INSTRUCTION MANUAL MODEL 5617 CORROSION TEST APPARATUS Revision S – December 2014 P/N: 56-170-10/15 S/N: ____________ 2001 N. Indianwood Ave. Broken Arrow, OK 74012 Telephone: 918-250-7200 Fax: 918-459-0165 E-mail: chandler.sales@ametek.com Website: http://www.chandlereng.com Copyright 2014, by Chandler Engineering Company L.L.C. All rights reserved. Reproduction or use of contents in any manner is prohibited without express permission from Chandler Engineering Company L.L.C. While every precaution has been taken in the preparation of this manual, the publisher assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained herein. This publication contains the following trademarks and/or registered trademarks: AMETEK, CHANDLER ENGINEERING. These trademarks or registered trademarks and stylized logos are all owned by AMETEK, Inc. All other company, product and service names and logos are trademarks or service marks of their respective owners. TABLE OF CONTENTS T-1 Table of Contents General Information ....................................................................... P-1 Introduction .................................................................................................................................. P-1 Purpose and Use ...................................................................................................................... P-1 Description .............................................................................................................................. P-1 Features and Benefits..................................................................................................................... P-1 Specifications ................................................................................................................................ P-2 Safety Requirements ...................................................................................................................... P-3 Where to Find Help ....................................................................................................................... P-3 Section 1 – Installation ....................................................................1-1 Unpacking the Instrument .............................................................................................................. 1-1 Utilities Required........................................................................................................................... 1-1 Tools/Equipment Required ............................................................................................................ 1-1 Setting Up the Instrument .............................................................................................................. 1-1 System Set-up ............................................................................................................................... 1-2 Remote Panel Connection ........................................................................................................ 1-2 Section 2 – Operating Instructions ..................................................2-1 Main Control Panel........................................................................................................................ 2-1 Remote Control Panel ................................................................................................................... 2-2 Sample Preparation........................................................................................................................ 2-3 Pressurizing the Cylinder ............................................................................................................... 2-3 Heating the Cylinder ...................................................................................................................... 2-4 Manual Controller Operation ................................................................................................... 2-4 Sample Rack Reciprocation ........................................................................................................... 2-4 Cooling the Cylinder ...................................................................................................................... 2-5 Emptying the Cylinder ................................................................................................................... 2-5 Water Flushing the Cylinder........................................................................................................... 2-6 Section 3 – Maintenance .................................................................3-1 Chillers .......................................................................................................................................... 3-1 Tools Required .............................................................................................................................. 3-1 After Every Test ............................................................................................................................ 3-1 Pressure Cylinder ..................................................................................................................... 3-1 Sample Rack............................................................................................................................ 3-2 Centerline Thermocouple ......................................................................................................... 3-2 Monthly......................................................................................................................................... 3-2 Drive Motor System ................................................................................................................ 3-2 Hydraulic Pump ....................................................................................................................... 3-2 Thermocouple and Temperature Control System...................................................................... 3-2 Packing Cartridge .................................................................................................................... 3-2 Three Months ................................................................................................................................ 3-3 Oil Filter .................................................................................................................................. 3-3 Six Months .................................................................................................................................... 3-3 T-2 TABLE OF CONTENTS Air Operated Valve .................................................................................................................. 3-3 Annually ........................................................................................................................................ 3-3 Pump ....................................................................................................................................... 3-3 Heater ..................................................................................................................................... 3-3 Thermocouple and Temperature Controller .............................................................................. 3-3 Maintenance Schedule ................................................................................................................... 3-4 Section 4 – Troubleshooting Guide .................................................4-1 Section 5 - Replacement Parts .........................................................5-1 Section 6 - Drawings and Schematics..............................................6-1 Includes: 2408i Universal Indicator and Alarm Unit PREFACE P-1 General Information Introduction Purpose and Use The corrosion test apparatus was designed to test the reaction rate of corrosive liquids on metals that are subjected to high temperature and pressure under dynamic conditions in compliance with ASTM G111. The corrosive liquid and the metal coupons are placed in glass jars that are placed in a metal rack. This rack is inserted into the pressure chamber, the chamber is filled with oil, and the rack is agitated during the temperature-pressure cycle. The agitation rate is adjustable. See Sample Rack Reciprocation in Section 2 -Operation. Description The pressure vessel is an alloy steel cylinder approximately 11 inches / 28 cm in diameter with a threaded plug for closure. Heat is applied using three external heaters with 9,000 Watt (VA) capacity. They generate a maximum rate of temperature rise of 7°F per minute. Internal and external cooling coils provide cylinder cooling. The pressure chamber with the heating jacket is mounted in a stainless steel cabinet that contains all the necessary piping and controls. The motor used to agitate the samples and pump rated for 10,000 psi / 69 MPa are also located in the cabinet. The system is fully equipped with safety equipment including an over-temperature protection, a pressure rupture disc, and pressure alarm relays. Optionally, the Model 5270 Data Acquisition and Control System (DACS) can be used to acquire and plot temperature and pressure data as a function of time. The software option requires a computer and data acquisition hardware located within the instrument. Features and Benefits • • • • • Designed for safe operation including both over-temperature and over-pressure protection. Operating pressure to 10,000 psi / 69 MPa. Operating temperature to 500oF / 260oC. Sample rack can be agitated during testing with 3 different agitation angles and 3 different agitation rates. Remote control operation allowing the user to control both temperature and pressure at a distance of up to 50 feet from the instrument. PREFACE Specifications Operating Conditions: Maximum Temperature: Maximum Pressure: 75°F - 500°F / 23°C - 260°C 500°F / 260°C 10,000 psi / 69 MPa Note: The pressure rating decreases as the temperature increases (see chart below). Model 5617 Corrosion Test Apparatus Pressure Rating Schedule 10000 9000 8000 7000 Press ure, psig P-2 6000 5000 4000 Safe Usage Area 3000 2000 1000 0 75 20 0 400 500 Temperature, Deg. F Input Voltage: Input Power: Heater Wattage: 230 VAC ± 15%; 50/60 Hz ± 10% 10 KVA 9000 Watts Dimensions: 67 in. / 170 cm high x 39 in. / 99 cm wide x 33 in. / 84 cm deep Net Weight: 2200 lbs / 998 kg Specimen Capacity: 20 – 4 fl. oz. sample bottles (or) 8 – 8 fl. oz. sample bottles 40o, 60o, or 80o 35, 60, or 100 cycles/minute 2oC/minute Agitation Angles: Agitation Rate: Maximum Temperature Rise: PREFACE P-3 Safety Requirements READ BEFORE ATTEMPTING OPERATION OF INSTRUMENT The Chandler Engineering Model 5617 Corrosion Test Apparatus is designed for operator safety. Any instrument that is capable of high temperatures and pressures should always be operated with CAUTION!! To ensure safety: • • • • • • • • • • Locate the instrument in a low traffic area. Post signs where the instrument is being operated to warn non-operating personnel. Read and understand instructions before attempting instrument operation. Observe caution notes! Observe and follow the warning labels on the instrument. Never exceed the instrument maximum temperature and pressure ratings. Always disconnect main power to the instrument before attempting any repair. Turn off the heater at completion of each test. Appropriately rated fire extinguishers should be located within close proximity. Note that the flash point of the mineral oil used in this instrument is less than the maximum operating temperature of the instrument. The auto ignition temperature of the mineral oil is at or above the maximum operating temperature. When operating the instrument at the maximum operating temperature, take appropriate steps to minimize the chance of fire if a leak should develop. Where to Find Help In the event of problems, contact your local sales representative or Chandler Engineering: • • • • Telephone: Fax: E-mail: Website: 918-250-7200 918-459-0165 chandler.sales@ametek.com www.chandlereng.com Instrument training classes are also available. P-4 PREFACE This page is intentionally left blank. SECTION 1 – INSTALLATION 1-1 Section 1 – Installation Unpacking the Instrument Remove the instrument from the packing crate carefully. The unit comes fully equipped with all the necessary components and ordered spare parts. Make sure that no parts are lost when discarding the packing materials. Place the instrument on a firm table, close to the water source and required electrical outlets. After the instrument is removed from the shipping crate, the equipment and spare parts should be checked against the packing list to ensure that all parts have been received and none are damaged. Note: File an insurance claim with your freight carrier if damage has occurred during shipping. Verify all parts shown on the enclosed packing list have been received. If items are missing, please notify Chandler Engineering immediately. Utilities Required Your unit will require dry, oil-free compressed shop air (not instrument quality) of 100 to 130 psi / 689 – 896 kPa, and a water supply of 20 to 80 psi / 138 – 552 kPa. The unit is capable of operating in ambient temperatures from 50°F to 120°F / 10°C - 49°C. Tools/Equipment Required An English unit mechanics tool set is adequate for the installation, operation, and maintenance of the instrument. No special tools are required. This unit is supplied with an accessory kit, which includes the necessary hardware for the water, air, and electrical hook-ups. The water and air hose may be cut to length and the appropriate barbed fittings inserted into the hose and clamped into place. Caution: The laboratory electrical power wiring must be capable of a 45-ampere load and comply with local electrical codes. The instrument must be securely connected to an appropriate earth ground. The ground wire must have a larger diameter than that of the supply voltage conductors. Setting up the Instrument The air, drain, and water connections are made at the lower rear of the instrument. The inlets are 1/4in. female pipe thread. The installation kit, provided with the instrument, contains the necessary hose and fittings to make the connections. Electrical connections are made using the 50-ampere rated connector and power cord provided with the instrument. Be certain that all power wiring is rated for the 45-ampere load. The wiring must be installed in accordance with local electrical codes, and the entire instrument must be securely connected to a separate ground. 1-2 SECTION 1 – INSTALLATION System Set-up Remote Panel Connection 56-0303 Thermocouple Cable 56-0302 Signal Cable MOD EL 5617 RS232 Cable 1. The remote panel assembly is connected to the instrument by connecting the thermocouple cable from the remote panel assembly to the labeled receptacle on the back of the instrument. The signal cable is also connected to a labeled receptacle at the back of the instrument. 2. If the system is equipped with 5270 DACS, the RS232 cable is connected to COM1 at the back of the computer. Note that an RS232/RS485 converter module is used between the computer and remote panel assembly. Connect the 5270 DACS security key to the parallel port on the computer. 3. Connect the printer cable to the parallel port with the security key. 4. Turn ON all equipment. SECTION 2 – OPERATING INSTRUCTIONS Section 2 – Operating Instructions Main Control Panel 5 4 6 7 8 9 11 10 12 13 3 16 17 18 2 MODEL 5617 1 19 ID 1 2 3 4 5 6 7 8 9 10 11 Description Thermocouple Receptacle Nameplate Caution Low Pressure Contact Pressure Gauge High Pressure Contact Drive Cooling Switch Cylinder Cooling Switch Air Exhaust Switch Air Supply Switch Pressure Release Switch 20 ID 12 13 14 15 16 17 18 19 20 21 22 21 22 Description Pump Switch Motor Switch Heater Switch Main Power Pressure and Temperature Rating Air Pressure Regulator Hoist Switch Flush Water Valve Drain Valve Pressure Release Valve Air-to-Cylinder Valve 14 15 2-1 2-2 SECTION 2 – OPERATING INSTRUCTIONS Remote Control Panel This instrument is furnished with a remote control panel, which permits operation of the instrument from a remote location. The remote panel assembly and the instrument may be separated up to 50 feet. From the remote panel, the operator may control the following items: • Control temperature using the programmable temperature controller. • Read the pressure on the digital display. • Control the pressure using the PUMP and PRESSURE RELEASE switches. • Turn the heater “ON” or “OFF” using the HEATER SWITCH. • Turn the cooling water to the cylinder jackets “ON” or “OFF” using the COOLING WATER SWITCH. • When the option exists, the remote control assembly is connected to the computer running the Model 5270 Data Acquisition and Control System (DACS). The values displayed on the temperature controller and pressure display are graphed and stored in the test data file. Note: The cylinder pressure can be automatically controlled by setting the high and low contacts of the pressure control gauge on the instrument panel to the desired pressure range. (Position switch #4 or #6 to “ON” to activate the LOW or HIGH pressure limit.) Pressure may still be controlled with the remote switches. SECTION 2 – OPERATING INSTRUCTIONS 2-3 Sample Preparation Generally, individual samples are placed inside each sample container and half filled with the corrosive media. The remaining internal volume is filled with mineral oil. To prevent rupturing the sample containers during pressure equalization, the caps must be loose. Optionally, a 1/8-inch / 4mm hole may be drilled in the cap of each sample container to provide a path for pressure equalization. Caution: The height of the 8- container rack prevents safe removal without first draining the oil from the vessel. Use caution to avoid burns when removing this rack. Rapid changes in the cylinder pressure must be avoided to prevent damage to the sample containers and increased contamination of the mineral oil. Since contamination of the mineral oil with acids is likely during a normal test, the oil in the cylinder must be replaced after each test to prevent corrosive attack of the cylinder and related components. Pressurizing the Cylinder 1. 2. 3. 4. Close all the valves. Turn the switches on the remote panel to “OFF.” Fill the reservoir with mineral oil, if required. With the cylinder to plug removed, turn “ON” the AIR SUPPLY SWITCH (#10) to partially fill the cylinder. Note that the sample racks displace considerable volume and must be taken into account when filling the cylinder. 5. Turn “OFF” the AIR SUPPLY SWITCH when the cylinder is approximately 1/2 full and turn “ON” the AIR EXHAUST VALVE SWITCH (#9). 6. The cylinder may be pre-heated at this point using the temperature controller. The rack must be placed in the cylinder to agitate the oil during the heating. Turn “ON” the MOTOR switch (#13) to agitate the rack. 7. If required, lubricate the cylinder plug threads and seal ring with high-temperature grease. This will allow the plug to be removed after the test is complete. Caution: The cylinder and rack may become extremely HOT. Severe burns can result from touching. 8. After lowering the rack with samples into the cylinder, secure plug using the technique described on drawing #19-0107. Use the torque wrench (supplied with the equipment) to progressively tighten the fasteners on top of the plug to 35 ft-lbs / 47 N-m. 9. Turn “OFF” the AIR EXHAUST SWITCH (#9) and turn “ON” the AIR SUPPLY SWITCH (#10). 10. Insert the center thermocouple and bleed displaced air through the thermocouple gland at the cylinder head, closing the gland with a 5/8 in. wrench when fluid appears. 11. Set the pressure gauge pointers on the PRESSURE CONTROL GAUGE to the desired high and low cutoff pressures. 12. Turn “OFF” the LOW and HIGH PRESSURE CONTACT SWITCHES (#4) and (#6). 13. Adjust the air pressure to the pump with the REGULATOR (#17). Air pressure is indicated on the panel gauge. The fluid/air pressure ratio is approximately 200 to 1. 2-4 SECTION 2 – OPERATING INSTRUCTIONS 14. Turn “ON” the PUMP SWITCH (#12) and allow the pressure to build to between the low and high set points on the PRESSURE CONTROL GAUGE. 15. When the desired fluid pressure is obtained, turn “OFF” the PUMP SWITCH (#12). Turn “ON” the LOW and HIGH PRESSURE CONTACT SWITCHES (#4) and (#6). The pressure gauge will control the pump and release valve to automatically maintain the preset pressures on the control gauge. Heating the Cylinder 1. Turn the REMOTE HEATER SWITCH position to “ON” and the MAIN PANEL HEATER SWITCH (#14) to “ON.” 2. Program the desired set point into the TEMPERATURE CONTROLLER. Heat will NOT be applied to the cylinder until the controller is placed in AUTO mode. If the data acquisition option exists, the 5270 DACS system may be used to program and start the controller when a test is started. 3. If the final temperature is set above 200°F, turn “ON” the DRIVE COOLING SWITCH (#7) to cool the packing during the test. Manual Controller Operation 1. Turn ON the HEATER SWITCH (#14) and the REMOTE HEATER SWITCH (#6). 2. Press the AUTO/MAN button to place the controller in automatic (AUTO) mode. 3. Press the Press (UP/DOWN) buttons to define the set point temperature. The set point value is indicated below the current temperature value. 4. The OP1 light, located towards the top of the controller display, will light indicating power is being applied to the heater. 5. The vessel temperature will converge on the defined set point value. Sample Rack Reciprocation Note: The ASTM Standards used when designing this instrument (ASTM G111 and ASTM G31) has no specific mention of agitation angles, speed, or duration used in a HPHT Apparatus. Therefore, the variables were left to the designer to determine. The reciprocating angle movement can be adjusted as desired to 40, 60 or 80 degrees, by locating the end bearing in the appropriate hole on the rotary table. The speed of reciprocation can be adjusted to either 35, 60 or 100 cycles per minute by the belt position on the three step pulleys. Please refer to the following illustration. SECTION 2 – OPERATING INSTRUCTIONS 2-5 Cooling the Cylinder 1. Turn the HEATER SWITCH (#14) to “OFF.” 2. Turn the CYLINDER COOLING SWITCH (#8) to “ON.” 3. The internal cooling coils provide cylinder cooling with resulting reduction of pressure due to thermal contraction. The control limits on the pressure gauge will maintain pressure through the cooling cycle. 4. Continue until the cylinder temperature is reduced as desired. Caution: When the cooling water is turned off, heat from the cylinder will cause the temperature to rise. Emptying the Cylinder Note that the instrument is designed to drain the mineral oil from the cylinder to the waste oil port at the back of the instrument. This allows contaminated oil to be safely removed for disposal or recycling. If uncontaminated oil must be returned to the internal reservoir, connect the waste oil port to the port located at the top of the internal oil reservoir. Caution: The waste oil may be hot from a test 1. Turn “ON” the AIR EXHAUST SWITCH (#9). Wait for the pressure to decrease to zero. 2-6 SECTION 2 – OPERATING INSTRUCTIONS 2. Open the DRAIN VALVE (#20) and AIR-TO-CYLINDER VALVE (#22). After the fluid has been drained from the cylinder, close the AIR TO CYLINDER VALVE. 3. Loosen the gland on the center thermocouple in cylinder plug, bleed off all the air and remove the thermocouple. 4. Remove the cylinder plug. Water Flushing the Cylinder 1. Turn “ON” the AIR EXHAUST VALVE SWITCH (#9). Wait for the pressure to decrease to zero. 2. Open the PRESSURE RELEASE VALVE (#21) and FLUSH WATER VALVE (#19). 3. When the cylinder has been sufficiently flushed, close the FLUSH WATER VALVE (#19) and PRESSURE RELEASE VALVE (#21). 4. Open the DRAIN VALVE (#20) and AIR-TO-CYLINDER VALVE (#22). After the fluid has been drained from the cylinder, close the AIR TO CYLINDER VALVE. 5. Loosen the gland on the center thermocouple in cylinder plug, bleed off all the air and remove the thermocouple. 