© Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/ Non-Automatic Air Circuit Breakers according to UL 489/IEC Catalog 4/2 4/6 4/6 4/7 4/8 4/9 4/15 4/16 4/28 Technical Information 4/29 4/35 4/40 4/45 4/50 4/51 4/60 4/62 4 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Introduction - Overview General data - Benefits - Application 3-pole, fixed-mounted versions - Selection and ordering data 3-pole, withdrawable versions - Selection and ordering data Options - Selection and ordering data Accessories and spare parts - Overview - Selection and ordering data - Options SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A General data - Design - Function - Configuration - Technical specifications Project planning aids - Characteristic curves - Dimensional drawings - Schematics - More information Siemens LV 16 · 2009 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Introduction ■ Overview Size I Size III Size II Air circuit breakers 3WL air circuit breakers/non-automatic air circuit breakers according to UL 489 up to 5000 A Size I, II, III Rated current In A 1000, 1600, 2000, 2500, 3000, 4000, 5000 V AC Up to 600 */347 Up to 600 */347, Up to 600 Up to 600 */347 Size I Size II Size III 65 (480 V) 100 (480 V) 100 (480 V) 10000 5000 Number of poles 3-pole, 4-pole on request Rated operational voltage Ue Rated ultimate short-circuit breaking capacity at 500 V AC kA Endurance Operating 10000 cycles Mounting position 3 0 ° 3 0 ° 4 N S E 0 _ 0 0 0 6 1 a Degree of protection With cover Without cover (with door sealing frame) 3 0 ° 3 0 ° N S E 0 _ 0 0 0 6 2 a IP55 IP41 Dimensions 3-/4-pole D 320/410 460/590 704/914 H mm 434 434 434 D mm 291 291 291 Withdrawable H mm 465.5 465.5 465.5 D mm 471 471 471 Type NSE0_01901 NSS0_00535 W mm Fixed mounting NSE0_01900 H W ETU25B ETU45B Electronic trip units for SENTRON 3WL circuit breakers Overload protection ✓ ✓ Short-time delayed short-circuit protection ✓ ✓ Instantaneous short-circuit protection ✓ ✓ Neutral conductor protection -- ✓ Ground-fault protection -- ❑ Zone Selective Interlocking -- ❑ LCD, 4-line -- ❑ LCD, graphic -- -- Communication through PROFIBUS DP -- ❑ Measurement function Plus -- ❑ Selectable parameter sets -- -- Parameters freely programmable -- -- CubicleBUS -- ✓ ✓ Standard -- Not available ❑ Optional 4/2 Siemens LV 16 · 2009 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Introduction Size I II III Type 3WL51 3WL52 3WL53 Switching capacity class S H H S H H 100 100 Short-circuit breaking capacity Icu = Ics acc. to UL 489 Up to 480 V AC kA 65 Up to 600 V AC */347 V AC kA 50 851) Up to 600 V AC kA -- 85 kA 65 85 85 85 -- Rated short-time withstand current acc. to UL 489 At max. delay time tsd = 0,4 s Short-circuit breaking capacity Icu = Ics acc. to IEC 60947-2 Up to 500 V AC Icm at 500 V AC kA kA 65 143 100 220 100 220 Up to 690 V AC Icm at 690 V AC kA kA 50 105 85 187 85 187 Rated short-time withstand current Icw acc. to IEC 60947-2 0.5 s kA 65 85 85 1s kA 50 80 80 1) Covered by 600 V AC (delta) test. S Circuit breakers with standard switching capacity S (Icu = Ics up to 65 kA at 480 V) H Circuit breakers with high switching capacity H (Icu = Ics up to 100 kA at 480 V) 4 The circuit breakers are indicated in the technical specifications by orange backgrounds. Siemens LV 16 · 2009 4/3 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Introduction SENTRON 3WL5: Superior individual products integrated into uniform power distribution systems – up to and including industry-specific industrial and infrastructure solutions 6 7 2 3 8 5 9 1 25 4 21 10 19 11 22 23 12 18 13 24 17 20 $Guide frames (pages 4/16) %Main circuit connection front, flange, horizontal, vertical (pages 4/26 and 4/27) &Position indicator switches (pages 4/12 and 4/22) )Shutters (page 4/25) *COM15 PROFIBUS modules or COM16 MODBUS modules (page 4/18) +External CubicleBUS modules (page 4/17) ,Closing solenoids, auxiliary trip units (page 4/24) -Auxiliary conductor plug-in systems (page 4/23) .Auxiliary switch blocks (page 4/24) /Door sealing frames (page 4/25) 0Interlocking sets for base plate (page 4/19) 1Transparent panels, function insert (page 4/19) 4/4 Siemens LV 16 · 2009 16 15 NSE0_01902 14 2EMERGENCY-STOP pushbuttons, key operated (page 4/22) 3Motorized operating mechanisms (page 4/24) 4Operating cycles counters (page 4/22) 5Breaker status sensors (BSS) (page 4/18) 6Protective devices with device holder, electronic trip units (ETU) (page 4/17) 7Remote reset solenoids (page 4/19) 8Breaker data adapters (BDA) (page 4/17) 9Four-line displays (page 4/17) :Ground-fault protection modules (page 4/17) ;Rated current modules (page 4/17) <Measuring function modules (page 4/18) =Circuit breakers (pages 4/7 to 4/9) © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Introduction Communication-capable circuit breakers (ETU45B electronic trip units) 21 Ethernet 19 20 PROFIBUS 4 8 5 14 22 15 16 6 1 18 7 CubicleBUS 10 1 17 11 9 12 13 3 1 SENTRON 3VL 12 ETU electronic trip unit 2 LCD ETU electronic trip unit 13 Measurement function Plus 3 ETU electronic trip unit 14 Zone Selective Interlocking module 4 COM10 PROFIBUS module including Zone Selective Interlocking 15 Digital output module with relay contacts 5 COM20 PROFIBUS module2) including Zone Selective Interlocking 16 Digital output module with relay contacts, configurable 6 Breaker Data Adapter (BDA) 17 Analog output module 7 BDA Plus with Ethernet interface 18 Digital input module 8 Browser-capable I/O device (e.g. notebook) 19 Switch ES Power on PC 9 SENTRON 3WL 20 PLC e.g. SIMATIC S7 10 COM15 PROFIBUS module1) 21 SIMATIC powercontrol 11 Breaker Status Sensor (BSS) 22 SENTRON PAC 4 NSE0_01105h 2 1) For a MODBUS connection you need the COM16 module. 2) For a MODBUS connection you need the COM21 module. Features • Coordinated communication concept using the PROFIBUS DP or MODBUS, ranging from 16 A to 5000 A with SENTRON 3VL and SENTRON 3WL5 • The high level of modularity of circuit breakers and accessories allows easy retrofitting of all communication components • Significant additional benefits for the switchboard due to the possibility of linking up external input and output modules to the circuit breaker-internal CubicleBUS of the SENTRON 3WL5 • Innovative software products for parameterization, operation, monitoring, and diagnostics of SENTRON circuit breakers, both locally or via PROFIBUS DP, MODBUS or Ethernet/Intranet/ Internet Communication: • For air circuit breakers with optional communication function (ETU45B electronic trip units) see pages 4/7 and 4/8. • For accessories see pages 4/17 and 4/18. • For further information, see also Catalog LV 1 "Low-Voltage Controls and Distribution – SIRIUS, SENTRON, SIVACON", chapter "Power Management System" and "Software for Power Distribution". Complete integration of the SENTRON circuit breakers into the Totally Integrated Power and Totally Integrated Automation solutions Siemens LV 16 · 2009 4/5 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A General data ■ Benefits ■ Application Low space requirements The SENTRON 3WL5 devices require very little space. Size I devices (up to 1600 A) fit into a 400 mm wide switchgear panel. Size III devices (up to 5000 A) are the smallest of their kind and with their construction width of 704 mm fit into a 800 mm wide switchgear panel. Modular design Components like auxiliary trip units, motorized operating mechanisms, electronic trip units, current sensors, auxiliary circuit signaling switches, automatic reset devices, interlocks or engagement operating mechanisms can all be exchanged or retrofitted at a later stage, thus allowing the circuit breaker to be adapted to new, changing requirements. Retrofittable modules for electronic trip units Modularity is one of the main features of the new SENTRON 3WL5 circuit breakers. Special LCDs, ground-fault modules, rated current modules and communication modules for the electronic trip units are available for fast and easy retrofitting and adaptation to changing requirements. Communication 4 The use of modern communication-capable circuit breakers opens up completely new possibilities in terms of start-up, parameterization, diagnostics, maintenance and operation. This allows many different ways of reducing costs and improving productivity in industrial plants, buildings and infrastructure projects to be achieved. • Timely information and response can prevent plant stoppages • Effective diagnostics management • Measured values are the basis for efficient load management, for drawing up power demand profiles and for assigning energy to cost centers • Preventive maintenance reduces the risk of expansive plant down-times 4/6 Siemens LV 16 · 2009 • As incoming-feeder, distribution, tie, and outgoing-feeder circuit breakers in electrical installations • For switching and protecting motors, capacitors, generators, transformers, busbars and cables Due to the reinforced use of electronic I&C systems, the demands made on air circuit breakers in terms of operator control and monitoring of network processes have increased. The extensive, coordinated SENTRON range of devices covers all applications between 16 A and 5000 A with compact and air circuit breakers. Standards SENTRON 3WL5 circuit breakers comply with: • UL 489 • IEC 60947-2 • DIN VDE 0660 Part 101 • Climate-proof according to IEC 60068-2-30. © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A 3-pole, fixed-mounted versions ■ Selection and ordering data Size Max. rated circuit breaker current In max. Rated current1) In Switching capacity 480 V A A kA DT Order No. Order No. supplements, see page 4/9 Price per PU PU PS* (UNIT, SET, M) PG Weight per PU approx. kg Horizontal main circuit connection I I 1000 1600 1000 1600 65 65 B B 3WL51 10-3@@32-.... 3WL51 16-3@@32-.... 1 1 1 unit 1 unit 103 103 43.000 43.000 II II II 2000 2500 3000 2000 2500 3000 100 100 100 B B B 3WL52 20-4@@32-.... 3WL52 25-4@@32-.... 3WL52 30-4@@32-.... 1 1 1 1 unit 1 unit 1 unit 103 103 103 56.000 59.000 64.000 III III 4000 5000 4000 5000 100 100 C C 3WL53 40-4@@32-.... 3WL53 50-4@@32-.... 1 1 1 unit 1 unit 103 103 82.000 82.000 Vertical main circuit connection I I 1000 1600 1000 1600 65 65 B B 3WL51 10-3@@31-.... 3WL51 16-3@@31-.... 1 1 1 unit 1 unit 103 103 43.000 43.000 II II II 2000 2500 3000 2000 2500 3000 100 100 100 B B B 3WL52 20-4@@31-.... 3WL52 25-4@@31-.... 3WL52 30-4@@31-.... 1 1 1 1 unit 1 unit 1 unit 103 103 103 56.000 59.000 64.000 III III 4000 5000 4000 5000 100 100 C C 3WL53 40-4@@31-.... 3WL53 50-4@@31-.... 1 1 1 unit 1 unit 103 103 82.000 82.000 Front main circuit connection, single hole I I 1000 1600 1000 1600 65 65 B B 3WL51 10-3@@33-.... 3WL51 16-3@@33-.... 1 1 1 unit 1 unit 103 103 43.000 43.000 II II II 2000 2500 3000 2000 2500 3000 100 100 100 B B B 3WL52 20-4@@33-.... 3WL52 25-4@@33-.... 3WL52 30-4@@33-.... 1 1 1 1 unit 1 unit 1 unit 103 103 103 56.000 59.000 64.000 III 4000 4000 100 C 3WL53 40-4@@33-.... 1 1 unit 103 82.000 Front main circuit connection, double hole I I 1000 1600 1000 1600 65 65 B B 3WL51 10-3@@34-.... 3WL51 16-3@@34-.... 1 1 1 unit 1 unit 103 103 43.000 43.000 II II II 2000 2500 3000 2000 2500 3000 100 100 100 B B B 3WL52 20-4@@34-.... 3WL52 25-4@@34-.... 3WL52 30-4@@34-.... 1 1 1 1 unit 1 unit 1 unit 103 103 103 56.000 59.000 64.000 III 4000 4000 100 C 3WL53 40-4@@34-.... 1 1 unit 103 82.000 Non-automatic air circuit breakers2) Without electronic trip unit Order No. supplements Additional price AA None Versions without ground-fault protection ETU25B: Protection functions LSI CB x ETU45B: Protection functions LSIN3) EB x ETU45B: Protection functions LSIN3) with 4-line display FB x Versions with ground-fault protection ETU45B: Protection functions LSING3)4) EG x ETU45B: Protection functions LSING3)4) with 4-line display FG x Electronic trip units Standard Order No. supplements (for further Order No. supplements, see page 4/9) Manual operating mechanism with mechanical closing Without 1st and 2nd auxiliary trip units; auxiliary switch 2 NC + 2 NO 1AA2 None x = additional price 4-pole version on request. Order No. supplements required, see page 4/9. Note: Max. voltage for auxiliary circuits 240 V. 1) The rated current is determined by the rated current module. For the standard version, the supplied module is equal to the rated current. If a lower rated current is required, adaptation by rated current module on page 4/17. 2) For permissible rated short-time current Icc and rated short-circuit making capacity Icm for non-automatic air circuit breakers see "Technical Specifications", page 4/45. 3) Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral point of the transformer are to be ordered separately, see page 4/18. 4) For ETU45B with ground-fault protection module GFM AT (alarm and tripping) see page 4/17. * You can order this quantity or a multiple thereof. Siemens LV 16 · 2009 4/7 4 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A 3-pole, withdrawable versions ■ Selection and ordering data Size Max. rated circuit breaker current In max. Rated current1) In Switching capacity 480 V A A kA DT Order No. Order No. supplements, see page 4/9 Price per PU PU PS* (UNIT, SET, M) PG Weight per PU approx. kg Without guide frames (for guide frames, see page 4/16) I I 1000 1600 1000 1600 65 65 B B 3WL51 10-3@@35-.... 3WL51 16-3@@35-.... 1 1 1 unit 1 unit 103 103 45.000 45.000 II II II 2000 2500 3000 2000 2500 3000 100 100 100 B B B 3WL52 20-4@@35-.... 3WL52 25-4@@35-.... 3WL52 30-4@@35-.... 1 1 1 1 unit 1 unit 1 unit 103 103 103 60.000 63.000 68.000 III III 4000 5000 4000 5000 100 100 C C 3WL53 40-4@@35-.... 3WL53 50-4@@35-.... 1 1 1 unit 1 unit 103 103 88.000 88.000 With guide frames, horizontal main circuit connection I I 1000 1600 1000 1600 65 65 B B 3WL51 10-3@@36-.... 3WL51 16-3@@36-.... 1 1 1 unit 1 unit 103 103 70.000 70.000 II II II 2000 2500 3000 2000 2500 3000 100 100 100 B B B 3WL52 20-4@@36-.... 3WL52 25-4@@36-.... 3WL52 30-4@@36-.... 1 1 1 1 unit 1 unit 1 unit 103 103 103 91.000 102.000 113.000 III III 4000 5000 4000 5000 100 100 C C 3WL53 40-4@@36-.... 3WL53 50-4@@36-.... 1 1 1 unit 1 unit 103 103 148.000 148.000 With guide frames, vertical main circuit connection 4 I I 1000 1600 1000 1600 65 65 B B 3WL51 10-3@@37-.... 3WL51 16-3@@37-.... 1 1 1 unit 1 unit 103 103 70.000 70.000 II II II 2000 2500 3000 2000 2500 3000 100 100 100 B B B 3WL52 20-4@@37-.... 3WL52 25-4@@37-.... 3WL52 30-4@@37-.... 1 1 1 1 unit 1 unit 1 unit 103 103 103 91.000 102.000 113.000 III III 4000 5000 4000 5000 100 100 C C 3WL53 40-4@@37-.... 3WL53 50-4@@37-.... 1 1 1 unit 1 unit 103 103 148.000 148.000 With guide frames, connecting flanges I I 1000 1600 1000 1600 65 65 B B 3WL51 10-3@@38-.... 3WL51 16-3@@38-.... 1 1 1 unit 1 unit 103 103 70.000 70.000 II II II 2000 2500 3000 2000 2500 3000 100 100 100 B B B 3WL52 20-4@@38-.... 3WL52 25-4@@38-.... 3WL52 30-4@@38-.... 1 1 1 1 unit 1 unit 1 unit 103 103 103 91.000 102.000 113.000 III 4000 4000 100 C 3WL53 40-4@@38-.... 1 1 unit 103 148.000 Non-automatic air circuit breakers2) Without electronic trip unit Order No. supplements Additional price AA None Versions without ground-fault protection ETU25B: Protection functions LSI CB x ETU45B: Protection functions LSIN3) EB x ETU45B: Protection functions LSIN3) with 4-line display FB x Versions with ground-fault protection ETU45B: Protection functions LSING3)4) EG x ETU45B: Protection functions LSING3)4) with 4-line display FG x Electronic trip units Standard Order No. supplements (for further Order No. supplements for circuit breakers and guide frames, see page 4/9) Manual operating mechanism with mechanical closing Without 1st and 2nd auxiliary trip units; auxiliary switch 2 NC + 2 NO 1AA2 None x = additional price 4-pole version on request. Order No. supplements required, see page 4/9. Note: Max. voltage for auxiliary circuits 240 V. 1) The rated current is determined by the rated current module. For the standard version, the supplied module is equal to the maximum rated current. If a lower rated current is required, adaptation by rated current module on page 4/17. 2) For permissible rated short-time current Icc and rated short-circuit making capacity Icm for non-automatic air circuit breakers see "Technical Specifications", page 4/45. 3) Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral point of the transformer are to be ordered separately, see page 4/18. 4) For ETU45B with ground-fault protection module GFM AT (alarm and tripping) see page 4/17. 4/8 Siemens LV 16 · 2009 * You can order this quantity or a multiple thereof. © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Options ■ Selection and ordering data Order No. supplement Additional price 3WL 5 . . . - . . . . . -7 7 7 7 Operating mechanisms Manual operating mechanism with mechanical closing 1 None 2 3 x x 4 5 6 x x x Manual operating mechanism with mechanical and electrical closing, closing solenoid suitable for uninterrupted duty, 100 % ON period Closing solenoid AC 50/60 Hz V V DC 120 240 125 240 Manual/motorized operating mechanism with mechanical and electrical closing, closing solenoid suitable for uninterrupted duty, 100 % ON period Motor Closing solenoid AC 50/60 Hz V V DC AC 50/60 Hz V V DC 208 ... 240 110 ... 127 -- 220 ... 250 110 ... 125 24 240 120 -- 240 125 24 To order different voltages for motorized operating mechanism and closing solenoid or closing solenoid for synchronization purposes: "1" at the 13th position of the Order No. and order codes, see page 4/11. 1st auxiliary trip units Without 1st auxiliary trip unit A None B C D E F G x x x x x x 4 Shunt trip unit suitable for uninterrupted duty, 100 % ON period Operating range 0.85 ... 1.1 x Us Us AC 50/60 Hz V Us V DC ----120 240 24 30 48 60 125 240 2nd auxiliary trip units Without 2nd auxiliary trip unit A None B C D E F G x x x x x x J K L U M N x x x x x x Q R S x x x Shunt trip unit suitable for uninterrupted duty, 100 % ON period Operating range 0.85 ... 1.1 x Us Us AC 50/60 Hz V Us V DC -24 -30 -48 -60 120 125 240 240 Undervoltage release, instantaneous ( 80 ms), short-delay ( 200 ms) Operating range 0.85 ... 1.1 x Us Us AC 50/60 Hz V Us V DC ----120 240 24 30 48 60 125 250 Undervoltage release, can be delayed between 0.2 s and 3.2 s Operating range 0.85 ... 