3P Series Molded Case Circuit Breakers
Overview
Overview
Features
Designed to provide branch and feeder
circuit protection in industrial control
panels, this line of Molded Case Circuit
Breakers supplies protection against
overload in conductors and short circuit in connected equipment such as
motors. They are UL listed for installation in UL 508 control panels. Their
small size, in relation to standard circuit
breakers or other comparable devices,
saves panel space. Four frame sizes
and all standard accessories are available.
Listings
• UL 489 MCCB, File: E7819
• Field-installed accessories:
UL file E64983
• CSA 22.2 No.5, File: 43556
• IEC 157-1
• NEMA Standards Pub. No. AB1-1993
• UL489 listed performance for branch
circuit overcurrent protection and
disconnecting means
• Patented contact conductor designs
featuring high-speed “blow-open”
action, providing superior performance
when high level fault currents produce
extra-ordinary electromechanical forces
• Advanced arc extinguishing technology
• Toggle handle provides three positions
(on/off/tripped) along with visual
indicators
• Manufactured in ISO 9000 certified
facilities
• HACR (heating, air conditioning and
refrigeration) rated
• G-Frame and F-Frame breakers are
suitable for reverse feed
• K-Frame and L-Frame breakers include
3-pole adjustable magnetic trip.
Manufactured by Eaton Corporation
Note: These parts available for sale to North American locations only.
Molded Case Circuit Breakers Technical Specifications
UL 489 Interrupting Ratings
Volts
Type
Federal
(rms
Symmetrical Amperes) (kA)
Circuit Breaker Ampere Rat- No.
of Specification
Volts AC (50/60 Hz)
Volts DC
Type
ing at 40°C Poles
AC DC Trip* W-C-375b
G-Frame
F-Frame
K-Frame
L-Frame
240
480
600
250**
15 -100
3
480
250
N.I.T.U
13b
65
22
–
10
60 - 225
3
600
250
N.I.T.U
22a
65
35
18
10
250 - 400
3
600
250
I.T.U
23a
65
35
25
10
400 - 600
3
600
250
I.T.U
23a
65
35
25
22
*Note: N.I.T.U denotes non-interchangeable trip unit. I.T.U denotes interchangeable trip unit.
**Note: For DC or 1-phase AC applications, use the two outside poles of the 3-pole circuit breaker
Molded Case Circuit Breakers Part Numbering System
G
3P - 020 - AUX
Accessory Description Code
AUX: auxiliary contact
STAC: shunt trip AC
STDC: shunt trip DC
UVAC: undervoltage release
n e oltage elea e
Amp Rating
3 Pole
Molded Case Circuit Breaker Series (by frame size)
G: 15 to 100 Amp
F: 60 to 225 Amp
K: 250 to 400 Amp
L: 400 to 600 Amp
Book 3 (14.3)
eCP-34
Circuit Protection
1 - 8 0 0 - 633 - 0 4 0 5
Prices as of April 27, 2016. Check Web site for most current prices.
3P Series Molded Case Circuit Breakers
60 - 225 Amp F-Frame
F-Frame circuit breakers are available
as a single unit, or with accessories preinstalled only. Accessories are not field
installable on this frame size.
Company
Information
Terminal Blocks
This frame size is suitable for reverse feed
use. All breakers include base mounting
hardware for panel mount applications.
F3P-060
F3P-070
F3P-080
F3P-090
F3P-100
F3P-125
F3P-150
F3P-150-AUX
F3P-150-STAC
F3P-150-STDC
F3P-150-UVAC
F3P-200
FHMVD12B
F3P-175
F3P-200
F3P-200-AUX
F3P-200-STAC
F3P-200-STDC
F3P-200-UVAC
F1S03C
F3P-225
Price
Pre-Installed Accessories*
Description
$572.00
$612.25
$612.25
$577.50
$612.25
$612.25
$612.25
$673.00
$673.00
$673.00
$673.00
Molded case circuit breaker with nonadjustable thermal magnetic trip; line
and load lug terminals included.
Molded case circuit breaker with nonadjustable thermal magnetic trip; line
and load lug terminals included.
Molded case circuit breaker with non$612.25 adjustable thermal magnetic trip; line
and load lug terminals included.
$612.25
$673.00 Molded case circuit breaker with non$673.00 adjustable thermal magnetic trip; line
$673.00 and load lug terminals included.
$673.00
Molded case circuit breaker with non$612.25 adjustable thermal magnetic trip; line
and load lug terminals included.
Ampere Voltage Interrupt
Rating
Capacity
None
None
None
None
None
None
None
auxiliary contact, SPDT
120 VAC shunt trip
24 VDC shunt trip
120 VAC undervoltage release
60
70
80
90
100
125
None
175
None
auxiliary contact, SPDT
120 VAC shunt trip
24 VDC shunt trip
120 VAC undervoltage release
200
None
225
M12 Junction
Blocks
Panel Interface
Connectors
Wiring Duct
150
240VAC
480VAC
600VAC
250VDC**
65kA
35kA
18kA
10kA
Power Supplies
DC Converters
$73.25
$104.50
$118.25
$320.25
$347.25
$52.00
$77.25
NEMA 1/12 rotary handle for F-frame. Position indicating. Lock-off feature. Shaft length: 12”
NEMA 4/4X rotary handle for F-frame. Position indicating. Lock-off feature. Shaft length: 12”
NEMA 4/4X rotary handle for F-frame. Position indicating. Lock-off feature. Shaft length: 24”
NEMA 1/12 flex shaft cable operator for F-frame. Flange mountable. Lockable. Cable length: 3’
NEMA 1/12 flex shaft cable operator for F-frame. Flange mountable. Lockable. Cable length: 6’
Multi-wire connector to allow 6 wires to be connected to the F-frame. UL for copper only. 14-6 AWG. Package of 3
Replacement lug kit for F-frame. Package of 3
F-Frame Electrical Ratings 1,2
Frequency
F-Frame
Auxiliary Switch
1
125 VDC DC
0.504
250 VDC DC
0.254
F-Frame Shunt Trip
F-Frame Undervoltage Release
Mechanism
6
2500
1. Endurance: 5000 electrical operations plus
4000 mechanical operatons.
