SENTRON 3WL5 Air Circuit Breakers/
Non-Automatic Air Circuit Breakers
according to UL 489/IEC
Catalog
4/2
4/6
4/6
4/7
4/8
4/9
4/15
4/16
4/28
Technical Information
4/29
4/35
4/40
4/45
4/50
4/51
4/60
4/62
4
SENTRON 3WL5 Air Circuit
Breakers/Non-Automatic Air
Circuit Breakers
According to UL 489/IEC 60947-2
for AC up to 5000 A
Introduction
- Overview
General data
- Benefits
- Application
3-pole, fixed-mounted versions
- Selection and ordering data
3-pole, withdrawable versions
- Selection and ordering data
Options
- Selection and ordering data
Accessories and spare parts
- Overview
- Selection and ordering data
- Options
SENTRON 3WL5 Air Circuit
Breakers/Non-Automatic Air
Circuit Breakers
According to UL 489/IEC 60947-2
for AC up to 5000 A
General data
- Design
- Function
- Configuration
- Technical specifications
Project planning aids
- Characteristic curves
- Dimensional drawings
- Schematics
- More information
Siemens LV 16 · 2009
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Introduction
■ Overview
Size I
Size III
Size II
Air circuit breakers
3WL air circuit breakers/non-automatic air circuit breakers
according to UL 489 up to 5000 A
Size
I, II, III
Rated current In
A
1000, 1600, 2000, 2500, 3000,
4000, 5000
V AC
Up to 600 */347
Up to 600 */347,
Up to 600
Up to 600 */347
Size I
Size II
Size III
65 (480 V)
100 (480 V)
100 (480 V)
10000
5000
Number of poles
3-pole, 4-pole on request
Rated operational
voltage Ue
Rated ultimate
short-circuit breaking
capacity at 500 V AC
kA
Endurance
Operating 10000
cycles
Mounting position
3 0 ° 3 0 °
4
N S E 0 _ 0 0 0 6 1 a
Degree of protection
With cover
Without cover
(with door sealing frame)
3 0 °
3 0 °
N S E 0 _ 0 0 0 6 2 a
IP55
IP41
Dimensions 3-/4-pole
D
320/410
460/590
704/914
H mm
434
434
434
D mm
291
291
291
Withdrawable
H mm
465.5
465.5
465.5
D mm
471
471
471
Type
NSE0_01901
NSS0_00535
W mm
Fixed
mounting
NSE0_01900
H
W
ETU25B
ETU45B
Electronic trip units for SENTRON 3WL circuit breakers
Overload protection
✓
✓
Short-time delayed
short-circuit protection
✓
✓
Instantaneous
short-circuit protection
✓
✓
Neutral conductor protection
--
✓
Ground-fault protection
--
❑
Zone Selective Interlocking
--
❑
LCD, 4-line
--
❑
LCD, graphic
--
--
Communication through
PROFIBUS DP
--
❑
Measurement function Plus
--
❑
Selectable parameter sets
--
--
Parameters freely programmable
--
--
CubicleBUS
--
✓
✓ Standard
-- Not available
❑ Optional
4/2
Siemens LV 16 · 2009
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Introduction
Size
I
II
III
Type
3WL51
3WL52
3WL53
Switching capacity class
S
H
H
S
H
H
100
100
Short-circuit breaking capacity Icu = Ics acc. to UL 489
Up to 480 V AC
kA
65
Up to 600 V AC */347 V AC
kA
50
851)
Up to 600 V AC
kA
--
85
kA
65
85
85
85
--
Rated short-time withstand current acc. to UL 489
At max. delay time tsd = 0,4 s
Short-circuit breaking capacity Icu = Ics acc. to IEC 60947-2
Up to 500 V AC
Icm at 500 V AC
kA
kA
65
143
100
220
100
220
Up to 690 V AC
Icm at 690 V AC
kA
kA
50
105
85
187
85
187
Rated short-time withstand current Icw acc. to IEC 60947-2
0.5 s
kA
65
85
85
1s
kA
50
80
80
1)
Covered by 600 V AC (delta) test.
S
Circuit breakers with standard switching capacity S
(Icu = Ics up to 65 kA at 480 V)
H
Circuit breakers with high switching capacity H
(Icu = Ics up to 100 kA at 480 V)
4
The circuit breakers are indicated in the technical
specifications by orange backgrounds.
Siemens LV 16 · 2009
4/3
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Introduction
SENTRON 3WL5:
Superior individual products integrated into uniform power
distribution systems – up to and including industry-specific
industrial and infrastructure solutions
6
7
2
3
8
5
9
1
25
4
21
10
19
11
22
23
12
18
13
24
17
20
$Guide frames (pages 4/16)
%Main circuit connection front, flange, horizontal, vertical
(pages 4/26 and 4/27)
&Position indicator switches (pages 4/12 and 4/22)
)Shutters (page 4/25)
*COM15 PROFIBUS modules or COM16 MODBUS modules (page 4/18)
+External CubicleBUS modules (page 4/17)
,Closing solenoids, auxiliary trip units (page 4/24)
-Auxiliary conductor plug-in systems (page 4/23)
.Auxiliary switch blocks (page 4/24)
/Door sealing frames (page 4/25)
0Interlocking sets for base plate (page 4/19)
1Transparent panels, function insert (page 4/19)
4/4
Siemens LV 16 · 2009
16
15
NSE0_01902
14
2EMERGENCY-STOP pushbuttons, key operated (page 4/22)
3Motorized operating mechanisms (page 4/24)
4Operating cycles counters (page 4/22)
5Breaker status sensors (BSS) (page 4/18)
6Protective devices with device holder, electronic trip units (ETU) (page 4/17)
7Remote reset solenoids (page 4/19)
8Breaker data adapters (BDA) (page 4/17)
9Four-line displays (page 4/17)
:Ground-fault protection modules (page 4/17)
;Rated current modules (page 4/17)
<Measuring function modules (page 4/18)
=Circuit breakers (pages 4/7 to 4/9)
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Introduction
Communication-capable circuit breakers (ETU45B electronic trip units)
21
Ethernet
19
20
PROFIBUS
4
8
5
14
22
15
16
6
1
18
7
CubicleBUS
10
1
17
11
9
12
13
3
1
SENTRON 3VL
12 ETU electronic trip unit
2
LCD ETU electronic trip unit
13 Measurement function Plus
3
ETU electronic trip unit
14 Zone Selective Interlocking module
4
COM10 PROFIBUS module including Zone Selective Interlocking
15 Digital output module with relay contacts
5
COM20 PROFIBUS module2) including Zone Selective Interlocking
16 Digital output module with relay contacts, configurable
6
Breaker Data Adapter (BDA)
17 Analog output module
7
BDA Plus with Ethernet interface
18 Digital input module
8
Browser-capable I/O device (e.g. notebook)
19 Switch ES Power on PC
9
SENTRON 3WL
20 PLC e.g. SIMATIC S7
10 COM15 PROFIBUS module1)
21 SIMATIC powercontrol
11 Breaker Status Sensor (BSS)
22 SENTRON PAC
4
NSE0_01105h
2
1) For a MODBUS connection you need the COM16 module.
2) For a MODBUS connection you need the COM21 module.
Features
• Coordinated communication concept using the PROFIBUS DP
or MODBUS, ranging from 16 A to 5000 A with SENTRON 3VL
and SENTRON 3WL5
• The high level of modularity of circuit breakers and accessories
allows easy retrofitting of all communication components
• Significant additional benefits for the switchboard due to the
possibility of linking up external input and output modules to
the circuit breaker-internal CubicleBUS of the SENTRON 3WL5
• Innovative software products for parameterization, operation,
monitoring, and diagnostics of SENTRON circuit breakers, both
locally or via PROFIBUS DP, MODBUS or Ethernet/Intranet/
Internet
Communication:
• For air circuit breakers with optional communication function
(ETU45B electronic trip units) see pages 4/7 and 4/8.
• For accessories see pages 4/17 and 4/18.
• For further information, see also Catalog LV 1 "Low-Voltage
Controls and Distribution – SIRIUS, SENTRON, SIVACON",
chapter "Power Management System" and "Software for Power
Distribution".
Complete integration of the SENTRON circuit breakers into the
Totally Integrated Power and Totally Integrated Automation
solutions
Siemens LV 16 · 2009
4/5
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
General data
■ Benefits
■ Application
Low space requirements
The SENTRON 3WL5 devices require very little space. Size I
devices (up to 1600 A) fit into a 400 mm wide switchgear panel.
Size III devices (up to 5000 A) are the smallest of their kind and
with their construction width of 704 mm fit into a 800 mm wide
switchgear panel.
Modular design
Components like auxiliary trip units, motorized operating
mechanisms, electronic trip units, current sensors, auxiliary
circuit signaling switches, automatic reset devices, interlocks or
engagement operating mechanisms can all be exchanged or
retrofitted at a later stage, thus allowing the circuit breaker to be
adapted to new, changing requirements.
Retrofittable modules for electronic trip units
Modularity is one of the main features of the new SENTRON 3WL5
circuit breakers.
Special LCDs, ground-fault modules, rated current modules and
communication modules for the electronic trip units are available for
fast and easy retrofitting and adaptation to changing requirements.
Communication
4
The use of modern communication-capable circuit breakers
opens up completely new possibilities in terms of start-up,
parameterization, diagnostics, maintenance and operation.
This allows many different ways of reducing costs and improving
productivity in industrial plants, buildings and infrastructure
projects to be achieved.
• Timely information and response can prevent plant stoppages
• Effective diagnostics management
• Measured values are the basis for efficient load management,
for drawing up power demand profiles and for assigning energy
to cost centers
• Preventive maintenance reduces the risk of expansive plant
down-times
4/6
Siemens LV 16 · 2009
• As incoming-feeder, distribution, tie, and outgoing-feeder circuit breakers in electrical installations
• For switching and protecting motors, capacitors, generators,
transformers, busbars and cables
Due to the reinforced use of electronic I&C systems, the demands
made on air circuit breakers in terms of operator control and
monitoring of network processes have increased.
The extensive, coordinated SENTRON range of devices covers
all applications between 16 A and 5000 A with compact and air
circuit breakers.
Standards
SENTRON 3WL5 circuit breakers comply with:
• UL 489
• IEC 60947-2
• DIN VDE 0660 Part 101
• Climate-proof according to IEC 60068-2-30.
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
3-pole, fixed-mounted versions
■ Selection and ordering data
Size
Max. rated circuit
breaker current
In max.
Rated current1)
In
Switching capacity 480 V
A
A
kA
DT
Order No.
Order No. supplements,
see page 4/9
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Horizontal main circuit connection
I
I
1000
1600
1000
1600
65
65
B
B
3WL51 10-3@@32-....
3WL51 16-3@@32-....
1
1
1 unit
1 unit
103
103
43.000
43.000
II
II
II
2000
2500
3000
2000
2500
3000
100
100
100
B
B
B
3WL52 20-4@@32-....
3WL52 25-4@@32-....
3WL52 30-4@@32-....
1
1
1
1 unit
1 unit
1 unit
103
103
103
56.000
59.000
64.000
III
III
4000
5000
4000
5000
100
100
C
C
3WL53 40-4@@32-....
3WL53 50-4@@32-....
1
1
1 unit
1 unit
103
103
82.000
82.000
Vertical main circuit connection
I
I
1000
1600
1000
1600
65
65
B
B
3WL51 10-3@@31-....
3WL51 16-3@@31-....
1
1
1 unit
1 unit
103
103
43.000
43.000
II
II
II
2000
2500
3000
2000
2500
3000
100
100
100
B
B
B
3WL52 20-4@@31-....
3WL52 25-4@@31-....
3WL52 30-4@@31-....
1
1
1
1 unit
1 unit
1 unit
103
103
103
56.000
59.000
64.000
III
III
4000
5000
4000
5000
100
100
C
C
3WL53 40-4@@31-....
3WL53 50-4@@31-....
1
1
1 unit
1 unit
103
103
82.000
82.000
Front main circuit connection, single hole
I
I
1000
1600
1000
1600
65
65
B
B
3WL51 10-3@@33-....
3WL51 16-3@@33-....
1
1
1 unit
1 unit
103
103
43.000
43.000
II
II
II
2000
2500
3000
2000
2500
3000
100
100
100
B
B
B
3WL52 20-4@@33-....
3WL52 25-4@@33-....
3WL52 30-4@@33-....
1
1
1
1 unit
1 unit
1 unit
103
103
103
56.000
59.000
64.000
III
4000
4000
100
C
3WL53 40-4@@33-....
1
1 unit
103
82.000
Front main circuit connection, double hole
I
I
1000
1600
1000
1600
65
65
B
B
3WL51 10-3@@34-....
3WL51 16-3@@34-....
1
1
1 unit
1 unit
103
103
43.000
43.000
II
II
II
2000
2500
3000
2000
2500
3000
100
100
100
B
B
B
3WL52 20-4@@34-....
3WL52 25-4@@34-....
3WL52 30-4@@34-....
1
1
1
1 unit
1 unit
1 unit
103
103
103
56.000
59.000
64.000
III
4000
4000
100
C
3WL53 40-4@@34-....
1
1 unit
103
82.000
Non-automatic air circuit breakers2)
Without electronic trip unit
Order No. supplements
Additional
price
AA
None
Versions without ground-fault protection
ETU25B: Protection functions LSI
CB
x
ETU45B: Protection functions LSIN3)
EB
x
ETU45B: Protection functions LSIN3) with 4-line display
FB
x
Versions with ground-fault protection
ETU45B: Protection functions LSING3)4)
EG
x
ETU45B: Protection functions LSING3)4) with 4-line display
FG
x
Electronic trip units
Standard Order No. supplements (for further Order No. supplements, see page 4/9)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary trip units; auxiliary switch 2 NC + 2 NO
1AA2
None
x = additional price
4-pole version on request.
Order No. supplements required, see page 4/9.
Note: Max. voltage for auxiliary circuits 240 V.
1)
The rated current is determined by the rated current module. For the standard
version, the supplied module is equal to the rated current. If a lower rated
current is required, adaptation by rated current module on page 4/17.
2)
For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see "Technical
Specifications", page 4/45.
3)
Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 4/18.
4)
For ETU45B with ground-fault protection module GFM AT (alarm and tripping)
see page 4/17.
* You can order this quantity or a multiple thereof.
Siemens LV 16 · 2009
4/7
4
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
3-pole, withdrawable versions
■ Selection and ordering data
Size
Max. rated circuit
breaker current
In max.
Rated current1)
In
Switching capacity 480 V
A
A
kA
DT
Order No.
Order No. supplements,
see page 4/9
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Without guide frames (for guide frames, see page 4/16)
I
I
1000
1600
1000
1600
65
65
B
B
3WL51 10-3@@35-....
3WL51 16-3@@35-....
1
1
1 unit
1 unit
103
103
45.000
45.000
II
II
II
2000
2500
3000
2000
2500
3000
100
100
100
B
B
B
3WL52 20-4@@35-....
3WL52 25-4@@35-....
3WL52 30-4@@35-....
1
1
1
1 unit
1 unit
1 unit
103
103
103
60.000
63.000
68.000
III
III
4000
5000
4000
5000
100
100
C
C
3WL53 40-4@@35-....
3WL53 50-4@@35-....
1
1
1 unit
1 unit
103
103
88.000
88.000
With guide frames, horizontal main circuit connection
I
I
1000
1600
1000
1600
65
65
B
B
3WL51 10-3@@36-....
3WL51 16-3@@36-....
1
1
1 unit
1 unit
103
103
70.000
70.000
II
II
II
2000
2500
3000
2000
2500
3000
100
100
100
B
B
B
3WL52 20-4@@36-....
3WL52 25-4@@36-....
3WL52 30-4@@36-....
1
1
1
1 unit
1 unit
1 unit
103
103
103
91.000
102.000
113.000
III
III
4000
5000
4000
5000
100
100
C
C
3WL53 40-4@@36-....
3WL53 50-4@@36-....
1
1
1 unit
1 unit
103
103
148.000
148.000
With guide frames, vertical main circuit connection
4
I
I
1000
1600
1000
1600
65
65
B
B
3WL51 10-3@@37-....
3WL51 16-3@@37-....
1
1
1 unit
1 unit
103
103
70.000
70.000
II
II
II
2000
2500
3000
2000
2500
3000
100
100
100
B
B
B
3WL52 20-4@@37-....
3WL52 25-4@@37-....
3WL52 30-4@@37-....
1
1
1
1 unit
1 unit
1 unit
103
103
103
91.000
102.000
113.000
III
III
4000
5000
4000
5000
100
100
C
C
3WL53 40-4@@37-....
3WL53 50-4@@37-....
1
1
1 unit
1 unit
103
103
148.000
148.000
With guide frames, connecting flanges
I
I
1000
1600
1000
1600
65
65
B
B
3WL51 10-3@@38-....
3WL51 16-3@@38-....
1
1
1 unit
1 unit
103
103
70.000
70.000
II
II
II
2000
2500
3000
2000
2500
3000
100
100
100
B
B
B
3WL52 20-4@@38-....
3WL52 25-4@@38-....
3WL52 30-4@@38-....
1
1
1
1 unit
1 unit
1 unit
103
103
103
91.000
102.000
113.000
III
4000
4000
100
C
3WL53 40-4@@38-....
1
1 unit
103
148.000
Non-automatic air circuit breakers2)
Without electronic trip unit
Order No. supplements
Additional
price
AA
None
Versions without ground-fault protection
ETU25B: Protection functions LSI
CB
x
ETU45B: Protection functions LSIN3)
EB
x
ETU45B: Protection functions LSIN3) with 4-line display
FB
x
Versions with ground-fault protection
ETU45B: Protection functions LSING3)4)
EG
x
ETU45B: Protection functions LSING3)4) with 4-line display
FG
x
Electronic trip units
Standard Order No. supplements (for further Order No. supplements for circuit breakers and guide frames, see page 4/9)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary trip units; auxiliary switch 2 NC + 2 NO
1AA2
None
x = additional price
4-pole version on request.
Order No. supplements required, see page 4/9.
Note: Max. voltage for auxiliary circuits 240 V.
1)
The rated current is determined by the rated current module. For the standard
version, the supplied module is equal to the maximum rated current. If a
lower rated current is required, adaptation by rated current module on
page 4/17.
2)
For permissible rated short-time current Icc and rated short-circuit making
capacity Icm for non-automatic air circuit breakers see "Technical Specifications", page 4/45.
3)
Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral
point of the transformer are to be ordered separately, see page 4/18.
4)
For ETU45B with ground-fault protection module GFM AT (alarm and tripping)
see page 4/17.
4/8
Siemens LV 16 · 2009
* You can order this quantity or a multiple thereof.
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Options
■ Selection and ordering data
Order No. supplement
Additional price
3WL 5 . . . - . . . . . -7 7 7 7
Operating mechanisms
Manual operating mechanism with mechanical closing
1
None
2
3
x
x
4
5
6
x
x
x
Manual operating mechanism with mechanical and
electrical closing,
closing solenoid suitable for uninterrupted duty,
100 % ON period
Closing solenoid
AC 50/60 Hz V
V DC
120
240
125
240
Manual/motorized operating mechanism with mechanical and
electrical closing,
closing solenoid suitable for uninterrupted duty,
100 % ON period
Motor
Closing solenoid
AC 50/60 Hz V
V DC
AC 50/60 Hz V
V DC
208 ... 240
110 ... 127
--
220 ... 250
110 ... 125
24
240
120
--
240
125
24
To order different voltages for motorized operating mechanism and
closing solenoid or closing solenoid for synchronization purposes:
"1" at the 13th position of the Order No. and order codes, see page 4/11.
1st auxiliary trip units
Without 1st auxiliary trip unit
A
None
B
C
D
E
F
G
x
x
x
x
x
x
4
Shunt trip unit suitable for uninterrupted duty, 100 % ON period
Operating range 0.85 ... 1.1 x Us
Us AC 50/60 Hz V Us V DC
----120
240
24
30
48
60
125
240
2nd auxiliary trip units
Without 2nd auxiliary trip unit
A
None
B
C
D
E
F
G
x
x
x
x
x
x
J
K
L
U
M
N
x
x
x
x
x
x
Q
R
S
x
x
x
Shunt trip unit suitable for uninterrupted duty, 100 % ON period
Operating range 0.85 ... 1.1 x Us
Us AC 50/60 Hz V Us V DC
-24
-30
-48
-60
120
125
240
240
Undervoltage release, instantaneous ( 80 ms),
short-delay ( 200 ms)
Operating range 0.85 ... 1.1 x Us
Us AC 50/60 Hz V Us V DC
----120
240
24
30
48
60
125
250
Undervoltage release, can be delayed between 0.2 s and 3.2 s
Operating range 0.85 ... 1.1 x Us
Us AC 50/60 Hz V Us V DC
-120
240
48
125
250
Auxiliary switches
1st auxiliary switch block
2 NO + 2 NC
2
None
1st + 2nd auxiliary switch block
4 NO + 4 NC
6 NO + 2 NC
5 NO + 3 NC
4
7
8
x
x
x
x = additional price
Siemens LV 16 · 2009
4/9
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Options
Add "–Z" to the complete Order No. and
indicate the appropriate order code(s).
Order No. with "–Z"
1 2 3 4 5
6 7
Additional price
8 9 10 11 12
13 14 15 16
3WL 5 . . . - . . . . . - . . . . - Z
and additional order code(s)
@@@+ . . . + . . .
Code for
"Further versions"–Z
Special packaging
Additional price
Special packaging for extended technical requirements
Cardboard packaging with wax coating (moisture protection),
internal bracing, tilt indicators
A 6 0
Rated current modules/Rating plugs
x
Additional price
Rated current
In
A
Only one module is possible per For size I, II
circuit breaker.
As standard the overcurrent
trip units are equipped with a
rated current module which is
equal to the maximum rated
current circuit breaker (In max).
The rated current of the selected
rated current module must be
smaller than In max.
