EE 204 Lecture 29 Three Phase Circuits Introduction of three phase circuit concept • The three phase circuit is the main circuit structure used in power system. • The electrical power generation is accomplished through three-phase circuit. • The three phase connection lines transmit power over long distance. • The energy is distributed and consumed at the load level through three phase and single phase. • The basic structure of a three phase system consists of voltage source, transformers, transmission line and connected loads. Balance Three Phase Voltages • Three sinusoidal voltages form a set of balanced voltages when they have the same amplitudes and frequency. • These voltages are shifted in phase by 120o with each other. • The standard practice is to name those phases by a, b and c and use phase a as reference. • These voltages represent phase a voltage, phase b voltage and phase c voltage. Balanced Y-connected Load • Large blocks of power are generated, transmitted, distributed and used with three phase circuits. • For economic reasons, three phase systems are usually designed to operate in the balanced state. Figure shows a balanced Y-connected load. • A balanced Load is composed of three identical impedances ZL. • For a Y-connected load the voltages across the loads are the phase voltages, regardless of whether neutral is attached. Balanced ∆-connected Load • Another common way of interconnecting the individual three phase loads is the delta connection. • In ∆ -connected load there is no neutral connection. • For a ∆ -connected load the voltages across the loads are the line to line voltages. Example 1: Consider a balanced wye-connected load where each load impedance is Zˆ L = 50 + j 50 Ω and the phase voltages are 120 V. Determine the total average power delivered to the load. Solution: The line currents are o ˆI = 120∠0 = 1.7∠ − 45o A a 50 + j 50 o ˆI = 120∠ − 120 = 1.7∠ − 165o A b 50 + j 50 o ˆI = 120∠120 = 1.7∠75o A c 50 + j 50 Hence, the average power delivered to each load is: ( )( ) Pav = Re ⎡⎣ 120∠0o 1.7∠45o ⎤⎦ ( ) Pav = 120 × 1.7 × cos 45o = 144 W The total average power delivered to the load is: PavTot = 3 × 144 = 432 W Example 2: If the line voltage of a balanced, wye-connected load is 208 V and the total average power delivered to the load is 900 W, determine each load if their power factors are 0.8 leading. Solution: From equation: PavTot = 3 × VL I L cos θ = 3VL I L cos θ 3 IL = then: 900 = 3VL I L cos θ 900 = 3.12 A 3(208)(0.8) The phase voltage is: VL 3 = 120 V Vp = Thus the magnitude of the individual load impedance is: ZL = Vp IL = 38.43 Ω Since the power factor is 0.8 leading (current leads voltage; voltage lags current), θ = − cos −1 0.8 = −36.87o Thus the individual loads are: Z L = 38.43 ∠ − 36.87o = 30.74 − j 23.06 Ω or Example 3: A balanced ∆ -connected load is 208 V, and the total average power delivered to the load is 600 W. Determine the individual loads if they have a lagging power factor of 0.7. Solution: The average power delivered to each load is 200 W, so that 200 = 3 × IL = IL VL cos θ 3 or 200 3 = 2.38 A (208)(0.7) Thus the magnitude of the individual load impedance is: ZL = VL IL 3 = 151.42 Ω Since the power factor is 0.7 lagging, θ = cos −1 0.7 = 45.57o Thus the individual loads are: Z L = 151.42 ∠45.57 o = 106.74 + j108.14 Ω Example 4: Three-phase power is supplied to a balanced, ∆ -connected load. The line-to-line voltage is 208 V, and the load consumes a total power of 15 kW at a lagging power factor of 0.6. Determine the transmission-line currents and the individual loads. Solution: From equation: PavTot = 3 × IL VL cos θ = 3VL I L cos θ 3 then: 15000 = 3VL I L cos θ Therefore the transmission-line current is: IL = 15000 = 69.39 A 3(208)(0.6) For delta connection, VP =VL, thus the magnitude of the individual load impedance is: ZL = Vp IL = 5.19 Ω Since the power factor is 0.6 lagging, θ = cos −1 0.6 = 53.13o Thus the individual loads are: Z L = 5.19 ∠53.13o = 3.12 + j 4.15 Ω