ATTACHMENT C TRANSFORMER DATA JULY, 2009 A E R C O U S T I C S ___________________________________________________________________________________E N G I N E E R I N G L I M I T E D Specification Power Transformers Technical Data Information Page 2 of 8 August 2006 063-P005328-0163-02-EA-0001-0B Specification Power Transformer Final version for Item 1B dated July 6, 2007 POWER TRANSFORMERS 1. Continuous ratings (For all windings) 2. (a) (b) (c) Number of phases 3. ONAN ONAF ONAF 66 88 110 3 MVA MVA MVA Frequency 60 Hz 4. Voltage ratio +/-8 x 1.125 kV 5. Winding Connections YNd11 6. Losses (guaranteed) (a) (b) (c) 7. No-Load loss at rated voltage, rated tap 92.5 kW* Load Loss at self-cooled rating, rated tap, 85°C 71 kW Total loss at self-cooled rating, rated voltage, rated tap, 85°C ___________ kW (d) Fans and/or pumps 6 kW Impedances at self-cooled rating, rated tap voltage, 85°C (a) Positive sequence (i) HV-LV, rated tap (ii) HV-LV, maximum tap (iii) HV-LV, minimum tap (b) zero sequence 4.50 4.64 4.47 % % % (i) 4.00 % HV-LV, rated tap * Guaranteed values, subject to the tolerances permitted in CSA Standard CAN3-C88-M79 8. Efficiencies at self-cooled rating, rated voltage, rated tap, 80°C, 1.0 PF 9. (a) 125% (b) 100% 99.769 (c) 75% 99.751 (d) 50% 99.688 (e) 25% 99.452 Regulation at self-cooled rating, rated voltage, rated tap, 80°C % % % % % Specification Power Transformers Technical Data Information Page 3 of 8 August 2006 063-P005328-0163-02-EA-0001-0B Specification Power Transformer Final version for Item 1B dated July 6, 2007 10. (a) 1.0 PF (b) 0.8 PF Flux density at rated voltage, rated tap Tesla Tesla 11. (a) Limbs 1.720 (b) Yokes 1.720 Current density at self-cooled rating, rated tap 1.31 1.25 A/mm² A/mm² 12. (a) HV winding (b) LV winding Exciting current on rated tap 0.3 0.3 A A 13. (a) 100% rated voltage (b) 110% rated voltage Basic insulation levels (BIL) 950 95 170 kV kV kV 14. (a) Windings (i) HV line end (ii) HV neutral end (iii) LV line end Winding construction and materials Disc Helical cu cu 15. (a) (b) Core construction core type 3 core 16. (a) shell or core type (b) Number of limbs Off-circuit tap changer N/A ______________ ______________ ______________ ______________ % % kV kV kV 17. (a) Range (b) Steps (c) Rated voltage (d) Rated current (e) BIL On-Load Tap Changer (a) (b) (c) (d) HV LV Manufacturer Resistor or reactor type Catalogue No. Winding location 0.201 2.852 ABB Comp. Resistor type ______________ Sep. reg. winding % % Specification Power Transformers Technical Data Information Page 4 of 8 August 2006 063-P005328-0163-02-EA-0001-0B Specification Power Transformer Final version for Item 1B dated July 6, 2007 (i) (ii) (iii) (iv) (v) (vi) (e) Range (f) Steps (g) Rated voltage (h) Rated current (i) BIL (j) Operating time (k) Drive motor Rating Voltage Number of phases Full load current Starting current Class of insulation (l) (m) 18. % steps kV A kV sec 0.37 440-480 HP V 1.1 - A 3 Lowest temperature at which tap changer will operate satisfactorily -25 C Estimated diverter contact life (operations at transformer full load current) 500 000 Cooling (i) (ii) (iii) (iv) (v) (vi) (vii) 19. +/-10 16 600 380 - (a) Fan motors Number Rating Voltage Number of phases Full load current Starting current Class of insulation 16xF26D 1/3 460 HP V 3 0.7 A 2.1 A F with class B temp. rise Bushings (i) (ii) (iii) (iv) (v) (vi) (a) HV Line Manufacture Type Catalogue No. Voltage class Current rating Creepage distance (b) HV neutral ABB Alamo 362W0800UB W11B873BB 326 800 262.125 kV A inch Specification Power Transformers Technical Data Information Page 5 of 8 August 2006 063-P005328-0163-02-EA-0001-0B Specification Power Transformer Final version for Item 1B dated July 6, 