1.1 x Us Us AC 50/60 Hz V Us V DC -120 240 48 125 250 Auxiliary switches 1st auxiliary switch block 2 NO + 2 NC 2 None 1st + 2nd auxiliary switch block 4 NO + 4 NC 6 NO + 2 NC 5 NO + 3 NC 4 7 8 x x x x = additional price Siemens LV 16 · 2009 4/9 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Options Add "–Z" to the complete Order No. and indicate the appropriate order code(s). Order No. with "–Z" 1 2 3 4 5 6 7 Additional price 8 9 10 11 12 13 14 15 16 3WL 5 . . . - . . . . . - . . . . - Z and additional order code(s) @@@+ . . . + . . . Code for "Further versions"–Z Special packaging Additional price Special packaging for extended technical requirements Cardboard packaging with wax coating (moisture protection), internal bracing, tilt indicators A 6 0 Rated current modules/Rating plugs x Additional price Rated current In A Only one module is possible per For size I, II circuit breaker. As standard the overcurrent trip units are equipped with a rated current module which is equal to the maximum rated current circuit breaker (In max). The rated current of the selected rated current module must be smaller than In max. For size I, II, III 250 B 0 2 None 315 B 0 3 None 400 B 0 4 None 500 B 0 5 None 630 B 0 6 None 800 B 0 8 None 1000 B 1 0 None 1250 B 1 2 None 1600 B 1 6 None 2000 B 2 0 None 2500 B 2 5 None 3000 B 3 0 None 3200 B 3 2 None 4000 B 4 0 None 5000 B 5 0 None 5-digit mechanical operating cycles counter1) C 0 1 x Electrical ON button Button with sealing cap in the operator panel2) Key operation with lock CES possible only for circuit breakers with closing solenoid C 1 1 x C 1 2 x For size II, III 4 For size III Indication/operator control elements, door sealing frames Storage status signaling switches2) (S21) 1 NO C 2 0 x Ready-to-close signaling switch (S20) 1 NO C 2 2 x For the first auxiliary trip unit (S22) C 2 6 x For the second auxiliary trip unit (S23) C 2 7 x Motor shutdown switch in the operator panel3) S 2 5 x EMERGENCY-STOP pushbuttons Mushroom pushbutton instead of the mechanical OFF pushbutton S 2 4 x Door sealing frames T 4 0 x Signal switches2) x = additional price 1) Only possible with motorized operating mechanism. Not possible with communications connection option, order code "F02" or "F12". 3) Only for circuit breakers with motorized operating mechanism, not possible with order codes "C11", "C12". 2) 4/10 Siemens LV 16 · 2009 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Options Add "–Z" to the complete Order No. and indicate the appropriate order code(s). Order No. with "–Z" 1 2 3 4 5 6 7 Additional price 8 9 10 11 12 13 14 15 16 3WL 5 . . . - . . . . . - . . . . - Z and additional order code(s) @@@+. . . + . . . Code for "Further versions"–Z Lockout devices and remote resets Automatic reset of the lockout device K 0 1 x Tripped signal switches1)2) K 0 7 x K K K K 1 1 1 1 0 1 2 3 x x x x M M M M 0 0 0 0 1 3 5 6 x x x x 24 30 48 M2 1 M2 2 M2 3 x x x 60 125 240 M2 4 M2 5 M2 6 x x x M M M M 3 3 3 3 1 3 5 6 x x x x M M M M 4 4 4 4 1 3 5 6 x x x x Breaker status sensor (BSS) F 0 1 x PROFIBUS communications interfaces4) including COM15 and breaker status sensor (BSS) F 0 2 x MODBUS communications interfaces4) including COM16 and breaker status sensor (BSS) F 1 2 x Measurement function Plus (without PROFIBUS/MODBUS communications interface) 5) F 0 5 x 1 CO contact Remote reset solenoid for displays and reset buttons including automatic reset of the lockout device AC 50/60 Hz V V DC --120 220 ... 240 24 48 120 220 ... 240 Motorized operating mechanisms and closing/opening solenoids Motorized operating mechanisms Only possible if the 13th position of the Order No. = "1" Motor AC 50/60 Hz V V DC --110 ... 127 208 ... 240 24 ... 30 48 ... 60 110 ... 125 220 ... 250 4 Closing solenoids suitable for uninterrupted duty, 100 % ON period – Only possible if the 13th position of the Order No. = "1" Activation solenoids AC 50/60 Hz V V DC ----120 240 Closing solenoids3) – unsuitable for uninterrupted duty, 5 % ON period – Only possible if the 13th position of the Order No. = "1" Activation solenoids AC 50/60 Hz V V DC --120 240 24 48 125 250 Opening solenoids (shunt trip unit)6) – unsuitable for uninterrupted duty, 5 % ON period Activation solenoids AC 50/60 Hz V V DC --120 240 24 48 125 250 Communication and measurement functions x = additional price 1) Not possible with communications connection option, order code "F02" or "F12". 2) Not available for non-automatic air circuit breakers. 3) Overexcited, i.e. closing time 50 ms (standard > 80 ms). 4) If ordering withdrawable circuit breaker and guide frame separately, specify order code "F02" or "F12" for withdrawable circuit breaker only. 5) 6) Additional voltage transformers are required for connection of the measurement function Plus, see page 4/18. Only possible if the 14th position of the Order No. for the circuit breaker is "A", i.e. "without 1st auxiliary trip unit". Siemens LV 16 · 2009 4/11 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Options Add "–Z" to the complete Order No. and indicate the appropriate order code(s). Order No. with "–Z" 1234 5 6 7 Additional price 8 9 10 11 12 13 14 15 16 3WL 5 . . . - . . . . . - . . . . -Z and additional order code(s) @@@ + . . . + . . . Code for "Further versions" -Z Order code for fixedmounted version Order code for withdrawable version @@@ @@@ S 5 5 -- -- -- x For withdrawable circuit breakers -with guide frame R 5 5 x For guide frames -- R 5 6 x For withdrawable circuit breakers -- R 5 7 x Shutters 2-part lockable with padlocks1) 3-pole Size I Size II Size III ---- R 2 1 R 2 1 R 2 1 x x x Position indicator switches for guide frames Connected Test position position Disconnected position 1 CO 1 CO 1 CO -- R 1 5 x 3 CO 2 CO 1 CO -- R 1 6 x Interlocks, covers, position indicator switches Mutual mechanical interlockings (interlocking module with Bowden wire 2 m) 4 Fixed-mounted circuit breakers Add "–Z" to the complete Order No. and indicate the appropriate order code(s). Order No. with "–Z" 1 2 3 4 5 6 7 Additional price 8 9 10 11 12 13 14 15 16 3WL 5 . . . - . . . . . - . . . . - Z and additional order code(s) @@@ +. . . + . . . Code for "Further versions"–Z EMC filters Common-mode interference F 3 1 suppressor filters (e.g. in IT networks, caused by frequency converters) EMC filters Insertion loss (asymmetric) in the range 40 kHz to 10 MHz > 40 dB. x = additional price 1) Padlocks not included in scope of supply. 4/12 Siemens LV 16 · 2009 x © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Options Add "–Z" to the complete Order No. and indicate the appropriate order code(s). Order No. with "–Z" 8 9 10 11 12 1234 5 6 7 13 14 15 16 3WL 5 . . . - . . . . . - . . . . -Z and additional order code(s) @@@ + . . . + . . . Code for "Further versions" Locking devices Locking devices against unauthorized closing, in the operator panels The disconnector unit fulfills the requirements for main control switches acc. to EN 60204 (VDE 0113) and UL 489. @@@ @@@ Additional price for withdrawable version S 0 1 x S 0 1 x Made by IKON S 0 3 x S 0 3 x Assembly kit FORTRESS or Castell1) S 0 5 x S 0 5 x Assembly kit for padlocks2) S 0 7 x S 0 7 x Made by Ronis S 0 8 x S 0 8 x Made by Profalux S 0 9 x S 0 9 x S 2 4 S 2 4 Made by CES -- R 6 1 x Made by Ronis -- R 6 8 x Made by Profalux -- R 6 0 x 4 S 3 3 Locking devices for operating mechanism handles with padlock2) Locking devices to prevent movement of the withdrawable circuit breakers Safety lock for mounting on the circuit breaker Order code for withdrawable version Made by CES EMERGENCY-STOP pushbuttons Mushroom pushbutton instead of the mechanical OFF pushbutton Locking devices against unauthorized closing, for withdrawable circuit breakers The disconnector unit fulfills the requirements for main circuit breakers acc. to EN 60204 (VDE 0113) and UL 489, consisting of lock in the cabinet door, active in connected position, the function is retained when the circuit breaker is replaced -Z Order code Additional for fixed price for mounting fixed-mounted version x S 3 3 x Made by CES -- S 7 1 x Made by Profalux -- S 7 5 x Made by Ronis -- S 7 6 x -- R 8 1 x -- R 8 5 x -- R 8 6 x R 3 0 x R 5 0 x P 6 1 x Locking devices Locking devices to prevent Made by CES movement of the withdrawable Made by Profalux circuit breakers in disconnected Made by Ronis positions, consisting of Bowden wire and lock in the cabinet door Locking devices To prevent opening of the cabinet door in: S 3 0 ON position (fixed-mounted version)/ in connected position (withdrawable version) To prevent movement with the cabinet door open x -- Connection methods for auxiliary conductors Connections for screwless terminals (tension spring) N 6 1 x x = additional price 1) 2) Locks must be ordered from the manufacturer. Padlock not included in the scope of supply. Siemens LV 16 · 2009 4/13 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Options Add "–Z" to the complete Order No. and indicate the appropriate order code(s). Order No. with "–Z" 1234 5 6 7 8 9 10 11 12 13 14 15 16 3WL 5 . . . - . . . . . - . . . . -Z and additional order code(s) @@@ + . . . + . . . Code for "Further versions"–Z For withdrawable circuit breakers with guide frames or without guide frames Additional price 3-pole To select this connection method, the 12th position of the Order No. for the circuit breaker must be a "6" Connection methods for main circuit connections 4 Top and bottom: Accessible from front, single hole Size I, up to 1600 A Size II, up to 2000 A Size II, up to 2500 A Size II, up to 3000 A Size III, up to 4000 A P P P P P 0 0 0 0 0 0 0 0 0 0 x x x x x Top and bottom: Accessible from front, double hole Size I, up to 1600 A Size II, up to 2000 A Size II, up to 2500 A Size II, up to 3000 A Size III, up to 4000 A P P P P P 0 0 0 0 0 1 1 1 1 1 x x x x x Top: Horizontal, double hole Bottom: Accessible from front, single hole Size I, up to 1600 A Size II, up to 2000 A Size II, up to 2500 A Size II, up to 3000 A Size III, up to 4000 A P P P P P 0 0 0 0 0 7 7 7 7 7 x x x x x Top: Vertical Bottom: Horizontal Size I, up to 1600 A Size II, up to 2000 A Size II, up to 2500 A Size II, up to 3000 A Size III, up to 4000 A Size III, up to 5000 A P P P P P P 1 1 1 1 1 1 8 8 8 8 8 8 x x x x x x Top: Connecting flange Bottom: Horizontal Size I, up to 1600 A Size II, up to 2000 A Size II, up to 2500 A Size II, up to 3000 A Size III, up to 4000 A P P P P P 1 1 1 1 1 9 9 9 9 9 x x x x x Top: Horizontal Bottom: Vertical Size I, up to 1600 A Size II, up to 2000 A Size II, up to 2500 A Size II, up to 3000 A Size III, up to 4000 A Size III, up to 5000 A P P P P P P 2 2 2 2 2 2 3 3 3 3 3 3 x x x x x x Additional price 3-pole For fixed-mounted circuit breakers To select this connection method, the 12th position of the Order No. for the circuit breaker must be a "2" Connection methods for main circuit connections Top: Horizontal Bottom: Accessible from front, single hole Size I, up to 1600 A Size II, up to 2000 A Size II, up to 2500 A Size II, up to 3000 A Size III, up to 4000 A N N N N N 1 1 1 1 1 1 1 1 1 1 x x x x x Top: Vertical Bottom: Horizontal Size I, up to 1600 A Size II, up to 2000 A Size II, up to 2500 A Size II, up to 3000 A Size III, up to 4000 A Size III, up to 5000 A N N N N N N 2 2 2 2 2 2 0 0 0 0 0 0 x x x x x x Top: Horizontal Bottom: Vertical Size I, up to 1600 A Size II, up to 2000 A Size II, up to 2500 A Size II, up to 3000 A Size III, up to 4000 A Size III, up to 5000 A N N N N N N 2 2 2 2 2 2 4 4 4 4 4 4 x x x x x x x = additional price 4/14 Siemens LV 16 · 2009 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Accessories and spare parts ■ Overview Determination of the number of auxiliary supply connectors required NSE0_01104 This selection is only required if the guide frame is ordered under a separate Order No. X7 X6 X5 X8 The required number of auxiliary supply connectors depends on: • Operating mechanism type • Electronic trip unit with/without current transformer • Type and number of auxiliary trip units • Number of auxiliary switches • COM15/COM16 communication interface Number of auxiliary supply connectors Terminal a First auxiliary supply connector X6 always required. 1 X6 b b1 b2 b3 Operating mechanisms Manual operating mechanism with stored-energy feature with mechanical closing Manual operating mechanism with stored-energy feature with mechanical and electrical closing Manual/motorized operating mechanism with stored-energy feature with mechanical and electrical closing 0 0 +1 X6 X5 c c1 c2 Electronic trip units Electronic trip units ETU25B Electronic trip units ETU45B(internal CubicleBUS) 0 +1 X8 c3 c4 Connections for external current transformers for overload protection in the N conductor and ground-fault protection Current transformer installed in the N conductor (required with 3-pole circuit breakers if c2 is not selected) Current transformer in the neutral point of the transformer (required if c2 or c3 is not selected) +1 +1 X8 X8 d d1 d2 Auxiliary trip units With/without 1st auxiliary trip unit (shunt trip unit F1) 2nd auxiliary trip unit (shunt trip unit F2, undervoltage release F3, delayable undervoltage release F4) 0 +1 X6 X5 e e1 e2 Auxiliary switch blocks 1st auxiliary switch block 2 NO + 2 NC 1st and 2nd auxiliary switch block 4 NO + 4 NC or 6 NO + 2 NC or 5 NO + 3 NC (required if b3 or d2 is not selected) 0 +1 X6 X5 f f1 f2 Communications modules Without communication module COM15/COM16 With communication module COM15/COM16 – occupies the entire terminal strip X7, making the following options no longer possible: • Tripped signal switch S24 • Stored-energy status indication S21 • Electrical ON button S10 • Signaling switch on first and second auxiliary trip unit S22 + S23 0 +1 X7 g g1 g2 g3 g4 g5 g6 g7 g8 Optional signals/accessories Tripped signal switch S24 (only possible if f2 is not selected) Stored-energy status indication S21 (only possible if f2 is not selected, required if g1 is not selected) Electrical ON button S10 (only possible if f2 is not selected, required if g1 or g2 is not selected) Signal switch on first auxiliary trip unit S22 (only possible if f2 is not selected, required if g1, g2 or g3 is not selected) Signal switch on second auxiliary trip unit S23 (only possible if f2 is not selected, required if g1, g2, g3 or g4 is not selected) Ready-to-close signaling switch S20 Motor shutdown switch S12 (only possible if motorized operating mechanism is selected) Remote reset magnet F7 (required if c2 is not selected) +1 +1 +1 +1 +1 0 0 +1 X7 X7 X7 X7 X7 X6 X5 X8 h Total number of auxiliary supply connectors (max. 4) Siemens LV 16 · 2009 4/15 4 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Accessories and spare parts ■ Selection and ordering data Guide frames for circuit breakers according to UL 489 Size Max. rated circuit breaker current In max. DT Guide frames for 3-pole circuit breakers Order No. (Order No. supplements required acc. to table below) A Price per PU PU PS* (UNIT, SET, M) PG Weight per PU approx. kg Front main circuit connection, single hole I I II II II III 1000 1600 2000 2500 3000 4000 B B B B B B 3WL9 251-1AA@@-@@A1 3WL9 251-2AA@@-@@A1 3WL9 252-3AA@@-@@A1 3WL9 252-4AA@@-@@A1 3WL9 252-5AA@@-@@A1 3WL9 253-6AA@@-@@A1 1 1 1 1 1 1 1 unit 1 unit 1 unit 1 unit 1 unit 1 unit 103 103 103 103 103 103 25.000 25.000 31.000 39.000 45.000 60.000 B B B B B B 3WL9 251-1AB@@-@@A1 3WL9 251-2AB@@-@@A1 3WL9 252-3AB@@-@@A1 3WL9 252-4AB@@-@@A1 3WL9 252-5AB@@-@@A1 3WL9 253-6AB@@-@@A1 1 1 1 1 1 1 1 unit 1 unit 1 unit 1 unit 1 unit 1 unit 103 103 103 103 103 103 25.000 25.000 31.000 39.000 45.000 60.000 B B B B B B B 3WL9 251-1AC@@-@@A1 3WL9 251-2AC@@-@@A1 3WL9 252-3AC@@-@@A1 3WL9 252-4AC@@-@@A1 3WL9 252-5AC@@-@@A1 3WL9 253-6AC@@-@@A1 3WL9 253-7AC@@-@@A1 1 1 1 1 1 1 1 1 unit 1 unit 1 unit 1 unit 1 unit 1 unit 1 unit 103 103 103 103 103 103 103 25.000 25.000 31.000 39.000 45.000 60.000 60.000 B B B B B B B 3WL9 251-1AD@@-@@A1 3WL9 251-2AD@@-@@A1 3WL9 252-3AD@@-@@A1 3WL9 252-4AD@@-@@A1 3WL9 252-5AD@@-@@A1 3WL9 253-6AD@@-@@A1 3WL9 253-7AD@@-@@A1 1 1 1 1 1 1 1 1 unit 1 unit 1 unit 1 unit 1 unit 1 unit 1 unit 103 103 103 103 103 103 103 25.000 25.000 31.000 39.000 45.000 60.000 60.000 B B B B B B 3WL9 251-1AE@@-@@A1 3WL9 251-2AE@@-@@A1 3WL9 252-3AE@@-@@A1 3WL9 252-4AE@@-@@A1 3WL9 252-5AE@@-@@A1 3WL9 253-6AE@@-@@A1 1 1 1 1 1 1 1 unit 1 unit 1 unit 1 unit 1 unit 1 unit 103 103 103 103 103 103 25.000 25.000 31.000 39.000 45.000 60.000 Front main circuit connection, double hole I I II II II III 1000 1600 2000 2500 3000 4000 Horizontal main circuit connection 4 I I II II II III III 1000 1600 2000 2500 3000 4000 5000 Vertical main circuit connection I I II II II III III 1000 1600 2000 2500 3000 4000 5000 Main circuit connection connecting flanges I I II II II III 1000 1600 2000 2500 3200 4000 Number of auxiliary supply connectors None 1 connector 2 connectors 3 connectors 4 connectors For required number of auxiliary supply connectors, see table on page 4/15 Order No. supplements Additional price None x x x x 0 1 2 3 4 Type of auxiliary circuit connections None With screw connections (SIGUT) With screwless connection method (tension spring) None x x 0 1 2 Position indicator switches None 0 None Option 1 Connected position 1 CO contact, Test position 1 CO contact, Disconnected position 1 CO contact 1 x Option 2 Connected position 3 CO contacts, Test position 2 CO contacts, Disconnected position 1 CO contact 2 x Shutters None With shutter, 2-part, Lockable Size I Size II Size III x = additional price 4-pole version on request. 4/16 Siemens LV 16 · 2009 A B None x x x All other accessory parts must be ordered by specifying "-Z" and the corresponding order code, see page 4/12 "Interlocks, Covers, Position Indicator Switches". * You can order this quantity or a multiple thereof. © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Accessories and spare parts Designation DT Order No. Price per PU PU PS* (UNIT, SET, M) PG Weight per PU approx. kg Electronic trip units Type With protection function ETU25B ETU45B without measurement function Plus ETU45B with measurement function Plus LSI LSIN(G) C C 3WL9 352-5AA00-0AA1 3WL9 354-5AA00-0AA1 1 1 unit 1 1 unit 103 103 0.720 0.720 LSIN(G) C 3WL9 354-5AA20-0AA1 1 1 unit 103 0.720 250 B 3WL9 111-2AA51-0AA0 1 1 unit 103 0.010 315 B 3WL9 111-2AA52-0AA0 1 1 unit 103 0.010 400 B 3WL9 111-2AA53-0AA0 1 1 unit 103 0.010 500 B 3WL9 111-2AA54-0AA0 1 1 unit 103 0.010 630 B 3WL9 111-2AA55-0AA0 1 1 unit 103 0.010 800 B 3WL9 111-2AA56-0AA0 1 1 unit 103 0.010 1000 B 3WL9 111-2AA57-0AA0 1 1 unit 103 0.010 1250 B 3WL9 111-2AA58-0AA0 1 1 unit 103 0.010 1600 B 3WL9 111-2AA61-0AA0 1 1 unit 103 0.010 2000 B 3WL9 111-2AA62-0AA0 1 1 unit 103 0.010 2500 B 3WL9 111-2AA63-0AA0 1 1 unit 103 0.010 3000 B 3WL9 111-2AA77-0AA0 1 1 unit 103 0.010 3200 B 3WL9 111-2AA64-0AA0 1 1 unit 103 0.010 4000 B 3WL9 111-2AA65-0AA0 1 1 unit 103 0.010 5000 B 3WL9 111-2AA66-0AA0 1 1 unit 103 0.010 GFM AT 45B (only for ETU45B) alarm and tripping B 3WL9 111-2AT53-0AA0 1 1 unit 103 0.200 4-line displays for ETU45B B 3WL9 111-1AT81-0AA0 1 1 unit 103 0.061 Digital output modules with rotary coding switches, relay outputs C 3WL9 111-1AT26-0AA0 1 1 unit 103 0.350 Digital output modules, configurable, relay outputs C 3WL9 111-1AT20-0AA0 1 1 unit 103 0.400 Digital input modules C 3WL9 111-1AT27-0AA0 1 1 unit 103 0.300 Analog output modules C 3WL9 111-1AT23-0AA0 1 1 unit 103 0.300 Zone Selective Interlocking modules C 3WL9 111-1AT21-0AA0 1 1 unit 103 0.240 Breaker Data Adapters (BDA)4) Parameterization, control, diagnostics, and B test of SENTRON circuit breakers via local interface; Breaker Data Adapter, connection cable to SENTRON circuit breakers and to the programming device (e.g. notebook); can be run with Internet Explorer with JAVA2 VM and higher 3WL9 111-2AT28-0AA0 1 1 unit 103 0.800 BDA Plus4) Same as BDA, but with additional Ethernet B interface for connection to Ethernet/ Intranet/Internet 3WL9 111-2AT33-0AA0 1 1 unit 103 1.000 Connection Connection cable for connection of BDA B cables for Plus to terminal X8 of the SENTRON 3WL BDA Plus circuit breaker. Required if neither COM15 nor COM16 nor other external CubicleBUS 3WL9 111-0AT28-0AA0 modules are available, length 2 m. 3WL9 111-0BC21-0AA0 1 1 unit 103 0.350 3ZS2 311-0CC10-0YA0 1 1 unit 133 0.200 Rated current modules/Rating plugs1) For size Rated current In (A) I, II I, II, III II, III n = 3 2 0 0 A N S E 0 _ 0 0 9 9 2 b 3WL9 111-2AA65-0AA0 III Ground-fault modules2) Displays CubicleBUS modules3) N S E 0 _ 0 1 0 2 3 a 3WL9 111-1AT23-0AA0 Tools for parameterization, operation and monitoring N S E 0 _ 0 1 0 2 4 a Switch ES Power parameterization software 1) 2) Calibration, operation, monitoring, and A diagnostics of SENTRON circuit breakers via PROFIBUS DP; runs under Windows 95, Windows 98, Windows NT, Windows 2000 and Windows XP Professional, requires additional PROFIBUS card e.g. CP5613 With the rated current module selected, the maximum rated current In max of the circuit breaker must not be exceeded. Following applies In < In max. For direct measurement of the ground-fault current, e.g. in the neutral point of the transformer, a 1200 A/1 A current transformer, class 1, is required. The internal load of the SENTRON 3WL is 0.11 m. If the ground-fault current * You can order this quantity or a multiple thereof. is to be determined using the vectorial sum of the phases, a transformer must be installed in the neutral conductor. Every CubicleBUS module is supplied with a factory-fitted 0.2 m cable. 