SEE MORE AT SORInc.com Request Quote Pressure and Vacuum Switches for Process Applications SOR® pressure switches are rugged, field-mounted instruments. The pressure sensing element of the SOR pressure switch is a force-balance, piston-actuated assembly. The sensing element is sealed by a flexible diaphragm and a static o-ring. A wide selection of wetted parts materials for media compatibility and containment are available. A metal diaphragm may be welded to the pressure port for certain applications, thereby eliminating the o-ring. B3 Application Information The SOR pressure switches in this catalog are suitable for a variety of process applications. Basic models with standard wetted parts are normally suitable for air, oil, water and noncorrosive processes. See the Quick Selection Guide on pages 4 and 5. Specific application requirements can normally be met by selecting optional components, such as switching elements, diaphragm systems and pressure ports. See How to Order on page 3. Certain applications may require customized specials. Consult the SOR representative in your area or the factory. NN This catalog describes switches that are: • General Purpose • Weatherproof • Conventional Explosion Proof Other specific types of switches available through your SOR representative are: • Hermetically Sealed (for hazardous locations) • Pivot Seal (for high shock pressures and cycle rates) • Differential Pressure • Temperature (remote and direct mount) • Electronic and Mechanical Level • Electronic Pressure Form 216 (01.16) ©SOR Inc. SORInc.com LC | 913-888-2630 | Registered Quality System to ISO 9001 1/32 Features and Benefits Pressure and Vacuum Switches Complete Product Line Standard models and customized specials cover pressure ranges from 30 inches Hg VAC to 4000 psi. Features Agency Listings/Certification Select models with ATEX, CSA, FM, GOST R, INMETRO, Rostechnadzor (RTN), TIIS, UL Meets most code and customer requirements. Robust Construction Rugged, high-cycle rate tolerance, long life, not critical to vibration, high overrange and proof pressures, excellent corrosion resistance to hostile environments. Enclosure ratings: NEMA 1, 4, 4X, 7, or 9 available. Ingress protection rating up to IP66. Instrument Quality High resolution of set points, high repeatability, narrow dead band, negligible temperature effect. Safety Certified to IEC 61508 (SIL) SOR products are certified to IEC 61508 for non-redundant use in SIL1 and SIL2 Safety Instrumented Systems for most models. For more details or values applicable to a specific product, see the Safety Integrity Level Quick Guide (Form 1528). Wetted Parts Wide selection materials, process connection configurations and sizes. Optional “fire-safe” pressure sensor. Snap-Action Electrical Switching Wide selection UL Listed and CSA Certified switching elements for AC and DC service. Optional “hermetically sealed” capsule for hazardous and hostile environments. Shock/Vibration Select models tested to MIL-S-901D (Navy) shock test. Select models tested to MIL-S-167 vibration test. Built-In Quality Rigid quality standards maintained from raw material to finished product. Field Adjustable Self-locking adjustment, no special tools required. No-charge factory calibration. Cost Effective Simple and fast installation without special tools, long service life, no required periodic service or spare parts. Delivery Routine shipments 7 to 10 working days. Emergency shipments via same day air. Service Factory sales engineers and area SOR representatives provide effective and prompt worldwide service. 2/32 Registered Quality System to ISO 9001 Warranty 3 years from date of manufacture. | 913-888-2630 | SORInc.com Form 216 (01.16) ©SOR Inc. Pressure and Vacuum Switches How to Order Model Number System 6NN-K5-M4-C2A-YY Piston Housing Switching Spring Element Diaphragm & O-Ring Pressure Port Accessories Quick Selection Guide Basic SOR pressure switches with standard wetted parts are normally suitable for air, oil, water and non-corrosive processes. The Quick Selection Guide on pages 4 and 5 shows these basic SOR pressure and vacuum switches. Corrosive service and particular customer requirements may require optional components. Refer to How to Order section below to build a customized model number or the dedicated page to locate optional components, such as switching elements, diaphragm systems, pressure ports and accessories. Each position in the model number, except Accessories, must have a designator. Design and specifications are subject to change without notice. For latest revision, see sorinc.com. Applications SOR pressure switches in this catalog are suitable for a wide variety of continuous pressure applications. Specific application requirements can normally be met by selecting optional components, such as, switching elements, diaphragm systems and pressure ports. Certain applications may require customized specials. Consult the SOR representative in your area or the factory. How to Order Information and data in this catalog are formatted to provide a convenient guide to assist instrument engineers, plant engineers and end users in selecting pressure switches for their unique applications. Steps 1 through 5 are required. Step 6 is optional. Orders must have complete Model Numbers, i.e., each component must have a designator. Step 1: Select Piston-Spring adjustable range/set point from Specifications (pages 7 & 8). Piston-Spring combination determines adjustable range. Step 2: Select Housing for type of pressure switch and service (page 9). Step 3: Select electrical Switching Element for electrical service (pages 10 & 11). Step 4: Select Diaphragm and O-Ring for process compatibility and containment (pages 12 & 13). Step 5: Select Pressure Port for process compatibility and connection (page 14). Step 6: Select Accessories required for service (page 16). Form 216 (01.16) ©SOR Inc. SORInc.com | 913-888-2630 | Registered Quality System to ISO 9001 3/32 Pressure and Vacuum Quick Selection Guide - Pressure Switches Basic SOR pressure switches with standard wetted parts are normally suitable for air, oil, water and non-corrosive processes. Corrosive service and particular customer requirements may require optional components. Refer to How to Order on page 3 to locate optional components, such as, housing, switching elements, diaphragm systems, pressure ports and accessories. Each position in the model number, except Accessories, must have a designator. Weatherproof Adjustable Range psi (in. wc.) Typical Dead Band psi (in. wc.) Explosion Proof Model Number 12NN - N66 - N4 - B1A (0.6 to 2.5) (0.4) 12L - N66 - N4 - B1A 12NN - K614 - N4 - B1A (2.5 to 45.0) (0.8) 12L - K614 - N4 - B1A 12NN - K2 - N4 - B1A 0.4 to 2.0 0.1 12L - K2 - N4 - B1A 12NN - K4 - N4 - B1A 0.5 to 6.0 0.1 12L - K4 - N4 - B1A 12NN - K5 - N4 - B1A 0.75 to 12 0.1 12L - K5 - N4 - B1A 12NN - K45 - N4 - B1A 1 to 16 0.15 12L - K45 - N4 - B1A Weatherproof Model Number (increasing pressure) Piston 12 Weatherproof Overrange 200 (psi) Adjustable Range Explosion Proof Model Number 2 to 8 0.2 4L - K2 - N4 - B1A 4NN - K4 - N4 - B1A 2 to 25 0.3 4L - K4 - N4 - B1A 4NN - K5 - N4 - B1A 3 to 50 0.4 4L - K5 - N4 - B1A 4NN - K45 - N4 - B1A 4 to 75 0.5 4L - K45 - N4 - B1A (increasing pressure) 4NN - K2 - N4 - B1A Piston 4 psi Overrange 750 (psi) Standard Construction • Housing: NN - aluminum; L - cast iron • Switching Element: SPDT; N - 10 amps @ 250 VAC; K - 15 amps @ 250 VAC • Diaphragm & O-ring: N4 - primary (wetted) diaphragm, TCP; o-ring (wetted) Buna-N • Pressure Port: 1/4” NPT(F); B1A - aluminum; F1A - carbon steel 4/32 Proof 400 (psi) Typical Dead Band psi Weatherproof Model Number Registered Quality System to ISO 9001 Explosion Proof Explosion Proof Proof 1000 (psi) Notes 1. See balance of catalog for construction options. 2. Dead band values are expressed as typical expected at mid-range for a particular model number. See Dead Band Considerations on page 8. 3. Design and specifications subject to change without notice. For latest revision, see sorinc.com. | 913-888-2630 | SORInc.com Form 216 (01.16) ©SOR Inc. Pressure and Vacuum Switches Quick Selection Guide - Pressure Typical Dead Band psi Explosion Proof Model Number 7 to 30 0.5 6L - K2 - N4 - F1A 6NN - K3- N4 - F1A 12 to 100 0.9 6L - K3 - N4 - F1A 6NN - K5- N4 - F1A 20 to 180 1.4 6L - K5 - N4 - F1A 6NN - K45- N4 - F1A 25 to 275 1.9 6L - K45 - N4 - F1A 5NN - K3- N4 - F1A 25 to 240 2.2 5L - K3 - N4 - F1A 5NN - K5- N4 - F1A 35 to 375 3.1 5L - K5 - N4 - F1A 5NN - K45- N4 - F1A 45 to 550 3.9 5L - K45 - N4 - F1A 9NN - K4- N4 - F1A 100 to 500 5.3 9L - K4 - N4 - F1A 9NN - K5- N4 - F1A 200 to 1000 9.2 9L - K5 - N4 - F1A 9NN - K45- N4 - F1A 200 to 1750 15 9L - K45 - N4 - F1A 1NN - K45- N4 - F1A 500 to 4000 98 1L - K45 - N4 - F1A Adjustable Range Weatherproof Model Number (increasing pressure) psi 6NN - K2 - N4 - F1A Weatherproof Piston 6, 5 9 1 Overrange 1500 (psi) 2500 5000 Standard Construction • • • • Housing: NN - aluminum; L - cast iron Switching Element: SPDT; K - 15 amps @ 250 VAC Diaphragm & O-ring: N4 - primary (wetted) diaphragm, TCP; o-ring (wetted) Buna-N Pressure Port: 1/4” NPT(F); B1A - aluminum; F1A - carbon steel Explosion Proof Proof 2500 (psi) 6000 6000 Notes 1. See balance of catalog for construction options. 2. Dead band values are expressed as typical expected at mid-range for a particular model number. See Dead Band Considerations on page 8. 3. Design and specifications subject to change without notice. For latest revision, see sorinc.com. Quick Selection Guide - Vacuum Adjustable Range Weatherproof Model Number Weatherproof Vacuum-O-Pressure in. Hg (in. wc) Typical Dead Band in. Hg (in. wc) Explosion Proof Model Number 52NN - K116 - M4 - B1A (20 - 0 - 20) (0.8) 52L - K116 - N4 - B1A 52NN - K117 - M4 - B1A (40 - 0 - 40) (0.9) 52L - K117 - N4 - B1A 54NN - K117 - M4 - B1A 15 - 0 - 15 0.4 54L - K117 - N4 - B1A 54NN - K118 - M4 - B1A 30 - 0 0.6 54L - K118 - N4 - B1A 56NN - K216 - M2 - F1A 30 - 0 - 20 0.8 56L - K216 - M2 - F1A 56NN - K316 - M2 - F1A 30 - 0 - 160 1.1 56L - K316 - M2 - F1A Piston 52 54 56 Overrange 200 (psi) 750 1500 Standard Construction • Housing: NN - aluminum; L - cast iron • Switching Element: SPDT; K - 15 amps @ 250 VAC • Diaphragm & o-ring: N4 - primary (wetted) diaphragm, TCP; o-ring (wetted) Buna-N. Piston 56 primary (wetted) diaphragm, 316SS. • Pressure Port: 1/4” NPT(F); B1A - aluminum; F1A - carbon steel Form 216 (01.16) ©SOR Inc. SORInc.com Explosion Proof Proof 400 (psi) 1000 2500 Notes 1. See balance of catalog for construction options. 