For size I, II, III
250
B 0 2
None
315
B 0 3
None
400
B 0 4
None
500
B 0 5
None
630
B 0 6
None
800
B 0 8
None
1000
B 1 0
None
1250
B 1 2
None
1600
B 1 6
None
2000
B 2 0
None
2500
B 2 5
None
3000
B 3 0
None
3200
B 3 2
None
4000
B 4 0
None
5000
B 5 0
None
5-digit mechanical
operating cycles counter1)
C 0 1
x
Electrical ON button
Button with sealing cap
in the operator panel2)
Key operation with lock CES
possible only for circuit breakers
with closing solenoid
C 1 1
x
C 1 2
x
For size II, III
4
For size III
Indication/operator control elements, door sealing frames
Storage status
signaling switches2) (S21)
1 NO
C 2 0
x
Ready-to-close signaling
switch (S20)
1 NO
C 2 2
x
For the first auxiliary trip unit (S22)
C 2 6
x
For the second auxiliary trip unit (S23)
C 2 7
x
Motor shutdown switch
in the operator panel3)
S 2 5
x
EMERGENCY-STOP pushbuttons Mushroom pushbutton instead of
the mechanical OFF pushbutton
S 2 4
x
Door sealing frames
T 4 0
x
Signal switches2)
x = additional price
1)
Only possible with motorized operating mechanism.
Not possible with communications connection option, order code "F02" or
"F12".
3) Only for circuit breakers with motorized operating mechanism, not possible
with order codes "C11", "C12".
2)
4/10
Siemens LV 16 · 2009
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Options
Add "–Z" to the complete Order No. and
indicate the appropriate order code(s).
Order No. with "–Z"
1 2 3 4 5
6 7
Additional price
8 9 10 11 12
13 14 15 16
3WL 5 . . . - . . . . . - . . . . - Z
and additional order code(s)
@@@+. . . + . . .
Code for
"Further versions"–Z
Lockout devices and remote resets
Automatic reset of the lockout device
K 0 1
x
Tripped signal switches1)2)
K 0 7
x
K
K
K
K
1
1
1
1
0
1
2
3
x
x
x
x
M
M
M
M
0
0
0
0
1
3
5
6
x
x
x
x
24
30
48
M2 1
M2 2
M2 3
x
x
x
60
125
240
M2 4
M2 5
M2 6
x
x
x
M
M
M
M
3
3
3
3
1
3
5
6
x
x
x
x
M
M
M
M
4
4
4
4
1
3
5
6
x
x
x
x
Breaker status sensor (BSS)
F 0 1
x
PROFIBUS communications interfaces4)
including COM15 and breaker status sensor (BSS)
F 0 2
x
MODBUS communications interfaces4)
including COM16 and breaker status sensor (BSS)
F 1 2
x
Measurement function Plus (without PROFIBUS/MODBUS
communications interface) 5)
F 0 5
x
1 CO contact
Remote reset solenoid for displays and reset buttons
including automatic reset of the lockout device
AC 50/60 Hz V
V DC
--120
220 ... 240
24
48
120
220 ... 240
Motorized operating mechanisms and closing/opening solenoids
Motorized operating mechanisms
Only possible if the 13th position of the Order No. = "1"
Motor
AC 50/60 Hz V
V DC
--110 ... 127
208 ... 240
24 ... 30
48 ... 60
110 ... 125
220 ... 250
4
Closing solenoids suitable for uninterrupted duty, 100 % ON period –
Only possible if the 13th position of the Order No. = "1"
Activation solenoids
AC 50/60 Hz V
V DC
----120
240
Closing solenoids3) – unsuitable for uninterrupted duty, 5 % ON period –
Only possible if the 13th position of the Order No. = "1"
Activation solenoids
AC 50/60 Hz V
V DC
--120
240
24
48
125
250
Opening solenoids (shunt trip unit)6) –
unsuitable for uninterrupted duty, 5 % ON period
Activation solenoids
AC 50/60 Hz V
V DC
--120
240
24
48
125
250
Communication and measurement functions
x = additional price
1)
Not possible with communications connection option, order code "F02" or
"F12".
2)
Not available for non-automatic air circuit breakers.
3)
Overexcited, i.e. closing time 50 ms (standard > 80 ms).
4) If ordering withdrawable circuit breaker and guide frame separately,
specify order code "F02" or "F12" for withdrawable circuit breaker only.
5)
6)
Additional voltage transformers are required for connection of the
measurement function Plus, see page 4/18.
Only possible if the 14th position of the Order No. for the circuit breaker is
"A", i.e. "without 1st auxiliary trip unit".
Siemens LV 16 · 2009
4/11
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Options
Add "–Z" to the complete Order No. and
indicate the appropriate order code(s).
Order No. with "–Z"
1234 5 6 7
Additional price
8 9 10 11 12
13 14 15 16
3WL 5 . . . - . . . . . - . . . . -Z
and additional order code(s)
@@@ + . . . + . . .
Code for
"Further versions"
-Z
Order code
for fixedmounted
version
Order code
for withdrawable
version
@@@
@@@
S 5 5
-- -- --
x
For withdrawable circuit breakers -with guide frame
R 5 5
x
For guide frames
--
R 5 6
x
For withdrawable circuit breakers --
R 5 7
x
Shutters
2-part
lockable
with padlocks1)
3-pole
Size I
Size II
Size III
----
R 2 1
R 2 1
R 2 1
x
x
x
Position indicator switches
for guide frames
Connected Test
position
position
Disconnected
position
1 CO
1 CO
1 CO
--
R 1 5
x
3 CO
2 CO
1 CO
--
R 1 6
x
Interlocks, covers, position indicator switches
Mutual mechanical
interlockings
(interlocking module
with Bowden wire 2 m)
4
Fixed-mounted circuit breakers
Add "–Z" to the complete Order No. and
indicate the appropriate order code(s).
Order No. with "–Z"
1 2 3 4 5
6 7
Additional price
8 9 10 11 12
13 14 15 16
3WL 5 . . . - . . . . . - . . . . - Z
and additional order code(s)
@@@
+. . . + . . .
Code for
"Further versions"–Z
EMC filters
Common-mode interference
F 3 1
suppressor filters (e.g. in IT
networks, caused by frequency
converters)
EMC filters
Insertion loss (asymmetric) in
the range 40 kHz to 10 MHz >
40 dB.
x = additional price
1)
Padlocks not included in scope of supply.
4/12
Siemens LV 16 · 2009
x
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Options
Add "–Z" to the complete Order No.
and indicate the appropriate order
code(s).
Order No. with "–Z"
8 9 10 11 12
1234 5 6 7
13 14 15 16
3WL 5 . . . - . . . . . - . . . . -Z
and additional order code(s)
@@@ + . . . + . . .
Code for
"Further versions"
Locking devices
Locking devices against
unauthorized closing,
in the operator panels
The disconnector unit fulfills the
requirements for main control
switches acc. to EN 60204
(VDE 0113) and UL 489.
@@@
@@@
Additional
price for
withdrawable
version
S 0 1
x
S 0 1
x
Made by IKON
S 0 3
x
S 0 3
x
Assembly kit FORTRESS or Castell1)
S 0 5
x
S 0 5
x
Assembly kit for padlocks2)
S 0 7
x
S 0 7
x
Made by Ronis
S 0 8
x
S 0 8
x
Made by Profalux
S 0 9
x
S 0 9
x
S 2 4
S 2 4
Made by CES
--
R 6 1
x
Made by Ronis
--
R 6 8
x
Made by Profalux
--
R 6 0
x
4
S 3 3
Locking devices for operating
mechanism handles
with padlock2)
Locking devices to prevent
movement of the withdrawable
circuit breakers
Safety lock for mounting on
the circuit breaker
Order code
for withdrawable
version
Made by CES
EMERGENCY-STOP pushbuttons Mushroom pushbutton instead of
the mechanical OFF pushbutton
Locking devices against
unauthorized closing,
for withdrawable circuit breakers
The disconnector unit fulfills the
requirements for main circuit
breakers acc. to EN 60204
(VDE 0113) and UL 489, consisting
of lock in the cabinet door,
active in connected position,
the function is retained when the
circuit breaker is replaced
-Z
Order code Additional
for fixed
price for
mounting
fixed-mounted
version
x
S 3 3
x
Made by CES
--
S 7 1
x
Made by Profalux
--
S 7 5
x
Made by Ronis
--
S 7 6
x
--
R 8 1
x
--
R 8 5
x
--
R 8 6
x
R 3 0
x
R 5 0
x
P 6 1
x
Locking devices
Locking devices to prevent
Made by CES
movement of the withdrawable
Made by Profalux
circuit breakers in disconnected
Made by Ronis
positions,
consisting of Bowden wire and lock
in the cabinet door
Locking devices
To prevent opening of the cabinet door in: S 3 0
ON position (fixed-mounted version)/
in connected position (withdrawable
version)
To prevent movement
with the cabinet door open
x
--
Connection methods for auxiliary conductors
Connections for screwless
terminals (tension spring)
N 6 1
x
x = additional price
1)
2)
Locks must be ordered from the manufacturer.
Padlock not included in the scope of supply.
Siemens LV 16 · 2009
4/13
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Options
Add "–Z" to the complete Order No. and
indicate the appropriate order code(s).
Order No. with "–Z"
1234 5 6 7
8 9 10 11 12
13 14 15 16
3WL 5 . . . - . . . . . - . . . . -Z
and additional order code(s)
@@@ + . . . + . . .
Code for
"Further versions"–Z
For withdrawable circuit breakers with guide frames
or without guide frames
Additional price
3-pole
To select this connection method, the 12th
position of the Order No. for the
circuit breaker must be a "6"
Connection methods for main circuit connections
4
Top and bottom:
Accessible from front,
single hole
Size I, up to 1600 A
Size II, up to 2000 A
Size II, up to 2500 A
Size II, up to 3000 A
Size III, up to 4000 A
P
P
P
P
P
0
0
0
0
0
0
0
0
0
0
x
x
x
x
x
Top and bottom:
Accessible from front,
double hole
Size I, up to 1600 A
Size II, up to 2000 A
Size II, up to 2500 A
Size II, up to 3000 A
Size III, up to 4000 A
P
P
P
P
P
0
0
0
0
0
1
1
1
1
1
x
x
x
x
x
Top:
Horizontal,
double hole
Bottom:
Accessible from front,
single hole
Size I, up to 1600 A
Size II, up to 2000 A
Size II, up to 2500 A
Size II, up to 3000 A
Size III, up to 4000 A
P
P
P
P
P
0
0
0
0
0
7
7
7
7
7
x
x
x
x
x
Top:
Vertical
Bottom:
Horizontal
Size I, up to 1600 A
Size II, up to 2000 A
Size II, up to 2500 A
Size II, up to 3000 A
Size III, up to 4000 A
Size III, up to 5000 A
P
P
P
P
P
P
1
1
1
1
1
1
8
8
8
8
8
8
x
x
x
x
x
x
Top:
Connecting flange
Bottom:
Horizontal
Size I, up to 1600 A
Size II, up to 2000 A
Size II, up to 2500 A
Size II, up to 3000 A
Size III, up to 4000 A
P
P
P
P
P
1
1
1
1
1
9
9
9
9
9
x
x
x
x
x
Top:
Horizontal
Bottom:
Vertical
Size I, up to 1600 A
Size II, up to 2000 A
Size II, up to 2500 A
Size II, up to 3000 A
Size III, up to 4000 A
Size III, up to 5000 A
P
P
P
P
P
P
2
2
2
2
2
2
3
3
3
3
3
3
x
x
x
x
x
x
Additional price
3-pole
For fixed-mounted circuit breakers
To select this connection method, the 12th
position of the Order No. for the
circuit breaker must be a "2"
Connection methods for main circuit connections
Top:
Horizontal
Bottom:
Accessible from front,
single hole
Size I, up to 1600 A
Size II, up to 2000 A
Size II, up to 2500 A
Size II, up to 3000 A
Size III, up to 4000 A
N
N
N
N
N
1
1
1
1
1
1
1
1
1
1
x
x
x
x
x
Top:
Vertical
Bottom:
Horizontal
Size I, up to 1600 A
Size II, up to 2000 A
Size II, up to 2500 A
Size II, up to 3000 A
Size III, up to 4000 A
Size III, up to 5000 A
N
N
N
N
N
N
2
2
2
2
2
2
0
0
0
0
0
0
x
x
x
x
x
x
Top:
Horizontal
Bottom:
Vertical
Size I, up to 1600 A
Size II, up to 2000 A
Size II, up to 2500 A
Size II, up to 3000 A
Size III, up to 4000 A
Size III, up to 5000 A
N
N
N
N
N
N
2
2
2
2
2
2
4
4
4
4
4
4
x
x
x
x
x
x
x = additional price
4/14
Siemens LV 16 · 2009
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Accessories and spare parts
■ Overview
Determination of the number of auxiliary supply connectors required
NSE0_01104
This selection is only required if the guide frame is ordered under a
separate Order No.
X7
X6
X5
X8
The required number of auxiliary supply connectors
depends on:
• Operating mechanism type
• Electronic trip unit with/without current transformer
• Type and number of auxiliary trip units
• Number of auxiliary switches
• COM15/COM16 communication interface
Number of
auxiliary supply
connectors
Terminal
a
First auxiliary supply connector X6 always required.
1
X6
b
b1
b2
b3
Operating mechanisms
Manual operating mechanism with stored-energy feature with mechanical closing
Manual operating mechanism with stored-energy feature with mechanical and electrical closing
Manual/motorized operating mechanism with stored-energy feature with mechanical and electrical closing
0
0
+1
X6
X5
c
c1
c2
Electronic trip units
Electronic trip units ETU25B
Electronic trip units ETU45B(internal CubicleBUS)
0
+1
X8
c3
c4
Connections for external current transformers for overload protection in the N conductor and ground-fault protection
Current transformer installed in the N conductor (required with 3-pole circuit breakers if c2 is not selected)
Current transformer in the neutral point of the transformer (required if c2 or c3 is not selected)
+1
+1
X8
X8
d
d1
d2
Auxiliary trip units
With/without 1st auxiliary trip unit (shunt trip unit F1)
2nd auxiliary trip unit (shunt trip unit F2, undervoltage release F3, delayable undervoltage release F4)
0
+1
X6
X5
e
e1
e2
Auxiliary switch blocks
1st auxiliary switch block 2 NO + 2 NC
1st and 2nd auxiliary switch block 4 NO + 4 NC or 6 NO + 2 NC or 5 NO + 3 NC (required if b3 or d2 is not selected)
0
+1
X6
X5
f
f1
f2
Communications modules
Without communication module COM15/COM16
With communication module COM15/COM16 –
occupies the entire terminal strip X7, making the following options no longer possible:
• Tripped signal switch S24
• Stored-energy status indication S21
• Electrical ON button S10
• Signaling switch on first and second auxiliary trip unit S22 + S23
0
+1
X7
g
g1
g2
g3
g4
g5
g6
g7
g8
Optional signals/accessories
Tripped signal switch S24 (only possible if f2 is not selected)
Stored-energy status indication S21 (only possible if f2 is not selected, required if g1 is not selected)
Electrical ON button S10 (only possible if f2 is not selected, required if g1 or g2 is not selected)
Signal switch on first auxiliary trip unit S22 (only possible if f2 is not selected, required if g1, g2 or g3 is not selected)
Signal switch on second auxiliary trip unit S23 (only possible if f2 is not selected, required if g1, g2, g3 or g4 is not selected)
Ready-to-close signaling switch S20
Motor shutdown switch S12 (only possible if motorized operating mechanism is selected)
Remote reset magnet F7 (required if c2 is not selected)
+1
+1
+1
+1
+1
0
0
+1
X7
X7
X7
X7
X7
X6
X5
X8
h
Total number of auxiliary supply connectors
(max. 4)
Siemens LV 16 · 2009
4/15
4
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Accessories and spare parts
■ Selection and ordering data
Guide frames for circuit breakers according to UL 489
Size
Max. rated
circuit breaker
current In max.
DT
Guide frames for 3-pole
circuit breakers
Order No.
(Order No. supplements
required acc. to
table below)
A
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Front main circuit connection, single hole
I
I
II
II
II
III
1000
1600
2000
2500
3000
4000
B
B
B
B
B
B
3WL9 251-1AA@@-@@A1
3WL9 251-2AA@@-@@A1
3WL9 252-3AA@@-@@A1
3WL9 252-4AA@@-@@A1
3WL9 252-5AA@@-@@A1
3WL9 253-6AA@@-@@A1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
25.000
25.000
31.000
39.000
45.000
60.000
B
B
B
B
B
B
3WL9 251-1AB@@-@@A1
3WL9 251-2AB@@-@@A1
3WL9 252-3AB@@-@@A1
3WL9 252-4AB@@-@@A1
3WL9 252-5AB@@-@@A1
3WL9 253-6AB@@-@@A1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
25.000
25.000
31.000
39.000
45.000
60.000
B
B
B
B
B
B
B
3WL9 251-1AC@@-@@A1
3WL9 251-2AC@@-@@A1
3WL9 252-3AC@@-@@A1
3WL9 252-4AC@@-@@A1
3WL9 252-5AC@@-@@A1
3WL9 253-6AC@@-@@A1
3WL9 253-7AC@@-@@A1
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
25.000
25.000
31.000
39.000
45.000
60.000
60.000
B
B
B
B
B
B
B
3WL9 251-1AD@@-@@A1
3WL9 251-2AD@@-@@A1
3WL9 252-3AD@@-@@A1
3WL9 252-4AD@@-@@A1
3WL9 252-5AD@@-@@A1
3WL9 253-6AD@@-@@A1
3WL9 253-7AD@@-@@A1
1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
103
25.000
25.000
31.000
39.000
45.000
60.000
60.000
B
B
B
B
B
B
3WL9 251-1AE@@-@@A1
3WL9 251-2AE@@-@@A1
3WL9 252-3AE@@-@@A1
3WL9 252-4AE@@-@@A1
3WL9 252-5AE@@-@@A1
3WL9 253-6AE@@-@@A1
1
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
103
25.000
25.000
31.000
39.000
45.000
60.000
Front main circuit connection, double hole
I
I
II
II
II
III
1000
1600
2000
2500
3000
4000
Horizontal main circuit connection
4
I
I
II
II
II
III
III
1000
1600
2000
2500
3000
4000
5000
Vertical main circuit connection
I
I
II
II
II
III
III
1000
1600
2000
2500
3000
4000
5000
Main circuit connection connecting flanges
I
I
II
II
II
III
1000
1600
2000
2500
3200
4000
Number of auxiliary supply connectors
None
1 connector
2 connectors
3 connectors
4 connectors
For required number of auxiliary supply connectors,
see table on page 4/15
Order No. supplements
Additional
price
None
x
x
x
x
0
1
2
3
4
Type of auxiliary circuit connections
None
With screw connections (SIGUT)
With screwless connection method (tension spring)
None
x
x
0
1
2
Position indicator switches
None
0
None
Option 1
Connected position 1 CO contact,
Test position 1 CO contact,
Disconnected position 1 CO contact
1
x
Option 2
Connected position 3 CO contacts,
Test position 2 CO contacts,
Disconnected position 1 CO contact
2
x
Shutters
None
With shutter,
2-part,
Lockable
Size I
Size II
Size III
x = additional price
4-pole version on request.
4/16
Siemens LV 16 · 2009
A
B
None
x
x
x
All other accessory parts must be ordered by specifying "-Z"
and the corresponding order code, see page 4/12 "Interlocks,
Covers, Position Indicator Switches".
* You can order this quantity or a multiple thereof.
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Accessories and spare parts
Designation
DT Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Electronic trip units
Type
With protection
function
ETU25B
ETU45B without measurement
function Plus
ETU45B with measurement
function Plus
LSI
LSIN(G)
C
C
3WL9 352-5AA00-0AA1
3WL9 354-5AA00-0AA1
1 1 unit
1 1 unit
103
103
0.720
0.720
LSIN(G)
C
3WL9 354-5AA20-0AA1
1 1 unit
103
0.720
250
B
3WL9 111-2AA51-0AA0
1 1 unit
103
0.010
315
B
3WL9 111-2AA52-0AA0
1 1 unit
103
0.010
400
B
3WL9 111-2AA53-0AA0
1 1 unit
103
0.010
500
B
3WL9 111-2AA54-0AA0
1 1 unit
103
0.010
630
B
3WL9 111-2AA55-0AA0
1 1 unit
103
0.010
800
B
3WL9 111-2AA56-0AA0
1 1 unit
103
0.010
1000
B
3WL9 111-2AA57-0AA0
1 1 unit
103
0.010
1250
B
3WL9 111-2AA58-0AA0
1 1 unit
103
0.010
1600
B
3WL9 111-2AA61-0AA0
1 1 unit
103
0.010
2000
B
3WL9 111-2AA62-0AA0
1 1 unit
103
0.010
2500
B
3WL9 111-2AA63-0AA0
1 1 unit
103
0.010
3000
B
3WL9 111-2AA77-0AA0
1 1 unit
103
0.010
3200
B
3WL9 111-2AA64-0AA0
1 1 unit
103
0.010
4000
B
3WL9 111-2AA65-0AA0
1 1 unit
103
0.010
5000
B
3WL9 111-2AA66-0AA0
1 1 unit
103
0.010
GFM AT 45B (only for ETU45B) alarm and tripping
B
3WL9 111-2AT53-0AA0
1 1 unit
103
0.200
4-line displays for ETU45B
B
3WL9 111-1AT81-0AA0
1 1 unit
103
0.061
Digital output modules with rotary coding switches,
relay outputs
C
3WL9 111-1AT26-0AA0
1 1 unit
103
0.350
Digital output modules, configurable,
relay outputs
C
3WL9 111-1AT20-0AA0
1 1 unit
103
0.400
Digital input modules
C
3WL9 111-1AT27-0AA0
1 1 unit
103
0.300
Analog output modules
C
3WL9 111-1AT23-0AA0
1 1 unit
103
0.300
Zone Selective Interlocking modules
C
3WL9 111-1AT21-0AA0
1 1 unit
103
0.240
Breaker
Data
Adapters
(BDA)4)
Parameterization, control, diagnostics, and B
test of SENTRON circuit breakers via local
interface; Breaker Data Adapter, connection
cable to SENTRON circuit breakers and to
the programming device (e.g. notebook);
can be run with Internet Explorer with
JAVA2 VM and higher
3WL9 111-2AT28-0AA0
1 1 unit
103
0.800
BDA Plus4)
Same as BDA, but with additional Ethernet B
interface for connection to Ethernet/
Intranet/Internet
3WL9 111-2AT33-0AA0
1 1 unit
103
1.000
Connection Connection cable for connection of BDA
B
cables for
Plus to terminal X8 of the SENTRON 3WL
BDA Plus
circuit breaker. Required if neither COM15
nor COM16 nor other external CubicleBUS
3WL9 111-0AT28-0AA0
modules are available, length 2 m.