4) A 24 V DC power supply unit is required. 3) Siemens LV 16 · 2009 4/17 4 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Accessories and spare parts Designation DT Order No. Price per PU PU PS* (UNIT, SET, M) PG Weight per PU approx. kg Retrofitting and spare parts for communication through PROFIBUS/MODBUS 1 2 3 4 5 6 7 8 9 Device CubicleBus COM15 PROFIBUS modules B 3WL9 111-1AT65-0AA0 1 1 unit 103 0.560 COM16 MODBUS modules C 3WL9 111-1AT15-0AA0 1 1 unit 103 0.180 Breaker status sensor (BSS) C 3WL9 111-1AT16-0AA0 1 1 unit 103 0.137 Measurement (voltage transformer required) function Plus1) B 3WL9 111-1AT03-0AA0 1 1 unit 103 0.310 PROFIBUS DP NSE-01025 3WL9 111-1AT65-0AA0 S45 S43 S42 S40 S44 S41 NSE01026 3WL9 111-1AT16-0AA0 All communication components, CubicleBUS modules and measurement functions are available for the ETU45B trip units. 4 Accessories for communications Preassembled cables for CubicleBUS modules SENTRON manuals for communication solutions2) 0.2 m long, for connection to SENTRON 3WL with COM15/COM16 B 3WL9 111-0BC04-0AA0 1 1 unit 103 0.020 1 m long, for connection to SENTRON 3WL with COM15/COM16 B 3WL9 111-0BC02-0AA0 1 1 unit 103 0.050 2 m long, for connection to SENTRON 3WL with COM15/COM16 B 3WL9 111-0BC03-0AA0 1 1 unit 103 0.060 2 m long, for connection to SENTRON 3WL without COM15/COM16 B 3WL9 111-0BC05-0AA0 1 1 unit 103 0.070 Detailed description of the communication functions for SENTRON circuit breakers with PROFIBUS DP. Installation, connection, start-up and description of Switch ES Power and BDA. GermanToken fee 20.–– € EnglishToken fee 20.–– € Free download from: http://www.siemens.com/lowvoltage/manuals Voltage 380 ... 690 V/100 V, class 0.5 transformers, 3-pole, for SENTRON 3WL with measurement function Plus A5E0151347-01 A5E0151353-01 B 3WL9 111-0BB68-0AA0 1 1 unit 103 2.600 Transformers for neutral conductor protection External transformers for N conductors (T5, see Technical Information "General Data", "Functions", "Measurement Method", page 4/39) Size I Size II Size III B B B 3WL9 111-0AA21-0AA0 3WL9 111-0AA22-0AA0 3WL9 111-0AA23-0AA0 1 1 unit 1 1 unit 1 1 unit 103 0.300 103 0.380 103 0.680 External transformers for N conductors with copper connection pieces (T5, see Technical Information 3WL9 111-0AA2.-0AA0 "General Data", "Functions", "Measurement Method", page 4/39) Size I Size II Size III B B B 3WL9 111-0AA31-0AA0 3WL9 111-0AA32-0AA0 3WL9 111-0AA33-0AA0 1 1 unit 1 1 unit 1 1 unit 103 1.600 103 4.260 103 8.500 X 3WL9 111-0AK32-0AA0 1 1 unit 103 0.280 N S E 0 _ 0 0 9 9 0 a N S E 0 _ 0 0 9 9 1 a 3WL9 111-0AA3.-0AA0 EMC filters EMC filters Common-mode interference suppressor filters (e.g. in ungrounded networks, caused by frequency converters) Insertion loss (asymmetric) in the range 40 kHz to 10 MHz > 40 dB 1) If retrofitted, a measuring accuracy of 3 % is achieved. 4/18 Siemens LV 16 · 2009 2) Manual for MODBUS communication solution available on request. * You can order this quantity or a multiple thereof. © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Accessories and spare parts Designation DT Order No. Price per PU PU PS* (UNIT, SET, M) PG Weight per PU approx. kg More accessories for electronic trip units N S E 0 _ 0 0 9 8 3 a E T U 2 5 B R a t in g P lu g T E S T Q U E R Y B 3WL9 111-0AT45-0AA0 1 1 unit 103 0.050 Automatic reset of the lockout devices B Spare part for option K01, see "-Z" + order code, page 4/11. 3WL9 111-0AK21-0AA0 1 1 unit 103 0.050 Remote reset solenoids1) For mechanical tripped indicator 24 V DC B 3WL9 111-0AK03-0AA0 1 1 unit 103 0.200 48 V DC B 3WL9 111-0AK04-0AA0 1 1 unit 103 0.200 Spare part for option K10 to K13, see "-Z" + order code, page 4/11. 120 V AC/ 125 V DC B 3WL9 111-0AK05-0AA0 1 1 unit 103 0.200 208-250 V AC/ 208-250 V DC B 3WL9 111-0AK06-0AA0 1 1 unit 103 0.200 B 3WL9 111-0AK30-0AA0 1 1 unit 103 0.150 D 3WL9 111-0AK31-0AA0 1 1 unit 103 0.020 Protective covers for Without safety lock B mechanical ON/OFF Made by CES B Consisting of 2 transparent covers each Made by IKON B 4) for sealing or for attaching padlocks , cover with 6.35 mm hole (for tool actuation), lock mount for safety lock for key operation 3WL9 111-0BA21-0AA0 3WL9 111-0BA22-0AA0 3WL9 111-0BA24-0AA0 1 1 unit 1 1 unit 1 1 unit 103 103 103 0.100 0.300 0.300 B 3WL9 111-0BA31-0AA0 1 1 unit 103 0.200 B B B 3WL9 111-0BA33-0AA0 3WL9 111-0BA34-0AA0 3WL9 111-0BA35-0AA0 1 1 1 1 unit 1 unit 1 unit 103 103 103 0.400 0.270 0.250 B B 3WL9 111-0BA36-0AA0 3WL9 111-0BA38-0AA0 1 1 1 unit 1 unit 103 103 0.200 0.200 B 3WL9 111-0BA41-0AA0 1 1 unit 103 0.360 B B B B B 3WL9 111-0BA51-0AA0 3WL9 111-0BA53-0AA0 3WL9 111-0BA57-0AA0 3WL9 111-0BA58-0AA0 3WL9 111-0BA50-0AA0 1 1 1 1 1 1 unit 1 unit 1 unit 1 unit 1 unit 103 103 103 103 103 0.300 0.300 0.300 0.300 0.227 B 3WL9 111-0BA71-0AA0 1 1 unit 103 0.080 B B B B B 3WL9 111-0BA73-0AA0 3WL9 111-0BA75-0AA0 3WL9 111-0BA76-0AA0 3WL9 111-0BA77-0AA0 3WL9 111-0BA80-0AA0 1 1 1 1 1 1 unit 1 unit 1 unit 1 unit 1 unit 103 103 103 103 103 0.300 0.200 0.300 0.300 0.400 B 3WL9 111-0BA43-0AA0 1 1 unit 103 0.360 Sealable covers C L E A R For ETU25B, ETU45B 3WL9 111-0AT45-0AA0 Retrofittable internal CubicleBUS wiring For ETU45B for connection to terminal X8 F 7 (without male connector2)) Retrofittable internal wiring for connection of the external N- and G-transformers to terminal X8 (without male connector) N S E 0 _ 0 0 9 9 9 a 3WL9 111-0AK0.-0AA0 Locking devices NSE00980 Locking devices against unauthorized closing, in the operator panel The disconnector unit ■ 3WL9 111-0BA22-0AA0 fulfills the requirements for main circuit breakers acc. to EN 60204 (VDE 0113) and UL 489 Spare part for option S01 to S09, see "-Z" + order code, page 4/13. Locking devices against unauthorized closing, for withdrawable circuit breakers ■ The disconnector unit fulfills the 3WL9 111-0BA31-0AA0 requirements for main circuit breakers acc. to EN 60204 (VDE 0113) and UL 489 consisting of lock in the cabinet door, active in connected position; function is retained when circuit breaker is replaced NSE00981 Assembly kit FORTRESS or CASTELL3) Made by Ronis Made by KIRKKey Made by Profalux Made by CES Made by IKON Assembly kit for padlocks4) Made by CES Made by IKON Made by KIRKKey Made by Ronis Made by Profalux Spare part for option R60, R61, R68, NSE00982 3WL9 111-0BA53-0AA0 see "-Z" + order code, page 4/13. Locking devices for operating mechanism handle with padlock4) Spare part for option S33, see "-Z" + order code, page 4/13. Locking devices against movement of the withdrawable circuit breakers Safety lock for mounting on the circuit breaker. Spare part for option S71, S75, S76, ■ see "-Z" + order code, page 4/13. Made by CES Made by IKON Made by Profalux Made by Ronis Made by KIRKKey NSE00984 Interlocking system Made by CES 3WL9 111-0BA71-0AA0 2 of the same keys for 3 switches, Locking device OFF position, Key-operated switch on operator panel. A maximum of 2 switches can be switched on. NSE00986 3WL9 111-0BA76-0AA0 1) Can only be used in conjunction with "automatic reset of lockout device", e.g. "–Z" + "K01", 3WL9 111-0AK21-0AA0 2) Required if communication is retrofitted. * You can order this quantity or a multiple thereof. 3) 4) Locks must be ordered from the manufacturer. Padlock not included in the scope of supply. ■ Start of delivery on request. Siemens LV 16 · 2009 4/19 4 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Accessories and spare parts Designation DT Order No. Price per PU PU PS* (UNIT, SET, M) PG Weight per PU approx. kg Locking devices To prevent movement of the withdrawable circuit breakers in disconnected positions, consisting of Bowden wire and lock in the cabinet door NSE00987 Made by CES Made by IKON Made by Profalux Made by Ronis B B B B 3WL9 111-0BA81-0AA0 3WL9 111-0BA83-0AA0 3WL9 111-0BA85-0AA0 3WL9 111-0BA86-0AA0 1 1 1 1 1 unit 1 unit 1 unit 1 unit 103 103 103 103 0.800 0.800 0.800 0.800 Fixed mounting B 3WL9 111-0BB12-0AA0 1 1 unit 103 0.600 B 3WL9 111-0BB13-0AA0 1 1 unit 103 0.150 Guide frames B 3WL9 111-0BB15-0AA0 1 1 unit 103 0.150 Fixed-mounted circuit breaker B 3WL9 111-0BB21-0AA0 1 1 unit 103 2.700 Module for withdrawable B circuit breaker with frame 3WL9 111-0BB24-0AA0 1 1 unit 103 1.130 B 3WL9 111-0BB22-0AA0 1 1 unit 103 1.100 Module for withdrawable B circuit breaker 3WL9 111-0BB23-0AA0 1 1 unit 103 0.150 B 3WL9 111-0BB30-0AA0 1 1 unit 103 0.100 B 3WL9 112-8AH47-0AA0 1 1 unit 103 0.160 B B B 3WL9 111-0BB45-0AA0 3WL9 111-0BB46-0AA0 3WL9 111-0BB47-0AA0 1 1 1 1 unit 1 unit 1 unit 103 103 103 0.150 0.220 0.360 3WL9 111-0BA83-0AA0 Spare part for option R81, R85, R86, see "-Z" + order code, page 4/13. To prevent opening of the cabinet door in ON position (can be defeated) Spare part for option S30, 3WL9 111-0BB12-0AA0 see "-Z" + order code, page 4/13. To prevent opening of the Guide frames Interlocking cabinet door (can be defeated) Spare part for option R30, see "-Z" + order code, page 4/13. To prevent movement with the cabinet door open Spare part for option R50, see "-Z" + order code, page 4/13. Interlocks 4 Mutual mechanical interlocking, with 2000 mm Bowden wire (one required for each circuit breaker) NSE00989 3WL9 111-0BB21-0AA0 Spare part for option S55, see "-Z" + order code, page 4/12. Spare part for option R55, see "-Z" + order code, page 4/12. When ordered separately Module for guide frame Spare part for option R56, see "-Z" + order code, page 4/12. Spare part for option R57, see "-Z" + order code, page 4/12. Adapter for size III Withdrawable circuit breaker Couplings on the circuit breaker (with ring) for mutual interlocking Can be used in all circuit breakers NSE0_01886 Bowden wires 3WL9 112-8HA47-0AA0 4/20 Siemens LV 16 · 2009 2000 mm 3000 mm 4500 mm * You can order this quantity or a multiple thereof. © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Accessories and spare parts Designation DT Order No. Price per PU PU PS* (UNIT, SET, M) PG Weight per PU approx. kg Test devices Manual testers for electronic trip units ETU25B and ETU45B B 3WL9 111-0AT32-0AA0 1 1 unit 103 1.100 C 3WL9 111-0AT44-0AA0 1 1 unit 103 8.210 3WL9 111-0BA14-0AA0 1 1 unit 103 0.520 For testing the electronic trip unit functions Function testers For testing the tripping characteristics for electronic trip unit ETU25B and ETU45B Capacitor storage devices Capacitor storage devices For shunt trip unit Rated control supply voltage/ rated operational voltage Storage time 5 min AC 50/60 Hz V V DC Rated control supply voltage must match the rated control supply voltage of the shunt trip unit 220 ... 240 220 ... 240 B Suitable also for 3VL circuit breakers. 4 * You can order this quantity or a multiple thereof. Siemens LV 16 · 2009 4/21 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Accessories and spare parts Designation DT Order No. Price per PU PU PS* (UNIT, SET, M) PG Weight per PU approx. kg Indicators, control elements B 3WL9 111-0AH01-0AA0 1 1 unit 103 0.020 B 3WL9 111-0AH02-0AA0 1 1 unit 103 0.020 B 3WL9 111-0AH14-0AA0 1 1 unit 103 0.080 B 3WL9 111-0AH07-0AA0 1 1 unit 103 0.100 B 3WL9 111-0AH08-0AA0 1 1 unit 103 0.030 Position indicator 1st block switches for guide frames (3 CO contacts) B 3WL9 111-0AH11-0AA0 1 1 unit 103 0.200 Spare part for option R15 B 3WL9 111-0AH12-0AA0 1 1 unit 103 0.400 Ready-to-close indicator switches 1 NO contact Spare part for option C22, see "-Z" + order code, page 4/10. Signal switches1)2) Spare part for option C26 and C27, see "-Z" + order code, page 4/10. N S E 0 _ 0 0 9 9 3 a 1st or 2nd auxiliary trip units 3WL9 111-0AH01-0AA0 Tripped signaling switches1)2) 1 CO N S E 0 _ 0 0 9 9 4 b Spare part for option K07, see "-Z" + order code, page 4/11. Operating cycles counters, mechanical3) Spare part for option C01, see "-Z" + order code, page 4/10. 3WL9 111-0AH02-0AA0 Stored energy status signaling switches1)2) 1 NO contact Spare part for option C20, see "-Z" + order code, page 4/10. 4 N S E 0 _ 0 0 9 9 5 a 3WL9 111-0AH07-0AA0 and R16, see "-Z" + 2nd block (6 CO contacts) order code, page 4/12. Electrical ON buttons1)4) (button+wiring)2), for operator panel. N S E 0 _ 0 0 9 9 6 a Possible only for circuit 3WL9 111-0AH12-0AA0 breakers with closing solenoid. With sealing cap B 3WL9 111-0AJ02-0AA0 1 1 unit 103 0.150 With CES assembly kit B 3WL9 111-0AJ03-0AA0 1 1 unit 103 0.140 With BKS assembly kit B 3WL9 111-0AJ04-0AA0 1 1 unit 103 0.140 With IKON assembly kit B 3WL9 111-0AJ05-0AA0 1 1 unit 103 0.140 B 3WL9 111-0AJ06-0AA0 1 1 unit 103 0.100 B 3WL9 111-0BA72-0AA0 1 1 unit 103 0.080 Spare part for option C11 and C12, see "-Z" + order code, page 4/10. N S E 0 0 0 9 9 7 a 3WL9 111-0AJ0.-0AA0 Motor shutdown switches 5) (mounting on operator panel) Spare part for option S25, see "-Z" + order code, page 4/10. EMERGENCY-STOP pushbuttons Mushroom pushbutton NSE00985 instead of the mechanical 3WL9 111-0BA72-0AA0 OFF pushbutton Spare part for option S24, see "-Z" + order code, page 4/10. 1) 2) Not possible with communications connection option, order code "F02" or "F12". X7 manual connector required for circuit breakers or guide frames. If this is not already available, please order additionally (see pages 4/15 and 4/23). 4/22 Siemens LV 16 · 2009 3) Only in conjunction with motorized operating mechanism. 4) Not possible with motor shutdown switch. 5) Not possible with electrical ON button. * You can order this quantity or a multiple thereof. © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Accessories and spare parts Designation DT Order No. Price per PU PU PS* (UNIT, SET, M) PG Weight per PU approx. kg Auxiliary conductor connections Male connectors for circuit breakers $ 3WL9 111-0AB01-0AA0 1 1 unit 103 0.100 Extensions for the 1000 V male connector versions B (male connector must be ordered separately) 3WL9 111-0AB02-0AA0 1 1 unit 103 0.150 B 3WL9 111-0AB10-0AA0 1 1 unit 103 1.000 Auxiliary supply connectors Screw connection B for circuit breakers or (SIGUT) guide frames % Screwless connection B method (tension spring) 3WL9 111-0AB03-0AA0 1 1 unit 103 0.070 3WL9 111-0AB04-0AA0 1 1 unit 103 0.070 3WL9 111-0AB04-0AA0 Coding kits for fixed-mounted version (X5 to X8) & B 3WL9 111-0AB07-0AA0 1 1 unit 103 0.020 B 3WL9 111-0AB08-0AA0 1 1 unit 103 0.100 B 3WL9 111-0AB18-0AA0 1 1 unit 103 0.120 B 3WL9 111-0AB12-0AA0 1 1 unit 103 0.030 NSE00978 B 3WL9 111-0AB01-0AA0 N S E 0 _ 0 1 2 6 8 Male connectors for extension for 1000 V NSE00974 N S E 0 _ 0 1 2 6 9 3WL9 111-0AB03-0AA0 3WL9 111-0AB07-0AA0 Sliding contact modules for guide frames ( 7 a 9 7 0 0 0 _ E N S NSE0_01586 3WL9 111-0AB08-0AA0 One-part sliding contact modules for 3WL9 111-0AB18-0AA0 guide frames Screw connection (SIGUT) ) Blanking blocks for circuit breakers For a complete auxiliary current connection you must order: Fixed-mounted version: Withdrawable version: $+%+& $+(+% or $+) * You can order this quantity or a multiple thereof. Siemens LV 16 · 2009 4/23 4 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Accessories and spare parts Designation DT Order No. Price per PU PU PS* (UNIT, SET, M) PG Weight per PU approx. kg Auxiliary trip units Closing solenoids/shunt trip units 24 V DC 3WL9 111-0AD06-0AA0 B 3WL9 111-0AD01-0AA0 1 1 unit 103 0.700 30 V DC B 3WL9 111-0AD02-0AA0 1 1 unit 103 0.700 48 V DC B 3WL9 111-0AD03-0AA0 1 1 unit 103 0.700 60 V DC B 3WL9 111-0AD04-0AA0 1 1 unit 103 0.700 120 V DC/125 V AC B 3WL9 111-0AD05-0AA0 1 1 unit 103 0.700 220 V DC/230 V AC B 3WL9 111-0AD06-0AA0 1 1 unit 103 0.700 24 V DC 100 % ON period 5 % ON period B 3WL9 111-0AD11-0AA0 1 1 unit 103 0.700 B 3WL9 111-0AD12-0AA0 1 1 unit 103 0.700 110 ... 125 V DC/110 ... 127 V AC B 3WL9 111-0AD13-0AA0 1 1 unit 103 0.700 240 V DC/240 V AC B 3WL9 111-0AD14-0AA0 1 1 unit 103 1.800 48 V DC NSE01001 Undervoltage releases 3WL9 111-0AE0.-0AA0 4 NSE01002 3WL9 111-0AE1.-0AA0 Instantaneous 24 V DC B 3WL9 111-0AE01-0AA0 1 1 unit 103 0.730 30 V DC B 3WL9 111-0AE02-0AA0 1 1 unit 103 0.730 48 V DC B 3WL9 111-0AE03-0AA0 1 1 unit 103 0.730 60 V DC B 3WL9 111-0AE07-0AA0 1 1 unit 103 0.730 120 V DC/125 V AC B 3WL9 111-0AE04-0AA0 1 1 unit 103 0.730 240 V DC/250 V AC B 3WL9 111-0AE05-0AA0 1 1 unit 103 0.730 Delayed B 3WL9 111-0AE11-0AA0 1 1 unit 103 0.740 120 V DC/125 V AC 48 V DC B 3WL9 111-0AE12-0AA0 1 1 unit 103 0.740 240 V DC/250 V AC B 3WL9 111-0AE13-0AA0 1 1 unit 103 0.740 24 ... 30 V DC B 3WL9 111-0AF01-0AA0 1 1 unit 103 1.510 48 ... 60 V DC B 3WL9 111-0AF02-0AA0 1 1 unit 103 1.510 120 V DC/125 V AC B 3WL9 111-0AF03-0AA0 1 1 unit 103 1.510 240 V DC/240 V AC B 3WL9 111-0AF04-0AA0 1 1 unit 103 1.510 Operating mechanisms Motorized operating mechanisms1) I N S E 0 _ 0 1 0 0 3 a 3WL9 111-0AF0.-0AA0 Auxiliary contacts Auxiliary switch blocks 2 NO + 2 NC B 3WL9 111-0AG01-0AA0 1 1 unit 103 0.180 2 NO B 3WL9 111-0AG02-0AA0 1 1 unit 103 0.080 1 NO + 1 NC B 3WL9 111-0AG03-0AA0 1 1 unit 103 0.070 3WL9 111-0AG03-0AA0 1) X7 manual connector required for circuit breakers or guide frames. If this is not already available, please order additionally (see pages 4/15 and 4/23). 4/24 Siemens LV 16 · 2009 * You can order this quantity or a multiple thereof. © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Accessories and spare parts Designation DT Order No. Price per PU PU PS* (UNIT, SET, M) PG Weight per PU approx. kg Door sealing frames, covers, shutters B 3WL9 111-0AP01-0AA0 1 1 unit 103 0.360 B 3WL9 111-0AP03-0AA0 1 1 unit 103 1.690 Size I B 3WL9 111-0AP04-0AA0 1 1 unit 103 0.500 Size II B 3WL9 111-0AP06-0AA0 1 1 unit 103 0.630 Size III B 3WL9 111-0AP07-0AA0 1 1 unit 103 0.860 Withdrawable part coding By customer, for 36 coding variants B 3WL9 111-0AR12-0AA0 1 1 unit 103 0.400 Support brackets For mounting fixed-mounted circuit breakers on vertical plane, only for sizes I and II (1 set = 2 units) B 3WL9 111-0BB50-0AA0 1 1 unit 103 7.000 Door sealing frames Spare part for option T40, see "-Z" + order code, page 4/10. Protective covers, IP55 Cannot be used in conjunction with door sealing frames, cover removable and can be opened on both sides NSE0_01028a 3WL9 111-0AP02-0AA0 Shutters Spare part for option R21, see "-Z" + order code, page 4/12. 