 WHTWSH34 WHTWSH34 WHTWSH34 1" Washer NTRWSH1 NTRWSH1 NTRWSH1 NTRWSH1 3 Optional Installed Items 13 SSAPB - Installed Accessory Pressure Bypass for SS Manifolds 14 15 76936 76936 76936 76936 SSATH - Installed Accessory Thermostatic Head for Manifold Mixing Panels n/a n/a 57094 57094 SSADDC - DDC Actuator Installed on Mixing Valve n/a n/a 56121 56121 71902 71902 71902 71902 77105 77105 77105 77105 Sold Separately 16 Key Lock ⁄2" 1 17 PEX to Manifold Connecters ⁄8" 77119 77119 77119 77119 ⁄4" 77122 77122 77122 77122 5 3 11 16 6 17 ® Installation, Operation, and Maintenance SSP / SST – SS Manifold Pump / Mixing Panels Heat Link www.heatlink.com SSP106RS shown SST106RS shown with SSATH 5 10 5 10 2 6 8 6 3 8 1 3 7 1 7 3 8 9 4 7 9 12 SSP106RL shown with SSAPB 10 14 3 8 7 2 9 9 SSP & SST small pump accessory pack SST106RL shown with SSADDC 5 10 2 5 6 2 6 13 3 8 1 3 7 1 7 15 3 8 8 7 9 3 7 9 12 4 9 9 SSP & SST large pump accessory pack 7 ® Installation, Operation, and Maintenance SSP / SST – SS Manifold Pump / Mixing Panels Heat Link www.heatlink.com Specifications SSP Series - SS Manifold Pump Panels SSP104RS Dimensions Weight Nominal panel output Nominal flow Nominal pressure drop outside of panel Max ambient temperature Max water temperature Circulator Power supply: pre-wired on system controller Auxiliary terminal Piping Piping connections Enclosure SSP106RS SSP104RL SSP106RL SSP108RS SSP110RS SSP108RL SSP110RL 36-3⁄4"H × 37-1⁄2"W × 5-7⁄8"D 36-3⁄4"H × 49-1⁄8"W × 5-7⁄8"D 62 lbs. 64 lbs. 68 lbs. 70 lbs. 109 lbs. 111 lbs. 115 lbs. 117 lbs. 45,000 61,000 62,000 87,000 76,000 111,000 88,000 132,000 Btu/h Btu/h Btu/h Btu/h Btu/h Btu/h Btu/h Btu/h 4.5 US gpm 6.1 US gpm 6.2 US gpm 8.7 US gpm 7.6 US gpm 11.1 US gpm 8.8 US gpm 13.2 US gpm @ 20°F ΔT @ 20°F ΔT @ 20°F ΔT @ 20°F ΔT @ 20°F ΔT @ 20°F ΔT @ 20°F ΔT @ 20°F ΔT based on 250' loops of 1⁄2" tubing 120°F 180°F Non-ferrous, Grundfos Ferrous, Grundfos Non-ferrous, Grundfos Ferrous, Grundfos UPS15-58RU UPS26-99FC UPS15-58RU UPS26-99FC 110 V(ac); 110 V(ac); 110 V(ac); 110 V(ac); max. current 2A max. current 3A max. current 2A max. current 3A Yes, dry contacts, 1×2 terminal strip, screw type, max. load 1.5A 3 3 ⁄4" 304SS tubing 1" 304SS tubing ⁄4" 304SS tubing 1" 304SS tubing 1" FNPT Galvanized steel, visible parts are satin coated steel. SST Series - SS Manifold Mixing Panels SST104RS Dimensions Weight Nominal panel output Nominal flow Nominal pressure drop outside of panel Max ambient temperature Max water temperature Circulator Power supply: pre-wired on system controller Auxiliary terminal Temperature control method Mix Valve Cv Piping Piping connections Enclosure 8 SST106RS SST104RL SST106RL SST108RS SST110RS SST108RL SST110RL 36-3⁄4"H × 37-1⁄2"W × 5-7⁄8"D 36-3⁄4"H × 49-1⁄8"W × 5-7⁄8"D 65 lbs. 67 lbs. 71 lbs. 73 lbs. 114 lbs. 116 lbs. 120 lbs. 122 lbs. 57,000 45,000 77,000 49,000 93,000 52,000 104,000 37,000 Btu/h Btu/h Btu/h Btu/h Btu/h Btu/h Btu/h Btu/h 3.7 US gpm 5.7 US gpm 4.5 US gpm 7.7 US gpm 4.9 US gpm 9.3 US gpm 5.2 US gpm 10.4 US gpm @ 20°F ΔT @ 20°F ΔT @ 20°F ΔT @ 20°F ΔT @ 20°F ΔT @ 20°F ΔT @ 20°F ΔT @ 20°F ΔT based on 250' loops of 1⁄2" tubing 120°F 180°F Non-ferrous, Grundfos Ferrous, Grundfos Non-ferrous, Grundfos Ferrous, Grundfos UPS15-58RU UPS26-99FC UPS15-58RU UPS26-99FC 110 V(ac); 110 V(ac); 110 V(ac); 110 V(ac); max. current 2A max. current 3A max. current 2A max. current 3A Yes, dry contacts, 1×2 terminal strip, screw type, max. load 1.5A 1 1 ⁄2" 3-Way 1" 3-Way ⁄2" 3-Way 1" 3-Way 2.9 5.3 2.9 5.3 3 3 ⁄4" 304SS tubing 1" 304SS tubing ⁄4" 304SS tubing 1" 304SS tubing 1" FNPT Galvanized steel, visible parts are satin coated steel. ® Installation, Operation, and Maintenance SSP / SST – SS Manifold Pump / Mixing Panels Heat Link