2. Pigtail wire size: 18 AWG
(0.82 mm2)
3. Use in electronice circuit of
100 micro-amperes and 15 VDC minimum.
4. Non-inductive load
Supply Min Operating VA
Voltage Voltage
120 VAC 36 VAC
24 VDC 9 VDC
570
400
AWG Wire Range Specifications
Dropout Volt- Pickup
Supply age
Voltage VA
Voltage
Min Max Maximum
120 VAC
44.5 VAC 77.0 VAC 93.5 VAC
1.5
Circuit Ampere Wire AWG Wire Metric Wire
Breaker Rating Type Range
Range mm2
F-Frame
60 - 100
Cu/AI
125 - 225
14 - 1/0
4 - 4/0
2.5 - 50
25 - 95
Book 3 (14.3)
w w w. a u t o m a t i o n d i r e c t . c o m / c i r c u i t- p r o t e c t i o n
Circuit Protection
Test
Equipment
Enclosures
Enclosure
Climate Control
Safety: Electrical
Components
Safety: Protective
Wear
Dielectric
Max
Notes
Amperes Withstand
Voltage
125 VAC 50/60 Hz
600 VAC 50/60 Hz
3
Transformers
and Filters
Tools
Description
Max
Volts
Wire
Wire
Management
Products
Price
3TA225FD
Cable Ties
Bulk
Multi-conductor
Cables
F-Frame Accessory Selection Guide
3TA150F6K
Multi-wire
Connectors
Sensor Cables
and Connectors
*Note: Available accessories are pre-installed on G-Frame and F-Frame Molded Case Circuit Breakers. They are not field
installable or interchangeable.
**Note: For DC or 1-phase AC applications, use the two outside poles of the 3-pole circuit breaker
Part Number
FHMVD12B
HM1R12X
HM1R24X
F1S03C
F1S06C
3TA150F6K
3TA225FD
Wiring
Accessories
ZIPLink
Connection
System
F-Frame Series Three Pole Molded Case Circuit Breakers
Part Number
Power
Distribution
Blocks
Circuit Protection
eCP-37
Terms and
Conditions
Prices as of April 27, 2016. Check Web site for most current prices.
3P Series Molded Case Circuit Breakers
60 Amp F-Frame
6000
7000
8000
9000
10000
5000
4000
3000
2000
600
700
800
900
1000
500
400
40 50 60 70 8090
200
30
100
20
2 HOURS
Circuit Breaker Time/Current Curves
F3P
2 HOURS
5 6 7 8 9 10
10,000
300
CURRENT IN AMPERES
60A
60 Amperes
1 HOUR
For application and coordination purposes only
.
Based on 40˚C ambient, cold start. Connected with four (4) feet of
rated wire (60˚C up to 125 amps, 75˚C above 125 amps) per terminal.
Tested in open air with current in all poles.
3,000
2,000
1 HOUR
5,000
5,000
3,000
2,000
Maximum AC Volts: 600 at 60 Hz
Maximum DC Volts: 250
Breaker Rating
Continuous Amperes
60 Amps
1,000
Interrupting Rating (UL/CSA Listed)
Breaker Symmetrical RMS Amperes (KA)
@ 240 VAC @ 480 VAC @ 600 VAC
Type
500
F3P
65
1,000
Instantaneous Trip Amperes
See Curve
35
18
Amps (KA)
250VDC
500
10
300
300
200
1
Single pole test data at 25˚C based on NEMA Procedures
(AB 4-1991) for verifying performance of molded case circuit
breakers.
200
100
100
50
50
30
30
20
20
Minimum
Maximum
5
5
3
3
2
2
1
1
.5
.5
.3
.3
.2
.2
.1
.1
TIME IN SECONDS
10
.05
TIME IN SECONDS
10
.05
.03
.03
Maximum Interrupting Time
.02
.02
.01
.01
Interrupting
Rating
Determines
End of Curve
(See Above)
.005
.003
.002
.005
.003
6000
7000
8000
9000
10000
5000
4000
3000
2000
600
700
800
900
1000
40 50 60 70 8090
500
30
400
20
300
5 6 7 8 9 10
200
.002
100
.001
1 MINUTE
1 MINUTE
Maximum Single
Pole Trip Times
at 25°C 1
.001
CURRENT IN AMPERES
Book 3 (14.3)
eCP-38
Circuit Protection
1 - 8 0 0 - 633 - 0 4 0 5
Prices as of April 27, 2016. Check Web site for most current prices.
3P Series Molded Case Circuit Breakers
70 Amp F-Frame
6000
7000
8000
9000
10000
5000
4000
3000
2000
600
700
800
900
1000
500
400
40 50 60 70 8090
200
30
100
20
300
CURRENT IN AMPERES
70A
2 HOURS
Circuit Breaker Time/Current Curves
F3P
2 HOURS
5 6 7 8 9 10
10,000
70 Amperes
1 HOUR
For application and coordination purposes onl y.
Based on 40˚C ambient, cold start. Connected with four (4) feet of
rated wire (60˚C up to 125 amps, 75˚C above 125 amps) per terminal.