3WL9 111-0BC21-0AA0
1 1 unit
103
0.350
3ZS2 311-0CC10-0YA0
1 1 unit
133
0.200
Rated current modules/Rating plugs1)
For size
Rated current In
(A)
I, II
I, II, III
II, III
n
= 3 2 0 0 A
N S E 0 _ 0 0 9 9 2 b
3WL9 111-2AA65-0AA0 III
Ground-fault modules2)
Displays
CubicleBUS modules3)
N S E 0 _ 0 1 0 2 3 a
3WL9 111-1AT23-0AA0
Tools for parameterization, operation and monitoring
N S E 0 _ 0 1 0 2 4 a
Switch ES
Power
parameterization
software
1)
2)
Calibration, operation, monitoring, and
A
diagnostics of SENTRON circuit breakers
via PROFIBUS DP; runs under Windows 95,
Windows 98, Windows NT, Windows 2000
and Windows XP Professional, requires
additional PROFIBUS card e.g. CP5613
With the rated current module selected, the maximum rated current In max
of the circuit breaker must not be exceeded. Following applies In < In max.
For direct measurement of the ground-fault current, e.g. in the neutral point
of the transformer, a 1200 A/1 A current transformer, class 1, is required.
The internal load of the SENTRON 3WL is 0.11 m. If the ground-fault current
* You can order this quantity or a multiple thereof.
is to be determined using the vectorial sum of the phases, a transformer
must be installed in the neutral conductor.
Every CubicleBUS module is supplied with a factory-fitted 0.2 m cable.
4)
A 24 V DC power supply unit is required.
3)
Siemens LV 16 · 2009
4/17
4
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Accessories and spare parts
Designation
DT Order No.
Price
per PU
PU
PS*
(UNIT,
SET,
M)
PG Weight
per PU
approx.
kg
Retrofitting and spare parts for communication
through PROFIBUS/MODBUS
1
2
3
4
5
6
7
8
9
Device
CubicleBus
COM15 PROFIBUS modules
B
3WL9 111-1AT65-0AA0
1 1 unit 103 0.560
COM16 MODBUS modules
C
3WL9 111-1AT15-0AA0
1 1 unit 103 0.180
Breaker status sensor (BSS)
C
3WL9 111-1AT16-0AA0
1 1 unit 103 0.137
Measurement (voltage transformer
required)
function
Plus1)
B
3WL9 111-1AT03-0AA0
1 1 unit 103 0.310
PROFIBUS DP
NSE-01025
3WL9 111-1AT65-0AA0
S45
S43
S42
S40
S44
S41
NSE01026
3WL9 111-1AT16-0AA0
All communication components, CubicleBUS modules and measurement functions are available for the ETU45B trip units.
4
Accessories for communications
Preassembled
cables for
CubicleBUS
modules
SENTRON
manuals for
communication
solutions2)
0.2 m long, for connection to SENTRON 3WL
with COM15/COM16
B
3WL9 111-0BC04-0AA0
1 1 unit 103 0.020
1 m long, for connection to SENTRON 3WL
with COM15/COM16
B
3WL9 111-0BC02-0AA0
1 1 unit 103 0.050
2 m long, for connection to SENTRON 3WL
with COM15/COM16
B
3WL9 111-0BC03-0AA0
1 1 unit 103 0.060
2 m long, for connection to SENTRON 3WL
without COM15/COM16
B
3WL9 111-0BC05-0AA0
1 1 unit 103 0.070
Detailed description of the communication
functions for SENTRON circuit breakers with
PROFIBUS DP. Installation, connection,
start-up and description of Switch ES Power
and BDA.
GermanToken fee 20.–– €
EnglishToken fee 20.–– €
Free download from:
http://www.siemens.com/lowvoltage/manuals
Voltage
380 ... 690 V/100 V, class 0.5
transformers,
3-pole, for
SENTRON 3WL
with measurement function
Plus
A5E0151347-01
A5E0151353-01
B
3WL9 111-0BB68-0AA0
1 1 unit 103 2.600
Transformers for neutral conductor protection
External transformers for N conductors
(T5, see Technical Information
"General Data", "Functions",
"Measurement Method", page 4/39)
Size I
Size II
Size III
B
B
B
3WL9 111-0AA21-0AA0
3WL9 111-0AA22-0AA0
3WL9 111-0AA23-0AA0
1 1 unit
1 1 unit
1 1 unit
103 0.300
103 0.380
103 0.680
External transformers for N conductors
with copper connection pieces
(T5, see Technical Information
3WL9 111-0AA2.-0AA0 "General Data", "Functions",
"Measurement Method", page 4/39)
Size I
Size II
Size III
B
B
B
3WL9 111-0AA31-0AA0
3WL9 111-0AA32-0AA0
3WL9 111-0AA33-0AA0
1 1 unit
1 1 unit
1 1 unit
103 1.600
103 4.260
103 8.500
X
3WL9 111-0AK32-0AA0
1 1 unit
103 0.280
N S E 0 _ 0 0 9 9 0 a
N S E 0 _ 0 0 9 9 1 a
3WL9 111-0AA3.-0AA0
EMC filters
EMC filters
Common-mode interference suppressor filters (e.g. in
ungrounded networks, caused by frequency converters)
Insertion loss (asymmetric) in the range 40 kHz to
10 MHz > 40 dB
1)
If retrofitted, a measuring accuracy of 3 % is achieved.
4/18
Siemens LV 16 · 2009
2)
Manual for MODBUS communication solution available on request.
* You can order this quantity or a multiple thereof.
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Accessories and spare parts
Designation
DT Order No.
Price
per PU
PU
PS*
(UNIT,
SET,
M)
PG
Weight
per PU
approx.
kg
More accessories for electronic trip units
N S E 0 _ 0 0 9 8 3 a
E T U 2 5 B
R a t in g P lu g
T E S T
Q U E R Y
B
3WL9 111-0AT45-0AA0
1 1 unit
103
0.050
Automatic reset of the lockout devices
B
Spare part for option K01, see "-Z" + order code, page 4/11.
3WL9 111-0AK21-0AA0
1 1 unit
103
0.050
Remote reset solenoids1)
For mechanical tripped indicator
24 V DC
B
3WL9 111-0AK03-0AA0
1 1 unit
103
0.200
48 V DC
B
3WL9 111-0AK04-0AA0
1 1 unit
103
0.200
Spare part for option K10 to K13,
see "-Z" + order code, page 4/11.
120 V AC/
125 V DC
B
3WL9 111-0AK05-0AA0
1 1 unit
103
0.200
208-250 V AC/
208-250 V DC
B
3WL9 111-0AK06-0AA0
1 1 unit
103
0.200
B
3WL9 111-0AK30-0AA0
1 1 unit
103
0.150
D
3WL9 111-0AK31-0AA0
1 1 unit
103
0.020
Protective covers for
Without safety lock B
mechanical ON/OFF
Made by CES
B
Consisting of 2 transparent covers each
Made by IKON
B
4)
for sealing or for attaching padlocks ,
cover with 6.35 mm hole (for tool actuation),
lock mount for safety lock for key operation
3WL9 111-0BA21-0AA0
3WL9 111-0BA22-0AA0
3WL9 111-0BA24-0AA0
1 1 unit
1 1 unit
1 1 unit
103
103
103
0.100
0.300
0.300
B
3WL9 111-0BA31-0AA0
1
1 unit
103
0.200
B
B
B
3WL9 111-0BA33-0AA0
3WL9 111-0BA34-0AA0
3WL9 111-0BA35-0AA0
1
1
1
1 unit
1 unit
1 unit
103
103
103
0.400
0.270
0.250
B
B
3WL9 111-0BA36-0AA0
3WL9 111-0BA38-0AA0
1
1
1 unit
1 unit
103
103
0.200
0.200
B
3WL9 111-0BA41-0AA0
1
1 unit
103
0.360
B
B
B
B
B
3WL9 111-0BA51-0AA0
3WL9 111-0BA53-0AA0
3WL9 111-0BA57-0AA0
3WL9 111-0BA58-0AA0
3WL9 111-0BA50-0AA0
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
0.300
0.300
0.300
0.300
0.227
B
3WL9 111-0BA71-0AA0
1
1 unit
103
0.080
B
B
B
B
B
3WL9 111-0BA73-0AA0
3WL9 111-0BA75-0AA0
3WL9 111-0BA76-0AA0
3WL9 111-0BA77-0AA0
3WL9 111-0BA80-0AA0
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
103
103
103
103
103
0.300
0.200
0.300
0.300
0.400
B
3WL9 111-0BA43-0AA0
1
1 unit
103
0.360
Sealable covers
C L E A R
For ETU25B,
ETU45B
3WL9 111-0AT45-0AA0 Retrofittable internal CubicleBUS wiring For ETU45B
for connection to terminal X8
F 7
(without male connector2))
Retrofittable internal wiring for connection of the
external N- and G-transformers to terminal X8
(without male connector)
N S E 0 _ 0 0 9 9 9 a
3WL9 111-0AK0.-0AA0
Locking devices
NSE00980
Locking devices against
unauthorized closing,
in the operator panel
The disconnector unit
■
3WL9 111-0BA22-0AA0 fulfills the requirements for main circuit
breakers acc. to EN 60204
(VDE 0113) and UL 489
Spare part for option S01 to S09,
see "-Z" + order code, page 4/13.
Locking devices against
unauthorized closing,
for withdrawable circuit breakers ■
The disconnector unit fulfills the
3WL9 111-0BA31-0AA0 requirements for main circuit breakers
acc. to EN 60204 (VDE 0113) and
UL 489 consisting of lock in the cabinet
door, active in connected position;
function is retained when circuit breaker
is replaced
NSE00981
Assembly kit
FORTRESS or
CASTELL3)
Made by Ronis
Made by KIRKKey
Made by Profalux
Made by CES
Made by IKON
Assembly kit for
padlocks4)
Made by CES
Made by IKON
Made by KIRKKey
Made by Ronis
Made by Profalux
Spare part for option R60, R61, R68,
NSE00982
3WL9 111-0BA53-0AA0 see "-Z" + order code, page 4/13.
Locking devices for operating
mechanism handle with padlock4)
Spare part for option S33, see
"-Z" + order code, page 4/13.
Locking devices against movement
of the withdrawable circuit breakers
Safety lock for mounting
on the circuit breaker.
Spare part for option S71, S75, S76, ■
see "-Z" + order code, page 4/13.
Made by CES
Made by IKON
Made by Profalux
Made by Ronis
Made by KIRKKey
NSE00984
Interlocking system
Made by CES
3WL9 111-0BA71-0AA0 2 of the same keys for 3 switches,
Locking device OFF position,
Key-operated switch on operator panel.
A maximum of 2 switches can be
switched on.
NSE00986
3WL9 111-0BA76-0AA0
1)
Can only be used in conjunction with "automatic reset of lockout device",
e.g. "–Z" + "K01", 3WL9 111-0AK21-0AA0
2)
Required if communication is retrofitted.
* You can order this quantity or a multiple thereof.
3)
4)
Locks must be ordered from the manufacturer.
Padlock not included in the scope of supply.
■ Start of delivery on request.
Siemens LV 16 · 2009
4/19
4
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Accessories and spare parts
Designation
DT Order No.
Price
per PU
PU
PS*
(UNIT,
SET,
M)
PG
Weight
per PU
approx.
kg
Locking devices
To prevent movement of the
withdrawable circuit breakers
in disconnected positions,
consisting of Bowden wire and
lock in the cabinet door
NSE00987
Made by CES
Made by IKON
Made by Profalux
Made by Ronis
B
B
B
B
3WL9 111-0BA81-0AA0
3WL9 111-0BA83-0AA0
3WL9 111-0BA85-0AA0
3WL9 111-0BA86-0AA0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
103
103
103
103
0.800
0.800
0.800
0.800
Fixed mounting
B
3WL9 111-0BB12-0AA0
1
1 unit
103
0.600
B
3WL9 111-0BB13-0AA0
1
1 unit
103
0.150
Guide frames
B
3WL9 111-0BB15-0AA0
1
1 unit
103
0.150
Fixed-mounted circuit
breaker
B
3WL9 111-0BB21-0AA0
1
1 unit
103
2.700
Module for withdrawable B
circuit breaker with frame
3WL9 111-0BB24-0AA0
1
1 unit
103
1.130
B
3WL9 111-0BB22-0AA0
1
1 unit
103
1.100
Module for withdrawable B
circuit breaker
3WL9 111-0BB23-0AA0
1
1 unit
103
0.150
B
3WL9 111-0BB30-0AA0
1
1 unit
103
0.100
B
3WL9 112-8AH47-0AA0
1
1 unit
103
0.160
B
B
B
3WL9 111-0BB45-0AA0
3WL9 111-0BB46-0AA0
3WL9 111-0BB47-0AA0
1
1
1
1 unit
1 unit
1 unit
103
103
103
0.150
0.220
0.360
3WL9 111-0BA83-0AA0 Spare part for option R81, R85,
R86, see "-Z" + order code,
page 4/13.
To prevent opening of the
cabinet door in ON position
(can be defeated)
Spare part for option S30,
3WL9 111-0BB12-0AA0 see "-Z" + order code, page 4/13.
To prevent opening of the
Guide frames
Interlocking
cabinet door
(can be defeated)
Spare part for option R30,
see "-Z" + order code, page 4/13.
To prevent movement with
the cabinet door open
Spare part for option R50,
see "-Z" + order code, page 4/13.
Interlocks
4
Mutual mechanical interlocking,
with 2000 mm Bowden wire
(one required for each circuit
breaker)
NSE00989
3WL9 111-0BB21-0AA0
Spare part for option
S55, see "-Z" + order
code, page 4/12.
Spare part for option
R55, see "-Z" + order
code, page 4/12.
When ordered separately
Module for guide frame
Spare part for option
R56, see "-Z" + order
code, page 4/12.
Spare part for option
R57, see "-Z" + order
code, page 4/12.
Adapter for size III
Withdrawable circuit
breaker
Couplings on the circuit
breaker (with ring)
for mutual interlocking
Can be used in all circuit breakers
NSE0_01886
Bowden wires
3WL9 112-8HA47-0AA0
4/20
Siemens LV 16 · 2009
2000 mm
3000 mm
4500 mm
* You can order this quantity or a multiple thereof.
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Accessories and spare parts
Designation
DT Order No.
Price
per PU
PU
PS*
(UNIT,
SET,
M)
PG
Weight
per PU
approx.
kg
Test devices
Manual testers for electronic trip units
ETU25B and ETU45B
B
3WL9 111-0AT32-0AA0
1
1 unit
103
1.100
C
3WL9 111-0AT44-0AA0
1
1 unit
103
8.210
3WL9 111-0BA14-0AA0
1
1 unit
103
0.520
For testing the electronic trip unit functions
Function testers
For testing the tripping characteristics for
electronic trip unit ETU25B and ETU45B
Capacitor storage devices
Capacitor storage devices
For shunt trip unit
Rated control supply voltage/
rated operational voltage
Storage time 5 min
AC 50/60 Hz V V DC
Rated control supply voltage
must match the rated control
supply voltage of the shunt trip
unit
220 ... 240
220 ...
240
B
Suitable also for
3VL circuit breakers.
4
* You can order this quantity or a multiple thereof.
Siemens LV 16 · 2009
4/21
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Accessories and spare parts
Designation
DT Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Indicators, control elements
B
3WL9 111-0AH01-0AA0
1
1 unit
103
0.020
B
3WL9 111-0AH02-0AA0
1
1 unit
103
0.020
B
3WL9 111-0AH14-0AA0
1
1 unit
103
0.080
B
3WL9 111-0AH07-0AA0
1
1 unit
103
0.100
B
3WL9 111-0AH08-0AA0
1
1 unit
103
0.030
Position indicator
1st block
switches for guide frames (3 CO contacts)
B
3WL9 111-0AH11-0AA0
1
1 unit
103
0.200
Spare part for option R15
B
3WL9 111-0AH12-0AA0
1
1 unit
103
0.400
Ready-to-close indicator switches
1 NO contact
Spare part for option C22,
see "-Z" + order code,
page 4/10.
Signal switches1)2)
Spare part for option
C26 and C27,
see "-Z" + order code,
page 4/10.
N S E 0 _ 0 0 9 9 3 a
1st or 2nd auxiliary trip
units
3WL9 111-0AH01-0AA0 Tripped signaling switches1)2)
1 CO
N S E 0 _ 0 0 9 9 4 b
Spare part for option K07,
see "-Z" + order code,
page 4/11.
Operating cycles counters,
mechanical3)
Spare part for option C01,
see "-Z" + order code,
page 4/10.
3WL9 111-0AH02-0AA0 Stored energy status
signaling switches1)2)
1 NO contact
Spare part for option C20,
see "-Z" + order code,
page 4/10.
4
N S E 0 _ 0 0 9 9 5 a
3WL9 111-0AH07-0AA0 and R16, see "-Z" +
2nd block
(6 CO contacts)
order code, page 4/12.
Electrical ON buttons1)4)
(button+wiring)2),
for operator panel.
N S E 0 _ 0 0 9 9 6 a
Possible only for circuit
3WL9 111-0AH12-0AA0 breakers with closing
solenoid.
With sealing cap
B
3WL9 111-0AJ02-0AA0
1
1 unit
103
0.150
With CES assembly kit
B
3WL9 111-0AJ03-0AA0
1
1 unit
103
0.140
With BKS assembly kit
B
3WL9 111-0AJ04-0AA0
1
1 unit
103
0.140
With IKON assembly kit
B
3WL9 111-0AJ05-0AA0
1
1 unit
103
0.140
B
3WL9 111-0AJ06-0AA0
1
1 unit
103
0.100
B
3WL9 111-0BA72-0AA0
1
1 unit
103
0.080
Spare part for option C11
and C12, see "-Z" +
order code, page 4/10.
N S E 0
0 0 9 9 7 a
3WL9 111-0AJ0.-0AA0
Motor shutdown
switches 5) (mounting on
operator panel)
Spare part for option S25,
see "-Z" + order code,
page 4/10.
EMERGENCY-STOP pushbuttons
Mushroom pushbutton
NSE00985
instead of the mechanical
3WL9 111-0BA72-0AA0 OFF pushbutton
Spare part for option S24,
see "-Z" + order code,
page 4/10.
1)
2)
Not possible with communications connection option, order code "F02" or
"F12".
X7 manual connector required for circuit breakers or guide frames. If this is
not already available, please order additionally (see pages 4/15 and 4/23).
4/22
Siemens LV 16 · 2009
3)
Only in conjunction with motorized operating mechanism.
4)
Not possible with motor shutdown switch.
5)
Not possible with electrical ON button.
* You can order this quantity or a multiple thereof.
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Accessories and spare parts
Designation
DT Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Auxiliary conductor connections
Male connectors for circuit breakers $
3WL9 111-0AB01-0AA0
1
1 unit
103
0.100
Extensions for the 1000 V male connector versions B
(male connector must be ordered separately)
3WL9 111-0AB02-0AA0
1
1 unit
103
0.150
B
3WL9 111-0AB10-0AA0
1
1 unit
103
1.000
Auxiliary supply connectors Screw connection
B
for circuit breakers or
(SIGUT)
guide frames %
Screwless connection B
method (tension spring)
3WL9 111-0AB03-0AA0
1
1 unit
103
0.070
3WL9 111-0AB04-0AA0
1
1 unit
103
0.070
3WL9 111-0AB04-0AA0 Coding kits for fixed-mounted version (X5 to X8) & B
3WL9 111-0AB07-0AA0
1
1 unit
103
0.020
B
3WL9 111-0AB08-0AA0
1
1 unit
103
0.100
B
3WL9 111-0AB18-0AA0
1
1 unit
103
0.120
B
3WL9 111-0AB12-0AA0
1
1 unit
103
0.030
NSE00978
B
3WL9 111-0AB01-0AA0
N S E 0 _ 0 1 2 6 8
Male connectors for extension for 1000 V
NSE00974
N S E 0 _ 0 1 2 6 9
3WL9 111-0AB03-0AA0
3WL9 111-0AB07-0AA0
Sliding contact modules for guide frames (
7 a
9 7
0 0
0 _
E
N S
NSE0_01586
3WL9 111-0AB08-0AA0 One-part sliding contact modules for
3WL9 111-0AB18-0AA0
guide frames
Screw connection (SIGUT) )
Blanking blocks for circuit breakers
For a complete auxiliary current connection you must order:
Fixed-mounted version:
Withdrawable version:
$+%+&
$+(+%
or
$+)
* You can order this quantity or a multiple thereof.