2. Dead band values are expressed as typical expected at mid-range for a particular model number. See Dead Band Considerations on page 8. 3. Design and specifications subject to change without notice. For latest revision, see sorinc.com. | 913-888-2630 | Registered Quality System to ISO 9001 5/32 Pressure and Vacuum Switches Glossary of Terms SOR recognizes that there is no industry convention with respect to terminology and definitions pertinent to pressure switches. This glossary applies to SOR pressure switches. Pressure Switch A bi-stable electromechanical device that actuates/deactuates one or more electrical switching element(s) at a predetermined discrete pressure/vacuum (set point) upon rising or falling pressure/vacuum. Adjustable Range The span of pressure between upper and lower limits within which the pressure switch may be adjusted to actuate/deactuate. It is expressed for increasing pressure. Set Point That discrete pressure at which the pressure switch is adjusted to actuate/deactuate on rising or falling pressure. It must fall within the adjustable range and be called out as increasing or decreasing pressure. Dead Band The difference in pressure between the increasing set point and the decreasing set point. It is expressed as typical, which is an average with the increasing set point at mid-range for a pressure switch with the standard K switching element. It is normally fixed (non-adjustable). Fire-Safe The ability of a welded seal pressure sensor to contain the process at elevated temperatures up to 1900°F at the rated overrange pressure, unsupported by the body of the pressure switch. Hermetically Sealed A welded steel capsule with glass-to-metal, factory-sealed electrical leads that isolates the electrical switching element(s) from the environment. Proof Pressure The maximum input pressure that may be continuously applied to the pressure switch without causing leakage or catastrophic material failure. Permanent change of set points may occur, or destruction of the device may be rendered inoperative. Repeatability The ability of a pressure switch to successively operate at a set point that is approached from a starting point in the same direction and returns to the starting point over three consecutive cycles to establish a pressure profile. Repeatability on SOR switches will be smaller than 1% of full scale per ISA/ANSI S51.1. SPDT Switching Element Single-Pole, Double Throw (SPDT) has three connections: C — Common, NO — Normally Open and NC — Normally Closed, which allows the switching element to be electrically connected to the circuit in either NO or NC state. DPDT Switching Element DPDT is two synchronized SPDT switching elements which actuate together at increasing set point and deactuate together at decreasing set point. Discrete SPDT switching elements allow two independent circuits to be switched; i.e., one AC and one DC. The synchronization linkage is factory set, and is not field adjustable. Synchronization is verified by connecting test lamps to the switching elements and observing them go “On” simultaneously at actuation and “Off” simultaneously at deactuation. Overrange The maximum input pressure that may be continuously applied to the pressure switch without causing permanent change of set point, leakage or material failure. 6/32 Registered Quality System to ISO 9001 | 913-888-2630 | SORInc.com Form 216 (01.16) ©SOR Inc. Pressure and Vacuum Switches Step 1: Piston-Spring 6NN-K5-M4-C2A-YY This table is a listing of piston-spring combinations and the corresponding adjustable ranges, dead bands, overrange and proof pressures. Adjustable range is expressed for increasing pressure; the set point must be within the adjustable range. Dead band is expressed as typical. See Dead Band Considerations on page 8. Piston-Spring Designators psi (in. wc) Typical Dead Band1 bar [mbar] psi (in. wc) bar [mbar] 12 - 662 (0.6 to 2.5) [1.5 to 6.2] (0.4) [1] 12 - 6143 (2.5 to 45) [6.2 to 110] (0.8) [2] 12 - 2 0.4 to 2.0 [30 to 140] 0.1 [6.9] 12 - 4 0.5 to 6.0 [35 to 415] 0.1 [6.9] 12 - 5 0.75 to 12 [50 to 830] 0.1 [6.9] 12 - 45 1 to 16 [70 to 1100] 0.15 [10.3] 4-2 2 to 8 [140 to 550] 0.2 [13.8] 4-4 2 to 25 0.14 to 1.7 0.3 [20.7] 4-5 3 to 50 0.2 to 3.5 0.4 [27.6] 4 - 45 4 to 75 0.3 to 5 0.5 [34.5] 6-2 7 to 30 0.5 to 2 0.5 [34.5] 6-3 12 to 100 0.8 to 7 0.9 [62.1] 6-5 20 to 180 1.4 to 12 1.4 [96.5] 6 - 45 25 to 275 1.7 to 19 1.9 0.13 5-3 25 to 240 1.7 to 16 2.2 0.15 5-5 35 to 375 2.4 to 26 3.1 0.21 5 - 45 45 to 550 3.1 to 38 3.9 0.27 9 - 46 100 to 500 7 to 35 5.3 0.37 9-5 9.2 0.63 200 to 1000 14 to 70 6 200 to 1750 14 to 120 15 1.03 1 - 456 500 to 4000 35 to 275 98 6.76 6 9 - 45 Adjustable Range4 1. Dead band values are expressed as typical expected at mid-range with the standard K switching element assembly installed. When optional switching elements are specified, corresponding dead band multipliers shown on pages 8 and 10 must be applied. 2. The 12/66 piston/spring combination is available with the N switching element only. 3. Adjustable range becomes 10 to 45 in. wc whenever switching elements other than K, KA, W, D or M are used. 4. Special ranges may be possible. Consult the factory or the SOR representative in your area. Form 216 (01.16) ©SOR Inc. SORInc.com Overrange Proof psi bar psi bar 200 14 400 28 750 50 1000 70 1500 100 2500 170 2500 170 6000 410 5000 340 6000 410 5. Diaphragms may have an additional effect on dead band. See page 13, Note 9. 6. Diaphragm life may be limited by using T or H switching elements with Numbers 1 and 9 pistons. 7. Metric bar (mbar) values are practical equivalents of the reference English values; not necessarily exact mathematical conversions. This data appears on the product nameplate when metric engineering units are specified. 8. A breather drain (Accessory KK, see page 16) should be specified when low pressure adjustable ranges are used in environments with significant ambient temperature changes. 9. Filled isolators attached to the pressure switch will affect dead band. | 913-888-2630 | Registered Quality System to ISO 9001 7/32 Pressure and Vacuum Switches Step 1: Piston-Spring 52NN-K116-M4-C2A-YY This table is a listing of piston-spring combinations and the corresponding adjustable ranges, dead bands, overrange and proof pressures. SOR vacuum switches are compound; they will operate in either vacuum or pressure modes. The adjustable range is expressed from maximum vacuum decreasing to zero gauge and increasing to maximum pressure. Dead band is expressed as typical. See dead band considerations below. The set point must be within the adjustable range. A vacuum switch is generally better suited than a pressure switch for set points very near zero gauge. Piston-Spring Adjustable Range2 (Vacuum - 0 - Pressure) in. Hg (in. wc) Typical Dead Band1 (Vacuum Mode) bar [mbar] in. Hg (in. wc) mbar 52 - 116 (20 - 0 - 20) [50 - 0 - 50] (0.8) 1.99 52 - 117 (40 - 0 - 40) [100 - 0 - 100] (0.9) 2.23 54 - 117 15 - 0 - 15 0.5 - 0 - 0.5 0.4 13.5 54 - 118 30 - 0 1.0 - 0 0.6 20.3 56 - 2163 30 - 0 - 20 1.0 - 0 - 0.7 0.8 27.1 56 - 316 30 - 0 - 160 1.0 - 0 - 5.4 1.1 37.3 3 Notes 1. Dead band values are expressed as typical expected at mid-range with the standard K switching element assembly installed. When optional switching elements are specified, the corresponding dead band multipliers shown below must be applied. 2. Special ranges may be possible. Consult the factory or the SOR representative in your area. Overrange Proof psi bar psi bar 200 14 400 28 750 50 1000 70 1500 100 2500 170 3. Number 56 piston is not available with a “T” micro switch 4. Diaphragms may have an additional effect on dead band. See page 13, Note 9. 5. Metric bar (mbar) values are practical equivalents of the reference English values; not necessarily exact mathematical conversions. This data appears on the product nameplate when metric engineering units are specified. Dead Band Considerations 1. Dead band values are expressed as typical expected at mid-adjustable range using the standard K switching element. When optional switching elements are specified, corresponding dead band multipliers must be applied. 2. Dead bands are fixed (non-adjustable), except when T or H switching elements are used. 3. Dead band can be adjustable by selecting T or H switching element. (Diaphragm life may be limited when used with Numbers 1 and 9 pistons.) 4. Dead band multipliers must be applied to the typical dead band value shown for piston spring combination in specifications, pages 7 and 8, whenever optional switching elements other than K, KA or W are used. 5. Dead band can be widened by selecting an optional switching element with a multiplier greater than 1.0. Example: Model 6NN-G5-M4-C2A-YY Typical Dead Band 1.4 psi G-Switching Element multiplier = 3 Corrected Typical Dead Band 1.4 x 3 = 4.2 psi 6. See item #9, page 7. 