Tested in open air with current in all poles.
3,000
2,000
3,000
1 HOUR
5,000
5,000
Breaker Rating
Continuous Amperes
70 Amps
Instantaneous Tr ip Amperes
See Curve
Interrupting Rating (UL/CSA Listed)
Breaker Symmetrical RMS Amperes (kA)
@ 240 V AC @ 480 V AC @ 600 V AC
Type
500
F3P
65
35
18
Amps (kA)
@250 V DC
1
Single pole test data at 25˚C based on NEMA Procedures
(AB 4-1991) for verifying performance of molded case circuit
breakers.
500
M12 Junction
Blocks
Panel Interface
Connectors
200
100
100
50
50
30
30
20
Wiring Duct
Cable Ties
Wire
Bulk
Multi-conductor
Cables
20
Minimum
ZIPLink
Connection
System
Sensor Cables
and Connectors
1 MINUTE
1 MINUTE
Maximum Single
Pole Trip Times
at 25°C 1
Wiring
Accessories
1,000
300
200
Power
Distribution
Blocks
Multi-wire
Connectors
10
300
Terminal Blocks
2,000
Maximum AC Vo lts: 600 at 60 Hz
Maximum DC Vo lts: 250
1,000
Company
Information
Wire
Management
Products
Maximum
10
10
5
5
DC Converters
3
3
2
2
Transformers
and Filters
Power Supplies
TIME IN SECONDS
Circuit Protection
1
.5
.5
Test
Equipment
Enclosures
TIME IN SECONDS
1
Tools
.3
.3
.2
.2
.1
.1
Safety: Electrical
Components
.05
Safety: Protective
Wear
.05
.03
Enclosure
Climate Control
.03
Terms and
Conditions
Maximum Interrupting Time
.02
.02
.01
.01
Interrupting
Rating
Determines
End of Curve
(See Above)
.005
.003
.002
.003
.001
6000
7000
8000
9000
10000
5000
4000
3000
2000
600
700
800
900
1000
40 50 60 70 8090
500
30
400
20
300
5 6 7 8 9 10
200
.002
100
.001
.005
CURRENT IN AMPERES
Book 3 (14.3)
w w w. a u t o m a t i o n d i r e c t . c o m / c i r c u i t- p r o t e c t i o n
Circuit Protection
eCP-39
Prices as of April 27, 2016. Check Web site for most current prices.
3P Series Molded Case Circuit Breakers
80 Amp F-Frame
6000
7000
8000
9000
10000
5000
4000
3000
2000
600
700
800
900
1000
500
400
200
40 50 60 70 80 90
100
30
2 HOURS
Circuit Breaker Time/Current Curves
2 HOURS
10,000
20
300
CURRENT IN AMPERES
80A
5 6 7 8 9 10
F3P 80 Amperes
1 HOUR
For application and coordination purposes only.
Based on 40˚C ambient, cold start. Connected with four (4) feet of
rated wire (60˚C up to 125 amps, 75˚C above 125 amps) per terminal
.
Tested in open air with current in all poles.
3,000
2,000
1 HOUR
5,000
5,000
3,000
2,000
Maximum AC Vo lts: 600 at 60 Hz
Maximum DC Vo lts: 250
Breaker Rating
Continuous Amperes
80 Amps
1,000
Interrupting Rating (UL/CSA Listed)
Breaker Symmetrical RMS Amperes (kA)
@ 240V. AC @ 480 V AC @ 600VAC
Type
500
F3P
65
1,000
Instantaneous Tr ip Amperes
See Curve
35
18
Amps (kA)
@ 250V DC
300
300
200
Maximum Single
Pole Trip Times
at 25°C 1
1
Single pole test data at 25˚C based on NEMA Procedures
(AB 4-1991) for verifying performance of molded case circui t
breakers.
200
100
100
50
50
30
30
20
20
10
10
5
5
3
3
Maximum
2
2
1
1
.5
.5
.3
.3
.2
.2
.1
.1
.05
TIME IN SECONDS
Minimum
TIME IN SECONDS
1 MINUTE
1 MINUTE
500
10
.05
.03
.03
Maximum Interrupting Time
.02
.02
.01
.01
Interrupting
Rating
Determines
End of Curve
(See Above)
.005
.003
.002
.003
6000
7000
8000
9000
10000
5000
4000
3000
2000
50 60 70 80 90
600
700
800
900
1000
40
500
30
400
20
300
5 6 7 8 9 10
200
.002
100
.001
.005
.001
CURRENT IN AMPERES
Book 3 (14.3)
eCP-40
Circuit Protection
1 - 8 0 0 - 633 - 0 4 0 5
Prices as of April 27, 2016. Check Web site for most current prices.
3P Series Molded Case Circuit Breakers
90 Amp F-Frame
6000
7000
8000
9000
10000
5000
4000
3000
2000
600
700
800
900
1000
500
400
40 50 60 70 8090
300
30
200
20
100
90A
2 HOURS
Circuit Breaker Time/Current Curves
2 HOURS
5 6 7 8 9 10
10,000
CURRENT IN AMPERES
F3P 90 Amperes
1 HOUR
For application and coordination purposes only
.
Based on 40˚C ambient, cold start. Connected with four (4) feet of
rated wire (60˚C up to 125 amps, 75˚C above 125 amps) per terminal.
Tested in open air with current in all poles.