3-pole 3WL9 111-0AP0.-0AA0 Withdrawable part coding NSE01009 3WL9 111-0AR12-0AA0 NSE-01022 Support brackets 3WL9 111-0BB50-0AA0 * You can order this quantity or a multiple thereof. Siemens LV 16 · 2009 4/25 4 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Accessories and spare parts Designation DT Order No. Price per PU PU PS* (UNIT, SET, M) PG Weight per PU approx. kg Main conductor connections, fixed mounting 3WL9 111-0AL06-0AA0 Specified for each connection Front-accessible main circuit connections, single hole at top Size I, 1000 A Size I, 1600 A B B 3WL9 111-0AL01-0AA0 3WL9 111-0AL02-0AA0 1 1 1 unit 1 unit 103 103 1.100 1.600 Size II, up to 2000 A Size II, up to 2500 A Size II, up to 3000 A B B B 3WL9 111-0AL03-0AA0 3WL9 111-0AL04-0AA0 3WL9 111-0AL05-0AA0 1 1 1 1 unit 1 unit 1 unit 103 103 103 2.000 3.600 3.500 NSE-01010 Size III, up to 4000 A B 3WL9 111-0AL06-0AA0 1 1 unit 103 6.100 3WL9 111-0AL56-0AA0 Front-accessible Size I, 1000 A Size I, 1600 A B B 3WL9 111-0AL51-0AA0 3WL9 111-0AL52-0AA0 1 1 1 unit 1 unit 103 103 1.000 1.300 B B 3WL9 111-0AL53-0AA0 3WL9 111-0AL54-0AA0 3WL9 111-0AL55-0AA0 1 1 1 1 unit 1 unit 1 unit 103 103 103 1.800 3.100 3.000 main circuit connections, Size II, up to 2000 A single hole at bottom Size II, up to 2500 A Size II, up to 3000 A 3WL9 111-0AL14-0AA0 4 NSE-01011 3WL9 111-0AL64-0AA0 Front-accessible main circuit connections, acc. to DIN 43673, double hole at top Size III, up to 4000 A B B 3WL9 111-0AL56-0AA0 1 1 unit 103 5.200 Size I, 1000 A Size I, 1600 A B B 3WL9 111-0AL07-0AA0 3WL9 111-0AL08-0AA0 1 1 1 unit 1 unit 103 103 1.400 2.000 Size II, up to 2000 A Size II, up to 2500 A Size II, up to 3000 A B B B 3WL9 111-0AL11-0AA0 3WL9 111-0AL12-0AA0 3WL9 111-0AL13-0AA0 1 1 1 1 unit 1 unit 1 unit 103 103 103 2.400 4.500 4.400 Size III, up to 4000 A B 3WL9 111-0AL14-0AA0 1 1 unit 103 7.800 Front-accessible main circuit connections, acc. to DIN 43673, double hole at bottom Size I, 1000 A Size I, 1600 A B B 3WL9 111-0AL57-0AA0 3WL9 111-0AL58-0AA0 1 1 1 unit 1 unit 103 103 1.300 1.700 Size II, up to 2000 A Size II, up to 2500 A Size II, up to 3000 A B B B 3WL9 111-0AL61-0AA0 3WL9 111-0AL62-0AA0 3WL9 111-0AL63-0AA0 1 1 1 1 unit 1 unit 1 unit 103 103 103 2.000 3.700 3.600 Size III, up to 4000 A B 3WL9 111-0AL64-0AA0 1 1 unit 103 6.400 Rear vertical main circuit connections Size I1), up to 1600 A B 3WL9 111-0AM01-0AA0 1 1 unit 103 0.500 Size II2), up to 3000 A B 3WL9 111-0AM02-0AA0 1 1 unit 103 2.200 Size III, up to 5000 A B 3WL9 111-0AM03-0AA0 1 1 unit 103 5.000 NSE-01012 3WL9 111-0AM03-0AA0 1) In the case of vertical connection size I, up to 1000 A one 3WL9 111–0AM01-0AA0 vertical connection is required, up to 1600 A two 3WL9 111-0AM01-0AA0 vertical connections are required. 2) In the case of vertical connection size II, up to 2500 A one 3WL9 111–0AM02-0AA0 vertical connection is required, up to 3200 A two 3WL9 111-0AM02-0AA0 vertical connections are required. 4/26 Siemens LV 16 · 2009 * You can order this quantity or a multiple thereof. © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Accessories and spare parts Designation DT Order No. Price per PU PU PS* (UNIT, SET, M) PG Weight per PU approx. kg Main conductor connections, withdrawable versions Specified for each connection NSE-01013 3WL9 111-0AN06-0AA0 Front-accessible main circuit Size I, 1000 A connections, Size I, 1600 A single hole at top or Size II, up to 2000 A at bottom1) Size II, up to 2500 A Size II, up to 3000 A Front-accessible main circuit connections, acc. to DIN 43673, double hole at top or at bottom1) NSE-01014 3WL9 111-0AN14-0AA0 B B 3WL9 111-0AN01-0AA0 3WL9 111-0AN02-0AA0 1 1 1 unit 1 unit 103 103 1.000 1.300 B B B 3WL9 111-0AN03-0AA0 3WL9 111-0AN04-0AA0 3WL9 111-0AN05-0AA0 1 1 1 1 unit 1 unit 1 unit 103 103 103 1.800 3.100 3.000 Size III, up to 4000 A B 3WL9 111-0AN06-0AA0 1 1 unit 103 5.200 Size I, 1000 A Size I, 1600 A B B 3WL9 111-0AN07-0AA0 3WL9 111-0AN08-0AA0 1 1 1 unit 1 unit 103 103 1.300 1.700 Size II, up to 2000 A Size II, up to 2500 A Size II, up to 3000 A B B B 3WL9 111-0AN11-0AA0 3WL9 111-0AN12-0AA0 3WL9 111-0AN13-0AA0 1 1 1 1 unit 1 unit 1 unit 103 103 103 2.000 3.700 3.600 Size III, up to 4000 A B 3WL9 111-0AN14-0AA0 1 1 unit 103 6.400 Supports for front and DIN connecting bars 3-pole for 3 bars Size I B 3WL9 111-0AN41-0AA0 1 1 unit 103 0.700 Size II B 3WL9 111-0AN42-0AA0 1 1 unit 103 1.350 Size III B 3WL9 111-0AN43-0AA0 1 1 unit 103 2.420 Size I, 1000 A Size I, 1600 A B B 3WL9 111-0AN15-0AA0 3WL9 111-0AN16-0AA0 1 1 1 unit 1 unit 103 103 0.660 0.870 Size II, up to 2000 A Size II, up to 2500 A Size II, up to 3000 A B B B 3WL9 111-0AN17-0AA0 3WL9 111-0AN18-0AA0 3WL9 111-0AN21-0AA0 1 1 1 1 unit 1 unit 1 unit 103 103 103 1.150 1.490 2.580 Size III, up to 5000 A B 3WL9 111-0AN22-0AA0 1 1 unit 103 6.380 Size I, 1000 A Size I, 1600 A B B 3WL9 111-0AN32-0AA0 3WL9 111-0AN33-0AA0 1 1 1 unit 1 unit 103 103 0.630 0.770 Size II, up to 2000 A Size II, up to 2500 A Size II, up to 3000 A B B B 3WL9 111-0AN34-0AA0 3WL9 111-0AN35-0AA0 3WL9 111-0AN36-0AA0 1 1 1 1 unit 1 unit 1 unit 103 103 103 1.020 1.240 2.170 Size III, up to 5000 A B 3WL9 111-0AN37-0AA0 1 1 unit 103 3.860 Size I, 1000 A Size I, 1600 A B B 3WL9 111-0AN24-0AA0 3WL9 111-0AN25-0AA0 1 1 1 unit 1 unit 103 103 0.610 0.640 NSE-01015 Size II, up to 2000 A Size II, up to 2500 A Size II, up to 3000 A B B B 3WL9 111-0AN26-0AA0 3WL9 111-0AN27-0AA0 3WL9 111-0AN28-0AA0 1 1 1 1 unit 1 unit 1 unit 103 103 103 0.980 1.020 1.310 3WL9 111-0AN22-0AA0 Size III, up to 4000 A B 3WL9 111-0AN31-0AA0 1 1 unit 103 2.370 Rear vertical main circuit connections Rear horizontal circuit connections NSE-01017 Connecting flanges NSE-01016 3WL9 111-0AN41-0AA0 3WL9 111-0AN24-0AA0 Conversion sets For converting fixed-mounted circuit breakers into withdrawable circuit breakers Guide frames and sliding contact modules must be ordered separately. 1) Number of poles Size 3-pole I B 3WL9 111-0BC11-0AA0 1 1 unit 103 5.100 II B 3WL9 111-0BC12-0AA0 1 1 unit 103 5.900 III B 3WL9 111-0BC13-0AA0 1 1 unit 103 8.100 Supports are required when using front-accessible main circuit connections (withdrawable circuit breakers). * You can order this quantity or a multiple thereof. Siemens LV 16 · 2009 4/27 4 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Accessories and spare parts ■ Options Structure of the Order No. 3WL5 Ô Ô Ò – Ö á â Õ Ó – Ó á Ü Ô Example 4 Ô 5th position: Size Size II 6th and 7th position: Max. rated circuit breaker current In max In max = 2000 A 8th position: Switching capacity class High breaking capacity "H": 100 kA 9th position: Electronic trip units ETU45B with pixel graphics display 10th position: Electronic trip unit supplement ... with ground-fault protection 11th position: Number of poles 3-pole 12th position: Installation type Fixed mounting, main circuit connections on rear, vertical They are used as an unambiguous means of communication for various purposes: ÔÒ • Offer processing Selection and configuration • Order processing Ordering Order confirmation Handling warehouse Products Order processing at the supply bases Delivery and shipment • Reporting and planning • Service and warranty Ö á â Õ 13th position: Operating mechanism Manual operating mechanism with mechanical closing 14th position: 1st auxiliary switch Shunt trip units AC 50/60 Hz 110 V 15th position: 2nd auxiliary switch Without 2nd auxiliary trip unit 16th position: Auxiliary switches An important prerequisite for computerbased order processing is that order numbers must be structured according to standardized criteria. The standardized structure ensures that only one Order No. has to be administered for one device. Ó This saves time and effort during planning, configuring, ordering and stock keeping, and consequently above all it saves costs. Ó The example opposite explains the various positions within an Order No. á Ü Ô 2 NO + 2 NC Accessories: with first order (components are already mounted) Example 3WL5 Ô Ô Ò – Ö á â Õ Ó – Ó á Ü Õ – õ áÒÔ Additional accessory components can be ordered ready-mounted. "–Z" with order code Communications connection "Standard" + Breaker Status Sensor (BSS) + communication module COM15 for connection to PROFIBUS DP õ áÒÔ These supplements are identified by "-Z". Even with additional components, one Order No. is sufficient. Accessories: for retrofitting (components for subsequent fitting) Example 3WL9 Ó Ó Ó – Ò Á Ü Ô Ó – Ò Ü Ü Ò Additional accessories which are not intended to be ready-mounted in the factory, such as spare parts for storage, can also be ordered separately from the circuit breaker. Protective cover for mechanical ON/OFF without lock Accessories for retrofitting are identified by the Order No. stem 3WL9. Documentation Manual Communication German English Free download of documentation from http://www.siemens.com/lowvoltage/manuals 4/28 Siemens LV 16 · 2009 Order No. Order No. A5E0151347-01 A5E0151353-01 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A General data ■ Design Max. circuit breaker current n max (A) Size III Switch-off capacity cu at 480 V AC (kA) Dimensions Fixed mounting Withdrawable 1) 3-/4-pole 1) 3-/4-pole 704 / 914 704 / 914 Width 434 / 434 460 / 460 Height 291 / 291 385 / 385 Depth 460 / 590 460 / 590 Width 434 / 434 460 / 460 Height 291 / 291 385 / 385 Depth 320 / 410 320 / 410 Width 434 / 434 460 / 460 Height 291 / 291 385 / 385 Depth 5000 H 4000 100 3000 Size II 2500 H 2000 100 1600 1000 4 Size I 1600 S 1000 65 The dimension for the depth of the circuit breakers is specified from the circuit breaker rear panel to the inside surface of the closed cabinet door. 4-pole version on request NSE0_01903a 1) Overview of SENTRON 3WL5 circuit breakers/non-automatic air circuit breakers Versions • Rated currents: 630 A to 5000 A • 3 sizes for different rated current ranges (see illustration "Overview of SENTRON 3WL5 Circuit Breakers/Non-Automatic Air Circuit Breakers") • 3-pole version, 4-pole version on request • Rated operational voltage up to 600 V AC • 2 different switching capacity classes in the range from 65 kA to 100 kA at 480 V AC The SENTRON 3WL5 circuit breakers are supplied complete with operating mechanism (manual operating mechanism with mechanical closing), electronic trip unit and auxiliary switches (2 NO contacts + 2 NC contacts in the standard version), and can be equipped with auxiliary trip units. Installation types Fixed-mounted or withdrawable version Ambient temperatures The SENTRON 3WL5 circuit breakers are climate-proof according to IEC 60068-2-30. They are intended for use in enclosed areas where no severe operating conditions (e.g. dust, corrosive vapors, damaging gases) are present. When installed in dusty and damp areas, suitable enclosures must be provided. Coordinated dimensions The dimensions of SENTRON 3WL5 circuit breakers only differ in terms of the width of the device which depends on the number of poles and the size. Due to the nature of the design, the dimensions of devices with a withdrawable version are determined by the dimensions of the guide frames, which are slightly larger. Non-automatic air circuit breakers One special version of circuit breaker is utilized as a non-automatic air circuit breaker. The non-automatic air circuit breakers are designed without an electronic trip unit system and do not perform any protection functions for the system. One potential application is the use as a bus coupler in systems with parallel feed-ins. The versions and features can be selected according to those of the circuit breakers. Operating mechanisms The circuit breakers are available with various optional operating mechanisms: • Manual operating mechanism with mechanical closing (standard design) • Manual operating mechanism with mechanical and electrical closing • Motorized operating mechanism with mechanical and electrical closing. The operating mechanisms with electrical closing can be used for synchronization tasks. Siemens LV 16 · 2009 4/29 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A General data Safety and reliability Fixed-mounted circuit breaker Front connection with single hole or double hole Horizontal connection N S E 0 _ 0 0 9 7 9 a N S E 0 _ 0 0 9 6 9 b N S E 0 _ 0 0 9 6 7 b N S E 0 _ 0 0 9 6 8 b To protect the circuit breakers and plant against unauthorized switching as well as the maintenance and operator personnel, the system contains many locking devices. Others can be retrofitted. Vertical connection N S E 0 _ 0 0 9 6 7 b N S E 0 _ 0 0 9 7 2 b N S E 0 _ 0 0 9 7 3 b Withdrawable circuit breaker, withdrawable guide frame Vertical connection Horizontal connection Flange connection Standard version Main circuit connections – connection types Main circuit connections All circuit breakers are equipped with horizontal main circuit connections on the rear for up to 5000 A as standard (horizontal connection to busbars). Connection using screw connection system (SIGUT) (standard) N S E 0 _ 0 0 9 7 6 b The following options are available, with all combinations of top and bottom connections possible: • Accessible from the front, single hole (for vertically installed busbars, only for fixed mounting) • Accessible from the front, double hole (holes according to DIN 43673) (for vertically installed busbars, only for fixed mounting) • At the rear, vertical (for vertically installed busbars) • Connecting flange (for direct connection to guide frame up to 4000 A). N S E 0 _ 0 0 9 7 5 b 4 Screwless connection method (tension springs) (optional) Connection options for auxiliary circuit connections Auxiliary circuit connections The type of connection for the auxiliary switches depends on the type of installation: • Withdrawable version: The internal auxiliary switches are connected to the male connector on the switch side. When fully inserted, the connector makes a connection with the sliding contact module (see the graphic "Guide Frame" in "Design") in the guide frame. Various adapters can then be used to complete the wiring (see the graphic "Connection options for auxiliary circuit connections"). • Fixed mounting: In this case the auxiliary supply connectors are engaged directly onto the circuit breaker. The connectors are equipped with coding pins that prevent them being mistakenly interchanged. Operator panel The operator panel is designed to protrude from a cut-out in the door providing access to all control elements and displays with the control cabinet door closed. The operator panels for all circuit breakers (fixed-mounted/ withdrawable versions, 3-/4-pole) are identical. The operator panel ensures degree of protection IP41. 4/30 Siemens LV 16 · 2009 Other safety features include: • Infeed from above or below, as required • Locking of the guide frame with the circuit breaker removed, as standard • Locking of the withdrawable circuit breaker against movement, as standard • High degree of protection with cover (enclosure rating) • Mechanical closing lockout after overload or short-circuit tripping as standard • The circuit breaker is always equipped with the required number of auxiliary supply connectors SENTRON 3WL5 circuit breakers are equipped with the following features as standard: • Mechanical ON and OFF pushbutton • Manual operating mechanism with mechanical closing • Switch position indicator • Ready-to-close indicator • Memory status indicator • Auxiliary switches 2 NO + 2 NC • Rear horizontal main circuit connections for fixed-mounted and withdrawable versions up to 5000 A • For 4-pole circuit breakers, the fourth pole (N) is installed on the left and is 100 % loadable with the rated current • Contact erosion indicator for the main contacts • Auxiliary circuit plug-in system with SIGUT screw terminals. Delivery inclusive of all auxiliary circuit connectors to internal features including coding device for the prevention of incorrect installation of auxiliary supply connectors for fixed-mounted circuit breakers • Mechanical tripped indicator for electronic trip unit system • Mechanical closing lockout after tripping operation • Operator panel cannot be taken off with the circuit breaker in the ON position Additional features of the withdrawable version: • Main contacts: Laminated receptacles in the guide frame, penetration blades on the withdrawable circuit breaker • Position indicator in the operator panel of the withdrawable circuit breaker • Captive manual crank handle for moving the withdrawable circuit breaker • Guide frame with guide rails for easy moving of the withdrawable circuit breaker • The withdrawable circuit breaker can be locked to prevent it being pushed out of position • The withdrawable circuit breaker cannot be moved when it is in the ON position • Coding of the rated current between the guide frame and the withdrawable circuit breaker. Standards SENTRON 3WL5 circuit breakers comply with: • UL 489 • IEC 60947-2 • DIN VDE 0660 Part 101 • Climate-proof according to IEC 60068-2-30. © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A General data Auxiliary trip units Indicators, signals and control elements Up to two auxiliary trip units can be installed at the same time. The following are available: Motor shutdown switch 1 shunt trip unit or 1 undervoltage release or 2 shunt trip units or 1 shunt trip unit + 1 undervoltage release. Signal switch for auxiliary trip units One signaling contact is used for each auxiliary trip unit to determine the switch positions of the auxiliary trip units. Shunt trip unit When the operational voltage is connected to the shunt trip unit, the circuit breaker is opened immediately. The shunt trip unit is available in the versions 5 % ON period for overexcitation and 100 % ON period for permanent excitation. This means that it is also possible to block the circuit breaker against being jogged into closing. An energy storage device for shunt trip units allows the circuit breaker to be opened even if the control voltage is no longer available. Undervoltage release The undervoltage release causes the circuit breaker to be opened if the operational voltage falls below a certain value or is not applied. The circuit breaker cannot be closed manually or by means of an electrical ON command if the undervoltage release is not connected to the operational voltage. The undervoltage release has no delay as standard. A delay can be set by the customer in the range between td < 80 ms and td < 200 ms. In addition, an undervoltage release with a delay in the range from 0.2 to 3.2 s is available. Closing solenoid The closing solenoid is used to close the circuit breaker electrically by means of a local electrical ON command or by a remote unit. Motorized operating mechanism Control switch for switching off the motorized operating mechanism (automatic loading). Operating cycles counter The motorized operating mechanism can be supplied with a 5-digit operating cycles counter. The display is incremented by "1" as soon as the spring energy store is fully loaded. Resetting the manual tripped signal When the circuit breaker has tripped, this is indicated by the protruding red mechanical tripped indicator