6. Remove the cylinder plug. SECTION 3 – MAINTENANCE 3-1 Section 3 – Maintenance The operating life of the Corrosion Test Apparatus can be extended measurably if operating and maintenance instructions provided in this manual are used. Avoidance of safety issues, down time and parts replacement depends on the proper cleaning, lubrication, replacement of filters, and calibration of instrumentation and controls. The following procedures correspond with the maintenance schedule time intervals included in this manual. Chillers Instruments using a chiller sometimes produce condensation. The use of a fan or air conditioned environment will help in keeping the moisture level lower. Be sure to empty the drip pan often and wipe away any condensation that may occur. Tools Required Standard English mechanics tool set. After Every Test Pressure Cylinder Inspect the sealing surfaces on the cylinder plug to determine if cuts, damage, or imbedded particles are present. If none of these conditions are noticed, wipe the seal surfaces free of foreign matter. The thread of the cylinder plug has been lubricated with molybdenum disulfide grease at the factory. If molybdenum disulfide grease is not immediately available, lubricating oil will be a satisfactory substitute. The condition of the cylinder and plug must be continuously evaluated to determine if corrosion is occurring on the inner surfaces of the vessel. Mineral oil is used to pressurize the sample containers and must not be re-used because it enters the loosely capped sample containers during the test. To avoid contaminating the cylinder, replace the mineral oil after each test. Warning: The condition of the pressure vessel is extremely important for maintaining the safety of the instrument at rated temperature and pressure. If the pressure vessel becomes corroded due to contaminated mineral oil, the vessel must be replaced. Therefore, the mineral oil must be replaced after each test. 3-2 SECTION 3 – MAINTENANCE The mineral oil supplied with the 5617 is suitable for most high temperature tests. Refer to the Material Safety Data Sheet (MSDS) for the mineral oil specifications. It is not recommended to operate above the flashpoint of the mineral oil. It is the responsibility of the user to establish the appropriate safety and health practices and determine the applicable oil to be used when operating above the flashpoint of the oil supplied. Warning: If the test temperature exceeds the flashpoint of the oil, a synthetic oil with suitable properties should be used. Sample Rack All components of the sample rack must be cleaned using suitable degreasing equipment and inspected after every test. Note that residual corrosive media may be present on the sample rack. Centerline Thermocouple Inspect the thermocouple to insure that it is straight and the threaded collar is positioned with two threads showing on the lower side. Inspect the threaded collar and gland nut for clean and well-formed threads. Worn threads, on either part, present a safety hazard to the operator. If the threads are damaged, the thermocouple may blow out under pressure. Inspect the exterior of the probe for thinning or nicking. Replace any or all components as required. Monthly Drive Motor System Periodic lubrication is required for the thrust bearing, end bearings, gear reducer, and 1/4 HP motor. Suitable lubricating oil, such as SAE #10, may be used for the pump and the 1/4 HP motor. The gear reducer should be checked occasionally and replenished, if necessary. Hydraulic Pump Lubricating oil for the air hydraulic pump is supplied by the air lubricator, which has a transparent reservoir. Mineral oil is used as the lubricant. Thermocouple and Temperature Control System API specs require that the temperature measuring system be verified for accuracy monthly. No equipment is supplied with the unit for performing these tests. Review the API specs for details or contact Chandler Engineering. Packing Cartridge The packing cartridge should be removed from inside the cylinder when the reciprocating shaft packing requires replacement. Loosen the connecting rod connection, unscrew the packing gland and lock ring, and lift the cartridge from the cylinder. Examine the O-Ring, and replace if required, after repacking. SECTION 3 – MAINTENANCE 3-3 Three Months Oil Filter Replace the oil filter element every three months. Six Months Air Operated Valve 1. 2. 3. 4. 5. 6. 7. 8. Relieve system pressure. Remove the valve from the system and place it securely in a vise. Fully open the valve stem. Remove the packing gland locking device. Unscrew the packing gland and remove the packing gland and stem. Remove the packing from the body. Note the packing and washer arrangement. Replace the packing and place the packing and packing washers into the valve body. Replace the stem and packing gland, tightening to the appropriate torque. Replace the packing gland locking device. Annually Replace the High Pressure Filter, Cylinder Pressure Release Valve, and Rupture Disk. Pump Chandler Engineering recommends that the pump valve body be disassembled, cleaned and rebuilt by our Service Department. A pump rebuild kit is available from Chandler Engineering. Heater Chandler Engineering recommends that the heater be inspected and tested for insulation breakdown and voltage leakage, which can lead to arcing on the cylinder wall. This procedure requires the use of specialized test equipment. Insulation breakdown poses two potentially hazardous conditions: electrical shock hazard to the operator, and pitting of the cylinder at the point of arcing. Chandler Engineering highly recommends that our Service Department perform a series of tests on the heater at this time interval. Thermocouple and Temperature Controller Our Service Department can perform a calibration procedure using specialized instrumentation to assure that temperature drift and inaccuracies, as a result of time and usage, are compensated for, in order to keep your instrument compliant with API specs. 3-4 Inspect Pressure Transducer Calibration Calibration Disassemble, Clean, Inspect MONTHLY Replace 3 MONTHS MAINTENANCE SCHEDULE INSTRUMENT NAME Disassemble, Replace Needle, Seat 6 MONTHS This maintenance schedule applies to normal usage of two tests per day. Detailed procedures for these operations are contained in your manual. Per API Specifications σ Where Applicable Rupture Disc Reservoir Heater Inspect Clean, Inspect, Replace Mineral Oil Replace EACH TEST Disassemble, Clean, Inspect Temperature Controller Thermocouple Pressure Gauge Pump Air Operated Valve Air to Cylinder Valve Cylinder Cylinder Pressure Release Valve σHigh Pressure Filter Low Pressure Filter Oil Motor Drive COMPONENT Sample Rack and Containers Maintenance Schedule SECTION 3 – MAINTENANCE Calibration by Qualified Factory Service Technician Calibration by Qualified Factory Service Technician Test by Qualified Factory Service Technician Clean-out by Qualified Factory Service Technician Replace Maintenance by Qualified Factory Service Technician Calibration Replace Replace Replace Disassemble, Clean, Inspect ANNUAL 3-4 SECTION 3 – MAINTENANCE SCHEDULE SECTION 4 – TROUBLESHOOTING GUIDE Section 4 – Troubleshooting Guide Problem Unit will not power-up Control system components inoperative Erratic/Incorrect temperature read-out Drive motor inoperative Heater System inoperative. 1. 2. 1. 2. 1. 2. 3. 1. 2. 3. 4. 1. 2. 3. 4. 5. Will not build pressure 6. 1. 2. 3. 4. 5. Plug jammed in cylinder 1. 2. Pressure will not bleed off 1. Erratic pump action 1. 2. Solution Check fuses, replace if necessary. Check main breaker, reset if necessary. Check fuses. Check all cables. Check all thermocouple wiring and components. Replace thermocouple wiring. Replace thermocouple. Check fuses. Check wiring. Check motor – the motor could be defective. Check switch – could be defective. Check fuses. Check switch – could be defective. Check over-temperature circuit – reset or adjust, as necessary. Check the heater – could be shorted to ground. Check the SSR and the signal from the SSR to the controller. Check the controller – could be defective. Disassemble and clean air control valve body and seat per maintenance instructions. Replace stem, seat, and packing on air control valve per maintenance instructions. Close or replace pressure bleed valve. Remove cylinder plug; clean and lube; replace seal per maintenance instructions. Contact Chandler Engineering Service Department for pump rebuild. Cool down the plug and unscrew by striking the handles with a rubber mallet. This can be caused by failure to lubricate the threads, foreign matter in the seal ring, or overtightening of the plug. This can be caused by foreign material in the manual valve. Disassemble and clean the valve or replace the valve. An air lock in the pump piston cavity will cause erratic pumping action. Increase the air drive pressure gradually to slow the pumping cycle. Contact Chandler Engineering for service to the pump. 4-1 5-2 SECTION 5 – REPLACEMENT PARTS This page is intentionally left blank. SECTION 5 – REPLACEMENT PARTS Section 5 - Replacement Parts Model Number 5617 #56-0187 - CYLINDER ASSEMBLY PART NUMBER DESCRIPTION 07-0772 Plug Handle 56-0076 Seal Ring 56-0077 Lock Nut 56-0078 Thrust Washer 56-0091 Bail 56-0117 Cooling Coil - Internal 56-0126 Cooling Coil - External 56-0148 Packing Cartridge Assembly 56-0166 Cylinder Plug 56-0167 Seal Shaft 56-0176 Thermocouple, Center 56-0178 Thermocouple, Side 56-0186 Cylinder 56-0188 Jacket, Insulation 56-0209 Stud, Cylinder Support 56-0218 Adapter, Side Thermocouple P-0408 Eye Bolt P-1661 "O" Ring, Packing Cartridge P-1979 Heater, 1/2 Band P-2031 Terminal, Screw Lug #56-0189 - DOUBLE SWIVEL ARM ASSEMBLY PART NUMBER DESCRIPTION 07-0017 Cap, Pipe 07-0018 Head, Pivot 07-0021 Plate 07-0023 Ring, Pulley 07-0026 Washer, Pulley Shaft 07-0027 Shaft, Pulley, Long 07-0028 Shaft, Pulley, Short 5-1 5-2 SECTION 5 – REPLACEMENT PARTS #56-0189 - DOUBLE SWIVEL ARM ASSEMBLY PART NUMBER DESCRIPTION 07-0030 Cable, Swivel Assembly 07-0292 Lid 07-0295 Bushing 56-0103 Weight Balancing 56-0129 Drum, Hoist 56-0142 Hoist, Guard Assembly 56-0191 Swivel Arm, Lower 56-0192 Cable Assembly 56-0193 Swivel Arm 56-0206 Swivel Arm, Top 56-0207 Guide Bearing P-0010 Bearing Thrust P-0411 Eye Bolt P-0693 Collar, Pulley P-0724 Nylon Line Clip P-0800 Bearing P-0801 Retaining Rings #56-0198 - ELECTRICAL PARTS PART NUMBER DESCRIPTION C07539 Fuse, 3 Amp C07676 Receptacle, Twist-lock, Power C07833 Transducer, Pressure C08262 Relay, 45A Solid State (SSR) C09339 Power Supply C09684 Relay, 40A C09685 Heat Sink, SSR P-0627 Transformer, Step-down P-0664 Fuse, Holder P-1130 Fuse, 1 Amp P-1887 Pressure Regulator P-1982 Switch, Hoist P-1983 Motor, 1/4 HP, (60 Hz Instrument Only) P-1984 Cabinet, Electrical P-1985 Box Switch Cover, Toggle Switches SECTION 5 – REPLACEMENT PARTS #56-0198 - ELECTRICAL PARTS PART NUMBER DESCRIPTION P-2713 Motor, 1/4 HP (50 Hz Instrument Only) P-2881 Switch, SPST, Rocker, 10A, 250V P-3388 Switch, Circuit Breaker P-3431 Relay, Power, DC Control P-3657 Motor, Gear, Hoist P-3658 Motor Brake #56-0322 - REMOTE CONTROL ASSEMBLY PART NUMBER DESCRIPTION 56-0300 Panel, Front Control 56-0302 Assembly, Thermocouple Cable 56-0303 Assembly, Remote Control Cable 56-0309 Panel, Rear Control 7050 Temperature Display 70617-89 Power Cord C07546 Receptacle, 14 Pin C07638 Socket, Connector C07639 Pin, Connector C07962 Display, Input Signal C07984 Receptacle, 19 Pin C08438 Modem Cable C09043 Module, E-Therm, RS-485, 2-wire C09693 Display, Pressure C09832 Controller, Temperature MISCELLANEOUS ITEMS PART NUMBER DESCRIPTION 70-0012 Assembly, Capillary Tube C08449 Solenoid Valve, 3-way, 220V C08964 Oil Filter C11091 Pump, Hydraulic, 12500 psi P-0284 Regulator, Air Pressure P-0518 Lubricator, Air Line P-0586 Check Valve P-0674 Muffler 5-3 5-4 SECTION 5 – REPLACEMENT PARTS MISCELLANEOUS ITEMS PART NUMBER DESCRIPTION P-0711 Coupling, 1/8 in. MP P-0735 Tube Adapter P-0766 Pipe Nipple, 1/4 NPT X 5 in. Lg. P-0866 Pipe Bushing, 1/4 FP X 3/8 MP P-0906 Tube Union, 1/4 T X 1/4 T P-1059 Tube Reducer P-1074 Pipe Nipple, 3/8 NPT X 1/4 NPT P-1206 Safety Head Assembly P-1246 Tube Elbow, 1/4 T X 1/8 MP P-1285 Pipe Elbow, Street 1/2 NPT P-1380 Tube Tee, 1/4 T X 1/4 T X 1/4 T P-1486 Tube Connector, 1/4 T X 1/8 MP P-1488 Tube Connector, 1/4 T X 1/4 MP P-1496 Pipe Elbow, Street 1/4 NPT P-1500 Valve, Reservoir P-1581 Rupture Disc, 10,500 psi P-1621 Pipe Reducing Adapter, 1/8 FP X 1/16 MP P-1706 Gauge, Pressure Control P-1840 Gauge, 0-200 psi P-1980 Column, Sight Glass P-2025 Tube Reducer, 3/8T x 1/4T P-2380 Receptacle, "J" Thermocouple P-2429 Plug, "J" Thermocouple P-2610 Fuse, .25A P-2854 Valve, Air Operated, Normally Open P-3048 Power Supply, DC P-3052 Receptacle, Power P-3107 Valve, Solenoid, 220V P-3330 Relay 07-0966 Relief Valve, 10K 07-1273 Cable Assembly 56-0105 Sample Rack (8 Container) 56-0115 Sample Rack (15 Container) 56-0196 56-0157 Sample Rack (20 Container) Rotary Reciprocating Mechanism Consisting of: SECTION 5 – REPLACEMENT PARTS MISCELLANEOUS ITEMS PART NUMBER P-1312 DESCRIPTION 56-0316 Agitating Shaft 56-0137 Pivot Arm 60-0089 Rotary Table 60-0091 Connector, Rod End Bearing 60-0092 Spacer 60-0093 Base, Thrust Bearing 60-0096 Sample Rack Coupling 60-0098 Support Shaft 60-0110 Thrust Bearing, Shaft Torque Wrench P-1765 Mineral Oil P-1792 Socket Head Set Screws, 5/8-11 x 5/8 in. Lg. P-2221 Bottles, 4oz P-2222 Bottles, 8oz To ensure correct part replacement, always specify model and serial number of instrument when ordering or corresponding. 5-5 5-6 SECTION 5 – REPLACEMENT PARTS This page is intentionally left blank. SECTION 6 – DRAWIINGS AND SCHEMATICS Section 6 - Drawings and Schematics Drawing Number 07-1026 19-0107 56-0148 56-0187 56-0198 56-0201 56-0203 56-0322 5617 Description Safety Head Assembly Modified Bridgeman Seal Assembly Packing Cartridge Assembly Cylinder Assembly Wiring Diagram Tubing Diagram Control Panel Identification Remote Control Enclosure Assembly Corrosion Test Apparatus w/Remote Control Console 6-1 6-2 SECTION 6 - DRAWINGS AND SCHEMATICS This page is intentionally left blank. 1 2 3 NOTES: 1. TEST PER 56-0320. 2. TORQUE ITEM 3 PER 19-0107. 4 5 6 7 8 9 10 11 REV M DESCRIPTION ECN T5818; UPDATED HEATER VIEW N ECN T6244; UPDATED TO CURRENT ASSEMBLY PER REDLINES 1 H 12 DATE 3/17/14 APPROVED TC 11/21/2014 LDR H 23 2 25 3 4 22 5 21 6 7 G COAT THREADS WITH C12056 G 24 13 10 10 COAT SEAL RING WITH C12056 31 7X 16 F B WATER OUTLET F B 9 9 9 20 11 26 30 8 12 7X 14 E E 31 7X 16 22.19 10 13 9 11 14 D 10 9 D 30 11 16 7.750 INTERNAL COOLING COIL DETAILS 13 SECTION B-B C 9 17 WATER OUTLET 26 18 15 WATER INLET B 19 A SECTION A-A 1 2 3 4 5 6 7 8 9 THIS DOCUMENT AND THE DRAWINGS AND TECHNICAL DATA CONTAINED HEREON ARE THE PROPERTY OF CHANDLER ENGINEERING COMPANY LLC. REPRODUCTION OR DISSEMINATION IN ANY FORM EXCEPT AS EXPRESSLY AUTHORIZED BY THE OWNER IS FORBIDDEN. THE HOLDER AGREES TO RETURN THE DOCUMENT TO THE OWNER ON DEMAND. COPYRIGHT BY CHANDLER ENGINEERING COMPANY LLC 10 C ITEM PART NUMBER DESCRIPTION 1 56-0091 BAIL, PLUG 2 56-0219 ADAPTER 3 P-1792 SCREW,SKHSS,5/8-11X5/8LG,FL 4 56-0077 LOCK NUT 5 56-0078 WASHER, THRUST 56-0166 CYLINDER PLUG 6 7 56-0186 CYLINDER 8 P-1246 ELBOW,BRS,1/8MNPTX1/4T 9 P-1244 CONN,BRS,1/4TX1/8MP SW ADAPT,BRS,1/8FPX1/16MP 10 P-1621 11 P-1979 HEATR,CIR,1500W,120V,11X3.5 12 56-0178 THERMOCOUPLE ASSY 13 56-0126 EXTERNAL COOLING COIL 14 56-0117 ASSY, COOLING COIL 15 56-0148 PACKING CARTRIDGE ASSY 16 56-0218 ADAPTER 17 56-0134 PLATE - LOWER CYLINDER STUD, CYLINDER SUPPORT 18 56-0209 19 H-125-001 NUT,HEX,CD,1-1/4-12 20 56-0336 JACKET, CYLINDER INSULATION 5617 21 07-0772 HANDLE, PLUG 22 56-0167 SEAL SHAFT 23 70-0023 THERMOCOUPLE 24 56-0076 SEAL RING 25 P-0408 BOLT,EYE,.25-20X2.0,STL BUSHG,BRS,RDCG,1/8FPX3/8MP WH 26 P-0269 27 P-2031 LUG ,#14-#6 CABLE,#10 STUD 28 R-0766 WIRE,8 AWG,MICA-MAT 29 H-31-002 WSHR,SS,5/16 FLAT 30 H-31-103 NUT,KEPS,SS,5/16-18 31 H-31-014 SCREW,HHCS,SS,5/15-18 X 3.00,STD BREAK EDGES, DEBURR DRAWN: TC 03-17-14 MFG: TC UON DIMS ARE IN INCHES 03-17-14 1 PLC 0.030 2 PLC 0.010 ENGR: JJM 03-17-14 CYLINDER ASSY 3 PLC 0.005 ANGL 1/2 TYPE: PN: 56-0187 SURFACE FINISH 63 RMS PROJ: 56 THIRD ANGLE PROJECTION STRUCT: QTY 1 1 12 1 1 1 1 4 6 2 3 1 3 2 1 3 1 3 9 1 2 1 1 1 2 6 16 6 FT 7 7 7 CHANDLER ENGINEERING 11 12 REV N SIZE D SHEET 1 OF 1 TITLE BLOCK REV 3 B A 1 2 3 4 5 6 7 8 9 10 11 REV NOTES: H 1. 2. 3. 4. H REFER TO 56-0198 WIRING DIAGRAM. ROUTE ALL AC WIRING AWAY FROM T/C AND DC SIGNAL WIRING. USE CABLE 56-0303 TO CONNECT TO THE MODEL 5617 CORROSION TEST APPARATUS. USE THERMOCOUPLE CABLE 56-0302 TO CONNECT TO THE MODEL 5617 CORROSION TEST APPARATUS. 5. MOUNT POWER SUPPLY TO INNER SIDE OF ENCLOSURE USING SUPPLIED HARDWARE. 6. CONNECT CHASSIS GROUND TO ENCLOSURE USING SUPPLIED HARDWARE. 24X 22 10 20 35 DESCRIPTION ECN T6244; CONVERTED TO SOLIDWORKS FILE 12 DATE APPROVED 11/21/14 LDR H 7 39 36 9 22 22 14 38 G G 4 4 F F 4 6 4 E 15 8 40 D E 23 3 41 2 27 28 D 4 4 4 C 4 B 1 5 33 5 5 5 37 32 A 1 2 3 4 5 6 7 8 9 THIS DOCUMENT AND THE DRAWINGS AND TECHNICAL DATA CONTAINED HEREON ARE THE PROPERTY OF CHANDLER ENGINEERING COMPANY LLC. REPRODUCTION OR DISSEMINATION IN ANY FORM EXCEPT AS EXPRESSLY AUTHORIZED BY THE OWNER IS FORBIDDEN. THE HOLDER AGREES TO RETURN THE DOCUMENT TO THE OWNER ON DEMAND. COPYRIGHT BY CHANDLER ENGINEERING COMPANY LLC 10 ITEM PART NUMBER DESCRIPTION 1 C08931 CONTROLLER,1/4 DIN,ETHERM,2404 2 C09693 DISPLAY,PANL 1/8 DN ETHRM2408I 3 56-0323 PANEL - FRONT 4 H-25-028 SCREW,THMS,SS,1/4-20X0.75,PHIL 5 P-2881 SWITCH, ON/OFF 6 C09788 ENCL,19" RACK MOUNTING 7 56-0321 PANEL - REAR CONN,SQR FLG, 16 COND 8 P-3061 9 P-2380 JACK,PNL,TC,1.12,SQ FACE 10 P-2438 CONNECTOR, DSUB, DB25S 11 C09339 POWER SUPPLY,5V/+15V -15V MODULE,E-THERM,RS-485,2-WIRE 12 C09043 13 C08975 CONVERTER,RS232/RS485, 3 WIRE 14 P-3052 FILTER, POWER LINE, 2A 15 P-3062 PIN, MALE, 18-14 GA, CIRC CONN 16 P-0417 BLK,TERMINAL,6 CNDTR,6-142 17 C05545 BLK,6PT BARR TERM,6-140 JMPR ,BARR BLK,142/542 SERIES 18 P-2005 19 70607-80 JMPR,BARR BLK,142/542 SERIES 20 C07560 STDF,M-F,6-32X0.25, 1/4 HEX 21 56-0337 TAG SET,REMOTE CONTROL BOX 22 H-100000 RIVET,POP,AL,0.093X0.375L 23 H-6015 SCREW,THMS,SS,6-32X0.375,PHIL 24 H-6041 NUT,KEPS,SS,6-32 25 H-25-036 NUT,1/4-20,SS,KEPS 26 H-25-007 WSHR,FLAT,SS,1/4 27 P-0458 INDICATOR,95 SERIES W/RED LENS 28 P-2209 SWITCH,SPST,PUSH BUTTON,MOM 29 P-0452 LAMP,T-3 1/4 MIN BAYONET,230V 30 35-0005-76 LABEL, "CHANDLER 7050" 31 56-0005-109 LABEL,"CHANDLER 7085" 32 56-0337-01 TAG, PRESSURE RELEASE, MODEL 5617 TAG, CYLINDER COOLING, MODEL 5617 33 56-0337-02 34 56-0337-03 TAG, HEATER, MODEL 5617 35 56-0337-04 TAG, RS-232, MODEL 5617 36 56-0337-05 TAG, THERMOCOUPLE, MODEL 5617 37 56-0337-06 TAG, PUMP, MODEL 5617 38 56-0337-07 TAG, POWER, MODEL 5617 39 56-0337-08 TAG, TO CORR. APP., MODEL 5617 40 56-0337-09 TAG, TEMPERATURE, MODEL 5617 41 56-0337-10 TAG, PRESSURE, MODEL 5617 42 56-0337-11 TAG, HEATER RESET, MODEL 5617 BREAK EDGES, DEBURR DRAWN: LDR 11/21/2014 MFG: UON DIMS ARE IN INCHES 1 PLC 0.030 2 PLC 0.010 ENGR: ASSY, REMOTE CONTROL ENCL QTY 1 1 1 8 4 1 1 1 1 1 1 2 1 1 16 1 1 4 3 4 1 24 4 4 8 8 1 1 1 1 1 REF REF REF REF REF REF REF REF REF REF REF CHANDLER ENGINEERING 3 PLC 0.005 ANGL 1/2 SURFACE FINISH 63 RMS THIRD ANGLE PROJECTION TYPE: STRUCT: 11 PN: 56-0322 PROJ: 56 12 REV H SIZE D SHEET 1 OF 1 TITLE BLOCK REV 3 C B A 2408i INDICATOR ENG Engineering handbook 2408i Indicator Engineering Manual MODEL 2408i INDICATOR Engineering Handbook Contents 1 Installing and Operating Instructions .............................................................................................................................................. 3 1.1 Contents of package ................................................................................................................................................................. 3 1.2 Dimensions and Installation .................................................................................................................................................... 3 1.2.1 To Install the Indicator.......................................................................................................................................................... 3 1.2.2 Removing The Indicator From The Sleeve ........................................................................................................................... 3 1.3 New Sleeve Design MkIII ........................................................................................................................................................ 4 1.3.1 Details ................................................................................................................................................................................... 4 1.3.2 Reasons for the Change......................................................................................................................................................... 4 1.3.3 Recommendations ................................................................................................................................................................. 4 1.4 Electrical Connections ............................................................................................................................................................. 5 1.4.1 Wiring ................................................................................................................................................................................... 5 1.4.2 Plug-in Module Connections ................................................................................................................................................ 5 1.4.3 Communications Modules .................................................................................................................................................... 5 2 Operation............................................................................................................................................................................................ 6 2.1.1 To View The Display Units................................................................................................................................................... 6 2.1.2 Home Display Options .......................................................................................................................................................... 6 2.2 Alarms....................................................................................................................................................................................... 7 2.2.1 Types of Alarm Used In The 2408i ....................................................................................................................................... 7 2.2.2 Alarm Relay Output .............................................................................................................................................................. 7 2.2.3 Alarm Indication ................................................................................................................................................................... 8 2.2.4 Alarm Messages .................................................................................................................................................................... 8 2.2.5 Diagnostic Alarms................................................................................................................................................................. 9 2.2.6 To Acknowledge An Alarm .................................................................................................................................................. 9 2.2.7 Alarm Inhibit......................................................................................................................................................................... 9 2.2.8 To Change The Alarm Setpoints (trip levels)...................................................................................................................... 10 2.3 Auto-Tare (Display Zero) ...................................................................................................................................................... 10 2.3.1 To Use Auto Tare................................................................................................................................................................ 10 2.4 to access and change parameter values................................................................................................................................. 11 2.4.1 Operator Level Navigation Diagram (factory default)......................................................................................................... 11 2.5 parameter tables..................................................................................................................................................................... 12 2.5.1 HOME List.......................................................................................................................................................................... 12 2.5.2 Alarm List ........................................................................................................................................................................... 12 2.5.3 Setpoint List ........................................................................................................................................................................ 12 2.5.4 Input List............................................................................................................................................................................. 13 2.5.5 User Calibration Lists – Inputs 1 and 2............................................................................................................................... 