3,000
2,000
3,000
1 HOUR
5,000
5,000
Breaker Rating
Continuous Amperes
90 Amps
Instantaneous Tr ip Amperes
See Curve
Interrupting Rating (UL/CSA Listed)
Breaker
Symmetrical RMS Amperes (kA)
@ 480 V AC
@ 600 V AC
Type @ 240 V AC
500
F3P
65
35
18
Amps (kA)
@ 250 VDC
1
Single pole test data at 25˚C based on NEMA Procedures
(AB 4-1991) for verifying performance of molded case circui
t
breakers.
ZIPLink
Connection
System
Sensor Cables
and Connectors
M12 Junction
Blocks
500
Panel Interface
Connectors
200
100
100
50
50
30
30
20
20
10
10
Wiring Duct
Cable Ties
1 MINUTE
1 MINUTE
Maximum Single
Pole Trip Times
at 25°C 1
Wiring
Accessories
1,000
300
200
Power
Distribution
Blocks
Multi-wire
Connectors
10
300
Terminal Blocks
2,000
Maximum AC Vo lts: 600 at 60 Hz
Maximum DC Vo lts: 250
1,000
Company
Information
Wire
Bulk
Multi-conductor
Cables
Wire
Management
Products
Power Supplies
Minimum
Maximum
DC Converters
3
3
2
2
Transformers
and Filters
TIME IN SECONDS
5
5
Circuit Protection
1
.5
.5
Test
Equipment
TIME IN SECONDS
1
Tools
.3
.3
Enclosures
.2
.2
Enclosure
Climate Control
.1
.1
Safety: Electrical
Components
.05
Safety: Protective
Wear
.05
.03
.03
Maximum Interrupting Time
.02
.01
.01
Interrupting
Rating
Determines
End of Curve
(See Above)
.005
.003
.002
.005
.003
.001
6000
7000
8000
9000
10000
5000
4000
3000
2000
600
700
800
900
1000
40 50 60 70 8090
500
30
400
20
300
5 6 7 8 9 10
200
.002
100
.001
.02
CURRENT IN AMPERES
Book 3 (14.3)
w w w. a u t o m a t i o n d i r e c t . c o m / c i r c u i t- p r o t e c t i o n
Circuit Protection
eCP-41
Terms and
Conditions
Prices as of April 27, 2016. Check Web site for most current prices.
4000
3000
2000
500
600
700
800
900
1000
400
30 40 50 60 708090
300
20
200
5 6 7 8 910
CURRENT IN AMPERES
2 HOURS
Circuit Breaker Time/Current Curves
F3P 100 Amperes
¨
5,000
3,000
2,000
Breaker Rating
Continuous Amperes
100 Amps
1,000
3,000
2,000
Instantaneous Trip Amperes
See Curve
Interrupting Rating (UL/CSA Listed)
Amps (KA)
Breaker Symmetrical RMS Amperes (KA)
@ 480 VAC @ 600 VAC @ 250VDC
Type @ 240 VAC
500
F3P
65
35
18
1,000
500
10
300
300
200
* Single pole test data at 25°C based on NEMA Procedures
(AB 4-1991) for verifying performance of molded case circuit
breakers.
Maximum Single
Pole Trip Times
at 25°C *
200
100
100
50
50
30
30
20
20
10
10
Minimum
Maximum
5
3
3
2
2
1
1
.5
.5
.3
.3
.2
.2
.1
.1
.05
TIME IN SECONDS
TIME IN SECONDS
5
1 MINUTE
1 MINUTE
5,000
For application and coordination purposes only
Based on 40°C ambient, cold start. Connected
with four
.
(4) feet of rated wire (60°C up to 125 amps, 75°C
above 125 amps) per terminal
Tested in open air with current in all poles.
Maximum AC Volts: 600 at 60 Hz
Maximum DC Volts: 250
1 HOUR
1 HOUR 2 HOURS
10,000
100
100A
5000
6000
7000
8000
9000
10000
3P Series Molded Case Circuit Breakers
100 Amp F-Frame
.05
.03
.03
Maximum Interrupting Time
.02
.02
.01
.01
Interrupting
Rating
Determines
End of Curve
(See Above)
.005
.003
.002
5000
6000
7000
8000
9000
10000
4000
3000
CURRENT IN AMPERES
2000
500
600
700
800
900
1000
40 50 60 708090
400
30
300
20
200
5 6 7 8 9 10
.003
.002
100
.001
.005
.001
Book 3 (14.3)
eCP-42
Circuit Protection
1 - 8 0 0 - 633 - 0 4 0 5
Prices as of April 27, 2016. Check Web site for most current prices.
3P Series Molded Case Circuit Breakers
125 Amp F-Frame
2 HOURS
6000
7000
8000
9000
10000
5000
4000
Circuit Breaker Time/Current Curves
125 Amperes
F3P Circuit Breakers
For application and coordination purposes only
5,000
Based on 40°C ambient, cold start. Connected with four (4) feet of
rated wire (60°C up to 125 amps, 75°C above 125 amps) per terminal.
Tested in open air with current in all poles.
.
5,000
3,000
3,000
Maximum AC Volts: 600 at 60 Hz
Maximum DC Volts: 250
2,000
Power
Distribution
Blocks
Wiring
Accessories
1 HOUR
1 HOUR
3000
2000
600
700
800
900
1000
500
400
40 50 60 70 8090
300
30
200
20
CURRENT IN AMPERES
Terminal Blocks
2 HOURS
5 6 7 8 9 10
10,000
100
125A
Company
Information
ZIPLink
Connection
System
2,000
Multi-wire
Connectors
Breaker Rating
1,000
Sensor Cables
and Connectors
Instantaneous Trip Amperes 1,000
See Curve
Continuous Amperes
125 Amps
Interrupting Rating (UL/CSA Listed)
500
Breaker
Type @
300
F3P
1
200
65
35
18
Amps (KA)
VAC
250 VDC
10
Single pole test data at 25°C based on NEMA Procedures
(AB 4-1991) for verifying performance of molded case circuit
breakers.