www.heatlink.com Panel Component Specifications Power Box Auxiliary Contacts Bypass OFF PUMP ON POWER This module provides the required power for all electronic components on the panel, via the ON/OFF switch. Power box may not be exactly as shown. PWRB1R2 CAUTION When wiring Thermostat to Terminal Strip: DO NOT CROSS terminals C and R This will cause damage to 24V transformer in this powerbox. Specifications: • Requires 115V power source. • Requires a maximum 15A circuit breaker. Thermometer (76940) The pipe mounted thermometer reads the supply fluid temperature. Specifications: • Temperature range of 32-210°F (0-100°C). 9 ® Installation, Operation, and Maintenance SSP / SST – SS Manifold Pump / Mixing Panels Heat Link www.heatlink.com Circulators The circulators moves the heated fluid through the hydronic system when there is a call for heat from the thermostat. Factory set to 3rd speed. Specifications: • The following pump curves apply. UPS15-58CIL2 Pump Curve 20 18 16 Head (feet) 14 12 10 8 6 4 2 0 0 2 4 6 8 10 12 14 16 Flow (gpm) 1st Speed 2nd Speed 3rd Speed UPS26-99FC Pump Curve 35 30 Type UPS 26-99 FC 115 V 1 PH 60 Hz 20 uF P 1 (w) 1.30 150 1.50 179 1.80 197 P/N: 52722512 P1 PC: 0939 US |1/1 (A) Class F IMPEDANCE PROTECTED 99K4 UL C US LISTED MAX. FlUID TEMP. 230˚F FOR INDOOR USE ONLY U LISTED L Head (feet) 25 20 15 99K4 10 5 0 0 5 10 15 20 25 Flow (gpm) 1st Speed 10 2nd Speed 3rd Speed 30 35 ® Installation, Operation, and Maintenance SSP / SST – SS Manifold Pump / Mixing Panels Heat Link www.heatlink.com 3-way Mixing Valve (SST Series only) A AB B A AB Three-way mixing valve for fluid temperature control in heating and cooling systems. Bronze valve body with brass nipples, protective cap, and stainless spindle with double O-ring seal. Outer O-ring replaceable without draining of system. Specifications: • Material - Housing: Bronze • Material - Spindle: Stainless steel • Spindle Sealing: 2 o-rings Valve open: A-AB is open A-AB is closed B-AB is closed B-AB is open Valve Pressure Loss in ft H2O 10 TL SS SS TS arg ma ll Valve closed: e B 1 0.1 0.01 0.1 1 10 50 Flow Rate in US gpm 11 ® Installation, Operation, and Maintenance SSP / SST – SS Manifold Pump / Mixing Panels Heat Link www.heatlink.com Stainless Steel Manifold Specifications: • Material: Stainless Steel EN 1.4301 (X5CrNi18-10) which is equivalent to SAE 304 (V2A) • Maximum Trunk Flow Rate: 18 US gpm (4.1 m3/h) • Maximum Circuit Flow Rate: 1.5 US gpm (0.34 m3/h) Return Manifold Primary Balancing. Black cap for manual shut-off only. Use drip cap ➀ for balancing. Supply Manifold Secondary Balancing (Fine Tuning). Flow meter balancing adjustment range: 0-1.5 US gpm or 0-5 L/min. Remove locking cap to adjust flow meter. Please note: Do not use tools to adjust flow meters. (Damage to the flow meter will occur, and will not be covered under warranty). 1 CCW = open CW = close CCW = open Balancing Notes: Return : Use for primary balancing purposes and manual shut-off. Use drip cap to adjust the return manifold.➀➁ Caution: Opening the return valve too far will result in removing the valve stem. Supply : Use for secondary balancing / fine tuning the flow rate. Remove locking cap to adjust the flow meter by hand, do not use tools. Balancing Method 1: Valve setting or flow characteristic known (pre-balancing) 1. Fully open supply valve (flow meter) [factory open]. 2. Close return valve completely [factory open]. 3. Open return valve the number of turns as per heatloss calculation or friction head graph. 4. After all valves are set, field adjustments may be necessary. 12 Balancing Method 2: Only flow rate known 1. Ensure all supply valves are open [factory open]. 2. Ensure all return valves are open (remove black cap). 