13 2.5.6 Access List .......................................................................................................................................................................... 13 3 Password Protected Levels of Operation ....................................................................................................................................... 14 3.1 access levels............................................................................................................................................................................. 14 3.1.1 To Select Full or Edit Access Levels .................................................................................................................................. 14 3.2 Navigation diagram (full and edit levels)............................................................................................................................. 15 3.3 parameter tables..................................................................................................................................................................... 17 3.3.1 HOME List.......................................................................................................................................................................... 17 3.3.2 Alarm List ........................................................................................................................................................................... 17 3.3.3 Setpoint List ........................................................................................................................................................................ 17 3.3.4 Input List............................................................................................................................................................................. 18 3.3.5 User Calibration Lists ......................................................................................................................................................... 19 3.3.6 Custom Linearisation List 1 or 2......................................................................................................................................... 21 3.3.7 Digital Communications List .............................................................................................................................................. 22 3.3.8 Information List .................................................................................................................................................................. 22 3.3.9 Access List .......................................................................................................................................................................... 22 3.4 To hide, reveal and promote parameters.............................................................................................................................. 23 3.4.1 List Headers ........................................................................................................................................................................ 23 3.4.2 Parameters........................................................................................................................................................................... 23 3.5 calibration............................................................................................................................................................................... 24 3.5.1 User Calibration .................................................................................................................................................................. 24 3.6 transducer calibration............................................................................................................................................................ 25 3.6.1 Shunt Calibration ................................................................................................................................................................ 25 3.6.2 To Calibrate a Strain Gauge Bridge Transducer.................................................................................................................. 25 3.6.3 Load Cell Calibration.......................................................................................................................................................... 27 3.6.4 To Calibrate a Load Cell ..................................................................................................................................................... 27 3.6.5 Comparison Calibration ...................................................................................................................................................... 28 3.6.6 To Calibrate by Comparison with an External Reference ................................................................................................... 28 3.6.7 Manual Calibration ............................................................................................................................................................. 29 Part Number HA027240 Issue 3.0 Nov-2003 1 Engineering Manual 4 5 6 7 2 2408i Indicator 3.6.8 Auto-Tare or Display Zero ..................................................................................................................................................29 3.6.9 To Enter a Fixed Offset to the Tare Value...........................................................................................................................30 3.7 Custom Linearisation .............................................................................................................................................................31 3.7.1 Example: To Linearise Input 1 ...........................................................................................................................................31 3.7.2 Compensation for Sensor Non-Linearities...........................................................................................................................31 CONFIGURATION LEVEL...........................................................................................................................................................32 4.1 Hardware configuration - I/O Modules ................................................................................................................................32 4.2 software configuration ...........................................................................................................................................................32 4.2.1 To Select Configuration Access Level.................................................................................................................................32 4.3 LOCATION OF parameterS – FROM INDICATOR BLOCK DIAGRAM .....................................................................33 4.4 Navigation diagram (configuration level) ............................................................................................................................34 4.5 Configuration Parameter Tables - All indicators.................................................................................................................36 4.5.1 Instrument configuration list................................................................................................................................................36 4.5.2 Sensor Input Configuration List ..........................................................................................................................................37 4.5.3 Alarm Configuration............................................................................................................................................................39 4.5.4 Alarm Inhibit .......................................................................................................................................................................40 4.5.5 2408i Indicator With Alarm Inhibit Timer ..........................................................................................................................41 4.5.6 Digital inputs 1 and 2 Configuration ...................................................................................................................................42 4.5.7 Peak Hold and Sample and Hold .........................................................................................................................................43 4.5.8 Relay Output 1 Configuration .............................................................................................................................................44 4.6 Configuration Parameter Tables – plug in modules.............................................................................................................46 4.6.1 Communications Module ....................................................................................................................................................46 4.6.2 Communications Parameters ...............................................................................................................................................46 4.6.3 PDS input Module...............................................................................................................................................................46 4.6.4 DeviceNet Communications ................................................................................................................................................48 4.6.5 Module 1, 2 and 3 Configuration Lists................................................................................................................................49 4.6.6 Changeover Relay or Dual Relay Output Module ...............................................................................................................49 4.6.7 Triple Logic Output Module................................................................................................................................................49 4.6.8 Triple Logic Input or Triple Contact Closure Input Module ...............................................................................................50 4.6.9 DC input Module.................................................................................................................................................................51 4.6.10 DC Retransmission Module............................................................................................................................................53 4.6.11 Strain Gauge Transducer Supply ....................................................................................................................................53 4.6.12 Transmitter Power Supply ..............................................................................................................................................53 4.7 Indicator calibration...............................................................................................................................................................54 4.7.1 To Calibrate Input 1 or 2 .....................................................................................................................................................54 4.7.2 To Calibrate Retransmission Output....................................................................................................................................55 4.7.3 To Restore Factory Calibration............................................................................................................................................55 4.7.4 Calibration Parameters ........................................................................................................................................................56 4.7.5 Password Configuration ......................................................................................................................................................56 4.7.6 To Leave Configuration Level.............................................................................................................................................56 Ordering Code..................................................................................................................................................................................57 Safety and EMC Information..........................................................................................................................................................58 Technical Specification ....................................................................................................................................................................59 Part Number HA027240 Issue3.0 Nov-2003 2408i Indicator Engineering Manual 2408i Indicator and Alarm Unit 1 Installing and Operating Instructions Thank you for choosing the 2408i panel mounted indicator. It will provide accurate measurement and display of temperature and other process variables. A modular build accepts a wide range of plug-in modules allowing: up to four alarm outputs, two process variable (PV) inputs, direct strain gauge/pressure sensor measurements, custom linearisation, analogue retransmission, remote setpoint (SP) input and digital communications. The indicator is supplied configured in accordance with the order code. The order code and instrument serial number is shown on a label fixed to the top of the case, and this can be checked against the order code given in section 5 of these instructions. 1.1 1. CONTENTS OF PACKAGE A peel-off label set - a convenient position is to fix a label to the top right of the display. A 2.49Ω resistor used as the load resistor for mA inputs Two panel retaining clips 2. 3. o C m/s x10 p.s.i p.s.i.x1 0 o F cm/s 1x10 bar mmHg K l/h l/min mbar Kg/cm2 kPa mWG T/h mPas gal/min V A % %pH rev/min mV mA %RH pH mile/h Amps 1.2 DIMENSIONS AND INSTALLATION 96 mm (3.78 in) E U R O T H E R M 48 mm (1.89 in) Panel retaining clips 2408I 88888 AL1 AL2 AL3 AL4 ACK/ RESET 150mm (5.9in) Latching ears (top & bottom) 1.2.1 To Install the Indicator Please read the safety information in section 6 before proceeding. The indicator is intended to be mounted on a panel within an enclosure such as a control cubicle. 1. Prepare the panel cut-out to the size shown. 2. Insert the indicator through the cut-out. 3. Spring the panel retaining clips into place. Secure the indicator in position by holding it level and pushing both retaining clips forward. 4. Peel off the plastic film protecting the front of the indicator. 92 -0.0 +0.8 X Recommended minimum spacing of indicators 45 mm -0.0 +0.6 38mm (1.5in) 3.62 0.0 +0.03 X 1.77 in -0.0 +0.02 (Not to scale) Panel cut-out 38mm (1.5in) 1.2.2 ! Removing The Indicator From The Sleeve The indicator can be removed from its sleeve by easing the latching ears outwards and pulling it forward out of the sleeve. When plugging the indicator back into its sleeve, ensure that the latching ears click into place to maintain the moisture sealing protection. It is recommended that power to the controller is turned off when removing or replacing the controller into its sleeve, to prevent premature wear on the connectors when current is flowing through them. This indicator meets the European directives on safety and EMC Part Number HA027240 Issue 3.0 Nov-2003 3 Engineering Manual 1.3 2408i Indicator NEW SLEEVE DESIGN MKIII From Jan-03 an improved design of 1/8 DIN long sleeve is shipped with all new 2408 controllers and indicators. (The month and year of manufacture are shown in the last two pairs of digits of the instrument serial number). 1.3.1 Details A new sealing gasket will be fitted onto the instrument bezel !. This gasket replaces the gasket which was moulded into the front of the sleeve of all previous instruments. The gasket previously moulded into the sleeve where it fits behind the panel is now supplied as a separate item ". 1.3.2 Reasons for the Change This change is to ensure that IP65 sealing is reliably achieved and less physical effort is required to insert the instrument into the new sleeve. 1.3.3 Recommendations 1. An instrument delivered after Jan 03 should be used with the sleeve supplied 2. If the instrument is required to replace one already in use, the existing sleeve should also be replaced 3. A new instrument can be fitted into an existing sleeve by carefully removing gasket ! but IP65 sealing willnot be maintained 4. An existing instrument can be fitted into a new sleeve but IP65 sealing will not be maintained It is, however, possible to achieve IP65 sealing for 3 and 4 above. A gasket kit is available from Eurotherm by quoting Part No SUB24/GAS2408. Then:5. To fit a new instrument in an older sleeve carefully remove gasket !. Replace it with the thinner (1.25mm) gasket from the kit 6. To fit an existing instrument into a new sleeve fit the thicker (1.6mm) gasket from the kit between the instrument and the sleeve The seal " supplied as a separate item with a new instrument, should be placed over the sleeve prior to mounting it through the panel cut out as shown below:Panel New Instrument Sleeve seal " (supplied as a separate item) Instrument sleeve New gasket ! fitted onto bezel 4 Part Number HA027240 Issue3.0 Nov-2003 2408i Indicator 1.4 Engineering Manual ELECTRICAL CONNECTIONS 3D 3C 3B 3A 2D 2C 2B 2A 1D 1C 1B 1A Configurable Plug-in Module Connections Module 3 JF Be sure to check the correct supply voltage before applying power ! Comms Module PDS Input Module Plug-in Communications Module Connections Module 1 Module 2 JE JD JC JB JA HF HE HD HC HB HA Sensor inputs V- Connections common to all indicators V+ VI AC AB AA LC LB LA N Relay Output 1 NC NO Com T/C Pt100 Low voltage supply Neutral Ground Digital input 2 mA Power Supply Connections L Line 24 24 85-264Vac 2.49Ω 20-29Vac/dc Digital input 1 0-10 Vdc Analogue Input 1 1.4.1 Ground Wiring The screw terminals accept wire sizes from 0.5 to 1.5 mm (16 to 22 AWG) and should be tightened to a torque of 0.4Nm (3.5lb in). Hinged terminal covers provide IP20 protection. 1.4.2 Plug-in Module Connections Modules are fitted in positions 1, 2 and 3 in accordance with the ordering code. The tables below show the connections for each module and the possible functions they can perform. Note: On the wiring label the module number precedes the terminal identity letter given in the table below. For example, 1A, 1B, 1C. Module Type Terminal Identity A B C D Typical Module Type Relay; changeover Alarm or Event Dual relay (normally open) DC retransmission Transmitter supply 24V Strain Gauge Transducer supply (see note 1) Alarms or events Terminal Identity A Functions B 2nd Analogue Input Typical C D Functions + - Thermocouple (Analogue Input 2) (module 3 only) + - Retrans. of PV + - + - To power transmitters To power strain gauges. (5V or 10V selectable) Cal resistor PRT + + - + - + Triple contact input - - ip1 ip2 ip3 mA (2.49Ω sense resistor) High impedance 0 - 2.0Vdc millivolts 0 - 10Vdc Com Triple digital input ip1 ip2 ip3 Com Notes:1. By default: Triple digital output op1 op2 op3 The transducer supply for input 1 is installed in module position 2 The transducer supply for input 2 is installed in module position 1 2. All module connections are isolated from the process value, earth, incoming supply and connections to other modules. 3. Digital inputs are non-isolated from the process value. Digital inputs are powered by the indicator. Switching voltage and current 24Vdc/20mA. ! 1.4.3 See Section 7 for specifications and maximum safety limits Communications Modules Digital Communications Module PDS Module Terminal identity Terminal identity Module type HB HC HD HE HF RS232 RS485 (2-wire) RS485 (4-wire) Profibus Rx+ Shield RxVP Com Com Com B Rx A (+) Tx+ A Tx B (-) TxDGND Part Number HA027240 Issue 3.0 Nov-2003 Setpoint Input JD JE JF - Signal Common 5 Engineering Manual 2408i Indicator 2 Operation Switch on the indicator. After a 3 second self-test sequence, you will see the display shown below. This is called the ‘HOME’ display. Operator Buttons The default is Process Value (PV). (See section 2.1.2 for other HOME display options) Increase parameter value 20 AL1 AL2 AL3 Decrease parameter value Select parameter AL4 Select parameter list heading See following sections for more detail Alarm 1 Alarm 2 Alarm Beacons ACK/ RESET Alarm 3 Press to acknowledge alarms Alarm 4 2.1.1 To View The Display Units If the indicator has been configured for a thermocouple or RTD input, the temperature units can be viewed as follows: Do This 1. This Is The Display You Should See Additional Notes Display Units Press and quickly release the or button. 0.5 sec * C Celsius OR *F Fahrenheit OR *K Kelvin The display units are shown for 0.5 second o 20 C Note: For linear inputs no units are displayed and, in this case: or 2.1.2 Pressing goes directly to the disp display - see section 2.1.2.. Pressing goes directly to the AL List - see section 2.2.4. Home Display Options When shipped from the factory the HOME display will show the measured temperature or process value. This is the ‘front’ display. or is pressed the display changes to the ‘back’ display for a period of two seconds. The back display can show an If either alternative measurement, such as alarm setpoint or second PV input value. Do This 1 1. This Is The Display You Should See Example Parameters which can be allocated to the Front and Back displays The HOME display will be blank and only alarm <nonE> messages will be flashed Setpoint (for deviation alarms) <SP> <rm.SP> Remote setpoint (for deviation alarms) ‘back’ display = Alarm setpoint. From the HOME display, or press 2 secs 100 20 or 2. or again to Press adjust the Alarm Setpoint between hi & lo limits ‘front’ display = Process Value Additional Notes <PV.Hi> <PV.Lo> <PV> <AL.SP> <L1> <L2> Displays the maximum value on input 1 Displays the minimum value on input 1 Process Value Alarm 1 setpoint Linearised input 1 Linearised input 2 Note: If the indicator has been ordered to read the highest (order code HI) or lowest values (order code LO) between input 1 and 2, the display shows only this value. If PV function ordered as FN, the displayed reading will be derived from inputs 1 and 2. The back display is not selectable in this mode i 6 Pressing and together will always return you to the HOME display. OR The display will always return to the HOME display if no button is pressed within 45 seconds. This time is reduced to 10 seconds if an alarm is being displayed. Part Number HA027240 Issue3.0 Nov-2003 2408i Indicator 2.2 Engineering Manual ALARMS Alarms are used to alert an operator when a pre-set level has been exceeded. They are normally used to switch an output (see section 2.2.2.) – usually a relay – to provide external actions to the process. Soft Alarms are indication only and do not operate an output. Events are generally defined as conditions, which occur as part of the operation of the plant. They do not require operator intervention and, therefore, do not cause an alarm message to be displayed. They can be attached to operate an output (relay) in the same way as an alarm. 2.2.1 Types of Alarm Used In The 2408i This section shows graphically the operation of different types of alarm used in the indicator. The graphs show changes in PV plotted against time. The PV may be derived from input 1, input 2 or the main PV which is derived from input 1 & 2. Alarm Type PV Full Scale High Process Variable (PV) Deviation High Deviation Band Setpoint (SP) Deviation Low Full Scale Low Rate of Change Output State Full Scale Low On Deviation Low On On On Deviation High Deviation Band On On On Full Scale High Rate of Change On On On Time Rate of change alarms detect if the rate of change in PV, set as units per minute or per second, exceeds the setpoint value. An alarm setpoint set + will detect positive rates of change. An alarm setpoint set - will detect negative rates of change. Therefore, if it is required to measure the rate of change in both directions then two alarms must be configured. Since rate of change alarms are calculated over a period of time a small delay may be apparent before the alarm is indicated. This is generally only noticeable if the PV changes very quickly. Hysteresis is the difference between the point at which the alarm switches ON and the point at which it switches OFF. It is used to prevent relay chatter. Deviation Alarms. The setpoint used for deviation alarms is normally derived as a remote input from another device - for example, a temperature controller. The setpoint can also be internally set within the controller - in this case called the local setpoint value. Delay a settable time between an alarm occurring and it being displayed on the indicator Blocking Alarms only occur after the start up phase when the alarm has first entered a safe state. The alarm is only indicated the next time it is active. It is used, for example, to ignore start up conditions which are not representative of running conditions. Latching Alarms see 2.2.6 2.2.2 Alarm Relay Output Alarm 1 i Alarms can operate a specific relay or logic output. Any individual alarm can operate an individual output or any combination of alarms can operate an individual output. They are either supplied pre-configured in accordance with the ordering code or set up in configuration level. nor Alarm 2 Alarm 3 SEnS OR Input fail Sensor break Logic or Relay output dIG inv Any combination of alarms can operate the relay or logic output. Typical alarms are shown Part Number HA027240 Issue 3.0 Nov-2003 7 Engineering Manual 2.2.3 2408i Indicator Alarm Indication An alarm occurs when the process conditions exceed a pre-set level (setpoint). It will be displayed on the indicator as follows:1. The relevant alarm beacon will begin to flash 2. A four character alarm message will be shown as a double repeating flash in the main display. This message specifies the alarm number (first character) and the type of alarm that has occurred (next three characters). The message is flashed in addition to the ‘front’ displayed value If more than one alarm is present the relevant beacon illuminates and further messages are flashed in the main display. The alarm indication will continue while the alarm condition is present and is not acknowledged. 