Maximum Single
Pole Trip Times
at 25°C 1
100
M12 Junction
Blocks
500
300
Panel Interface
Connectors
200
Wiring Duct
100
50
50
30
30
20
20
10
Cable Ties
1 MINUTE
1 MINUTE
Symmetrical RMS Amperes (KA)
@ 480 VAC @ 600
240 VAC
Wire
Bulk
Multi-conductor
Cables
Wire
Management
Products
10
Power Supplies
Minimum
Maximum
5
3
3
2
2
DC Converters
TIME IN SECONDS
TIME IN SECONDS
5
Transformers
and Filters
Circuit Protection
1
1
.5
.5
Test
Equipment
.3
.3
Enclosures
.2
.2
Enclosure
Climate Control
.1
.1
Safety: Electrical
Components
.05
.03
Maximum Interrupting Time
.02
.01
Terms and
Conditions
.02
.01
.005
Interrupting
Rating
Determines
End of Curve
(See Above)
.003
.002
.005
.003
.001
6000
7000
8000
9000
10000
5000
4000
3000
2000
600
700
800
900
1000
40 50 60 70 8090
500
30
400
20
300
5 6 7 8 9 10
200
.002
100
.001
Safety: Protective
Wear
.05
.03
CURRENT IN AMPERES
Book 3 (14.3)
w w w. a u t o m a t i o n d i r e c t . c o m / c i r c u i t- p r o t e c t i o n
Circuit Protection
Tools
eCP-43
Prices as of April 27, 2016. Check Web site for most current prices.
3P Series Molded Case Circuit Breakers
150 Amp F-Frame
T ype F3P 150 A m peres
6000
7000
8000
9000
10000
5000
Circuit Breaker Time/Current Curves
¨
F3P Circuit Breaker 150 Amperes
5,000
5,000
For application and coordination purposes only.
Based on 40˚C ambient, cold start. Connected with four (4) feet of
rated wire (60˚C up to 125 Amps, 75˚C above 125 Amps) per terminal.
Tested in open air with current in all poles.
.
3,000
2,000
3,000
1 HOUR
1 HOUR
4000
3000
2000
600
700
800
900
1000
500
400
40 50 60 70 8090
300
30
200
20
2 HOUR S
5 6 7 8 9 10
CURRENT IN AMPERES
2 HOUR S
10,000
100
150A
2,000
M ax im u m A C Vo l t s : 600 at 60 Hz
M ax im u m D C Vo l t s : 250
Breaker Rating
Continuous A mperes
150 A m ps
1,000
500
M axim um Single
Po leTr ip Tim es
at 25˚C 1
300
500
10
300
Single pole test data at 25˚C based on NEMA
(AB4-1991) for verifying performance of molded
case circuit breakers.
200
100
50
50
30
30
20
20
10
10
M inim um
M axim um
1 MINU TE
1 MINU TE
Am ps (k A)
@250VDC
1,000
100
5
5
3
3
2
2
1
1
.5
.5
.3
.3
.2
.2
.1
.1
.05
.05
.03
TIME IN SECONDS
TIME IN SECONDS
Interrupting Rating (UL/CSA listed)
B reaker S ym m etrical RM S A mperes (k A)
@ 480 VAC
@ 600VAC
Type @240VAC
F3 P
65
35
18
1
200
Instantaneous Trip Amperes
See Curve
.03
M axim um Interrupting Tim e
.02
.02
.01
.01
Interrupting
Rate
determines
End of Curve
.005
.003
(See A bove)
.002
.003
6000
7000
8000
9000
10000
5000
4000
3000
2000
500
40 50 60 70 8090
600
700
800
900
1000
30
400
20
300
5 6 7 8 9 10
200
.002
100
.001
.005
.001
C urve No.
CURRENT IN AMPERES
Book 3 (14.3)
eCP-44
Octo ber 1997
Circuit Protection
1 - 8 0 0 - 633 - 0 4 0 5
Prices as of April 27, 2016. Check Web site for most current prices.
3P Series Molded Case Circuit Breakers
175 - 225 Amp F-Frame
2 HOURS
Circuit Breakers Time/Current Curves
Molded-Case Circuit Breakers
5,000
3,000
Maximum AC Volts: 690 at 50/60 Hz
Maximum DC Volts: 250
3,000
1 HOUR
Catalog Types F3P Circuit Breakers
For application and coordination purposes only
.
Based on 40˚C ambient, cold start. Connected with four (4) feet of rated
wire (75˚C) per terminal. Tested in open air with current in all poles.
2,000
À
1,000
Multi-wire
Connectors
2,000
Instantaneous Pick-up, Amperes
2400
2400
2400
Sensor Cables
and Connectors
1,000
Interrupting Ratings
Breaker
Type
Maximum Single
Pole Trip Times
at 25˚C
Á
300
480 VAC
35
600 VAC
18
250 VAC
10
500
À Fixed Inverse Ð Time Overcurrent Release.
Á Single Pole Test Data at 25 ˚C based on NEMA Procedures (AB 4-1991)
for verifying performances of Molded Case Circuit Breakers.
 Total Operation Time.
à Interrupting Rating Determines End of Curve.
