Technical Committee on Fire Pumps (FIM-AAA) MEMORANDUM DATE: October 2, 2014 TO: Principal and Alternate Members of the Technical Committee on Fire Pumps (FIM-AAA) FROM: Chad Duffy, NFPA Staff Liaison Office: (617) 984-7562 Email: cduffy@nfpa.org SUBJECT: AGENDA – NFPA 20 Second Draft Meeting (Annual 2015) Enclosed is the agenda for the Second Draft meeting for NFPA 20, Standard on the Installation of Stationary Pumps for Fire Protection, which will be held at the UL LLC office in Northbrook, IL 8:00am to 5:00pm CDT on Tuesday October 21, 2014, and 8:00am to 5:00pm on Wednesday October 22, 2014. Please submit requests for additional agenda items to the chair at least seven days prior to the meeting, and notify the chair and staff liaison as soon as possible if you plan to introduce any Second revisions at the meeting. All NFPA Technical Committee meetings are open to the public. Please contact me for information on attending a meeting as a guest. Read NFPA's Regulations Governing the Development of NFPA Standards (Section 3.3.3.3) for further information. Additional Meeting Information: See the Meeting Notice on the Document Information Page (www.nfpa.org/20next) for meeting location details. If you have any questions, please feel free to contact Elena Carroll, Project Administrator at 617-984-7952 or by email ecarroll@nfpa.org. C. Standards Administration Page 1 of 5 Technical Committee on Fire Pumps (FIM-AAA) NFPA 20 Second Draft Meeting (Annual 2015) Tuesday, Oct.21, 2014 and Wednesday, Oct. 22, 2014, 8:00am – 5:00pm CDT UL LLC, 333 Pfingsten Road, Northbrook, IL AGENDA Tuesday, October 21, 2014 1. Call to Order – 8:00 AM 2. Introductions and Attendance 3. Review Agenda 4. NFPA Staff Liaison Presentation and Review of Key Dates in Current Cycle 5. Chairman Comments 6. Approval of Previous Meeting Minutes 7. Brief discussion of Controller Connectivity 8. Act on Public Comments for NFPA 20- Tentative order of presentation a. b. c. d. e. f. g. h. i. j. k. Task Group 9 – Controller Connectivity James Nasby – Chair Task Group 1 - Chapter 4, 6 & 7 Darrell Snyder – Chair Task Group 2 – Chapter 5 Dave Fuller - Chair Task Group 3 – Chapter 8 Jennifer McGrath - Chair Task Group 4 – Chapters 9 & 10 John Kovacik – Chair Task Group 5 – Chapter 11 & 12 John Whitney – Chair Task Group 6 – Chapters 13 Alan Dorini – Chair Task Group 7 – Chapter 14 Bill Harvey – Chair Task Group 11 – Table A.14.2.6.4 Task Group 10 – Coordination with NFPA 25 John Kovacik - Chair Task Group 8 – Electric Grid Reliability Dana Haagensen – Chair 9. Adjourn - TBD Wednesday, October 22, 2014 1. Call to Order – 8:00 AM 2. Complete Action on Public Comment for NFPA 20 3. Dissolution of current task groups 4. New business 5. Adjourn Meeting – 5:00 PM Please submit requests for additional agenda items to the chair at least seven days prior to the meeting. Page 2 of 5 Technical Committee on Fire Pumps (FIM-AAA) NFPA 20 Second Draft Meeting (Annual 2015) Tuesday, Oct.21, 2014 and Wednesday, Oct. 22, 2014, 8:00am – 5:00pm CDT UL LLC, 333 Pfingsten Road, Northbrook, IL Please notify the chair and staff liaison as soon as possible if you plan to introduce any committee input at the meeting. Key Dates for the Annual 2015 Revision Cycle Proposal Closing Date July 8, 2013 December 13, 2013 January 1, 2014 February 21, 2014 March 7, 2014 May 16, 2014 October 31, 2014 December12, 2014 January 2, 2014 January 16, 2015 Final Date for First Draft Meeting Posting of First Draft and TC Ballot Ballots Returned By Post Final First Draft Comment Closing Date Final Date for Second Draft Meeting Posting of Second Draft and TC Ballot Ballots Returned By Posting Final Second Draft Closing Date for Notice of Intent to Make a Motion March 6, 2015 (NITMAM) Issuance of Consent Document (No NITMAMs) May 26, 2015 NFPA Annual Meeting June 22-25, 2015 Issuance of Document with NITMAM August 20, 2015 Technical Committee deadlines are in bold. Page 3 of 5 Technical Committee on Fire Pumps (FIM-AAA) NFPA 20 Second Draft Meeting (Annual 2015) Tuesday, Oct.21, 2014 and Wednesday, Oct. 22, 2014, 8:00am – 5:00pm CDT UL LLC, 333 Pfingsten Road, Northbrook, IL Meeting Preparation Committee members are strongly encouraged to review the published comments prior to the meeting and to be prepared to act on each item. Handout materials should be submitted to the chair at least seven days prior to the meeting. Only one posting of the comments will be made; it will be arranged in section/order and will be pre-numbered. This will be posted to the NFPA Document information pages located at www.nfpa.org/20. If you have trouble accessing the website please contact Elena Carroll at ecarroll@nfpa.org. Mandatory Materials: Last edition of the standard Meeting agenda Public input/comments Committee Officers' Guide (Chairs) Roberts’ Rules of Order (Chairs; An abbreviated version may be found in the Committee Officer’s Guide) Optional Materials: NFPA Annual Directory NFPA Manual of Style Prepared committee input/comments (If applicable) Regulations and Guiding Documents All committee