8/32 Registered Quality System to ISO 9001 | 913-888-2630 | SORInc.com Switching Element Designators Dead Band Multiplier K, KA, N, W 1.0 D, E, J, M, Y 1.5 A, B, EF, G, JF 3.0 L, YY 3.5 AF, CA, EE 4.0 BD, C, JJ, S 5.0 EG, JG 5.5 AA, BB, GG, KK 6.0 LL 6.5 AG 8.5 T 2.5 to 6.5 H 1.0 to 3.0 Form 216 (01.16) ©SOR Inc. Pressure and Vacuum Switches Step 2: Housing 6NN-K5-M4-C2A-YY General Purpose NEMA 1 PP Electrical: 3/4” NPT(F) - Right Material: Aluminum See Agency Listings pages 17 & 18. See Switching Element Groups 1, 2, 3 & 4 below. P3 Electrical: 3/4” NPT(F) - Left, Right Material: Aluminum See Switching Element Groups 1, 2, 3, & 4 below. H3 Electrical: Exposed contacts Material: Aluminum Open bracket with exposed switching element-does not meet NEMA 1. See Switching Element Groups 1 & 3 below. Weatherproof NEMA 4, 4X, IP66 NN N6 Electrical: 3/4” NPT(F) - Right Material: Aluminum See Agency Listings pages 17 & 18. See Switching Element Groups 1, 2, 3 & 4 below. Electrical: 3/4” NPT(F) - Right Material: Carbon Steel See Switching Element Group 1 below. N3 RN RM Electrical: 3/4” NPT(F) - Left, Right Material: Aluminum See Agency Listings pages 17 & 18. See Switching Element Groups 1, 2, 3 & 4 below. N4 Electrical - RN: 3/4” NPT(F) - Right Electrical - RM: M20 x 1.5 - Right Six-place compression type terminal block Material: Aluminum See Agency Listings pages 17 & 18. See Switching Element Groups 1, 2, 3 & 5 below. RT RS RB Electrical: 3/4” NPT(F) - Right Material: Aluminum Cover: Heavy Duty with Viton gasket See Agency Listings pages 17 & 18. See Switching Element Groups 1, 2, 3 & 4 below. Electrical - RT: 3/4” NPT(F) - Right Electrical - RS: M20 x 1.5 - Right Six-place compression type terminal block Material: 316SS See Agency Listings pages 17 & 18. See Switching Element Groups 1, 2, 3 & 5 below. Electrical: 3/4” NPT(F) - Right Manual reset only Six-place compression type terminal block Material: Aluminum See Agency Listings pages 17 & 18. See Switching Element Group 6 below. Hazardous Locations - Conventional Explosion Proof NEMA 4, 4X, 7, 9, IP66 *L *S *TA UL Listed Class I, Group C & D; Class II, Group E, F, & G; Divisions 1 & 2 as an outlet box only Electrical: 3/4” NPT(F) - Right Material: Cast Iron Weatherproof with Option CG See Switching Element Groups 1, 3 below. Ul Listed Class I, Group C & D; Class II, Group E, F, & G; Divisions 1 & 2 as an outlet box only Electrical: 3/4” NPT(F) - Left, Right, Top Material: Cast Iron Weatherproof with Option CG See Switching Element Groups 1, 3, 6 below. Class I, Group A, B, C, & D; Class II, Groups E, F, & G; Divisions 1 & 2 as an outlet box only Electrical: 3/4” NPT(F) - Left, Right, Top Material (Housing): Aluminum Material (Cover): Aluminum Weatherproof with Option CG. See Switching Element Groups 1 & 3 below. *LC *SC *J4 UL Listed Class I, Groups C & D; Class II, Groups E, F & G; Divisions 1 & 2 as an outlet box only Electrical: 3/4” NPT(F) - Right Six-place compression type terminal block with Option LL Material: Copper-free aluminum Weatherproof See Switching Element Groups 1, 2 & 3 below. Separate electrical and set point adjustment compartments. Weatherproof Six-place, compression-type terminal block. See Agency Listings pages 17 & 18. UL Listed Class I, Groups C & D; Class II, Groups E, F & G; Divisions 1 & 2 as an outlet box only Electrical: 3/4” NPT(F)-Right, Left, Top Six-place, compression-type terminal block with Option LL Material: Copper-free aluminum Weatherproof See Switching Element Groups 1, 2, 3 & 6 below. Separate electrical and set point adjustment compartments. Six-place, compression-type terminal block. Explosion Proof IIB - T4. Material: Aluminum Right hand electrical outlet: PF 3/4” (F) See Switching Element Groups 1, 2, & 3 below. *B3 Electrical: 3/4” NPT(F) - Left, Right Material: Aluminum *B4 Electrical: M20 x 1.5 - Left, Right Material: Aluminum *B5 Electrical: M20 x 1.5 - Left, Right Material: Cast Iron *B6 Electrical: 3/4” NPT(F) - Left, Right Material: Cast Iron Switching Element Groups 1, 2, 3 & 5 below. *Not recommended for direct mount where vibration is expected. Housing should be securely mounted to a flat surface (bulkhead or panel rack) or pipe stanchion. Switching Element Group/Housing Compatibility Group 1 Group 2 Group 3 Group 4 Group 5 Group 6 A, AA, B, BB, BD*, C**, CA***, E, EE, G, J, JJ, K, KA, L, N, S, W, Y GG, KK, LL, YY T H AF, AG, EF, EG, JF, JG D, M *BD only available with RN, RT housings. **C micro switch is not available in L, S and TA housings. ***CA micro switch only available in PP, NN, N3 and N4 housings. Form 216 (01.16) ©SOR Inc. SORInc.com | 913-888-2630 | Registered Quality System to ISO 9001 9/32 Pressure and Vacuum Switches Step 3: Switching Element 6NN-K5-M4-C2A-YY Switching Element Service Electrical Contact Type Electrical Connection Type Wide Dead Band AC AC or DC Wide Dead Band DC Narrow Dead Band DC Very Wide Dead Band DC Very HighCapacity DC Magnetic Blow-Out Hi-Ambient Temperature Rating - 400°F Low Pressure Service 12-66 only Wide Adjustable Dead Band Narrow Adjustable Dead Band Manual Reset Decreasing Pressure (Automatic Actuation Increasing Pressure) Manual Reset Increasing Pressure (Automatic Actuation Decreasing Pressure) Hermetically Sealed Switching Element Hermetically Sealed Gold Contacts FM-Approved Service Only Explosion Proof EEx d IIC T6 (SW Only) K, KA, G, L, C, N, S, Y, W Switching Elements - Screw Terminals. All other Switching Elements _ 18” 18 AWG Color-Coded Wire Leads except when terminal blocks are specified. T & H Switching Elements - Consult Factory. Low Power Gold Contacts Single Switching Element SPDT - (1) SPDT Double Switching Element DPDT - (2) SPDT Synchronized actuation/deactuation at increasing/decreasing set points. Normal Service AC AC Rating Dead Band Multiplier DC Rating Resistive Designator Volts Amps Volts Amps Volts Amps SPDT DPDT SPDT DPDT 250 15 125 0.4* 30 5.0* 1.0 6.0 K KK 125 1 - - 28 1.0* 1.0 - KA - 125 1 - - 30 1.0 1.5 5.0 J JJ 250 15 125 0.5 - - 3.0 6.0 G GG 250 11 125 0.5* 30 5.0 3.0 6.0 A AA 250 15 125 0.5 30 10* 3.5 6.5 L LL 250 5 125 0.5* 30 5.0* 1.5 4.0 E EE 250 15 125 0.5 - - 5.0 - C - - - 5.0 - S - 1.5 125 10 125 Minimum 10.0 Maximum 250 5 125 0.3 - - 3.0 6.0 B BB 250 5 125 0.5* - - 1.5 3.5 Y YY 250 5 125 0.3* - - 1.0 - W - 250 10 - - - - 1.0 - N - 250 15 125 0.4* - - 2.5 to 6.5 - T - 250 15 - - - - 1.0 to 3.0 - H - D - M - 250 15 125 0.5 - - 1.5 - 250 11 125 0.5* 30 5.0 4.0 8.5 AF AG 250 5.0 125 0.5* 30 5.0* 3.0 5.5 EF EG 125 1.0 - - 30 1.0 3.0 5.5 JF JG 250 22 125 0.5 - - 4.0 - CA - 250 7.0 250 0.25 30 7.0 5.0 - BD - Cross reference compatibility chart on page 9 to ensure that switching element will fit in housing. Review notes on page 11 for more details. 10/32 Registered Quality System to ISO 9001 | 913-888-2630 | SORInc.com Form 216 (01.16) ©SOR Inc. Pressure and Vacuum Switches Step 3: Switching Element 6NN-K5-M4-C2A-YY Notes 1. Double switching elements have wire leads except when supplied in housings RB, RM, RN, RS, RT, B3, B4, B5, B6 and J4. Terminal blocks are standard in these housings. 2. Dead band multipliers must be applied to the typical dead band figures given in the specification tables on pages 7 and 8. 3. Switching element ambient temperature limits: -65 to 400oF -65 to 250oF -40 to 167oF -13 to 158oF -65 to 180oF (-54 to 204oC) B, Y, W (-54 to 120oC) A, E, & J (-40 to 75oC) AF, AG, EF, EG, JF, JG (-25 to 70oC) BD (-54 to 80oC) All others 4. The hermetically sealed switching element capsule is ATEX Approved, UL Listed, CSA Certified and TestSafe Approved as an explosion proof snap switch according to the following table with conditions and exceptions specified in Note 3. Agency Hazardous Location Conditions Designator UL Listed CSA Certified Class I, Groups A, B, C, & D Class I, Groups E, F & G; Divisions 1 & 2 AF, EF, AG, EG, JF, JG TestSafe Approved Ex s IIC T6 IP65 Class I, Zone I DIP T6 IP65 AF, EF, AG, EG ATEX Approved II 2 G EEx m II AF, EF, AG, EG, JF, JG Form 216 (01.16) ©SOR Inc. SORInc.com 5. Switching elements W, & Y have Elgiloy springs. 6. Certain switching elements are capable of handling greater voltage and/or amperage. Consult the factory should your requirements exceed catalog values. All switching elements above except BD are UL Recognized and CSA Certified. The DC current ratings marked with an asterisk (*) are not UL Listed but have been verified by testing and/or experience. 7. Ambient temperature is reduced to 200°F (93°C) for J, JJ, A, AA, E, EE, B, BB, Y, YY, & W switching elements when CV accessory is selected. CAUTION: The switching element assembly has been precisely positioned in the housing at the factory for optimum performance. Any inadvertent movement or replacement in the field will degrade performance, could render the device inoperative, and can void the warranty unless factory authorized procedures are followed. | 913-888-2630 | Registered Quality System to ISO 9001 11/32 Pressure and Vacuum Switches Step 4: Diaphragm & O-Ring 6NN-K5-M4-C2A-YY Notes 1. N4 diaphragm system is standard, but requires a designator in the model number. It is normally suitable for air, oil, water and noncorrosive processes. M2 diaphragm system is standard on Number 56 vacuum switches. (See notes 10 & 13.) 2. U7 designates a welded flush-type diaphragm. Available only in 1” NPT(M) 316SS on Numbers 5 & 6 pistons with K switching element. See page 15. 3. U8 designates the welded fire-safe diaphragm system. 316SS is stocked. Not available on Number 1 piston or vacuum switches. Example: U8-C2A is a 316SS fire-safe welded diaphragm system. See page 15. 4. U9 designates a welded diaphragm system. Not available on vacuum switches. Example: U9-A1A is a Monel welded diaphragm system. See page 15. 5. Other diaphragm and o-ring combinations may be available. Consult the factory or the SOR representative in your area for more information. 6. Wetted parts have been selected as representing the most suitable commercially available material for use in the service intended. However, they do not constitute a guarantee against corrosion or permeation, since processes vary from plant to plant and concentration of harmful fluids, gases or solids vary from time to time in a given process. Empirical experience by users should be the final guide. Alternate materials are generally available. O-Ring (Wetted) Viton Kalrez* Viton Kalrez* Viton Kalrez* Viton Kalrez* Designator A4 Monel A6 H4 Hastelloy-B H6 J4 Hastelloy-C J6 L4 Carpenter-20 L6 Viton GLT M1 Buna-N M2 Viton M4 Neoprene M5 316L SS Kalrez* M7 Aflas M8 M9 EPR (See Note 11) N1 Viton Buna-N Buna-N (See Note 13) N3 (See Note 7) TCP Teflon-Coated Polyimide N4 Standard (See Notes 1 & 13) N5 Kalrez* (See Note 13) Kalrez* Kalrez EPR Aflas TCP Teflon-Coated Polyimide Buna-N Buna-N Neoprene Neoprene Viton (Continued on page 13.) Diaphragm (Wetted Primary) Viton GLT N6 N7 (See Note 13) N8 (See Note 13) P1 (See Note 13) R1 S1 Viton S2 Buna-N Viton Neoprene W2 W4 Tantalum (See Note 10) W5 Kalrez* W6 EPR EPR Y1 None Welded None Fire-Safe Welded None Welded U7 (See Note 2) U8 (See Note 3) U9 (See Note 4) *Kalrez or equivalent Perfluoroelastomer (FFKM) o-rings 12/32 Registered Quality System to ISO 9001 | 913-888-2630 | SORInc.com Form 216 (01.16) ©SOR Inc. Pressure and Vacuum Switches Step 4: Diaphragm & O-Ring 6NN-K5-M4-C2A-YY 7. N3 diaphragm system utilizes a durable back-up diaphragm for high cycle-rate, high shock applications where Buna-N and TCP are compatible with the process. Consult factory if process temperatures are well below freezing. 