1FSL 20 ‘front’ display = Process Value (PV) AL1 ‘The message indicates the alarm type eg. <1FSL> = Alarm 1 Full Scale Low See ‘Alarm Messages’ below for the full list. Alarm Beacon 2.2.4 Alarm Messages Display Alarm type Input Source Alarm description and function First character 1--- Alarm 1 is active 2--- Alarm 2 is active 3--- Alarm 3 is active 4--- Alarm 4 is active Last three characters -FSL Full Scale Low The process value is:- below the low alarm setting on the main PV PV 1 below the low alarm setting on PV 1 -FL2 PV 2 below the low alarm setting on PV 2 -FSH Full Scale High -FH1 -FH2 -dLo Deviation Low -dL1 -dL2 -dHi Deviation High -dH1 -dH2 -Dev Deviation Band -Dv1 -Dv2 Main PV above the high alarm setting on the main PV PV 1 above the high alarm setting on PV 1 PV 2 above the high alarm setting on PV 2 Main PV below the low deviation setting on main PV PV 1 below the low deviation setting on PV1 PV 2 below the low deviation setting on PV2 Main PV above the high deviation setting on main PV PV 1 above the high deviation setting on PV1 PV 2 above the high deviation setting on PV2 Main PV above or below the high and low deviation setting on main PV PV 1 above or below the high and low deviation setting on PV1 PV 2 above or below the high and low deviation setting on PV2 -rat Rate of change (minutes) Main PV changing faster than the rate-of change alarm setting in minutes for main input. -ras Rate of change (seconds) Main PV changing faster than the rate-of change alarm setting in seconds for main input. -rt1 Rate of change (minutes) Input 1 changing faster than the rate-of change alarm setting in minutes for input 1. -rs1 Rate of change (seconds) Input 1 changing faster than the rate-of change alarm setting in seconds for input 1. -rt2 Rate of change (minutes) Input 2 changing faster than the rate-of change alarm setting in minutes for input 2. -rs2 Rate of change (seconds) Input 2 changing faster than the rate-of change alarm setting in seconds for input 2. -LSP Setpoint Low Main PV -HSP Setpoint High Main PV Sbr i 8 Main PV -FL1 The setpoint is:- below the low alarm setting above the high alarm setting Sensor Break alarm (open circuit input on whichever input is being used as the PV) If the process value flashes but no other alarm message is displayed, this indicates that the input which is being used as the PV is out of range. Part Number HA027240 Issue3.0 Nov-2003 2408i Indicator 2.2.5 Engineering Manual Diagnostic Alarms In addition to the process alarms given in the previous column the following diagnostic alarms may also appear. These warn that a fault exists in either the indicator or the connected devices. Alarm What it means EE.Er Electrically Erasable Memory Error: The value of an operator or configuration parameter has been corrupted. This fault will automatically select configuration level. Check all configuration parameters before returning to operator level. Once in operator level, check all operator parameters before resuming normal operation. If the fault persists or occurs frequently, return the unit for repair. What to do about it LLLL Out of range low reading Check the value of the input HHHH Out of range high reading Check the value of the input Err1 Error 1: ROM self-test fail Return the indicator for repair Err2 Error 2: RAM self-test fail Return the indicator for repair Err3 Error 3: Watchdog fail Return the indicator for repair Err4 Error 4: Keyboard failure. Stuck button, or a button was pressed during power up. Switch the power off and then on without touching any of the indicator buttons. If the error continues return the unit for repair. Err5 Error 5: Input circuit failure Return the unit for repair Hw.Er Hardware error Check that the correct modules are fitted. Go to configuration mode and set up the required parameter(s). See section 4 for further information. Indication that a module is of the wrong type, missing faulty, or a new module has been fitted. Pwr.F Power failure: The line voltage is too low Check that the supply is within rated limits rmt.F Remote input fail Connect an input device (eg. transducer, thermocouple, mA source) to input 2 2.2.6 To Acknowledge An Alarm An alarm can be acknowledged in two ways:1. Press the ACK/RESET button. (If this does not work it may have been disabled when the indicator was configured). 2. Press and together. The action, which now takes place, will depend on the type of latching, which has been configured Non Latched Alarms If the indicator has been configured for non-latching alarms the following action occurs:Alarm condition present when the alarm is acknowledged, will be indicated by a single repeating flash of the alarm message and the beacon will continuously illuminate. This state will continue for as long as the alarm condition remains. When the alarm condition disappears the indication will also disappear. If a relay has been attached to the alarm output, it will operate when the alarm condition occurs and remain in the operated condition until the alarm is acknowledged AND it is no longer present. If the alarm condition disappears before it is acknowledged the alarm indication disappears as soon as the condition disappears. Latched Alarms The indicator may have been configured for Automatic or Manual reset. The action which occurs when the acknowledge button is pressed is described below:- Automatic. The alarm continues to be active until both the alarm condition is removed AND the alarm is acknowledged. The acknowledgement can occur BEFORE the alarm condition is removed. Manual The alarm continues to be active until both the alarm condition is removed AND the alarm is acknowledged. The acknowledgement can only occur AFTER the alarm condition is removed. 2.2.7 Alarm Inhibit If a digital input has been configured for alarm inhibit, then all process alarm indication will be prevented for as long as the input is ON. When the input is turned to OFF any alarms which are active will be displayed. If a delay has been set on the alarm, the delay period will start from the time when the input is turned OFF. If the alarm has been configured as latching the latching action is also inhibited whenever the input is ON. See section 4.5.4 and 4.5.6. Part Number HA027240 Issue 3.0 Nov-2003 9 Engineering Manual 2.2.8 2408i Indicator To Change The Alarm Setpoints (trip levels) Parameters are grouped in ‘lists’ according to their function. Each list has a heading. The button steps through the parameter list headings (see section 2.4.1.) The first list is the alarm setpoints list AL Do This This Is The Display You Should See 1. From any display press as many times as necessary to show the ‘Alarm List’ header 2. Press to show the first parameter in the list or Press alarm setpoint 3. to change the AL 400.0 1--- Additional Notes i or are pressed the word <List> is If displayed for 2 secs i There are four alarm setpoints. The first character is the alarm number, the next three the alarm type (see section 2.2.4.) List AL If an alarm has been disabled in configuration level, it will not appear in this list. or 4. To return to the HOME display:• Press • • or continue to press or the indicator will return to the HOME display if no button is pressed for 45 seconds (10 seconds if an alarm condition is present). 2.3 and together AUTO-TARE (DISPLAY ZERO) The auto-tare function is used, for example, when it is required to weigh the contents of a container but not the container itself. Alternatively, it can be used to set a fixed offset on an initial measured value. 2.3.1 To Use Auto Tare Place the empty container on the weigh-bridge. Then:Do This 1. From any display press as many times as necessary to show the <CAL1> List’ header This Is The Display You Should See CAL1 to scroll to <tAre> 2. Press 3. Press or and change from <Off> to <on> tare on Additional Notes i i Use <CAL2> if the load cell is connected to input 2 The indicator automatically calibrates itself to the empty container. When <tArE> is turned to <on>, the display will change to <buSY>. When calibration is complete the display will return to the HOME display. It will then return to the main display. If the calibration fails the alarm message <tdr.F> (transducer fail) will flash. Press acknowledge. buSY 4. and to 20 Return to the HOME display as described above Note:The indicator will not return to the HOME display until the calibration procedure completes. If calibration does not complete after a period of 5 minutes, then calibration is aborted. 10 Part Number HA027240 Issue3.0 Nov-2003 2408i Indicator 2.4 Engineering Manual TO ACCESS AND CHANGE PARAMETER VALUES Parameters are settings within the indicator, which determine how it will operate. Examples are Alarm Setpoints and Tare Values already mentioned. They are organised into different lists. Each list has a named heading which describes a particular subject, for example ‘Alarms’ <AL> 2.4.1 Operator Level Navigation Diagram (factory default) This list shows the parameters available in operator level in a new instrument. To find a parameter:Press to select the list heading Press to select the parameter Press or Examples are shown in sections 2.2 8. and 2.3.1. to change its value To return to HOME page keep pressing Note:- The first press displays the instrument units described in 2.1.1. HOME List Alarm List Setpoint List Input List Input 1 calibration List AL SP iP CAL1 1--- sp L int.t 2--- sp H X2 20 Input 2 calibration List Access List CAL2 ACCS (2) (1) dsp.f CodE (1) dsp.b Goto (1) Cid 3--(1) Only present if ordered with configuration options SG or MP, see ordering code section 5. See also section 3 for the full list of parameters available and calibration details. 4--- i • Blocks shown shaded are dependant upon the order code as follows:- (1) These parameters are only shown if the alarm has been configured (2) CAL2 list is only shown if Input 2 has been configured • The above list can be customised to suit the requirements of a particular process. Complete lists or individual parameters in a list can be added during commissioning. The procedure is described in section 3.4 ‘To Hide. Reveal and Promote Parameters’. Part Number HA027240 Issue 3.0 Nov-2003 11 Engineering Manual 2.5 2408i Indicator PARAMETER TABLES The parameter tables provide a full list of parameters, an explanation of their use and where to find them. Use these lists to adjust:• The alarm setpoints • The alarm setpoint limits 2.5.1 • • • The User calibration The input filter time constant The communications address HOME List 20 HOME Home List dSP.F HOME display front Selectable options The HOME display will be blank <nonE> and only alarm messages will be flashed Setpoint (for deviation alarms) <SP> <rm.SP> Remote setpoint (for deviation alarms) Displays the maximum value on <PV.Hi> input 1. This parameter is the same as <LOG.H> in <inFo> list Displays the minimum value on <PV.Lo> input 1. This parameter is the same as <LOG.L> in <inFo> list Process Value <PV> Alarm 1 setpoint <AL.SP> <L1> <L2> dSP.b HOME display back C.id Customer defined identity number - an indicator can be associated with a physical position 2.5.2 Default PV Linearised input 1 Linearised input 2 0 to 9999 0 Alarm List AL AL Alarm list Comments Adjustable Range 1--- Alarm 1 setpoint The last three letters indicate the Between low and high setpoint limits which 2--- Alarm 2 setpoint Alarm type. See section 2.2.4. As set in the SP list. 3--- Alarm 3 setpoint If the alarm is disabled the parameter Rate of change alarms are direction sensitive 4--- Alarm 4 setpoint will not appear in this list from-9999 to +99999 units/sec or min 2.5.3 Setpoint List Default 0 0 0 0 SP sp Setpoint list Adjustable Range Default SP L Setpoint low limit – PV alarms Input range min and max (combination of As per SP H Setpoint high limit – PV alarms inputs 1 & 2 12 Part Number HA027240 order code Issue3.0 Nov-2003 2408i Indicator 2.5.4 Engineering Manual Input List iP ip Setpoint list Adjustable Range int.t Input filter integrating time constant OFF to 999.9 seconds Default 1.6 Set to a value which reduces the effect of any input noise to an acceptable level. The higher the value the more sluggish the response 2.5.5 User Calibration Lists – Inputs 1 and 2 CAL.1 or CAL.2 (CaL 2 only appears if input 2 has been configured) CAL.CAL.- User calibration 1 or 2 list Adjustable Range Default tAre Performs automatic ‘Tare’ correction OFF = Off on = start correction busy = inputting value done = finished inputting value OFF See also section 2.3. 2.5.6 ACCS code Access List The Access List provides password protected access to further levels of operation as listed below. See section 3 for further details. or buttons. If an incorrect code number is entered the display will revert A code number can be entered using the to <codE>. If no button is pressed within 45 seconds the indicator will automatically return to the HOME display. For information on further levels of access, see the following sections. Part Number HA027240 Issue 3.0 Nov-2003 13 Engineering Manual 3 2408i Indicator Password Protected Levels of Operation 3.1 ACCESS LEVELS Parameters are protected under different levels of access for which numerical password codes can be set up. The levels are:Access Level What you can do Default Code OPer To view and adjust a limited set of parameters within limits set in higher levels FuLL To view and adjust all parameters which are required to operate the indicator 1 Edit Allows parameters to be hidden or promoted to operator levels (see section 3.4) 1 Conf Allows access to configure the fundamental characteristics of the indicator 2 CAL.P This special level which appears in the CAL1 and CAL2 lists allows access to the calibration procedure for the indicator 3 The following sections this manual describe the features available in Full, Edit and Configuration levels. 3.1.1 To Select Full or Edit Access Levels Do This This Is The Display You Should See 1. From any display press as many times as necessary to access the ‘Access List’ header menu 2. Press or to show <code>Press to enter the password ACCs 2 secs Press 4. Press or <FuLL> level PASS codE 2 secs ! i 14 to select If or are pressed the word <List> is displayed for 2 secs List ACCS The factory default password is 1 to show <Goto> 3. Additional Notes FuLL Goto <PASS> will be displayed momentarily when the correct password is been entered In the special case that the passcodes have been configured as 0, it will not be necessary to enter a passcode Options are: Operator level - shows selected operator parameters <OPEr> <FuLL> Reveals the ‘FULL’ set of parameters <Edit> Allows parameters to be hidden or promoted <ConF> Gives access to configuration level (see section 4). The factory default password is 2 Having entered a higher level you can select <OPEr>, <FuLL> or <Edit> levels at will. Remember to return to <OPEr> level following completion of commissioning or configuring the instrument.. This may be done by:1. Switching the indicator off and back on again. OR 2. Go to <OPEr> level and enter a false password number to re-lock the indicator in this level. Part Number HA027240 Issue3.0 Nov-2003 2408i Indicator 3.2 Engineering Manual NAVIGATION DIAGRAM (FULL AND EDIT LEVELS) Use the following lists to adjust: • The alarm setpoints • The alarm setpoint limits • The input filter time constant • The User calibration • The communications address The diagram below shows the complete list of possible parameters which may be shown in Full and Edit access levels. In practice, the parameters that appear will depend upon the configuration of your particular indicator . HOME List Alarm List This list only contains parameters for alarms which have been configured Setpoint List Input List SP ip Transducer Calibration List 1 This list is only applicable to transducer on input 1 Transducer Calibration List 2 This list is only applicable to transducer on input 2 X2 20 AL CAL1 CAL2 X2 DsP.F (1) DsP.b C.id 1--- (2) 2--- (2) 3--- (2) 4--HY 1 (7) Hy 2 (7) Hy 3 FiLt TaRe rm.SP int.t rm.tr (4) stP.b CAL CAL Sp (7) FLt.2 pnt.L pnt.L SP 1 (7) in2.t Adj.L Adj.L Sp 2 (7) st2.b pnt.H pnt.H (12) CaLp (12) CaLp OFS1 adj.H adj.H Sp H (7) OFS2 tare.v tare.v 1dEL (7) Sp 1.L (5) Lo.IP inp.L inp.L 2deL (7) Sp 1H (5) Hi.IP scL.L scL.L Sp 2L (5) F.1 inp.H inp.H 3deL 4dEL (7) (7) Sp 2H (5) (6) Parameters are hidden by default. See section 3.4 to ‘Reveal’ Parameters are only displayed when the option has been configured as follows:- (1) Each alarm must be configured (2) Only shown if a DC Input module is fitted in slot 3 and ‘Remote F.2 Issue 3.0 Nov-2003 scL.H scL.H PV.iP mV.1 (7) (8) (9) mV.2 EmiS EmS.2 setpoint input’ is configured (10) CJC.1 (3) If filter Type = Integration (4) If filter Type = Step (11) CJC.2 (5) Only shown if a DC Input module is fitted in slot 3 and ‘Derived Value’ is configured (<Func> = <Ftn>, see section 4.6.7.) Li.1 (6) Only shown if a DC Input module is fitted in slot 3 and ‘Select input 2’ is configured (7) Li.2 (7) Only shown if a DC Input module is fitted in slot 3 (8) Only shown if the input is configured for ‘Pyrometer’ (7) PV.SL (9) Only shown if a DC Input module is fitted in slot 3 and ‘Pyrometer’ input is configured (10) Only shown if the input is configured for ‘Thermocouple’ (11) Only shown if a DC Input module is fitted in slot 3 and ‘Thermocouple’ input is configured Figure 3-1: Navigation Diagram Part Number HA027240 TaRe (3) Sp L Hy 4 i L-r For parameter availability see ‘User Calibration Lists’ section 3.3.5. 12. Only shown if SG is present in the Options field of the ordering code 15 Engineering Manual 2408i Indicator Summary A. Press to step across the list headings. B. Press to step down the parameters within a particular list. You will eventually return to the list heading. C. Press to view the value of a selected parameter. Keep pressing to decrease the value. D. Press to view the value of a selected parameter. Keep pressing to increase the value. Custom Linearisation List 1 This list only appears if custom linearisation on input 1 is configured Custom Linearisation List 2 This list only appears if custom linearisation on input 2 is configured CUSt1 CUSt1 cmS in L Addr (13) in L (13) Communications List This list only appears if a communications board is fitted Information List Access List inFo ACCS Log.L CodE Goto VAL.L VAL.L Log.H in H in H LoG.A VAL.H VAL.H LoG.t in 2 in 2 Log.u VAL.2 VAL.2 rES.L in 14 in 14 VAL.14 VAL.14 13. Only shown if:- <mV.C>, <V.C> or <mA.C> are configured, see Sensor Input Configuration List section 4.5.2. 16 Part Number HA027240 Issue3.0 Nov-2003 2408i Indicator 3.3 Engineering Manual PARAMETER TABLES 3.3.1 HOME List 20 Mnem -onic Meaning dSP.F HOME display front See ‘HOME display options’ PV dSP.b HOME display back section 2.1.2. None C.id Customer defined identity number 0 to 9999 0 Adjustable Range Default setting 3.3.2 Adjustable Range Default setting Customer setting Alarm List AL Mnem -onic Meaning 1--- Alarm 1 setpoint In place of dashes, the last three letters indicate Between low and high setpoint limits which are set in the <SP> list 0 2--- Alarm 2 setpoint the alarm type: as shown in Rate of change alarms are direction 3--- Alarm 3 setpoint the ‘Alarm Messages’ sensitive from-9999 to +99999 4--- Alarm 4 setpoint table section 2.2.4. units/sec or min 0 0 0 Customer setting If the alarm is disabled the parameter will not appear in this list HY 1 Alarm 1 Hysteresis Prevents relay ‘chatter’ 1 to 99999 display units 1 HY 2 Alarm 2 Hysteresis by setting a 1 to 99999 display units 1 HY 3 Alarm 3 Hysteresis difference between the relay 1 to 99999 display units 1 HY 4 Alarm 4 Hysteresis ON and OFF points 1 to 99999 display units 1 1dEL Alarm 1 delay Used to ignore transient 0 to 999.9 seconds 0 2dEL Alarm 2 delay alarms. Alarms must 0 to 999.9 seconds 0 3dEL Alarm 3 delay be true for the delay time 0 to 999.9 seconds 0 4dEL Alarm 3 delay before they become active 0 to 999.9 seconds 0 In.AL Inhibit alarm timer To inhibit alarms for a time On/OFF OFF InH.t Time alarm inhibited see section 4.5.5 0 to 999.9 seconds 0 3.3.3 Setpoint List SP Mnem -onic Meaning Adjustable Range Default setting L- r Remote setpoint enable Loc Select local SP Loc rmt Select remote SP rm.SP Remote master setpoint (for deviation alarms) Displays remote SP value N/A rm.tr Remote setpoint track. OFF No tracking OFF This parameter only appears if remote setpoint has been configured trAc Local SP tracks remote SP SP 1 Local master setpoint value for deviation alarms on input 1 SP1.L to Sp1.H 20 SP 2 Local master setpoint value for deviation alarms on input 2 SP2.L to SPH.2 20 SP Setpoint value when the combination of inputs 1 & 2 provide the measured value to the indicator (for deviation alarms) SPL to SPH SP L SP H PV Alarms Setpoint low limit Setpoint High limit Input range min and max (combination of input 1 2) As per order code SP1.L SP1.H Input 1 Alarms Setpoint Low Setpoint High Between input 1 sensor range min and max As per order code SP2.L SP2.H Input 2 Alarms Setpoint Low Setpoint High Between input 2 sensor range min and max As per order code Part Number HA027240 Issue 3.0 Nov-2003 Customer setting Read only 17 Engineering Manual 3.3.4 2408i Indicator Input List iP Mnemonic Meaning FiLt Input 1 Filter Type Int.t Input 1 filter time constant StP.b Input 1 filter Step Band Adjustable Range For explanation of filter action see section 3.3.4.2. Off Int StEP Default setting No input filter Integrating Step Appears if Filter Type = <Int> Used to reduce process value flicker on any input other than weigh scales OFF to 999.9 seconds 1.6 Appears if Filter Type = 1 to 100 10 <StEP> Used to reduce Customer setting (% maximum noise band) process value flicker on weigh scale inputs The above three parameters are repeated for input 2 as <FLt2>, OFS1 Input 1 calibration Offset OFS2 (1) Lo.IP Hi.IP <in2.t> and <st2.b> respectively See section 3.5.1 999.9 to 999.9 Input 2 calibration Offset 999.9 to 999.9 Transition of indication between input 1 and 2 (if configured) Between input sensor range minimum and maximum. As per order code • The displayed value is derived from input 1when PV is below <Lo.IP> and from input 2 when PV is above <Hi.IP> • When PV is between <Lo.IP> and <Hi.IP> the displayed value is a combination of both inputs • <Lo.IP> cannot be set to a value above <Hi.IP> This is described further in section 4.6.9.1 F.1 (2) <F.1> and <F.2> are constants to achieve a derived PV -9.99 to 10.00 0.5 F.2 (2) where PV = <F.1> x input 1 + <F.2> x input 2 -9.99 to 10.00 0.5 ip.1 Input 1 selected ip.1 ip.2 Input 2 selected PV.ip (1) mV.1 Selects input 1 or input 2 Input 1 mV measured at the rear terminals Read-only Read-only mV.2 Input 2 mV measured at the rear terminals (module 3) Read-only Read-only CJC.1 Input 1 Cold junction compensation temperature measured at the rear terminals. Only applies if the input 1 type = thermocouple Read-only Read-only CJC.2(1) Input 2 Cold junction compensation temperature measured at the rear terminals (module 3) Only applies if the input 2 type = thermocouple Read-only Read-only Emis Input 1 Emissivity. Only applies if the input 1 type = pyrometer EmS.2 (1) Input 2 Emissivity. Only applies if the input 2 type = pyrometer Li.1 Input 1 Linearised value Read-only Read-only Input 2 Linearised value (module 3) Read-only Read-only (1) Li.2 (1) PV.SL Shows the currently selected PV input ip.1 ip.2 both ip.1 Input 1 selected Input 2 selected Both input 1 and input 2 are configured Notes: (1) These parameters only appear if input 2 has been configured (2) These parameters only appear if a derived input has been configured 3.3.4.1 1. 2. 3. 