members are expected to behave in accordance with the Guide for the Conduct of Participants in the NFPA Codes and Standards Development Process. All actions during and following the committee meetings will be governed in accordance with the Regulations Governing the Development of NFPA Standards. Failure to comply with these regulations could result in challenges to the standards-making process. A successful challenge on procedural grounds could prevent or delay publication of the document. The style of the document must comply with the Manual of Style for NFPA Technical Committee Documents. Page 4 of 5 Technical Committee on Fire Pumps (FIM-AAA) NFPA 20 Second Draft Meeting (Annual 2015) Tuesday, Oct.21, 2014 and Wednesday, Oct. 22, 2014, 8:00am – 5:00pm CDT UL LLC, 333 Pfingsten Road, Northbrook, IL General Procedures for Meetings Use of tape recorders or other means capable of producing verbatim transcriptions of any NFPA Committee Meeting is not permitted. Attendance at all NFPA Committee Meetings is open. All guests must sign in and identify their affiliation. Participation in NFPA Committee Meetings is generally limited to committee members and NFPA staff. Participation by guests is limited to individuals, who have received prior approval from the chair to address the committee on a particular item, or who wish to speak regarding public input or comments that they submitted. The chairman reserves the right to limit the amount of time available for any presentation. No interviews will be allowed in the meeting room at any time, including breaks. All attendees are reminded that formal votes of committee members will be secured by letter ballot. Voting at this meeting is used to establish a sense of agreement, but only the results of the formal letter ballot will determine the official action of the committee. Note to Special Experts: Particular attention is called to Section 3.3(e) of the NFPA Guide for the Conduct of Participants in the NFPA Codes and Standards Development Process in the NFPA Directory. This section requires committee members to declare any interest they may represent, other than their official designation as shown on the committee roster. This typically occurs when a special expert is retained by and represents another interest category on a particular subject. If such a situation exists on a specific issue or issues, the committee member shall declare those interests to the committee and refrain from voting on any action relating to those issues. Smoking is not permitted at NFPA Committee Meetings. Page 5 of 5 NEW PROCESS ACTIONS AND MOTIONS Possible Action #1: Accept Public Comment (exactly as it is) Action Required Sample motion Create a Second Revision I move to create a Second Revision using PC # ______. Possible action #2: Reject but see (revise submitted text) Action Required Sample motion Step 1 Create a Second Revision based on a Public Comment I move to create a Second Revision based on PC # _____with the following changes to the text . . . If the revision is related to multiple PCs, Step 2 respond to all of them together using the cart function I move to create a Second Revision based on PC # ____and incorporating PC #s _____with the following changes to the text . . . Possible action #3: Reject (no change to the standard) Action Required Sample motion Generate a statement (substantiation) I move to reject PC # ____ with the following substantiation . . . Possible Action #4: Reject but hold (new material) Action Required Sample motion I move to reject PC # ____ but hold it for Reject Public Comment for this cycle, but consideration during the First Draft meeting next save for next revision cycle cycle. Attachment #1: Previous Meeting Minutes MINUTES of the NFPA 20 Public Input meeting Orlando, FL – October 1 thru 3, 2013 Tuesday; October 1 1. Chairman Gayle Pennel called the meeting to order at 8 AM. 2. A presentation was furnished by Doug Stevens regarding transducers. 3. Recessed in order for the Task Groups to deliberate. 4. Reconvened at 1:00 PM. 5. All attendees made self-Introductions; See attached attendance. 6. Staff Liaison Chad Duffy addressed the revised Standard Development Process. 7. Chairman Pennel provided standard meeting instructions 8. Staff Liaison Chad Duffy instructed Technical Committee on Roster update and attendance log. 9. Chairman Pennel called for a motion to accept minutes of October 2011 ROC meeting of the TECHNICAL COMMITTEE in San Antonio, TX. Motion passed unanimously. 10. A presentation was furnished by Jim Nasby regarding electrical connectivity. 11. Technical Committee began the review and action process on 159 public input proposals beginning with Task Group reports and actions: a. Task Group on Chps 4, 6, &7 by Darrell Snyder b. Task Group on Chp 5 by David Fuller c. Task Group on Chp 8 by Jennifer McGrath d. Task Group on Chps 9 & 10 by Hugh Castles e. Task Group on Chps 11 & 12 by John Whitney f. Task Group on Chp 13 by Alan Dorini g. Task Group on Chp 14 by Bill Harvey h. Task Group on Electric Grid Reliability by Dana Haagensen 12. Session recessed at 6:10PM Wednesday; October 2 13. Technical Committee reconvened at 8:00 AM on 10/2 and continued the review and action process on the Public Input proposals beginning with unfinished Task Group reports and actions:, 14. Chairman Pennel entertained a discussion by Victoria Valentine (NFPA 13) regarding Hanging and Bracing. 