2007 (i) (ii) (iii) (iv) (v) (vi) (i) (ii) (iii) (iv) (v) (vi) Manufacture Type Catalogue No. Voltage class Current rating Creepage distance (c) LV Line Manufacture Type Catalogue No. Voltage rating Current rating Creepage distance (i) (ii) (iii) (iv) (v) (vi) (d) LV neutral Manufacture Type Catalogue No. Voltage rating Current rating Creepage distance N/A (i) (ii) (iii) (iv) (v) (vi) (e) TV line Manufacture Type Catalogue No. Voltage rating Current rating Creepage distance N/A (i) (ii) (iii) (iv) (v) (vi) (f) TV neutral Manufacture Type Catalogue No. Voltage rating Current rating Creepage distance (g) (h) Core ground Voltage rating ABB Alamo 025W0412AT W7B522BB 25 400 21 kV A inch ABB.Alamo 046W2000UD W17B450BB 46 2000 59.906 kV A inch N/A Rod bushing F310H ________________ kV Specification Power Transformers Technical Data Information Page 6 of 8 August 2006 063-P005328-0163-02-EA-0001-0B Specification Power Transformer Final version for Item 1B dated July 6, 2007 20. Weights (a) (b) (c) (d) (e) (f) Core and windings Tank and fittings Oil Total Heaviest piece of shipping Filling medium for shipping 21. Volume of conservator 22. Dimensions (i) (ii) (iii) (i) (ii) (iii) 23. 24. 25. 92.900 kg 44.300 kg 43.150 kg 180.350 kg 115.700 kg ________________ ~3950 (a) Overall Height 7900 Length 8200 Width 4300 (b) Shipping (largest piece) Height 4600 Length 8200 Width 3100 (c) Height to remove core and windings (excluding lifting gear) (d) Height to remove HV bushings (excluding lifting gear) l mm mm mm mm mm mm - mm - mm Vacuum (a) (b) Required during filling operations _____________ Maximum permissible 0.095 MPa (a) (b) Manufacture Type Oil Nynas or Ergon _________________ Auxiliaries (i) (ii) (a) Gas detector relay Manufacture Type ABB Model 12 Specification Power Transformers Technical Data Information Page 7 of 8 August 2006 063-P005328-0163-02-EA-0001-0B Specification Power Transformer Final version for Item 1B dated July 6, 2007 (iii) Catalogue No. ________________ (i) (ii) (iii) (b) Winding temperature indicator Manufacture Type Catalogue No. Qualitrol 104-250 ________________ (i) (ii) (iii) (c) Pressure relief device Manufacture Type Catalogue No. Qualitrol 208-007-04 _______________ (i) (ii) (iii) (d) Voltage regulating relay Manufacture not included in scope of supply Type ________________ Catalogue No. ________________ (e) 26. Other control devices and auxiliary equipment to be itemized below : Noise level: Noise level of the transformer measured at 100 % of the nominal voltage with all cooling motors in operation measured according to ANSI/IEEE C57.12.90 76 dB(A) Mode ONAN 75 dB(A) 26. Drawings The following drawings are included with this bid: Drawing No. Preliminary dimension drawing PL-3764-07 dated February 14 2007. Other: Specification Power Transformers Technical Data Information Page 8 of 8 August 2006 063-P005328-0163-02-EA-0001-0B Specification Power Transformer Final version for Item 1B dated July 6, 2007 27. Descriptive Literature The following descriptive literature is included with this bid: 28. Gasket materials The type of gasket materials and applications will be as itemized below: 29. Method of shipment Description of method used for delivery of materials to site: 30. Special tools All special tools required for installation and maintenance of the equipment are itemized below: 31. Erection estimate Estimate of man-hours required to fully assemble the transformers at Site: ** Per transformer N/A man-hours for assembling transformer including vacuum filling and commissioning. 32. Repair facilities Name and address of nearest repair facilities and serviceman: 33. Further information and recommendations: 34. Maximum insulation Power Factor Test value. - %