18 Example: To Measure to Differential Between Input 1 and Input 2 From the above list, select <F.1> and set its value to 1. From the above list, select <F.2> and set its value to -1. The derived PV will read the difference between Input 1 and Input 2 Part Number HA027240 Issue3.0 Nov-2003 2408i Indicator 3.3.4.2 Engineering Manual Filter Type There are three settings for the filter type 1. Filter Type = Off. The display will respond immediately to any change in the PV input. If, however, there is any input noise this will result in fluctuations of the reading 2. Filter Type = Integrating action. This is designed for all process input types with the exception of weigh cell transducers as explained in section 3.6. The function is exponential which means that, for a step change in the input, the displayed value will move rapidly at first towards the new reading then gradually slow as the reading approaches the PV value. The effect is that small rapidly changing input values are ignored. The rate of response is set, in seconds, by the parameter Int.t, which only appears for this type of filter. The larger the value the more sluggish the response 3. Filter Type = Step Band. This is specifically designed for weighing applications. The filter only responds when the displayed value becomes close to the measured value. This means that for a step change in the input the displayed value will change rapidly towards the measured value then slow as it reaches this value. The step band is set by the parameter StP.b which only appears for this type of filter. The units approximate to 1µV steps – the larger the setting more sluggish the response over the final stages of the reading. This type of filter is used, for example, where a weigh bridge or load cell is subject to vibrations 3.3.5 User Calibration Lists These lists only appear if the ‘Type of Calibration’, <tYPE>, is configured for strain gauge type transducer applications (see Configuration Chapter for further details). The lists below are shown for each type of calibration. If <Type> = <OFF> the lists are not displayed. Some parameter mnemonics remain the same for each type of transducer, but their functions may vary in detail between the different types. The tables are repeated, therefore, for each calibration type. The tables are followed by a description of procedure to use for each type of calibration. 3.3.5.1 Calibration Type = Shunt (<tYPE> = <Shnt>) See also section 3.6.1. CAL1 or CAL2 Mnemonic Meaning Adjustable Range Default setting tArE Performs automatic ‘Tare’ correction OFF = Off on = Start correction busy = Calculating value OFF 0 to 99999 3 See ’USER CALIBRATION’ section for further description CAL.P Calibration password -See ‘USER CALIBRATION’ The following three parameters only appear when the correct password has been entered Factory calibration restored Calibration type Fact CAL USEr Customer setting FAct User calibration enabled The following two parameters are only shown if <USEr> is selected as the calibration type Start point low calibration OFF Calibration complete Note: In shunt mode this parameter starts both zero and span calibration. Its mnemonic is common to other transducer applications on Start calibration tArE.v Tare Value This allows a fixed offset to be applied to the displayed reading. It must be set before auto tare is started -999.9 to 99999 display units 0.0 S.G Specific gravity multiplier For materials with specific gravity different from water (1) 0.01 to 999.9 1.00 ScL.L Scale Low point Defines the low calibration point for the transducer (normally 0% of the transducer range) -999.9 to 99999 display units 0 ScL.H Scale High point Defines the high calibration point for the transducer (normally 80% of the transducer range) -999.9 to 99999 display units 0 Pnt.L Part Number HA027240 Issue 3.0 Nov-2003 OFF 19 Engineering Manual 3.3.5.2 2408i Indicator Calibration Type = Load Cell (<tYPE> = <Ld.C>) See also section 3.6.3. CAL1 or CAL2 Mnemonic Meaning Adjustable Range Default setting tArE Performs automatic ‘Tare’ correction OFF = Off on = Start correction busy = Calculating value OFF See ’USER CALIBRATION’ section for further description Calibration password -See ‘USER CALIBRATION’ 0 to 99999 3 CAL.P The following four parameters only appear when the correct password has been entered Calibration type Factory calibration restored CAL Fact USEr Customer setting FAct User calibration enabled The following three parameters are only shown if <USEr> is selected as the calibration type Pnt.L Pnt.H Start point low calibration Start point high calibration OFF Calibration complete on Start low point calibration OFF Calibration complete on Start high point calibration OFF OFF tArE.v Tare Value This allows a fixed offset to be applied to the displayed reading. It must be set before auto tare is started -999.9 to 99999 display units 0.0 S.G Specific gravity multiplier For materials with specific gravity different from water (1) 0.01 to 999.9 1.00 ScL.L Scale Low point Defines the value which will be displayed when the load is removed from the cell -999.9 to 99999 display units 0 ScL.H Scale High point Defines the value which will be displayed when the load is placed on the cell -999.9 to 99999 display units 0 3.3.5.3 Calibration Type = Comparison <tYPE> = <Cm.P> See also section 3.6.5. CAL1 Mnemonic tArE CAL.P or CAL2 Meaning Adjustable Range Default setting Performs automatic ‘Tare’ correction OFF = Off on = Start correction busy = Calculating value OFF See ’USER CALIBRATION’ section for further description Calibration password -See ‘USER CALIBRATION’ 0 to 99999 3 The following four parameters only appear when the correct password has been entered Factory calibration restored Calibration type Fact CAL USEr Customer setting FAct User calibration enabled The following three parameters are only shown if <USEr> is selected as the calibration type Pnt.L Pnt.H Start point low calibration Start point high calibration OFF Calibration complete on Start low point calibration OFF Calibration complete on Start high point calibration OFF OFF tArE.v Tare Value This allows a fixed offset to be applied to the displayed reading. It must be set before auto tare is started -999.9 to 99999 display units 0.0 S.G Specific gravity multiplier For materials with specific gravity different from water (1) 0.01 to 999.9 1.00 ScL.L Scale Low point Automatically adjusts to the value entered at <Pnt.L> -999.9 to 99999 display units ScL.H Scale High point Automatically adjusts to the value entered at <Pnt.H> -999.9 to 99999 display units 20 Part Number HA027240 Issue3.0 Nov-2003 2408i Indicator Engineering Manual Calibration Type = Manual <tYPE> = <mAn> 3.3.5.4 See also section 3.6.7. CAL1 or CAL2 Mnemonic Meaning Adjustable Range Default setting CAL.P Calibration password -See ‘USER CALIBRATION’ 0 to 99999 3 The following four parameters only appear when the correct password has been entered Factory calibration restored Calibration type Fact CAL USEr Customer setting FAct User calibration enabled The following three parameters are only shown if <USEr> is selected as the calibration type inP.L Input low Set to the low electrical input which is to correspond to the low display reading -999.9 to 99999 display units ScL.L Scale Low point Set to the display reading corresponding to <inP.L> -999.9 to 99999 display units inP.H Input high Set to the high electrical input which is to correspond to the high display reading -999.9 to 99999 display units ScL.H Scale High point Set to the display reading which corresponds to<inP.H> -999.9 to 99999 display units 0 Adjustable Range Default setting 3.3.6 0 Custom Linearisation List 1 or 2 CUSt1 or CUSt2 Mnemonic Meaning in L Adjust low input value min input VAL.L Adjust displayed value corresponding to input low min display in H Adjust high input value Max input VAL.H Adjust displayed value corresponding to input high max display in 2 Adjust input break point 2 value VAL.2 Adjust displayed value corresponding to point 2 Customer setting The values entered must be continuously increasing or decreasing to in 14 Adjust input break point 14 value VAL.14 Adjust displayed value corresponding to point 14 This list only appears if a custom download input has been configured. Further information on Custom Linearisation is given in section 3.7. i Having entered the values for the custom linearisation it is necessary to power down the instrument and power back up again to enter the values otherwise they will be clamped to zero. Alternatively enter then leave configuration level. Part Number HA027240 Issue 3.0 Nov-2003 21 Engineering Manual 3.3.7 2408i Indicator Digital Communications List cmS Mnemonic Meaning Adjustable Range Default setting Addr Indicator communications address 1 to 99 EI Bisynch 1 Customer setting 1 to 254 Modbus This list only appears if digital communications has been configured. 3.3.8 Information List inFo Mnemonic Meaning Adjustable Range Default setting Customer setting Log.L Logged Minimum Process Value Can be manually adjusted Read-only Read-only LoG.H Logged Maximum Process Value These values are logged by the indicator Can be manually adjusted Read-only Read-only Log.A Logged Average Process Value from switch on Read-only Read-only LoG.t Time process value is above threshold level To reset switch the indicator supply off and Time displayed in minutes Read-only Read-only Log.v Process value threshold for timer log on again or scroll to <rESL> and select <YES> Between display min and max 0 rES.L Logging reset no YES 3.3.9 Logging in progress no Will reset logged values Access List The Access List is the same as section 2.5.6. ACCS Mnemonic Meaning OPer To view and adjust a limited set of parameters within limits set in higher levels FuLL To view and adjust all parameters which are required to operate the indicator Edit Allows parameters to be hidden or promoted to operator levels (see section 3.4.) Conf Allows access to configure the fundamental characteristics of the indicator CAL.P This special level which appears in the CAL1 and CAL2 lists allows access to the calibration procedure for the indicator 22 Part Number HA027240 Issue3.0 Nov-2003 2408i Indicator 3.4 Engineering Manual TO HIDE, REVEAL AND PROMOTE PARAMETERS In Edit level you can choose customise the operator level display by choosing which parameters can be made available. The choices are:- <Altr> <HidE> <rEAd> <Pro> 3.4.1 The parameter will be alterable The parameter will be hidden The parameter will be read-only The parameter will be ‘promoted’ into the HOME list (see below) List Headers Any list of parameters shown in the Navigation Diagram, section 3.2. can be made available or hidden in Operator level. Do This This Is The Display You Should See 1. Enter <Edit> level as described in 3.1.1. 2 secs 2. 2 secs 3. Press to select the list to be hidden eg <SP> the setpoint parameters or Press Additional Notes Edit Goto HidE SP If <HidE> is selected the complete list will not be available in Operator level to select <HidE> or <rEAd> 3.4.2 Parameters Any parameter in a list can be made available or hidden in the same way as the complete list header as described above. They can also be made read only or promoted as shown in the two following examples. 3.4.2.1 The <Pro Pro> Pro (Promote) option Up to twelve commonly used parameters can be ‘promoted’ into the HOME list. This will give the operator quick access to them by simply pressing the button. This feature, used in combination with ‘hide’ and ‘read only’ allows you to organise the way in which you want your indicator formatted. Pro Low alarm 1 has been selected Press or to choose <Pro>. 1FSL The parameter <1fsL> will now appear in the HOME list. Repeat the procedure for any other parameters you wish to promote. To de-promote a parameter go to <edit> level, select the parameter from the relevant list and change the choice from <Pro> back to <ALtr>, <rEAd> or <HidE>. 3.4.2.2 Read Only Example read In this example Full scale High alarm 2 will be read only. This means that its value will be displayed in operator level but it cannot be changed. 2FSH Part Number HA027240 Issue 3.0 Nov-2003 23 Engineering Manual 3.5 2408i Indicator CALIBRATION The indicator is calibrated in three ways. These are:1. Factory Calibration. The controller is calibrated to very high accuracy during manufacture and the calibration values are permanently stored within the controller. Factory calibration is not available to the user 2. Transducer Scaling. Transducer scaling allows offsets to be entered to compensate for errors or differences in the process measurement system 3. User Calibration. This allows the instrument to be calibrated against a certified field calibration source See also section 3.3.5. for the full list of calibration parameters 3.5.1 User Calibration User calibration allows you to:1. Calibrate the controller to the your reference standards 2. Match the calibration of the controller to that of a particular transducer or sensor input 3. Calibrate the controller to suit the characteristics of a particular installation The following can be calibrated: 1. Input 1. This applies to the fixed PV input on terminals V1, V+, V-. It allows you to set the displayed reading to correspond to the electrical input range on linear mV volt or mA inputs 2. Input 2. This applies to module 3 when fitted with a DC Input module. It allows you to set the displayed reading to correspond to the electrical input range on linear mV volt or mA inputs 3. Analogue I/O Modules configured as DC Retransmission. It allows you set up the electrical output to correspond with the displayed value 3.5.1.1 Single Point Offset A single offset applies to Inputs 1 & 2 and applies a fixed offset over the full display range of the controller. To calibrate, proceed as follows: Displayed value 1. Factory calibration Fixed offset 2. Set the source to the desired calibration value. 3. The controller will display the current measurement of the value. If the displayed value is correct, then the controller is correctly calibrated and no further action is necessary. If it is incorrect, then follow the steps shown below. 4. Input Connect the input of the controller to the source device to which you wish to calibrate. Figure 3-2: Fixed Offset 3.5.1.2 To Apply an Offset to Input 1 Do This This Is The Display You Should See 1. From any display press as many times as necessary to access the <iP List> header menu iP 2. Press to show <OfS.1> (Offset on input 1) OFS.1 or 3. Press required offset 3.5.1.3 to enter the 1.0 Additional Notes i An offset on Input 1 of +1.0 unit will be applied over the full range of the input. The same procedure is followed to apply an offset to Input 2 Two Point Calibration Two point calibration is only available in Configuration level and allows you to adjust both the low point (zero) and high point (span) independently when using a mV, volt or mA input. The examples in sections 4.5.2. and 4.6.10. show how this is applied to a process input and retransmission value respectively. 24 Part Number HA027240 Issue3.0 Nov-2003 2408i Indicator 3.6 Engineering Manual TRANSDUCER CALIBRATION This indicator supports a number of different two and four wire transducer types. Each type is explained in this section. 3.6.1 Shunt Calibration Shunt calibration is so called since it refers to switching a calibration resistor across one arm of the four wire measurement bridge in a strain gauge transducer. It also requires the use of a Transducer Power Supply module wired as shown in Figure 3-3. Calibration resistor A A D C D C B B 3D 3C 3B 3A 2D 2C + 2B - 2A 1D 1C Tdcr PSU 1 JF 1B 1A HA PV input 1 V- V+ VI AC AB AA LC LB LA 3D 3C 3B 3A 2D 2C Calibration resistor Further terminals removed for clarity JF 2B + 2A 1D 1C 1B Tdcr PSU 1 1A HA PV input 1 V- V+ VI Relay Output 1 AC AB AA LC LB LA Relay Output 1 Wiring for Transducer with Internal Calibration Resistor Wiring for Transducer with External Calibration Resistor Both diagrams show connections to Input 1/main input. If Input 2 is used in module position 3, the transducer output can be connected to terminals 3C (+) and 3D (-) Figure 3-3: Wiring for Strain Gauge Calibration 3.6.2 To Calibrate a Strain Gauge Bridge Transducer The strain gauge transducer is calibrated as follows:1. Remove any load from the transducer to establish a zero reference 2. Enter ‘Scale Low’ <ScL.L> and ‘Scale High’ <ScL.H> values which are normally set at 0% and 80% of the span of the transducer 3. Start the procedure using the low point calibration parameter <pnt.L>, or a digital input wired to this parameter The indicator will automatically perform the following sequence for a transducer with its own integrated calibration resistor: 1. Disconnect the shunt resistor 2. Calculate the low point calibration value by continuously averaging two lots of 50 measurements of the input until stable readings are obtained 3. Connect the shunt resistor by closing a contact between terminals D and C. 4. Calculate the high point calibration value by averaging two lots of 50 measurements of the input For transducers which do not contain a calibration resistor the indicator will switch in its own internal calibration resistor. Part Number HA027240 Issue 3.0 Nov-2003 25 Engineering Manual 3.6.2.1 First - Enter The Calibration Password Do This 1. From any display press as many times as necessary to access the <CaL1> (or <2>) List’ header to scroll to <CAL.P> 2. Press 3. Press or to enter the calibration password. In a new instrument the default is <3> to show <CAL> 4. Press 5. Press or to turn calibration to <USEr> 3.6.2.2 to scroll to <ScL.L> 6. Press 7. Press or to enter the scale low value (normally 0) 8. Press 9. Press or to enter the scale high value 11. Press to scroll to <ScL.H> Additional Notes CAL1 CAL.P i The first parameter in the list is <tArE> Calibration of Tare weight has already been described in Operator Level Section 2.3 When the correct password is entered <PASS> will flash briefly on the display A password of <0> allows the instrument to proceed directly to the next parameter 3 See start of this section for a description of User and Factory calibration USEr CAL This Is The Display You Should See ScL.L 0 Additional Notes i This sets the minimum (zero) point at which the transducer is to be calibrated. This is typically 0%. This sets the maximum (span) point at which the transducer is to be calibrated. This is typically 80% of the transducer range. ScL.H 80.00 to show <Pnt..L> or to turn calibration to <on> 26 This Is The Display You Should See Next – Calibrate the Strain Gauge Transducer Do This 10. Press 2408i Indicator on Pnt.L buSY i The indicator will show ‘busy’ while calibrating before returning to <Pnt.L> If the calibration fails the alarm message <tdr.F> is flashed The <Pnt.L> parameter may have been wired to a digital input for activation by an external switch The operation is identical except that the indication will return to the display which was being shown prior to the activation of the switch Part Number HA027240 Issue3.0 Nov-2003 2408i Indicator 3.6.3 Engineering Manual Load Cell Calibration A load cell with V, mV or mA output may be connected to Input 1 or Input 2. Indicator under Calibration 3D 3C 3B 3A 2D 2C Reference Weight 2B This diagram shows connections to input 1/main input + 2A 1D 1C 1B 1A Transducer supply 1 JF JE JD JC JB If Input 2 is used in module position 3, the transducer output can be connected to terminals 3C (+) and 3D (-) JA HF HE HD HC HB HA PV input 1 Load Cell V- V+ VI AC AB AA LC LB LA Figure 3-4: Load Cell Calibration 3.6.4 To Calibrate a Load Cell The load cell is calibrated as follows: 1. Set <ScL.L> and <ScL.H> for the required ‘zero’ and ‘span’ readings on the display 2. Remove any load and start the procedure using the low point calibration parameter <Pnt.L> 3. or a digital input wired to this parameter. The indicator will calculate the low calibration point 4. Place a reference weight on the load cell and turn on the high point calibration parameter <Pnt.H>, or a digital input wired to this parameter. The indicator will then calculate the high calibration point. Note:If <Pnt.L’= ‘On’, <Pnt.H> cannot be turned to <on> If <Pnt.H’= ‘On’, <Pnt.L> cannot be turned to <on> Either must complete before the other can be set to <on> First enter the calibration password as described in section 3.6.2.1. Then:Do This This Is The Display You Should See Additional Notes Set the required display ‘Span’ and ‘Zero’ parameters to scroll to <ScL.L> 6. Press 7. Press or to enter the scale low value (normally 0) 8. ScL.L 0 i This sets the minimum (zero) display reading when the transducer has its lowest weight This sets the maximum (span) display reading when the transducer has its highest weight Repeat for <ScL.H> Set the load cell to its ‘zeroed’ condition 9. Press to show <Pnt..L> 10. Press or to turn calibration to <on> Pnt.L on buSY The indicator will show ‘busy’ while calibrating If the calibration fails the alarm message <tdr.F> is flashed When the calibration low point is complete, place the reference load on the load cell 11. Press to show <Pnt..H> Pnt.H 12. Press or to turn calibration to <on> on buSY i Part Number HA027240 Issue 3.0 Nov-2003 The indicator will show ‘busy’ while calibrating and will flash <done> when complete . If the calibration fails the alarm message <tdr.F> is flashed The <Pnt.L> and <Pnt.H> parameters may have been wired to digital inputs for activation by external switches The operation is identical except that the indication will return to the display which was being shown prior to the activation of the switches 27 Engineering Manual 3.6.5 2408i Indicator Comparison Calibration Comparison calibration is most appropriate when calibrating the indicator against a second reference instrument. Reference Measurement Indicator under Calibration 3D 3C 3B 3A 2D 2C 2B + 2A 1D 1C 1B 1A This diagram shows connections to Input 1/main input Transducer supply 1 JF JE JD JC JB If Input 2 is used in module position 3, the transducer output can be connected to terminals 3C (+) and 3D (-) JA HF HE HD HC HB HA PV input 1 V- V+ VI AC AB AA LC LB LA Reference Transducer Measurement Transducer Load Figure 3-5: Comparison Calibration 3.6.6 To Calibrate by Comparison with an External Reference In this case the process calibration points are not entered ahead of performing the calibration. The input may be set to any value and, when the system is stable, a reading is taken from the reference measurement device and entered into the indicator. The indicator stores both this new target value and the actual reading taken from its input. The process is repeated at a different value, with the indicator storing both the new target value and the reading taken from its input. First enter the calibration password as described in section 3.6.2.1 Then:Do This This Is The Display You Should See Additional Notes Allow the process to settle at the low calibration point to show <Pnt..L> 6. Press 7. Press or to turn calibration to <on> Pnt.L on The indicator will alternate between the message ‘Adjust’ and the value shown in the main display If no key is pressed for 45 seconds the indicator will return to the HOME display This parameter can be configured to operate from a digital input which, in turn, may be connected to a push-button switch 8. Press or to enter the value read by the reference instrument .0.012 Adj The indicator will resume the alternating display The values will only be accepted by scrolling away from <Adj>, unless this parameter has been activated by a digital input Allow the process to settle at the high calibration point 9. Repeat 2 to 4 above for <Pnt.H> Pnt.H on This parameter can be configured to operate from a digital input which, in turn, may be connected to a push-button switch i Note:The low calibration point cannot be higher than the high calibration point These inputs can, however, be scaled to values which are inverted The indicator is now calibrated against the reference source. When complete the indication returns to the HOME display. 