8. This table shows allowable minimum and maximum temperatures for o-rings. Consult the factory for temperatures down to –65°F on fire-safe and welded metal diaphragm systems. O-Ring Material °F °C Viton 32 to 400 0 to 204 Viton GLT -20 to 400 -29 to 204 Kalrez* 5 to 400 -15 to 204 Aflas 25 to 400 -4 to 204 Buna-N Neoprene EPR -30 to 200 -34 to 93 Fire-Safe/Welded Diaphragm System -30 to 400 -34 to 204 TCP Teflon-Coated Polyimide Diaphragm -30 to 400 -34 to 204 9. Dead bands are slightly higher when using H, J, N3, N6, U or W series diaphragm options. Consult the factory. 10.Diaphragm systems N1, N3, N4, N5, N6, N7, N8, P1, R1, S1, S2, W2, W4, W5, W6, Y1, U8, U9 are not available on vacuum switches with number 52, 54 or 56 pistons. 11.M9 diaphragm system is suggested for steam applications up to 400°F. 12.If Kalrez, EPR or Viton is selected for high temperature process media or ambient temperature requirements, the A, B, E, J, W or Y switching elements are suggested with reference to the table in Note 3, page 11. 13.Only diaphragm systems N1, N4, N5, N7, N8 and P1 are available on the 12-66 piston spring combination. *Kalrez or equivalent Perfluoroelastomer (FFKM) o-rings Form 216 (01.16) ©SOR Inc. SORInc.com | 913-888-2630 | Registered Quality System to ISO 9001 13/32 Pressure and Vacuum Switches Step 5: Pressure Port 6NN-K5-M4-C2A-YY Piston Process Connection Size Aluminum Series 2000 Wrought 356 or 360 Casting Pressure Port Material Carbon Steel Ledloy Wrought or WCB Casting 12, 4 52, 54 6, 5, 9 1, 56 1/4” NPT(F) B1A (Standard) - 12, 4 52, 54 6, 5, 9 1, 56 1/2” NPT(F) 6, 5, 9 1, 56 4, 54 12, 52 12, 52 3/4” NPT(M) 1” NPT(M) 1” NPT(F) 2” NPT(F) 1/4” NPT(F) Flushing Port - B2A - - - - - F1A - F2A F3A - - - C4A* C5A C6A (Standard) 316SS/316LSS Wrought or CF-8M Casting C1A C2A C3A 347 Stainless Steel Wrought or CF-8C Casting E1A E2A E3A Carpenter 20 Stainless Steel Wrought or CF-7M Casting L1A L2A L3A Brass (See Note 6) Half Hard Yellow Wrought or Silicon Brass Casting D1A D2A D3A Hastelloy-B H1A H2A H3A Consult factory availability of pressure port material and process connection size. Hastelloy-C J1A J2A J3A Monel A1A A2A A3A *C4A only available with Pistons 5 & 6 when U7 diaphragm is specified. See page 15. Notes 1. Select designators for material and connection size. Large bold-face letters denote those items generally available from stock. Small light-face letters denote items with limited stock and possible long delivery. 2. 1/4” and 1/2” tapered BSP(F) pressure ports are available. Consult factory. 3. Combinations are possible when a particular connection size is not available for the range (piston spring) desired. For example, if 2” NPT(F) is desired for a Number 4 piston, the Number 12 pressure port can be supplied. The piston would be designated as Number 124 and the overrange and proof pressures for Number 12 apply. Note: 124, 125 and 126 are the only available combinations. 4. Many other materials such as PVC, Kynar, etc., are available. Denote materials not shown by specifying an X followed by the required connection size, and describe the material. Examples: X2A = PVC pressure port with 1/2” NPT(F) connection. X1A = Titanium pressure port with 1/4” NPT(F) connection. Non-metal pressure ports generally reduce proof pressure and may reduce overrange pressure. The pressure port material may limit the process temperature. Delivery may be longer than normal. 5. Raised-face and flat-face flanges to match ASA 150 and ASA 300 lb. in commercially available materials can be supplied on Series 12 and 4 pistons by adding an X suffix to the model numbers and specifying “X - (size) inch (material) (raised- or flat-) face flange to match ASA (rating) lb.” 6. Brass not available on Piston Numbers 9 and 1. 7. 1/4” NPT(F) Flushing Port standard on C6A pressure ports. See next page for presentation of welded diaphragm and FM Approved fire-safe systems. 14/32 Registered Quality System to ISO 9001 | 913-888-2630 | SORInc.com Form 216 (01.16) ©SOR Inc. Pressure and Vacuum Switches Designator U7 Process Connection Process Face U8 Piston Shaft Spring Stop Cylinder Disc Diaphragm Pressure Port U9 Diaphragm Pressure Port Welded Diaphragm & Fire-Safe Systems Description Welded Flush-Type Diaphragm System A metal diaphragm is welded to the process face of the pressure port, thereby, eliminating the o-ring. This arrangement may be indicated for viscous or slurry process where cleanliness is required or where process build-up and clogging is unacceptable. The pressure port designator determines the material: Only 1” NPT(M) 316SS is available. Example: U7-C4A U7 = 316SS welded flush-type diaphragm C4A = 1” NPT(M) 316SS pressure port Note: U7 is limited to Numbers 5 and 6 pistons and the K switching element. Not available on vacuum switches. Fire-Safe Welded Diaphragm System Factory Mutual System Approved - U.S Patent Number 4,438,305 Tested in flames at 1900oF for periods up to 30 minutes while pressurized to the rated overrange pressure. A metal diaphragm, the cylinder disc and the pressure port are welded as a unit, thereby, eliminating the o-ring. This arrangement may be indicated for extremely corrosive, hot, harsh or volatile process where o-rings are not suitable. See firesafe definition on page 6. 316SS is stocked. Hastelloy B and C, and Monel are available, but may require a longer lead time. The pressure port designator determines the material. Example: U8-C2A U8 = Fire-safe welded diaphragm system C2A = 1/2” NPT(F) 316SS pressure port Note: 1/2” NPT(F) is stocked; 1/4” NPT(F) is not stocked and has a longer lead time. Not available on Number 1 piston and vacuum switches. Welded Diaphragm System A metal diaphragm is welded to the pressure port, thereby, eliminating the o-ring. This arrangement may be indicated for extremely corrosive, hot or harsh process where o-rings are not suitable. 316SS is stocked. Hastelloy B and C, and Monel are available, but may require a longer lead time. The pressure port designator determines the material. Example: U9 - A2A U9 = Monel welded diaphragm A2A = 1/2” NPT(F) Monel pressure port Note: Not available on vacuum switches. C6A Two-inch Pressure Port The wide pressure port minimizes the possibility of clogging when the process media is sludgy or viscous. See page 20 for dimensions. A 2” NPT(F) pressure port with a 1/4” NPT(F) flushing port can be supplied with a welded diaphragm, or with a conventional diaphragm and o-ring combination. Form 216 (01.16) ©SOR Inc. SORInc.com | 913-888-2630 | Registered Quality System to ISO 9001 15/32 Pressure and Vacuum Switches Step 6: Accessories 6NN-K5-M4-C2A-YY Accessory/Option & Description Designator Wetted parts are cleaned for oxygen service. BB ATEX approved pressure/vacuum switch. See Agency Listings on page 18 for details. CL CSA Certified pressure/vacuum switch. Available with PP, NN, RB, RN, RT, B3 and B6. Housing has earth (ground) lug. See Agency Listings on page 17 & 18 for details. CS Neoprene cover gasket (o-ring) to make L, S and TA explosion-proof housings weathertight. CG Canadian Registration Number (CRN) - Process ratings may be affected. Consult the factory for details. CV Cemented cover gasket on weathertight housings. GC Sealed electrical lead adapter. Provides protection to housing interior, switching element and dry side of pressure sensing assembly from condensate in the electrical conduit and corrosive atmospheres. (Protrudes approximately 2” from housing.) GG Universal terminal box. Stainless steel, 1/2” NPT(F). ATEX Approved EEx d IIC T4, T5 & T6. HB** Universal terminal box. Stainless steel, M20 x 1.5(F). ATEX Approved EEx d IIC T4, T5 & T6. HBME** Universal terminal box. Stainless steel, 1/2” NPT(F). FM Approved and CSA Certified. Explosion Proof Class I, Groups A, B, C, & D; Class II, Groups E, F & G; Class III; Divisions 1 & 2 (NEMA 4X IP65) Breather Drain Crouse Hinds ECD-15 for Hazardous Locations Class I, Groups C & D, Class II, Groups E, F & G; on S or SC housings only. Sintered metal plug in weathertight housing. HT** KK Terminal block. 6-place compression type standard in B and R series housings. Optional in LC and SC housings. 