MIEE – Chapter 22 – Mobile Generator Link Box (MGLB) 22 Mobile Generator Link Box (MGLB) 22.1 Background Mobile generators are used throughout Defence in various forms to ensure continuity of power supply during times of extended power outages or for deployable sites where there is a need to connect deployable generators and mains power supply may be unavailable. This policy describes the Defence requirements for Mobile Generator Link Boxes (MGLB) used to connect mobile generators to building and equipment loads. MGLB are switchboards provided to enable the safe and convenient connection of mobile generators, either hire or Defence owned generators, to building and equipment loads. MGLB can be required for deployable equipment hardstands and other important facilities when the expense of a permanent Local Emergency Generator (LEG) cannot be justified. MGLB are also provided for each LEG installation to facilitate continued generator support when the LEG is unserviceable, or undergoing extended maintenance. 22.2 Performance Objective The objective of this policy is to: a) facilitate the safe and convenient connection of mobile generators, and b) provide a consistent mobile generator connection interface. 22.3 Technical Requirements The MGLB can be either wall mounted or free standing. It shall be located adjacent to the mobile generator hardstand, externally to the building where wall mounted, within reasonable access of the generator to minimise cabling. The MGLB and hardstand shall be in a position that ensures the MGLB and the mobile generator will not obstruct access or egress to the facility and in a manner that ensures noise or vibration from the generator will not have an adverse impact on the facility. The generator hardstand or generator set down area shall include suitable environmental control provisions to accommodate the generator and the required fuel storage. This hardstand or set down area shall be suitably located so that it is directly accessible by truck. The typical MGLB arrangements are shown in Figure 22.1. The MGLB shall be provided with the following: a) 5 suitably sized reusable lugs for the connection of power cabling to the generator such as ALM “KULUG” type Q or QA, or similar; b) Fail safe type phase rotation indicator (i.e. indicates both correct and incorrect generator supply phase rotation) and voltmeter with phase selector switch; c) Suitable bottom cable entry for the generator connecting cables. The MGLB connection arrangement shall ensure the weather proofing of the connections, and shall prevent accidental contact of personnel with live parts, in all circumstances; and 230V socket MIEE 2011, Amend1 – 15 Sept 2010 Chapter 22 - MGLB Page 1 of 5 MIEE – Chapter 22 – Mobile Generator Link Box (MGLB) outlet, where mains power is available. The mobile generator link box shall be provided with a suitable 230V socket outlet to allow connection of the generator auxiliaries such as battery charges. MIEE 2011, Amend1 – 15 Sept 2010 Chapter 22 - MGLB Page 2 of 5 MIEE – Chapter 22 – Mobile Generator Link Box (MGLB) NOTE: ENCLOSURE MANUFACTURED FROM 2mm SHEET STEEL FOLDED AND FULLY WELDED. ALL WELDS GROUND SMOOTH. IP56 (MAIN CABINET DOOR). PHASE ROTATION AND VOLTMETER ENCLOSURE FINISH: EXTERNAL - PALE GREY POWDER COAT . METER SELECTOR SWITCHES INSULATED POST TO SUPPORT BUS BAR ARRANGEMENT QLUGS LOCKABLE "T" HANDLE 604 TUMBLER 1000x1000 CONC. N25 SLAB WITH F72 FABFIC. FIX LABELS AS DETAILED TO OUTSIDE LINK BOX. REMOVABLE ACCESS PANEL TRAILING CABLE SUPPORT BAR MOBILE GENERATOR LINK BOX 2 OFF KNURLED CAPTIVE SCREWS MINIMUM GENERATING CAPACITY FOR OPERATION xxxkVA CABLE ACCESS HINGED COVER TRAILING CABLES CONCRETE FOOTING 2 X 100mm HD uPVC CONDUITS FRONT VIEW SECTION TYPICAL GROUND MOUNTED ARRANGEMENT BUS BAR ACCESS VIA REMOVABLE PANEL WEATHERPROOF SEAL BETWEEN WALL/PANEL ANGLED ROOF AND RAIN GUTTER INSULATED POST TO SUPPORT BUS BAR ARRANGEMENT PHASE ROTATION AND VOLTMETER METER SELECTOR SWITCHES TRAILING CABLE SUPPORT BAR REMOTE STOP/START CONTROL LINKS (DIN RAIL TERMINAL STRIP) FULLY WELDED SECTION BETWEEN EXTERIOR PANEL BUS BAR TRANSITION THROUGH WALL QLUGS CABLE ACCESS HINGED COVER 2 OFF KNURLED CAPTIVE SCREWS TRAILING CABLES FRONT VIEW SECTION TYPICAL WALL MOUNTED ARRANGEMENT Figure 22.1: Typical Mobile Generator Link Box Arrangements MIEE 2011, Amend1 – 15 Sept 2010 Chapter 22 - MGLB Page 3 of 5 MIEE – Chapter 22 – Mobile Generator Link Box (MGLB) 22.3.1 Socket Outlets Should a plug/socket arrangement be required by the end users to connect the mobile generator, the