28 Part Number HA027240 Issue3.0 Nov-2003 2408i Indicator 3.6.7 Engineering Manual Manual Calibration Manual calibration sets the minimum and maximum displayed reading to correspond to the minimum and maximum electrical input values. For example, 0 to 8mV to read 1.0 to 500.0 units. First enter the calibration password as described in section 3.6.2.1 Then:Do This 6. Press This Is The Display You Should See to show <inP..L> 7. or to adjust the Press input to the minimum electrical input, e.g. <0.0> 8. Press 9. or to adjust the Press input to the minimum display reading, e.g. <1.0> inP.L 0.0 to show <ScL..L> ScL.L 10. Repeat 6 to 9 above for <inP.H> and <ScL.H> Additional Notes inP.H 1.0 8.0 .500.0 ScL.H 3.6.8 Auto-Tare or Display Zero The auto-tare (display zero) function is used, for example, when it is required to weigh the contents of a container but not the container itself. The procedure is to place the empty container on the weigh bridge and ‘zero’ the controller. Since it is likely that following containers may have different tare weights the auto-tare feature is always available in the indicator at Operator access level. The effect of auto-tare is to introduce a DC bias to the measurement, as shown in Figure 3-6 below. New Scale High Tare offset Scale High New Scaling Tare value PV at tare point New Scale Low Scale Low Original Scaling Tare offset Tare offset Input Low Input at autoInput High tare point Figure 3-6: Effect of Auto-Tare The procedure to initiate tare calibration was described in 2.3. Note:- A Tare calibration will change the values of ‘Scale High’ <ScL.L> and ‘Scale Low’ <ScL.H> The parameter <tArE.v> sets a fixed offset on the tare value. This may be used, for example, if containers of different weights are placed on a pallet of known weight. This known weight can then be entered in <tArE.v>. Part Number HA027240 Issue 3.0 Nov-2003 29 Engineering Manual 3.6.9 2408i Indicator To Enter a Fixed Offset to the Tare Value Do This The Display You Should See 1. Press as many times as necessary to select ‘CAL1 CAL1’ CAL2’ CAL1 or ‘CAL2 CAL2 as appropriate 2. Press ‘CAL CAL’ CAL 3. or Press select ‘USER’ 4. Press ‘tare.v tare.v’ tare.v 5. or to Press enter the offset value to scroll to Additional Notes CAL1 CAL USER to to scroll to tare.v 10 The offset value represents the weight of the pallet for example If this value is to be changed on a regular basis, it may be convenient to ‘promote’ the tare.v parameter to the Operator level. The procedure for this is described in section 3.4. 30 Part Number HA027240 Issue3.0 Nov-2003 2408i Indicator 3.7 Engineering Manual CUSTOM LINEARISATION The linearisation uses a 15 point straight line fit. Figure 3-7 shows an example of a curve to be linearised and is used to illustrate the terminology used in the parameter list Displayed value Notes: VAL.H 1. The linearisation block works on rising inputs/rising outputs or rising inputs/falling outputs. It is not suitable for outputs which rise and fall on the same curve. Terminated search 2. Input Lo/Output Lo and Input Hi/Output Hi are entered first to define the low and high points of the curve. It is not necessary to define all 15 intermediate points if the accuracy is not required. Points not defined will be ignored and a straight line fit will apply between the last point defined and the Input Hi/Output Hi point. VAL.2 to VAL.14 Ignored data points VAL.L in L in H in 2 ( to 14) Electrical input Figure 3-7: Linearisation Example 3.7.1 Example: To Linearise Input 1 Do This This Is The Display You Should See 1. Press as many times as necessary to access the <CUSt1> list header menu in L Press 3. Press or to enter the low electrical input value 4. Press VAL.L Press or to enter the low electrical input value 6. Repeat steps 2 to 5 for the high end and then for all intermediate steps Input 1 is set to +1.0 units 1.0 to show <VAL.L> 5. 3.7.2 CUSt1 to show <in L> 2. Additional Notes The display will read 2.0 corresponding to the low electrical input (+1 unit) 2.0 Note:The values entered must be continuously increasing or decreasing Compensation for Sensor Non-Linearities The custom linearisation feature can also be used to compensate for errors in the sensor or measurement system, so that discontinuities in the curve can be calibrated out. Figure 3.8 shows an example of the type of discontinuity which can occur in the linearisation of a temperature sensor. Output Hi eg 1000oC Cal Point 6 The calibration of the sensor uses the same procedure as described above. Adjust the output (displayed) value against the corresponding input value to compensate for any errors in the standard linearisation of the sensor Cal Point 5 Output 2( to 14) Cal Point 4 Cal Point 3 Cal Point 2 Cal Point 1 Output Lo eg 0oC Input Lo eg 0oC Electrical input Input 2( to 14) Input Hi eg 1000oC Figure 3-8: Sensor Non-linearities Part Number HA027240 Issue 3.0 Nov-2003 31 Engineering Manual 4 2408i Indicator CONFIGURATION LEVEL The 2408I indicator is supplied configured in accordance with the ordering code (see section 5). The configuration of the indicator, as defined by columns 11 to 16 of the order code, can be changed on site, if necessary, to meet the requirements of the installation. Similarly, the positions or types of plug in module can be changed if required. This section describes the procedures to be followed. 4.1 HARDWARE CONFIGURATION - I/O MODULES Optional plug-in modules are fitted simply by sliding them into the relevant position as shown in Figure 4-1. The connections for these modules are made to the upper row of connector blocks as shown in section 1.3. When a module is added, removed or changed the indicator will flash hardware error ‘<HWEr> on power up. To acknowledge this it is necessary to go into configuration level. 1. Press either or until <ConF> is displayed. 2. Press or to enter the configuration level password passcode (factory default 2) 3. Press either or again and the hardware error is acknowledged The full list of modules available is shown in the ordering code. Figure 4-1: View of the Plug-in Modules 4.2 SOFTWARE CONFIGURATION Configuration level allows you to set up parameters in the indicator which defines how it will operate. Examples are:• • • • • The configuration of the alarms The digital input functions The relay output configuration The configuration of the modules The passwords Parameter tables in this section give the full list of configuration parameters. 4.2.1 To Select Configuration Access Level Do This 1. From any display press as many times as necessary to access the ‘Access List’ header 2. Press 3. Press or passcode to show <Code> Press 5. Press or <conF> level 6. Press 7. ACCs PASS CodE Press or to enter the configuration level passcode If or are pressed the word <List> is displayed for 2 secs List ACCS <PASS> will be displayed momentarily when the correct password has been entered In the special case that the passcodes have been configured as <0>, it will not be necessary to enter a passcode 2 secs conF Goto to select to show <ConF> Additional Notes The factory default passcode is <1> 2 secs to enter the to show <Goto> 4. This Is The Display You Should See The configuration factory default passcode is <2> 2 secs PASS ConF ‘<PASS> will be displayed momentarily when the correct password has been entered In the special case that the passcodes have been configured as <0>, it will not be necessary to enter a passcode The indicator is now in configuration level 32 Part Number HA027240 Issue3.0 Nov-2003 2408i Indicator 4.3 Engineering Manual LOCATION OF PARAMETERS – FROM INDICATOR BLOCK DIAGRAM The indicator consists of a number of internal function blocks connected together. Each function block has a number of parameters found in lists to which the user has access. The block diagram shows location of these parameters within the indicator. Display Parameters 200.0 iP ConF PLANT INPUTS Input 1 TCs PRT Pyrometer mA. mV, Volts HOME List For example Process Variable Alarm Setpoint Linearised Input 1 Linearised Input 2 iP LiSt Parameters in Operator level iP ConF Parameters in configuration level iP LiSt SP LiSt SP LiSt PLANT OUTPUTS Input Cal <tYPE> = <OFF> Input linearisation Transducer scaling Li.1 3A ConF SP1H SP1L 3A ConF Hi Lo Ftn SEL trAn iP LiSt 3A Cal <tYPE> = <OFF> Input 2 TCs PRT Pyrometer mA. mV, Volts Input linearisation Transducer scaling PV.SL Func = rSP SP1 SPH SPL SP.PV Li.2 SP2H SP2L SP2 Alarms AL ConF AA ConF AL LiSt Alarm 1 Normal/ Invert AA Relay output Relay Normal/ Invert Relay /logic Module output Relay, Logic, Alarm 2 OR Alarm 3 Other alarms Alarm 4 1a-3A 1a 3A ConF Digital Comms cmS ConF Digital Inputs Logic inputs LA, LB, Module 2 Logic I/P Digital Comms LA ConF 1a-3A 1a 3A ConF OP PV Err SP Issue 3.0 Nov-2003 RS232 RS484 RS422 Modbus/ Profibus Retrans-mission Lb ConF ConF Figure 4-2: Indicator Block Diagram Part Number HA027240 cmS LiSt Retransmission mA, Volts 33 Engineering Manual 4.4 2408i Indicator NAVIGATION DIAGRAM (CONFIGURATION LEVEL) he navigation diagram shows the location of configuration parameters. A. Press to step across the list headings. This is a continuous list. B. Press to step down the parameters within a particular list. You will eventually return to the list heading. C. D. Press Press to view the value of a selected parameter. Keep pressing to decrease the value. to view the value of a selected parameter. Keep pressing to increase the value. The diagram below shows the full list of possible parameters. In practice, the parameters that appear will depend upon the configuration of your particular indicator . Instrument Configuration Sensor Input Configuration Alarm Configuration Digital input 1 Configuration Digital input 2 Configuration Relay output 1 Configuration Comms Module Configuration HA inSt iP AL unit inPt AL 1 id id id dEc.P CJC Ltch Func Func Func Func Ac.bu imP bLoc Section 4.5.4 Section 4.5.4 SEnS baud Section 4.5.1 inP.L AL 2 AL 1 PrtY inP.H Ltch AL 2 dELY VAL.L bLoc AL 3 rES VAL.H AL 3 AL 4 Section 4.6.1 tYPE Ltch Sbr bAnd bLoc SPAn Section 4.5.2 AL 4 rmt.F Ltch iP1.F bLoc nw.AL Section 4.5.3 Section 4.5.7 LA Lb AA id Figure 4-3: Navigation Diagram 34 Part Number HA027240 Issue3.0 Nov-2003 2408i Indicator Engineering Manual Return to inSt PDSIO Module Configuration Module 1 Configuration Module 2 Configuration Module 3 Configuration Calibration Passwords Leaving Configuration 1A/b/C 2A/b/C 3A/b/C CAL PASS Exit id id id id rCAL ACC.P Func Func Func Func PV cnF.P Section 4.7.1 to 4.7.4 CAL.P JA VAL.L VAL.H The parameters which follow depend upon the type of module fitted. See Sections 4.6.3. to 4.6.9. Section 4.7.6 Section 4.7.5 Section 4.6.2 Part Number HA027240 Issue 3.0 Nov-2003 35 Engineering Manual 4.5 2408i Indicator CONFIGURATION PARAMETER TABLES - ALL INDICATORS The tables in this section list the parameters available for the fixed functionality of the indicator. 4.5.1 Instrument configuration list inSt inst Instrument list Option Meaning Default setting unit To select display units *C Celsius Defined by the *F Fahrenheit ordering code, *K Kelvin otherwise *C nonE None (for linear inputs) nnnn nnn.n nn.nn n.nnn None To enable Front panel EnAb Button enabled Ack/Reset button diSa Button disabled dEC.P Ac.bu 4.5.1.1 To set the number of decimal places in the display Customer setting Defined by the ordering code, otherwise nnnn One Two Three EnAB Example: To Change the Number of Decimal Places in the Display Do This This Is The Display You Should See Additional Notes Enter configuration level as described in section 4.2.1. 1. Press until the ‘Instrument List’ header is shown 2. Press shown 3. until <dEc.P> is or to move the Press decimal point position 4.5.1.2 inSt 2 secs nnn.n dEc.P i The display will return to <dEc.P> after approximately 2 seconds Example: To Disable the Front Panel Ack/Reset Button Do This This Is The Display You Should See Additional Notes Enter configuration level as described in section 4.2.1. 1. Press until the ‘Instrument List’ header is shown 2. Press shown until <Ac.bu> is Press disabled or 3. 36 to select inSt 2 secs diSA Ac.bu i The display will return to <Ac.bu> after approximately 2 seconds Part Number HA027240 Issue3.0 Nov-2003 2408i Indicator 4.5.2 Engineering Manual Sensor Input Configuration List IP iP Sensor Input Option Meaning Default setting inPt To configure input type j.tc J thermocouple Defined by the See also example 4.4.2.1. k.tc K thermocouple ordering code, L.tc L thermocouple otherwise ktc NOTE: r.tc R thermocouple After selecting an input type, do b.tc B thermocouple not forget to adjust the setpoint n.tc N thermocouple limits in Full Access level. t.tc T thermocouple S.tc S thermocouple PL 2 Platinell II none Custom downloaded input rtd 100Ω Platinum resistance thermometer custom input is mV Linear millivolt supplied, voLt Linear voltage none will be mA Linear milliamps replaced by the Sr V Square root volts reference number Sr A Square root milliamps shown in the mV.C 16-point millivolt custom linearisation ORDERING V.C 16-point Voltage custom linearisation CODE mA.C 16-point milliamp custom linearisation section 5 Auto See 15-point CuSt list CJC ImP Cold junction compensation Auto Automatic compensation (CJC does not appear for 0*C 0°C external reference Process or RTD inputs. 45*C 45°C external reference For process see 50*C 50°C external reference ‘Linear input scaling’ below OFF No cold junction compensation Input impedance threshold for OFF Sensor break alarm disabled sensor break alarm Auto 1.5KΩ If the sensor impedance Hi 5KΩ exceeds this value, sensor HiHi 15KΩ break alarm activates Customer setting * If a different Auto Linear input scaling (-9.99 to +80.00mV). These parameters appear after <inPt> whenever <mV>, <voLt>, <mA>, <Sr V> or <Sr A> are chosen as the input type. This allows for the low and high displayed values to be set up against the corresponding electrical input values. Off Type of calibration (see 3.3.5.) tYPE Off Shunt Shnt Load Cell Ld.C Comparison CmP Manual mAn bAnd 0-99.99 Settling band. 0-99.99 0.5 The indicator automatically determines when the input has become stable by continuous sampling. When the average value between two consecutive samples is within the settling band the indicator will then allow calibration to take place. If readings are not stable within this period the indicator will abort the calibration The following parameters appear for process inputs and allow the display to be calibrated to the electrical input. See also example 4.5.2.2. InP.L Electrical input low -100.0 to100.0 mV InP.H Electrical input high 0.0 to 20.0 mA 0.0 to 10.0 Volts 0.0 100.0 if mV 20.0 if mA 10.0 if volts VaL.L Displayed value low -9999 to 99999 Defined by the SP limits in ordering code, else 0 VAL.H Displayed value high -9999 to 99999 Defined by the SP limits in ordering code, else 100 Part Number HA027240 Issue 3.0 Nov-2003 37 Engineering Manual 4.5.2.1 2408i Indicator Example: To Select a Different Thermocouple Type Do This This Is The Display You Should See Additional Notes Enter configuration level as described in section 4.2.1. 1. Press until the ‘Input List’ header is shown 2. Press 3. Press or input type until <inPt> is shown iP 2 secs r.tc inPt to select the i The display will return to <inPt> after approximately 2 seconds Notes: The next parameter is cold junction compensation, <CJC>. It is used to compensate for ambient temperature changes measured at the point at which the thermocouple (or compensating) cable connects to the indicator. Automatic, Auto, measures the temperature at the rear terminals and compensates for any ambient temperature changes. It will only be necessary to change the <CJC> parameter if an external temperature reference source is to be used. Sensor break is measured by the impedance, <imP>, of the sensor circuit and an alarm is given if this is greater than a set amount. For thermocouples set this to <Auto>. For certain types of sensor its working impedance may be greater than the 1.5KΩ set by Auto. It will only be necessary to change <imP> if this type of sensor is to be used. 4.5.2.2 Example: To Adjust Display Reading for a Process Type Input This example is 4 – 20mA input to read 0 to 100 on the display Do This This Is The Display You Should See Additional Notes Enter configuration level as described in section 4.2.1. The mA input is selected in the same way as the thermocouple input above. 1. 2. 3. In the input list press <inP.L> is shown Press or input eg 4mA Press shown until to set the low Displayed value inP.L 2 secs 20.0 or Press input eg 20mA 5. Press shown to set the high until <VAL.L> is VAL.L eg (0) inP.H Inp.L eg (4) 2 secs 0.0 6. or to set the low Press displayed value eg 0.0 7. Press shown 38 4.0 VAL.H eg (10) until <inP.H> is 4. 8. 2 secs until <VAL.H> is or to set the low Press displayed value eg 100.0 VAL.L 2 secs 100.0 VAL.H Inp.H eg (20) Electrical Input i The display will return to <inPt> after approximately 2 seconds Part Number HA027240 Issue3.0 Nov-2003 2408i Indicator 4.5.3 Engineering Manual Alarm Configuration Alarms are used to alert an operator when the process value has exceeded a pre-set level or when some other fault condition has occurred. They normally switch an output - usually relay - to provide an interlock on a machine/process or audio/visual indication to an operator. The Model 2408i has four internal ‘soft’ alarms which are configured in the <AL> list below. A soft alarm means indication only. To make a soft alarm activate a physical output it must be ‘attached’ to that output. See: section 4.5.8. ‘Relay Output Configuration’ ALARM DEFINITIONS: The following alarm types can be configured: Full Scale High Full Scale Low Deviation band Deviation high Deviation low Rate of change The Process Value is above a set high level The Process Value is below a set low level The difference between setpoint and the process value is outside a set band The difference between setpoint and the process value is above a set value The difference between setpoint and the process value is below a set value The Process Value is changing faster than a set rate AL Alarm list Option Meaning Default setting AL 1 To select Alarm 1 Type OFF The alarm is disabled Defined by the FSL Full Scale Low alarm - main process value ordering code, FSH Full Scale High alarm - main process value otherwise OFF dEv Deviation band alarm - main process value DHi Deviation High alarm - main process value DLo Deviation Low alarm - main process value dv1 Deviation band alarm - input 1 DH1 Deviation High alarm - input 1 DL1 Deviation Low alarm - input 1 dv2 Deviation band alarm - input 2 DH2 Deviation High alarm - input 2 DL2 Deviation Low alarm - input 2 FL2 Full Scale Low alarm on Process Value input 2 FH2 Full Scale High alarm on Process Value input 2 LSP Master Setpoint Low alarm HSP Master Setpoint High alarm FL1 Full scale low alarm on linearised input 1 FH1 Full scale high alarm on linearised input 1 rat Rate of change alarm, minutes – main PV raS Rate of change alarm, seconds – main PV rt1 Rate of change alarm, minutes - input 1 rS1 Rate of change alarm, seconds - input 1 rt2 Rate of change alarm, minutes - input 2 rS2 no YES Eunt mAn Rate of change alarm, seconds - input 2 Non-latching Latched with automatic resetting (See note 1) (See note 3) Event output (See note 2) Latched with manual resetting No blocking Blocked until first good (See note 4) (See note 5) Disabled. Inhibits alarms Enabled. Alarms operate when in sensor break Ltch To select alarm latching type bLoc To select alarm blocking no YES Sbr.t To inhibit process alarms in sensor break disA EnAb The above sequence is repeated for: Note 1 Customer setting Alarm number 1 2 3 4 no no EnAb <AL 2> (alarm 2), <AL 3> (alarm 3) and <AL 4> (alarm 4) Automatic Resetting means that, once the alarm has been acknowledged, it will automatically clear when it is no longer true Note 2 Manual resetting means that the alarm must first clear before it can be reset Note 3 Events can be used to operate an output in the same way as an alarm but will NOT flash an alarm message, and can be used to trigger external events. For example, an event output could be used to open/close a vent at a pre-set temperature Note 4 Blocking Mode. After power on, the process value must first enter a good state before the alarm becomes active. When once this process has been completed the alarm operates in its normal mode and does not become relevant again until power to the indicator is turned off and on again. This is particularly useful for low alarms which can be ‘blocked’ while the process is warming up. It is advised that blocking alarms are not used with rate of change alarms Note 5 Sbr.t When this parameter is set to ‘Disabled’, all alarms from the process will be inhibited should a sensor break condition occur. When Enabled process alarms will be shown (as in previous software versions) even in a sensor break condition. Part Number HA027240 Issue 3.0 Nov-2003 39 Engineering Manual 4.5.3.1 2408i Indicator Example: To Configure Alarm 2 to Operate When Input 2 Exceeds A Set Value Do This This Is The Display You Should See Additional Notes Enter configuration level as described in section 4.2.1. 1. Press until the ‘Alarm List’ header is shown 2. Press shown until the <AL 2> is Press shown or 3. AL 2 secs FH2 AL 2 until <FH2> is i The display will return to <AL 2> after approximately 2 seconds <FH2> is Full Scale High alarm on input 2 The next two parameters – Alarm Latching and Alarm Blocking may be set in the same way if they are required. 4.5.4 Alarm Inhibit The alarm inhibit feature may be used to prevent any alarms from being indicated until a ‘noisy’ process variable has settled. Alarm inhibit is activated by a digital input on either Digital Input 1 or 2 - see section 4.5.4. When the digital input is turned to OFF any alarms which are active will be displayed. If a delay has been set on the alarm, the delay period will start from the time when the input is turned OFF. Entering Alarm Inhibit resets both the alarm delay timer and latched alarms. The action of Alarm Inhibit is shown in the diagram below for a Full Scale High Alarm. PV Alarm Inhibit input ON Alarm Inhibit input OFF Alarm Inhibit Input PV High Alarm setpoint threshold Time PV High Alarm State Alarm indicated No Alarm Inhibit Alarm indicated With Alarm Inhibit Alarm indicated With Alarm Inhibit + Delay Delay time Figure 4-4: Effect of Alarm Inhibit 40 Part Number HA027240 Issue3.0 Nov-2003 2408i Indicator 4.5.5 Engineering Manual 2408i Indicator With Alarm Inhibit Timer 2408i indicators fitted with software versions 3 and greater contain an alarm inhibit timer which is used to inhibit alarms for a set period after power-up and when a digital input is closed. 4.5.5.1 Operation In the ‘AL’ list in Operator Level there are two parameters associated with the inhibit function see section 3.3.2. These are the alarm inhibit status’ In.AL and the inhibit time ‘InH.t’. To adjust the alarm inhibit time:Do This This Is The Display You Should See Additional Notes 2 secs as 1. In Operator Level, press many times as necessary to select ‘AL’ LiSt AL 2 secs 2. Press to read ‘InAL’ 3. Press ‘OFF’ or OFF to select ‘On’ or 10.0 InH.t to read ‘InH.t’ This sets the Alarm Inhibit status: On/OFF. The display will revert to ‘In.AL’ after 2 seconds In.AL 2 secs 4. Press Press or to show ‘List’ if required. The display will revert to ‘AL’ after 2 seconds This sets the Alarm Inhibit Time 0 to 999.9 seconds. The display will revert to ‘InH.t’ after 2 seconds or to select the 5. Press Alarm Inhibit Time On power up alarms will be inhibited for the set time. When the inhibit time is set to OFF, the timed inhibit is disabled. 4.5.5.2 Configuration of Digital Inputs for Alarm Inhibit Two digital input functions can be configured for the alarm inhibit. Permanent alarm inhibit The permanent inhibit function ‘in.AL’ is level triggered. It permanently inhibits all alarms when closed and enable all alarms when open. Do This This Is The Display You Should See as 1. In Configuration Level, press many times as necessary to select ‘LA’ or ‘Lb’ – the digital inputs. See also section 4.5.6. 2. Press 3. Press to select ‘in.AL’ Digital input configuration ConF LA/Lb 2 secs to read ‘Func’ or 2 secs Additional Notes in.AL Func Level triggered alarm inhibit Please note: when using this function ensure that the inhibit timer is set to OFF. Timed alarm inhibit The timed inhibit function ‘tm.AL’ is edge triggered. It will start the inhibit timer when closed and do nothing when opened. Alarms will be inhibited during the timing period at the end of which they will be enabled again. From stage 1 above:Do This 4. Press to read ‘Func’ 5. Press or This Is The Display You Should See 2 secs to select ‘in.AL’ Part Number HA027240 Issue 3.0 Additional Notes Timed alarm inhibit tm.AL Func Nov-2003 41 Engineering Manual 4.5.6 2408i Indicator Digital inputs 1 and 2 Configuration LA Lb or LA Digital input 1 Lb Digital input 2 id Func Option Meaning Default setting Customer setting Identity of input LoG.i Logic input LoG.i Read only Function nonE Function not configured none rmt Remote setpoint select Ac.AL Alarm acknowledge Accs Select full access level Loc.b Keylock (disables all front panel buttons except the ACK/RESET button) up Simulate pressing of the button dwn Simulate pressing of the button ScrL Simulate pressing of the button PAGE Simulate pressing of the button PV.SL Process value select. Closed = input 1 4.5.6.1 Open = input 2 tar.1 Initiate automatic tare calibration of input 1 tar.2 Initiate automatic tare calibration of input 2 PtL.1 Start the calibration at point 1, normally the low point PtL.2 Start the calibration at point 2, normally the low point PtH.1 Start the calibration at point 1, normally the high point Pth.2 Start the calibration at point 2, normally the high point in.AL Alarm inhibit (often used in conjunction with transducer calibration to prevent alarms during the calibration process) P.HLd Peak hold HLd1 Sample and Hold on PV input 1 HLd2 Sample and Hold on PV input 2 UCAL Enables calibration access for CAL1 and CAL2 lists Example: To Configure Digital Input ‘A’ for Tare Calibration Do This This Is The Display You Should See Additional Notes Enter configuration level as described in section 4.2.1. 