Siemens LV 16 · 2009
4/23
4
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Accessories and spare parts
Designation
DT Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Auxiliary trip units
Closing solenoids/shunt trip units
24 V DC
3WL9 111-0AD06-0AA0
B
3WL9 111-0AD01-0AA0
1
1 unit
103
0.700
30 V DC
B
3WL9 111-0AD02-0AA0
1
1 unit
103
0.700
48 V DC
B
3WL9 111-0AD03-0AA0
1
1 unit
103
0.700
60 V DC
B
3WL9 111-0AD04-0AA0
1
1 unit
103
0.700
120 V DC/125 V AC
B
3WL9 111-0AD05-0AA0
1
1 unit
103
0.700
220 V DC/230 V AC
B
3WL9 111-0AD06-0AA0
1
1 unit
103
0.700
24 V DC
100 % ON period
5 % ON period
B
3WL9 111-0AD11-0AA0
1
1 unit
103
0.700
B
3WL9 111-0AD12-0AA0
1
1 unit
103
0.700
110 ... 125 V DC/110 ... 127 V AC
B
3WL9 111-0AD13-0AA0
1
1 unit
103
0.700
240 V DC/240 V AC
B
3WL9 111-0AD14-0AA0
1
1 unit
103
1.800
48 V DC
NSE01001
Undervoltage releases
3WL9 111-0AE0.-0AA0
4
NSE01002
3WL9 111-0AE1.-0AA0
Instantaneous
24 V DC
B
3WL9 111-0AE01-0AA0
1
1 unit
103
0.730
30 V DC
B
3WL9 111-0AE02-0AA0
1
1 unit
103
0.730
48 V DC
B
3WL9 111-0AE03-0AA0
1
1 unit
103
0.730
60 V DC
B
3WL9 111-0AE07-0AA0
1
1 unit
103
0.730
120 V DC/125 V AC
B
3WL9 111-0AE04-0AA0
1
1 unit
103
0.730
240 V DC/250 V AC
B
3WL9 111-0AE05-0AA0
1
1 unit
103
0.730
Delayed
B
3WL9 111-0AE11-0AA0
1
1 unit
103
0.740
120 V DC/125 V AC
48 V DC
B
3WL9 111-0AE12-0AA0
1
1 unit
103
0.740
240 V DC/250 V AC
B
3WL9 111-0AE13-0AA0
1
1 unit
103
0.740
24 ... 30 V DC
B
3WL9 111-0AF01-0AA0
1
1 unit
103
1.510
48 ... 60 V DC
B
3WL9 111-0AF02-0AA0
1
1 unit
103
1.510
120 V DC/125 V AC
B
3WL9 111-0AF03-0AA0
1
1 unit
103
1.510
240 V DC/240 V AC
B
3WL9 111-0AF04-0AA0
1
1 unit
103
1.510
Operating mechanisms
Motorized operating mechanisms1)
I
N S E 0 _ 0 1 0 0 3 a
3WL9 111-0AF0.-0AA0
Auxiliary contacts
Auxiliary switch blocks
2 NO + 2 NC
B
3WL9 111-0AG01-0AA0
1
1 unit
103
0.180
2 NO
B
3WL9 111-0AG02-0AA0
1
1 unit
103
0.080
1 NO + 1 NC
B
3WL9 111-0AG03-0AA0
1
1 unit
103
0.070
3WL9 111-0AG03-0AA0
1)
X7 manual connector required for circuit breakers or guide frames. If this is
not already available, please order additionally (see pages 4/15 and 4/23).
4/24
Siemens LV 16 · 2009
* You can order this quantity or a multiple thereof.
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Accessories and spare parts
Designation
DT Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Door sealing frames, covers, shutters
B
3WL9 111-0AP01-0AA0
1
1 unit
103
0.360
B
3WL9 111-0AP03-0AA0
1
1 unit
103
1.690
Size I
B
3WL9 111-0AP04-0AA0
1
1 unit
103
0.500
Size II
B
3WL9 111-0AP06-0AA0
1
1 unit
103
0.630
Size III
B
3WL9 111-0AP07-0AA0
1
1 unit
103
0.860
Withdrawable part coding
By customer, for 36 coding variants
B
3WL9 111-0AR12-0AA0
1
1 unit
103
0.400
Support brackets
For mounting fixed-mounted circuit breakers
on vertical plane, only for sizes I and II
(1 set = 2 units)
B
3WL9 111-0BB50-0AA0
1 1 unit
103
7.000
Door sealing frames
Spare part for option T40,
see "-Z" + order code, page 4/10.
Protective covers, IP55
Cannot be used in conjunction
with door sealing frames, cover
removable and can be opened on
both sides
NSE0_01028a
3WL9 111-0AP02-0AA0
Shutters
Spare part for option R21,
see "-Z" + order code, page 4/12.
3-pole
3WL9 111-0AP0.-0AA0
Withdrawable part coding
NSE01009
3WL9 111-0AR12-0AA0
NSE-01022
Support brackets
3WL9 111-0BB50-0AA0
* You can order this quantity or a multiple thereof.
Siemens LV 16 · 2009
4/25
4
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Accessories and spare parts
Designation
DT Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Main conductor connections, fixed mounting
3WL9 111-0AL06-0AA0
Specified for each connection
Front-accessible
main circuit
connections,
single hole at top
Size I, 1000 A
Size I, 1600 A
B
B
3WL9 111-0AL01-0AA0
3WL9 111-0AL02-0AA0
1
1
1 unit
1 unit
103
103
1.100
1.600
Size II, up to 2000 A
Size II, up to 2500 A
Size II, up to 3000 A
B
B
B
3WL9 111-0AL03-0AA0
3WL9 111-0AL04-0AA0
3WL9 111-0AL05-0AA0
1
1
1
1 unit
1 unit
1 unit
103
103
103
2.000
3.600
3.500
NSE-01010
Size III, up to 4000 A
B
3WL9 111-0AL06-0AA0
1
1 unit
103
6.100
3WL9 111-0AL56-0AA0 Front-accessible
Size I, 1000 A
Size I, 1600 A
B
B
3WL9 111-0AL51-0AA0
3WL9 111-0AL52-0AA0
1
1
1 unit
1 unit
103
103
1.000
1.300
B
B
3WL9 111-0AL53-0AA0
3WL9 111-0AL54-0AA0
3WL9 111-0AL55-0AA0
1
1
1
1 unit
1 unit
1 unit
103
103
103
1.800
3.100
3.000
main circuit
connections,
Size II, up to 2000 A
single hole at bottom Size II, up to 2500 A
Size II, up to 3000 A
3WL9 111-0AL14-0AA0
4
NSE-01011
3WL9 111-0AL64-0AA0
Front-accessible
main circuit
connections,
acc. to DIN 43673,
double hole at top
Size III, up to 4000 A
B
B
3WL9 111-0AL56-0AA0
1
1 unit
103
5.200
Size I, 1000 A
Size I, 1600 A
B
B
3WL9 111-0AL07-0AA0
3WL9 111-0AL08-0AA0
1
1
1 unit
1 unit
103
103
1.400
2.000
Size II, up to 2000 A
Size II, up to 2500 A
Size II, up to 3000 A
B
B
B
3WL9 111-0AL11-0AA0
3WL9 111-0AL12-0AA0
3WL9 111-0AL13-0AA0
1
1
1
1 unit
1 unit
1 unit
103
103
103
2.400
4.500
4.400
Size III, up to 4000 A
B
3WL9 111-0AL14-0AA0
1
1 unit
103
7.800
Front-accessible
main circuit
connections,
acc. to DIN 43673,
double hole at
bottom
Size I, 1000 A
Size I, 1600 A
B
B
3WL9 111-0AL57-0AA0
3WL9 111-0AL58-0AA0
1
1
1 unit
1 unit
103
103
1.300
1.700
Size II, up to 2000 A
Size II, up to 2500 A
Size II, up to 3000 A
B
B
B
3WL9 111-0AL61-0AA0
3WL9 111-0AL62-0AA0
3WL9 111-0AL63-0AA0
1
1
1
1 unit
1 unit
1 unit
103
103
103
2.000
3.700
3.600
Size III, up to 4000 A
B
3WL9 111-0AL64-0AA0
1
1 unit
103
6.400
Rear vertical
main circuit
connections
Size I1), up to 1600 A
B
3WL9 111-0AM01-0AA0
1
1 unit
103
0.500
Size II2), up to 3000 A
B
3WL9 111-0AM02-0AA0
1
1 unit
103
2.200
Size III, up to 5000 A
B
3WL9 111-0AM03-0AA0
1
1 unit
103
5.000
NSE-01012
3WL9 111-0AM03-0AA0
1)
In the case of vertical connection size I, up to 1000 A one
3WL9 111–0AM01-0AA0 vertical connection is required,
up to 1600 A two 3WL9 111-0AM01-0AA0 vertical connections
are required.
2)
In the case of vertical connection size II, up to 2500 A one
3WL9 111–0AM02-0AA0 vertical connection is required,
up to 3200 A two 3WL9 111-0AM02-0AA0 vertical connections
are required.
4/26
Siemens LV 16 · 2009
* You can order this quantity or a multiple thereof.
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Accessories and spare parts
Designation
DT Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Main conductor connections, withdrawable versions
Specified for each connection
NSE-01013
3WL9 111-0AN06-0AA0
Front-accessible
main circuit
Size I, 1000 A
connections,
Size I, 1600 A
single hole at top or
Size II, up to 2000 A
at bottom1)
Size II, up to 2500 A
Size II, up to 3000 A
Front-accessible
main circuit
connections,
acc. to DIN 43673,
double hole at top or
at bottom1)
NSE-01014
3WL9 111-0AN14-0AA0
B
B
3WL9 111-0AN01-0AA0
3WL9 111-0AN02-0AA0
1
1
1 unit
1 unit
103
103
1.000
1.300
B
B
B
3WL9 111-0AN03-0AA0
3WL9 111-0AN04-0AA0
3WL9 111-0AN05-0AA0
1
1
1
1 unit
1 unit
1 unit
103
103
103
1.800
3.100
3.000
Size III, up to 4000 A
B
3WL9 111-0AN06-0AA0
1
1 unit
103
5.200
Size I, 1000 A
Size I, 1600 A
B
B
3WL9 111-0AN07-0AA0
3WL9 111-0AN08-0AA0
1
1
1 unit
1 unit
103
103
1.300
1.700
Size II, up to 2000 A
Size II, up to 2500 A
Size II, up to 3000 A
B
B
B
3WL9 111-0AN11-0AA0
3WL9 111-0AN12-0AA0
3WL9 111-0AN13-0AA0
1
1
1
1 unit
1 unit
1 unit
103
103
103
2.000
3.700
3.600
Size III, up to 4000 A
B
3WL9 111-0AN14-0AA0
1
1 unit
103
6.400
Supports for front
and DIN connecting
bars
3-pole for 3 bars
Size I
B
3WL9 111-0AN41-0AA0
1
1 unit
103
0.700
Size II
B
3WL9 111-0AN42-0AA0
1
1 unit
103
1.350
Size III
B
3WL9 111-0AN43-0AA0
1
1 unit
103
2.420
Size I, 1000 A
Size I, 1600 A
B
B
3WL9 111-0AN15-0AA0
3WL9 111-0AN16-0AA0
1
1
1 unit
1 unit
103
103
0.660
0.870
Size II, up to 2000 A
Size II, up to 2500 A
Size II, up to 3000 A
B
B
B
3WL9 111-0AN17-0AA0
3WL9 111-0AN18-0AA0
3WL9 111-0AN21-0AA0
1
1
1
1 unit
1 unit
1 unit
103
103
103
1.150
1.490
2.580
Size III, up to 5000 A
B
3WL9 111-0AN22-0AA0
1
1 unit
103
6.380
Size I, 1000 A
Size I, 1600 A
B
B
3WL9 111-0AN32-0AA0
3WL9 111-0AN33-0AA0
1
1
1 unit
1 unit
103
103
0.630
0.770
Size II, up to 2000 A
Size II, up to 2500 A
Size II, up to 3000 A
B
B
B
3WL9 111-0AN34-0AA0
3WL9 111-0AN35-0AA0
3WL9 111-0AN36-0AA0
1
1
1
1 unit
1 unit
1 unit
103
103
103
1.020
1.240
2.170
Size III, up to 5000 A
B
3WL9 111-0AN37-0AA0
1
1 unit
103
3.860
Size I, 1000 A
Size I, 1600 A
B
B
3WL9 111-0AN24-0AA0
3WL9 111-0AN25-0AA0
1
1
1 unit
1 unit
103
103
0.610
0.640
NSE-01015
Size II, up to 2000 A
Size II, up to 2500 A
Size II, up to 3000 A
B
B
B
3WL9 111-0AN26-0AA0
3WL9 111-0AN27-0AA0
3WL9 111-0AN28-0AA0
1
1
1
1 unit
1 unit
1 unit
103
103
103
0.980
1.020
1.310
3WL9 111-0AN22-0AA0
Size III, up to 4000 A
B
3WL9 111-0AN31-0AA0
1
1 unit
103
2.370
Rear vertical
main circuit
connections
Rear horizontal
circuit connections
NSE-01017
Connecting flanges
NSE-01016
3WL9 111-0AN41-0AA0
3WL9 111-0AN24-0AA0
Conversion sets
For converting fixed-mounted circuit breakers
into withdrawable circuit breakers
Guide frames and sliding contact modules
must be ordered separately.
1)
Number of poles
Size
3-pole
I
B
3WL9 111-0BC11-0AA0
1
1 unit
103
5.100
II
B
3WL9 111-0BC12-0AA0
1
1 unit
103
5.900
III
B
3WL9 111-0BC13-0AA0
1
1 unit
103
8.100
Supports are required when using front-accessible main circuit connections
(withdrawable circuit breakers).
* You can order this quantity or a multiple thereof.
Siemens LV 16 · 2009
4/27
4
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Accessories and spare parts
■ Options
Structure of the Order No.
3WL5 Ô Ô Ò – Ö á â Õ Ó – Ó á Ü Ô
Example
4
Ô
5th position:
Size
Size II
6th and 7th
position:
Max. rated
circuit breaker
current In max
In max = 2000 A
8th position:
Switching capacity
class
High breaking capacity
"H": 100 kA
9th position:
Electronic trip units
ETU45B with pixel graphics
display
10th position:
Electronic trip unit
supplement
... with ground-fault
protection
11th position:
Number of poles
3-pole
12th position:
Installation type
Fixed mounting, main circuit connections
on rear, vertical
They are used as an unambiguous
means of communication for various
purposes:
ÔÒ
• Offer processing
Selection and configuration
• Order processing
Ordering
Order confirmation
Handling warehouse
Products
Order processing at the
supply bases
Delivery and shipment
• Reporting and planning
• Service and warranty
Ö
á
â
Õ
13th position:
Operating
mechanism
Manual operating mechanism
with mechanical closing
14th position:
1st auxiliary switch
Shunt trip units
AC 50/60 Hz 110 V
15th position:
2nd auxiliary switch Without 2nd auxiliary trip unit
16th position:
Auxiliary switches
An important prerequisite for computerbased order processing is that order
numbers must be structured according
to standardized criteria.
The standardized structure ensures
that only one Order No. has to be
administered for one device.
Ó
This saves time and effort during
planning, configuring, ordering
and stock keeping, and consequently
above all it saves costs.
Ó
The example opposite explains the
various positions within an
Order No.
á
Ü
Ô
2 NO + 2 NC
Accessories: with first order (components are already mounted)
Example
3WL5 Ô Ô Ò – Ö á â Õ Ó – Ó á Ü Õ – õ
áÒÔ
Additional accessory components
can be ordered ready-mounted.
"–Z" with order code
Communications connection
"Standard" + Breaker Status Sensor (BSS)
+ communication module COM15 for
connection to PROFIBUS DP
õ
áÒÔ
These supplements are identified
by "-Z".
Even with additional components,
one Order No. is sufficient.
Accessories: for retrofitting (components for subsequent fitting)
Example
3WL9 Ó Ó Ó – Ò Á Ü Ô Ó – Ò Ü Ü Ò
Additional accessories which are not
intended to be ready-mounted in the
factory, such as spare parts for storage, can also be ordered separately
from the circuit breaker.
Protective cover for mechanical ON/OFF
without lock
Accessories for retrofitting are identified
by the Order No. stem 3WL9.
Documentation
Manual
Communication
German
English
Free download of documentation from
http://www.siemens.com/lowvoltage/manuals
4/28
Siemens LV 16 · 2009
Order No.
Order No.
A5E0151347-01
A5E0151353-01
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
General data
■ Design
Max. circuit
breaker current
n max (A)
Size III
Switch-off capacity
cu at 480 V AC (kA)
Dimensions
Fixed
mounting
Withdrawable
1)
3-/4-pole 1)
3-/4-pole
704 / 914
704 / 914
Width
434 / 434
460 / 460
Height
291 / 291
385 / 385
Depth
460 / 590
460 / 590
Width
434 / 434
460 / 460
Height
291 / 291
385 / 385
Depth
320 / 410
320 / 410
Width
434 / 434
460 / 460
Height
291 / 291
385 / 385
Depth
5000
H
4000
100
3000
Size II
2500
H
2000
100
1600
1000
4
Size I
1600
S
1000
65
The dimension for the depth of the circuit breakers is specified from the circuit breaker rear panel to the inside surface of the closed cabinet door.
4-pole version on request
NSE0_01903a
1)
Overview of SENTRON 3WL5 circuit breakers/non-automatic air circuit
breakers
Versions
• Rated currents: 630 A to 5000 A
• 3 sizes for different rated current ranges (see illustration
"Overview of SENTRON 3WL5 Circuit Breakers/Non-Automatic
Air Circuit Breakers")
• 3-pole version,
4-pole version on request
• Rated operational voltage up to 600 V AC
• 2 different switching capacity classes in the range from 65 kA
to 100 kA at 480 V AC
The SENTRON 3WL5 circuit breakers are supplied complete
with operating mechanism (manual operating mechanism with
mechanical closing), electronic trip unit and auxiliary switches
(2 NO contacts + 2 NC contacts in the standard version), and
can be equipped with auxiliary trip units.
Installation types
Fixed-mounted or withdrawable version
Ambient temperatures
The SENTRON 3WL5 circuit breakers are climate-proof according
to IEC 60068-2-30. They are intended for use in enclosed areas
where no severe operating conditions (e.g. dust, corrosive vapors,
damaging gases) are present.
When installed in dusty and damp areas, suitable enclosures
must be provided.
Coordinated dimensions
The dimensions of SENTRON 3WL5 circuit breakers only differ in
terms of the width of the device which depends on the number
of poles and the size.
Due to the nature of the design, the dimensions of devices with
a withdrawable version are determined by the dimensions of the
guide frames, which are slightly larger.
Non-automatic air circuit breakers
One special version of circuit breaker is utilized as a non-automatic
air circuit breaker. The non-automatic air circuit breakers are
designed without an electronic trip unit system and do not
perform any protection functions for the system.
One potential application is the use as a bus coupler in systems
with parallel feed-ins.
The versions and features can be selected according to those of
the circuit breakers.
Operating mechanisms
The circuit breakers are available with various optional operating
mechanisms:
• Manual operating mechanism with mechanical closing
(standard design)
• Manual operating mechanism with mechanical and electrical
closing
• Motorized operating mechanism with mechanical and electrical
closing.
The operating mechanisms with electrical closing can be used
for synchronization tasks.
Siemens LV 16 · 2009
4/29
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
General data
Safety and reliability
Fixed-mounted circuit breaker
Front connection with single
hole or double hole
Horizontal
connection
N S E 0 _ 0 0 9 7 9 a
N S E 0 _ 0 0 9 6 9 b
N S E 0 _ 0 0 9 6 7 b
N S E 0 _ 0 0 9 6 8 b
To protect the circuit breakers and plant against unauthorized
switching as well as the maintenance and operator personnel, the
system contains many locking devices. Others can be retrofitted.
Vertical
connection
N S E 0 _ 0 0 9 6 7 b
N S E 0 _ 0 0 9 7 2 b
N S E 0 _ 0 0 9 7 3 b
Withdrawable circuit breaker, withdrawable guide frame
Vertical
connection
Horizontal
connection
Flange
connection
Standard version
Main circuit connections – connection types
Main circuit connections
All circuit breakers are equipped with horizontal main circuit
connections on the rear for up to 5000 A as standard (horizontal
connection to busbars).
Connection using
screw connection
system (SIGUT)
(standard)
N S E 0 _ 0 0 9 7 6 b
The following options are available, with all combinations of top
and bottom connections possible:
• Accessible from the front, single hole (for vertically installed
busbars, only for fixed mounting)
• Accessible from the front, double hole (holes according to
DIN 43673) (for vertically installed busbars, only for fixed
mounting)
• At the rear, vertical (for vertically installed busbars)
• Connecting flange (for direct connection to guide frame up to
4000 A).
N S E 0 _ 0 0 9 7 5 b
4
Screwless connection
method
(tension springs)
(optional)
Connection options for auxiliary circuit connections
Auxiliary circuit connections
The type of connection for the auxiliary switches depends on the
type of installation:
• Withdrawable version: The internal auxiliary switches are
connected to the male connector on the switch side. When
fully inserted, the connector makes a connection with the
sliding contact module (see the graphic "Guide Frame" in
"Design") in the guide frame. Various adapters can then be
used to complete the wiring (see the graphic "Connection
options for auxiliary circuit connections").
• Fixed mounting: In this case the auxiliary supply connectors
are engaged directly onto the circuit breaker. The connectors
are equipped with coding pins that prevent them being
mistakenly interchanged.
Operator panel
The operator panel is designed to protrude from a cut-out in the
door providing access to all control elements and displays with
the control cabinet door closed.
The operator panels for all circuit breakers (fixed-mounted/
withdrawable versions, 3-/4-pole) are identical. The operator
panel ensures degree of protection IP41.
4/30
Siemens LV 16 · 2009
Other safety features include:
• Infeed from above or below, as required
• Locking of the guide frame with the circuit breaker removed,
as standard
• Locking of the withdrawable circuit breaker against movement,
as standard
• High degree of protection with cover (enclosure rating)
• Mechanical closing lockout after overload or short-circuit
tripping as standard
• The circuit breaker is always equipped with the required number
of auxiliary supply connectors
SENTRON 3WL5 circuit breakers are equipped with the following
features as standard:
• Mechanical ON and OFF pushbutton
• Manual operating mechanism with mechanical closing
• Switch position indicator
• Ready-to-close indicator
• Memory status indicator
• Auxiliary switches 2 NO + 2 NC
• Rear horizontal main circuit connections for fixed-mounted
and withdrawable versions up to 5000 A
• For 4-pole circuit breakers, the fourth pole (N) is installed on
the left and is 100 % loadable with the rated current
• Contact erosion indicator for the main contacts
• Auxiliary circuit plug-in system with SIGUT screw terminals.