15. Technical Committee continued with the review and action process on remaining Public Input proposals 16. Session recessed at 6:25PM Thursday; October 3 17. Technical Committee reconvened at 8:00 AM on 10/3 and continued the review and action process on the remaining Public Input proposals 18. Chairman Pennel announced a ballot for this NFPA 20 meeting on Public Input would be forwarded to the Technical Committee members for their official vote. 19. Chairman Pennel announced that the next meeting will likely be scheduled in August, September, or October 2014. Exact date and location to be announced in the future. 20. Chairman Pennel called for a motion to adjourn at 12:15 PM. Motion passed unanimously. Respectfully submitted, R. T. Leicht, Secretary Attendees: Gayle Pennel, Chair R. T. Leicht, Secretary Chad Duffy, NFPA Staff Liaison Principals Alternates Michael Aaron Timothy Ballengee James Beals Marinus Both Pat Brock Hugh Castles Stephen Clark Mohammad Dadgardoust Alan Dorini David Fuller Dana Haagensen David hague Bill Harvey Hatem Kheir John Kovacik Jennifer McGrath Charles McKnight James Nasby Jeffrey Roberts Michael Rothmier Richard Schneider Darrell Snyder Terry Victor John Whitney Kerry Bell Brad Cronin Jerald Huff Kenneth Isman Floyd Luinstra William Stelter Thomas Wellen Guests Peter Schwab Brian Buscler Kevin Kunkler Tim Jordan Les Andree Rogen Montenbeault Steven Baird Matt Paine Doug Stephens Victoria Valentine Attachment #2: Public Comment/20 National Fire Protection Association Report 1 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 33-NFPA 20-2014 [ Section No. 3.3.41 ] 3.3.41 Record Drawing (As-Built). Drawings that document the installed layout, including piping and the location of all devices, appliances, wiring sequences, wiring methods, and connections to the components of the system as installed A design, working drawing, or as-built drawing that is submitted as the final record of documentation for the project . Statement of Problem and Substantiation for Public Comment This puts the section back to the language in the previous edition. The revision was taken from NFPA 72 and uses terms that are not common in the fire pump industry. Traditionally, "as built" drawings are prepared by the sprinkler contractor and do not include wiring diagrams or wiring sequences. These might be provided by the electrician or the controller manufacturer, but they are separate from the as built drawings that would show the water-filled pipe provided by the sprinkler contractor. Related Item First Revision No. 3-NFPA 20-2013 [Section No. 3.3.41] Submitter Information Verification Submitter Full Name: Kenneth Isman Organization: National Fire Sprinkler Association Street Address: City: State: Zip: Submittal Date: Thu May 08 16:22:22 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 2 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 35-NFPA 20-2014 [ Section No. 4.3.1 ] 4.3.1 In the event of fire pump operation that is not a part of a scheduled weekly or monthly churn test , qualified personnel shall respond to the fire pump location to determine that the fire pump is operating in a satisfactory manner. Statement of Problem and Substantiation for Public Comment First Revisions 58 and 59 permit an automatic timer to shut off the fire pump. This implies that the committee intends to allow fire pumps to run unattended during the weekly or monthly churn test. While we are not particularly in favor of that idea, we note that such unattended running of the pump would violate this section, so it needs to be modified. We don't know how the committee intends for the data collected during the test to be recorded without a person present in the pump room, but assuming that a building owner could figure out how to record this data remotely, it is possible that the pump room could be unattended. Related Item First Revision No. 58-NFPA 20-2013 [New Section after 10.5.2.6.3] First Revision No. 59-NFPA 20-2013 [Section No. 10.5.4.2] Submitter Information Verification Submitter Full Name: Kenneth Isman Organization: National Fire Sprinkler Association Affilliation: NFSA E&S Committee Street Address: City: State: Zip: Submittal Date: Thu May 08 16:42:17 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 3 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 39-NFPA 20-2014 [ Section No. 4.13.1.3 ] 4.13.1.3 Fire Pump Buildings or Rooms with Diesel Engines. Fire pump buildings or rooms enclosing diesel engine pump drivers and day tanks shall be protected with an automatic sprinkler system installed in accordance with NFPA 13 as an Extra Hazard Group 2 occupancy. 