6-place screw type standard in J4 housing. LL Multi-Listed pressure/vacuum switch. ATEX, CSA & UL. Available with B3 & B6 housings. See Agency Listings on Pages 17 & 18 for details. ML Vacuum protector plate. Retains diaphragm in pressure switch if subjected to vacuum greater than 10 in. Hg. If a pressure switch is subjected to continuous, rapid changes of vacuum, other protection may be available (consult factory). Material matches or exceeds pressure port material. N/A on Pistons 52, 54, or 56. MM Compliance to NACE Certification MR0175/ISO 15156. NC* INMETRO approved pressure/vacuum switch. See Agency Listings on page 18 for details. NM Carbon steel body with stainless steel adjusting nut. PB Pipe (stanchion) mounting kit for (1-1/2 to 2” pipe). PK Tag, fiber. Attached with plastic wire to housing. Stamped with customer-specified tagging information. PP Powder coat epoxy coating. No coating on stainless steel parts or plated screws. (500 hours-salt spray) PY Tag, stainless steel. Attached with stainless steel wire to housing. Stamped with customer-specified tagging information. (2 lines, 18 characters and spaces per line.) RR Stainless steel body and adjusting nut for corrosive environments. SB Stainless steel piston and cylinder disc for corrosion resistance. SP Explosion proof weatherproof electrical junction box with screw terminals. Aluminum 3/4” NPT(F) top or right conduit connections as required. UL Listed and CSA Certified Class I, Groups A, B, C & D; Class II, Groups E, F & G; Divisions 1 & 2. (Available on L, LC, S, SC and TA housing.) Includes cover o-ring for weatherproof applications. TB** Oversize stainless steel nameplate or separate stainless steel tag. Permanently attached to housing. Stamped with customer-specified tagging information. TT Fungicidal varnish. Covers exterior and interior except working parts. VV UL Listed pressure vacuum switch. Available with B3 and B6 housings. See Agency Listings on page 17 & 18 for details. WV “X” is used as a suffix to the model number for special requirements not keyed elsewhere in the model number by an “X”. Each “X” must by completely identified in the text of the order or inquiry. When more than one “X” is required, use “X” followed by the number of such items. For example, “X3” means three separate otherwise unidentifiable requirements. X Epoxy coating. Exterior only. Polyimide epoxy with 316SS pigment. (200 hours-salt spray) YY Chained cover with captive screws to conform to former JIC specification. ZZ Note: See pages 17 & 18 for Agency Approved, Certified or Listed Accessories Options. Representative Information Only: A slash and a three-digit number (/000) appearing after the last Accessory designator letter in the model number denotes special administrative procedures with respect to factory representatives. It is not part of the model number and is used only by the factory or a factory representative. * Consult the factory for materials other than 316/316L. ** Agency ratings for SOR product sold with junction boxes will be limited to either the rating of the instrument housing or junction box, whichever is lower. 16/32 Registered Quality System to ISO 9001 | 913-888-2630 | SORInc.com Form 216 (01.16) ©SOR Inc. Pressure and Vacuum Switches Certificates C1 Calibration ¿ C2 Hydrostatic Pressure Test C3 C4 C5 C6 C8 ¿ Inspection Report ¿ Compliance / Conformance Test Certificates B1 B4 B5 B6 B7 A1 A2 A3 A4 A5 A6 A7 A8 ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ Dielectric Test ¿ ¿ Insulation Resistance ¿ ¿ Typical Material of Wetted Parts ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ ¿ Agency Listings UL For Hazardous Locations Class I, Groups B, C, & D; Class II, Groups E, F, & G; Divisions 1 & 2 Piston ALL CSA Housing Switching Element B3, B6 A, AA, AF, AG, B, BB, C, E, EE, EF, EG, G, GG, H, J, JF, JG, JJ, K, KA, KK, L, LL, N, P, S, T, W, Y, YY Spring Diaphragm & O-Ring Pressure Port Material & Connection Size Accessories WV or ML Required ALL ALL ALL All except CG, GC, GG, HB, HT, KK, LL, ME, TB, ZZ For Hazardous Locations Class I, Groups B, C, & D; Class II, Groups E, F, & G; Divisions 1 & 2 Piston ALL Housing Switching Element B3, B6 A, AA, AF, AG, B, BB, C, E, EE, EF, EG, G, GG, H, J, JF, JG, JJ, K, KA, KK, L, LL, N, P, S, T, W, Y, YY Spring Diaphragm & O-Ring Pressure Port Material & Connection Size Accessories CS or ML Required ALL ALL ALL Diaphragm & O-Ring Pressure Port Material & Connection Size All except CG, GC, GG, HB, HT, KK, LL, ME, TB, ZZ General Purpose and Weathertight (CSA Enclosure Type 4) Piston Housing PP (General Purpose) NN (Type 4) ALL Switching Element Spring A, AA, B, BB, C, E, EE, G, GG, GA, H, J, JJ, JL, K, KK, KA, L, LL, N, S, T, W, Y, YY RN, RT (Type 4) A, AA, AF, AG, B, BB, C, E, EE, EF, EG, G, GG, GA, J, JJ, JL, JF, JG, K, KK, KA, L, LL, N, S, T, W, Y, YY RB, RH (Type 4) D, DA, M (Manual Reset only) Form 216 (01.16) ©SOR Inc. SORInc.com Accessories CS Required ALL ALL ALL All except GC, LL | 913-888-2630 | Registered Quality System to ISO 9001 17/32 Pressure and Vacuum Switches TIIS For Hazardous Locations Rating: Explosion Proof Class IIBT4 Piston Housing Switching Element J4 A, AA, B, BB, C, E, EE, G, GG, GA, H, J, JJ, JL, K, KK, KL, L, LL, N, S, T, W, WW, Y, YY 1, 4, 5, 6, 9, 12, 52, 54, 56 FM Agency Listings Spring ALL Diaphragm & O-Ring ALL Pressure Port Material & Accessories Connection Size BB, MM, NN, PB, PC, PK, PP, RR, SB, TT, W, YY, X ALL Pressure Supervisory Switches for Fuel Gas/Fuel Oil, and Ventilating or Combustion Air Piston Housing Switching Element Spring Diaphragm & O-Ring 2, 3, 4, 5, 45, 614 M2, M4, M5, N1, N3, N4, N5, N6, P1, R1, S1 U9, W2, W4, W5, W6, Y1 PP (NEMA 1) 1, 4, 5, 6, 9, 12 NN, N3, N4 (NEMA 4) CA Pressure Port Material & Accessories Connection Size ALL ALL Thread Type: A, B KK (PP Housing only) BB, MM, GG, PP, RR, SS, TT, VV, YY, ZZ Airflow Interlocking Switches for Ventilating or Combustion Air ATEX or INMETRO Piston Housing 4, 12 PF (NEMA 1) Switching Element Spring N (12 Piston only) 66 (N switch) C, EE, G, K, L, S, T, W 2, 4, 5, 45, 614 Switching Element Spring Diaphragm & O-Ring P1 Pressure Port Material & Accessories Connection Size B1A, B2A PP, RR, SS (SS same as TT) EEx d IIC T6 Piston ALL Housing B3, B4, B5, B6 Diaphragm & O-Ring Pressure Port Material & Accessories Connection Size CL (for all Hsgs) or ML (for B3/B6 Hsgs) required for ATEX A, AA, AF, AG, B, BB, C, E, EE, EF, EG, G, GG, H, J, JF, JG, JJ, K, KA, KK, L, LL, N, P, S, T, W, Y, YY ALL J, JJ, JF, JG ALL ALL ALL NM required for INMETRO All except CG, GC, GG, HB, HT, KK, LL, ME, TB, ZZ Ex ia IIC T6...T4 Gb ALL RN, RM, RT, RS ALL ALL CL Rostechnadzor (RTN) Certificate Permit for instruments used and operated in hazardous industrial facilities in Russia. Standard on most models. Certificate available on request. 18/32 Registered Quality System to ISO 9001 | 913-888-2630 | SORInc.com Form 216 (01.16) ©SOR Inc. Pressure and Vacuum Switches Manual Reset Manual Reset Button RB - Weatherproof S - Explosion Proof SOR Pressure Switches in this catalog may be specified with manual reset electrical switching elements D or M. D actuates automatically on increasing pressure. M actuates automatically on decreasing pressure. Depress the button to manually reset. Housings must be RB (weatherproof) or S (explosion proof) because of the requirement of a hub for the manual reset assembly. Refer to page 3 for How to Order instructions. Weights Housing Weight (lbs) (kgs) H3 1.5 0.75 NN, N3, N4, PF, PP, P3 2 1 RB, RM, RN 2.5 1.25 N6 3 1.5 LC, SC 4 2 L, S 5 2.5 TA 6 3 B3, B4, J4, RT, RS 8 4 B5, B6 10 5 Actual shipping weights may vary from the charted values because of product material, configuration and packaging requirements. Note PK Pipe Kit adds approximately 1.5 lbs. (0.7 kgs). TB Junction box adds approximately 5 lbs (2.25 kgs). Dimensions Dimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certified drawings for a particular model number. Notes 1. Dimensions in this catalog are expressed as millimeters over inches (Linear = mm/in.). 2. Dimensions marked with an asterisk (*) on housing dimension drawings (pages 20 through 31) vary with respect to process connection size. The chart below lists these dimension variances. 3. Electrical Connection Size: 3/4” NPT(F) standard. 1/2” NPT(F), 1/2” NPT(M), M20 x 1.5, PG 13.5, PF 3/4” optional. Consult the factory for compatibility with selected housing or agency listing. Process Connection Size Piston Number 12, 52 4, 54 6, 5, 9, 1, 56 1/4” NPT(F) Shown Shown Shown 1/2” NPT(F) Shown Shown Add 13.2 0.52 3/4” NPT(M) - - Add 23.1 0.91 1” NPT(F) Add 5.6 0.22 - - 1” NPT(M) - Add 46.0 1.81 - 2” NPT(F) Add 25.4 1.00 - - Length “A” 1/4” NPT(M) Add 29.7 1.17 Add 29.7 1.17 Add 29.7 1.17 Length “A” 1/2” NPT(M) Add 38.9 1.52 Add 38.9 1.52 Add 38.9 1.52 Form 216 (01.16) ©SOR Inc. SORInc.com | 913-888-2630 | Registered Quality System to ISO 9001 19/32 Pressure and Vacuum Switches Dimensions Dimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certified drawings for a particular model number. Drawing 0091354 Wide Pressure Port: C6A See description on page 15. 20/32 Drawing 0090300 Drawing 0091353 Pipe Mounting Kit: PK Junction Box with Terminal Block: TB Registered Quality System to ISO 9001 | 913-888-2630 | SORInc.com Form 216 (01.16) ©SOR Inc. Pressure and Vacuum Switches Dimensions Dimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certified drawings for a particular model number. Weatherproof - NEMA 4, 4X, IP66 MODEL # MODEL # SALES ORDER # LINE ITEM # LINE ITEM # PURCHASE ORDER # 108.1 4.25 52.4 2.06 19.3 0.76 69.9 2.75 **56.5 2.22 52.4 2.06 18.7 0.73 28.6 1.13 33.3 1.31 PROCESS CONNECTION SIZE 1/4 NPTM SHOWN 26.1 1.03 CLEARANCE SLOTS FOR HOUSING GROUP ** DIMENSION NN & N3 SHOWN 63.5 MIN 2.5 76.2 TO MAX MOUNTING HOLES 3.00 HARDWARE WITH 1/4 NPTF 1/2 NPTF 5.6 0.22 25.4 ADD 1.00 1 NPTM SEE DETAIL 6.4 0.25 63.5 MIN 2.5 76.2 TO MAX MOUNTING HOLES 3.00 2.31 ISO-9001 HARDWARE WITH DRAWN BY PRODUCT CERTIFICATION DRAWING ALL DIMENSIONS ARE ±1/16 IN UNLESS OTHERWISE SPECIFIED MM LINEAR = IN 14685 W 105TH ST LEN 913-888SORINC.C CLEARANCE SLOTS FOR 14685 W 105TH ST LENEXA, KS 66215 USA 913-888-2630 *58.7 SORINC.COM 7.1 0.28 PROCESS CONNECTION SIZE 40.5 1.59 ADD ISO-9001 1/4 OR 1/2 NPTM PROCESS CONNECTION OPTIONAL N4 PP & P3 SHOWN 2 NPTF SEE DETAIL K MITCHELL CHECKED BY J REHM PRODUCT CERTIFICATION DRAWIN ALL DIMENSIONS ARE ±1/16 IN UNLESS OTHERWISE SPECIFIED MM LINEAR = IN ENGINEER APPROVAL S BOAL DATE 10 OCT 2011 THIS DRAWING IS THE EXCLUSIVE PRO NO USE WHATSOEVER OF THE INFORMA HEREON, NOR REPRODUCTION IN WHOL MADE WITHOUT THE EXPRESS WRITTEN P THIS DRAWING IS THE EXCLUSIVE PROPERTY OF SOR. NO USE WHATSOEVER OF THE INFORMATION CONTAINED HEREON, NOR REPRODUCTION IN WHOLE OR PART MAY BE MADE WITHOUT THE EXPRESS WRITTEN PERMISSION OF SOR. A 1/4 NPTF FLUSHING PORT TITLE TITLE DIMENSION DRAWING 12/52 NN/N3/N4/PP/P3 DETAIL 2 NPTF PROCESS CONNECTION SCALE 0.38 EO NUMBER: 5123 SCALE: 0.75 DO NOT SCALE PRINT Model Name: 0090100.ASSEM/15/0+ DRAWING NUMBER Drawing 0090100 15 SHEET 1 OF 1 DIMENSION DRAWING 4/54 NN, N3, N4, PP & P3 1/4 OR 1/2 NPTM PROCESS CONNECTION OPTIONAL REV 0090100 Model Name: 0090110.ASSEM/12/1+ DWG SIZE PROCESS CONNECTION 7.1 0.28 B EO NUMBER: 5123 SCALE: 1.00 DO NOT SCALE PRINT Drawing 0090110 Designators: NN, N3, N4, PP, PF, P3 Piston Numbers 12, 52 Housings PP, P3 and PF are General Purpose. (Cover gasket is not installed.) MODEL # SALES ORDER # Reset Form Designators: NN, N3, N4, PP, PF, P3 Piston Numbers 4, 54 Housings PP, P3 and PF are General Purpose. (Cover gasket is not installed.) 