Delivery inclusive of all auxiliary circuit connectors to internal
features including coding device for the prevention of incorrect
installation of auxiliary supply connectors for fixed-mounted
circuit breakers
• Mechanical tripped indicator for electronic trip unit system
• Mechanical closing lockout after tripping operation
• Operator panel cannot be taken off with the circuit breaker in
the ON position
Additional features of the withdrawable version:
• Main contacts:
Laminated receptacles in the guide frame, penetration blades
on the withdrawable circuit breaker
• Position indicator in the operator panel of the withdrawable
circuit breaker
• Captive manual crank handle for moving the withdrawable
circuit breaker
• Guide frame with guide rails for easy moving of the
withdrawable circuit breaker
• The withdrawable circuit breaker can be locked to prevent it
being pushed out of position
• The withdrawable circuit breaker cannot be moved when it is
in the ON position
• Coding of the rated current between the guide frame and the
withdrawable circuit breaker.
Standards
SENTRON 3WL5 circuit breakers comply with:
• UL 489
• IEC 60947-2
• DIN VDE 0660 Part 101
• Climate-proof according to IEC 60068-2-30.
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
General data
Auxiliary trip units
Indicators, signals and control elements
Up to two auxiliary trip units can be installed at the same time.
The following are available:
Motor shutdown switch
1 shunt trip unit
or 1 undervoltage release
or 2 shunt trip units
or 1 shunt trip unit
+ 1 undervoltage release.
Signal switch for auxiliary trip units
One signaling contact is used for each auxiliary trip unit to determine
the switch positions of the auxiliary trip units.
Shunt trip unit
When the operational voltage is connected to the shunt trip unit,
the circuit breaker is opened immediately. The shunt trip unit is
available in the versions 5 % ON period for overexcitation and
100 % ON period for permanent excitation. This means that it is
also possible to block the circuit breaker against being jogged
into closing.
An energy storage device for shunt trip units allows the circuit
breaker to be opened even if the control voltage is no longer
available.
Undervoltage release
The undervoltage release causes the circuit breaker to be
opened if the operational voltage falls below a certain value or is
not applied. The circuit breaker cannot be closed manually or by
means of an electrical ON command if the undervoltage release
is not connected to the operational voltage. The undervoltage release has no delay as standard. A delay can be set by the
customer in the range between td < 80 ms and td < 200 ms.
In addition, an undervoltage release with a delay in the range
from 0.2 to 3.2 s is available.
Closing solenoid
The closing solenoid is used to close the circuit breaker electrically
by means of a local electrical ON command or by a remote unit.
Motorized operating mechanism
Control switch for switching off the motorized operating mechanism
(automatic loading).
Operating cycles counter
The motorized operating mechanism can be supplied with a 5-digit
operating cycles counter. The display is incremented by "1" as
soon as the spring energy store is fully loaded.
Resetting the manual tripped signal
When the circuit breaker has tripped, this is indicated by the
protruding red mechanical tripped indicator on the ETU. When
the mechanical tripped indicator is activated, the tripping solenoid
and tripped signal are reset. If this display is to be reset remotely,
the reset button can be equipped with a reset solenoid.
This option allows the circuit breaker to be reset both manually
and electrically.
Automatic resetting of closing lockout
When the ETU is activated, reclosing of the circuit breaker is
prevented until the trip unit is either electrically or manually reset.
If the "Automatic resetting of closing lockout" option is used, the
pre-tensioned circuit breaker is ready to close immediately after
tripping. Resetting the manual tripped indicator is not included
in this option.
Tripped signal switch
If the circuit breaker has tripped due to an overload, short-circuit,
ground fault or extended protection function, the tripped signal
switch can indicate this. This signal switch is available as an
option. If the circuit breaker is used for communication, this
option is supplied as standard.
Ready-to-close indicator switches
The SENTRON 3WL5 circuit breakers are equipped with an optical
ready-to-close indicator as standard. In addition, the ready-toclose status can be transmitted by means of a signal switch as
an option. If the switch is used for communication, the signal
switch is supplied as standard.
The operating mechanism is used to load the spring energy
store automatically.
The operating mechanism is activated if the spring energy store
has been unloaded and the control voltage is available.
It is switched off automatically after loading. This does not affect
manual operation of the stored-energy feature.
Siemens LV 16 · 2009
4/31
4
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
General data
Circuit breakers
(28)
(1)
(2)
(27)
(26)
(3)
(4)
(25)
(5)
(24)
(1)
Arc chutes
(2)
Carrying handle
(3)
Labeling plates
(4)
Motor shutdown switch (option) or
"Electrical ON" (option)
(5)
Name plate for UL and IEC circuit breaker
(6)
Memory status indicator
(7)
"Mechanical ON" button
(8)
Rated current indication
(9)
Positioning pictogram
(10) Operating cycles counter (option)
(6)
(11) Hand-operated lever
(23)
(12) Crank handle
(7)
(22)
(13) Withdrawable unit drive shaft
(14) Equipment plate
(21)
(15) Ground terminal
(20)
(8)
(16) Position indicator
(9)
(17) Table for ground-fault protection
(18) Safety lock for crank handle (option)
(19)
(19) Mechanical unlocking of crank handle
(option)
(10)
(11)
(20) Electronic trip units
(18)
4
(21) Rated current modules
(17)
(16)
(12)
(22) "Mechanical OFF" button or "EMERGENCYSTOP" mushroom pushbutton (option)
(13)
(23) Ready-to-close indicator
(24) Switch position indicator
(14)
(15)
(25) Tripped indicator (reset button)
(26) "Secure OFF" locking device (option)
NSE0_01904
(27) Operator panel
(28) Male connector for auxiliary circuit connections
Guide frames
(1 )
(2 )
(3 )
(1 8 )
(1)
Arc chute cover (option)
(2)
Blow-out openings
(3)
Opening for crane hook
(4)
Shutter (option)
(5)
Locking device (shutter) (option)
(6)
Type plate for guide frame
(7)
Isolating contacts
(8)
Ground terminal Ø 14 mm
(9)
Locking device for racking rail
(10) Locking device against movement when
control cabinet door is open (option)
(4 )
(1 7 )
(5 )
(6 )
(1 6 )
(7 )
(1 5 )
(12) Racking rail
(13) Factory-set rated current coding
(14) Sliding contact for breaker grounding
(option)
(15) Equipment-dependent coding (option)
(16) Shutter actuator (optional)
(17) Position indicator switch (optional)
(1 4 )
(8 )
(1 3 )
(1 2 )
(9 )
(1 1 )
(1 0 )
4/32
(11) Door interlocking for guide frame (option)
N S E 0 _ 0 0 9 6 6 b
Siemens LV 16 · 2009
(18) Sliding contact module for auxiliary
conductors
(number depends on equipment)
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
General data
Locking devices
Sealing devices
Locking device in OFF position
Sealing cap for "Electrical ON" button
This function prevents closing of the circuit breaker and complies
to the specifications for main switches to EN 60204 (VDE 0113)
and UL 489 – disconnector unit. This lockout only affects this
circuit breaker.
The "Electrical ON button" is equipped with a sealing cap as
standard.
If the circuit breaker is replaced, closing is no longer prevented
unless the new circuit breaker is also protected against
unauthorized closing.
The locking set contains covering caps which can be sealed.
To activate the locking device, the circuit breaker must be
opened. The locking device is disabled when the circuit breaker
is closed. The lock is only activated when the key is removed.
The safety key can be removed only in the "OFF" position.
Sealing cap for "Mechanical ON" and "OFF" button
Sealing device for electronic trip units
The transparent cover can be sealed. The parameter setting
sections are covered to prevent unauthorized access. Openings
allow access to the query and test button.
Locking devices
Locking device for "Electrical ON"
(see graphic "Circuit breakers")
Locking device against movement for withdrawable circuit
breakers when the control cabinet door is open
This prevents unauthorized electrical closing from the operator
panel. Mechanical closing and remote closing remain possible.
The lock is only activated when the key is removed.
The crank handle is blocked when the control cabinet door is
open and cannot be removed. The withdrawable circuit breaker
cannot be moved. The lock only affects the inserted crank handle.
Locking device for "Mechanical ON"
(see graphic "Circuit breakers")
This prevents unauthorized mechanical closing. The mechanical
ON button can only be activated if the key is inserted (key
operation). Closing with the "Electrical ON" button and remote
closing remain possible. The lock is only activated when the key
is removed.
"Secure OFF" circuit breaker-independent locking device
against unauthorized closing
This special switch-independent function for withdrawable circuit
breakers prevents closing and fulfills the specifications for main
switches to EN 60204 (VDE 0113) and UL 489 – disconnector
unit. Unauthorized closing remains impossible even after the
circuit breaker has been exchanged.
To activate the lock, the circuit breaker must be opened. The
locking device is disabled when the circuit breaker is closed.
The lock is only activated when the key is removed. The safety
key can be removed only in the "OFF" position.
Locking device for crank handle
Prevents removal of the crank. The circuit breaker is protected
against movement. The lock is only activated when the key is
removed.
Locking of the control cabinet door
The control cabinet door cannot be opened if
• The fixed-mounted circuit breaker is closed (the blocking
signal is transmitted via the Bowden wire) or
• The withdrawable circuit breaker is in the connected position.
Blocking mechanism using "Mechanical ON" and "OFF" buttons
The "Mechanical ON" and "OFF" buttons are covered with a cap
which only allows actuation with a tool. These covering caps are
part of the locking set.
Optional equipment for guide frames
Shutters
The sealing strips of the shutter seal the laminated contacts of
the guide frame when the withdrawable circuit breaker is
removed and therefore implement touch protection.
The sealing strips can be manually opened using the strip
levers.
The position of the sealing strips can be locked in various
positions using padlocks for securing against tampering.
Locking device for "Mechanical OFF"
Prevents unauthorized mechanical opening from the operator
panel. The "Mechanical OFF pushbutton" can only be activated
if the key is inserted (key operation). Remote opening remains
possible. The lock is only activated when the key is removed.
Locking device for hand-operated lever
The hand-operated lever can be locked with a padlock. The
spring energy store cannot be loaded manually.
Locking device against resetting the tripped indicator
A lockable cover prevents manual resetting of the tripped indicator
after overcurrent tripping. This locking device is supplied together
with the transparent cover for electronic trip units.
Siemens LV 16 · 2009
4/33
4
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
General data
Rated current coding unit between circuit breaker and guide frame
Equipment-dependent coding
Withdrawable circuit breakers and guide frames are equipped
with a rated current coding unit as standard.
Withdrawable circuit breakers and guide frames can be retrofitted
with an equipment-dependent coding unit.
This ensures that only circuit breakers whose penetration blades
are suited to the laminated contacts of the guide frame can be
inserted into a guide frame (see diagram below).
This allows different designs of circuit breakers and guide
frames to be uniquely assigned. If the circuit breaker and guide
frame have been assigned different codes, the circuit breaker
cannot be inserted.
N S E 0 _ 0 1 0 3 1 a
36 different coding options can be selected.
N S E 0 _ 0 1 0 3 2 a
Position indicator switches for guide frame
(1 )
The guide frame can be equipped with position indicator
switches. These can be used to determine the position of the
circuit breaker in the guide frame.
Two versions are available:
(4 )
Option 1
Connected position
1 changeover contact
Test position
1 changeover contact
Disconnected position 1 changeover contact
(2 )
(5 )
(3 )
(1) Guide frame, interior of l/h side; interior of r/h side similar
Option 2
Connected position
3 changeover contacts
Test position
2 changeover contacts
Disconnected position 1 changeover contact
(2) Coding pin on racking rail in guide frame
(3) Racking rail
(4) Withdrawable circuit breaker, r/h side; l/h side similar
(5) Coding pin on guide frame
4
Rated current coding unit between circuit breaker and guide frame
Positions of the withdrawable circuit breaker in the guide frame
Display
Position indicator
Maintenance position
(2 )
CONNECT
Main circuit
Auxiliary circuit
Control cabinet
door
Shutters
Disconnected
Disconnected
Open
Closed
Disconnected
Disconnected
Closed
Closed
Disconnected
Connected
Closed
Closed
Connected
Connected
Closed
Open
(1 )
TEST
(4 )
DISCON
N S E 0 _ 0 1 0 3 3 a
NSE01037
Disconnected position
CONNECT
(3 )
TEST
DISCON
N S E 0 _ 0 1 0 3 4 a
NSE01038
Test position
CONNECT
TEST
DISCON
N S E 0 _ 0 1 0 3 5 a
Connected position
NSE01039
CONNECT
TEST
DISCON
N S E 0 _ 0 1 0 3 6 a
(1) Auxiliary circuit
(2) Main circuit
NSE01040
(3) Control cabinet door
(4) Shutter
Phase barriers
Door sealing frame and cover
The plant engineering company can manufacture phase barriers
made of insulating material for the arcing fault barriers. The rear
panel of the fixed-mounted circuit breakers or guide frames are
equipped with guide grooves.
SENTRON 3WL5 circuit breakers have degree of protection IP20
as standard. However, if the switchgear is to be equipped with a
higher degree of protection, a door sealing frame with IP41 and
a cover with IP55 are available.
Arc chute cover
The arc chute cover is included as standard in orders with guide
frame. It protects switchgear components which are located
directly above the circuit breaker.
4/34
Siemens LV 16 · 2009
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
General data
■ Function
Rating Plug
NSE0_01906
NSE0_01905
12
=
IR
R
tR
Isd
t sd
s d
t
s d
Ig
tg
Ii
NSE0 00953a
N S E 0 _ 0 0 9 5 1 b
ETU25B
ETU45B
✔
✔
Functions of the electronic trip units
4
Basic protection functions
Overload protection
L
Short-time delayed short-circuit protection
S
✔
✔
Instantaneous short-circuit protection
I
✔
✔
Neutral conductor protection
N
--
✔
Ground-fault protection
G
--
❑
N-conductor protection can be switched on/off
--
✔
N-conductor protection adjustable
--
✔
Instantaneous short-circuit protection can be switched on/off
--
✔
Additional functions
Instantaneous short-circuit protection can be switched on/off
--
✔
Thermal image can be switched on/off
--
✔
Load monitoring
--
✔
Short-time delayed short-circuit protection switchable to I2t
--
✔
Instantaneous short-circuit protection adjustable
--
✔
Overload protection switchable to I4t
--
✔
Overload protection can be switched on/off
--
--
Selectable parameter sets
--
--
Parameterization through rotary coding switches (10 steps)
✔
✔
Parameterization through communication (absolute values)
--
--
Parameterization through user interface of ETU (absolute values)
--
--
Parameterization of the extended protection functions
--
❑
LCD alphanumerical
--
❑
Graphic LCD
--
--
--
❑
CubicleBUS
--
✔
Communication through PROFIBUS DP
--
❑
Communication through MODBUS
--
❑
Communication through Ethernet
--
❑
Parameterization and display
Measurement function
Measurement function Plus
Communication
✔ Standard
-- Not available
❑ Optional
Detailed information about the functions of the electronic trip units is given in the following.
Siemens LV 16 · 2009
4/35
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
General data
Electronic trip units (ETU)
Tripped indicator/
Reset button
The electronic trip unit is controlled by a microprocessor and
operates independently of an auxiliary voltage. It enables
systems to be adapted to the different protection requirements
of distribution systems, motors, transformers and generators.
Communication capabilities
LCD alphanumeric
with 15°
inclination
and rotatable
through 180°
The international standard PROFIBUS DP or MODBUS can be
used to transmit data such as current values, switching states,
reasons for tripping etc. to central computers.
Data acquisition and energy management are possible in
conjunction with the Plus measurement function.
4
Sliding-dolly
for switchable
overload
characteristic
curve
A new internal circuit breaker data bus allows switchboard panel
communication between the circuit breaker and secondary
devices in the circuit breaker panel:
• Actuation of analog displays
• Facility to test the communication build-up with circuit breakers
• Display of tripping state and tripping reasons
• Input module for reading in further switchgear panel signals
and for transmission of these signals to the PROFIBUS DP or
MODBUS
• Various output modules for displaying measured values.
Rated current
module/
rating plug
This means that it is not only possible to monitor the device
remotely, but also to transmit current values from the entire
system and perform switching operations remotely.
Ground-fault
protection module
(retrofittable)
I2t and I4t characteristic curve for overload protection
The best protection for the whole switchgear is achieved by
setting the tripping characteristic curve to an optimum value.
In order to achieve optimal discrimination for upstream fuses or
medium voltage protection systems, the inclination of the
characteristic curve can be selected for the overload range.
The overload protection L (long time protection) for the electronic
trip units ETU45B allows the characteristic curve to be switched
between I2t and I4t.
The I4t characteristic improves discrimination for downstream
circuit breakers and fuses.
Electronic trip units ETU
Modularity has also been strictly emphasized during the
development of the electronic trip units. These are some of the
modules which can be easily retrofitted at any time:
• Ground-fault protection module
• Communication
• Measurement function
• Display
• Rated current module (Rating Plug)
This allows quick adaptation to new local mains specifications.
In addition, innovative functions have been included in the ETUs.
4/36
Siemens LV 16 · 2009
Example of configuration for ETU45B
Rated current modules / Rating plugs
The rated current module is an exchangeable module which allows the user to reduce the rated device current so as to adapt
it optimally to the plant; e.g. if a new plant section is taken into
operation. The rated current module must be selected to fit the
rated current of the system.
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
General data
ETU25B electronic trip unit
Option: Sicherheitsschloss
safety lock
prevents pressing
verhindert
Drückenofdes
reset
button
after
Resetknopfes
nach
overcurrent release
Überstromauslösung
Mechanical RESET
Mechanisches
for reclosing lockout
für Wiedereinschaltsperre
and
mechanical
und
mechanische
tripped indicator
Ausgelöstanzeige
Anzeige
Überstromauslöser
Indicator:
overcurrent
aktiviert
release activated
Indicator:
alarm
Anzeigeoverload
Überlastalarm
ETU25B
Indicator:
fault inim
Anzeige Fehler
overcurrent
release
Überstromauslöser
Rating Plug
Rated current module
Bemessungsstrommodul
Drehschalter
Rotary switchEinstellwert
for setting
Überlastauslösung
value,
overload release
Indicator:
of release
Anzeigen cause
Auslöseursache
Drehschalter
Rotary switchEinstellwert
for setting
kurzzeitverzögerte
value,
instantaneous
Kurzschlussauslösung
short-circuit release
Short-circuit
protection
Kurzschlussschutz
fixed setting
festeingestellt
Rotary switchVerzögerung
for delay,
Drehschalter
short-circuit release
Kurzschlussauslösung
NSE0_01907
Query
pushbutton
Taster
Abfrage
Taster
Prüfung
Test
pushbutton
Sealing ring
Plombieröse
Clear pushbutton
Taster
Löschen
Test socket
Prüfbuchse
Application:
Classical building, motor and system
protection with time-selective
coordination for up to 5000 A
Features:
• Adjustable overload protection
with I2t characteristic curve
Delay time
tR = 10 seconds at 6 × IR
• Short-time delayed short-circuit
protection adjustable in the
range 1.25 ... 12 × In and
• Instantaneous short-circuit
protection preset to 20 × In,
max. 50 kA
• Can be adapted at any time to
the required plant currents
through retrofittable rated current
module, thus ensuring overload
protection in the range from 100 A
to 5000 A.
• Overload display
• Indicates the reason for tripping
by means of an LED
• Test facility for the trip unit
• Protection functions are
set by means of the
rotary coding switch
4
For technical details see the table
"Functional Overview of the
Electronic Trip Unit System"
under "Technical Specifications".
Siemens LV 16 · 2009
4/37
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
General data
ETU45B electronic trip unit
Mechanical RESET
for reclosing lockout
and mechanical
tripped indicator
Scroll up
Application:
Option: safety lock
prevents pressing of
reset button after
overcurrent release
Option: alphanumeric display
Indicators:
Overcurrent release
activated
Overload alarm
Scroll down
Indicator: fault in
overcurrent release
COMMUNICATION
EXPANDED
OFF ON
Rated current module
Rating Plug
Rotary switch for setting
value, overload release
=
1
1
1
1
1
Rotary switch for delay,
overload release
Rotary switch for delay,
short-circuit release
Indicator: cause of release
12
Rotary switch for setting
value, instantaneous
short-circuit release
Features:
Thermal memory on/off
N-conductor protection on/off
Setting value
N-conductor overload
Transfer of overload
characteristic 2 t / 4t
ETU45B
Rotary switch for setting
value, short-circuit
protection
Sealing ring
Option: earth-fault module
Selector for
earth-fault protection
SI
Rotary switch for setting
value, earth-fault
protection
Rotary switch for setting
value, earth-fault alarm
Indicator: earth-fault alarm
g
Indicator: earth-fault tripped
Rotary switch for delay,
earth-fault protection t g /
Clear pushbutton
Test socket
Test pushbutton
Query pushbutton
Low-cost all-round system for intelligent
buildings and all types of industrial
applications – "CubicleBUS integrated"
2
tg
NSE0_01908
4
The same as ETU25B but also
• Adjustable time-lag class for overload
protection
• Selectable characteristic for overload
and short-delayed short-circuit range
(current discrimination) for more accurate
discrimination adaptation to upstream
fuses and protective devices
• Thermal image as restart protection for
tripped motor outgoing feeders
• Reversible and adjustable neutral
conductor protection
• Modular ground-fault protection module
with alarm and tripping functions which can
be adjusted separately
• Communication interface, measurement
function Plus, optional connection of
external modules or for retrofitting
• Storage of events and causes for tripping
for detailed fault analysis
• Extended protection function possible with
measurement function
• Optional high-contrast display with viewing
angle adjustment option
• The protection functions can be set by
means of a rotary coding switch or slide
switch
For technical details see the table "Functional
Overview of the Electronic Trip Unit System"
under "Technical Specifications".