on the ETU. When the mechanical tripped indicator is activated, the tripping solenoid and tripped signal are reset. If this display is to be reset remotely, the reset button can be equipped with a reset solenoid. This option allows the circuit breaker to be reset both manually and electrically. Automatic resetting of closing lockout When the ETU is activated, reclosing of the circuit breaker is prevented until the trip unit is either electrically or manually reset. If the "Automatic resetting of closing lockout" option is used, the pre-tensioned circuit breaker is ready to close immediately after tripping. Resetting the manual tripped indicator is not included in this option. Tripped signal switch If the circuit breaker has tripped due to an overload, short-circuit, ground fault or extended protection function, the tripped signal switch can indicate this. This signal switch is available as an option. If the circuit breaker is used for communication, this option is supplied as standard. Ready-to-close indicator switches The SENTRON 3WL5 circuit breakers are equipped with an optical ready-to-close indicator as standard. In addition, the ready-toclose status can be transmitted by means of a signal switch as an option. If the switch is used for communication, the signal switch is supplied as standard. The operating mechanism is used to load the spring energy store automatically. The operating mechanism is activated if the spring energy store has been unloaded and the control voltage is available. It is switched off automatically after loading. This does not affect manual operation of the stored-energy feature. Siemens LV 16 · 2009 4/31 4 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A General data Circuit breakers (28) (1) (2) (27) (26) (3) (4) (25) (5) (24) (1) Arc chutes (2) Carrying handle (3) Labeling plates (4) Motor shutdown switch (option) or "Electrical ON" (option) (5) Name plate for UL and IEC circuit breaker (6) Memory status indicator (7) "Mechanical ON" button (8) Rated current indication (9) Positioning pictogram (10) Operating cycles counter (option) (6) (11) Hand-operated lever (23) (12) Crank handle (7) (22) (13) Withdrawable unit drive shaft (14) Equipment plate (21) (15) Ground terminal (20) (8) (16) Position indicator (9) (17) Table for ground-fault protection (18) Safety lock for crank handle (option) (19) (19) Mechanical unlocking of crank handle (option) (10) (11) (20) Electronic trip units (18) 4 (21) Rated current modules (17) (16) (12) (22) "Mechanical OFF" button or "EMERGENCYSTOP" mushroom pushbutton (option) (13) (23) Ready-to-close indicator (24) Switch position indicator (14) (15) (25) Tripped indicator (reset button) (26) "Secure OFF" locking device (option) NSE0_01904 (27) Operator panel (28) Male connector for auxiliary circuit connections Guide frames (1 ) (2 ) (3 ) (1 8 ) (1) Arc chute cover (option) (2) Blow-out openings (3) Opening for crane hook (4) Shutter (option) (5) Locking device (shutter) (option) (6) Type plate for guide frame (7) Isolating contacts (8) Ground terminal Ø 14 mm (9) Locking device for racking rail (10) Locking device against movement when control cabinet door is open (option) (4 ) (1 7 ) (5 ) (6 ) (1 6 ) (7 ) (1 5 ) (12) Racking rail (13) Factory-set rated current coding (14) Sliding contact for breaker grounding (option) (15) Equipment-dependent coding (option) (16) Shutter actuator (optional) (17) Position indicator switch (optional) (1 4 ) (8 ) (1 3 ) (1 2 ) (9 ) (1 1 ) (1 0 ) 4/32 (11) Door interlocking for guide frame (option) N S E 0 _ 0 0 9 6 6 b Siemens LV 16 · 2009 (18) Sliding contact module for auxiliary conductors (number depends on equipment) © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A General data Locking devices Sealing devices Locking device in OFF position Sealing cap for "Electrical ON" button This function prevents closing of the circuit breaker and complies to the specifications for main switches to EN 60204 (VDE 0113) and UL 489 – disconnector unit. This lockout only affects this circuit breaker. The "Electrical ON button" is equipped with a sealing cap as standard. If the circuit breaker is replaced, closing is no longer prevented unless the new circuit breaker is also protected against unauthorized closing. The locking set contains covering caps which can be sealed. To activate the locking device, the circuit breaker must be opened. The locking device is disabled when the circuit breaker is closed. The lock is only activated when the key is removed. The safety key can be removed only in the "OFF" position. Sealing cap for "Mechanical ON" and "OFF" button Sealing device for electronic trip units The transparent cover can be sealed. The parameter setting sections are covered to prevent unauthorized access. Openings allow access to the query and test button. Locking devices Locking device for "Electrical ON" (see graphic "Circuit breakers") Locking device against movement for withdrawable circuit breakers when the control cabinet door is open This prevents unauthorized electrical closing from the operator panel. Mechanical closing and remote closing remain possible. The lock is only activated when the key is removed. The crank handle is blocked when the control cabinet door is open and cannot be removed. The withdrawable circuit breaker cannot be moved. The lock only affects the inserted crank handle. Locking device for "Mechanical ON" (see graphic "Circuit breakers") This prevents unauthorized mechanical closing. The mechanical ON button can only be activated if the key is inserted (key operation). Closing with the "Electrical ON" button and remote closing remain possible. The lock is only activated when the key is removed. "Secure OFF" circuit breaker-independent locking device against unauthorized closing This special switch-independent function for withdrawable circuit breakers prevents closing and fulfills the specifications for main switches to EN 60204 (VDE 0113) and UL 489 – disconnector unit. Unauthorized closing remains impossible even after the circuit breaker has been exchanged. To activate the lock, the circuit breaker must be opened. The locking device is disabled when the circuit breaker is closed. The lock is only activated when the key is removed. The safety key can be removed only in the "OFF" position. Locking device for crank handle Prevents removal of the crank. The circuit breaker is protected against movement. The lock is only activated when the key is removed. Locking of the control cabinet door The control cabinet door cannot be opened if • The fixed-mounted circuit breaker is closed (the blocking signal is transmitted via the Bowden wire) or • The withdrawable circuit breaker is in the connected position. Blocking mechanism using "Mechanical ON" and "OFF" buttons The "Mechanical ON" and "OFF" buttons are covered with a cap which only allows actuation with a tool. These covering caps are part of the locking set. Optional equipment for guide frames Shutters The sealing strips of the shutter seal the laminated contacts of the guide frame when the withdrawable circuit breaker is removed and therefore implement touch protection. The sealing strips can be manually opened using the strip levers. The position of the sealing strips can be locked in various positions using padlocks for securing against tampering. Locking device for "Mechanical OFF" Prevents unauthorized mechanical opening from the operator panel. The "Mechanical OFF pushbutton" can only be activated if the key is inserted (key operation). Remote opening remains possible. The lock is only activated when the key is removed. Locking device for hand-operated lever The hand-operated lever can be locked with a padlock. The spring energy store cannot be loaded manually. Locking device against resetting the tripped indicator A lockable cover prevents manual resetting of the tripped indicator after overcurrent tripping. This locking device is supplied together with the transparent cover for electronic trip units. Siemens LV 16 · 2009 4/33 4 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A General data Rated current coding unit between circuit breaker and guide frame Equipment-dependent coding Withdrawable circuit breakers and guide frames are equipped with a rated current coding unit as standard. Withdrawable circuit breakers and guide frames can be retrofitted with an equipment-dependent coding unit. This ensures that only circuit breakers whose penetration blades are suited to the laminated contacts of the guide frame can be inserted into a guide frame (see diagram below). This allows different designs of circuit breakers and guide frames to be uniquely assigned. If the circuit breaker and guide frame have been assigned different codes, the circuit breaker cannot be inserted. N S E 0 _ 0 1 0 3 1 a 36 different coding options can be selected. N S E 0 _ 0 1 0 3 2 a Position indicator switches for guide frame (1 ) The guide frame can be equipped with position indicator switches. These can be used to determine the position of the circuit breaker in the guide frame. Two versions are available: (4 ) Option 1 Connected position 1 changeover contact Test position 1 changeover contact Disconnected position 1 changeover contact (2 ) (5 ) (3 ) (1) Guide frame, interior of l/h side; interior of r/h side similar Option 2 Connected position 3 changeover contacts Test position 2 changeover contacts Disconnected position 1 changeover contact (2) Coding pin on racking rail in guide frame (3) Racking rail (4) Withdrawable circuit breaker, r/h side; l/h side similar (5) Coding pin on guide frame 4 Rated current coding unit between circuit breaker and guide frame Positions of the withdrawable circuit breaker in the guide frame Display Position indicator Maintenance position (2 ) CONNECT Main circuit Auxiliary circuit Control cabinet door Shutters Disconnected Disconnected Open Closed Disconnected Disconnected Closed Closed Disconnected Connected Closed Closed Connected Connected Closed Open (1 ) TEST (4 ) DISCON N S E 0 _ 0 1 0 3 3 a NSE01037 Disconnected position CONNECT (3 ) TEST DISCON N S E 0 _ 0 1 0 3 4 a NSE01038 Test position CONNECT TEST DISCON N S E 0 _ 0 1 0 3 5 a Connected position NSE01039 CONNECT TEST DISCON N S E 0 _ 0 1 0 3 6 a (1) Auxiliary circuit (2) Main circuit NSE01040 (3) Control cabinet door (4) Shutter Phase barriers Door sealing frame and cover The plant engineering company can manufacture phase barriers made of insulating material for the arcing fault barriers. The rear panel of the fixed-mounted circuit breakers or guide frames are equipped with guide grooves. SENTRON 3WL5 circuit breakers have degree of protection IP20 as standard. However, if the switchgear is to be equipped with a higher degree of protection, a door sealing frame with IP41 and a cover with IP55 are available. Arc chute cover The arc chute cover is included as standard in orders with guide frame. It protects switchgear components which are located directly above the circuit breaker. 4/34 Siemens LV 16 · 2009 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A General data ■ Function Rating Plug NSE0_01906 NSE0_01905 12 = IR R tR Isd t sd s d t s d Ig tg Ii NSE0 00953a N S E 0 _ 0 0 9 5 1 b ETU25B ETU45B ✔ ✔ Functions of the electronic trip units 4 Basic protection functions Overload protection L Short-time delayed short-circuit protection S ✔ ✔ Instantaneous short-circuit protection I ✔ ✔ Neutral conductor protection N -- ✔ Ground-fault protection G -- ❑ N-conductor protection can be switched on/off -- ✔ N-conductor protection adjustable -- ✔ Instantaneous short-circuit protection can be switched on/off -- ✔ Additional functions Instantaneous short-circuit protection can be switched on/off -- ✔ Thermal image can be switched on/off -- ✔ Load monitoring -- ✔ Short-time delayed short-circuit protection switchable to I2t -- ✔ Instantaneous short-circuit protection adjustable -- ✔ Overload protection switchable to I4t -- ✔ Overload protection can be switched on/off -- -- Selectable parameter sets -- -- Parameterization through rotary coding switches (10 steps) ✔ ✔ Parameterization through communication (absolute values) -- -- Parameterization through user interface of ETU (absolute values) -- -- Parameterization of the extended protection functions -- ❑ LCD alphanumerical -- ❑ Graphic LCD -- -- -- ❑ CubicleBUS -- ✔ Communication through PROFIBUS DP -- ❑ Communication through MODBUS -- ❑ Communication through Ethernet -- ❑ Parameterization and display Measurement function Measurement function Plus Communication ✔ Standard -- Not available ❑ Optional Detailed information about the functions of the electronic trip units is given in the following. Siemens LV 16 · 2009 4/35 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A General data Electronic trip units (ETU) Tripped indicator/ Reset button The electronic trip unit is controlled by a microprocessor and operates independently of an auxiliary voltage. It enables systems to be adapted to the different protection requirements of distribution systems, motors, transformers and generators. Communication capabilities LCD alphanumeric with 15° inclination and rotatable through 180° The international standard PROFIBUS DP or MODBUS can be used to transmit data such as current values, switching states, reasons for tripping etc. to central computers. Data acquisition and energy management are possible in conjunction with the Plus measurement function. 4 Sliding-dolly for switchable overload characteristic curve A new internal circuit breaker data bus allows switchboard panel communication between the circuit breaker and secondary devices in the circuit breaker panel: • Actuation of analog displays • Facility to test the communication build-up with circuit breakers • Display of tripping state and tripping reasons • Input module for reading in further switchgear panel signals and for transmission of these signals to the PROFIBUS DP or MODBUS • Various output modules for displaying measured values. Rated current module/ rating plug This means that it is not only possible to monitor the device remotely, but also to transmit current values from the entire system and perform switching operations remotely. Ground-fault protection module (retrofittable) I2t and I4t characteristic curve for overload protection The best protection for the whole switchgear is achieved by setting the tripping characteristic curve to an optimum value. In order to achieve optimal discrimination for upstream fuses or medium voltage protection systems, the inclination of the characteristic curve can be selected for the overload range. The overload protection L (long time protection) for the electronic trip units ETU45B allows the characteristic curve to be switched between I2t and I4t. The I4t characteristic improves discrimination for downstream circuit breakers and fuses. Electronic trip units ETU Modularity has also been strictly emphasized during the development of the electronic trip units. These are some of the modules which can be easily retrofitted at any time: • Ground-fault protection module • Communication • Measurement function • Display • Rated current module (Rating Plug) This allows quick adaptation to new local mains specifications. In addition, innovative functions have been included in the ETUs. 4/36 Siemens LV 16 · 2009 Example of configuration for ETU45B Rated current modules / Rating plugs The rated current module is an exchangeable module which allows the user to reduce the rated device current so as to adapt it optimally to the plant; e.g. if a new plant section is taken into operation. The rated current module must be selected to fit the rated current of the system. © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A General data ETU25B electronic trip unit Option: Sicherheitsschloss safety lock prevents pressing verhindert Drückenofdes reset button after Resetknopfes nach overcurrent release Überstromauslösung Mechanical RESET Mechanisches for reclosing lockout für Wiedereinschaltsperre and mechanical und mechanische tripped indicator Ausgelöstanzeige Anzeige Überstromauslöser Indicator: overcurrent aktiviert release activated Indicator: alarm Anzeigeoverload Überlastalarm ETU25B Indicator: fault inim Anzeige Fehler overcurrent release Überstromauslöser Rating Plug Rated current module Bemessungsstrommodul Drehschalter Rotary switchEinstellwert for setting Überlastauslösung value, overload release Indicator: of release Anzeigen cause Auslöseursache Drehschalter Rotary switchEinstellwert for setting kurzzeitverzögerte value, instantaneous Kurzschlussauslösung short-circuit release Short-circuit protection Kurzschlussschutz fixed setting festeingestellt Rotary switchVerzögerung for delay, Drehschalter short-circuit release Kurzschlussauslösung NSE0_01907 Query pushbutton Taster Abfrage Taster Prüfung Test pushbutton Sealing ring Plombieröse Clear pushbutton Taster Löschen Test socket Prüfbuchse Application: Classical building, motor and system protection with time-selective coordination for up to 5000 A Features: • Adjustable overload protection with I2t characteristic curve Delay time tR = 10 seconds at 6 × IR • Short-time delayed short-circuit protection adjustable in the range 1.25 ... 