1 SALES PAGE LINE ITEM # PURCHASE ORDER # 108.1 4.25 52.4 2.06 **56.5 2.22 69.9 2.75 PROCESS CONNECTION SIZE 1/4 NPTM SHOWN 28.6 1.13 33.3 1.31 26.1 1.03 NN & N3 ELECTRICAL CONNECTION 3/4 NPTF STD 1/2 NPTF OPT M20 X 1.5 F OPT (BOTH SIDES ON N3 & P3 HSGS) N4 PROCESS CONN SIZE 1/2 NPTF 9/16 SAE 3/4 NPTM 13.5 7.1 X 0.53 0.28 MOUNTING SLOTS 2X 7.1 0.28 ISO-9001 ** DIMENSION SHOWN 4.6 0.18 1.5 0.06 * LENGTH * LENGTH 1, 5, 6, 9, 56 2, 3 14.0 SHOWN ADD 0.55 24.1 13.2 ADD ADD 0.95 0.52 14.0 N/A ADD 0.55 23.1 ADD N/A 0.91 SUBTRACT 1/4 NPTF *54.7 2.15 29.7 1.17 38.9 1.53 ADD PP & P3 40.5 1.59 *146.8 5.78 LENGTH A 1/2 NPTM HOUSING GROUP 14685 W 105TH ST LENEXA, KS 66215 USA 913-888-2630 SORINC.COM DRAWN BY PRODUCT CERTIFICATION DRAWING ALL DIMENSIONS ARE ±1/16 IN UNLESS OTHERWISE SPECIFIED MM LINEAR = IN K MITCHELL CHECKED BY J REHM ENGINEER APPROVAL S BOAL DATE 21 JAN 2013 THIS DRAWING IS THE EXCLUSIVE PROPERTY OF SOR. NO USE WHATSOEVER OF THE INFORMATION CONTAINED HEREON, NOR REPRODUCTION IN WHOLE OR PART MAY BE MADE WITHOUT THE EXPRESS WRITTEN PERMISSION OF SOR. A TITLE Drawing 0090120 1/4 OR 1/2 NPTM PROCESS CONNECTION OPTIONAL Designators: NN, N3, N4, PP, PF, P3 Piston Numbers 5, 6, 1, 9, 56 Housing PP, P3 and PF are General Purpose. (Cover gasket is not installed.) Model Name: 0090120.ASSEM/22/0+ DIMENSION DRAWING 1/2/3/5/6/9/56 NN/N3/N4/PP/P3 PROCESS CONNECTION EO NUMBER: 5195 SCALE: 1.00 DO NOT SCALE PRINT DRAWING NUMBER REV 0090120 22 SHEET 1 OF 1 DWG SIZE B Reset Form *Refer to Dimensions table on page 19 for changes in length due to process connection size, including A dimension. **Contact the factory for certified drawings. Form 216 (01.16) ©SOR Inc. * NN & N3 SHOWN 1 NPTF PROCESS CONNECTION A HOUSING GROUP ELECTRICAL CONNECTION 3/4 NPTF STD 1/2 NPTF OPT M20 X 1.5 F OPT (BOTH SIDES ON N3 & P3 HSGS) * LENGTH 1/4 NPTF *150.9 5.94 1/2 NPTF 6.4 0.25 1/2 NPTM DETAIL 1 NPTM PROCESS CONNECTION SCALE 0.3 4.6 0.18 1.5 SUBTRACT 0.06 PROCESS CONNECTION SIZE PROCESS CONNECTION SIZE 1/4 NPTM SHOWN 26.1 1.03 ADD PP & P3 40.5 1.59 28.6 1.13 33.3 1.31 29.7 1.17 38.9 1.53 N4 *149.5 5.89 **56.5 2.22 69.9 2.75 LENGTH A 1/2 NPTM ELECTRICAL CONNECTION 3/4 NPTF STD 1/2 NPTF OPT M20 X 1.5 F OPT (BOTH SIDES ON N3 & P3 HSGS) *57.4 2.26 SALES ORDER # 1 SALES PAGE PURCHASE ORDER # 108.1 4.25 SORInc.com | 913-888-2630 | Registered Quality System to ISO 9001 21/32 DRAWING NUMBE 009 SHEET Pressure and Vacuum Switches Dimensions Dimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certified drawings for a particular model number. 1 SALES PAGE MODEL # SALES ORDER # LINE ITEM # PURCHASE ORDER # Weatherproof - NEMA 4, 4X, IP66 107.3 4.22 MODEL # 52.0 2.05 10.1 0.40 69.9 2.75 65.6 2.58 18.7 0.74 69.9 RL 2.75 26.2 1.03 ELECTRICAL CONNECTION SEE CHART 1/4 NPTF FLUSHING PORT DETAIL 2 NPTF *175.9 PROCESS CONNECTION 6.92 SCALE 0.5 *174.5 6.87 40.5 1.59 CLEARANCE SLOTS 6.4 FOR HARDWARE 0.25 *58.7 2.31 63.5 MIN 2.50 76.2 TO MAX 3.00 WITH *57.4 2.26 1/4 OR 1/2 NPTM PROCESS CONNECTION OPTIONAL 1/4 NPTF A SHOWN 1/2 NPTF SHOWN Model Name: 0090247.ASSEM/4/2+ Drawing 0090247 7.1 0.28 RM M20 X 1.5 F RH ONLY RN 3/4 NPTF STD 1/2 NPTF OPT RH ONLY RS M20 X 1.5 F RH ONLY RT 3/4 NPTF STD 1/2 NPTF OPT RH ONLY RU 3/4 NPTF STD 1/2 NPTF OPT LH & RH 26.2 1.03 40.5 1.59 M20 X 1.5 F CLEARANCE SLOTS LH & RH 6.4 RY M20 X 1.5 F 63.5 LH & RH WITH 2.5 MIN FOR 0.25 28.6 1.13 71.4 2.81 RN, RT, RM, RS 3/4” NPT(F) M20 x 1.5 Designators: RM, RN, RS, RT Piston Numbers 12, 52 95.3 3.75 7.1 0.28 DRAWN BY 5.6 0.22 25.4 ADD 1.00 71.4 2.81 PROCESS CONNECTION 1/4 OR 1/2 NPTM K MITCHELL CHECKED BY PROCESS CONNECTION OPTIONAL M SMITH ENGINEER APPROVAL S BOAL DATE 03 JUN 2011 THIS DRAWING IS THE EXCLUSIVE PROPERTY OF SOR. 133.4 OF THE INFORMATION CONTAINED NO USE WHATSOEVER HEREON, NOR5.25 REPRODUCTION IN WHOLE OR PART MAY BE MADE WITHOUT THE EXPRESS WRITTEN PERMISSION OF SOR. 0.31 MOUNTING HARDWARE 29.7 EO NUMBER: 5090 1.17 SCALE: 0.75 38.9 1/2 NPTM Model Name: 0090246.ASSEM/9/0 DO NOT SCALE PRINT 1.53 DRAWING NUMBER REV 0090247 6 DWG SIZE SHEET 1 OF 1 * LENGTH 1/4 NPTF 1/2 NPTF SHOWN 1 NPTM R-SERIES 1/4 NPTM SHOWN PROCESS CONN SIZE B Reset Form Drawing 0090246 ADD PROCESS CONN SIZE 1/4 NPTM SHOWN Housing Electrical Connection RN, RT, RM, RS 3/4” NPT(F) M20 x 1.5 LINE ITEM # 52.0 2.05 65.6 2.58 1 50.8 2.00 33.3 1.31 29.7 1.17 38.9 1.53 ELECTRICAL CONNECTION SEE CHART *171.8 6.76 PIPE KIT MOUNTING BRACKET OPTIONAL 40.5 1.59 95.3 3.75 71.4 2.81 28.6 1.13 *54.7 2.15 7.1 0.28 PROCESS CONN SIZE * LENGTH 1, 5, 6, 9, 56 1/4 NPTF PROCESS CONNECTION A1 1/2 NPTF SHOWN ADD 9/16 SAE 37.3 1.47 71.4 2.81 9.7 0.31 MOUNTING HARDWARE 133.4 5.25 CLEARANCE FOR 1/4 OR 1/2 NPTM PROCESS CONNECTION OPTIONAL 6.4 0.25 63.5 HARDWARE WITH MIN 2.5 76.2 TO MAX MOUNTING HOLES 3.00 CLEARANCE SLOTS FOR 3/4 NPTM PROCESS CONN SIZE 1/4 NPTM SHOWN 1/2 NPTM 13.2 0.52 N/A ADD 1 * LENGTH 2, 3 14.0 ADD 0.55 24.1 ADD 0.95 14.0 ADD 0.55 23.1 0.91 29.7 1.17 38.9 1.53 Housing ELECTRICAL CONNECTION RL 3/4 NPTF STD 1/2 NPTF OPT LH & RH RM M20 X 1.5 F RH ONLY RN 3/4 NPTF STD 1/2 NPTF OPT RH ONLY RS M20 X 1.5 F RH ONLY RT 3/4 NPTF STD 1/2 NPTF OPT RH ONLY RU 3/4 NPTF STD 1/2 NPTF OPT LH & RH RW M20 X 1.5 F LH & RH RY M20 X 1.5 F LH & RH 1 Designators: RM, RN, RS, RT Piston Numbers 5, 6, 1, 9, 56 Registered Quality System to ISO 9001 | 913-888-2630 | SORInc.com M SMITH ENGINEER APPROVAL S BOAL DATE TITLE DIM DWG 1, 2, 3, 5, 6, 9 & 56 R - SERIES W/PIPE KIT OPTION SCALE: 0.75 DO NOT SCALE PRINT DRAWING NUMBER REV 0090245 8 SHEET 1 OF 1 3/4” NPT(F) M20 x 1.5 *Refer to Dimensions table on page 19 for changes in length due to process connection size, including A dimension. 22/32 CHECKED BY 06 JUN 2011 Model Name: 0090245.ASSEM/6/5+ RN, RT, RM, RS K MITCHELL THIS DRAWING IS THE EXCLUSIVE PROPERTY OF SOR. NO USE WHATSOEVER OF THE INFORMATION CONTAINED HEREON, NOR REPRODUCTION IN WHOLE OR PART MAY BE MADE WITHOUT THE EXPRESS WRITTEN PERMISSION OF SOR. EO NUMBER: 5090 Form 216 (01.16) ©SOR Inc. RW M20 X LH & RY M20 X LH & DO NOT SCALE PRINT DRAWN BY Electrical Connection 3/4 NPT 1/2 NPT LH & SCALE: 0.69 14685 W 105TH ST LENEXA, KS 66215 USA 913-888-2630 SORINC.COM ISO-9001 N/A LENGTH A HOUSING PRODUCT CERTIFICATION DRAWING ALL DIMENSIONS ARE ±1/16 IN UNLESS OTHERWISE SPECIFIED MM LINEAR = IN RU EO NUMBER: 5123 1. DIMENSION APPROXIMATE AND BASED ON A FIVE THREAD ENGAGEMENT 26.2 1.03 M20 X RH O 3/4 NPT 1/2 NPT RH O DIMENSION DRAWING 4/54 R - SERIES W/PIPE KIT OPTION PURCHASE ORDER # 28.6 1.12 RS RT TITLE NOTES: 69.9 2.75 3/4 NPT 1/2 NPT RH O THIS DRAWING IS THE EXCLUSIVE PROPERTY NO USE WHATSOEVER OF THE INFORMATION HEREON, NOR REPRODUCTION IN WHOLE OR P MADE WITHOUT THE EXPRESS WRITTEN PERMIS 46.0 1.81 SALES PAGE SALES ORDER # M20 X RH O RN PRODUCT CERTIFICATION DRAWING ALL DIMENSIONS ARE ±1/16 IN UNLESS OTHERWISE SPECIFIED MM LINEAR = IN LENGTH A 1/2 NPTM 107.3 4.22 RM 14685 W 105TH ST LENEXA, 913-888-2630 SORINC.COM ISO-9001 PIPE KIT OPTIONAL Designators: RM, RN, RS, RT Piston Numbers 4, 54 MODEL # Drawing 0090245 3/4 NPT 1/2 NPT LH & HARDWARE TITLE Housing ELECTR CONNE RL 50.8 2.00 LENGTH A CLEARANCEDIM 9.7 DWG #12/52 FOR Electrical Connection HOUSING DETAIL 1 NPTM PROCESS CONNECTION SCALE 0.3 ELECTRICAL CONNECTION SEE CHART RW PRODUCT CERTIFICATION DRAWING ALL DIMENSIONS ARE ±1/16 IN UNLESS OTHERWISE SPECIFIED 37.2 MM 1.47 LINEAR = IN ADD 2 NPTF SEE DETAIL PROCESS CONNECTION 28.6 1.12 3/4 NPTF STD 1/2 NPTF OPT LH & RH MAX 14685 W 105TH ST LENEXA, KS 66215TOUSA 3.00 913-888-2630 MOUNTING HOLES SORINC.COM ISO-9001 * LENGTH 1 NPTF A 33.3 1.31 PURCHASE ORDER # 65.6 2.58 76.2 PROCESS CONN SIZE MOUNTING CENTERS LINE ITEM # ELECTRICAL 52.0 CONNECTION 2.05 28.6 1.12 33.3 1.31 SALE SALES ORDER # 107.3 4.22 HOUSING DWG SIZE B Reset Form DRAWING NUMBER 0090246 SHEET 1 O Pressure and Vacuum Switches Dimensions Dimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certified drawings for a particular model number. Open Bracket Drawing 0090007 Drawing 0090017 Designators: H3 Piston Numbers 12, 52 Designators: H3 Piston Numbers 4, 54 Drawing 0090027 Designators: H3 Piston Numbers 5, 6, 9, 1, 56 *Refer to Dimensions table on page 19 for changes in length due to process connection size, including A dimension. Form 216 (01.16) ©SOR Inc. SORInc.com | 913-888-2630 | Registered Quality System to ISO 9001 23/32 Pressure and Vacuum Switches Dimensions Dimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certified drawings for a particular model number. Weatherproof - NEMA 4, 4X, IP66 Drawing 0090009 Drawing 0090010 Designators: N6 Piston Numbers 12, 52 Designators: N6 Piston Numbers 4, 54 Drawing 0090020 Designators: N6 Piston Numbers 5, 6, 9, 1, 56 *Refer to Dimensions table on page 19 for changes in length due to process connection size, including A dimension. 