Ground-fault protection
Selector for
earth-fault
detection
I
Rotary switch
for setting
value,
earth-fault
protection
g TRIP
G
OFF
ALARM
A
B
C
D
E
Rotary switch
for setting value
earth-fault alarm
GFM AT 45B ground-fault module
4/38
Siemens LV 16 · 2009
Indicators:
Earth-fault
alarm
GFM AT 45B
Earth-fault
tripped
ALARM t g (s)
TRIP
.5
.4
.3
.2
.1
NSE0_00962a
2
I tg
.1
.2
.3
.4
.5
Rotary switch
for setting
value, earthfault protection delay
2
tg/I tg
Ground-fault releases "G" sense fault currents that flow to ground
and that can cause fire in the plant. Multiple circuit breakers
connected in series can have their delay times adjusted so as to
provide graduated discrimination.
When setting the parameters for the electronic trip unit it is possible
to choose between "alarm" and "trip" in the event that the set current
value is exceeded. The reason for tripping is indicated by means of
an LED when the query button is activated.
The ETU45B electronic trip unit version can be retrofitted with a
ground-fault protection module.
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
General data
Measurement method
Setting
Vectorial summation current formation (measurement method 1)
How the module is set depends on the measurement method
used (see above):
The three phase currents and the N-conductor current are
measured directly.
The electronic trip unit determines the ground-fault current by
means of vectorial summation current formation for the three
phase currents and the N conductor current.
A standard transformer with the following data is used for
measurement of the ground-fault current:
1200 A/1 A, Class 1 (the internal load of SENTRON 3WL5 is 0.11 ).
The transformer can be installed directly in the grounded neutral
point of a transformer.
T5
L1
L2
L3
N
PE
NSE 00946
3-pole circuit breakers, current transformers in the N conductor
SENTRON WL
L1
L2
L3
N
T6
PE
T6: 1200 A/1 A
NSE 00947
3-pole circuit breakers, current transformers in the grounded neutral
point of the transformer.
SENTRON WL
.
Measurement method 2: in position
.
Ground-fault protection with
I 2t
characteristic curve
All versions of the ground-fault modules are supplied with an I2t
characteristic curve which can be activated.
Direct measurement of the ground-fault current
(measurement method 2)
SENTRON WL
Measurement method 1: in position
L1
L2
L3
Selection criteria for SENTRON 3WL circuit breakers
Basic criteria for selecting circuit breakers are:
• Max. short-circuit current at place of installation of circuit
breaker I k! max.
This value determines the short-circuit breaking capacity
or short-circuit current carrying capacity of the circuit breaker.
• It is compared with the value Icu, Ics, Icw of the circuit breaker
and essentially determines the size of the circuit breaker.
See illustration "Overview of SENTRON 3WL5 Circuit Breakers/
Non-Automatic Air Circuit Breakers".
• Rated current In which is to flow through the branch circuit.
This value must not be larger than the maximum rated current
for the circuit breaker.
The rated current for the SENTRON 3WL5 is set with the rated
current module. See "Design", illustration "Overview of SENTRON
3WL5 Circuit Breakers/Non-Automatic Air Circuit Breakers".
• Ambient temperature
for the circuit breaker.
This is usually the control cabinet internal temperature.
• Design of the circuit breaker
• Minimum short-circuit current
which flows through the switching device. The trip unit must
still detect this value as a short-circuit and must respond by
tripping.
Protection functions of the circuit breaker.
These are determined by the selection of the
corresponding electronic trip unit, see the table
"Functions of the Electronic Trip Units" under "Functions".
N
T6
PE
T6: 1200 A/1 A
NSE 00948
4-pole circuit breakers, current transformers in the grounded neutral
point of the transformer.
Siemens LV 16 · 2009
4/39
4
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
General data
■ Configuration
Mutual mechanical circuit breaker interlocking
• The bending radii of the Bowden wire must be greater than
500 mm.
• The sum of all bending angles along the Bowden wire must not
exceed 640°.
• In a vertical arrangement of circuit breakers to be interlocked,
the interlocking mechanisms must be in line.
• Circuit breakers to be interlocked must be arranged so that
Bowden cables can be optimally installed in compliance with
the conditions mentioned in the above points.
• The installed Bowden cable must be fixed (with cable ties or
the like) before the interlock is adjusted.
• Select the width of switchgear cubicle to allow enough freedom
of movement for adjusting the interlock!
• Openings and cut-outs in system elements must be designed
so that Bowden cables are not changed in direction or
obstructed when they are passed through.
The module for mutual mechanical interlocking can be used for
one or two SENTRON 3WL5 circuit breakers and can be
adapted easily to the corresponding versions. The fixedmounted and withdrawable circuit breaker versions are fully
compatible and can therefore be used in a mixed configuration
in an installation.
The circuit breakers can be mounted alongside each other or
one above the other, whereby the distance of the circuit breakers
is determined solely by the length of the Bowden wire (lengths:
2 m/3 m/4.5 m). Interlock signals are looped through using the
Bowden cables. Interlocking is only effective in the connected
position in the case of withdrawable circuit breakers. The
mechanical endurance of the Bowden cables is 10000 operating
cycles.
Minimum requirements must be fulfilled in the switchgear for the
interlocking to function:
• Bowden cables must be installed as far as possible in a
straight line with minimum bending.
Mutual mechanical interlocking of circuit breakers – examples
Mutual interlocking of
two circuit breakers
4
Interlocking between
three circuit breakers
Mutual interlocking of
three circuit breakers
G
S1
S2
4/40
G
G
S1
S3
S2
NSE01041
Interlocking of three circuit
breakers, two of them mutual
NSE01042
Siemens LV 16 · 2009
S1
S1
NSE01043
S2
S2
S3
S1
S3
S2
S3
NSE01044
NSE01045
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
General data
Communication-capable circuit breakers
PC with Switch ES Power
SENTRON 3WL/3VL parameterization
and visualization tool through
PROFIBUS DP
PLC e.g. SIMATIC S7
data acquisition and
processing
Digital input module
Analog output module
NSE0_01820a
BDA
BDA Plus
ETU
Measurementfunction Plus
Digital output module
Relay, configurable
BSS
Digital output module
Relay
COM15
Zone Selective
Interlocking module
Output device
e.g. notebook
with browser
Ethernet/
Intranet/
Internet
Communication with PROFIBUS DP
4
Configuration and
display software
MODBUS Master
PLC or monitoring software
MODBUS
Digital input module
Analog output module
BDA
BDAPlus
ETU
Measurement
function Plus
NSE0_01894
BSS
Digital output module
Relay, configurable
COM16
Digital output module
Relay
Output device
e.g. notebook
with browser
Zone Selective
Interlocking module
Ethernet/
Intranet/
Internet
Communication with MODBUS
The requirements for power distribution in terms of communication
capability, data transparency, flexibility and integration are
constantly increasing. An integrated and modular communication
architecture was designed for the SENTRON 3WL5 to ensure
that it can satisfy these requirements.
The core component of this architecture is the CubicleBUS,
which links together all of the intelligent components within the
SENTRON 3WL5 and enables the easy and safe connection of
other additional external components to the circuit breaker. The
CubicleBUS is already incorporated and pre-connected in all
complete circuit breakers with ETU45B trip units.
The high level of modularity of the system allows communication
functions to be retrofitted at any time (e.g. the measurement
function). Similarly, the upgrade of a non-communication-capable
SENTRON 3WL5 (e.g. changeover from ETU25B to ETU45B with
CubicleBUS) can be carried out easily on site in the plant. All
modules connected to the CubicleBUS can directly access the
existing source data of the circuit breaker, which guarantees the
quickest possible access to information and response to events.
Furthermore, additional external modules (including digital inputs/
outputs, analog outputs) can be connected to the CubicleBUS
to provide cost-effective solutions for the automation of further
devices in the switchgear.
Siemens LV 16 · 2009
4/41
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
General data
SENTRON 3WL5 communication-capable circuit breakers
Function
Electronic
trip unit
version
Breaker PROFIstatus BUS/
sensors MODBUS
communication
ports
Measure- Analog Digital Digital ZSI
Breaker Breaker
ment
output output input
module Data
Data
Adapters Adapters
function modules modules modules
Plus
Plus
ETU45B
Functions of the communication-capable SENTRON 3WL circuit breakers
4
Indication of measured values in trip unit (current only)
✓
❏
❏
❏
❏
❏
❏
❏
❏
❏
Indication of measured values in trip unit
(U, I, P, S, Q, p.f., etc.)
✓
❏
❏
✓
❏
❏
❏
❏
❏
❏
Output of measured values (current only)
to rotary coil instruments in control cabinet door
✓
❏
❏
❏
✓
❏
❏
❏
❏
❏
Output of measured values (U, I, P, S, Q, p.f., etc.) to
rotary coil instruments in control cabinet door
✓
❏
❏
✓
✓
❏
❏
❏
❏
❏
Output of digital signals (e.g. reason for tripping,
alarm signals, status) through contacts
✓
❏
❏
❏
❏
✓
❏
❏
❏
❏
Read in digital signals and forward to PROFIBUS/
MODBUS
✓
❏
✓
❏
❏
❏
✓
❏
❏
❏
Transmission of switch information on HTML basis
locally to a PC
✓
✓
❏
❏
❏
❏
❏
❏
✓
✓
Transmission of switch information on HTML basis
through Ethernet
✓
✓
❏
❏
❏
❏
❏
❏
❏
✓
Short-time grading control for S tripping and
G protection
✓
❏
❏
❏
❏
❏
❏
✓
❏
❏
Local storage of harmonic analysis and waveform
memory and transmission through PROFIBUS
✓
✓
✓
✓
❏
❏
❏
❏
❏
❏
Read out protection parameters through
PROFIBUS/MODBUS
✓
✓
✓
❏
❏
❏
❏
❏
❏
❏
✓
Required
❏
Not necessary for this function, optionally combinable
Function can optionally be taken over by one of these modules.
4/42
Siemens LV 16 · 2009
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
General data
Data that can be transmitted over the PROFIBUS DP/MODBUS or the Breaker Data Adapter
All SENTRON 3WL5s with ETU45B (CubicleBUS integrated)
Transmittable circuit breaker data
BSS
Order code (Order No. of circuit breaker + "–Z")
BDA BSS
F01
+"BDA/BDAPLUS"
Order No.
Order No.
COM15/COM16
F02/
F12
Potential applications
Transmission of circuit breaker data to PROFIBUS DP or MODBUS and integration into
higher-level visualization systems are possible
e.g. in PCS7, Power Management Systems, WinCC (including add-ons like the text message radio server)
--
✔
Transmission of circuit breaker data and software (i.e. HTML pages with data) to a local output
device, or remotely through Ethernet/Intranet/Internet (without the possibility of integration into
higher-level visualization systems)
e.g. for monitoring, diagnostics, maintenance and parameterization of individual circuit breakers
✔
--
Utilization of the functionality of all CubicleBUS modules
e.g. configuration of the configurable digital output module, status check of the digital input modules,
diagnostics
✔
✔
✔
✔
--1)
✔
Operating statuses
On/off status message, spring energy store, tripped, readiness
Switching position (connected, test and disconnected position, not present) for withdrawable circuit breakers,
PROFIBUS/MODBUS write protection on/off, free user input
✔
--1)
--1)
✔
✔
✔
Control commands
Switch circuit breaker on/off, switch free user output on/off
Reset tripped signal
Delete event and history memory
Reset the min./max. measured values, reset the maintenance information
--1)
✔
--1)
✔
✔
✔
✔
✔
History
Read out the event protocol, read out the release protocol
--1)
✔
Maintenance information
Number of tripping operations L, S/I and in total, contact wear
Number of operating cycles under load and in total, number of operating hours
✔
--1)
✔
✔
Event signals
Tripped signal with details of the tripping current
Alarm signals (e.g. overload) with incoming/outgoing information
All of the named event signals with time stamp
✔
--1)
--1)
✔
✔
✔
Parameterization of the protection functions
Reading out of the protection function parameters
✔
✔
Measured values
Phase currents, each with min./max. value
Temperature in the circuit breaker with min./max. value
Temperature in the control cabinet with min./max. value
All of the named measured values with time stamp
✔
--1)
--1)
--1)
✔
✔
✔
✔
Transmittable circuit breaker data without integrated measurement function
Device identification
Communication address, Order No., circuit breaker in delivery status, circuit breaker parameters
(size, number of poles, rated current module etc.), identification numbers, release type,
free text for plant code and comments
4
Measurement function
Plus
Order code F01+ ... or F02 or F12+ ...
F05
Additional transmittable circuit breaker data with integrated measurement function
Additional event signals
Threshold value alarms (e.g. over/underfrequency, over/undervoltage)
✔
Parameterization of the extended protection functions and setpoints (threshold values)
Reading out the parameters of the extended protection functions
Settings for the extended protection function parameters can be changed
Reading out and adjusting threshold values
✔
✔
✔
Additional measured values
Voltages, power, energy, power factor, frequency, each with min./max. value
Harmonic analysis
Recording of currents and voltages for configurable events in the curve form memory
✔
✔
✔
1)
Data only available in conjunction with the COM15/COM16 module
(BUS connection not required).
✔ Available
-- Not available
Siemens LV 16 · 2009
4/43
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
General data
CubicleBUS modules
Digital output modules with rotary coding switch
6 items of binary information concerning the state of the circuit
breaker (reasons for tripping and warnings) can be output via
this module to external signaling devices (e.g. LED, horn) or be
used for the selective shut-down of other system components
(e.g. frequency converters).
Digital output modules are available in versions with and without
a rotary coding switch. On modules with a rotary coding switch
it is possible to choose between two signaling blocks each with
6 defined assignments and to set an additional response delay.
All the digital output modules are available as a version with
relay outputs (CO contacts, up to 12 A). Up to two modules of
this type can be connected to one SENTRON 3WL5.
Analog output module
Digital input modules
With the digital input module, up to 6 additional binary signals
(24 V DC) in the circuit breaker environment can be connected
to the system. It is thus possible to send messages concerning
the state of a switch disconnector or a control cabinet door to the
PROFIBUS DP or MODBUS.
One module each of this type can be used for holding the six
items of digital information and for automatically switching over
the parameters.
Digital output module with rotary coding switch
4
Digital output modules, configurable
The configurable output module is available for higher-performance
solutions. With this module, random events on the CubicleBUS
can be switched directly to one of six available outputs or three
of these outputs can be assigned with up to six events. In other
words, up to six events can be placed on one physical output
with OR operation. Either BDA/BDA Plus or Switch ES Power is
used for configuring.
A relay variant is also available here the same as for the output
modules with rotary coding switch. Only one module of this type
is possible per SENTRON 3WL5.
Digital input module
ZSI modules (short-time grading control)
The use of ZSI modules is recommended when Siemens circuit
breakers are arranged in several staggered levels but full grading
with the smallest possible delay is to be assured nevertheless.
The circuit breakers are interconnected by these modules. In
case of a short-circuit, each affected circuit breaker asks the
circuit breakers directly downstream whether the short-circuit
has also occurred in the next, lower level. The short-circuit is
exactly localized as the result, and only the next upstream circuit
breaker in the energy flow direction is switched off.
Digital output module, configurable
Analog output modules
The analog output module can be used to output the following
measured values to analog indicators in the control cabinet
door:
• IL1, IL2, IL3, IN or
• UL12, UL23, UL31, UL1N or
• PL1, PL2, PL3, Stot or
• p.f.1 , p.f.2 , p.f.3, I% or
• favg, ULLavg, Ptot, p.f.avg
Four 4-20-mA/0-10-V interfaces are available for this. The
measured values to be output are selected with a rotary coding
switch. By using the analog output module it is possible to do
without additional converters and their conventional installation/
wiring in the main current path. Up to two modules of this type
can be connected to one SENTRON 3WL5.
4/44
Siemens LV 16 · 2009
ZSI module (short-time grading control)
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
General data
■ Technical specifications
Size
I
II
III
Type
3WL51
3WL52
3WL53
Switching capacity class
S
H
H
S
H
H
100
100
Short-circuit breaking capacity Icu = Ics acc. to UL 489
Up to 480 V AC
kA
65
Up to 600 V */347 V AC
kA
50
851)
Up to 600 V AC
kA
--
85
kA
65
85
85
85
--
Rated short-time withstand current acc. to UL 489
At max. delay time tsd = 0.4 s
Short-circuit breaking capacity Icu = Ics acc. to IEC 60947-2
Up to 500 V AC
Icm at 500 V AC
kA
kA
65
143
100
220
100
220
Up to 690 V AC
Icm at 690 V AC
kA
kA
50
105
85
187
85
187
Rated short-time withstand current Icw acc. to IEC 60947-2
0.5 s
kA
65
85
85
1s
kA
50
80
80
1)
Covered by 600 V AC (delta) test.
Further technical specifications
I
3WL51 10
3WL51 16
3WL52 20
A
A
A
Up to 1000
1000
1000
1600
1600
1600
2000
2000
2000
Rated voltage Ue at 50/60 Hz
V AC
600 */347
600 */347
600
Ambient temperature of the system
!C
–25/+40
–25/+40
–25/+40
Power loss at rated current
with 3-phase symmetrical load
• Fixed-mounted circuit breakers
• Withdrawable circuit breakers
W
W
100
195
150
350
180
320
ms
ms
35
38
35
38
35
34
ms
ms
80
73
80
73
100
73
ms
ms
73
50
73
50
73
50
10000
4000
10000
4000
10000
4000
1/h
60
60
60
Minimum interval
ms
Between tripping operation by electronic trip unit and next making
operation of the circuit breaker (only with automatic mechanical
resetting of the lockout device)
80
80
80
400 × 460 × 380
400 × 460 × 380
500 × 460 × 380
Rated current In at 50/60 Hz
Main conductor
At 40 °C
At 55 °C
At 60 °C
Operating times
• Make-time
• Opening time
• Electrical make-time (through activation solenoid)
• Electrical opening time (through shunt trip unit)
1)
• Electrical opening time (instantaneous undervoltage release)
• Opening time due to ETU, instantaneous short-circuit release
Endurance
• Mechanical (without maintenance)
• Electrical (without maintenance)
Operating cycles
Operating cycles
Switching frequency
Minimum dimension
Circuit breaker
3-pole
compartment
Width × height × depth
mm
II
Mounting position
3 0 °
3 0 °
and/
or
N S E 0 _ 0 0 0 6 1 a
Main conductor
minimum cross-sections
Auxiliary conductors (Cu)
Max. number of auxiliary
conductors × crosssection (solid/stranded)
Weights
3-pole
1)
Unit(s) 2
mm2 or 6.4 × 76.2
inches 1/4 × 3
3 0 °
4
h m a x .
= 1 m m
Size
Type
3 0 °
N S E 0 _ 0 0 9 2 7 a
N S E 0 _ 0 0 0 6 2 a
2
6.4 × 76.2
1/4 × 3
2
6.4 × 102
1/4 × 4
Standard connection = strain-relief clamp
• Without end sleeve
• With end sleeve acc. to DIN 46228 Part.22)
• With twin end sleeve
2 × 0.5 mm2 (AWG 20) up to 2 × 1.5 mm2 (AWG 16); 1 × 2.5 mm2 (AWG 14)
1 × 0.5 mm2 (AWG 20) up to 1 × 1.5 mm2 (AWG 16)
2 × 0.5 mm2 (AWG 20) up to 2 × 1.5 mm2 (AWG 16)
Optional connection = tension spring
• Without end sleeve
• With end sleeve to DIN 46228 Part 2
2 × 0.5 mm2 (AWG 20) up to 2 × 2.5 mm2 (AWG 14)
2 × 0.5 mm2 (AWG 20) up to 2 × 1.5 mm2 (AWG 16)
• Fixed-mounted circuit breakers
• Withdrawable circuit breakers
• Guide frames
kg
kg
kg
43
45
25
Make-time through activation solenoid for synchronization purposes (short-time excited) 50 ms.
43
45
25
56
60
31
2)
Important: Approval of end sleeves.
Siemens LV 16 · 2009
4/45
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
General data
Size
II
Type
3WL52 25
3WL52 30
3WL53 40
3WL53 50
Rated current In at 50/60 Hz
Main conductors
At 40 °C
At 55 °C
At 60 °C
A
A
A
2500
2500
2500
3000
3000
3000
4000
4000
4000
5000
5000
5000
Rated voltage Ue at 50/60 Hz
V AC
600
600
Up to 600 */347
Up to 600 */347
Ambient temperature of the system
!C
–25/+40
–25/+40
–25/+40
–25/+40
Power loss at rated current
with 3-phase symmetrical load
• Fixed-mounted circuit breakers
• Withdrawable circuit breakers
W
W
270
520
410
710
520
810
630
1050
Operating times
• Make-time
• Opening time
• Electrical make-time (through activation solenoid)1)
• Electrical opening time (through shunt trip unit)
• Electrical opening time (instantaneous undervoltage release)
• Opening time due to ETU, instantaneous short-circuit release
ms
ms
ms
ms
ms
ms
35
34
100
73
73
50
35
34
100
73
73
50
35
34
100
73
73
50
35
34
100
73
73
50
10000
4000
10000
4000
1/h
60
60
60
60
Minimum interval
ms
Between tripping operation by electronic trip unit and next making
operation of the circuit breaker (only with automatic mechanical
resetting of the lockout device)
80
80
80
80
800 × 460 × 380
800 × 460 × 380
Operating cycles
Operating cycles
Switching frequency
Minimum dimension
Circuit breaker compartment
Width × height × depth
3-pole
mm
500 × 460 × 380
Mounting position
3 0 °
500 × 460 × 380
3 0 °
3 0 °
3 0 °
and/
or
N S E 0 _ 0 0 0 6 1 a
Unit(s) 2
mm2 or 6.4 × 127
inches 1/4 × 5
Main conductor
minimum cross-sections
Auxiliary conductors (Cu)
Max. no. of auxiliary
conductors × cross-section
(solid/stranded)
5000
1000
N S E 0 _ 0 0 9 2 7 a
N S E 0 _ 0 0 0 6 2 a
4
4
6.4 × 63.5 6.4 × 102
1/4 × 2–1/2 1/4 × 4
5000
1000
h m a x .