12 × In and • Instantaneous short-circuit protection preset to 20 × In, max. 50 kA • Can be adapted at any time to the required plant currents through retrofittable rated current module, thus ensuring overload protection in the range from 100 A to 5000 A. • Overload display • Indicates the reason for tripping by means of an LED • Test facility for the trip unit • Protection functions are set by means of the rotary coding switch 4 For technical details see the table "Functional Overview of the Electronic Trip Unit System" under "Technical Specifications". Siemens LV 16 · 2009 4/37 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A General data ETU45B electronic trip unit Mechanical RESET for reclosing lockout and mechanical tripped indicator Scroll up Application: Option: safety lock prevents pressing of reset button after overcurrent release Option: alphanumeric display Indicators: Overcurrent release activated Overload alarm Scroll down Indicator: fault in overcurrent release COMMUNICATION EXPANDED OFF ON Rated current module Rating Plug Rotary switch for setting value, overload release = 1 1 1 1 1 Rotary switch for delay, overload release Rotary switch for delay, short-circuit release Indicator: cause of release 12 Rotary switch for setting value, instantaneous short-circuit release Features: Thermal memory on/off N-conductor protection on/off Setting value N-conductor overload Transfer of overload characteristic 2 t / 4t ETU45B Rotary switch for setting value, short-circuit protection Sealing ring Option: earth-fault module Selector for earth-fault protection SI Rotary switch for setting value, earth-fault protection Rotary switch for setting value, earth-fault alarm Indicator: earth-fault alarm g Indicator: earth-fault tripped Rotary switch for delay, earth-fault protection t g / Clear pushbutton Test socket Test pushbutton Query pushbutton Low-cost all-round system for intelligent buildings and all types of industrial applications – "CubicleBUS integrated" 2 tg NSE0_01908 4 The same as ETU25B but also • Adjustable time-lag class for overload protection • Selectable characteristic for overload and short-delayed short-circuit range (current discrimination) for more accurate discrimination adaptation to upstream fuses and protective devices • Thermal image as restart protection for tripped motor outgoing feeders • Reversible and adjustable neutral conductor protection • Modular ground-fault protection module with alarm and tripping functions which can be adjusted separately • Communication interface, measurement function Plus, optional connection of external modules or for retrofitting • Storage of events and causes for tripping for detailed fault analysis • Extended protection function possible with measurement function • Optional high-contrast display with viewing angle adjustment option • The protection functions can be set by means of a rotary coding switch or slide switch For technical details see the table "Functional Overview of the Electronic Trip Unit System" under "Technical Specifications". Ground-fault protection Selector for earth-fault detection I Rotary switch for setting value, earth-fault protection g TRIP G OFF ALARM A B C D E Rotary switch for setting value earth-fault alarm GFM AT 45B ground-fault module 4/38 Siemens LV 16 · 2009 Indicators: Earth-fault alarm GFM AT 45B Earth-fault tripped ALARM t g (s) TRIP .5 .4 .3 .2 .1 NSE0_00962a 2 I tg .1 .2 .3 .4 .5 Rotary switch for setting value, earthfault protection delay 2 tg/I tg Ground-fault releases "G" sense fault currents that flow to ground and that can cause fire in the plant. Multiple circuit breakers connected in series can have their delay times adjusted so as to provide graduated discrimination. When setting the parameters for the electronic trip unit it is possible to choose between "alarm" and "trip" in the event that the set current value is exceeded. The reason for tripping is indicated by means of an LED when the query button is activated. The ETU45B electronic trip unit version can be retrofitted with a ground-fault protection module. © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A General data Measurement method Setting Vectorial summation current formation (measurement method 1) How the module is set depends on the measurement method used (see above): The three phase currents and the N-conductor current are measured directly. The electronic trip unit determines the ground-fault current by means of vectorial summation current formation for the three phase currents and the N conductor current. A standard transformer with the following data is used for measurement of the ground-fault current: 1200 A/1 A, Class 1 (the internal load of SENTRON 3WL5 is 0.11 ). The transformer can be installed directly in the grounded neutral point of a transformer. T5 L1 L2 L3 N PE NSE 00946 3-pole circuit breakers, current transformers in the N conductor SENTRON WL L1 L2 L3 N T6 PE T6: 1200 A/1 A NSE 00947 3-pole circuit breakers, current transformers in the grounded neutral point of the transformer. SENTRON WL . Measurement method 2: in position . Ground-fault protection with I 2t characteristic curve All versions of the ground-fault modules are supplied with an I2t characteristic curve which can be activated. Direct measurement of the ground-fault current (measurement method 2) SENTRON WL Measurement method 1: in position L1 L2 L3 Selection criteria for SENTRON 3WL circuit breakers Basic criteria for selecting circuit breakers are: • Max. short-circuit current at place of installation of circuit breaker I k! max. This value determines the short-circuit breaking capacity or short-circuit current carrying capacity of the circuit breaker. • It is compared with the value Icu, Ics, Icw of the circuit breaker and essentially determines the size of the circuit breaker. See illustration "Overview of SENTRON 3WL5 Circuit Breakers/ Non-Automatic Air Circuit Breakers". • Rated current In which is to flow through the branch circuit. This value must not be larger than the maximum rated current for the circuit breaker. The rated current for the SENTRON 3WL5 is set with the rated current module. See "Design", illustration "Overview of SENTRON 3WL5 Circuit Breakers/Non-Automatic Air Circuit Breakers". • Ambient temperature for the circuit breaker. This is usually the control cabinet internal temperature. • Design of the circuit breaker • Minimum short-circuit current which flows through the switching device. The trip unit must still detect this value as a short-circuit and must respond by tripping. Protection functions of the circuit breaker. These are determined by the selection of the corresponding electronic trip unit, see the table "Functions of the Electronic Trip Units" under "Functions". N T6 PE T6: 1200 A/1 A NSE 00948 4-pole circuit breakers, current transformers in the grounded neutral point of the transformer. Siemens LV 16 · 2009 4/39 4 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A General data ■ Configuration Mutual mechanical circuit breaker interlocking • The bending radii of the Bowden wire must be greater than 500 mm. • The sum of all bending angles along the Bowden wire must not exceed 640°. • In a vertical arrangement of circuit breakers to be interlocked, the interlocking mechanisms must be in line. • Circuit breakers to be interlocked must be arranged so that Bowden cables can be optimally installed in compliance with the conditions mentioned in the above points. • The installed Bowden cable must be fixed (with cable ties or the like) before the interlock is adjusted. • Select the width of switchgear cubicle to allow enough freedom of movement for adjusting the interlock! • Openings and cut-outs in system elements must be designed so that Bowden cables are not changed in direction or obstructed when they are passed through. The module for mutual mechanical interlocking can be used for one or two SENTRON 3WL5 circuit breakers and can be adapted easily to the corresponding versions. The fixedmounted and withdrawable circuit breaker versions are fully compatible and can therefore be used in a mixed configuration in an installation. The circuit breakers can be mounted alongside each other or one above the other, whereby the distance of the circuit breakers is determined solely by the length of the Bowden wire (lengths: 2 m/3 m/4.5 m). Interlock signals are looped through using the Bowden cables. Interlocking is only effective in the connected position in the case of withdrawable circuit breakers. The mechanical endurance of the Bowden cables is 10000 operating cycles. Minimum requirements must be fulfilled in the switchgear for the interlocking to function: • Bowden cables must be installed as far as possible in a straight line with minimum bending. Mutual mechanical interlocking of circuit breakers – examples Mutual interlocking of two circuit breakers 4 Interlocking between three circuit breakers Mutual interlocking of three circuit breakers G S1 S2 4/40 G G S1 S3 S2 NSE01041 Interlocking of three circuit breakers, two of them mutual NSE01042 Siemens LV 16 · 2009 S1 S1 NSE01043 S2 S2 S3 S1 S3 S2 S3 NSE01044 NSE01045 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A General data Communication-capable circuit breakers PC with Switch ES Power SENTRON 3WL/3VL parameterization and visualization tool through PROFIBUS DP PLC e.g. SIMATIC S7 data acquisition and processing Digital input module Analog output module NSE0_01820a BDA BDA Plus ETU Measurementfunction Plus Digital output module Relay, configurable BSS Digital output module Relay COM15 Zone Selective Interlocking module Output device e.g. notebook with browser Ethernet/ Intranet/ Internet Communication with PROFIBUS DP 4 Configuration and display software MODBUS Master PLC or monitoring software MODBUS Digital input module Analog output module BDA BDAPlus ETU Measurement function Plus NSE0_01894 BSS Digital output module Relay, configurable COM16 Digital output module Relay Output device e.g. notebook with browser Zone Selective Interlocking module Ethernet/ Intranet/ Internet Communication with MODBUS The requirements for power distribution in terms of communication capability, data transparency, flexibility and integration are constantly increasing. An integrated and modular communication architecture was designed for the SENTRON 3WL5 to ensure that it can satisfy these requirements. The core component of this architecture is the CubicleBUS, which links together all of the intelligent components within the SENTRON 3WL5 and enables the easy and safe connection of other additional external components to the circuit breaker. The CubicleBUS is already incorporated and pre-connected in all complete circuit breakers with ETU45B trip units. The high level of modularity of the system allows communication functions to be retrofitted at any time (e.g. the measurement function). Similarly, the upgrade of a non-communication-capable SENTRON 3WL5 (e.g. changeover from ETU25B to ETU45B with CubicleBUS) can be carried out easily on site in the plant. All modules connected to the CubicleBUS can directly access the existing source data of the circuit breaker, which guarantees the quickest possible access to information and response to events. Furthermore, additional external modules (including digital inputs/ outputs, analog outputs) can be connected to the CubicleBUS to provide cost-effective solutions for the automation of further devices in the switchgear. Siemens LV 16 · 2009 4/41 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A General data SENTRON 3WL5 communication-capable circuit breakers Function Electronic trip unit version Breaker PROFIstatus BUS/ sensors MODBUS communication ports Measure- Analog Digital Digital ZSI Breaker Breaker ment output output input module Data Data Adapters Adapters function modules modules modules Plus Plus ETU45B Functions of the communication-capable SENTRON 3WL circuit breakers 4 Indication of measured values in trip unit (current only) ✓ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ Indication of measured values in trip unit (U, I, P, S, Q, p.f., etc.) ✓ ❏ ❏ ✓ ❏ ❏ ❏ ❏ ❏ ❏ Output of measured values (current only) to rotary coil instruments in control cabinet door ✓ ❏ ❏ ❏ ✓ ❏ ❏ ❏ ❏ ❏ Output of measured values (U, I, P, S, Q, p.f., etc.) to rotary coil instruments in control cabinet door ✓ ❏ ❏ ✓ ✓ ❏ ❏ ❏ ❏ ❏ Output of digital signals (e.g. reason for tripping, alarm signals, status) through contacts ✓ ❏ ❏ ❏ ❏ ✓ ❏ ❏ ❏ ❏ Read in digital signals and forward to PROFIBUS/ MODBUS ✓ ❏ ✓ ❏ ❏ ❏ ✓ ❏ ❏ ❏ Transmission of switch information on HTML basis locally to a PC ✓ ✓ ❏ ❏ ❏ ❏ ❏ ❏ ✓ ✓ Transmission of switch information on HTML basis through Ethernet ✓ ✓ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ✓ Short-time grading control for S tripping and G protection ✓ ❏ ❏ ❏ ❏ ❏ ❏ ✓ ❏ ❏ Local storage of harmonic analysis and waveform memory and transmission through PROFIBUS ✓ ✓ ✓ ✓ ❏ ❏ ❏ ❏ ❏ ❏ Read out protection parameters through PROFIBUS/MODBUS ✓ ✓ ✓ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ✓ Required ❏ Not necessary for this function, optionally combinable Function can optionally be taken over by one of these modules. 4/42 Siemens LV 16 · 2009 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A General data Data that can be transmitted over the PROFIBUS DP/MODBUS or the Breaker Data Adapter All SENTRON 3WL5s with ETU45B (CubicleBUS integrated) Transmittable circuit breaker data BSS Order code (Order No. of circuit breaker + "–Z") BDA BSS F01 +"BDA/BDAPLUS" Order No. Order No. COM15/COM16 F02/ F12 Potential applications Transmission of circuit breaker data to PROFIBUS DP or MODBUS and integration into higher-level visualization systems are possible e.g. in PCS7, Power Management Systems, WinCC (including add-ons like the text message radio server) -- ✔ Transmission of circuit breaker data and software (i.e. HTML pages with data) to a local output device, or remotely through Ethernet/Intranet/Internet (without the possibility of integration into higher-level visualization systems) e.g. for monitoring, diagnostics, maintenance and parameterization of individual circuit breakers ✔ -- Utilization of the functionality of all CubicleBUS modules e.g. configuration of the configurable digital output module, status check of the digital input modules, diagnostics ✔ ✔ ✔ ✔ --1) ✔ Operating statuses On/off status message, spring energy store, tripped, readiness Switching position (connected, test and disconnected position, not present) for withdrawable circuit breakers, PROFIBUS/MODBUS write protection on/off, free user input ✔ --1) --1) ✔ ✔ ✔ Control commands Switch circuit breaker on/off, switch free user output on/off Reset tripped signal Delete event and history memory Reset the min./max. measured values, reset the maintenance information --1) ✔ --1) ✔ ✔ ✔ ✔ ✔ History Read out the event protocol, read out the release protocol --1) ✔ Maintenance information Number of tripping operations L, S/I and in total, contact wear Number of operating cycles under load and in total, number of operating hours ✔ --1) ✔ ✔ Event signals Tripped signal with details of the tripping current Alarm signals (e.g. overload) with incoming/outgoing information All of the named event signals with time stamp ✔ --1) --1) ✔ ✔ ✔ Parameterization of the protection functions Reading out of the protection function parameters ✔ ✔ Measured values Phase currents, each with min./max. value Temperature in the circuit breaker with min./max. value Temperature in the control cabinet with min./max. value All of the named measured values with time stamp ✔ --1) --1) --1) ✔ ✔ ✔ ✔ Transmittable circuit breaker data without integrated measurement function Device identification Communication address, Order No., circuit breaker in delivery status, circuit breaker parameters (size, number of poles, rated current module etc.), identification numbers, release type, free text for plant code and comments 4 Measurement function Plus Order code F01+ ... or F02 or F12+ ... F05 Additional transmittable circuit breaker data with integrated measurement function Additional event signals Threshold value alarms (e.g. over/underfrequency, over/undervoltage) ✔ Parameterization of the extended protection functions and setpoints (threshold values) Reading out the parameters of the extended protection functions Settings for the extended protection function parameters can be changed Reading out and adjusting threshold values ✔ ✔ ✔ Additional measured values Voltages, power, energy, power factor, frequency, each with min./max. value Harmonic analysis Recording of currents and voltages for configurable events in the curve form memory ✔ ✔ ✔ 1) Data only available in conjunction with the COM15/COM16 module (BUS connection not required). ✔ Available -- Not available Siemens LV 16 · 2009 4/43 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A General data CubicleBUS modules Digital output modules with rotary coding switch 6 items of binary information concerning the state of the circuit breaker (reasons for tripping and warnings) can be output via this module to external signaling devices (e.g. LED, horn) or be used for the selective shut-down of other system components (e.g. frequency converters). Digital output modules are available in versions with and without a rotary coding switch. On modules with a rotary coding switch it is possible to choose between two signaling blocks each with 6 defined assignments and to set an additional response delay. All the digital output modules are available as a version with relay outputs (CO contacts, up to 12 A). Up to two modules of this type can be connected to one SENTRON 3WL5. Analog output module Digital input modules With the digital input module, up to 6 additional binary signals (24 V DC) in the circuit breaker environment can be connected to the system. It is thus possible to send messages concerning the state of a switch disconnector or a control cabinet door to the PROFIBUS DP or MODBUS. One module each of this type can be used for holding the six items of digital information and for automatically switching over the parameters. Digital output module with rotary coding switch 4 Digital output modules, configurable The configurable output module is available for higher-performance solutions. With this module, random events on the CubicleBUS can be switched directly to one of six available outputs or three of these outputs can be assigned with up to six events. In other words, up to six events can be placed on one physical output with OR operation. Either BDA/BDA Plus or Switch ES Power is used for configuring. A relay variant is also available here the same as for the output modules with rotary coding switch. Only one module of this type is possible per SENTRON 3WL5. Digital input module ZSI modules (short-time grading control) The use of ZSI modules is recommended when Siemens circuit breakers are arranged in several staggered levels but full grading with the smallest possible delay is to be assured nevertheless. The circuit breakers are interconnected by these modules. In case of a short-circuit, each affected circuit breaker asks the circuit breakers directly downstream whether the short-circuit has also occurred in the next, lower level. The short-circuit is exactly localized as the result, and only the next upstream circuit breaker in the energy flow direction is switched off. Digital output module, configurable Analog output modules The analog output module can be used to output the following measured values to analog indicators in the control cabinet door: • IL1, IL2, IL3, IN or • UL12, UL23, UL31, UL1N or • PL1, PL2, PL3, Stot or • p.f.1 , p.f.2 , p.f.3, I% or • favg, ULLavg, Ptot, p.f.avg Four 4-20-mA/0-10-V interfaces are available for this. The measured values to be output are selected with a rotary coding switch. By using the analog output module it is possible to do without additional converters and their conventional installation/ wiring in the main current path. Up to two modules of this type can be connected to one SENTRON 3WL5. 