24/32 Registered Quality System to ISO 9001 | 913-888-2630 | SORInc.com Form 216 (01.16) ©SOR Inc. Pressure and Vacuum Switches Dimensions Dimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certified drawings for a particular model number. Conventional Explosion Proof MODEL # SALES ORDER # SALES ORDER # LINE ITEM # PURCHASE ORDER # 20.6 0.81 71.1 2.80 137.3 5.41 20.6 0.81 71.1 2.80 *115.3 4.54 227.2 8.94 161.1 6.34 80.8 3.18 TYP 120.7 4.75 40.4 1.59 TYP *181.5 7.15 1/4 NPTF FLUSHING PORT *115.3 DETAIL 2 NPTF 4.54PROCESS CONNECTION SCALE 0.5 CLEARANCE 6.4 FOR 0.25 MOUNTING HARDWARE *74.9 2.95 6.4 0.25 6.4 0.25 80.8 3.18 40.4 TYP 1.59 TYP *181.5 7.15 ELECTRICAL CONNECTION 3/4 NPTF STD 1/2 NPTF OPT 26.6 1.05 ELECTRICAL CONNECTION 3/4 NPTF STD 1/2 NPTF OPT PURCHASE ORDER # 86.1 3.39 105.9 4.17 137.3 5.41 LINE ITEM # 1 SALES PAGE MODEL # *74.9 2.95 14685 W 105TH 91 SO HARDWARE ISO-9001 14685 W 105TH ST LENEXA, KS 66215 USA 913-888-2630 SORINC.COM PROCESS CONN SIZE ISO-9001 A 1/4 OR 1/2 NPT MALE PROCESS CONNECTION OPTIONAL PROCESS CONN SIZE * LENGTH 1/4 NPTF 1/2 NPTF SHOWN PROCESS CONNECTION 1 NPTM 2 NPTF SEE DETAIL 5.6 0.22 25.4 ADD 1.00 1/4 NPTM SHOWN Drawing 0090146 1/2 NPTM DRAWN BY PRODUCT CERTIFICATION DRAWING ALL DIMENSIONS ARE ±1/16 IN SPECIFIED AUNLESS OTHERWISEMM LINEAR = IN ADD 29.7 1.17 38.9 1.53 Model Name: 0090146.ASSEM/6/3+ CHECKED BY J REHM ENGINEER APPROVAL PROCESS CONNECTION S ROOS DATE SHOWN 1 NPTM 16 MAY 2012 ADD 1/4 NPTM SHOWN 1/4 NPTM OR 1/2 NPTM PROCESS CONNECTION OPTIONAL Drawing 0090145 Model Name: 0090145.ASSEM/6/0+ EO NUMBER: 5123 SCALE: 0.75 DO NOT SCALE PRINT DRAWING NUMBER THIS DRAWING IS THE EXCLU NO USE WHATSOEVER OF THE I HEREON, NOR REPRODUCTION I MADE WITHOUT THE EXPRESS W TITLE 29.7 1.17 38.9 1.53 1/2 NPTM PRODUCT CERTIFICATION DR ALL DIMENSIONS ARE ±1 UNLESS OTHERWISE SPEC MM LINEAR = IN 46.0 1.81 LENGTH A THIS DRAWING IS THE EXCLUSIVE PROPERTY OF SOR. NO USE WHATSOEVER OF THE INFORMATION CONTAINED HEREON, NOR REPRODUCTION IN WHOLE OR PART MAY BE MADE WITHOUT THE EXPRESS WRITTEN PERMISSION OF SOR. DIMENSION DRAWING 12/52 L * LENGTH 1/4 NPTF 1/2 NPTF K MITCHELL TITLE LENGTH A DETA 1 NPT PROCESS CON SCALE 6.7 0.26 CLEARANCE 6.4 FOR MOUNTING 0.25 DIM DWG 4/54 L EO NUMBER: 5123 SCALE: 0.88 DO NOT SCALE PRINT REV 0090146 8 SHEET 1 OF 1 DWG SIZE B Reset Form Designators: L Piston Numbers 4, 54 Designators: L Piston Numbers 12, 52 1 SALES PAGE MODEL # SALES ORDER # LINE ITEM # PURCHASE ORDER # PROCESS CONN SIZE 137.3 5.41 79.4 3.12 133.4 5.25 1/4 NPTF 50.8 2.00 1/2 NPTF 20.7 0.81 71.1 2.80 ELECTRICAL CONNECTION 3/4 NPTF STD 1/2 NPTF OPT 9/16 SAE 6.4 0.25 3/4 NPTM PROCESS CONN SIZE 1/4 NPTM SHOWN PIPE KIT MOUNTING BRACKET OPTIONAL 80.8 3.18 40.4 TYP 1.59 TYP *178.8 7.04 71.4 2.81 *112.6 4.43 13.2 0.52 N/A ADD 23.1 0.91 N/A LENGTH A 29.7 1.17 38.9 1.53 95.3 3.75 ISO-9001 CLEARANCE 7.9 FOR 0.31 MOUNTING HARDWARE 71.4 2.81 SHOWN ADD * LENGTH 2, 3 14.0 ADD 0.55 24.1 ADD 0.95 14.0 ADD 0.55 28.6 1.13 CLEARANCE 6.4 FOR 0.25 MOUNTING HARDWARE *72.2 2.84 1/2 NPTM * LENGTH 1, 5, 6, 9, 56 11.9 0.47 14685 W 105TH ST LENEXA, KS 66215 USA 913-888-2630 SORINC.COM DRAWN BY PRODUCT CERTIFICATION DRAWING ALL DIMENSIONS ARE ±1/16 IN UNLESS OTHERWISE SPECIFIED MM LINEAR = IN A K MITCHELL CHECKED BY J REHM ENGINEER APPROVAL S BOAL DATE 12 OCT 2012 1/4 OR 1/2 NPTM PROCESS CONNECTION OPTIONAL Drawing 0090144 PROCESS CONNECTION THIS DRAWING IS THE EXCLUSIVE PROPERTY OF SOR. NO USE WHATSOEVER OF THE INFORMATION CONTAINED HEREON, NOR REPRODUCTION IN WHOLE OR PART MAY BE MADE WITHOUT THE EXPRESS WRITTEN PERMISSION OF SOR. TITLE DIMENSION DRAWING 1/2/3/5/6/9/56 L HOUSING W/PIPE KIT OPTION EO NUMBER: 5166 SCALE: 0.80 Designators: L Piston Numbers 5, 6, 9, 1, 56 DO NOT SCALE PRINT DRAWING NUMBER REV 0090144 10 SHEET 1 OF 1 Model Name: 0090144.ASSEM/10/0+ DWG SIZE B Reset Form *Refer to Dimensions table on page 19 for changes in length due to process connection size, including A dimension. Form 216 (01.16) ©SOR Inc. SORInc.com | 913-888-2630 | Registered Quality System to ISO 9001 25/32 DRAWI S Pressure and Vacuum Switches Dimensions Dimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certified drawings for a particular model number. Conventional Explosion Proof 1 SALES PAGE MODEL # SALES ORDER # 142.3 5.60 LINE ITEM # PURCHASE ORDER # 20.6 0.81 71.1 2.80 6.4 0.25 ELECT CONN 3/4 NPTF(STD) 1/2 NPTF(OPT) OR PLUGGED(OPT) (TYP 3) 80.8 3.18 (TYP) *186.5 7.34 40.4 1.59 (TYP) *115.3 4.54 1/4 NPTF FLUSHING PORT 26.6 1.05 DETAIL 2"NPTF PROCESS CONNECTION SCALE 0.5 CLEARANCE 6.4 FOR MOUNTING 0.25 *74.9 2.95 HARDWARE 1/4 OR 1/2 NPT MALE PROCESS CONNECTION (OPTIONAL) LENGTH A 1/4 NPT(M) = 1/2 NPT(M) = ISO-9001 PROCESS CONNECTION A 14685 W 105TH ST LENEXA, KS 66215 USA 913-888-2630 SORINC.COM DRAWN BY 106.0 4.17 29.7 (SHOWN) 1.17 38.9 1.53 PRODUCT CERTIFICATION DRAWING ALL DIMENSIONS ARE ± 1/16 IN UNLESS OTHERWISE SPECIFIED MM LINEAR = IN PROCESS CONN SIZE 1/4 NPT(F) 1/2 NPT(F) 1 NPT(F) Drawing 0090149 2 NPT(F) SEE DETAIL J FIXSEN CHECKED BY M SMITH ENGINEER APPROVAL S BOAL DATE 05-05-04 * LENGTH SHOWN ADD 5.6 0.22 25.4 ADD 1.00 THIS DRAWING IS THE EXCLUSIVE PROPERTY OF SOR. NO USE WHATSOEVER OF THE INFORMATION CONTAINED HEREON, NOR REPRODUCTION IN WHOLE OR PART MAY BE MADE WITHOUT THE EXPRESS WRITTEN PERMISSION OF SOR. TITLE DIM DWG #12/52 S EO NUMBER: 4596 DRAWING NUMBER REV Drawing 0090148 SCALE: 0.75 DO NOT SCALE PRINT Model Name: 0090149.ASSEM/5/3+ 0090149 6 SHEET 1 OF 1 DWG SIZE B Reset Form Designators: S Piston Numbers 4, 54 Designators: S Piston Numbers 12, 52 MODEL # SALES ORDER # LINE ITEM # 79.4 3.12 142.3 5.60 71.1 2.80 CLEARANCE 6.4 FOR MOUNTING 0.25 PURCHASE ORDER # 50.8 2.00 PROCESS CONN SIZE * LENGTH 1, 5, 6, 9, 5 1/4 NPTF SHOWN 1/2 NPTF 20.6 0.81 9/16 SAE 6.4 0.25 3/4 NPTM PROCESS CONN SIZE 1/4 NPTM SHOWN ELECT CONN 3/4 NPTF(STD) 1/2 NPTF(OPT) OR PLUGGED(OPT) (TYP 3) HARDWARE ADD 13.2 0.52 SHOWN ADD 23.1 0.91 LE 1/2 NPTM 80.8 3.18 (TYP) 40.4 1.59 (TYP) *183.8 7.23 40.4 1.59 71.4 2.81 95.3 3.75 28.6 1.13 *112.6 4.43 *72.2 2.84 PIPE KIT MOUNTING BRACKET OPTIONAL A PROCESS CONNECTION Drawing 0090147 35.0 1.38 Designators: S Piston Numbers 5, 6, 9, 1, 56 1/4 OR 1/2 NPTM PROCESS CONNECTION (OPTIONAL) THIS DRAWING IS THE EXCLUSIVE PR NO USE WHATSOEVER OF THE INFORM HEREON, NOR REPRODUCTION IN WHO MADE WITHOUT THE EXPRESS WRITTEN P 133.4 5.25 TITLE DIMENSION DRAWING 1/2/3/5/6/9/56 W/PK EO NUMBER: 5195 Model Name: 0090147.ASSEM/7/0+ Registered Quality System to ISO 9001 14685 W 105TH ST LE 913-88 SORINC PRODUCT CERTIFICATION DRAWIN ALL DIMENSIONS ARE ±1/16 IN UNLESS OTHERWISE SPECIFIED MM LINEAR = IN 71.4 2.81 *Refer to Dimensions table on page 19 for changes in length due to process connection size, including A dimension. 26/32 ISO-9001 | 913-888-2630 | SORInc.com Form 216 (01.16) ©SOR Inc. SCALE: 0.63 DO NOT SCALE PRINT DRAWING NUMB 009 SHEET Pressure and Vacuum Switches Dimensions Dimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certified drawings for a particular model number. Conventional Explosion Proof MODEL # SALES ORDER # LINE ITEM # 149.5 MIN 5.88 106.2 4.18 133.4 5.25 50.8 2.00 ELECTRICAL CONNECTION 3/4 NPTF STD 1/2 NPTF OPT 71.4 MIN 2.81 PROCESS CONNECTION SIZE 1/4 NPTM SHOWN 34.0 1.34 SHOWN SHOWN 1/2 NPTF SHOWN SHOWN 1 NPTF ADD ADD 19.8 0.78 25.4 1.00 ADD ADD 71.4 MIN 2.81 *121.7 4.79 5.6 0.22 25.4 1.00 54.0 2.13 TYP ISO-9001 71.4 2.81 *67.7 DRAWN BY 2.67 K MITCHELL CHECKED BY ISO-9001 DATE PROCESS CONNECTION A PRODUCT CERTIFICATION DRAWING ALL DIMENSIONS ARE ±1/16 IN UNLESS OTHERWISE SPECIFIED MM LINEAR = IN CLEARANCE 7.9 FOR 0.31 MOUNTING HARDWARE S ROOS EO NUMBER: 5195 SCALE: 0.75 0090399 DWG SIZE B EO NUMBER: 5195 Model Name: 0090456_1NPTM.ASSEM/4/0+ SC shown. LC identical except right-hand electrical connection only. LINE ITEM # PROCESS CONNECTION SIZE 1/4 NPTM SHOWN PROCESS CONN SIZE 8.7 0.34 1/4 NPTF * LENGTH 2, 3 14.0 ADD 0.55 24.1 ADD 0.95 SHOWN ADD 1/2 NPTM ADD 3/4 NPTM 108.0 4.25 TYP 29.7 1.17 38.9 1.53 * LENGTH 1, 5, 6, 9, 56 1/2 NPTF 9/16 SAE 54.0 2.13 TYP *200.2 7.88 LENGTH A 1/2 NPTM 34.0 1.34 71.4 MIN 2.81 1 SALES PAGE PURCHASE ORDER # 106.2 4.18 149.5 MIN 5.88 13.2 0.52 23.1 0.91 N/A SHOWN ADD ADD 23.1 0.91 14.0 0.55 N/A ELECTRICAL CONNECTION 3/4 NPTF STD 1/2 NPTF OPT SCALE 0.25 *119.0 4.68 CLEARANCE 6.4 FOR 0.25 MOUNTING HARDWARE *65.0 2.56 ISO-9001 14685 W 105TH ST LENEXA, KS 66215 USA 913-888-2630 SORINC.COM DRAWN BY PRODUCT CERTIFICATION DRAWING ALL DIMENSIONS ARE ±1/16 IN UNLESS OTHERWISE SPECIFIED MM LINEAR = IN K MITCHELL CHECKED BY M SMITH ENGINEER APPROVAL S ROOS DATE 19 NOV 2012 A THIS DRAWING IS THE EXCLUSIVE PROPERTY OF SOR. NO USE WHATSOEVER OF THE INFORMATION CONTAINED HEREON, NOR REPRODUCTION IN WHOLE OR PART MAY BE MADE WITHOUT THE EXPRESS WRITTEN PERMISSION OF SOR. TITLE Drawing 0090408 1/4 OR 1/2 NPTM PROCESS CONNECTION OPTIONAL PROCESS CONNECTION DIMENSION DRAWING 1/2/3/5/6/9/56 LC W/HEX NIPPLE OPTION EO NUMBER: 5195 SCALE: 0.75 DO NOT SCALE PRINT DRAWING NUMBER REV 0090408 10 SHEET 1 OF 1 Designators: LC SC Piston Numbers 5, 6, 9, 1, 56 SC shown. LC identical except right-hand electrical connection only. Model Name: 0090408.ASSEM/***/*** DWG SIZE B Reset Form *Refer to Dimensions table on page 19 for changes in length due to process connection size, including A dimension. Form 216 (01.16) ©SOR Inc. SORInc.com 0090456 SHEET 1 OF 1 Res Drawing 0090456 Designators: LC SC Piston Numbers 4, 54 SALES ORDER # DATE DRAWING NUMBER SCALE: 0.25 DO NOT SCALE PRINT Designators: LC SC Piston Numbers 12, 52 SC shown. LC identical except right-hand electrical connection only. S ROOS DIMENSION DRAWING 4/54 LC W/HEX NIPPLE & PIPE KIT OPTIONS SCALE 0.25 Reset Form Drawing 0090399 ENGINEER A TITLE 1/4 OR 1/2 NPTM PROCESS CONNECTION OPTIONAL 5 SHEET 1 OF 1 DO NOT SCALE PRINT Model Name: 0090399.ASSEM/4/0+ CHECKED BY M SMIT 19 NO DIMENSION DRAWING 12/52 LC W/ HEX NIPPLE & PIPE KIT OPTIONS REV K MITC THIS DRAWING IS THE EXCLUSIVE PROPERTY OF SOR NO USE WHATSOEVER OF THE INFORMATION CONTAIN HEREON, NOR REPRODUCTION IN WHOLE OR PART MA MADE WITHOUT THE EXPRESS WRITTEN PERMISSION OF TITLE DRAWING NUMBER 14685 W 105TH ST LENEXA, KS 662 913-888-2630 SORINC.COM DRAWN BY M SMITH ENGINEER APPROVAL THIS DRAWING IS THE EXCLUSIVE PROPERTY OF SOR. NO USE WHATSOEVER OF THE INFORMATION CONTAINED HEREON, NOR REPRODUCTION IN WHOLE OR PART MAY BE MADE WITHOUT THE EXPRESS WRITTEN PERMISSION OF SOR. MODEL # 29 1. 