= 1 m m
Endurance
• Mechanical (without maintenance)
• Electrical (without maintenance)
4
III
4
10 × 120
1/4 × 52)
4
10 × 120
1/4 × 52)
Standard connection = strain-relief clamp
2 × 0.5 mm2 (AWG 20) up to 2 × 1.5 mm2 (AWG 16); 1 × 2.5 mm2 (AWG 14)
• Without end sleeve
• With end sleeve acc. to DIN 46228 Part 2 1 × 0.5 mm2 (AWG 20) up to 1 × 1.5 mm2 (AWG 16)
2 × 0.5 mm2 (AWG 20) up to 2 × 1.5 mm2 (AWG 16)
• With twin end sleeve
Optional connection = tension spring
2 × 0.5 mm2 (AWG 20) up to 2 × 2.5 mm2 (AWG 14)
• Without end sleeve
• With end sleeve acc. to DIN 46228 Part 2 2 × 0.5 mm2 (AWG 20) up to 2 × 1.5 mm2 (AWG 16)
Weights
3-pole
• Fixed-mounted circuit breakers
• Withdrawable circuit breakers
• Guide frames
kg
kg
kg
1)
Make-time through activation solenoid for synchronization purposes
(short-time excited) 50 ms.
2)
1/4 × 5 for fixed-mounted circuit breakers on request.
4/46
Siemens LV 16 · 2009
59
63
39
64
68
45
82
88
60
82
88
60
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
General data
Size
I to III
Type
3WL5
Manual operating mechanism with mechanical closing
Closing/Charging
stored-energy feature
Max. force required to operate the hand lever
Required number of strokes on the hand lever
N
" 230
9
Manual operating mechanism with mechanical and electrical closing
Charging stored-energy feature
Closing solenoid (CC)
• Operating range
0.85 ... 1.1 x Us
• Extended operating range for battery operation
At 24 V DC, 48 V DC
60 V DC, 110 V DC
220 V DC
• Power consumption
AC/DC
• Minimum command duration at Us for the closing solenoid
0.7 ... 1.26 x Us
VA/W 15/15
ms
60
1A
• Short-circuit protection
Manual/motorized operating mechanism with mechanical and electrical closing
For data see above.
Manual operating mechanism
Motor
0.85 ... 1.1 x Us
• Operating range
• Extended operating range for battery operation
At 24 V DC, 48 V DC
60 V DC, 110 V DC
220 V DC
• Power consumption of motor
AC/DC
0.7 ... 1.26 x Us
VA/W 110/110
s
• Time required to charge the spring energy store at 1 × Us
For motor and
closing solenoid
"8
For data see above.
Closing solenoid
• Short-circuit protection
Motor and closing solenoid for the same rated control supply voltages
• Smallest permissible fuse
2A
At Us 24 ... 30 V
At Us 48 ... 60 V
At Us 110 ... 127 V
At Us 220 ... 250 V
4
2A
2A
1A
1A
Electronic trip unit signals
Protection functions acc. to
UL 489
Current indication " 5 %;
Measurement functions
base quantities " 1 %;
Measurement functions
derived quantities " 4 %
Measuring accuracy of the electronic trip unit
Auxiliary trip units
Undervoltage releases
UVR (F3) and
UVR-td (F4)
• Response values
# 0.85 × Us (circuit breaker
can be closed)
0.35 ... 0.7 × Us (circuit
breaker is tripped)
Pickup
Dropout
0.85 ... 1.1
• Operating range
0.85 ... 1.26
• Extended operating range for battery operation
At 24 V DC, 30 V DC,
48 V DC, 110 V DC,
220 V DC
• Rated control supply voltage Us
Instantaneous
AC 50/60 Hz
V
• Power consumption (pickup/uninterrupted duty)
• Opening time of circuit breaker at Us = 0
110 ... 127/208 ... 240/
380 ... 415
24/30/48/60/110/220 ... 250
DC
V
Delayed
AC 50/60 Hz
V
DC
V
110 ... 127/208 ... 240/
380 ... 415
48/110 ... 125/220 ... 250
AC
DC
VA
W
20/5
20/5
ms
200
- Version UVR (F3)
Instantaneous
With delay
ms
ms
80
200
- Version UVR-td (F8)
With delay, td = 0.2 to 3.2 s
Reset through additional NC contact, direct switching-off
s
ms
0.2 ... 3.2
" 100
A
1
Short-circuit protection
Siemens LV 16 · 2009
4/47
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
General data
Size
I to III
Type
3WL5
Auxiliary trip units
Shunt trip unit (ST)
(F1, F2)
• For continuous command
(100 % ON period), locks
out on momentarycontact commands
- Response value
> 0.7 × Us (circuit breaker is
tripped)
Pickup
- Operating range
- Extended operating range
for battery operation
0.85 ... 1.1 × Us
At 24 V DC, 48 V DC
60 V DC, 110 V DC, 220 V DC
- Rated control supply voltage Us AC 50/60 Hz
DC
- Power consumption
V 110; 230
V 24; 30; 48; 60; 110; 220
VA/W 15/15
AC/DC
ms 60
- Min. command duration at Us
- Opening time of circuit
breaker at Us = 100 %
AC/DC
ms 80
- Short-circuit protection
• 5 % ON period
- Response value
1A
> 0.7 × Us
(circuit breaker is tripped)
Pickup
0.85 ... 1.1 × Us
- Operating range
- Extended operating range
for battery operation
At 24 V DC, 48 V DC
60 V DC, 110 V DC, 220 V DC
- Rated control supply voltage Us AC 50/60 Hz
DC
- Power consumption
4
VA/W 15/15
AC/DC
ms 25
AC/DC
ms 50
1A
- Short-circuit protection
• With stored energy
feature consisting of
shunt trip unit and
capacitor storage
device
- Rated control supply voltage Us AC 50/60 Hz
DC
V 110; 230
V 110; 220
0.85 ... 1.1 × Us
- Operating range
- Power consumption
0.7 ... 1.26 × Us
V 110 ... 127; 208 ... 240
V 24; 48; 110 ... 125; 220 ... 250
- Min. command duration at Us
- Opening time of circuit
breaker at Us = 100 %
0.7 ... 1.26 × Us
VA/W 1/1
AC/DC
- Storage time at Us/
recharging time at Us
max. 5 min/min. 5 s
- Opening time of circuit breaker, short-circuit protection
As with "for continuous command"
Remote reset solenoid for mechanical tripped indicator (F7)
0.85 ... 1.1 × Us
- Operating range
Remote reset solenoid for
mechanical tripped indicator (F7)
- Extended operating range
for battery operation
At 24 V DC, 48 V DC
110 V DC, 220 V DC
- Power consumption
AC/DC
0.7 ... 1.26 × Us
VA/W 50/50
- Minimum command duration at Us for the remote
reset solenoid
ms 60
- Short-circuit protection
Smallest permissible DIAZED fuse (gL operational class)/
miniature circuit breaker with C characteristic
2 A TDz (slow)/1 A at 24 V DC
and 48 V DC,
1 A TDz (slow)/1 A at 110 V
and 208 ... 250 V
Contact position-driven auxiliary switches (S1, S2, S3, S4, S7, S8)
V AC/DC 500
Rated insulation voltage Ui
Rated operational voltage Ue
V AC/DC 500
Rated impulse withstand voltage Uimp
kV
4
A
A
10
10
A
10
V
A
250
0.2
A
2
Switching capacity
• Alternating current 50/60 Hz A 300 heavy duty
• DC current
P 300 heavy duty
Largest permissible fuse
Short-circuit protection
Ready-to-close signaling switch (S20) (acc. to UL 1054)
Switching capacity
• Rated operational voltage Ue
• Rated operational current Ie
Largest permissible fuse
Short-circuit protection
Tripped signal switch (S24) and signal switch for auxiliary trip units (S22, S23) (acc. to UL 1054)
Switching capacity
• Rated operational voltage Ue
• Rated operational current Ie
V 250
A 0.2
Position indicator switch on guide frame
Type of contact
• Signal:
- "Circuit breaker in connected position"
- "Circuit breaker in test position"
- "Circuit breaker in disconnected position"
AC 50/60 Hz
DC
Rated insulation voltage Ui
Rated operational voltage Ue
Rated impulse withstand voltage Uimp
Switching capacity
4/48
• Rated operational current Ie
Siemens LV 16 · 2009
3 CO
2 CO
1 CO
V 440
V 250
V 250
kV 4
A 0.2
or
1 CO
1 CO
1 CO
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
General data
Protection functions
Parameterization by
ETU25B
D
ETU45B
D &S
✓
0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1
--
✓
0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1
✓
10 s fixed
--at tsd = 20 ms (M)
---✓
-1.25-1.5-2-2.5-3-4-6-8-10-12
0-M-100-200-300-400 ms
--
2-3-5-5.5-8-10-14-17-21-25-30 s
1-2-3-4-5 s
✓
at tsd = 20 ms (M)
✓
✓
0.5 ... 1
✓
✓
1.25-1.5-2-2.5-3-4-6-8-10-12
M-100-200-300-400 ms
✓
--✓
-fixed for Ii # 20 $ In, max. 50 kA
100-200-300-400 ms
by CubicleBUS module
✓
✓
1.5-2.2-3-4-6-8-10-12-0.8 $ Ics
-----
❑ Module can be retrofitted
✓
✓
✓
--
✓
-----
A-B-C-D-E
A-B-C-D-E
100-200-300-400-500 ms
✓
---
100-200-300-400-500 ms
by CubicleBUS module
Alphanumeric LCD (4-line)
--
❑
CubicleBUS integrated
Communication-capable through PROFIBUS DP
Communication-capable through MODBUS
----
✓
✓
✓
Measurement function Plus
--
❑
✓
✓
✓
✓
✓
✓
------
✓
✓
✓
✓
✓
✓
✓
✓ (only with ground-fault protection module)
✓ (only with ground-fault protection module)
✓
✓
--------------
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓ (only with ground-fault protection module)
✓ (only with ground-fault protection module)
✓
✓
Functional overview of the electronic trip unit system
Overload protection
Setting range IR = In × ...
L
R
R
N
S
s d
s d
i
N S E 0 _ 0 0 8 8 8 b
I
g
G
g
N S E 0 _ 0 0 8 8 9 a
Switchable overload protection
(I2t- or I4t-dependent function)
Setting range for time-lag class tR at I2t
Setting range for time-lag class tR at I4t
Thermal image can be switched on/off
Phase failure sensitivity
Neutral conductor protection
Function can be switched on/off
N conductor setting range IN = In × ...
Short-time delayed short-circuit protection
Function can be switched on/off
Setting range Isd = In × ...
Setting range for delay time tsd
Switchable short-time delayed short-circuit protection
(I2t-dependent function)
Setting range for delay time tsd at I2t
Zone Selective Interlocking function
Instantaneous short-circuit protection
Function can be switched on/off
Setting range Ii = In × ...
Ground-fault protection
Tripping and alarm function
Tripping function can be switched on/off
Detection of the ground-fault current through summation
current formation with internal or external N conductor
transformer
Detection of ground-fault current through external
transformer
Setting range of the operating current Ig for tripping
Setting range of the operating current Ig for alarm
Setting range of the delay time tg
Switchable ground-fault protection characteristic curve
(I2t-dependent function)
Setting range for delay time tg at I2t
Zone Selective Interlocking ground-fault protect. function
4
LCD
Communication
Measurement function
LED display
Electronic trip unit active
Alarm
ETU fault
L-release
S-release
I-release
N-release
G-release
NSE00890
G-alarm
Release through extended protection function
Communication
Signals from signal switches with external CubicleBUS module (relay)
Overload warning
Load shedding, load receiving
Leading signal overload trip 200 ms
Temperature alarm
Phase unbalance
Instantaneous short-circuit release
Short-time delayed short-circuit release
Overload trip
NSE00891
Neutral conductor release
Ground-fault protection release
Ground-fault alarm
Auxiliary relay
ETU fault
Delay time figures given in ms.
M = motor protection, corresponds to 20 ms.
D = rotary coding switch
D & S = rotary coding and slide switch
✓ Available.
-- Not available.
❑ Optional.
Setting range of the
operating current Ig
Size I and size II Size III
A
100 A
400 A
B
300 A
600 A
C
600 A
800 A
D
900 A
1000 A
E
1200 A
1200 A
Siemens LV 16 · 2009
4/49
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Project planning aids
■ Characteristic curves
1,25 ... 12 x
sd =
const
sd max
n
sd max
sd min
i > 20 x n
max. 50 kA
0,01
1
0,1
10
100
/
n
10000
4
R
const
0,4 ... 1,0 x
1000
NSE0_01522a
SENTRON 3WL5 circuit breaker with ETU25B electronic trip unit,
LSI characteristic curve
const
sd =
1,25 ... 12 x
i
10
2
sd min
0,1
n
sd =
10
0 ... 0,4 s
100
2
n
100
1
Opening time [s]
sd
R max
0,4 ... 1,0 x
1000
NSE0_01520
R min
NSE0_01523a
1000
1
= const
n
2
= const
100
R
2 ... 30s for 2
1 ... 5s for 4
10
1
0,1 ... 0,4 s
0,1
0,1
0,02 ... 0,4 s
0,01
1
10
0,01
100
/
10000
Opening time [s]
1000
100
10
1
x
1
Siemens LV 16 · 2009
g
10
2
= const
100 ... 1200 A1)
g
10
/ n
0,1 ... 0,5 s
0,01
1
/
100
1000
cs
SENTRON 3WL5 circuit breaker with ETU45B electronic trip unit,
I characteristic curve
Tolerances for the set currents
L : Tripping operations between 1.05 and 1.2 x IR
S : –0 %, +20 %
I : –0 %, +20 %
G : –0 %, +20 %
Tolerances for the tripping times
L : –20 %, +0 % for I2t characteristic curve
S : –0 %, +60 ms or –0 %, +10 % for characteristic curve with fixed delay time
I : < 50 ms
G : –0 ms, +60 ms or –0 %, +10 % for characteristic curve with fixed delay time
4/50
100
0,1
cs
0,01
0,1
1000
1
i
n ... 0,8
100
n
SENTRON 3WL5 circuit breaker with ETU45B electronic trip unit,
L characteristic curve
NSE0_01524a
10000
1,5 x
10
/
SENTRON 3WL5 circuit breaker with ETU45B electronic trip unit,
S characteristic curve
0,1
1
0,1
n
NSE0_01525a
0,1
Opening time [s]
4
Opening time [s]
10000
10000
Opening time [s]
Every electronic trip unit type and every setting has its own
characteristic curve. Only a selection is shown in the following.
The characteristic curves each show the largest and smallest
setting range of SENTRON 3WL5 circuit breakers with 1000 A
rated current at 480 V rated voltage with various trip units. In
order to obtain a complete tripping characteristic, the relevant
parts of the characteristics have to be combined. The
characteristic curves show the behavior of the electronic trip unit
when it is activated by a current that is already flowing before the
tripping operation. If the overcurrent tripping occurs immediately
after switch on and the electronic trip unit is therefore not yet
enabled, the opening time is extended, depending on the level
of the overcurrent by up to 15 ms. In order to determine the
break-times of the circuit breakers, approximately 15 ms must
be added to the opening times shown for the arcing time.
Refer to the following legend for tolerances.
The characteristic curves shown apply to ambient temperatures
at the circuit breaker between -5 and +55 °C. The trip unit can
be operated at ambient temperatures of -20 to +70 °C. An
extended tolerance band can apply at these temperatures.
10000
100000
A
SENTRON 3WL5 circuit breaker with ETU45B electronic trip unit,
G characteristic curve
Further characteristic curves are shown in the manual and the
planning and configuring tool SIMARIS design, or ask your
Siemens contact person.
1)
Sizes I and II: 100 ... 1200 A
Size III: 400 ... 1200 A
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Project planning aids
■ Dimensional drawings
Ext. transformers for N conductor without copper connection pieces
Voltage transformer for SENTRON 3WL5
Size I, 3WL9 111-0AA21-0AA0
260
6 0
1 6
R
2 2
4 0
87
N S E 0 _ 0 1 3 7 5
NSE0_01103b
1 3 ,1
8 ,9
R
2 2
8 1
9 6 ,8
125
8
For mounting on
35 mm standard
mounting rail
1 8
5 1
3 6
7 0
8 3
Current transformers for overload protection in the N conductor
External transformers for N conductor with copper connection pieces
Size II, 3WL9 111-0AA22-0AA0
Size I, 3WL9 111-0AA31-0AA0
1 5
4 1
R
2 7
6 5 ,5
N S E 0 _ 0 1 3 7 6
5 4
1 1 5
1 3 1
1 3 ,5
1 7 0
9 7
4
1 6 1
R 1 5
3 × 1 0
3 1
5 0 ,5
3
3 0
N S E 0 _ 0 1 3 7 7
4 5
Size II, 3WL9 111-0AA32-0AA0
3 0
3
Size III, 3WL9 111-0AA23-0AA0
1 0 7
1 2 3
5 5
8 3
5 1
8 8
9 5
1 1 3
N S E 0 _ 0 0 6 0 6 b
9 1
1 3 0
6 8
5 1
2 4
4 4
Ø
Ø 1 3 ,5
5 1
9 1
Door cut-out for operator panel
1 7 0
1 3 0
6 8
5 1
2 4
4 4
1 6 0
1 8 4
Door cut-out with edge protector
N S E 0 _ 0 0 6 0 7 b
2 9 5
9 0
1 1 3
Inner dimensions with mounted
edge protector
1 3 1
3 4 0
Size III, 3WL9 111-0AA33-0AA0
3 0
3 0
3 × 1 0
3 0
5 2
2 4 0
1 3 ,5
1 6 0
1 8 4
N S E 0 _ 0 0 1 6 4 c
1 7 0
N S E 0 _ 0 0 6 0 8 b
9 1
1 3 0
6 8
5 1
2 4
4 4
Ø
Door cut-out for operator panel
using the door sealing frame
1 2 3
Option with/without door interlocking
3 1 4
3 0 0
1 2 0
Ø 5 ,5
4 0
3 )
N S E 0 _ 0 0 6 1 0 c
2 )
5 ,5
Ø
1 8 5
1 8 0
4 0
1 2 0
5 ,5
6 5
■ Dimensions for option with door interlocking
1 4 0
1 7 5
3 5 0
Ø
1 4 0
R 5
R 5
2) Center SENTRON 3WL5 operator panel
3) 8 mounting holes for door sealing frame
4) 3 mounting holes for door interlocking
1 1 ,5
1) Mounting surface
1 )
1 2
2 1
4 )
4 0
Siemens LV 16 · 2009
4/51
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Project planning aids
CubicleBUS modules
Breaker Data Adapter (BDA)
3WL9 111-0AT2.-0AA0
70
3WL9 111-0AT28-0AA0,
3WL9 111-0AT33-0AA0
81,9
45,5
38
19
153
16(B
94
47,5
86
16(B
6
30
Door cut-out for operator panel using protective cover IP55
NSE0_01910
Protective cover, IP55
4 x R5
4
°
80
70
Circuit breaker mounting level
330
352
Lateral
Rear
(each side)
mm
mm
Size I, fixed-mounted version
480
600
751)
751)
Size I, withdrawable version,
with arc chute cover
480
600
0
0
751)
751)
Size II, withdrawable version,
with arc chute cover
480
600
0
0
0
0
751)
751)
Size III, withdrawable version,
with arc chute cover
480
600
0
0
02)
02)
0
0
0
0
0
0
Lateral
Rear
(each side)
mm
mm
480
600
150
300
20
50
20
125
480
600
14
14
100
100
14
14
480
600
250
600
50
100
20
140
50
225
14
14
20
100
20
125
50
200
14
14
Size II, withdrawable version,
with arc chute cover
02)
2)
0
0
0
0
0
0
0
480
600
14
14
Size III, fixed-mounted version
02)
2)
0
480
600
75
500
Size III, withdrawable version,
with arc chute cover
0
0
Value for plate; 0 mm for struts and grids
2)
40 mm (size II: 70 mm) for plates which cover the lateral openings in the
guide frame
Siemens LV 16 · 2009
Above auxiliary
connector
mm
Size II, fixed-mounted version
1)
4/52
Rated operational
voltage
V/AC
Size I, withdrawable version,
with arc chute cover
Size III, fixed-mounted version
480
600
149
Size I, fixed-mounted version
0
0
Size II, fixed-mounted version
480
600
Circuit breaker
mounting level
Safety clearances from live parts
Safety clearances from grounded parts
Rated operational voltage Above auxiliary
connector
V/AC
mm
17
NSE0_01909
77
295
444
116
340
4 x Ø5,5
480
600
14
14
All safety clearances above the circuit breaker refer to the upper
edge of the auxiliary connector - not to the upper edge of the arc
chute! See dimensional drawings on pages 4/53 to 4/58, parts 4)
and 5).
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Project planning aids
Size I, up to 1600 A, fixed-mounted version, 3- and 4-pole
4)
55
4 7
421
N S E 0 _ 0 0 6 1 2 c
e
55
3)
123,5
2 )
8 2
60 90
90
90
Front connection (double hole)
according to DIN 43673
Ø 13,5
4 7
55
40
9 )
6 0 ,5
26
d
c
55
55
55
NSE00616b
421
11)
f
4
N S E 0 _ 0 0 6 1 4 c
40
14
7 6
a
6
80
2 7 5
1 5 0
5 ,5
2 0
3)
g
3 2 7 ,5
5 4 1 ,5
4 6 1 ,5
a
N S E 0 _ 0 0 6 1 5 c
80
8 )
3 3 ,5
3 )
11)
35
434
NSE00611
1 )
55
6
15
10
270
300
390
55
Æ 13,5
275
439,5
5)
35
Optional connection variants
Front connection (single)
NSE00613b
Standard version
Horizontal connection
4 5
1 3 0
1 5 0
2 1 0
2 3 0
c
8 2
6 )
60 90
90
90
1 0 6
1 2 7
Vertical connection
35
90
90
90 60
55
3 5
1 1 )
b
NSE00619
6 0
Ø 13,5
11)
NSE00617a
N S E 0 _ 0 0 6 1 8 c
1 2 7 ,5
ØM8
3)
3 0
7)
2 6 7 ,5
3)
7)
139
320
410
58
1 3 ,5
1 1 3 ,5
1 2 8 ,5
60
90
90
90
NSE00620
3)
60
90
90
90
——— 4-pole version (on request)
1) Mounting space for removal of the arc chutes.