4/44 Siemens LV 16 · 2009 ZSI module (short-time grading control) © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A General data ■ Technical specifications Size I II III Type 3WL51 3WL52 3WL53 Switching capacity class S H H S H H 100 100 Short-circuit breaking capacity Icu = Ics acc. to UL 489 Up to 480 V AC kA 65 Up to 600 V */347 V AC kA 50 851) Up to 600 V AC kA -- 85 kA 65 85 85 85 -- Rated short-time withstand current acc. to UL 489 At max. delay time tsd = 0.4 s Short-circuit breaking capacity Icu = Ics acc. to IEC 60947-2 Up to 500 V AC Icm at 500 V AC kA kA 65 143 100 220 100 220 Up to 690 V AC Icm at 690 V AC kA kA 50 105 85 187 85 187 Rated short-time withstand current Icw acc. to IEC 60947-2 0.5 s kA 65 85 85 1s kA 50 80 80 1) Covered by 600 V AC (delta) test. Further technical specifications I 3WL51 10 3WL51 16 3WL52 20 A A A Up to 1000 1000 1000 1600 1600 1600 2000 2000 2000 Rated voltage Ue at 50/60 Hz V AC 600 */347 600 */347 600 Ambient temperature of the system !C –25/+40 –25/+40 –25/+40 Power loss at rated current with 3-phase symmetrical load • Fixed-mounted circuit breakers • Withdrawable circuit breakers W W 100 195 150 350 180 320 ms ms 35 38 35 38 35 34 ms ms 80 73 80 73 100 73 ms ms 73 50 73 50 73 50 10000 4000 10000 4000 10000 4000 1/h 60 60 60 Minimum interval ms Between tripping operation by electronic trip unit and next making operation of the circuit breaker (only with automatic mechanical resetting of the lockout device) 80 80 80 400 × 460 × 380 400 × 460 × 380 500 × 460 × 380 Rated current In at 50/60 Hz Main conductor At 40 °C At 55 °C At 60 °C Operating times • Make-time • Opening time • Electrical make-time (through activation solenoid) • Electrical opening time (through shunt trip unit) 1) • Electrical opening time (instantaneous undervoltage release) • Opening time due to ETU, instantaneous short-circuit release Endurance • Mechanical (without maintenance) • Electrical (without maintenance) Operating cycles Operating cycles Switching frequency Minimum dimension Circuit breaker 3-pole compartment Width × height × depth mm II Mounting position 3 0 ° 3 0 ° and/ or N S E 0 _ 0 0 0 6 1 a Main conductor minimum cross-sections Auxiliary conductors (Cu) Max. number of auxiliary conductors × crosssection (solid/stranded) Weights 3-pole 1) Unit(s) 2 mm2 or 6.4 × 76.2 inches 1/4 × 3 3 0 ° 4 h m a x . = 1 m m Size Type 3 0 ° N S E 0 _ 0 0 9 2 7 a N S E 0 _ 0 0 0 6 2 a 2 6.4 × 76.2 1/4 × 3 2 6.4 × 102 1/4 × 4 Standard connection = strain-relief clamp • Without end sleeve • With end sleeve acc. to DIN 46228 Part.22) • With twin end sleeve 2 × 0.5 mm2 (AWG 20) up to 2 × 1.5 mm2 (AWG 16); 1 × 2.5 mm2 (AWG 14) 1 × 0.5 mm2 (AWG 20) up to 1 × 1.5 mm2 (AWG 16) 2 × 0.5 mm2 (AWG 20) up to 2 × 1.5 mm2 (AWG 16) Optional connection = tension spring • Without end sleeve • With end sleeve to DIN 46228 Part 2 2 × 0.5 mm2 (AWG 20) up to 2 × 2.5 mm2 (AWG 14) 2 × 0.5 mm2 (AWG 20) up to 2 × 1.5 mm2 (AWG 16) • Fixed-mounted circuit breakers • Withdrawable circuit breakers • Guide frames kg kg kg 43 45 25 Make-time through activation solenoid for synchronization purposes (short-time excited) 50 ms. 43 45 25 56 60 31 2) Important: Approval of end sleeves. Siemens LV 16 · 2009 4/45 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A General data Size II Type 3WL52 25 3WL52 30 3WL53 40 3WL53 50 Rated current In at 50/60 Hz Main conductors At 40 °C At 55 °C At 60 °C A A A 2500 2500 2500 3000 3000 3000 4000 4000 4000 5000 5000 5000 Rated voltage Ue at 50/60 Hz V AC 600 600 Up to 600 */347 Up to 600 */347 Ambient temperature of the system !C –25/+40 –25/+40 –25/+40 –25/+40 Power loss at rated current with 3-phase symmetrical load • Fixed-mounted circuit breakers • Withdrawable circuit breakers W W 270 520 410 710 520 810 630 1050 Operating times • Make-time • Opening time • Electrical make-time (through activation solenoid)1) • Electrical opening time (through shunt trip unit) • Electrical opening time (instantaneous undervoltage release) • Opening time due to ETU, instantaneous short-circuit release ms ms ms ms ms ms 35 34 100 73 73 50 35 34 100 73 73 50 35 34 100 73 73 50 35 34 100 73 73 50 10000 4000 10000 4000 1/h 60 60 60 60 Minimum interval ms Between tripping operation by electronic trip unit and next making operation of the circuit breaker (only with automatic mechanical resetting of the lockout device) 80 80 80 80 800 × 460 × 380 800 × 460 × 380 Operating cycles Operating cycles Switching frequency Minimum dimension Circuit breaker compartment Width × height × depth 3-pole mm 500 × 460 × 380 Mounting position 3 0 ° 500 × 460 × 380 3 0 ° 3 0 ° 3 0 ° and/ or N S E 0 _ 0 0 0 6 1 a Unit(s) 2 mm2 or 6.4 × 127 inches 1/4 × 5 Main conductor minimum cross-sections Auxiliary conductors (Cu) Max. no. of auxiliary conductors × cross-section (solid/stranded) 5000 1000 N S E 0 _ 0 0 9 2 7 a N S E 0 _ 0 0 0 6 2 a 4 4 6.4 × 63.5 6.4 × 102 1/4 × 2–1/2 1/4 × 4 5000 1000 h m a x . = 1 m m Endurance • Mechanical (without maintenance) • Electrical (without maintenance) 4 III 4 10 × 120 1/4 × 52) 4 10 × 120 1/4 × 52) Standard connection = strain-relief clamp 2 × 0.5 mm2 (AWG 20) up to 2 × 1.5 mm2 (AWG 16); 1 × 2.5 mm2 (AWG 14) • Without end sleeve • With end sleeve acc. to DIN 46228 Part 2 1 × 0.5 mm2 (AWG 20) up to 1 × 1.5 mm2 (AWG 16) 2 × 0.5 mm2 (AWG 20) up to 2 × 1.5 mm2 (AWG 16) • With twin end sleeve Optional connection = tension spring 2 × 0.5 mm2 (AWG 20) up to 2 × 2.5 mm2 (AWG 14) • Without end sleeve • With end sleeve acc. to DIN 46228 Part 2 2 × 0.5 mm2 (AWG 20) up to 2 × 1.5 mm2 (AWG 16) Weights 3-pole • Fixed-mounted circuit breakers • Withdrawable circuit breakers • Guide frames kg kg kg 1) Make-time through activation solenoid for synchronization purposes (short-time excited) 50 ms. 2) 1/4 × 5 for fixed-mounted circuit breakers on request. 4/46 Siemens LV 16 · 2009 59 63 39 64 68 45 82 88 60 82 88 60 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A General data Size I to III Type 3WL5 Manual operating mechanism with mechanical closing Closing/Charging stored-energy feature Max. force required to operate the hand lever Required number of strokes on the hand lever N " 230 9 Manual operating mechanism with mechanical and electrical closing Charging stored-energy feature Closing solenoid (CC) • Operating range 0.85 ... 1.1 x Us • Extended operating range for battery operation At 24 V DC, 48 V DC 60 V DC, 110 V DC 220 V DC • Power consumption AC/DC • Minimum command duration at Us for the closing solenoid 0.7 ... 1.26 x Us VA/W 15/15 ms 60 1A • Short-circuit protection Manual/motorized operating mechanism with mechanical and electrical closing For data see above. Manual operating mechanism Motor 0.85 ... 1.1 x Us • Operating range • Extended operating range for battery operation At 24 V DC, 48 V DC 60 V DC, 110 V DC 220 V DC • Power consumption of motor AC/DC 0.7 ... 1.26 x Us VA/W 110/110 s • Time required to charge the spring energy store at 1 × Us For motor and closing solenoid "8 For data see above. Closing solenoid • Short-circuit protection Motor and closing solenoid for the same rated control supply voltages • Smallest permissible fuse 2A At Us 24 ... 30 V At Us 48 ... 60 V At Us 110 ... 127 V At Us 220 ... 250 V 4 2A 2A 1A 1A Electronic trip unit signals Protection functions acc. to UL 489 Current indication " 5 %; Measurement functions base quantities " 1 %; Measurement functions derived quantities " 4 % Measuring accuracy of the electronic trip unit Auxiliary trip units Undervoltage releases UVR (F3) and UVR-td (F4) • Response values # 0.85 × Us (circuit breaker can be closed) 0.35 ... 0.7 × Us (circuit breaker is tripped) Pickup Dropout 0.85 ... 1.1 • Operating range 0.85 ... 1.26 • Extended operating range for battery operation At 24 V DC, 30 V DC, 48 V DC, 110 V DC, 220 V DC • Rated control supply voltage Us Instantaneous AC 50/60 Hz V • Power consumption (pickup/uninterrupted duty) • Opening time of circuit breaker at Us = 0 110 ... 127/208 ... 240/ 380 ... 415 24/30/48/60/110/220 ... 250 DC V Delayed AC 50/60 Hz V DC V 110 ... 127/208 ... 240/ 380 ... 415 48/110 ... 125/220 ... 250 AC DC VA W 20/5 20/5 ms 200 - Version UVR (F3) Instantaneous With delay ms ms 80 200 - Version UVR-td (F8) With delay, td = 0.2 to 3.2 s Reset through additional NC contact, direct switching-off s ms 0.2 ... 3.2 " 100 A 1 Short-circuit protection Siemens LV 16 · 2009 4/47 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A General data Size I to III Type 3WL5 Auxiliary trip units Shunt trip unit (ST) (F1, F2) • For continuous command (100 % ON period), locks out on momentarycontact commands - Response value > 0.7 × Us (circuit breaker is tripped) Pickup - Operating range - Extended operating range for battery operation 0.85 ... 1.1 × Us At 24 V DC, 48 V DC 60 V DC, 110 V DC, 220 V DC - Rated control supply voltage Us AC 50/60 Hz DC - Power consumption V 110; 230 V 24; 30; 48; 60; 110; 220 VA/W 15/15 AC/DC ms 60 - Min. command duration at Us - Opening time of circuit breaker at Us = 100 % AC/DC ms 80 - Short-circuit protection • 5 % ON period - Response value 1A > 0.7 × Us (circuit breaker is tripped) Pickup 0.85 ... 1.1 × Us - Operating range - Extended operating range for battery operation At 24 V DC, 48 V DC 60 V DC, 110 V DC, 220 V DC - Rated control supply voltage Us AC 50/60 Hz DC - Power consumption 4 VA/W 15/15 AC/DC ms 25 AC/DC ms 50 1A - Short-circuit protection • With stored energy feature consisting of shunt trip unit and capacitor storage device - Rated control supply voltage Us AC 50/60 Hz DC V 110; 230 V 110; 220 0.85 ... 1.1 × Us - Operating range - Power consumption 0.7 ... 1.26 × Us V 110 ... 127; 208 ... 240 V 24; 48; 110 ... 125; 220 ... 250 - Min. command duration at Us - Opening time of circuit breaker at Us = 100 % 0.7 ... 1.26 × Us VA/W 1/1 AC/DC - Storage time at Us/ recharging time at Us max. 5 min/min. 5 s - Opening time of circuit breaker, short-circuit protection As with "for continuous command" Remote reset solenoid for mechanical tripped indicator (F7) 0.85 ... 1.1 × Us - Operating range Remote reset solenoid for mechanical tripped indicator (F7) - Extended operating range for battery operation At 24 V DC, 48 V DC 110 V DC, 220 V DC - Power consumption AC/DC 0.7 ... 1.26 × Us VA/W 50/50 - Minimum command duration at Us for the remote reset solenoid ms 60 - Short-circuit protection Smallest permissible DIAZED fuse (gL operational class)/ miniature circuit breaker with C characteristic 2 A TDz (slow)/1 A at 24 V DC and 48 V DC, 1 A TDz (slow)/1 A at 110 V and 208 ... 250 V Contact position-driven auxiliary switches (S1, S2, S3, S4, S7, S8) V AC/DC 500 Rated insulation voltage Ui Rated operational voltage Ue V AC/DC 500 Rated impulse withstand voltage Uimp kV 4 A A 10 10 A 10 V A 250 0.2 A 2 Switching capacity • Alternating current 50/60 Hz A 300 heavy duty • DC current P 300 heavy duty Largest permissible fuse Short-circuit protection Ready-to-close signaling switch (S20) (acc. to UL 1054) Switching capacity • Rated operational voltage Ue • Rated operational current Ie Largest permissible fuse Short-circuit protection Tripped signal switch (S24) and signal switch for auxiliary trip units (S22, S23) (acc. to UL 1054) Switching capacity • Rated operational voltage Ue • Rated operational current Ie V 250 A 0.2 Position indicator switch on guide frame Type of contact • Signal: - "Circuit breaker in connected position" - "Circuit breaker in test position" - "Circuit breaker in disconnected position" AC 50/60 Hz DC Rated insulation voltage Ui Rated operational voltage Ue Rated impulse withstand voltage Uimp Switching capacity 4/48 • Rated operational current Ie Siemens LV 16 · 2009 3 CO 2 CO 1 CO V 440 V 250 V 250 kV 4 A 0.2 or 1 CO 1 CO 1 CO © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A General data Protection functions Parameterization by ETU25B D ETU45B D &S ✓ 0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1 -- ✓ 0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1 ✓ 10 s fixed --at tsd = 20 ms (M) ---✓ -1.25-1.5-2-2.5-3-4-6-8-10-12 0-M-100-200-300-400 ms -- 2-3-5-5.5-8-10-14-17-21-25-30 s 1-2-3-4-5 s ✓ at tsd = 20 ms (M) ✓ ✓ 0.5 ... 1 ✓ ✓ 1.25-1.5-2-2.5-3-4-6-8-10-12 M-100-200-300-400 ms ✓ --✓ -fixed for Ii # 20 $ In, max. 50 kA 100-200-300-400 ms by CubicleBUS module ✓ ✓ 1.5-2.2-3-4-6-8-10-12-0.8 $ Ics ----- ❑ Module can be retrofitted ✓ ✓ ✓ -- ✓ ----- A-B-C-D-E A-B-C-D-E 100-200-300-400-500 ms ✓ --- 100-200-300-400-500 ms by CubicleBUS module Alphanumeric LCD (4-line) -- ❑ CubicleBUS integrated Communication-capable through PROFIBUS DP Communication-capable through MODBUS ---- ✓ ✓ ✓ Measurement function Plus -- ❑ ✓ ✓ ✓ ✓ ✓ ✓ ------ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ (only with ground-fault protection module) ✓ (only with ground-fault protection module) ✓ ✓ -------------- ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ (only with ground-fault protection module) ✓ (only with ground-fault protection module) ✓ ✓ Functional overview of the electronic trip unit system Overload protection Setting range IR = In × ... L R R N S s d s d i N S E 0 _ 0 0 8 8 8 b I g G g N S E 0 _ 0 0 8 8 9 a Switchable overload protection (I2t- or I4t-dependent function) Setting range for time-lag class tR at I2t Setting range for time-lag class tR at I4t Thermal image can be switched on/off Phase failure sensitivity Neutral conductor protection Function can be switched on/off N conductor setting range IN = In × ... Short-time delayed short-circuit protection Function can be switched on/off Setting range Isd = In × ... Setting range for delay time tsd Switchable short-time delayed short-circuit protection (I2t-dependent function) Setting range for delay time tsd at I2t Zone Selective Interlocking function Instantaneous short-circuit protection Function can be switched on/off Setting range Ii = In × ... Ground-fault protection Tripping and alarm function Tripping function can be switched on/off Detection of the ground-fault current through summation current formation with internal or external N conductor transformer Detection of ground-fault current through external transformer Setting range of the operating current Ig for tripping Setting range of the operating current Ig for alarm Setting range of the delay time tg Switchable ground-fault protection characteristic curve (I2t-dependent function) Setting range for delay time tg at I2t Zone Selective Interlocking ground-fault protect. function 4 LCD Communication Measurement function LED display Electronic trip unit active Alarm ETU fault L-release S-release I-release N-release G-release NSE00890 G-alarm Release through extended protection function Communication Signals from signal switches with external CubicleBUS module (relay) Overload warning Load shedding, load receiving Leading signal overload trip 200 ms Temperature alarm Phase unbalance Instantaneous short-circuit release Short-time delayed short-circuit release Overload trip NSE00891 Neutral conductor release Ground-fault protection release Ground-fault alarm Auxiliary relay ETU fault Delay time figures given in ms. M = motor protection, corresponds to 20 ms. D = rotary coding switch D & S = rotary coding and slide switch ✓ Available. -- Not available. ❑ Optional. Setting range of the operating current Ig Size I and size II Size III A 100 A 400 A B 300 A 600 A C 600 A 800 A D 900 A 1000 A E 1200 A 1200 A Siemens LV 16 · 2009 4/49 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Project planning aids ■ Characteristic curves 1,25 ... 12 x sd = const sd max n sd max sd min i > 20 x n max. 50 kA 0,01 1 0,1 10 100 / n 10000 4 R const 0,4 ... 1,0 x 1000 NSE0_01522a SENTRON 3WL5 circuit breaker with ETU25B electronic trip unit, LSI characteristic curve const sd = 1,25 ... 12 x i 10 2 sd min 0,1 n sd = 10 0 ... 0,4 s 100 2 n 100 1 Opening time [s] sd R max 0,4 ... 1,0 x 1000 NSE0_01520 R min NSE0_01523a 1000 1 = const n 2 = const 100 R 2 ... 30s for 2 1 ... 5s for 4 10 1 0,1 ... 0,4 s 0,1 0,1 0,02 ... 0,4 s 0,01 1 10 0,01 100 / 10000 Opening time [s] 1000 100 10 1 x 1 Siemens LV 16 · 2009 g 10 2 = const 100 ... 1200 A1) g 10 / n 0,1 ... 0,5 s 0,01 1 / 100 1000 cs SENTRON 3WL5 circuit breaker with ETU45B electronic trip unit, I characteristic curve Tolerances for the set currents L : Tripping operations between 1.05 and 1.2 x IR S : –0 %, +20 % I : –0 %, +20 % G : –0 %, +20 % Tolerances for the tripping times L : –20 %, +0 % for I2t characteristic curve S : –0 %, +60 ms or –0 %, +10 % for characteristic curve with fixed delay time I : < 50 ms G : –0 ms, +60 ms or –0 %, +10 % for characteristic curve with fixed delay time 4/50 100 0,1 cs 0,01 0,1 1000 1 i n ... 0,8 100 n SENTRON 3WL5 circuit breaker with ETU45B electronic trip unit, L characteristic curve NSE0_01524a 10000 1,5 x 10 / SENTRON 3WL5 circuit breaker with ETU45B electronic trip unit, S characteristic curve 0,1 1 0,1 n NSE0_01525a 0,1 Opening time [s] 4 Opening time [s] 10000 10000 Opening time [s] Every electronic trip unit type and every setting has its own characteristic curve. Only a selection is shown in the following. The characteristic curves each show the largest and smallest setting range of SENTRON 3WL5 circuit breakers with 1000 A rated current at 480 V rated voltage with various trip units. In order to obtain a complete tripping characteristic, the relevant parts of the characteristics have to be combined. The characteristic curves show the behavior of the electronic trip unit when it is activated by a current that is already flowing before the tripping operation. If the overcurrent tripping occurs immediately after switch on and the electronic trip unit is therefore not yet enabled, the opening time is extended, depending on the level of the overcurrent by up to 15 ms. In order to determine the break-times of the circuit breakers, approximately 15 ms must be added to the opening times shown for the arcing time. Refer to the following legend for tolerances. The characteristic curves shown apply to ambient temperatures at the circuit breaker between -5 and +55 °C. The trip unit can be operated at ambient temperatures of -20 to +70 °C. An extended tolerance band can apply at these temperatures. 10000 100000 A SENTRON 3WL5 circuit breaker with ETU45B electronic trip unit, G characteristic curve Further characteristic curves are shown in the manual and the planning and configuring tool SIMARIS design, or ask your Siemens contact person. 1) Sizes I and II: 100 ... 1200 A Size III: 400 ... 1200 A © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Project planning aids ■ Dimensional drawings Ext. transformers for N conductor without copper connection pieces Voltage transformer for SENTRON 3WL5 Size I, 3WL9 111-0AA21-0AA0 260 6 0 1 6 R 2 2 4 0 87 N S E 0 _ 0 1 3 7 5 NSE0_01103b 1 3 ,1 8 ,9 R 2 2 8 1 9 6 ,8 125 8 For mounting on 35 mm standard mounting rail 1 8 5 1 3 6 7 0 8 3 Current transformers for overload protection in the N conductor External transformers for N conductor with copper connection pieces Size II, 3WL9 111-0AA22-0AA0 Size I, 3WL9 111-0AA31-0AA0 1 5 4 1 R 2 7 6 5 ,5 N S E 0 _ 0 1 3 7 6 5 4 1 1 5 1 3 1 1 3 ,5 1 7 0 9 7 4 1 6 1 R 1 5 3 × 1 0 3 1 5 0 ,5 3 3 0 N S E 0 _ 0 1 3 7 7 4 5 Size II, 3WL9 111-0AA32-0AA0 3 0 3 Size III, 3WL9 111-0AA23-0AA0 1 0 7 1 2 3 5 5 8 3 5 1 8 8 9 5 1 1 3 N S E 0 _ 0 0 6 0 6 b 9 1 1 3 0 6 8 5 1 2 4 4 4 Ø Ø 1 3 ,5 5 1 9 1 Door cut-out for operator panel 1 7 0 1 3 0 6 8 5 1 2 4 4 4 1 6 0 1 8 4 Door cut-out with edge protector N S E 0 _ 0 0 6 0 7 b 2 9 5 9 0 1 1 3 Inner dimensions with mounted edge protector 1 3 1 3 4 0 Size III, 3WL9 111-0AA33-0AA0 3 0 3 0 3 × 1 0 3 0 5 2 2 4 0 1 3 ,5 1 6 0 1 8 4 N S E 0 _ 0 0 1 6 4 c 1 7 0 N S E 0 _ 0 0 6 0 8 b 9 1 1 3 0 6 8 5 1 2 4 4 4 Ø Door cut-out for operator panel using the door sealing frame 1 2 3 Option with/without door interlocking 3 1 4 3 0 0 1 2 0 Ø 5 ,5 4 0 3 ) N S E 0 _ 0 0 6 1 0 c 2 ) 5 ,5 Ø 1 8 5 1 8 0 4 0 1 2 0 5 ,5 6 5 ■ Dimensions for option with door interlocking 1 4 0 1 7 5 3 5 0 Ø 1 4 0 R 5 R 5 2) Center SENTRON 3WL5 operator panel 3) 8 mounting holes for door sealing frame 4) 3 mounting holes for door interlocking 1 1 ,5 1) Mounting surface 1 ) 1 2 2 1 4 ) 4 0 Siemens LV 16 · 2009 4/51 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Project planning aids CubicleBUS modules Breaker Data Adapter (BDA) 3WL9 111-0AT2.