2. Press until the <LA> List’ header is shown 2. 3. Press shown Press is shown until the <Func> is or until <tAr.1> LA The display will return to Func after approximately 2 seconds 2 secs tAr.1 Func When a connection is made between rear terminals LC and LA a tare calibration is initiated. The same procedure applies to any other option shown in the Digital Inputs table and also to the second digital input which uses list <Lb>. 42 Part Number HA027240 Issue3.0 Nov-2003 2408i Indicator 4.5.7 Engineering Manual Peak Hold and Sample and Hold Peak Hold logs the maximum and minimum values that the indicator reads during a particular process. The peak hold value can be displayed as the main front or back display parameter, as described in section 2.1.2. Sample and Hold logs the reading at the moment that the digital input becomes true. Both functions are initiated by turning digital input 1 or digital input 2 to ON. They are edge triggered so to reset and re-start the input must be turned OFF and ON again, as detailed in Figure 4.5 below. The values may be read in two ways:1. From Information List <inFo> as:LoG.L LoG.H LoG.A Minimum process variable Maximum process variable Average process variable These values are reset when the parameter <rES.L> in the <inFo> list is turned to <YES>, or the indicator power is cycled. 2. Maximum and minimum values can be promoted to the main front or back display as <PV.Hi> or <PV.Lo>, see section 2.1.2. They are reset when the power to the controller is cycled or by setting the values of <LoG.L> and <LoG.H> to zero in the <inFo> list. Peak Hold PV Maximum PV <LoG.H> Average PV <LoG.A> PV Minimum PV <LoG.L> Sample and Hold Peak Hold does not read this point since the digital input is not set ON Digital input LA or LB OFF Set Restart Time Figure 4-5: Action of Sample and Hold and Peak Hold Part Number HA027240 Issue 3.0 Nov-2003 43 Engineering Manual 4.5.8 2408i Indicator Relay Output 1 Configuration The controller can be supplied so that Relay 1 will operate when a particular alarm occurs. This will be defined in the order code, see section 5. This list defines which of the internal ‘soft’ alarms are attached to relay output 1. It is possible to attach more than one alarm to operate this relay. The procedure is described below:- AA AA Relay output 1 Option Meaning Default setting Customer setting id Identity of output rELY Relay rELY Read only Func Function of output none diG None Output disabled diG Digital alarm output. Output enabled nor inv Inverted (relay de-energised in alarm) SenS Sense of the output. inv Normal (relay energised in alarm) To Attach Alarms to the Relay Output. Any combination of the following alarms can be attached to relay output 1. Press to select a particular alarm. Press or to select YES if you want it to activate the relay. Select no to disconnect a given alarm. These parameters only appear if Func = diG 1---* Alarm 1 YES / no 2---* Alarm 2 YES / no 3---* Alarm 3 YES / no 4---* Alarm 4 YES / no Sbr Sensor break alarm YES / no Span Span The Process value exceeds the display limits YES / no rmt.F Remote failure. Either PDS remote setpoint input, OR 2nd analogue input open circuit YES / no no iP1.F Input 1 fail YES / no no nw.AL New alarm YES / no no 1. 44 Attaching Alarms to the relay nor Relay output 1 dIG no no no SEnS OR YES no inv no The three dashes correspond to the alarm type set in the <AL> list. If the alarm is disabled, <AL 1> or <AL 2> or <AL 3> or <AL 4> will be shown. Part Number HA027240 Issue3.0 Nov-2003 2408i Indicator 4.5.8.1 Engineering Manual Example 1: To Attach Alarm 1 to Relay Output AA It is recommended that an external device is connected so that an alarm condition is indicated when the relay is de-energised. In this way if the indicator is removed or its power is removed an alarm is indicated. To achieve this set relay sense to inverted operation. Indicator supply N/O Alarm indication supply AA Alarm ON N/C AB Relay Alarm OFF Figure 4-6: Example External Alarm Wiring Do This This Is The Display You Should See Additional Notes Enter configuration level as described in section 4.2.1. and configure Alarm 1 to the required type – see example 4.4.3.1. 1. Press until the <AA> List header is shown 2. Press shown 3. until the <Func> is Press or AA 2 secs Func to select diG The display will return to <Func> after approximately 2 seconds <diG> 4. 5. until the <SEnS> is Press shown or Press 2 secs SEnS to select inv <inv> 6. Press shown until the <1---> is 7. Press <YES> or 4.5.8.2 2 secs 1--- to select YES When alarm 1 is active the AA relay connected to terminals AA and AB will operate Example 2: To Operate Relay 1 of a Dual Relay Output Module Fitted in Slot 2 when Both Alarms 2 and 3 are Active The wiring should be as shown in Section 1.3 using rear terminals 2A and 2B Do This This Is The Display You Should See Additional Notes Enter configuration level as described in section 4.2.1. and configure Alarms 2 and 3 to the required types – see example 4.4.3.1. 1. Press until the <2A> List’ header is shown 2. Repeat steps 3 to 5 above 3. Press shown until the <2---> is 4. Press <Yes> or 5. Press shown until the <3---> is 6. Press <Yes> or 2A 2 secs 2--- to select YES i The display will return to <2---> after approximately 2 seconds The display will return to <inPt> after approximately 2 seconds 2 secs 3--- to select YES Relay 1 of module 2 will operate when either Alarm 2 or Alarm 3 is active This procedure can be repeated for all alarms which require to operate an output relay. Notes: 1. Logic module outputs can also be attached to alarms 2. Part Number HA027240 Issue 3.0 Nov-2003 Do not forget to say <no> to any alarm which may already be attached to an output if it is not required 45 Engineering Manual 4.6 2408i Indicator CONFIGURATION PARAMETER TABLES – PLUG IN MODULES 4.6.1 Communications Module The 2408i indicator can be fitted with the following digital communications modules:Protocol ModBus EI-Bisynch Module Fitted 2-wire RS485 4-wire RS422 RS232 2-wire RS485 4-wire RS422 RS232 DeviceNet 4.6.2 Order Code 2YM 2FM 2AM 2YE 2FE 2AE 2DN Communications Parameters HA HA Comms Module configuration Option id Identity of module cms Func Function (selects the comms. protocol) mod Meaning Default setting Customer setting Communications cms Read only Modbus protocol EI.bi EI-Bisynch protocol dnEt Devicenet - if the Devicenet module is fitted ProF Profibus - if the Profibus module is fitted bAud Selects the baud rate 1200, 2400, 4800, 9600, 19.20 (19,200) 9600 dELY Response delay: required by no No delay no some communications adapters YES 10mS delay Selects the parity nonE No parity (Modbus only) Even Even parity Prty res 4.6.3 nonE Odd Odd parity Selects the resolution FuLL Full resolution (Modbus and Profibus only) Int Integer resolution Option Meaning Default setting Customer setting Read only FuLL PDS input Module JA JA Comms Module configuration id Identity of module Pds.i PDS input Pds.i Func Function nonE No function configured none Sp.iP Setpoint input (to accept an input signal from a master source such as a controller with pds output) VAL.L Setpoint low value VAL.H Setpoint high value 46 -9999 to 99999 -9999 to 99999 0 0 Part Number HA027240 Issue3.0 Nov-2003 2408i Indicator 4.6.3.1 Engineering Manual Example: To configure Function, Baud Rate, Resolution and Node Address:Do This This Is The Display You Should See as many times as 6. Press necessary to select ‘HA’. 7. Press HA This is the position in which a digital communications module is fitted id If the module is present ‘id’ = Cms (digital communications) or ‘none’ if the module is not present ConF to read ‘id’ cms 8. Press to read ‘Func’ Func dnEt 9. Press to read ‘Baud’ 10. Press baud rate or 11. Press to read ‘rES to select the bAud 500 rES FuLL 12. ’ Press or ‘FuLL’ or ‘Int’ Additional Notes If Modbus or EI Bisync module is fitted, ‘Func’ = ‘mod’ or ‘EI.bi If Profibus module is fitted, ‘Func’ = ‘Prof’ If the DeviceNet module is fitted, ‘Func’ = ‘dnEt’ These ware be read only For Modbus or EI Bisync baud rate can be set to 1200, 2400, 4800, 9600, or 19,200 For Profibus baud rate is set automatically to a maximum of 1M5 For Devicenet baud rate can be set to 125(K), 250(K) or 500(K) ‘FuLL’ the decimal point position is implied, eg 100.1 is transmitted as 1001. ‘Int’ rounded to the nearest the integer value to select Node Address is set up in Full Access level Exit configuration level as described in the Installation and Operation Handbook, Chapter 6. Then:Do This This Is The Display You Should See cmS 1. Press as many times as necessary to select ‘cms’. 2. Press Additional Notes LiSt Addr to read ‘Addr’ Valid addresses are from 0 - 63 5 3. Press or to select the address for the instrument 4. Press nw.St to read ‘nw.St’ run Part Number HA027240 Issue 3.0 Nov-2003 Indicates the network status:‘run’ = network connected and operational ‘rdy’ = network connected but not operational OFF.L’ = network not connected 47 Engineering Manual 4.6.4 2408i Indicator DeviceNet Communications The following is applicable to DeviceNet only. 4.6.4.1 The EDS File The EDS (Electronic Data Sheet) file for the 2408i is named 2400.EDS and is available from your supplier, or electronically by going to Web site (www.eurotherm.com). The EDS file is designed to automate the DeviceNet network configuration process by precisely defining vendor-specific and required device parameter information. Following a data sheet metaphor, the EDS file describes a device’s configurable parameters, including its legal and default values and the public interfaces to those parameters. Software configuration tools utilize the EDS files to configure a DeviceNet network. 4.6.4.2 ODVA Compliance This interface has been tested to comply with the full requirements of the ODVA (Open DeviceNet Vendors Association) conformity tests. 4.6.4.3 DeviceNet Wiring Connections Terminal Reference CAN Label Color Chip HA V+ Red HB CAN_H White HC SHIELD None HD CAN_L Blue HE V- Black HF # # # ! Description DeviceNet network power positive terminal. Connect the red wire of the DeviceNet cable here. If the DeviceNet network does not supply the power, connect to the positive terminal of an external 11-25 Vdc power supply. DeviceNet CAN_H data bus terminal. Connect the white wire of the DeviceNet cable here. Shield/Drain wire connection. Connect the DeviceNet cable shield here. To prevent ground loops, ground the DeviceNet network in only one location. DeviceNet CAN_L data bus terminal. Connect the blue wire of the DeviceNet cable here. DeviceNet network power negative terminal. Connect the black wire of the DeviceNet cable here. If the DeviceNet network does not supply the power, connect to the negative terminal of an external 11-25 Vdc power supply. Connect to instrument earth Note: Power taps are recommended to connect the DC power supply to the DeviceNet trunk line. Power taps include: A Schottky Diode to connect the power supply V+ and allows for multiple power supplies to be connected. 2 fuses or circuit breakers to protect the bus from excessive current which could damage the cable and connectors. The earth connection, HF, to be connected to the main supply earth terminal. V+ 5 CAN-H Drain CAN-L V- 1 HA Wht V+ HB CAN-H HC Drain Blu Blk L N E HD CAN-L 121! terminating resistor required if not fitted internally Typical Interface Card (MASTER) Network Supply 24Vdc ( +1%) 250mV p-p Ripple Controller 0 Red HE VHF (SLAVE) Address 11 Controller 1 HA V+ V+ HB 121! HC HD V- HE V- L N E Fit 121Ω terminating resistor to last instrument in the chain HF (SLAVE) Address N+1 Daisy chain to further instruments Figure 4-7: Typical DeviceNet Wiring Diagram 48 Part Number HA027240 Issue3.0 Nov-2003 2408i Indicator 4.6.5 Engineering Manual Module 1, 2 and 3 Configuration Lists The identity of a module fitted in slots 1, 2 or 3 is shown by the first parameter in the module lists. • If the module is a single output only channel <A> is shown • If the module is a dual output channel <a> and channel <C> are shown • If the module is a triple output Channel <A>, channel <b> and channel <C> are shown Module configuration lists are summarised below:- 1A to 3C LIST HEADINGS: MODULE 1 MODULE 2 MODULE 3 1a, 1b, 1C 2a, 2b, 2C 3a, 3b, 3C (Note: The list heading corresponds to the terminal number to which the input/output is wired) Note: Channel ‘b’ only appears if a dual or triple channel module is fitted. Channel ‘C’ only appears if a triple channel module is fitted Customer setting in each channel number Module Parameters Option Meaning id nonE Module not fitted rELY Relay output LoG Logic output LoG.i Logic or contact closure input dC.iP 2nd analogue input module (Module 3 only) dc.re DC retransmission TPSU Transmitter power supply SG.SU Strain gauge power supply Identity of module 4.6.6 Changeover Relay or Dual Relay Output Module 4.6.7 Triple Logic Output Module 1A 1B 1C 2A 2B 2C 3A 3b 3C 3b 3C The parameter lists are the same for each of these modules as listed below:id Identity of module reLY LoG Logic Func Function of output nonE diG Module operation turned off SenS Sense of the output nor inv Output energises when TRUE Relay Customer settings in each channel 1A 1B 1C 2A 2B 2C 3A Digital Output de-energises when TRUE (default for alarms) If Func = nonE no further parameters are shown 1--- Alarm 1 YES / no 2--- Alarm 2 YES / no 3--- Alarm 3 YES / no Alarms are 4--- Alarm 4 YES / no attached to the Sbr Sensor break alarm YES / no output in the same Span Span YES / no way as relay rmt.F Remote failure YES / no output 1 iP1.F Input 1 fail YES / no nw.AL New alarm YES / no The changeover relay output module has a single output so the above parameters are shown under list <-A> only The triple logic module has three outputs so the above parameters are shown under lists The dual relay module has two outputs so the above parameters are shown under lists Part Number HA027240 Issue 3.0 Nov-2003 <-A>, <-b>, and <-A> and <-C> <-C> 49 Engineering Manual 4.6.8 2408i Indicator Triple Logic Input or Triple Contact Closure Input Module The triple logic input module allows further digital inputs in addition to those in the basic instrument. The list of parameters is the same as the fixed digital inputs 1 & 2, section 4.5.6. as follows:Customer settings in each channel 1A id Identity of module LoG.i Logic input Func Function nonE Function not configured rmt Remote setpoint select Ac.AL Alarm acknowledge Accs Select full access level Loc.b Keylock (disables all front panel buttons except the ACK/RESET button) up Simulate pressing of the button dwn 1B 1C 2A 2B 2C 3A 3b 3C Read only Simulate pressing of the button ScrL PAGE Simulate pressing of the button Simulate pressing of the button PV.SL Process value select. Closed = input 1 tar.1 Initiate automatic tare calibration of input 1 tar.2 Initiate automatic tare calibration of input 2 PtL.1 Start the calibration at point 1, normally the low point PtL.2 Start the calibration at point 2, normally the low point PtH.1 Start the calibration at point 1, normally the high point Pth.2 Start the calibration at point 2, normally the high point in.AL Alarm inhibit P.HLd Peak hold HLd1 Sample and Hold on PV input 1 HLd2 Sample and Hold on PV input 2 UCAL Enables calibration access for CAL1 and CAL2 lists Open = input 2 The triple logic or triple contact closure module has three inputs so the above parameters are shown under lists <-A>, <-b>, and <-C> 50 Part Number HA027240 Issue3.0 Nov-2003 2408i Indicator 4.6.9 Engineering Manual DC input Module The DC Input module can only be fitted in slot 3. The following parameters appear:Module Parameters Option Customer settings 3B Meaning id Identity of module dC.iP DC input Func Function nonE No function. Input used for monitoring and alarm only rSP Read only Remote setpoint input. When selected this becomes the setpoint for deviation alarms. In <FuLL> access level, set Remote SP Enable, <L-r> = <rmt> (Remote SP selected) Hi Process Value = the highest of Input 1 and input 2 is displayed in normal operation. In normal operation the display cannot be switched between ‘front’ and ‘back’ views. The reading shows the highest or lowest value only. Lo Process Value = the lowest of Input 1 and input 2 is displayed in normal operation. In normal operation the display cannot be switched between ‘front’ and ‘back’ views. The reading shows the highest or lowest value only. Ftn Derived value. Process Value = (<F.1> x Input 1) + (<F.2> x input 2), where <F.1> and <F.2> are scalars found in the <ip> list in Full Access level. Refer to section 3.3.4. for an example of differential measurement. SEL Select input 1 or input 2 via comms, a digital input, or in the Operator <ip> list. If a digital input is configured use the parameter <PV.SL>. If the input is selected through the Operator list in Full Access use the parameter <PV.iP> tran Transition region between <iP.1> and <iP.2>, set by <Lo.IP> and <Hi.IP> in Operator Level. See example 4.6.7.1. If <Func> = <nonE no further parameters are shown. When <Func> ≠ <nonE>, input 2 parameters are shown in the Input List in Full access level The parameters that follow are the same as those in the <iP> configuration list plus inPt <HiLn> - the high impedance input option Refer to <iP> list section 4.5.2. plus the following parameter HiIn CJC Customer settings 0 to 2volt high impedance input Refer to <iP> list Imp InP.L ImP.H VAL.L VAL.H tYPe Type of calibration off Shnt Ld.C CmP man Off Shunt Load Cell Comparison Manual bAnd Settling band. 099.99 (Default The indicator automatically determines when the input has become stable by continuous sampling. When the average value between two consecutive samples is within the settling band the indicator will then allow calibration to take place. If readings are not stable within this period the indicator will abort the calibration 0.5) The DC input module has a single input so the above parameters are shown under list <3A> only 4.6.9.1 Example: Input 1 and Input 2 are Configured for Transition An example of the use for this could be the measurement of temperature over a wide range. The lower temperatures may be measured by a base metal thermocouple connected to Input 1 and higher temperatures may be measured by a pyrometer or precious metal thermocouple connected to input 2. The reason for such a combination is to provide the most accurate readings over the full temperature range where the thermocouple cannot be used at high temperatures and the pyrometer is too insensitive at low temperatures to provide an accurate reading. The thermocouple may be withdrawn, to prevent damage to it, using a high alarm set around the upper limit of the thermocouple. PV = Input 2 ↑ Event set at the upper limit of the thermocouple on input 1 to signal withdrawal. Hi.iP During the transition stage the display reads a combination of Input 1 and input 2. If <Hi.iP> = <Lo.iP> the displayed reading will switch from input 1 to input 2 Lo..iP PV = Input 1 ↓ Figure 4-8: Input 1/Input 2 Transition Part Number HA027240 Issue 3.0 Nov-2003 51 Engineering Manual 2408i Indicator Do This This Is The Display You Should See A. Configure the DC Input Module fitted in slot 3 for transition function 1. Press shown until the <3A> List header is 2. Press shown until 3. trAn Func to select B. Press shown until the ‘Alarm List’ header is 2. to select alarm 1, 2, 3, or 4 as Press appropriate Press or 4. Press to select <Ltch> 5. Press or i This configures alarm 1 for full scale high AL 1 Evnt LtcH i This configures alarm 1 for an event so that an alarm message is not displayed as the PV exceeds the alarm setpoint. Attach the alarm to a relay output as described in examples 4.4.5.1 or 4.4.5.2. Exit configuration level and enter Full access level to set the transition values and full scale high alarm (event) setpoint Press shown until the ‘Input List’ header is 2. Press until the <Lo.iP> is shown 3. Press or to set a level at which the sensor on input 1 is to be phased out 4. Press 5. Press or to set a level at which the sensor on input 2 is to be phased in 6. Press until the <Hi.iP> is shown until the <F1> is shown iP 2 secs 1000 Lo.iP 2 secs 1100 Hi.iP Repeat for <F2> 9. Press shown 10. Press 11. Press or to set the level at which the base metal thermocouple is to be removed If <Lo.iP> is set to the same value as <Hi.iP> the displayed reading will jump from Input 1 to input 2 at this value <F.1> and <F.2> are constants to achieve a derived PV 0.5 F1 until the ‘Alarm List’ header is until the <AL1> is shown i 2 secs Press or to set a multiplying factor on input 1 if necessary 8. 52 FSH 2 secs 1. 7. 2 secs to select <Evnt> C. The display will return to <Func> after approximately 2 seconds AL to select <FSH> 3. i Configure an alarm as a full scale high event 1. D. 3A 2 secs <Func> is or Press <trAn> Additional Notes where PV = <F.1> x input 1 + <F.2> x input 2 As the displayed reading, in normal operation, moves between Input 1 and input 2 it will do so in a controlled manner. Some experiment may be necessary with the four parameters to achieve ideal settings AL 2 secs 1110 AL1 Part Number HA027240 Issue3.0 Nov-2003 2408i Indicator Engineering Manual 4.6.10 DC Retransmission Module The following parameters appear. Module Parameters Option Meaning id Identity of module dc.rE DC retransmission Func Function nonE None configured PV Process value retransmission wSP Setpoint retransmission Err Error from setpoint retrans. IP.1 Input 1 retransmission Ip.2 Input 2 retransmission Customer settings 1A 2A 3A If Func = nonE no further parameters are shown Retransmission value low VAL.L VAL.H Retransmission value High UniT Electrical output units voLt = Volts, mA = milliamps Minimum electrical output Maximum electrical output Out.L Out.H The DC retransmission module has a single output so the above parameters are shown under list -A only 4.6.10.1 Example: To Scale the DC Retransmission Output The retransmission output can be scaled so that the output value corresponds to the range of the signal to be transmitted. Figure 4.5 shows an example where the retransmitted signal is <PV> or <wSP > and an electrical output of 4-20mA represents a displayed value of 20.0 to 200.0 units. Retransmission Value VAL.H eg 200.0 VAL.L eg 20.0 Out.L eg 4 mA Out.H eg 20mA Electrical Output Figure 4-9: Scaling a Retransmission Output 4.6.11 Strain Gauge Transducer Supply The following parameters appear:Module Parameters Option Meaning id Identity of module SG.SU Strain Gauge supply Func Function nonE iP 1 ip 2 None Customer settings 1A 2A 3A Bridge supply for input 1 Bridge supply for input 2 BrG.V Bridge voltage 5 10 5 volt bridge supply SHnt Calibration shunt resistor Ext Int External shunt resistor used 10 volt bridge supply Internal shunt resistor used The strain guage transducer module has a single input so the above parameters are shown under list -A only 4.6.12 Transmitter Power Supply The following parameters appear:Module Parameters Option id Identity of module tP.SU Transmitter power supply Func Function nonE Fixed 24Vdc 20mA supply Part Number HA027240 Issue 3.0 Meaning Nov-2003 53 Engineering Manual 4.7 2408i Indicator INDICATOR CALIBRATION This section explains how to calibrate PV inputs 1 and 2, and retransmission outputs. It should not be confused with User Calibration described in section 3.6 which allows the user to add offsets to compensate for external measurement inaccuracies. Calibration of the indicator should not normally be necessary and must only be carried out using calibrated reference sources. It is always possible to revert to factory calibration settings if necessary. 4.7.1 • To Calibrate Input 1 or 2 A mV calibration should be carried out before thermocouple and RTD calibrations. • Connect a mV, volt source to the input which you wish to calibrate. • If the input is RTD connect a resistance box. mV Source 2400i Indicator Copper cable Input 1 or 2 terminals Figure 4-10: mV Input Calibration 4.7.1.1 To Calibrate mV or Volt Inputs:Do This This Is The Display You Should See 1. From any display press as many times as necessary to access the <CaL> List’ header Additional Notes CAL Set the mV source to 0.000mV 2. to show <rcAL> Press 3. Press or to select input 1 or 2 <PV.1> or <PV.2> 4. Press to show <PV> Press or 5. PV.1 rcAL PV to select mv.L <mv.L> 6. Press to show <GO> 7. Press <YES> or i i .YES GO to select For 0 - 10V input range and high impedance input range, set the volt source to 0.000V This allows you to choose the parameter to be calibrated donE buSY GO When the indicator is calibrating the message <buSY> is shown. When complete the message <donE> is flashed briefly and the display returns to <GO>. The low point calibration is now complete Set the mV source to 10.000mV 8. mv.H PV Repeat the above steps for <mV.H> 4.7.1.2 i For 0 - 10V input range, set the volt source to 10.000V For RTD input range, set the resistance box to 400.00Ω For high impedance input range, set volt source to 1.000V To Calibrate CJC Having calibrated mV inputs as above it is then only necessary to calibrate Cold Junction Compensation (CJC), as follows:Do This This Is The Display You Should See Additional Notes 1. Replace the copper cable from the mV source with the appropriate compensating cable 2. Configure the indicator for a thermocouple type. A base metal thermocouple such as type K is recommended 3. Set the mV source to the same thermocouple compensation 4. Set the mV source to 0.000mV 5. From the <PV> list press or as many times as necessary to access <CJC> 6. 