Hochiki America Corporation

advertisement
DCP-AMS SERIES ADDRESSABLE MANUAL PULL STATIONS
SPECIFICATIONS
Operating Voltage (SLC)
Average Current Consumption
Ambient Temperature
Maximum Humidity
Dimensions
Mounting
17~41 VDC
550uA (Typical)
660uA (Alarm)
32°F (0 °C) ~ 120°F (49°C)
90% RH, non-condensing
3.4"W x 4.8"H x 2.0"D
Single gang or 4" square
electrical box
MODEL DESCRIPTION
DCP-AMS
DCP-AMS-KL
DCP-AMS
DCP-AMS-LP
DCP-AMS-KL
DCP-AMS-KL-LP
Single Action Hex Key Lock
Dual Action Hex Key Lock
Single Action Key Lock
Dual Action Key Lock
DESCRIPTION
The DCP-AMS are the Hochiki America series of
addressable manual pull stations that provide a fast and
practical means of manually initiating a fire alarm signal.
Both single action and dual action manual pull stations
are available. Resetting of the pull station requires either
a Cat 30 key or a 1/8" hex key (depending upon the
model used).
DCP-AMS-LP
DCP-AMS-KL-LP
STANDARD FEATURES
•
•
•
•
•
•
•
•
•
•
•
•
Addressable integrated design
All metal construction
Single and dual action models available
Extremely easy to operate
Bi-colored status LED indicates Standby and
Alarm conditions
Address is programmable in EEPROM
Address can be programmed when installed
Key lock or hex key lock models available
Enclosed switch with glass rod (included)
Terminals accept up to 14AWG wire
Surface mount back box available
ADA compliant (except LP models)
An alarm condition is actuated by pulling down on the
handle of the DCP-AMS and DCP-AMS-KL single action
models. On the dual action models DCP-AMS-LP and
DCP-AMS-KL-LP the Lift and Pull cover must be lifted
before pulling down on the pull station handle. Once
the pull station is activated, the handle cannot be put
back into a normal standby condition without using the
key operated reset feature.
The DCP-AMS series is electronically addressable and
includes a bi-colored status LED. The LED blinks green
indicating normal communication with the DCP
compatible SLC loop. When an alarm condition is
actuated by pulling the handle, the LED will latch Red
to indicate the alarm condition.
PRODUCT LISTINGS
California State
Fire Marshal
S6512
Specifications subject to change without notice.
Hochiki America Corporation
7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com
3033215
7150-0410:169
Continued on back.
Find latest revision at www.hochiki.com
F0066
09/2012
ENGINEERING SPECIFICATIONS
Manual pull stations shall be Hochiki addressable AMS-series single or dual action models, DCP-AMS, DCP-AMSKL, DCP-AMS-LP, or DCP-AMS-KL-LP. Models shall be made of 14 AWG CRS and painted with Red enamel. The
words Fire Alarm shall be in a contrasting color and be embossed text 1/2" tall. The electronics shall be fully
integrated into the manual pull station requiring only connection to the SLC loop of the control panel. Programming of
the manual pull station address must be possible with the manual pull station fully installed.
Manual pull stations shall be Underwriters Laboratories Inc. Listed, CSFM Approved, and be installed within the limits
defined in the Americans With Disabilities Act.
WIRING DIAGRAMS
Hochiki America Corporation
DCP-AMS
OUT TO
NEXT
MODULE
Addressable Manual Pull Station
Ser. No.
SC-
S+
SC-
S+
For Proper Installation, see HA-06-135 Rev 12/05
S6512
NON-CODED ALARM BOX
36CC
UL
Listed
+ S
Hochiki
DCP
- SC
Compatible
Panel
TYPICAL WIRING DIAGRAM EXAMPLE, CONNECTED
TO A COMPATIBLE LISTED CONTROL PANEL
Class B (Style 4)
Hochiki America Corporation
DCP-AMS
Hochiki America Corporation
DCP-AMS
Hochiki America Corporation
DCP-AMS
Addressable Manual Pull Station
Addressable Manual Pull Station
Addressable Manual Pull Station
Ser. No.
Ser. No.
Ser. No.
S+
SC-
S6512
+ S
UL
Listed
- SC
Hochiki
DCP
+ S
Compatible
Panel
- SC
SC-
S+
For Proper Installation, see HA-06-135 Rev 12/05
NON-CODED ALARM BOX
36CC
S+
SC-
For Proper Installation, see HA-06-135 Rev 12/05
For Proper Installation, see HA-06-135 Rev 12/05
S6512
S6512
NON-CODED ALARM BOX
36CC
NON-CODED ALARM BOX
36CC
Class A Return (Style 6)
Class A (Style 7)
Hochiki America Corporation
DCP-AMS
Hochiki America Corporation
DCP-AMS
Addressable Manual Pull Station
Addressable Manual Pull Station
+
For Proper Installation, see HA-06-135 Rev 12/05
(OUT) S
(OUT) SC
S6512
NON-CODED ALARM BOX
36CC
DCP-SCI
SC-
SER. NO. XXXXXXXXX
S+
LISTED
SIGNALING DEVICE
ISSUE NO. AH-9774
(IN) SC
Hochiki America Corporation
(IN) S
S5694
DCP-SCI
SER. NO. XXXXXXXXX
LISTED
SIGNALING DEVICE
ISSUE NO. AH-9774
(OUT) S
(OUT) SC
Hochiki America Corporation
(IN) SC
S5694
NON-CODED ALARM BOX
36CC
(IN) S
For Proper Installation, see HA-06-063 Rev 2/02
S6512
DCP-SCI
For Proper Installation, see HA-06-135 Rev 12/05
(OUT) S
(OUT) SC
SER. NO. XXXXXXXXX
SC-
LISTED
SIGNALING DEVICE
ISSUE NO. AH-9774
S+
Hochiki America Corporation
(IN) SC
S5694
(IN) S
For Proper Installation, see HA-06-063 Rev 2/02
DCP-SCI
SER. NO. XXXXXXXXX
LISTED
SIGNALING DEVICE
ISSUE NO. AH-9774
Hochiki America Corporation
UL
Listed
Hochiki
DCP
Compatible
Panel - SC
S5694
-
S
SC
For Proper Installation, see HA-06-063 Rev 2/02
+
For Proper Installation, see HA-06-063 Rev 2/02
Ser. No.
Ser. No.
(IN) S
(IN) SC
(OUT) S
(OUT) SC
S
Hochiki America Corporation DCP-AMS, DCP-AMS-LP, DCP-AMS-KL AND DCP-AMS-KL-LP
Specifications subject to change without notice.
Download