-0AA0 70 3WL9 111-0AT28-0AA0, 3WL9 111-0AT33-0AA0 81,9 45,5 38 19 153 16(B 94 47,5 86 16(B 6 30 Door cut-out for operator panel using protective cover IP55 NSE0_01910 Protective cover, IP55 4 x R5 4 ° 80 70 Circuit breaker mounting level 330 352 Lateral Rear (each side) mm mm Size I, fixed-mounted version 480 600 751) 751) Size I, withdrawable version, with arc chute cover 480 600 0 0 751) 751) Size II, withdrawable version, with arc chute cover 480 600 0 0 0 0 751) 751) Size III, withdrawable version, with arc chute cover 480 600 0 0 02) 02) 0 0 0 0 0 0 Lateral Rear (each side) mm mm 480 600 150 300 20 50 20 125 480 600 14 14 100 100 14 14 480 600 250 600 50 100 20 140 50 225 14 14 20 100 20 125 50 200 14 14 Size II, withdrawable version, with arc chute cover 02) 2) 0 0 0 0 0 0 0 480 600 14 14 Size III, fixed-mounted version 02) 2) 0 480 600 75 500 Size III, withdrawable version, with arc chute cover 0 0 Value for plate; 0 mm for struts and grids 2) 40 mm (size II: 70 mm) for plates which cover the lateral openings in the guide frame Siemens LV 16 · 2009 Above auxiliary connector mm Size II, fixed-mounted version 1) 4/52 Rated operational voltage V/AC Size I, withdrawable version, with arc chute cover Size III, fixed-mounted version 480 600 149 Size I, fixed-mounted version 0 0 Size II, fixed-mounted version 480 600 Circuit breaker mounting level Safety clearances from live parts Safety clearances from grounded parts Rated operational voltage Above auxiliary connector V/AC mm 17 NSE0_01909 77 295 444 116 340 4 x Ø5,5 480 600 14 14 All safety clearances above the circuit breaker refer to the upper edge of the auxiliary connector - not to the upper edge of the arc chute! See dimensional drawings on pages 4/53 to 4/58, parts 4) and 5). © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Project planning aids Size I, up to 1600 A, fixed-mounted version, 3- and 4-pole 4) 55 4 7 421 N S E 0 _ 0 0 6 1 2 c e 55 3) 123,5 2 ) 8 2 60 90 90 90 Front connection (double hole) according to DIN 43673 Ø 13,5 4 7 55 40 9 ) 6 0 ,5 26 d c 55 55 55 NSE00616b 421 11) f 4 N S E 0 _ 0 0 6 1 4 c 40 14 7 6 a 6 80 2 7 5 1 5 0 5 ,5 2 0 3) g 3 2 7 ,5 5 4 1 ,5 4 6 1 ,5 a N S E 0 _ 0 0 6 1 5 c 80 8 ) 3 3 ,5 3 ) 11) 35 434 NSE00611 1 ) 55 6 15 10 270 300 390 55 Æ 13,5 275 439,5 5) 35 Optional connection variants Front connection (single) NSE00613b Standard version Horizontal connection 4 5 1 3 0 1 5 0 2 1 0 2 3 0 c 8 2 6 ) 60 90 90 90 1 0 6 1 2 7 Vertical connection 35 90 90 90 60 55 3 5 1 1 ) b NSE00619 6 0 Ø 13,5 11) NSE00617a N S E 0 _ 0 0 6 1 8 c 1 2 7 ,5 ØM8 3) 3 0 7) 2 6 7 ,5 3) 7) 139 320 410 58 1 3 ,5 1 1 3 ,5 1 2 8 ,5 60 90 90 90 NSE00620 3) 60 90 90 90 ——— 4-pole version (on request) 1) Mounting space for removal of the arc chutes. 2) Space above arc chute, space for electrical auxiliary circuit connections. 3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the system. 4) Auxiliary connector with screw connections (SIGUT). 5) Auxiliary connector with screwless connection method (tension spring). 6) Dimension to inside surface of the closed cabinet door. 7) Fixing points for mounting the circuit breaker in the system. 8) "Secure OFF" locking device. Rated circuit a breaker current b c d e f g A Up to 1000 10 10 10 11 451 34 541 1600 15 15 15 6 461 39 551 For safety clearances to grounded parts and to live parts see page 4/52. 9) Key operation. 11) Terminal face. Siemens LV 16 · 2009 4/53 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Project planning aids Size I, up to 1600 A, withdrawable version, 3- and 4-pole 2 6 0 38 Ø 13,5 b 55 2 8 7 NSE00628a 30 150 165 9 0 1 5 9 0 9 0 Flange connection M 5 5 5 5 1 2 3 3 55 55 55 55 121 2 8 7 5 9 6 9 6 ) 1 5 9 0 9 0 9 0 38 4 2 3 ) 1 4 2 ,5 4 5 5 8 8 8 ,5 1 2 1 ,5 1 4 0 ,5 2 2 0 3 6 7 ,5 3 8 2 ,5 2 7 2 8 2 ,5 7 6 1 0 ) 4 0 4 2 6 1 5 0 3 1 2 7 5 5 9 a 3 ) 2 6 0 5 5 5 5 3 2 7 ,5 4 6 0 3 5 0 14 a 8 ) 9 ) NSE00631 7 ) N S E 0 _ 0 0 6 2 4 b N S E 0 _ 0 0 6 3 2 a 13 210 300 10) 3 ) 6 9 123,5 267,5 127,5 275 465,5 30 60 4) 3 5 0 11) N S E 0 _ 0 0 6 2 9 a 320 270 5) Optional connection variants Vertical connection NSE00621 Standard version Horizontal connection Ø 13,5 NSE00627a 11) 139 270 320 410 68 25 NSE00630 3) 10) 55 15 90 90 90 10) ——— 4-pole version (on request) 3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the system. Rated circuit breaker current 4) Auxiliary connector with screw connections (SIGUT). A 5) Auxiliary connector with screwless connection method (tension spring). Up to 1000 6) Dimension to inside surface of the closed cabinet door. 1600 7) SENTRON 3WL5 in connected position. For safety clearances to grounded parts and to live parts see page 4/52. 8) SENTRON 3WL5 in test position. 9) SENTRON 3WL5 in disconnected position. 10) Fixing holes 9 mm. 11) Terminal face. 4/54 Siemens LV 16 · 2009 a b c 10 15 10 15 10 15 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Project planning aids Size II, up to 3000 A, fixed-mounted version, 3- and 4-pole Optional connection variants Front connection (single) 4) 5) 90 4 7 90 90 40 421 90 4 7 130 130 90 40 90 13,5 40 90 90 3) NSE00638c 6 11) 1 5 0 a 14 2 7 5 g 3 ) 421 3 2 7 ,5 5 4 1 ,5 4 6 1 ,5 a N S E 0 _ 0 0 6 3 7 d 80 2 ) 130 8 2 Front connection (double hole) according to DIN 43673 1 ) 11) 35 26 d c 40 NSE00633 123,5 3) 10 85 570 NSE00635c N S E 0 _ 0 0 6 3 4 d 6 e 434 275 435,5 40 270 440 90 35 Standard version Horizontal connection c 80 6 ) 40 f 5 ,5 4 5 1 3 0 1 5 0 2 1 0 2 3 0 7 6 2 0 N S E 0 _ 0 0 6 3 6 d 90 130 130 130 4 13,5 8 2 1 0 6 1 2 7 9 0 3 0 9 0 1 3 ,5 3) 5 9 0 1 2 8 98 134,5 9 N S E 0 _ 0 0 6 3 9 d 4 × 1 3 9 4 6 0 NSE00641 1 1 ) 7 ) 3 ) 290 7 ) 30 3 0 b Ø 13,5 1 3 0 3 5 1 3 0 30 Vertical connection, up to 3000 A 1 3 0 35 NSE00640b 11) 90 113,5 128,5 130 130 130 ——— 4-pole version (on request) 1) Mounting space for removal of the arc chutes. 2) Space above arc chute, space for electrical auxiliary circuit connections. 3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the system. Rated circuit a breaker current b c d e f g A 4) Auxiliary connector with SIGUT screw terminals. Up to 2000 10 10 10 11 451 34 541 5) Auxiliary connector with tension spring connection. 2500 15 15 20 6 461 39 551 6) Dimension to inside surface of the closed cabinet door. 3000 30 30 20 6 461 39 551 7) Fixing points for mounting the circuit breaker in the system. For safety clearances to grounded parts and to live parts see page 4/52. 11) Terminal face. Siemens LV 16 · 2009 4/55 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Project planning aids Size II, up to 3000 A, withdrawable version, 3- and 4-pole Standard version Horizontal connection Optional connection variants Vertical connection up to 3000 A 4) 5 3 0 11) 38 30 30 275 465,5 b N S E 0 _ 0 0 6 5 1 a 2 8 7 6 9 135 123,5 290 3 ) 100 461 4 0 0 NSE00650a 5) NSE00643a 270 350 10) 40 157 172 10) 55 5 5 4 5 1 3 0 1 3 0 1 3 0 480 5 3 0 1 2 9 0 N S E 0 _ 0 0 6 5 4 a 4 0 0 M 4 0 4 27 42 5 9 2 8 2 ,5 76 6) 121 4 5 1 3 0 1 3 0 1 3 0 30 38 30 45 58 88,5 121,5 140,5 6 9 31 40 220 367,5 382,5 2 8 7 3 ) 10) 1 4 2 ,5 150 275 5 9 2 6 3 3 327,5 a 460 a 40,5 8) 9) NSE00653 Flange connection 7) NSE0_01911 Ø 13,5 NSE00649a 11) 139 270 460 590 90 90 90 NSE00652a 90 138 95 3) 10) 55 45 130 130 130 10) ——— 4-pole version (on request) 3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the system. Rated circuit breaker current 4) Auxiliary connector with SIGUT screw terminals. A a b c 5) Auxiliary connector with tension spring connection. Up to 2000 10 10 10 6) Dimension to inside surface of the closed cabinet door. 2500 15 15 20 7) SENTRON 3WL5 in connected position. 3000 30 30 20 8) SENTRON 3WL5 in test position. For safety clearances to grounded parts and to live parts see page 4/52. 9) SENTRON 3WL5 in disconnected position. 10) Fixing holes, diameter 9 mm. 11) Terminal face. 4/56 Siemens LV 16 · 2009 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Project planning aids Size III, up to 5000 A, fixed-mounted version, 3- and 4-pole Optional connection variants Front connection (single) up to 4000 A 5) 4) 160 47 NSE00655 NSE00656c 160 NSE00657c 3) 11) 26 12 205 160 50 130 20 82 210 210 35 270 680 11 890 160 50 421 451 6 123,5 434 275 439 13,5 35 Standard version Horizontal connection up to 5000 A 210 Front connection (double hole) according to DIN 43673 up to 4000 A 1 ) 2 ) Ø 1 3 ,5 1 6 0 5 0 5 0 1 6 0 5 0 5 0 1 6 0 1 6 0 N S E 0 _ 0 0 6 5 9 d 3 ) N S E 0 _ 0 0 6 6 0 c 6 4 2 1 2 7 5 3 ) 5 4 1 3 2 7 ,5 5 4 1 ,5 4 6 1 ,5 3 0 8 0 4 0 4 7 1 1 ) 8 0 2 0 6 ) 2 1 0 1 3 0 4 0 5 ,5 4 5 1 3 0 1 5 0 2 1 0 2 3 0 3 4 N S E 0 _ 0 0 6 5 8 d 1 4 7 6 1 5 0 3 0 2 0 2 1 0 2 1 0 8 2 1 0 6 1 2 7 Vertical connection up to 5000 A N S E 0 _ 0 0 6 6 1 d 4 × 9 1 4 1 3 9 7 0 4 9 2 4 8 20 10 107 15 30 1 1 ) 7 ) 3 ) NSE00663 3) 11) 330,5 1 3 ,5 1 3 0 40 94,5 120 7 ) 2 1 0 1 5 3 5 1 6 0 40 Ø 13,5 142 162 NSE00662a 2 1 0 2 1 0 3 0 85 210 210 210 NSE00664a 3) 130 210 210 210 130 ——— 4-pole version (on request) 1) Mounting space for removal of the arc chutes. 2) Space above arc chute, space for electrical auxiliary circuit connections. 3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the system. 4) Auxiliary connector with SIGUT screw terminals. 5) Auxiliary connector with tension spring connection. 6) Dimension to inside surface of the closed cabinet door. 7) Fixing points for mounting the circuit breaker in the system. 11) Terminal face. For safety clearances to grounded parts and to live parts see page 4/52. Siemens LV 16 · 2009 4/57 4 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Project planning aids Size III, up to 5000 A, withdrawable version, 3- and 4-pole 10) 800 270 590 160 38 11) 2 0 1 0 N S E 0 _ 0 0 6 7 3 b 2 8 7 10) 57 6 3 0 7 0 4 24 177 197 Ø 13,5 6 9 123,5 461 10) 8 4 0 NSE00672a NSE00665a 30 4) 275 466,5 5) Optional connection variants Vertical connection up to 5000 A 330,5 94,5 124,5 Standard version Horizontal connection up to 5000 A 5 7 a b 5 9 0 b 2 1 0 8 0 0 9 1 4 Flange connection, up to 4000 A 1 6 0 1 6 0 1 6 0 M 3 3 327,5 30 5 3 0 2 1 0 5 7 8 5 121 2 1 0 5 9 0 2 1 0 8 0 0 9 1 4 Ø 13,5 30 38 30 5 9 2 8 7 27 42 6) 6 9 45 58 88,5 121,5 140,5 220 367,5 382,5 31 40 4 76 10) 2 8 2 ,5 1 4 2 ,5 2 6 150 5 9 275 30 460 3) N S E 0 _ 0 0 6 7 6 a 8 4 0 6 3 0 7 0 4 1 6 0 1 2 30 8) 9) NSE00675 7) NSE0_01912 40,5 NSE00671a 11) 914 160 160 160 NSE00674 160 260 217 139 270 704 57 85 210 210 210 ——— 4-pole version (on request) 3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the system. Rated circuit breaker current 4) Auxiliary connector with SIGUT screw terminals. A 5) Auxiliary connector with tension spring connection. 4000 5000 6) Dimension to inside surface of the closed cabinet door. 7) SENTRON 3WL5 in connected position. 8) SENTRON 3WL5 in test position. 9) SENTRON 3WL5 in disconnected position. 10) Fixing holes, diameter 9 mm. 11) Terminal face. 4/58 Siemens LV 16 · 2009 a b 40 40 210 210 For safety clearances to grounded parts and to live parts see page 4/52. © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Project planning aids Installation conditions for UL circuit breakers NSE0_01585 W2 1) H D 2 2) D 1 3) NSE0_01584 W1 4 1) Ventilation opening on top. 2) Insulation plate, e.g. NEMA GPO-3 material, min. 2.3 mm thick. 3) Ventilation opening on bottom. Size In max Minimum dimensions of the installation space Dimensions of the insulation plate Height H Depth D1 Width W2 3/4-pole Depth D2 Ventilation A Width W1 3/4-pole I I 800, 1000 1250, 1600 400/500 400/500 4601) 4601) 380 380 350/450 350/450 300 300 Not required II II II 800, 1600, 2000 2000 3000 500/600 500/600 500/600 4601) 4601) 4601) 380 380 380 450/550 450/550 450/550 300 300 300 Not required III III 4000 5000 800/1000 800/1000 4601) 4601) 380 380 750/900 750/900 300 300 Not required 1) Height of installation compartment applies in case of roof insulation or for guide frame with arcing space cover. UL certificate 3WL5 circuit breakers are not listed by Underwriters Laboratories (UL) under the Order No. but as individual components with their corresponding order numbers. The UL designation of the basic circuit breaker (without electronic trip unit, auxiliary trip unit, auxiliary switch, ...) is visible on the operator panel. The file numbers are: E231263 for circuit breakers E236088 for accessories E236299 for guide frames Designation of basic circuit breaker: 3WL51 10-3 FB 32 $ $ % & ( % &( Order No. 1st to 8th position 9th and 10th position: ETU electronic trip unit 11th position: Number of poles 12th position: Version 1, 2, 3, 4: Fixed mounting 5, 6, 7, 8: Withdrawable versions The file number can be obtained from the following Internet site: http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/ gfilenbr.html Siemens LV 16 · 2009 4/59 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Project planning aids ■ Schematics Terminal assignment diagram Interne Beschaltung Internal wiring optional Zubehör / Accessories (Hilfsschalter S1, S2 = Standard) (Auxiliary switch S1, S2 = Standard) Externe Beschaltung External wiring L / L+ s/ c N / L– 14 G-Wandler / G transformer S2 12 G-Wandler / G transformer S1 11 N-Wandler / N sensor S2 10 N-Wandler / N sensor S1 9 z.B. Wandler im TransformatorSternpunkt oder Summenstromwandler 1200 A /1 A e.g. current transformer in the star point of power transformer or a summation current transformer 1200 A /1A Brücke, wenn kein N-Wandler Short terminals if no N-sensor ext. Spannungswandler Stern / ext. voltage transformer Com 8 L1 ext. Spannungswandler / ext. voltage transformer L3 7 L2 ext. Spannungswandler / ext. voltage transformer L2 6 L3 ext. Spannungswandler / ext. voltage transformer L1 5 N 13 Speicherzustandsmeldung / "Spring charged" signal S21 11 Elektrisch "EIN" / Local electric close S10 9 13 12 10 8 7 6 Meldeschalter am ersten Hilfsauslöser / S22 Signaling contact at the 1 st auxiliary release 5 4 3 Meldeschalter am zweiten Hilfsauslöser / S23 Signaling contact at the 2nd auxiliary release 2 1 2 3 4 5 6 7 8 9 14 /COM16 (Option F02/F12) L / L+ s/ c Internal Ausgelöst-Meldeschalter (Stellung nach Auslösung) / trip signalling switch S24 (position after tripping) Abschlusswiderstand, wenn kein externes CB-modul! Termination resistor, if not external CB-module! External 1 Open – + OUT F1, 2 2 BUS Y1 BUS + 24 V DC input Close – + 3 Free – + 4 DPWrite Free Enable 0 V DC 24 V DC IN Not available with communication connection "F02" or “F12”. COM15/COM16 module is at position "-X7". Fern-Rücksetzmagnet / Remote reset bell alarm & tripped indicator F7 Nicht vorhanden bei Kommunikationsfunktion "F02" oder “F12”. Auf der Position von "-X7" befindet sich das Modul COM15/COM16. 4 Klemmen Terminals 1 Erster Hilfsauslöser F1 "f" / 1st auxiliary release F1 "ST" 14 L / L+ 13 N / L– c 12 S1 "S" / "NO" 11 10 S1 "Ö" / "NC" 9 Einschaltmagnet / Closing solenoid 8 N / L– 7 L / L+ c 6 5 Einschaltbereitschaftsmeldung / "Ready to close" signal S20 4 S2 "S" / "NO" 3 2 S2 "Ö" / "NC" 1 nur F4 "Schnell AUS" / F4 only "quick OFF" 14 nur F4 "Schnell AUS" / F4 only "quick OFF" 13 Zweiter Hilfsauslöser: F2 "ST", F3 "UVR", F4 "UVR td" / 2nd auxiliary release: F2 "ST", F3 "UVR", F4 "UVR td" 12 11 10 S3 "S" oder S7 "S" / S3 "NO" or S7 "NO" 9 8 S3 "Ö" oder S7 "S" / S3 "NC" or S7 "NO" 7 6 S4 "S" oder S8 "S" / S4 "NO" or S8 "NO" 5 4 4/60 Siemens LV 16 · 2009 NSE0_00605 o S4 "Ö" oder S8 "S" / S4 "NC" or S8 "NO" Motorantrieb / Charging motor opt.: Motorabstellschalter / opt. motor main switch S12 NOT-AUS oder Brücke EMERGENCY OFF or short terminals L / L+ c N / L– (sw) M (br) 3 2 1 L / L+ N / L– c © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Project planning aids Example of an overall circuit diagram for SENTRON 3WL5 (3WL5. ..–.....–4GN4–Z C11+ C22 + K07) Manual/motorized operating mechanism with stored-energy feature with electrical ON button (option C11), with ready-to-close signaling L1 (L+) enabling contacts switch (option C22), with LSING electronic trip unit, with "UVR" undervoltage release (F3), with "ST" shunt trip unit (F1), with tripped signal switch (option K07), with auxiliary switch 4 NO + 4 NC. L1 (L+) OFF Version electr. ON -X5.6 -X5.4 -X5.10 -X5.8 -X6.4 -X6.2 -X6.12 -X6.10 ETU L -S10 -A1 5 1 3 -X6.6 -X7.12 -X7.14 -X5.12 -X6.14 -X6.7 -X7.9 -X5.2 ON S I N N G -S11 -F3 -Y1 U< -T2 NSE0_01913 -T3 -S12 -A1 -S1/-S2 -S3/-S4 -S7 (optional) F1 F2 -S8 (optional) F3 Q1 S1 & S2 S3 & S4 1 S24 A1 2 T1 T2 T3 T4 3 -S10 -S11 -S12 NSE0_01559c L S I N N G -X5.5 -X5.3 -X5.7 -X6.3 -X6.1 -X6.9 -X6.11 -X5.9 (2 NO + 2 NC) S1+S2 (4 NO + 4 NC) S1+S2+S3+S4 (6 NO+ 2 NC) S1+S2+S7+S8 (5 NO + 3 NC) S1+S2+S3+S8 -S20 -S24 Electrical ON button Internal motor shutdown switch (if spring is tensioned) Motor shutdown switch (no automatic tensioning of spring) Ready-to-close signaling switch Tripped signal switch -F1 -F3 -F5 1st auxiliary trip unit shunt trip unit 2nd auxiliary trip undervoltage release Tripping solenoid -M -P -QS -Q1 -T1/-T2/-T3 -X5/-X6/-X7/-X8 -Y1 -R Motor for "charging store" Spring energy store Actuator lever for "stored-energy feature" Main contacts Current transformers Terminals Closing solenoid Indicator and reset button for electronic trip unit -X8.9/-X8.10 Connection option: external neutral conductor trans former F5 Y1 Electronic trip unit ETU 1st auxiliary switch block (2 NO + 2 NC) 2nd auxiliary switch block (2 NO + 2 NC) 2nd auxiliary switch block, S7 (2 NO) can be used if there is no S3 - S3 and S7 have the same terminal assignment/mounting space 2nd auxiliary switch block, S8 (2 NO) can be used if there is no S4 - S4 and S8 have the same terminal assignment/mounting space 3WL5. ..-.....-...2 3WL5. ..-.....-...4 3WL5. ..-.....-...7 3WL5. ..-.....-...8 F4 M1 P 4 * Jumper, if no neutral transformer Function diagram of SENTRON 3WL5 circuit breaker S20 6 2 4 -X8.9 N (L-) * -X8.10 -X7.13 -X6.5 -X5.11 -X6.8 -X6.13 -F1 -X5.1 N (L-) -S4 -S3 -T1 M mech. ON -S2 -S1 -Q1 P QS mech. OFF -S24 -F5 -S20 R Siemens LV 16 · 2009 4/61 © Siemens AG 2008 SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According to UL 489/IEC 60947-2 for AC up to 5000 A Project planning aids Example of the mode of operation of Zone Selective Interlocking functionality in power distribution 5 6 1 2 3 4 ZSI module ZSI module SENTRON 3WL 3 4 5 6 ZSI module SENTRON 3WL 3 4 5 6 SENTRON 3WL ZSI module SENTRON 3VL NSE0_01898 SENTRON 3WL 3 4 5 6 NSE0_01897 ZSI module SENTRON 3WL 3 4 5 6 SENTRON 3WL 3 4 5 6 ZSI module SENTRON 3WL 3 4 5 6 ZSI module SENTRON 3WL 3 4 5 6 ZSI module ZSI module SENTRON 3WL 3 4 5 6 Connection diagram for a Zone Selective Interlocking functionality with multiple infeed and several outgoing units with SENTRON 3WL5 circuit breakers SENTRON 3VL and SENTRON 3WL5 circuit breakers used in various staggered levels 5 6 1 2 3 4 ZSI module ZSI module SENTRON 3WL 3 4 5 6 ZSI module SENTRON 3WL 3 4 5 6 4 NSE0_01899 SENTRON 3WL SENTRON 3WL 3 4 5 6 ZSI module ZSI module SENTRON 3WL 3 4 5 6 Zone Selective Interlocking functionality: Connection using a coupling switch, use of SENTRON 3WL5 circuit breakers ■ More information Up-to-date information on the Internet at: http://www.siemens.com/sentron 4/62 Siemens LV 16 · 2009