7. Press to show <GO> Press or <YES> 54 to select CJC PV .YES GO donE buSY GO When the indicator is calibrating the message <buSY> is shown. When complete the message <donE> is flashed briefly and the display returns to <GO>. The CJC calibration is now complete. Part Number HA027240 Issue3.0 Nov-2003 2408i Indicator 4.7.2 Engineering Manual To Calibrate Retransmission Output Connect the retransmission output to a multi-meter set to volts or mV as appropriate. Calibrated voltmeter or ammeter 2400i Indicator Module output terminals Figure 4-11: Retransmission output calibration Do This 1. This Is The Display You Should See From the <rcAL> list press as many times as or necessary to select the module to be calibrated, e.g. <1A.Hi> to show <CAL.H> 2. Press 3. Press or to adjust the required output read on the meter 4. Press list .605 CAL.H to select the <rcAL> 5. or as many times Press as necessary to select the module to be calibrated, e.g. <1A.Lo> 6. Press 7. Press or to adjust the required output read on the meter 4.7.3 1A.Hi rcAL to show <CAL.L> 1A.Lo rcAL .-960 CAL.L Additional Notes In this example module 1 will be calibrated. The high output is calibrated first i The reading on the indicator can be adjusted between –999 and +999. This is an arbitrary value which acts as a trim on the output The low output is calibrated next i The reading on the indicator can be adjusted between –999 and +999. This is an arbitrary value which acts as a trim on the output To Restore Factory Calibration Factory calibration of PV input and PV input 2 can be restored as follows:Do This 1. From the <PV> list press This Is The Display You Should See or as many times as necessary to select <FACt> Part Number HA027240 Issue 3.0 FACT PV Nov-2003 Additional Notes The factory set calibration values are restored 55 Engineering Manual 4.7.4 2408i Indicator Calibration Parameters CAL CAL Basic Indicator Calibration rCAL Selected re-calibration parameter PV PV or PV.2 calibration point Selected parameter nonE PV.1 PV.2 1A.Hi 1A.Lo 2A.Hi 2A.Lo 3A.Hi 3A.Lo If rCAL = PV1 or PV2 the following parameters appear: Idle state - no calibration performed Main process value input selected Second analogue input selected (this will always be in module position 3) Module 1 DC retransmission high output (if installed) Module 1 DC retransmission low output (if installed) Module 2 DC retransmission high output (if installed) Module 2 DC retransmission low output (if installed) Module 3 DC retransmission high output (if installed) Module 3 DC retransmission low output (if installed) Calibration point IdLE mv.L mv.H V 0 V 10 CJC rtd HI 0 HI 1.0 Calibration value Idle mV low calibration point selected mV high calibration point selected 0 Volt calibration point selected 10 Volt calibration point selected Cold junction calibration Resistance input calibration High impedance input. 0 Volt calibration point selected High impedance input. 1.0 Volt calibration point selected Restore factory calibration selected Waiting to calibrate PV point Start calibration Busy calibrating Calibration complete Calibration failed 0.000 mV 50.000 mV 0.000V 10.000V See below 400.00Ω 0.000V 1.000V FACt no YES busy done FaiL If rCAL = 1AHi to 3aLo (DC output module calibration) the following parameters appear: DC output calibration low point 0 0 = Factory cal. Trim value to give output = + 1V or +2mA cAL.L GO Start calibration cAL.H DC output calibration high point 4.7.5 0 Password Configuration PASS Passwords ACC.P Full and Edit level password 09999 cnF.P Configuration level password 09999 CAL.P User calibration password 09999 4.7.6 Range Notes When passwords are changed please make a note of the new numbers Having once entered the correct password, operator, full or edit level can be selected at will. To return to operator level and lock the indicator in this level, either switch the indicator off and on again or enter an invalid password as described in section 4.2.1. Configuration level can only be entered from the above level. You must exit this level to return to operator level by following the exit procedure in section 4.7.6. User calibration level (described in Section 3.5.1.) can be entered from operator level. To return to normal operation: 1. Enter an incorrect password 2. Switch power off and on again Default setting Customer setting 1 2 3 To Leave Configuration Level Do This This Is The Display You Should See 1. Press display to reach the <exit> 2. Press <YES> or 56 100 = Factory cal. Trim value to give output = + 9V or +18mA to select Exit YES Additional Notes i After 2 secs the display will blank then return to the HOME display in Operator level Part Number HA027240 Issue3.0 Nov-2003 2408i Indicator Engineering Manual 5 Ordering Code Model number 2408i Function AL AP Function Indicator/Alarm unit Profibus Indicator GN RD Display colour Green display Red display VH VL Supply voltage 85-264Vac 20-29Vac/dc Display colour Note 1: By default, alarm 1 will be assigned to relay output 1 and alarms 2, 3 and 4 will be assigned to Modules 1, 2 and 3 respectively. Note 2: The allocation of alarms to the dual relay outputs must be performed in configuration by the customer. Note 3: Triple contact or logic inputs can be configured, by the user, for any of the functions listed under Digital Inputs 1 and 2. Note 4: The triple logic output can configured as alarm outputs or as telemetry outputs via digital communications. Sensor Input Supply voltage Module 1 Module 2 Module 3 Modules 1, 2 and 3 XX Module not fitted Alarm Relay output (change-over) R4 Module fitted unconfigured OR Select alarm configuration from table A. DC retransmission D6 Module fitted unconfigured First character VProcess Value retransmission SSetpoint retransmisssion ZError retransmission Second character -1 0-20mA -2 4-20mA -3 0-5Vdc -4 1-5Vdc -5 0-10Vdc Dual relay (Note 2) RR Module fitted unconfigured Triple contact input (Note 3) TK Module fitted unconfigured Triple logic input (Note 3) TL Module fitted unconfigured Triple logic output (Note 4) TP Module fitted unconfigured Transmitter supply MS 24Vdc, 20mA supply Strain Gauge Transducer supply (modules 1 & 2 only) (note 5) G3 5V transducer supply G5 10v transducer supply 2nd analogue input (module 3 only) D5 Module fitted unconfigured For configuration, see PV Function field SOFTWARE CONFIGURATION Setpoint Setpoint Display Digital min max Units input 1 Note 6 Note 6 Sensor input & 2nd DC input Comms Module Table A: Alarm relay configuration (See note 1) Non-latched alarms FH High alarm FL Low alarm DB Deviation band alarm DL Deviation low alarm DH Deviation high alarm RA Rate-of -change alarm Latched alarms HA High alarm LA Low alarm BD Deviation band alarm WD Deviation low alarm AD Deviation high alarm RT Rate-of -change alarm NW New alarm 10 XXX ENG FRA GER NED SPA SWE ITA Note 5: By default, the transducer supply for input 1 will be installed in module position 2 and the transducer supply for input 2 in module position 1. Manual PDS module Module not fitted Module fitted unconfigured Remote setpoint input Manual None English French German Dutch Spanish Swedish Italian Configuration of 2nd analogue input requires D5 in module 3 PV Function 2nd Input 2nd Input ConfiguratDisplay Min Display Max ion option Note 8 Note 8 °C °F Min Max -210 1200 -200 1372 -200 400 -200 900 -250 1300 -50 1768 -50 1768 0 1820 0 1369 -200 850 Range Min -9999 -9999 -9999 -9999 -9999 -9999 Min Max -340 2192 -325 2500 -325 750 -325 1650 -418 2370 -58 3200 -58 3200 32 3308 32 2496 -325 1562 Range Max 99999 99999 99999 99999 99999 99999 C o F o XX LO HI FN RS XX AC KL SR PV M5 0 to 2319 32 to 4200 J1 0 to 2399 -270 to 999 0 to 1399 0 to 1870 0 to 2000 0 to 2010 10 to 2300 0 to 2000 32 to 4350 -450 to 1830 32 to 2550 32 to 3398 32 to 3632 32 to 3650 50 to 4172 32 to 3632 J2 200 to 1800 -45 to 650 XX M6 RS Setpoint min & max Thermocouples J Type J K Type K T Type T L Type L N Type N R Type R S Type S B Type B P Platinell II Z Pt100 Process inputs (Scaled to setpoints max & min) F -100 to +100mV Y 0 to 20mA (note 2) A 4 to 20mA (note 2) W 0 to 5Vdc G 1 to 5Vdc V 0 to 10Vdc Factory downloaded input C Type C -W5%Re/W26%Re “Table Reference (default downloaded input) Number” Ctc D Type D - W3%Re/W25%Re “T035” E E thermocouple “T012” 1 Ni/Ni18%Mo “T033” 2 Pt20%Rh/Pt40%Rh “T025” 3 W/W26%Re (Engelhard) “T09” 4 W/W26%Re (Hoskins) “T029” 5 W5%Re/W26%Re (Engelhard) “T011” 6 W5%Re/W26%Re “T038” (Bucose) 7 Pt10%Rh/Pt40%/Rh “T023” 8 Exergen K80 I.R. Pyrometer “Er80” PDS Module Comms module XX Module not fitted RS232 Module A2 Module fitted unconfigured AM Modbus protocol AE EI-Bisynch protocol RS485 (2-wire) Module Y2 Module fitted unconfigured YM Modbus protocol YE EI-Bisynch protocol RS485 (4-wire) (= RS422) Module F2 Module fitted unconfigured FM Modbus protocol FE EI-Bisynch protocol Profibus Module PB High speed RS485 Relay Output 1 XX Not fitted RF Fitted unconfigured OR Select alarm configuration from table A 2nd DC Input Note 7 Digital input 2 Relay Output 1 392 to 3272 -49 to 1202 J3 J4 XX SG MP C F Display Units K X o K Blank PV function Input 1 displayed PV = the lowest of i/p 1 and 2 PV = the highest of i/p 1 and 2 PV derived from i/p 1 and 2 Remote setpoint Digital inputs 1 & 2 Disabled Alarm acknowledge Keylock Remote setpoint select Select process value input 2 CTX mode 5 (digital input 2 only). For use with PDTCX ‘smart’ current transformer. Initiate tare correction on strain gauge input 1 Initiate tare correction on strain gauge input 2 Initiate automatic calibration of strain gauge input 1 Initiate automatic calibration of strain gauge input 2 Configuration Option Standard Load cell/strain gauge pressure transducer Note 6: Setpoint min and max: Include the decimal points required in the displayed value. Note 7: Select the code required from the Sensor Input table. Note 8: These two fields are used to scale the 2nd DC input if it is a linear process input, otherwise it should be left blank. Note 9: For mA inputs, a 1% 2.49Ω current sense resistor is supplied. If greater accuracy is required, a 0.1% resistor can be ordered as Part No. SUB2K/249R.1. Part Number HA027240 Issue 3.0 Nov-2003 57 Engineering Manual 2408i Indicator 6 Safety and EMC Information Enclosure of live parts Safety The indicator must be installed in an enclosure to prevent hands or metal tools touching parts that may be electrically live. This indicator complies with the European Low Voltage Directive 73/23/EEC, amended by 93/68/EEC, by the application of the safety standard EN 61010. Caution: Live sensors The alarm acknowledge/keylock input is electrically connected to the sensor input (e.g. thermocouple). In some installations the temperature sensor may become live. The indicator is designed to operate under these conditions, but you must ensure that this will not damage other equipment connected to the logic input/output and that service personnel do not touch this connection while it is live. With a live sensor, all cables, connectors and switches for connecting the sensor and non-isolated inputs and outputs must be mains rated. ! Electromagnetic compatibility This indicator conforms to the essential protection requirements of the EMC Directive 89/336/EEC, amended by 93/68/EEC, by the application of a Technical Construction File. This indicator satisfies the general requirements of the industrial environment defined in EN 50081-2 and EN 50082-2. General The information contained in these instructions is subject to change without notice. While every effort has been made to ensure the accuracy of the information, your supplier shall not be held liable for errors contained herein. Wiring Wire the indicator in accordance with the wiring data given in these instructions. Take particular care not to connect AC supplies to the low voltage sensor input or logic outputs. Only use copper conductors for connections, (except thermocouple). Ensure that the installation complies with local wiring regulations, and observe maximum voltage safety limits. ! Unpacking and storage The packaging should contain the indicator, two panel retaining clips, a 2.49Ω current sense resistor and this instruction leaflet. If the packaging or the indicator is damaged, do not install the product but contact your supplier. This indicator has no user serviceable parts. Contact your supplier for repair. Power Isolation ! Caution: Charged capacitors ! Before removing the indicator from its sleeve, switch off the supply and wait two minutes to allow capacitors to discharge. Failure to observe this precaution may damage the indicator or cause mild electric shock. Voltage rating Precautions Against Electrostatic Discharge Damage ! ! When the indicator is removed from its sleeve, it is vulnerable to damage by electrostatic. To avoid this, observe anti-static handling precautions. Conductive pollution ! Safety Symbols The following safety symbols are used on the controller and in this manual: ! i Caution, Important Functional earth (ground) terminal safety information Useful information or hint Personnel Installation must be carried out by qualified personnel. The maximum continuous voltage applied between any connection and ground must not exceed 264Vac. For the above reason the indicator should not be wired to a three-phase supply with an unearthed star connection. Under fault conditions such a supply could rise above 264Vac with respect to ground and the product would not be safe. Cleaning Do not use water or water based products to clean labels or they will become illegible. Isopropyl alcohol may be used to clean labels. A mild soap solution may be used to clean other exterior surfaces of the product. The installation must include a power isolating switch or circuit breaker that disconnects all current carrying conductors. The device should be mounted in close proximity to the indicator, within easy reach of the operator and marked as the disconnecting device for the indicator. Electrically conductive pollution must be excluded from the cabinet in which the indicator is mounted. For example, carbon dust is a form of electrically conductive pollution. Where condensation is likely, for example at low temperatures, include a thermostatically controlled heater in the cabinet. Installation requirements for EMC • • For general guidance refer to EMC Installation Guide, HA025464. It may be necessary to fit a filter across the relay output to suppress conducted emissions. The filter requirements will depend on the type of load. For typical applications we recommend Schaffner FN321 or FN612. Routing of wires To minimise the pick-up of electrical noise, the sensor input wiring should be routed away from high-current power cables. Where it is impractical to do this, use shielded cables with the shield grounded at both ends. 58 Part Number HA027240 Issue3.0 Nov-2003 2408i Indicator Engineering Manual 7 Technical Specification Main process value input and second DC input Low level range High level range Sample rate Resolution Linearity Calibration accuracy User calibration Input filtering Thermocouple types Cold junction compensation 3-wire Pt100 input Bulb current: Maximum lead resistance 2nd analogue input functions Input impedance, mV inputs Input impedance, Volt inputs -100 to +100mV 0-20mA or 0-10Vdc 9Hz <2µV for low level inputs <2mV for high level inputs Better than 0.2oC +0.2% of reading, or +1oC or +1LSD, whichever is the greater Low and high offsets can be applied OFF to 999.9 seconds Refer to ordering code sensor input table In automatic mode, >30:1 rejection of ambient temperature change. 0.3mA Up to 22Ω in each lead without error 2nd process value, remote setpoint, select min, select max, derived value >10MΩ >69KΩ Digital inputs Contact closure or open collector inputs Note: These are powered by the controller Digital inputs 1 & 2 (Non isolated from PV) Triple contact closure inputs Switching voltage/current: 24Vdc/20mA nominal Off state resistance <100Ω On state resistance >28KΩ Isolated. Specification as dig. inputs 1 & 2 Number of alarms Alarm types Alarm modes Alarm delay Off state: <5Vdc On state: 10.8 to 30Vdc @ 2.5mA Four High, low, deviation high, deviation low, deviation band, rate of change in units/sec, rate of change in units/min, new alarm status. Sensor break alarm Latching or non-latching. Blocking Energised or de-energised in alarm OFF to 999.9 secs Communications Module types Protocols RS232, 2-wire RS485 and 4-wireRS485 Modbus or EI-Bisynch (ASCII) PDS Functions Remote setpoint input from master controller General Display colour Number of digits Supply Power consumption Operating ambient Storage temperature Panel sealing Dimensions Weight EMC Standards: Safety standards Atmospheres Externally powered inputs Triple logic inputs Alarms Red or green options Five with up to three decimal places 100 to 240Vac -15%+10% OR 24 Vdc or ac -15%+20% 15W max 0 to 55oC and 5 to 95% RH non-condensing -10 to +70oC IP65 96W x 48H x 150D 400g max EN50081-2 & EN50082-2 generic standards for industrial environments Meets EN 61010, Installation category II, pollution degree 2. Not suitable for use above 2000m or in explosive or corrosive atmospheres Digital input functions As per digital inputs 1 & 2 in the ordering code Digital outputs Relay rating Triple logic output Digital output functions 2A, 264Vac resistive 8mA, 12Vdc per channel as per the ordering code DC retransmission Range Resolution Retransmission values Scaleable between 0-20mA and 0-10Vdc 1 part in 10,000 Process value, setpoint or error from Transmitter supply Rating 20mA, 24Vdc Strain gauge bridge supply Bridge voltage Bridge resistance Internal shunt resistor Part Number HA027240 Software selectable, 5 or 10Vdc 300Ω to 10KΩ 30.1KΩ at 0.25%, used for calibration of 350Ω bridge Issue 3.0 Nov-2003 59 INTERNATIONAL SALES AND SERVICE AUSTRALIA Sydney Eurotherm Pty. Ltd. Telephone (+61 2) 9838 0099 Fax (+61 2) 98389288 ITALY Como Eurotherm S.r.l Telephone (+39 031) 975111 Fax (+39 031) 977512 AUSTRIA Vienna Eurotherm GmbH Telephone (+43 1) 7987601 Fax (+43 1) 7987605 JAPAN Tokyo Densei-Lambda K.K. Eurotherm Division Telephone (+81 3) 5714 0620 Fax (+81 3) 5714 0621 BELGIUM Moha & LUXEMBURG Huy Eurotherm S.A./N.V. Telephone (+32 ) 85 274080 Fax (+32 ) 85 274081 KOREA Seoul Eurotherm Korea Limited Telephone (+82 31) 2868507 Fax (+82 31) 2878508 BRAZIL Campinas-SP Eurotherm Ltda. Telephone (+55 19) 3237 3413 Fax (+55 19) 3234 7050 NETHERLANDS Alphen a/d Ryn Eurotherm B.V. Telephone (+31 172) 411752 Fax (+31 172) 417260 DENMARK Copenhagen Eurotherm Danmark A/S Telephone (+45 70) 234670 Fax (+45 70) 234660 NORWAY Oslo Eurotherm A/S Telephone (+47 67) 592170 Fax (+47 67) 118301 FINLAND ABO Eurotherm Finland Telephone (+358) 22506030 Fax (+358) 22503201 SPAIN Madrid Eurotherm España SA Telephone (+34 91) 6616001 Fax (+34 91) 6619093 FRANCE Lyon Eurotherm Automation SA Telephone (+33 478) 664500 Fax (+33 478) 352490 SWEDEN Malmo Eurotherm AB Telephone (+46 40) 384500 Fax (+46 40) 384545 GERMANY Limburg Eurotherm Deutschland GmbH Telephone (+49 6431) 2980 Fax (+49 6431) 298119 Also regional offices SWITZERLAND Freienbach Eurotherm Produkte (Schweiz) AG Telephone (+41 55) 4154400 Fax (+41 55) 4154415 HONG KONG Aberdeen Eurotherm Limited Telephone (+852) 28733826 Fax (+852) 28700148 INDIA Chennai Eurotherm India Limited Telephone (+9144) 4961129 Fax (+9144) 4961831 IRELAND Dublin Eurotherm Ireland Limited Telephone (+353 01) 4691800 Fax (+353 01) 4691300 UNITED KINGDOM Worthing Eurotherm Limited CONTROLS & DATA MANAGEMENT Telephone (+44 1903) 695888 Fax (+44 1903) 695666 PROCESS AUTOMATION Telephone (+44 1903) 205277 Fax (+44 1903) 236465 U.S.A Leesburg Eurotherm Inc. Telephone (+1 703) 443 0000 Fax (+1 703) 669 1300 Web www.eurotherm.com ED 35 http://www.eurotherm.co.uk © Copyright Eurotherm Limited 2003 All rights are strictly reserved. No part of this document may be reproduced, modified, or transmitted in any form by any means, nor may it be stored in a retrieval system other than for the purpose to act as an aid in operating the equipment to which the document relates, without the prior written permission of Eurotherm limited. Eurotherm Limited pursues a policy of continuous development and product improvement. The specifications in this document may therefore be changed without notice. The information in this document is given in good faith, but is intended for guidance only. Eurotherm Limited will accept no responsibility for any losses arising from errors in this document. ENG HA027240 Model 5617 CORROSION TEST APPARATUS Test Corrosivity at High Pressure and High Temperature Throughout the Oil & Gas Industry, the corrosivity of fluids and the effectiveness of corrosion inhibitors are critical to keeping operations reliable, safe and cost-effective. The Model 5617 Corrosion Test Apparatus is designed to test the reaction rate of corrosive liquids on metals that are subjected to high pressure and high temperature (HPHT) under dynamic conditions. Simultaneously test up to twenty Samples The Model 5617 is designed to help engineers maximize their testing productivity and optimize test repeatability. The chamber of the instrument can hold up to twenty glass sample bottles with corrosionresistant caps during a single test. Each bottle may contain a different metal coupon and sample fluid if desired. Corrosion rates are determined by weight loss of each coupon. Alternatively, the instrument can be ordered to hold larger sample bottles. User-Controlled Test Conditions and Sample Agitation The test cylinder’s pressure is easily set. During a test, the pressure control gauge controls a pump and release valve to automatically maintain the preset pressure. The automatic temperature control can regulate the temperature heat-up rate which has a maximum of 5.4°F/ 3°C per minute. Enhanced Safety and Productivity 3 Simultaneously test up to twenty samples 3 Maximum test pressure of 10,000 psi / 69 MPa 3 Maximum test temperature Enhanced user safety in the Model 5617 begins with a remote control panel. This control panel enables the user to monitor and control the instrument’s pressure and temperature from a safe distance. The pressurization system safely pressurizes and depressurizes the test cylinder. The system includes user-adjustable upper and lower pressure set-points which prevent over and under- pressure conditions during a test. Pressure and temperature can be automatically tracked via an optional Model 5270 Data Acquisition and Control System. The instrument is also designed to minimize the cool-down and clean-up times between tests. 2001 North Indianwood Avenue, Broken Arrow, OK 74012 FEATURES Phone: 918-250-7200 © 2008, by AMETEK, Inc. All rights reserved. e-mail: chandler.sales@ametek.com of 500°F / 260°C 3 Remote control panel for enhanced user-safety 3 Adjustable sample agitation angles and rates 3 Cooling capabilities 3 Compatible with the Model 5270 Data Acquisition and Control System Fax: 918-459-0165 www.chandlereng.com AEROSPACE & DEFENSE Model 5617 Specifications Specimen Capacity Remote Control Console 20 - 4 fl. oz. / 50 mL sample bottles Maximum Separation Distance 8 - 8 fl. oz. / 100 mL sample bottles optional 50 ft / 15.25 m Maximum Pressure Size (H x W x D) 10,000 psi / 69 MPa 10 in. x 20 in. x 20 in. / 25 x 50 x 50 cm Maximum Temperature Weight 500°F / 260°C 25 lb / 11 kg Maximum Temperature Rise Enviromental 5.4°F / 3°C per minute Operating temperature Agitation Angles 32° to 105°F / 0 to 40°C 40°, 60°, or 80° Operating Humidity Agitation Rates 0 to 95% non-condensing 35, 60, or 100 cycles/minute Utilities Physical Dimensions Power Instrument 230 VAC ± 15%; 50/60 Hz ± 10%; 10 kVA Size (H x W x D) Compressed air 67 in. x 39 in. x 33 in. / 170 x 99 x 84 cm 100 to 130 psi / 690 to 900 kPa; intermittent flow Weight Cooling water 2,200 lb / 998 kg 20 to 80 psi / 140 to 550 kPa *Manufacturer’s specifications subject to change without notice R0309.002 Houston Sales and Services 4903 W. Sam Houston Parkway, N., Suite A-400, Houston, TX 77041 Tel: +1 713-466-4900 Fax: +1 713-849-1924 2001 North Indianwood Avenue, Broken Arrow, OK 74012 Tel: +1 918-250-7200 Fax: +1 918-459-0165 e-mail: chandler.sales@ametek.com Printed in the U.S.A. www.chandlereng.com © 2008, by AMETEK, Inc. All rights reserved. XM808PDF (360000)