4.13.1.3.1 Diesel fire pump controllers shall be protected from the sprinkler spray or provided with a National Electrical Manufacturers Association (NEMA) Type 4, waterproof enclosure(s) or an enclosure(s) with an ingress protection (IP) rating of IP66. Statement of Problem and Substantiation for Public Comment The minimum enclosure required by NFPA 20, paragraph 12.3.3.1.1 is a NEMA type 2. This is not suitable for sprinkler spray. It is only suitable for dripping water from the vertical. Spray from a sprinkler head can directly enter a type 2 enclosure and potentially damage or destroy the controller. Related Item First Revision No. 12-NFPA 20-2013 [Section No. 4.12.1.3] Submitter Information Verification Submitter Full Name: William Stelter Organization: Master Control Systems, Inc. Street Address: City: State: Zip: Submittal Date: Sat May 10 09:58:54 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 4 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 40-NFPA 20-2014 [ Section No. 4.13.1.4 ] 4.13.1.4 Fire Pump Buildings or Rooms with Electric Drivers. For buildings that are required to be sprinklered, fire pump buildings or rooms enclosing electric fire pump drivers shall be protected with an automatic sprinkler system installed in accordance with NFPA 13 as an Ordinary Hazard Group 1 occupancy. 4.13.1.4.1 Electric fire pump controllers shall be protected from the sprinkler spray or provided with a National Electrical Manufacturers Association (NEMA) Type 4, waterproof enclosure(s) or an enclosure(s) with an ingress protection (IP) rating of IP66. Statement of Problem and Substantiation for Public Comment The minimum enclosure required by NFPA 20, paragraph 10.3.3.1 is a NEMA type 2. This is not suitable for sprinkler spray. It is only suitable for dripping water from the vertical. Spray from a sprinkler head can directly enter a type 2 enclosure and potentially damage or destroy the controller. Related Item First Revision No. 12-NFPA 20-2013 [Section No. 4.12.1.3] Submitter Information Verification Submitter Full Name: William Stelter Organization: Master Control Systems, Inc. Street Address: City: State: Zip: Submittal Date: Sat May 10 10:16:27 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 5 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 9-NFPA 20-2014 [ Section No. 4.13.1.4 ] 4.13.1.4 Fire Pump Buildings or Rooms with Electric Drivers. For buildings that are required to be sprinklered, fire pump buildings or rooms enclosing electric fire pump drivers shall be protected with an automatic sprinkler system installed in accordance with NFPA 13 as an Ordinary Hazard Group 1 occupancy. Delete this new proposed clause. Statement of Problem and Substantiation for Public Comment Delete this new clause. No reason has been given to deviate from Table 4.12.1.1.2. No new evidence has been given to indicate that an electric fire pump is more of a fire hazard than previously. Further, spraying fire water on electical equipment (motor and controller) is not good practice. This especially since the controller is protected only from vertical dripping water, wheras fire water from sprinklers is not only vertical. Related Item First Revision No. 12-NFPA 20-2013 [Section No. 4.12.1.3] Submitter Information Verification Submitter Full Name: James Nasby Organization: Columbia Engineering Street Address: City: State: Zip: Submittal Date: Mon Apr 14 17:52:01 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 6 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 51-NFPA 20-2014 [ Section No. 4.13.2.1.1 [Excluding any Sub-Sections] ] Except as provided in 4.13.2.1.1.1, fire pump rooms not directly accessible from the outside shall be accessible through an enclosed passageway from an enclosed stairway or exterior exit, provided neither of which are part of a required means of egress . Statement of Problem and Substantiation for Public Comment NFPA's Building Code Development Committee (BCDC) agrees that a passageway from the exterior to a fire pump room is acceptable. We think it should not interfere with a required means of egress. This Public Comment is related to Public Input #134 but revises the text from Public Input #134. This allows the existing access from a room that is normally unoccupied, and therefore not needing a means of egress. This change does not affect the FR30 for a local application. Related Item Public Input No. 134-NFPA 20-2013 [Section No. 4.12.2.1.1] Submitter Information Verification Submitter Full Name: Jim Muir Organization: Building Safety Division, Clark County, Washington Affilliation: NFPA's Building Code Development Committee (BCDC) Street Address: City: State: Zip: Submittal Date: Thu May 15 13:18:45 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 7 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 10-NFPA 20-2014 [ Section No. 4.19.7.2 [Excluding any Sub-Sections] ] Where pump discharge water is piped back to pump suction and the pump is driven by a diesel engine with heat exchanger cooling, the controller shall provide a visual indicator and audible alarm and stop the engine when a high cooling water temperature signal