Solid State Remote Power Controller E-1048-S6... 7

advertisement
Solid State Remote Power Controller E-1048-S6...
Description
The E-T-A Solid State Remote Power Controller (SSRPC) E-1048-S6xx
is an opto decoupled transistorised switching device providing both
protection and signalisation.
It may be used wherever safe switching and protection of resistive,
inductive or lamp loads in DC voltage systems is required.
Typical applications
Automation
- interface module providing inexpensive power amplification
at PLC outputs
- optimum protection of individual loads by monitoring the load
circuit
Protection and control of
-motors
-solenoids
-lamps
E-1048-S602
Technical data (Tambient = 25 °C; at UN)
Load circuit
Features
l
l
l
l
l
l
l
Optimum load protection. Available in current ratings of 0.5 A; 1 A;
2 A; 4 A. No derating required over entire temperature range!
Fast short-circuit limitation and disconnection
Time/current dependent overload disconnection (simulating thermal-magnetic CBE trip curve)
Remote control
Fault indication: LED and signal output for overload/short-circuit
signalisation, and wire break indication in the OFF condition (version -600) and in the OFF and ON condition (version -602)
Physically isolated fault indication.
Compact plug-in type
Ordering information
Type No.
E-1048
Solid State Remote Power Controller
Version
S600 wire break indication in OFF condition
(standard)
S602 with permanent wire break monitoring
Voltage rating
DC 24 V DC 24 V (standard)
Current ratings
0.5 A
1.0 A
2.0 A
4.0 A
E-1048 - S600 DC24 V 1.0 A
Voltage rating US
DC 24 V (18...36 V)
Current rating IN
0.5 A; 1 A; 2 A; 4 A (other ratings to special order)
Closed-circuit current IContr
typically 0.3 mA
Min. load current Standard version:Iload > 1 mA
wire break indication in OFF condition
Option: wire break indication in OFF and ON condition
wire break ind. in OFF cond. Rload > typ. 500 kΩ
wire break ind. in ON cond. Iload < typ. 130 mA (0.5/1 A unit)
Iload < typ. 500 mA (2/4 A unit)
0.15 V; 0.3 V; 0.1 V; 0.2 V
Voltage drop UDSmax
Switch-on/switch-off time ton/toff typ. 300 µs/700 µs with resistive load
Overload disconnection 100 ms Short-circuit current
(self-limiting)
Short-circuit disconnection approx. 1.5 (±0.3) x IN after approx.
max. 25 A (with 0.5 A and 1 A current ratings)
max. 75 A (with 2 A and 4 A current
ratings)
< 250 µs
Control circuit
Voltage rating Voltage controlled input UE Input current IE
Max. switching frequency fmax
Reset time after shortcircuit/overload disconnection
DC 24 V
DC 0 V < low level < 5 V
DC 8.5 V < high level < 36 V
1...10 mA (8.5...36 V)
500 Hz
1 ms
Fault indication output F (opto coupler)
ordering example
Where remote control, wire break and LED indication is not required, please
contact us for a thermal-magnetic circuit breaker (e.g. types 2210, 3600, 3900).
Voltage rating range
DC 5...36 V
Voltage rating range
DC 5...36 V
Max. load current
100 mA (∆U < 2 V), with reverse polarity protection
Error indication
output F+ / F- conductive
-wire break in load circuit
-after short-circuit/overload disconnection
Parallel connection possible, as leakage current < 10 µA
General data
Temperature range
Insulation voltage
(IEC 60664/VDE 0110)
Vibration
Mass
2015/16
www.e-t-a.de
0 °C...+60 °C
2.5 kVrms
3 g, test to EN 60068-2-6 test Fc
34 g
7-7
7
Solid State Remote Power Controller E-1048-S6...
Dimensions
At the appropriate input level (>8.5 V), the opto decoupled input in the
SSRPC will switch on a power transistor to connect the load to the
plus pole of the load circuit supply (US).
The transistor will switch off when
- the control voltage (UE) is removed
- there is a short-circuit/overload in the load circuit.
Status indication is provided by two LEDs (red and green).
Thermal-magnetic style overload protection occurs at approx.
1.5 times rated current. See time/current characteristic curves.
The SSRPC is fitted with blade terminals DIN 46244-A6.3-0.8 and
is suitable for plug-in mounting with various E-T-A sockets (see
Accessories).
70
2.75
60
2.36
Control circuit
ON condition:
If a voltage higher than 8.5 V is applied to the input terminals (-IN,
+IN), the control current (from the PLC) will flow through the opto
coupler. The output transistor will be conductive, the green LED will
be lighted.
OFF condition:
A control voltage lower than 5 V will switch the output transistor off.
Fault indication output
The fault indication circuit (F+, F-) is opto decoupled from the load
and control circuit.
In the OFF condition, this circuit will provide wire break indication,
with the transistor output being open.
In the ON condition, the circuit will provide short-circuit and overload
monitoring and indication.
Visual fault indication by red LED.
3
6
4
1
10.3
.405
7
LED green
6.8
.267
blade terminals
DIN 46244-6.3-0.8
50
1.97
F
E-1048
-S60X
xxA
LED red
This is a metric design and millimeter dimensions take precedence ( mm )
inch
Typical time/current characteristics (TA = 25 °C)
0.5 A and 1 A
1000
100
Fault indication output
(opto coupler)
Trip time in ms
Status indication
Status indication
5
6x6.8=40.8
6x.267=1.60
reverse plug-in
protection
12.3
Load circuit
The load circuit switches depending on the control signal (“0” or “1”).
It is electronically monitored for faults. In the event of a short-circuit
the circuit is disconnected after max. 250 µs whilst upon inadmissible
overload it is disconnected according to the time/current curves
shown.