3. Use the return valve to adjust flow to desired setting (flow meter). 4. Valves adjusted first may need to be re-adjusted once all other loops have been set. CW = close 1 2 Notes: • Hose bib thread is an ASME thread.➁ • After fill procedure: the drip cap ➀ should be placed back on to the hose bib ➁. • Pipe to manifold connectors sold separately. ® Installation, Operation, and Maintenance SSP / SST – SS Manifold Pump / Mixing Panels Heat Link www.heatlink.com Stainless Steel Manifold # of turns from closed position 0.25 30 (90) 0.5 0.75 1 1.5 2 3.5 10 (30) Pressure Drop in ft H2O (kPa) 5 (15) 1 (3) 0.5 (1.5) 0.1 (0.3) 0.05 (0.15) 0.01 (0.03) 0.01 (0.04) 0.05 (0.19) 0.1 (0.38) 0.5 (1.89) 1 (3.78) 3 (11.36) Mass Flow Rate in US gpm (L/min) Working loop flow ranges from 0.1 to 1.25 US gpm (0.38 to 4.7 L/m) for floor heating and from 1.5 to 2.5 US gpm (5.7 to 9.5 L/m) for snowmelting. Pressure drop must be closely checked when water flow is beyond the upper working range. 13 ® Installation, Operation, and Maintenance SSP / SST – SS Manifold Pump / Mixing Panels Heat Link www.heatlink.com SSADDC - Optional DDC Actuator Installed on Mixing Valve (#56121; SST Series only) These actuators allow for additional room temperature control in conjunction with a direct digital control system. Specifications: • Operating Voltage: 24 V(ac), 50/60Hz • Control Voltage: 0-10 V(dc), RE = 100kΩ • Power Consumption: 2 VA • Max. Current: max. 250 mA for max. 2 min • Type: Normally Closed • Opening and Closing Time: 3 min • Protection Class: IP 54 • Force: 100 N ± 5% • Cable Length: 1 m / 3.28 ft (removable) • Standards / Listings: CE Sample Wiring Diagram Red + 0-10V DC Blue 0 24V~ AC Black - Travel (mm) 4 3 Valve travel=0 2 1 Range beyond valve travel Valve adapter rim 0 14 1 2 3 4 5 6 7 UST in V active control voltage range 8 9 10 ® Heat Link www.heatlink.com Installation, Operation, and Maintenance SSP / SST – SS Manifold Pump / Mixing Panels Assembly Screw the valve adapter onto the valve and hand tighten. Align the actuator and push down until it snaps it into place. Make all necessary electrical connections according to the diagram. Standby After the voltage has been removed for 20 min. the actuator is still in a standby mode. The valve is closed, however when a voltage is applied again the actuator can respond rapidly. Signal Noise The actuator reacts only to voltages starting from 1V DC to avoid reaction to signal noise. “First open” function The actuator is delivered in an open position. When power is applied, the calibration process cancels the first open function, ie. the actuator is ready for operation in ~6 min. Automatic calibration When voltage is first applied and approx. twice each day the actuator performs a calibration process, in order to adjust itself to the valve. During this process the actuator opens and closes completely, and important points are stored. During this process the control voltage is ignored. If the results deviate then the calibration is repeated. After calibrating itself the actuator response is proportional to the applied voltage. Adaption check After releasing the first open function and commissioning, the adaption between the valve and the actuator can be inspected. When no voltage is applied, the function indicator should be elevated slightly. It should not be flush with the body nor should the indicator region be visible. Function indicator The current operating status can be seen at the function indicator. Disassembly Press down on the lower front cover button and pull up the actuator. Do not use force to open the body. To prevent removal of the actuator from its mount simply remove the front cover. Notes If the power supply cable is damaged, it must be replaced by the manufacturer or its service agent or a similarly qualified person in order to avoid a hazard. A contact separation of at least 3 mm in all poles must be incorporated in the fixed wiring. Ensure the power supply is isolated via a safety transformer. The actuator is not protected against valve leaks. 