as required by 11.2.4.4.8 is received, provided there are no active emergency requirements for the pump to run. This includes; fire water demand, remote switch actuation and deluge valve or fire detection signal to run. Statement of Problem and Substantiation for Public Comment As written, the test in not very enforceable, if at all, since no definition is given for "active emergency requirements for the pump to run". This is too esoteric as well as too vague. Related Item First Revision No. 75-NFPA 20-2013 [Section No. 4.18.7.2 [Excluding any Sub-Sections]] Submitter Information Verification Submitter Full Name: James Nasby Organization: Columbia Engineering Street Address: City: State: Zip: Submittal Date: Mon Apr 14 18:05:50 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 8 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 41-NFPA 20-2014 [ Section No. 4.20.2.9.2 ] 4.20.2.9.2 Series fire pump controller(s) shall be provided with the extra contacts for remote indication in accordance with 4.20.2.9.1.1 or 4.20.2.9.1.2. 4.20.2.9.2.1 Where other means are used to communicate this information, the extra contacts in 4.20.2.9.2 are not required. Statement of Problem and Substantiation for Public Comment To provide all the information and signals required in 4.20.2.2 and 4.20.2.9 a network connection will most likely be supplied between controllers. This comment will allow signals by extra contacts and by other means such as a network connection. Related Item First Revision No. 35-NFPA 20-2013 [Section No. 4.19.2] Submitter Information Verification Submitter Full Name: William Stelter Organization: Master Control Systems, Inc. Street Address: City: State: Zip: Submittal Date: Sat May 10 10:24:16 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 9 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 11-NFPA 20-2014 [ Section No. 4.28.4.6 ] 4.28.4.6 Retroactive installation of a backflow prevention device shall not reduce the suction pressure below that permitted in this standard and accepted by the authority having jurisdiction. This shall not apply to backflow prevention devices retroactively installed prior to the adoption of the adoption of this edition of this standard. Statement of Problem and Substantiation for Public Comment It is not clear that extant installations need not comply with this new requirement since the term "retroactive installation" is used. Related Item First Revision No. 36-NFPA 20-2013 [New Section after 4.27.4.5] Submitter Information Verification Submitter Full Name: James Nasby Organization: Columbia Engineering Street Address: City: State: Zip: Submittal Date: Mon Apr 14 18:18:59 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 10 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 12-NFPA 20-2014 [ Section No. 4.28.4.6 ] 4.28.4.6 Retroactive installation of a backflow prevention device shall not reduce the suction pressure below that permitted in this standard and accepted by the authority having jurisdiction. This shall not apply to backflow prevention devices retroactively installed prior to the adoption of the adoption of this edition of this standard. Statement of Problem and Substantiation for Public Comment It is not clear that extant installations need not comply with this new requirement since the term "retroactive installation" is used. Related Item First Revision No. 36-NFPA 20-2013 [New Section after 4.27.4.5] Submitter Information Verification Submitter Full Name: James Nasby Organization: Columbia Engineering Street Address: City: State: Zip: Submittal Date: Mon Apr 14 18:22:38 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 11 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 23-NFPA 20-2014 [ Section No. 4.30.1 ] 4.30.1 A packaged fire pump assembly, with or without an enclosure, shall meet all of the following requirements: (1) The components shall be assembled and affixed onto a steel framing structure. (2) Welders shall be qualified in accordance with the Section 9 of ASME Boiler and Pressure Vessel Code or with the American Welding Society AWS D1.1, Structural Welding Code — Steel. (1) The assembly shall be listed for fire pump service. (2) The total assembly shall be engineered and designed by a system designer as referenced in 4.3.2. (3) All plans and data sheets shall be submitted and reviewed by the authority having jurisdiction, with copies of the stamped approved submittals used in the assembly and for record keeping. Additional Proposed Changes File Name 20_Keeping_Comment_4-29-1.pdf Description Approved PC form Statement of Problem and Substantiation for Public Comment The Committee Statement did not provide a satisfactory explanation as to why a prepackaged fire pump assembly would need to be listed. It only made some vague reference to problems with some pump packages. It did not offer any details as to what these problems may be, so they cannot be addressed at this phase. Concerning problems with prepackaged fire pump assemblies however, it is hard to image how they could be more severe than those associated