socket shall be mounted externally on the link box and shall be provided in addition to the typical link box connection arrangements of Figure 22.1 above. The purpose of the plug/socket arrangement is to provide additional flexibility for the connection of the mobile generator and shall in no way interfere with the operation of the link box as described in above. Suitable instructions shall be provided in the link box on the use of the socket outlet in the form of an engraved label. The socket outlet shall be clearly labeled to prevent improper use. 22.3.2 Main Switchboards The main switchboard shall be provided with an appropriate changeover switch to connect the facility or equipment either to mains supply or to the mobile generator supply as required. The configuration of the changeover switch shall ensure that the mobile generator can be safely connected whilst mains supply remains available to the equipment or facility. The changeover switch shall have three resting positions which shall be labeled “Mains”, “Off” and “Mobile Generator”. Maximum demand indicators shall be provided in the main switchboard to facilitate the assessment of the required generator size for the facility or equipment. 22.3.3 MGLB External Labeling The link box shall include an external label “Mobile Generator Link Box” as well as an internal label “Minimum Generator Size for Operation XXXKVA” (the generator size required shall be determined during the design stage and shall be based on the requirements set out in the design brief). MGLBs incorporating the main switchboard shall also be provided with a switchboard label and circuit schedule in accordance with Defence Low Voltage Distribution Pillars and Switchboards Labelling and Numbering requirements. 22.3.4 Local Emergency Generator Installations In addition to the above requirements, MGLB used for LEG applications also require the control circuit connections necessary to allow automatic starting and stopping of the mobile generator (in lieu of the LEG) through the LEG control system. The control connection shall be provided in a suitable location within the MGLB to allow termination of the control cable from the mobile generator. The LEG control system shall be suitably arranged to facilitate the remote operation of the mobile generator. To achieve this, the LEG control system may need to monitor the position of the transfer switch to determine when the mobile generator has been selected. The control system shall in no way inhibit the use of manual start generators. For LEG applications, the main switchboard or generator switchboard shall be provided with an appropriate manual transfer switch that allows connection of the LEG or the mobile generator. The transfer switch shall have an off position to allow both the LEG and the link box to be isolated (to allow the mobile generator to be safely connected or the LEG to be isolated for maintenance). The manual transfer switch shall be suitably labelled (e.g. “LEG”, MIEE 2011, Amend1 – 15 Sept 2010 Chapter 22 - MGLB Page 4 of 5 MIEE – Chapter 22 – Mobile Generator Link Box (MGLB) “OFF” and “Mobile Generator Link Box”); the switch position shall also be monitored by the LEG control system. Maximum demand indicators are to be provided in the LV switchboard to facilitate the assessment of the required mobile generator size for the facility where the intelligent meter cannot provide the required data. It shall be possible to use the LEG dummy load, where provided with the mobile generator. 22.3.5 Deployable Equipment Sites MGLB provided for deployable equipment hardstands shall be incorporated as part of the Main Switchboard (MSB). The MGLB/MSB shall be located adjacent the generator hardstand and the deployable equipment hardstand in a suitable manner to minimise cabling between the switchboard and generator, and the switchboard and equipment cabin, respectively. Mobile generators used for deployed equipment sites, such as deployable aircraft navigation aids, may have automatic start ability. MGLB provided for these deployed equipment sites should consider the inclusion of an automatic changeover facility to automatically start and connect the mobile generator to the intended load on a power failure. The system shall be suitably configured to allow connection of either automatic or manual start generators. The MGLB for deployed equipment sites needs to incorporate the main switchboard element, cable protection and suitable equipment connection arrangements. MIEE 2011, Amend1 – 15 Sept 2010 Chapter 22 - MGLB Page 5 of 5