15 ® Heat Link www.heatlink.com Installation, Operation, and Maintenance SSP / SST – SS Manifold Pump / Mixing Panels SSATH - Optional Installed Accessory Thermostatic Head (#57094; SST Series only) Sensing Bulb Used as injection control for HeatLink® zone valves. Senses 0.4°F (0.2°C) supply water change. Takes 15 minutes to close from full open. Specifications: • Temperature Setting Range: 96-150°F (36-66°C) • Sensor: Liquid filled contact sensor • Type: Normally closed Capillary Setting arrow Notes: Do not use any tools when installing the thermostatic head onto the zone valve! Hand tighten only! Do not kink capillary when installing the head!! Doing so will render the capillary unusable. SSAPB - Optional Installed Accessory Pressure Bypass (#76937) Adjustable pressure bypass valve kit for 76100 and 76200 series stainless steel manifolds. This valve prevents a steep rise of the pump head and maintains flow at a stable rate. Also ensures only required amount of circulating water is used for hydronic systems. Specifications: • Adjustment Range: 0.05 - 0.5 bar (1.67 - 16.73 ft H2O) 16 ® Installation, Operation, and Maintenance SSP / SST – SS Manifold Pump / Mixing Panels Heat Link www.heatlink.com Mounting Step 1 Use a screwdriver or similar thin tool through the hole to bend the mounting tabs out 90 degrees from the enclosure. Step 2 If electrical wiring will be coming from the top, remove the appropriate knockouts. 26-7/16" 20-7/16" 14-9/16" 7/8" O.D. 10-1/16" 3-3/4" 36" 38-1/16" 32-1/16" 14-9/16" 7/8" O.D. 10-1/16" 3-3/4" 47-5/8" Step 3 Build a 2×6 supporting frame where the panel is to be mounted. The panel should be mounted at least 12" above the floor. 17 ® Heat Link www.heatlink.com Installation, Operation, and Maintenance SSP / SST – SS Manifold Pump / Mixing Panels Mounting continued Step 3 Lift and place the panel onto the supporting frame. This panel is heavy; 2-3 person lift required. Step 4 Complete the supporting frame by adding a top plate. Be sure to drill corresponding holes in the top plate if any knockouts were removed. Step 5 Secure the panel in place by putting screws into each of the mounting tabs. Note: Panel contents are not shown in the diagrams. 18 ® Heat Link www.heatlink.com Installation, Operation, and Maintenance SSP / SST – SS Manifold Pump / Mixing Panels Piping Hookup Step 1 Before making any connections, identify the required connections to and from the panel. Adapters are 3⁄4" M BSPP × 1" FNPT or 1" M BSPP × 1" FNPT, and must use the supplied adapters and rubber washers. Step 2 Connect all adapters. 1. Connect MNPT adapter E to copper pipe or tubing F . 2. Screw supplied M × FNPT adapter D onto E using appropriate thread sealant. 3. Take assembly D E F and place rubber washer C on flat surface of D . 4. Without disturbing rubber washer C , place assembly against flanged stainless steel pipe B . 5. Slide nut A over adapter D and finger tighten nut. Then, tighten the nut (using two 40mm wrenches for 1" adapters or 30mm wrenches for 3⁄4" adapters), taking care not to overtighten the nut, as this will damage the rubber washer. SST106RL shown Floor Supply Floor Return Primary Return Primary Supply A B C D E F Do not overtighten brass nuts! Note: Use precautions when soldering or applying heat within 16" of the panel. 19 ® Heat Link www.heatlink.com Installation, Operation, and Maintenance SSP / SST – SS Manifold Pump / Mixing Panels Piping Hookup continued Step 3 Connect all tubing to manifold adapters. (77100 series connectors sold separately) 1. Lubricate the inside of the manifold port with silicone o-ring lubricant (#79952 sold separately). 