with fire pump systems that are taken to the job site in component pieces and assembled there in the field. Additionally, the Committee Statement did not offer any comment on the Substantiation (copied below for reference) that was provided with the Public Input. It did not speak to the points about the current requirement: - Limiting who can build prepackaged assemblies; - Limiting the ability to provide customized skids to meet a client’s specific needs; - That there should be no differences in the acceptability of prepackaged assemblies vs. systems assembled on the job sites; and - The fallacy of the previous cycle Proposals, 20-16 & 20-17 attributing unit responsibility to the fire pump manufacturer. Public Input Substantiation: There is no need to require a packaged fire pump assembly to be specifically listed. This requirement basically limits the supply of packaged fire pump assemblies to ones produced solely by fire pump manufacturers and limits the ability of fire protection contractors to supply customized skids to suit a client’s specific needs. There should be no differences in the acceptability between a package that a contractor prepares off site and ships preassembled to the job site, from one that is taken to the job site in its component pieces and is assembled there. They are both fire pump units that must be installed, inspected and tested in the same manner. During the previous revision cycle, Proposals 20-16 and 20-17 argued that it is the fire pump manufacturer that has unit responsibility, but this is not correct. As noted in A.4.4.1, the entity designated as having unit responsibility is responsible for the pump, the driver, the controller, the transfer switch and the accessories. Each of these components is generally made by a different manufacturer, so none of them would be the single entity that could answer and resolve all problems. Thus the unit responsibility must move further up the supply chain. Naturally though, the entity with unit responsibility often has to consult with one or more of the manufacturers to resolve any questions or problems. As noted, it should be no different, no matter where or in what order the components are assembled. 6/4/2014 9:15 AM National Fire Protection Association Report 12 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Related Item Committee Input No. 24-NFPA 20-2013 [Section No. 4.29.1] Submitter Information Verification Submitter Full Name: Larry Keeping Organization: Professional Loss Control Street Address: City: State: Zip: Submittal Date: Thu Apr 24 13:43:25 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 13 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 34-NFPA 20-2014 [ Section No. 5.5 ] 5.5 Auxiliary Power. Where electric motors are used, a reliable emergency source of power in or a back-up fire pump in accordance with Section 9.6 3 shall be provided for the fire pump installation. Statement of Problem and Substantiation for Public Comment A diesel engine back-up fire pump should be permitted as an alternative to a generator. Chapter 9 already allows this and Chapter 5 should not over-ride Chapter 9. Related Item First Revision No. 44-NFPA 20-2013 [Section No. 5.5] First Revision No. 137-NFPA 20-2013 [Section No. 9.3.1] Submitter Information Verification Submitter Full Name: Kenneth Isman Organization: National Fire Sprinkler Association Street Address: City: State: Zip: Submittal Date: Thu May 08 16:31:41 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 14 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 13-NFPA 20-2014 [ Section No. 5.6.1.4 ] 5.6.1.4 Each refill valve shall be sized and arranged to independently refill the tank in a maximum time of 8 hours. supply the system fiure protection demand. I.E.: Revert to original wording. Statement of Problem and Substantiation for Public Comment This section applies to "Very Tall Buildings" where the building height exceeds the pumping capacity of the fire department apparatus. While I agree that in certain circumstances the refill rate being equal to the fire protection demand can be difficult to achieve, the proposed change to an 8 hour refill time is not sufficent to ensure a reasonable refill rate to maintain building fire protection. In most cases the water supply duration requirement will be 30 or 60 minutes total. Going from a 1:1 to a 1:16 or 1:8 refill ratio leaves the building without fire protection for far too long in context of a very tall building where evacuation times are lenghthy and/or protect in place stratgies are used and there is sole reliance on the building fire protection water supply. The original requirements were written to permit up to 1/2 of the total stored demand to be out of service with the understanding that refill rate would compensate for the storage out of service. Where the refill comes from a standpipe below this can be accomplished at minimal cost (larger refill pipe and valve from the top of a standpipe to a tank). For a ground level tank the municipal supply must make up the refill. The originally