2) Space above arc chute, space for electrical auxiliary circuit connections.
3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the system.
4) Auxiliary connector with screw connections (SIGUT).
5) Auxiliary connector with screwless connection method (tension spring).
6) Dimension to inside surface of the closed cabinet door.
7) Fixing points for mounting the circuit breaker in the system.
8) "Secure OFF" locking device.
Rated circuit
a
breaker current
b
c
d
e
f
g
A
Up to 1000
10
10
10
11
451
34
541
1600
15
15
15
6
461
39
551
For safety clearances to grounded parts and to live parts see
page 4/52.
9) Key operation.
11) Terminal face.
Siemens LV 16 · 2009
4/53
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Project planning aids
Size I, up to 1600 A, withdrawable version, 3- and 4-pole
2 6 0
38
Ø 13,5
b
55
2 8 7
NSE00628a
30
150
165
9 0
1 5
9 0
9 0
Flange connection
M
5 5
5 5
1 2
3 3
55
55
55
55
121
2 8 7
5 9
6 9
6 )
1 5
9 0
9 0
9 0
38
4 2
3 )
1 4 2 ,5
4 5
5 8
8 8 ,5
1 2 1 ,5
1 4 0 ,5
2 2 0
3 6 7 ,5
3 8 2 ,5
2 7
2 8 2 ,5
7 6
1 0 )
4 0
4
2 6
1 5 0
3 1
2 7 5
5 9
a
3 )
2 6 0
5 5
5 5
3 2 7 ,5
4 6 0
3 5 0
14
a
8 )
9 )
NSE00631
7 )
N S E 0 _ 0 0 6 2 4 b
N S E 0 _ 0 0 6 3 2 a
13
210
300
10)
3 )
6 9
123,5
267,5
127,5
275
465,5
30
60
4)
3 5 0
11)
N S E 0 _ 0 0 6 2 9 a
320
270
5)
Optional connection variants
Vertical connection
NSE00621
Standard version
Horizontal connection
Ø 13,5
NSE00627a
11)
139
270
320
410
68
25
NSE00630
3)
10)
55
15
90
90
90
10)
——— 4-pole version (on request)
3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the
system.
Rated circuit breaker current
4) Auxiliary connector with screw connections (SIGUT).
A
5) Auxiliary connector with screwless connection method (tension spring).
Up to 1000
6) Dimension to inside surface of the closed cabinet door.
1600
7) SENTRON 3WL5 in connected position.
For safety clearances to grounded parts and to live parts see
page 4/52.
8) SENTRON 3WL5 in test position.
9) SENTRON 3WL5 in disconnected position.
10) Fixing holes 9 mm.
11) Terminal face.
4/54
Siemens LV 16 · 2009
a
b
c
10
15
10
15
10
15
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Project planning aids
Size II, up to 3000 A, fixed-mounted version, 3- and 4-pole
Optional connection variants
Front connection (single)
4)
5)
90
4 7
90
90
40
421
90
4 7
130
130
90
40
90
13,5
40
90
90
3)
NSE00638c
6
11)
1 5 0
a
14
2 7 5
g
3 )
421
3 2 7 ,5
5 4 1 ,5
4 6 1 ,5
a
N S E 0 _ 0 0 6 3 7 d
80
2 )
130
8 2
Front connection (double hole)
according to DIN 43673
1 )
11)
35
26
d
c
40
NSE00633
123,5
3)
10
85
570
NSE00635c
N S E 0 _ 0 0 6 3 4 d
6
e
434
275
435,5
40
270
440
90
35
Standard version
Horizontal connection
c
80
6 )
40
f
5 ,5
4 5
1 3 0
1 5 0
2 1 0
2 3 0
7 6
2 0
N S E 0 _ 0 0 6 3 6 d
90 130
130
130
4
13,5
8 2
1 0 6
1 2 7
9 0
3 0
9 0
1 3 ,5
3)
5 9 0
1 2 8
98
134,5
9
N S E 0 _ 0 0 6 3 9 d
4 ×
1 3 9
4 6 0
NSE00641
1 1 )
7 )
3 )
290
7 )
30
3 0
b
Ø 13,5
1 3 0
3 5
1 3 0
30
Vertical connection, up to 3000 A
1 3 0
35
NSE00640b
11)
90
113,5
128,5
130
130
130
——— 4-pole version (on request)
1) Mounting space for removal of the arc chutes.
2) Space above arc chute, space for electrical auxiliary circuit connections.
3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the
system.
Rated circuit
a
breaker current
b
c
d
e
f
g
A
4) Auxiliary connector with SIGUT screw terminals.
Up to 2000
10
10
10
11
451
34
541
5) Auxiliary connector with tension spring connection.
2500
15
15
20
6
461
39
551
6) Dimension to inside surface of the closed cabinet door.
3000
30
30
20
6
461
39
551
7) Fixing points for mounting the circuit breaker in the system.
For safety clearances to grounded parts and to live parts see
page 4/52.
11) Terminal face.
Siemens LV 16 · 2009
4/55
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Project planning aids
Size II, up to 3000 A, withdrawable version, 3- and 4-pole
Standard version
Horizontal connection
Optional connection variants
Vertical connection up to 3000 A
4)
5 3 0
11)
38
30
30
275
465,5
b
N S E 0 _ 0 0 6 5 1 a
2 8 7
6 9
135
123,5
290
3 )
100
461
4 0 0
NSE00650a
5)
NSE00643a
270
350
10)
40
157
172
10)
55
5 5 4 5
1 3 0
1 3 0
1 3 0
480
5 3 0
1 2
9 0
N S E 0 _ 0 0 6 5 4 a
4 0 0
M
4 0
4
27
42
5 9
2 8 2 ,5
76
6)
121
4 5
1 3 0
1 3 0
1 3 0
30
38
30
45
58
88,5
121,5
140,5
6 9
31
40
220
367,5
382,5
2 8 7
3 )
10)
1 4 2 ,5
150
275
5 9
2 6
3 3
327,5
a
460
a
40,5
8)
9)
NSE00653
Flange connection
7)
NSE0_01911
Ø 13,5
NSE00649a
11)
139
270
460
590
90
90
90
NSE00652a
90
138
95
3)
10)
55 45
130
130
130
10)
——— 4-pole version (on request)
3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in
the system.
Rated circuit breaker current
4) Auxiliary connector with SIGUT screw terminals.
A
a
b
c
5) Auxiliary connector with tension spring connection.
Up to 2000
10
10
10
6) Dimension to inside surface of the closed cabinet door.
2500
15
15
20
7) SENTRON 3WL5 in connected position.
3000
30
30
20
8) SENTRON 3WL5 in test position.
For safety clearances to grounded parts and to live parts see
page 4/52.
9) SENTRON 3WL5 in disconnected position.
10) Fixing holes, diameter 9 mm.
11) Terminal face.
4/56
Siemens LV 16 · 2009
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Project planning aids
Size III, up to 5000 A, fixed-mounted version, 3- and 4-pole
Optional connection variants
Front connection (single) up to 4000 A
5) 4)
160
47
NSE00655
NSE00656c
160
NSE00657c
3)
11)
26
12
205
160
50
130
20
82
210
210
35
270
680
11
890
160
50
421
451
6
123,5
434
275
439
13,5
35
Standard version
Horizontal connection up to 5000 A
210
Front connection (double hole)
according to DIN 43673 up to 4000 A
1 )
2 )
Ø 1 3 ,5
1 6 0
5 0 5 0
1 6 0
5 0 5 0
1 6 0
1 6 0
N S E 0 _ 0 0 6 5 9 d
3 )
N S E 0 _ 0 0 6 6 0 c
6
4 2 1
2 7 5
3 )
5 4 1
3 2 7 ,5
5 4 1 ,5
4 6 1 ,5
3 0
8 0
4 0
4 7
1 1 )
8 0
2 0
6 )
2 1 0
1 3 0
4 0
5 ,5
4 5
1 3 0
1 5 0
2 1 0
2 3 0
3 4
N S E 0 _ 0 0 6 5 8 d
1 4
7 6
1 5 0
3 0
2 0
2 1 0
2 1 0
8 2
1 0 6
1 2 7
Vertical connection up to 5000 A
N S E 0 _ 0 0 6 6 1 d
4 ×
9 1 4
1 3 9
7 0 4
9
2 4 8
20
10
107
15
30
1 1 )
7 )
3 )
NSE00663
3)
11)
330,5
1 3 ,5
1 3 0
40
94,5
120
7 )
2 1 0
1 5
3 5
1 6 0
40
Ø 13,5
142
162
NSE00662a
2 1 0
2 1 0
3 0
85
210
210
210
NSE00664a
3)
130
210
210
210
130
——— 4-pole version (on request)
1) Mounting space for removal of the arc chutes.
2) Space above arc chute, space for electrical auxiliary circuit connections.
3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the
system.
4) Auxiliary connector with SIGUT screw terminals.
5) Auxiliary connector with tension spring connection.
6) Dimension to inside surface of the closed cabinet door.
7) Fixing points for mounting the circuit breaker in the system.
11) Terminal face.
For safety clearances to grounded parts and to live parts see
page 4/52.
Siemens LV 16 · 2009
4/57
4
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Project planning aids
Size III, up to 5000 A, withdrawable version, 3- and 4-pole
10)
800
270
590
160
38
11)
2 0
1 0
N S E 0 _ 0 0 6 7 3 b
2 8 7
10)
57
6 3 0
7 0 4
24
177
197
Ø 13,5
6 9
123,5
461
10)
8 4 0
NSE00672a
NSE00665a
30
4)
275
466,5
5)
Optional connection variants
Vertical connection up to 5000 A
330,5
94,5
124,5
Standard version
Horizontal connection up to 5000 A
5 7
a
b
5 9 0
b
2 1 0
8 0 0
9 1 4
Flange connection, up to 4000 A
1 6 0
1 6 0
1 6 0
M
3 3
327,5
30
5
3 0
2 1 0
5 7 8 5
121
2 1 0
5 9 0
2 1 0
8 0 0
9 1 4
Ø 13,5
30
38
30
5 9
2 8 7
27
42
6)
6 9
45
58
88,5
121,5
140,5
220
367,5
382,5
31
40
4
76
10)
2 8 2 ,5
1 4 2 ,5
2 6
150
5 9
275
30
460
3)
N S E 0 _ 0 0 6 7 6 a
8 4 0
6 3 0
7 0 4
1 6 0
1 2
30
8)
9)
NSE00675
7)
NSE0_01912
40,5
NSE00671a
11)
914
160
160
160
NSE00674
160
260
217
139
270
704
57 85
210
210
210
——— 4-pole version (on request)
3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in
the system.
Rated circuit breaker current
4) Auxiliary connector with SIGUT screw terminals.
A
5) Auxiliary connector with tension spring connection.
4000
5000
6) Dimension to inside surface of the closed cabinet door.
7) SENTRON 3WL5 in connected position.
8) SENTRON 3WL5 in test position.
9) SENTRON 3WL5 in disconnected position.
10) Fixing holes, diameter 9 mm.
11) Terminal face.
4/58
Siemens LV 16 · 2009
a
b
40
40
210
210
For safety clearances to grounded parts and to live parts see
page 4/52.
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Project planning aids
Installation conditions for UL circuit breakers
NSE0_01585
W2
1)
H
D
2
2)
D
1
3)
NSE0_01584
W1
4
1) Ventilation opening on top.
2) Insulation plate, e.g. NEMA GPO-3 material, min. 2.3 mm thick.
3) Ventilation opening on bottom.
Size
In max
Minimum dimensions of the installation space
Dimensions of the insulation plate
Height
H
Depth
D1
Width
W2
3/4-pole
Depth
D2
Ventilation
A
Width
W1
3/4-pole
I
I
800, 1000
1250, 1600
400/500
400/500
4601)
4601)
380
380
350/450
350/450
300
300
Not
required
II
II
II
800, 1600, 2000
2000
3000
500/600
500/600
500/600
4601)
4601)
4601)
380
380
380
450/550
450/550
450/550
300
300
300
Not
required
III
III
4000
5000
800/1000
800/1000
4601)
4601)
380
380
750/900
750/900
300
300
Not
required
1)
Height of installation compartment applies in case of roof insulation or for
guide frame with arcing space cover.
UL certificate
3WL5 circuit breakers are not listed by Underwriters Laboratories
(UL) under the Order No. but as individual components with their
corresponding order numbers.
The UL designation of the basic circuit breaker (without electronic
trip unit, auxiliary trip unit, auxiliary switch, ...) is visible on the
operator panel.
The file numbers are:
E231263 for circuit breakers
E236088 for accessories
E236299 for guide frames
Designation of basic circuit breaker:
3WL51 10-3 FB 32
$
$
%
&
(
% &(
Order No. 1st to 8th position
9th and 10th position: ETU electronic trip unit
11th position: Number of poles
12th position: Version
1, 2, 3, 4: Fixed mounting
5, 6, 7, 8: Withdrawable versions
The file number can be obtained from the following Internet site:
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/
gfilenbr.html
Siemens LV 16 · 2009
4/59
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Project planning aids
■ Schematics
Terminal assignment diagram
Interne
Beschaltung
Internal wiring
optional
Zubehör / Accessories
(Hilfsschalter S1, S2 = Standard)
(Auxiliary switch S1, S2 = Standard)
Externe Beschaltung
External wiring
L / L+
s/ c
N / L–
14
G-Wandler / G transformer S2
12
G-Wandler / G transformer S1
11
N-Wandler / N sensor S2
10
N-Wandler / N sensor S1
9
z.B. Wandler im TransformatorSternpunkt oder Summenstromwandler 1200 A /1 A
e.g. current transformer in the
star point of power transformer
or a summation current
transformer 1200 A /1A
Brücke, wenn kein N-Wandler
Short terminals if no N-sensor
ext. Spannungswandler Stern / ext. voltage transformer Com
8
L1
ext. Spannungswandler / ext. voltage transformer L3
7
L2
ext. Spannungswandler / ext. voltage transformer L2
6
L3
ext. Spannungswandler / ext. voltage transformer L1
5
N
13
Speicherzustandsmeldung /
"Spring charged" signal S21
11
Elektrisch "EIN" / Local electric close S10
9
13
12
10
8
7
6
Meldeschalter am ersten Hilfsauslöser / S22
Signaling contact at the 1 st auxiliary release
5
4
3
Meldeschalter am zweiten Hilfsauslöser / S23
Signaling contact at the 2nd auxiliary release
2
1 2 3 4 5 6 7 8 9
14
/COM16
(Option F02/F12)
L / L+
s/ c
Internal
Ausgelöst-Meldeschalter
(Stellung nach Auslösung) /
trip signalling switch S24
(position after tripping)
Abschlusswiderstand,
wenn kein externes CB-modul!
Termination resistor,
if not external CB-module!
External
1
Open
– + OUT
F1, 2
2
BUS
Y1
BUS +
24 V DC input
Close
– +
3
Free
– +
4
DPWrite Free
Enable
0 V DC
24 V DC
IN
Not available with communication connection "F02" or “F12”.
COM15/COM16 module is at position "-X7".
Fern-Rücksetzmagnet /
Remote reset bell alarm & tripped indicator F7
Nicht vorhanden bei Kommunikationsfunktion "F02" oder “F12”.
Auf der Position von "-X7" befindet sich das Modul COM15/COM16.
4
Klemmen
Terminals
1
Erster Hilfsauslöser F1 "f" / 1st auxiliary release F1 "ST"
14
L / L+
13
N / L–
c
12
S1 "S" / "NO"
11
10
S1 "Ö" / "NC"
9
Einschaltmagnet / Closing solenoid
8
N / L–
7
L / L+
c
6
5
Einschaltbereitschaftsmeldung / "Ready to close" signal S20
4
S2 "S" / "NO"
3
2
S2 "Ö" / "NC"
1
nur F4 "Schnell AUS" / F4 only "quick OFF"
14
nur F4 "Schnell AUS" / F4 only "quick OFF"
13
Zweiter Hilfsauslöser: F2 "ST", F3 "UVR", F4 "UVR td" /
2nd auxiliary release: F2 "ST", F3 "UVR", F4 "UVR td"
12
11
10
S3 "S" oder S7 "S" / S3 "NO" or S7 "NO"
9
8
S3 "Ö" oder S7 "S" / S3 "NC" or S7 "NO"
7
6
S4 "S" oder S8 "S" / S4 "NO" or S8 "NO"
5
4
4/60
Siemens LV 16 · 2009
NSE0_00605 o
S4 "Ö" oder S8 "S" / S4 "NC" or S8 "NO"
Motorantrieb / Charging motor
opt.: Motorabstellschalter / opt. motor main switch S12
NOT-AUS oder Brücke
EMERGENCY OFF
or short terminals
L / L+
c
N / L–
(sw)
M
(br)
3
2
1
L / L+
N / L–
c
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Project planning aids
Example of an overall circuit diagram for SENTRON 3WL5
(3WL5. ..–.....–4GN4–Z C11+ C22 + K07)
Manual/motorized operating mechanism with stored-energy feature
with electrical ON button (option C11), with ready-to-close signaling
L1
(L+)
enabling
contacts
switch (option C22), with LSING electronic trip unit, with "UVR"
undervoltage release (F3), with "ST" shunt trip unit (F1), with tripped
signal switch (option K07), with auxiliary switch 4 NO + 4 NC.
L1
(L+)
OFF
Version
electr.
ON
-X5.6
-X5.4
-X5.10
-X5.8
-X6.4
-X6.2
-X6.12
-X6.10
ETU
L
-S10
-A1
5
1
3
-X6.6
-X7.12
-X7.14
-X5.12
-X6.14
-X6.7
-X7.9
-X5.2
ON
S
I
N N
G
-S11
-F3
-Y1
U<
-T2
NSE0_01913
-T3
-S12
-A1
-S1/-S2
-S3/-S4
-S7 (optional)
F1
F2
-S8 (optional)
F3
Q1
S1 & S2
S3 & S4
1
S24
A1
2
T1
T2
T3
T4
3
-S10
-S11
-S12
NSE0_01559c
L
S
I
N N
G
-X5.5
-X5.3
-X5.7
-X6.3
-X6.1
-X6.9
-X6.11
-X5.9
(2 NO + 2 NC) S1+S2
(4 NO + 4 NC) S1+S2+S3+S4
(6 NO+ 2 NC) S1+S2+S7+S8
(5 NO + 3 NC) S1+S2+S3+S8
-S20
-S24
Electrical ON button
Internal motor shutdown switch (if spring is tensioned)
Motor shutdown switch
(no automatic tensioning of spring)
Ready-to-close signaling switch
Tripped signal switch
-F1
-F3
-F5
1st auxiliary trip unit shunt trip unit
2nd auxiliary trip undervoltage release
Tripping solenoid
-M
-P
-QS
-Q1
-T1/-T2/-T3
-X5/-X6/-X7/-X8
-Y1
-R
Motor for "charging store"
Spring energy store
Actuator lever for "stored-energy feature"
Main contacts
Current transformers
Terminals
Closing solenoid
Indicator and reset button for electronic trip unit
-X8.9/-X8.10
Connection option: external neutral conductor trans
former
F5
Y1
Electronic trip unit ETU
1st auxiliary switch block (2 NO + 2 NC)
2nd auxiliary switch block (2 NO + 2 NC)
2nd auxiliary switch block, S7 (2 NO) can be used
if there is no S3 - S3 and S7 have the same terminal
assignment/mounting space
2nd auxiliary switch block, S8 (2 NO) can be used
if there is no S4 - S4 and S8 have the same terminal
assignment/mounting space
3WL5. ..-.....-...2
3WL5. ..-.....-...4
3WL5. ..-.....-...7
3WL5. ..-.....-...8
F4
M1
P
4
* Jumper, if no neutral transformer
Function diagram of
SENTRON 3WL5 circuit breaker
S20
6
2
4
-X8.9
N
(L-)
*
-X8.10
-X7.13
-X6.5
-X5.11
-X6.8
-X6.13
-F1
-X5.1
N
(L-)
-S4
-S3
-T1
M
mech.
ON
-S2
-S1
-Q1
P
QS
mech.
OFF
-S24
-F5
-S20
R
Siemens LV 16 · 2009
4/61
© Siemens AG 2008
SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers
According to UL 489/IEC 60947-2 for AC up to 5000 A
Project planning aids
Example of the mode of operation of Zone Selective Interlocking functionality in power distribution
5
6
1
2
3
4
ZSI
module
ZSI module
SENTRON 3WL
3
4
5
6
ZSI
module
SENTRON 3WL
3
4
5
6
SENTRON 3WL
ZSI
module
SENTRON 3VL
NSE0_01898
SENTRON 3WL
3
4
5
6
NSE0_01897
ZSI
module
SENTRON 3WL
3
4
5
6
SENTRON 3WL
3
4
5
6
ZSI
module
SENTRON 3WL
3
4
5
6
ZSI
module
SENTRON 3WL
3
4
5
6
ZSI
module
ZSI
module
SENTRON 3WL
3
4
5
6
Connection diagram for a Zone Selective Interlocking functionality with
multiple infeed and several outgoing units with SENTRON 3WL5 circuit
breakers
SENTRON 3VL and SENTRON 3WL5 circuit breakers used in various
staggered levels
5
6
1
2
3
4
ZSI
module
ZSI module
SENTRON 3WL
3
4
5
6
ZSI
module
SENTRON 3WL
3
4
5
6
4
NSE0_01899
SENTRON 3WL
SENTRON 3WL
3
4
5
6
ZSI
module
ZSI
module
SENTRON 3WL
3
4
5
6
Zone Selective Interlocking functionality: Connection using a coupling
switch, use of SENTRON 3WL5 circuit breakers
■ More information
Up-to-date information on the Internet at:
http://www.siemens.com/sentron