2. Cut the PEX tubing at a 90˚ angle. 3. Place the Nut and Split Ring Ferrule onto the PEX tubing. Method A 5. Push the Brass Insert onto the PEX tubing as far as it will go. 6. Push the PEX tubing with Brass Insert as far as it will go into the manifold module. Ensure the o-ring is clean and take care not to pinch it. Method B 5. Push Brass Insert as far as it will go into the manifold. Ensure the o-ring is clean and take care not to pinch it. 6. Push PEX tubing onto the Brass Insert as far as it will go. 7. Use a wrench to tighten the nut. 90° Brass Insert with O-ring Split Ring Ferrule Nut 20 ® Installation, Operation, and Maintenance SSP / SST – SS Manifold Pump / Mixing Panels Heat Link www.heatlink.com SSP Series Fill And Purge The following steps are recommended in order to fill the panel with water and purge entrained air once piping is completed, and before activation of the panel. E The discharged system fluid from the fill and purge process is not for consumption or washing. C D F A Note: Additional purging steps may be required for the rest of the hydronic system. Note: Isolation and drain valves are not included with the panel, but are necessary to properly fill and purge the panel, and to isolate the panel for service. Step 1 Ensure the panel is not powered. Step 2 SST Series only - Adjust the mixing valve G so that it is fully open (i.e. cap removed). If a DDC actuator or Thermostatic Head is installed, it must be removed. Step 3 Fully close valves A , B , and C . Fully close all supply E and all return F manifold valves. Fully open valve D . Step 4 Attach a purge hose (not included) to the main supply line. Open valve B . D SST Series . Pressurize E C Step 5 Open the first return manifold valve F . Open the first supply manifold valve E . Watch the hose in the pail until you observe a steady stream of water (no air or spitting). Close the first return manifold valve F . Step 6 Repeat Step 5 for each loop until all loops are filled with water, and air is purged from pipes. Step 7 Purging is complete when there is no more air and/or spitting. Close valve D then valve B . Step 8 Remove hose from drain valve Step 9 Check for leaks at connections. If any leaks are found use a back-up wrench and carefully tighten until leak stops. Do not overtighten. Step 10 SST Series only - Redjust the mixing valve G to provide a proper mixed fluid temperature to the hydronic system (see page 11). If a DDC actuator or Thermostatic Head was removed, reinstall it. D B D G F A B . 21 ® Installation, Operation, and Maintenance SSP / SST – SS Manifold Pump / Mixing Panels Heat Link www.heatlink.com Panel Wiring Note: Terminal headers are removable to make wiring connections easier. Thermostat Wiring • 24V low voltage power may be supplied to the thermostat. Wiring of thermostat should be done by qualified electrician and should meet local codes and jurisdictions. Wiring to the terminal strip requires 18 gauge 4 wire. 2-Wire Thermostat (battery only or non-electric) Signal C AUX 3-Wire Thermostat (HeatLink thermostats) Jumper to Dry Contact W R 24 V AUX 24 V C 24 V W R 24 V Signal 24 V Signal • Do not exceed 2VA. • Do not cross terminals C and R – this will damage the Power Box. W R C AUX 4-Wire Thermostat (with dry contact signal) Other Terminals Auxiliary Contacts The auxiliary contact set is dry, meaning no supply of power is present at the terminal. The maximum allowable load is 1.5A. The auxiliary dry contact located on the terminal is to switch another device (ie. the heat source) when there is a call for heat from any zone. 110V