In this interruption region:
The curve is drawn for I n = 200A. For I n ¹ 200A, the end points in this
region are displaced along the current-axis by a factor (200A/I n )
300
Panel Interface
Connectors
200
Wiring Duct
Notes:
200
Cable Ties
100
100
50
50
30
Wire
1 MINUTE
1 MINUTE
65
F3P
500
M12 Junction
Blocks
Symmetrical RMS Amperes (kA), Icu
240 VAC
Power
Distribution
Blocks
ZIPLink
Connection
System
1 HOUR
5,000
Breaker Rating
In Amperes
175
200
225
Terminal Blocks
Wiring
Accessories
600
700
800
900
1000
500
400
300
200
60
70
80
90
100
50
5 6 7 8 9
40
4
20
3
10
2
2 HOURS
5 6 7 8 91
10,000
30
CURRENT IN MULTIPLES of I n (AMP)
175-225A
Company
Information
Bulk
Multi-conductor
Cables
30
Maximum
Trip Time
20
20
10
10
Wire
Management
Products
Power Supplies
5
5
3
3
TIME IN SECONDS
2
Minimum
Trip Time
1
1
Transformers
and Filters
TIME IN SECONDS
2
DC Converters
Circuit Protection
Tools
175 A
.5
.5
Test
Equipment
.3
Enclosures
200 A
.3
225 A
.2
.2
.1
.1
.05
Safety: Electrical
Components
.05
.03
Safety: Protective
Wear
.03
Â
Ã
.02
Terms and
Conditions
.02
.01
.01
.005
.005
.003
.003
.002
.002
600
700
800
900
1000
500
400
300
200
.001
50
5 6 7 8 9
60
70
80
90
100
4
40
3
30
2
20
1
10
.001
Enclosure
Climate Control
CURRENT IN MULTIPLES of In (AMP)
Book 3 (14.3)
w w w. a u t o m a t i o n d i r e c t . c o m / c i r c u i t- p r o t e c t i o n
Circuit Protection
eCP-45
Prices as of April 27, 2016. Check Web site for most current prices.
3P Series Molded Case Circuit Breakers –
Dimensions
15 - 100 Amp G-Frame
inches(mm)
60 - 225 Amp F-Frame
inches(mm)
Book 3 (14.3)
eCP-50
Circuit Protection
1 - 8 0 0 - 633 - 0 4 0 5
Prices as of April 27, 2016. Check Web site for most current prices.
3P Series Molded Case Circuit Breakers –
Accessories
Field Mountable Accessories
Rotary Handle
A universal rotary handle is available for each frame size of molded case
circuit breaker. The handles are suitable for use with NEMA 1, 12, 4 or 4x
enclosures. Features include:
• Large handle easily accommodates gloves
• Global ON/OFF markings (I/ON, O/OFF) and TRIP indication on handle
• Access Handle Lock-Off by pressing arrow on handle insert
• Door interlock and defeater
• Metal shaft and base
• Pipe valve operation (ON=Vertical, OFF=Horizontal) with 90 degree rotation
• UL 489, IEC 947-1/-2, CSA
GHMVD12B
Rotary Handle Accessory Selection Guide
Part Number Price
Description
$66.25 NEMA 1/12 black rotary handle for G-Frame MCCB. Shaft length: 6”
GHMVD06B
GHMVD12B
FHMVD12B
HM1R12X
$73.25 NEMA 1/12 black rotary handle for G-Frame MCCB. Shaft length: 12”
$73.25 NEMA 1/12 black rotary handle for F-Frame MCCB. Shaft length: 12”
HM1R12X
$104.50 NEMA 4/4X black rotary handle for F-Frame MCCB. Shaft length: 12”
HM1R24X
$118.25 NEMA 4/4X black rotary handle for F-Frame MCCB. Shaft length: 24”
KHMVD12B
$106.50 NEMA 1/12 black rotary handle for K-Frame MCCB. Shaft length: 12”
HM3R12X
$129.25 NEMA 4/4X black rotary handle for K-Frame MCCB. Shaft length: 12”
HM3R24X
$143.75 NEMA 4/4X black rotary handle for K-Frame MCCB. Shaft length: 24”
LHMVD12B
$122.50 NEMA 1/12 black rotary handle for L-Frame MCCB. Shaft length: 12”
HM4R12X
$167.50 NEMA 4/4X black rotary handle for K-Frame MCCB. Shaft length: 12”
HM4R24X
$176.50 NEMA 4/4X black rotary handle for K-Frame MCCB. Shaft length: 24”
Flex Shaft™ Flexible Handle
Meeting crucial time limits for shutdown procedures is easier with an externally mounted handle. The flexible handle makes it possible to operate
the circuit breaker externally, and can be used in enclosures of varying
depths and heights. It can be used with NEMA 1, NEMA 3R and NEMA
12 enclosures, and accepts up to three padlock shackles.
Note: A
minimum bending radius of four inches is necessary for proper operation.
Flexible Handle Accessory Selection Guide
Part Number Price
Description
$286.75 NEMA 1/12 flex shaft cable operator for G-Frame MCCB. Cable length: 3’
F0S03C
F0S03C
F0S06C
$320.25 NEMA 1/12 flex shaft cable operator for G-Frame MCCB. Cable length: 6’
F1S03C
$320.25 NEMA 1/12 flex shaft cable operator for F-Frame MCCB. Cable length: 3’
F1S06C
$347.25 NEMA 1/12 flex shaft cable operator for F-Frame MCCB. Cable length: 6’
F3S03C
$381.00 NEMA 1/12 flex shaft cable operator for K-Frame MCCB. Cable length: 3’
F3S06C
$403.25 NEMA 1/12 flex shaft cable operator for K-Frame MCCB. Cable length: 6’
F4S04C
$437.25 NEMA 1/12 flex shaft cable operator for L-Frame MCCB. Cable length: 4’
F4S06C
$504.50 NEMA 1/12 flex shaft cable operator for L-Frame MCCB. Cable length: 6’
Book 3 (14.3)
eCP-52
Circuit Protection
1 - 8 0 0 - 633 - 0 4 0 5
Prices as of April 27, 2016. Check Web site for most current prices.