38 1. DETAIL 1 NPTM SCALE 0.25 28.6 1.13 CLEARANCE 6.4 FOR 0.25 MOUNTING HARDWARE 14685 W 105TH ST LENEXA, KS 66215 USA 913-888-2630 SORINC.COM 19 NOV 2012 119.4 4.70 LENG PIPE KIT OPTIONAL *121.7 4.79 94.5 3.72 ADD 108.0 4.25 TYP PRODUCT CERTIFICATION DRAWING ALL DIMENSIONS ARE ±1/16 IN UNLESS OTHERWISE SPECIFIED MM LINEAR = IN 1/4 OR 1/2 NPTM PROCESS CONNECTION OPTIONAL SHO 1 NPTM PROCESS CONN SIZE 1/4 NPTM SHOWN SCALE 0.25 CLEARANCE 7.9 FOR 0.31 MOUNTING HARDWARE PROCESS CONNECTION A 8.7 0.34 * LEN 1/4 NPTF 1/2 NPTF 95.3 3.75 28.6 1.13 CLEARANCE 6.4 FOR 0.25 MOUNTING HARDWARE *67.7 2.67 34.0 1.34 1/2 NPTM *202.9 7.99 95.3 3.75 71.4 2.81 PROCESS CONN SIZE 50.8 2.00 ELECTRICAL CONNECTION 3/4 NPTF STD 1/2 NPTF OPT 108.0 4.25 TYP *202.9 7.99 PURCHASE ORDER # 106.2 4.18 133.4 5.25 1/4 NPTF 2 NPTF LINE ITEM # 149.5 MIN 5.88 29.7 1.17 38.9 1.53 PROCESS * LENGTH * LENGTH CONN SIZE BRASS & ALUM ALL OTHER PIPE KIT MOUNTING BRACKET OPTIONAL 54.0 2.13 TYP SALES ORDER # LENGTH A 1/2 NPTM 8.7 0.34 SALES PAGE 1 SALES PAGE MODEL # PURCHASE ORDER # | 913-888-2630 | Registered Quality System to ISO 9001 27/32 Pressure and Vacuum Switches Dimensions Dimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certified drawings for a particular model number. Conventional Explosion Proof 1 SALES PAGE MODEL # SALES ORDER # LINE ITEM # PURCHASE ORDER # MODEL # * LENGTH 1/4 NPTF SHOWN 1/2 NPTF SHOWN 141.3 5.56 70.6 2.78 2X 78.5 3.09 88.9 3.50 CLEARANCE 6.4 FOR 0.25 MOUNTING HARDWARE 39.1 1.54 SALES PA PROCESS CONN SIZE 5.6 0.22 25.4 ADD 1.00 1 NPTF 25.0 0.98 70.6 2.78 2X 78.5 3.09 39.1 1.54 LENGTH A 1/4 NPTM SHOWN 3X ELECTRICAL CONNECTION 3/4 NPTF STD 1/2 NPTF OPT OR PLUGGED OPT 29.7 1.17 38.9 1.53 1/2 NPTM 9.8 0.39 *184.9 7.28 *183.6 1/4 NPTF7.23 FLUSHING PORT LINE ITEM # CLEARANCE 6.4 FOR 0.25 MOUNTING HARDWARE 88.9 3.50 22.2 0.88 14685 W 105TH ST LENEXA, KS 66 913-888-2630 SORINC.COM DRAWN CHECKED BY PRODUCT CERTIFICATION DRAWING ALL DIMENSIONS ARE ±1/16 IN UNLESS OTHERWISE SPECIFIED MM LINEAR = IN M SMITH ENGINEER APPROVAL S BOAL DATE DIM DWG 12 & 52 TA EO NUMBER: 5090 SCALE: 0.75 DO NOT SCALE PRINT Model Name: 0090155.ASSEM/6/3+ Model Name: 0090154.ASSEM/6/3+ DRAWING NUMBER REV 0090155 7 SHEET 1 OF 1 1/4 OR 1/2 NPTM PROCESS CONNECTION OPTIONAL PROCESS CONNECTION ENGINEE S BOA DATE DIM DWG - 4 & 54 TA SCALE: 0.75 B DO NOT SCALE PRINT Reset Form DRAWING NUMBER 0090154 SHEET 1 OF 1 Re Drawing 0090154 Designators: TA Piston Numbers 12, 52 Designators: TA Piston Numbers 4, 54 Designators: TA Piston Numbers 5, 6, 9, 1, 56 *Refer to Dimensions table on page 19 for changes in length due to process connection size, including A dimension. | 913-888-2630 | SORInc.com M SM TITLE EO NUMBER: 5090 DWG SIZE Drawing 0090155 Registered Quality System to ISO 9001 CHECKED 07 J Drawing 0090153 28/32 K MIT THIS DRAWING IS THE EXCLUSIVE PROPERTY OF SO NO USE WHATSOEVER OF THE INFORMATION CONTA HEREON, NOR REPRODUCTION IN WHOLE OR PART M MADE WITHOUT THE EXPRESS WRITTEN PERMISSION O TITLE PROCESS CONNECTION 2 1 3 1 ISO-9001 K MITCHELL THIS DRAWING IS THE EXCLUSIVE PROPERTY OF SOR. NO USE WHATSOEVER OF THE INFORMATION CONTAINED HEREON, A NOR REPRODUCTION IN WHOLE OR PART MAY BE MADE WITHOUT THE EXPRESS WRITTEN PERMISSION OF SOR. 1/4 OR 1/2 NPTM PROCESS CONNECTION OPTIONAL ADD DETAIL 1 NP PROCESS CONNE SCALE 0.2 5.2 0.20 07 JUN 2011 A SH 1 NPTM SEE DETAIL 9.8 0.39 DRAWN BY *76.0 SH 1/2 NPTF LENGTH A DETAIL 2 NPTF PROCESS CONNECTION SCALE 0.25 PRODUCT CERTIFICATION 2.99 DRAWING ALL DIMENSIONS ARE ±1/16 IN UNLESS OTHERWISE SPECIFIED MM LINEAR = IN * LE 1/4 NPTF 1/2 NPTM 3X ELECTRICAL CONNECTION 3/4 NPTF STD 1/2 NPTF OPT OR PLUGGED OPT ISO-9001 *77.3 3.04 PROCESS CONN SIZE 1/4 NPTM SHOWN 14685 W 105TH ST LENEXA, KS 66215 USA *115.3 913-888-2630 4.54 SORINC.COM *116.7 4.59 PURCHASE ORDER # 141.3 5.56 ADD 2 NPTF SEE DETAIL 22.2 0.88 SALES ORDER # Form 216 (01.16) ©SOR Inc. Pressure and Vacuum Switches Dimensions Dimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certified drawings for a particular model number. Explosion Proof SALES PAGE MODEL # SALES ORDER # SALES PAGE MODEL # SALES ORDER # LINE ITEM # DIMENSION APPROXIMATE AND BASED ON A FIVE THREAD ENGAGEMENT 1 150.1 5.91 75.1 2.95 110.3 4.34 80.0 3.15 ELECTRICAL CONNECTION 3/4 NPTF STD 1/2 NPTF OPT LH & RH M20 X 1.5 F LH & RH 3/4 PFF RH ONLY HOUSING 11.9 0.47 35.3 1.39 B3 & B6 40.0 1.58 9.5 0.38 B4 & B5 J4 EXTERNAL GROUND LUG 2X 9.1 0.36 MOUNTING HOLES *227.7 8.96 33.4 1.32 1/4 NPTF VENT CONNECTION LH & RH *122.5 4.82 29.7 1.17 1/2 NPTM 38.9 1.53 110.3 4.34 50.8 2.00 35.3 1.39 B3 & B6 B4 & B5 9.5 0.38 J4 PIPE KIT MOUNTING BRACKET OPTIONAL EXTERNAL GROUND LUG * LENGTH 1/4 NPTF, BSPF, PTF SHOWN *227.7 1/2 NPTF, 8.96 BSPF, PTF SHOWN 1 NPTF, BSPF, PTF 5.6 ADD 0.22 2X 9.1 0.36 MOUNTING HOLES 35.7 DRAWN BY 1.41 K MITCHELL 26.6 1.05 71.4 2.81 ENGINEER APPROVAL M SMITH S BOAL DETAIL 2 NPTF PROCESS CONNECTION SCALE 0.25 EO NUMBER: 5248 SCALE: 0.69 DO NOT SCALE PRINT DRAWING NUMBER 11 SHEET 1 OF 1 Model Name: 0090284.ASSEM/11.3 EO NUMBER: 5248 DO NOT SCALE PRINT B Designators: B3, B4, B5, B6, J4 Piston Numbers 12, 52 Designators: B3, B4, B5, B6, J4 Piston Numbers 4, 54 1 SALES PAGE SALES ORDER # LINE ITEM # PURCHASE ORDER # DIMENSION APPROXIMATE AND BASED ON A FIVE THREAD ENGAGEMENT 1 PROCESS CONNECTION SIZE 1/4 NPTM SHOWN 150.1 5.91 75.1 2.95 110.3 4.34 40.0 1.58 PROCESS CONN SIZE 1/4 NPTF 1/4 BSPF 1/4 PTF 1/2 NPTF 1/2 BSPF 1/2 PTF 50.8 2.00 35.3 1.39 PIPE KIT MOUNTING BRACKET 7/16 - 20 SAE OPTIONAL 9/16 SAE EXTERNAL GROUND LUG 3/4 NPTM 3/4 BSPM 3/4 PTM 2X 9.1 0.36 MOUNTING HOLES 4X *119.9 4.72 9.5 0.38 MOUNTING HOLES 35.7 1.41 LENGTH A 29.7 1.17 38.9 1.53 1/2 NPTM 80.0 3.15 71.4 2.81 HOUSING B3 & B6 B4 & B5 J4 33.4 1.32 9.5 0.38 1/4 NPTF VENT CONNECTION LH & RH 71.4 2.81 95.3 3.75 28.6 1.13 ELECTRICAL CONNECTION SEE CHART 26.6 1.05 ISO-9001 * LENGTH 1, 5, 6, 9, 56 * LENGTH 2, 3 SHOWN ADD 14.0 0.55 13.2 ADD 0.52 ADD 24.1 0.95 SHOWN ADD SHOWN ADD ADD 23.1 0.91 14.0 0.55 14.0 0.55 N/A ELECTRICAL CONNECTION 3/4 NPTF STD 1/2 NPTF OPT LH & RH M20 X 1.5 F LH & RH 3/4 PFF RH ONLY 14685 W 105TH ST LENEXA, KS 66215 USA 913-888-2630 SORINC.COM DRAWN BY PRODUCT CERTIFICATION DRAWING ALL DIMENSIONS ARE 1/16 IN UNLESS OTHERWISE SPECIFIED MM LINEAR = IN K MITCHELL CHECKED BY M SMITH ENGINEER APPROVAL S BOAL DATE 05 JUN 2015 THIS DRAWING IS THE EXCLUSIVE PROPERTY OF SOR. NO USE WHATSOEVER OF THE INFORMATION CONTAINED HEREON, NOR REPRODUCTION IN WHOLE OR PART MAY BE MADE WITHOUT THE EXPRESS WRITTEN PERMISSION OF SOR. A1 TITLE 1/4 OR 1/2 NPTM PROCESS CONNECTION OPTIONAL Drawing 0090882 PROCESS CONNECTION DIMENSION DRAWING 1/2/3/5/6/9/56 B/J HOUSING W/PIPE KIT OPTION EO NUMBER: 5248 SCALE: 0.65 DO NOT SCALE PRINT Designators: B3, B4, B5, B6, J4 Piston Numbers 5, 6, 9, 1, 56 Model Name: 0090882.ASSEM/5.2 DRAWING NUMBER REV 0090882 6 SHEET 1 OF 1 DWG SIZE B Reset Form *Refer to Dimensions table on page 19 for changes in length due to process connection size, including A dimension. Form 216 (01.16) ©SOR Inc. SORInc.com 0090284 SHEET 1 OF 1 Rese Drawing 0090284 *225.0 8.86 S BOAL DATE DRAWING NUMBER SCALE: 0.69 DWG SIZE Drawing 0090297 41.2 1.62 ENGINEER APP DIMENSION DRAWING 4/45/46/54 B/J HOUSING WI PIPE KIT OPTION PROCESS CONNECTION Reset Form MODEL # M SMITH TITLE 1/4 OR 1/2 NPTM PROCECSS CONNECTION OPTIONAL REV 0090297 Model Name: 0090297.ASSEM/10.3 K MITCH CHECKED BY 01 JUN DIMENSION DRAWING 12/52/124/125/126 B/J HOUSING 1/4 NPTF FLUSHING PORT 14685 W 105TH ST LENEXA, KS 6621 913-888-2630 SORINC.COM THIS DRAWING IS THE EXCLUSIVE PROPERTY OF SOR. NO USE WHATSOEVER OF THE INFORMATION CONTAINED HEREON, NOR REPRODUCTION IN WHOLE OR PART MAY B MADE WITHOUT THE EXPRESS WRITTEN PERMISSION OF SO TITLE PROCESS CONNECTION SHOW DATE A1 1/4 OR 1/2 NPTM PROCESS CONNECTION OPTIONAL SHOW 1/2 NPTF, BSPF, PTF DRAWN BY THIS DRAWING IS THE EXCLUSIVE PROPERTY OF SOR. NO USE WHATSOEVER OF THE INFORMATION CONTAINED HEREON, NOR REPRODUCTION IN WHOLE OR PART MAY BE MADE WITHOUT THE EXPRESS WRITTEN PERMISSION OF SOR. 94.5 3.72 1/4 NPTF, BSPF, PTF PRODUCT CERTIFICATION DRAWING ALL DIMENSIONS ARE 1/16 IN UNLESS OTHERWISE SPECIFIED MM LINEAR = IN 01 JUN 2015 A 1 * LENG ISO-9001 1/4 NPTF VENT CONNECTION LH & RH CHECKED BY 38.9 1.53 PROCESS CONNECTION SIZE 33.4 1.32 9.5 0.38 MOUNTING HOLES 29.7 1.17 1/2 NPTM 71.4 2.81 4X LENGTH 1/4 NPTM SHOWN 28.6 1.13 ELECTRICAL CONNECTION SEE CHART SORINC.COM PRODUCT CERTIFICATION DRAWING ALL DIMENSIONS ARE 1/16 IN UNLESS OTHERWISE SPECIFIED MM LINEAR = IN ELECTRICAL CONNECTION 3/4 NPTF STD 1/2 NPTF OPT LH & RH M20 X 1.5 F LH & RH 3/4 PFF RH ONLY HOUSING 75.1 2.95 PROCESS CONNECTION SIZE 1/4 NPTM SHOWN ISO-9001 DIMENSION APPROXIMATE AND BAS ON A FIVE THREAD ENGAGEMENT 1 2 NPTF 25.4 ADD SEE DETAIL 1.00 *122.5 14685 W 105TH ST LENEXA, KS 66215 USA 4.82 913-888-2630 26.6 1.05 PURCHASE ORDER # 40.0 1.58 LENGTH A ELECTRICAL CONNECTION SEE CHART LINE ITEM # 150.1 5.91 80.0 3.15 PROCESS CONNECTION SIZE PROCESS 41.2 1.62 CONNECTION SIZE 41.2 1.62 1 PURCHASE ORDER # | 913-888-2630 | Registered Quality System to ISO 9001 29/32 Pressure and Vacuum Switches Dimensions Dimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certified drawings for a particular model number. Weatherproof - NEMA 4, 4X, IP66 Drawing 0090269 Drawing 0090270 Designators: RB Manual Reset Piston Numbers 12, 52 Designators: RB Manual Reset Piston Numbers 4, 54 Drawing 0090271 Designators: RB Manual Reset Piston Numbers 5, 6, 1, 9, 56 *Refer to Dimensions table on page 19 for changes in length due to process connection size, including A dimension. 30/32 Registered Quality System to ISO 9001 | 913-888-2630 | SORInc.com Form 216 (01.16) ©SOR Inc. Pressure and Vacuum Switches Dimensions Dimensions in this catalog are for reference only. They may be changed without notice. Contact the factory for certified drawings for a particular model number. Conventional Explosion Proof Drawing 0090167 Drawing 0090168 Designators: S Manual Reset Piston Numbers 12, 52 Designators: S Manual Reset Piston Numbers 4, 54 Drawing 0090169 Designators: S Manual Reset Piston Numbers 5, 6, 1, 9, 56 *Refer to Dimensions table on page 19 for changes in length due to process connection size, including A dimension. Form 216 (01.16) ©SOR Inc. SORInc.com | 913-888-2630 | Registered Quality System to ISO 9001 31/32 SOR Inc. | Lenexa, KS USA | 913-888-2630 | Fax 913-888-0767 | SORInc.com REGIONAL OFFICES China Middle East SOR China | Beijing, China SOR Measurement & Control Equipment Trading DMCC | Dubai, UAE +86 (10) 5820 8767 | Fax +86 (10) 58 20 8770 32/32 Registered Quality System to ISO 9001 +971 4 278 9632 | Fax +971 4 279 8399 | 913-888-2630 | SORInc.com Form 216 (01.16) ©SOR Inc.