Power 110V power wiring should be done by qualified electrician and should meet local codes and jurisdictions. Field Wiring To Thermostat To Heat Source Contacts W R C Thermostat Connection Auxiliary Contacts BYPASS OFF PUMP ON PB2R1 POWER CAUTION When wiring Thermostat to Terminal Strip: DO NOT CROSS terminals C and R This will cause damage to 24V transformer in this powerbox. Field Wiring Ground Neutral Live 22 ® Installation, Operation, and Maintenance SSP / SST – SS Manifold Pump / Mixing Panels Heat Link www.heatlink.com Panel Control Sequence 1. When power is provided to the 110V terminals connected to the power module 1 , and the 3-way switch is placed in the “ON” position the red LED will be lit, indicating that the panel is powered with 110V. 2. The Bypass function for the 3-way switch is for troubleshooting purposes only. Only switch to the Bypass position if the red and green LED’s on the power module do not light up during a call for heat. Please refer to the troubleshooting section of the manual for further details. 3. When the thermostat calls for heat, its internal 24V contacts close, the auxiliary terminals close, and the pump turns on. 4. SST panels only - As the circulator on the user settings (page 11). 5. When the requirements of the thermostat are met, the internal contacts of the thermostat open, the auxiliary contacts open, and the circulator stops. 2 moves fluid through the panel the mixing valve adjusts the fluid temperature based Field Wiring To Thermostat To Heat Source Contacts W R C Thermostat Connection Auxiliary Contacts 1 BYPASS OFF PUMP ON PB2R1 POWER CAUTION When wiring Thermostat to Terminal Strip: DO NOT CROSS terminals C and R This will cause damage to 24V transformer in this powerbox. Field Wiring Ground Neutral Live 2 23 ® Installation, Operation, and Maintenance SSP / SST – SS Manifold Pump / Mixing Panels Heat Link www.heatlink.com Troubleshooting Problem Check / Verify Possible Cause Low Temperature Within Room Misplacement of thermostat location within room. Make sure thermostat is not being influenced by an additional heat source, such as lighting or air duct. Low temperature setting of the thermostat. Adjust the temperature setting on thermostat. The system fails to turn on if the thermostat is set to high setting Thermostat may be out of calibration or defective. Replace thermostat. The electronic actuator fails to open during a call for heat The electronic actuator may be improperly seated or may be defective. Replace if necessary. Low supply mixed fluid temperature. Adjust the power box to the appropriate setting. Wiring from heat source to panel. Check that the wiring is done properly. Consult qualified electrician prior to alteration of wiring between heat source and panel. Output of heat source is unable to meet demand of heating system. Compare output of heat source to the requirements of the heating system. The red and green LED’s on the power module The zone valve controller may be defective or do not light up during a call for heat. there is no power being supplied to the panel or the power module is not on. If this is so, switch the power module to Bypass mode. The green LED will be lit, indicating that the panel is powered with 110V and the pump will run. This will provide constant circulation so long as there is still 110V power to the panel. High Temperature Within Room 24 Circulator is not on during a call for heat. (Use a stethoscope or similar device to verify) The power box or circulator may be defective. When zone valves are installed outside the panel a qualified electrician should verify 24V power is supplied to the thermostats and actuator. The power module only supplies enough power for a thermostat; any external actuators