3P Series Molded Case Circuit Breakers –
Accessories
Field Mountable Accessories
Auxiliary Contact
Note:Field installable auxiliary contacts are not available for the G and F frame breakers.
For G and F frame auxiliary contacts, order breakers with -AUX as part of the part
number. Please see G and F-frame sections for available selections.
Sensor Cables
and Connectors
Description
$193.50 Field installable auxiliary contact for L-Frame MCCB, SPDT, 18” pigtail leads
50/60 Hz
DC
DC
6
0.50
Max Frequency Max Dielectric
Volts
Amperes Withstand
Voltage
600
1. Endurance: 5000
electrical operations
plus 1000 mechanical
operatons.
2. Pigtail wire size: 18
AWG (0.82 mm²)
3. Non-inductive load
3
2500
0.253
L-Frame
Auxiliary 125
Switch
250
50/60 Hz
6
DC
0.503
DC
3
M12 Junction
Blocks
2500
0.25
Cable Ties
Wire
Bulk
Multi-conductor
Cables
L-Frame Electrical Ratings 1,2
Notes
Multi-wire
Connectors
Wiring Duct
$188.75 Field installable auxiliary contact for K-Frame MCCB, SPDT, 18” pigtail leads
K-Frame Electrical Ratings 1,2
ZIPLink
Connection
System
Panel Interface
Connectors
Auxiliary Contact Accessory Selection Guide
A1X3PK
A1X4PK
600
Power
Distribution
Blocks
Wiring
Accessories
Part Number Price
K-Frame 125
Auxiliary
Switch 250
Terminal Blocks
The auxiliary contact provides circuit breaker contact status information
by monitoring the position of the molded cross bar which contains the
moving contact arms. The auxiliary switch is used for remote indication
and interlock system verification, and consists of one SPDT switch housed
in a plug-in module. Each SPDT switch has one ‘a’ and one ‘b’ contact.
When the circuit breaker contacts are open, the ‘a’ contact is open and
the ‘b’ contact is closed.
A1X3PK
Max Frequency Max Dielectric
Volts
Amperes Withstand
Voltage
Company
Information
Notes
1. Endurance: 5000
electrical operations
plus 1000 mechanical
operatons.
2. Pigtail wire size: 18
AWG (0.82 mm²)
3. Non-inductive load
Wire
Management
Products
Power Supplies
DC Converters
Transformers
and Filters
Circuit Protection
Undervoltage Release
This product monitors a voltage (typically a line voltage) and trips the circuit breaker
when the voltage falls to between 70% and 35% of the solenoid coil rating. It consists
of a continuous rated solenoid, with a plunger and tripping lever mounted in a
plug-in module.
Note: The undervoltage release is a pre-installed accessory on G-Frame and F-Frame breakers.
Undervoltage Release Accessory Selection Guide
UVH3LP21K
Part Number
UVH3LP08K
UVH4LP08K
UVH3LP21K
UVH4LP21K
Dropout Pickup
Supply Voltage Voltage VA Notes
Voltage
Min Max Max
K-Frame
Undervolt24 VDC 8.4 16.8 20.4
age Release
2
Mechanism 110 VAC
120 VAC2 44.5 77.0 93.5
127 VAC2
3.1
1.8
2.1
2.4
1. Endurance: 5000
electrical operations plus 1000
mechanical
operatons.
2. 50/60 Hz
Price
$383.25
$386.00
$383.25
$409.25
Field installable 110 - 127 VAC undervoltage release for K-Frame MCCB
Field installable 110 - 127 VAC undervoltage release for L-Frame MCCB
Field installable 24 VDC undervoltage release for K-Frame MCCB
Field installable 24 VDC undervoltage release for L-Frame MCCB
Dropout Pickup
Supply Voltage Voltage VA Notes
Voltage
Min Max Max
120 VAC2 44.5 77.0
127 VAC2
93.5
3.1
1.8
2.1
2.4
1. Endurance:
5000 electrical
operations plus
1000 mechanical operatons.
2. 50/60 Hz
Book 3 (14.3)
w w w. a u t o m a t i o n d i r e c t . c o m / c i r c u i t- p r o t e c t i o n
Circuit Protection
Test
Equipment
Enclosures
Enclosure
Climate Control
Safety: Electrical
Components
Description
L-Frame
Undervoltage Release 24 VDC 2 8.4 16.8 20.4
Mechanism 110 VAC
Tools
eCP-53
Safety: Protective
Wear
Terms and
Conditions
Prices as of April 27, 2016. Check Web site for most current prices.
3P Series Molded Case Circuit Breakers –
Accessories
Field Mountable Accessories
Shunt Trip
The Shunt Trip provides remote controlled tripping of the circuit breaker. Consisting of
an intermittent rated solenoid with a tripping plunger and a cutoff switch assembled
to a plug-in module, shunt trip coils are designed to be applied at specific AC or DC
voltages.
Shunt Trip Accessory Selection Guide
Part Number
SNT3P11K
SNT4RP11K
SNT3P04K
SNT4RP03K
Price
$383.25
$409.25
$383.25
$409.25
Description
Field installable 110/240 VAC / 110/125 VDC shunt trip for K-Frame MCCB.