2
IN
Technical description
LED
green red
10
non-conductive, no duty
1
conductive, normal duty
current limitation
overload or short circuit at the output
(and with option wire break indication in
ON condition)
0.1
wire break, in the OFF position
IN
2 A and 4 A
Connection diagram
Trip time in ms
E-1048-S600
1
control circuit
IN+
IN-
fault output
F+
F-
+US
2
5
7
20
30
I (A)
100
green
control and
monitoring
electronics
4
3
6
10
Q
load
7
10
1000
1
current limitation
-US
0.1
red
IN
7-8
www.e-t-a.de
20
40
60
80
I (A))
2015/16
Solid State Remote Power Controller E-1048-S6...
Functional diagrams E-1048-S6xx
Functional diagram E-1048-S6xx
wire break indication
E-1048-S600
wire breakage monitoring only in OFF condition
Version
Operating voltage is applied
US
E-1048-S602
wire breakage monitoring in ON and OFF condition
Version
Operating voltage is applied
US
1
1
IN
IN
0
0
LED green
LED green
1
1
output
output
0
0
LED red
LED red
opto coupler
opto coupler
Error indication
Error indication
Error
wire break
Error
wire break
Functional diagram E-1048-S6xx
overload /short-circuit indication
E-1048-S600/-S602
without fault storage
Version
Operating voltage is applied
US
1
IN
0
LED green
1
output
0
LED red
*
opto coupler
1
IN = input set / output = switched through
Error indication
n
overload /
short-circuit
2015/16
7
Fault indication is reset when control coltage is switched off,
whether the failure is still active or not.
0
Error
*
LED lights
www.e-t-a.de
7-9
Solid State Remote Power Controller E-1048-S6...
Accessories for E 1048-S6xx
12.5
.492
2(k)
11
12
24
23
2(i)
12.5
.492
80
3.15
symmetrical rail
EN 50022-35x7.5
adapter X20040901
polarization recess
G-profile
EN 50035-G32
6
.236
2
.079
max. 30
max. 1.18
~70
~2.76
cylinder head screw washer
M4x4 ISO1207
A 4.3 DIN 125
nickel plated
nickel plated
2
.079
female
connector
Retaining clip
Y 308 792 01
recommended for a tight fit of types
ESX10 / E-1048-S6xx / SB-S11-P1-xx
with terminal blocks type 17 and 17plus
64
2.52
10
.394
12.8
.504
75
2.95
4.4
.173
100 quick-connect tabs 6.3 (.250)
DIN 46247 tinned brass,
insulated
M4 Cu rail, tin-plated
7
.276
50
1.97
retaining
clip
10
.394
Connector bus links -P10
X 210 588 01 / 1.5 mm2,(AWG 16), brown (up to 13 A max. load)
X 210 588 02 / 2.5 mm2, (AWG 14), black (up to 20 A max. load)
X 210 588 03 / 2.5 mm2,(AWG 14), red (up to 20 A max. load)
X 210 588 04 / 2.5 mm2, (AWG 14),blau (up to 20 A max. load)
Busbar (10-way) (supplied as a complete package)
for type 17 socket
(for max. 100 A continuous load),
more positions available on request
X 211 157 01 with terminal
X 211 157 02 without terminal
Phoenix terminal AKG 35
max.cross section 35 mm2 (AWG 2)
polarized
recess
12.5
.492
21
.827
45.8
1.80
5
.197
41.3
1.63
1
25
.984
6 x .268 = 1.61 6.8
.268
retaining clip
4.4
.173
22.2
polarized blade terminals
7.4 DIN 46244-A6.3-0.8 (QC .250) .874
.291
6.25
12.5
.246
.492
50
1.97
57.4
2.26
64
2.52
10
.394
10
.394
7.4
.291
10
.394
1.4
.055
24
2(i)
23
33.3
1.31
11
6.5
.256
25.8
1.02
8.5
.335
depth
10 mm
(.394 in.)
2(k)
12
2.8
.110
6.3
.248
retaining clip
1
-P70
3.5
.138
blade terminal DIN 46244 part 2
C profile (2xA2.8-0.8) (QC 2x.110)
6-way mounting socket
63-P10-Si
50
1.97
57.4
2.26
6 x 6.8 = 40.8
17-P10-Si-20025
17-P70-Si-20025
polarized blade terminal
DIN 46244-A6.3-0.8 (QC .250)
-P10
slot for fitting labels from
Phoenix, Weidmüller
2-way mounting socket
23-P10-Si
(with adapter)
64
2.52
Single mounting sockets
(up to 16 A max. load)
17-P10-Si
17-P70-Si
(retaining clip Y 308 792 01)
.5
64 4
2.5
pressure-relief joint
(1.1 mm (.043 in.)
thick constriction)
154.8
6.09
Insulating sleeving for busbar (10-way)
Y 303 824 01
9
.354
125
4.92
17
.669
5.4
.213
7
This is a metric design and millimeter dimensions take precedence ( mm )
inch
Pin selection 17-P10-Si fitted with E-1048-S6xx
E-1048-S6xx 17-P10-Si
IN +
IN F+
F-UB
Q
+UB
7 - 10
(2)
(5)
(7)
(3)
(6)
(4)
(1)
(2)
(5)
(7)
(3)
(6)
(4)
(1)
[2(k)]
[12]
[24]
[2(i)]
[23]
[11]
[1]
All dimensions without tolerances are for reference only. In the interest of improved design,
performance and cost effectiveness the right to make changes in these specifications without
notice is reserved. Product markings may not be exactly as the ordering codes. Errors and
omissions excepted.
www.e-t-a.de
2015/16
Download