must be powered from an external 24V transformer. The 24V transformer may have failed. If this so, switch the power module to Bypass mode. This will provide constant circulation so long as there is still 110V power to the panel. Prior to Bypass mode selection, any zone valves must be opened manually to avoid deadheading of the circulator. Check current setting of the thermostat. Adjust the temperature setting on thermostat to a lower setting. High supply mixed fluid temperature. Adjust the Thermostatic Mixing Valve to the appropriate settings. Installed electronic actuators remain open after the thermostat is satisfied. An obstruction inside the zone valve is not allowing the actuator to fully close or the thermostat is still calling for heat. Bypass may be on. Check that the Power switch on the power box is in the “ON” position. ® Heat Link www.heatlink.com Installation, Operation, and Maintenance SSP / SST – SS Manifold Pump / Mixing Panels Maintenance Yearly maintenance should be done on the panel prior to each heating season to ensure the efficient and accurate operation of the panel. Complete the following check list: • Raise all thermostats to cause a call for heat within the system. Verify that the circulator starts, via a stethoscope or similar device. • Confirm that the Auxiliary Contacts close. • If applicable, verify that each zone valve opens during the call for heat – the actuator should be warm to the touch, the LED will light up (on 5620x models) and the white indicator should rise from the top of the actuator. • Return all thermostats to a desirable setting. You are now ready for another heating season with HeatLink. 25 ® Heat Link www.heatlink.com Installation, Operation, and Maintenance SSP / SST – SS Manifold Pump / Mixing Panels SSP Series Manifold Pump Panels SSP Series For all of these models, primary piping with circulator must have no pressure differential between panel primary supply and return, i.e. close tees. Heat Source (e.g. boiler or heat exchanger) Notes: A) This drawing is for illustrative purposes only. It is not intended to be used as a wiring or piping diagram. Not all required components are shown. Local codes, regulations, and authorities have final jurisdiction. 26 ® Heat Link www.heatlink.com Installation, Operation, and Maintenance SSP / SST – SS Manifold Pump / Mixing Panels SST Series Manifold Mixing Panels SST Series For all of these models, primary piping with circulator must have no pressure differential between panel primary supply and return, i.e. close tees. Heat Source (e.g. boiler or heat exchanger) Notes: A) This drawing is for illustrative purposes only. It is not intended to be used as a wiring or piping diagram. Not all required components are shown. Local codes, regulations, and authorities have final jurisdiction. 27 Canada Manufactured & distributed by HeatLink Group Inc. Head Office: 4603E - 13th Street N.E. Calgary, Alberta, T2E 6M3 Eastern Canada Distribution Center: 2810 Argentia Road, Units 5-7 Mississauga, Ontario, L5N 8L2 Toll Free: 1-800-661-5332 Fax: 1-866-450-1155 China Distributed by Cathay-Links International Phone: 852-25693213 Fax: 852-25359271 Ireland Distributed by Jamoni Ltd. Phone: 057 - 932 4062 Fax: 057 - 932 4063 Freephone: 1800-311338 México Distributed by Distribuidora Caisa S.A. de C.V. Phone: (52-55) 3300-4400 Fax: (52-55) 3300-4406 United States Distributed by HeatLink Group Inc. USA Distribution Center: 1000 - 100th Street SW, Suite B Byron Center, MI, 49315 Toll Free: 1-800-661-5332 Fax: 1-800-869-6098 www.heatlink.com HeatLink, the HeatLink logo, and “Mechanical Room in a Box” logo are either registered trademarks or trademarks of HeatLink Group Inc. August 1, 2013 Printed in Canada © HeatLink Group Inc.