required refill rate is a minimal cost item that should apply to all high rise building where evacuation is impractical. Related Item First Revision No. 60-NFPA 20-2013 [Section No. 5.6.1.4] Submitter Information Verification Submitter Full Name: James Nasby Organization: Columbia Engineering Street Address: City: State: Zip: Submittal Date: Mon Apr 14 18:32:07 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 15 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 50-NFPA 20-2014 [ Section No. 5.6.1.4 ] 5.6.1.4 Each refill valve shall be sized and arranged to independently refill the tank in a maximum time of 8 of 4 hours. Statement of Problem and Substantiation for Public Comment NFPA's Building Code Development Committee (BCDC) agrees with the intent of this First Revision. This Public Comment would require each refill valve shall be sized and arranged to independently refill the tank in a maximum time of 4-hours, rather than 8 hours. The current code requires that the storage tank refill at a very quick rate. The proposed language in FR #60 allows for a maximum of 8 hours to refill the tank, which appears to be an excessive amount of time without full capabilities of water supply. Fire flow requirements set forth in NFPA 1 section 18.4.5.1.2 have a maximum duration for the largest buildings at four hours. A four-hour time period would allow the system to be up to full capabilities much faster without the extreme draw that is currently allowed. Related Item First Revision No. 60-NFPA 20-2013 [Section No. 5.6.1.4] Submitter Information Verification Submitter Full Name: Jim Muir Organization: Building Safety Division, Clark County, Washington Affilliation: NFPA's Building Code Development Committee (BCDC) Street Address: City: State: Zip: Submittal Date: Thu May 15 13:08:50 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 16 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 42-NFPA 20-2014 [ Section No. 9.6.5.3 ] 9.6.5.3 The fire pump circuit breaker shall not be required to be coordinated with the generator power source protective device provided it is used as a an individual branch circuit breaker and is coordinated with all other line side protective devices, where used . Statement of Problem and Substantiation for Public Comment NFPA 70 has several definitions for a branch circuit. The "Branch Circuit, Individual" definition is most appropriate for this use. Also, "where used" was added since other line side protective devices are not always used. Related Item First Revision No. 49-NFPA 20-2013 [Section No. 9.6.5] Submitter Information Verification Submitter Full Name: William Stelter Organization: Master Control Systems, Inc. Street Address: City: State: Zip: Submittal Date: Sat May 10 10:36:51 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 17 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 43-NFPA 20-2014 [ Section No. 10.3.4.5.3 ] 10.3.4.5.3 Except as provided in 4.20.2. 3 2(1) and 10.9.4 , remote shutdown or interlock to prevent normal operation shall not be permitted unless approved by the authority having jurisdiction. Statement of Problem and Substantiation for Public Comment Paragraph reference corrected and added the reference to10.9.4 which specifically allows shutdown under specified conditions. Related Item First Revision No. 52-NFPA 20-2013 [New Section after 10.3.4.5.2] Submitter Information Verification Submitter Full Name: William Stelter Organization: Master Control Systems, Inc. Street Address: City: State: Zip: Submittal Date: Sat May 10 11:01:03 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 18 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 44-NFPA 20-2014 [ Section No. 10.5.2.1.1.2 ] 10.5.2.1.1.2 For multistage multiport pumps, a separate pressure-actuated switch or electronic pressure sensor as described in 10.5.2.1.1.1 shall be provided for each discharge port of the pump as part of the controller. 10.5.2.1.1.3 There For multistage multiport pumps, a separate pressure recorder as described in 10.5.2.1.7.2 shall be provided for each discharge port of the pump as part of the controller. Statement of Problem and Substantiation for Public Comment This will add a requirement to monitor the pressure in each zone as is the case with individual pumps in each zone. Related Item First Revision No. 126-NFPA 20-2013 [Sections 10.5.2.1.1.1, 10.5.2.1.1.2] Submitter Information Verification Submitter Full Name: William Stelter Organization: Master Control Systems, Inc. Street Address: City: State: Zip: Submittal Date: Sat May 10 11:08:31 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 19 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 52-NFPA 20-2014 [ Section No. 10.5.2.1.3.1 ] 10.5.2.1.3.1 * Where the transducer pressure reading exceeds 10 psi (0.68 bar) during any automatic pump start that was initiated by the solenoid drain valve, as required by 10.5.2.1.8.3 , the controller shall activate a visual and audible alarm, that can be silenced. Statement of Problem and Substantiation for Public Comment The clause is overly restrictive