Field installable 110/240 VAC shunt trip for L-Frame MCCB
Field installable 12/24 VAC/DC shunt trip for K-Frame MCCB
Field installable 12/24 VAC/DC shunt trip for L-Frame MCCB
SNT3P04K
Supply Min
Supply Min
Operating
VA
VA Notes
Voltage Voltage
Voltage Operating
Voltage
VAC 50/60 Hz
K-Frame 12
24
Shunt
110
Trip
120
127
208
220
240
9
60
VDC
45
200
100
120
140
420
470
550
12
24
110
120
125
–
–
–
8.4
77
77
77
–
–
–
35
170
110
130
140
–
–
–
1. Endurance: 5000
electrical operations
plus 1000 mechanical
operatons.
2. Approx. unlatching
time: 6 ms
Approx. total circuit
breaker contact opening time: 8 ms
Supply Min
Supply Min
VA Voltage Operating VA Notes
Voltage Operating
Voltage
Voltage
VAC 50/60 Hz
L-Frame
Shunt
Trip
12
24
110
120
127
208
220
240
9
60
VDC
45
200
100
120
140
420
470
550
12
24
–
–
–
–
–
–
9
–
–
–
–
–
–
35
170
–
–
–
–
–
–
1. Endurance: 5000
electrical operations
plus 1000 mechanical
operatons.
2. Approx. unlatching
time: 6 ms
Approx. total circuit
breaker contact opening time: 18 ms
Book 3 (14.3)
eCP-54
Circuit Protection
1 - 8 0 0 - 633 - 0 4 0 5
Prices as of April 27, 2016. Check Web site for most current prices.
3P Series Molded Case Circuit Breakers –
Accessories
Company
Information
Terminal Blocks
Field Mountable Accessories
Power
Distribution
Blocks
Six-wire Connector
Wiring
Accessories
This is a field installable multi-wire connector which allows six wires to be connected
to the load side (OFF) end terminals. It is used to distribute the load from the circuit
breaker to multiple devices without the use of separate distribution terminal blocks.
UL listed for copper only as used on the load side (OFF) end. Includes mounting
hardware, insulators and tin-plated aluminum connectors.
ZIPLink
Connection
System
Multi-wire
Connectors
Sensor Cables
and Connectors
Six-wire Connector Accessory Selection Guide
Part Number
3TA100G6K
3TA150F6K
Price
$52.00
$52.00
Description
For G-Frame MCCBs. Pkg. of 3. Wire size: 14 - 6 AWG, copper
For F-Frame MCCBs. Pkg. of 3. Wire size: 14 - 6 AWG, copper
3TA100G6K
M12 Junction
Blocks
Panel Interface
Connectors
Replacement Lug Kit
Wiring Duct
Line and load terminals provide wire connecting capabilities for specific ranges of
continuous current ratings and wire types. Replacement lugs will accept wire types
Cu/AI as standard.
Cable Ties
Wire
Bulk
Multi-conductor
Cables
Replacement Lug Kit Accessory Selection Guide
Part Number
Price
3TA225FD
$77.25
3TA401K
$81.00
3TA603LDK
$100.25
Description
Replacement lug kit for F-Frame MCCB. Wire range (1) #4-4/0 (25-95 mm²).
Package of (3) terminals.
Replacement lug kit for K-Frame MCCB. Wire range (2) 2/0-250 kcmil or (1) 2/0-500
kcmil (70-240 mm²). 3-pole kit (one terminal per pole and one terminal cover).
Replacement lug kit for L-Frame MCCB. 3-pole kit (one terminal per pole and one
terminal cover). Wire range 400-500 AWG (185-240 m²), 2 conductors.
Wire
Management
Products
3TA401K
Power Supplies
DC Converters
Note: G-frame terminals are factory-installed only. No replacement terminals available.
Transformers
and Filters
Din Rail Mounting Clip
Circuit Protection
Din Rail Mount Clip Accessory Selection Guide
Part Number
­­­GDIN
Price
$9.00
GDIN
Type C361 door interlocking safety handle kits are designed for use with AutomationDirect 3P series MCCBs and flexible handle, when mounted in an SDN12, or equivalent,
enclosure. These handles secure the SDN12 enclosure, protecting against unauthorized entry while the MCCB is in the ON position. Use them on enclosures with right
side flanges only and material thickness from 16 gauge through 3/16”. All mounting
hardware is included for enclosures up to 40” tall. The addition of the C361KR roller
kit is necessary for enclosures taller than 40” that require a 3-point latch. See SDN12
Enclosures section for enclosure specifications
Safety Door Hardware Selection Guide
Price
C361KJ4
$232.00
C361KJ6
$243.75
C361KR
$52.50
Test
Equipment
Clip for mounting G-Frame to 35 mm Din rail. Mounting hardware included. Pkg of 1
NEMA 12 Safety Door Hardware
Part Number
Tools
Description
Enclosures
Enclosure
Climate Control
Safety: Electrical
Components
Safety: Protective
Wear
Handle
in OFF
position
Terms and
Conditions
Description
Handle length: 4”. Mounting hardware included for enclosures up to 40” tall. For
taller enclosures that require a 3-point latch, the C361KR (purchase separately) will
also be needed.
Handle length: 6”. Mounting hardware included for enclosures up to 40” tall. For
taller enclosures that require a 3-point latch, the C361KR (purchase separately) will
also be needed.
Door Interlocking safety roller kit for use with the C361KJ4 and C361KJ6 safety
handle kits when the SDN12 series enclosure is taller than 40 inches and 3-point
latching is required. Kit includes roller and all hardware.
Note: The 1/4” x 1/2” standard mill rectangular locking bar is not supplied with these kits. The bar is
supplied with the enclosures.