by requiring pressure to be limited to a maximum of 10psi (No technical data has been presented to support this level) when the solenoid drain valve is opened. The intent of the clause is already addressed by clause 10.5.2.7.5 (Automatic testing section) which requires the transducer output pressure reading to fall below the system low pressure start point, and initiate an automatic start, or an alarm is activated. Related Item First Revision No. 53-NFPA 20-2013 [New Section after 10.5.2.1.2] Submitter Information Verification Submitter Full Name: CAM WORKMAN Organization: EATON Street Address: City: State: Zip: Submittal Date: Fri May 16 12:10:39 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 20 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 7-NFPA 20-2014 [ Section No. 10.5.2.7.1 ] 10.5.2.7.1 Where permitted by the AHJ, The controller equipment shall be arranged to automatically start, run, and shut down the motor at the minimum no-flow test frequency and duration required by NFPA 25. Statement of Problem and Substantiation for Public Comment The proposed wording circumvents of the AHJ’s authority by allowing an automatic start then shutdown in the first circumstance even when the AHJ has decided that it must be manual. There are compelling reasons for an AHJ to require manual shutdown under all circumstances and it is the AHJ prerogative to enforce the arrangement that he deems appropriate. The Standard should not be dictating the AHJ as how fire pumps are to be arranged in his jurisdiction. The AHJ is still the final word on accepting an installation. NFPA 25 requires a person to be in attendance when a fire pump is running. Related Public Comments for This Document Related Comment Relationship Public Comment No. 5-NFPA 20-2014 [Section No. 12.7.2.7.1] Public Comment No. 6-NFPA 20-2014 [Section No. 12.7.5.2.1] Related Item First Revision No. 66-NFPA 20-2013 [Section No. 12.7.5.2] Submitter Information Verification Submitter Full Name: John Chartier Organization: Northeastern Regional Fire Cod Street Address: City: State: Zip: Submittal Date: Mon Apr 07 12:18:47 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 21 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 16-NFPA 20-2014 [ Section No. 10.5.4.2.1 ] Revert to extant 10.5.4.2 text . 1 Automatic shutdown shall be permitted only in the following circumstances: (1) During automatic testing in accordance with 10.5.2.7 (2) Where approved by the authority having jurisdiction for non-testing conditions Statement of Problem and Substantiation for Public Comment No good reason has been given for eliminating automatic stopping for pumps which are not sole source pumps. This will cause any number of pumps to burn up, which is why Chicago requires automatic stopping of ALL electric fire pumps. While I feel that sole source pumps should require manual stopping, this seems excessive where multiple pumps are involved. The net result will be to REDUCE the reliability of fire protection on many of these cases rather than either maintaining or enhancing said reliability. Related Item First Revision No. 59-NFPA 20-2013 [Section No. 10.5.4.2] Submitter Information Verification Submitter Full Name: James Nasby Organization: Columbia Engineering Street Address: City: State: Zip: Submittal Date: Wed Apr 16 18:50:49 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 22 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 8-NFPA 20-2014 [ Section No. 10.5.4.2.1 ] 10.5.4.2.1 Automatic shutdown shall be permitted only in the following circumstances: (1) During automatic testing in accordance with 10.5.2.7 when permitted by the AHJ (2) Where approved by the authority having jurisdiction for non-testing conditions Statement of Problem and Substantiation for Public Comment The proposed wording circumvents of the AHJ’s authority by allowing an automatic start then shutdown in the first circumstance even when the AHJ has decided that it must be manual. There are compelling reasons for an AHJ to require manual shutdown under all circumstances and it is the AHJ prerogative to enforce the arrangement that he deems appropriate. The Standard should not be dictating the AHJ as how fire pumps are to be arranged in his jurisdiction. The AHJ is still the final word on accepting an installation. NFPA 25 requires a person to be in attendance when a fire pump is running. Related Public Comments for This Document Related Comment Relationship Public Comment No. 5-NFPA 20-2014 [Section No. 12.7.2.7.1] Public Comment No. 6-NFPA 20-2014 [Section No. 12.7.5.2.1] Public Comment No. 7-NFPA 20-2014 [Section No. 10.5.2.7.1] Related Item First Revision No. 66-NFPA 20-2013 [Section No. 12.7.5.2] Submitter Information Verification Submitter Full Name: John Chartier Organization: Northeastern Regional Fire Cod Street Address: City: State: Zip: Submittal Date: Mon Apr 07 12:22:09 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 23 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 17-NFPA 20-2014 [ Section No. 10.5.4.2.2 ] Revert to extant 10.5.4.2 text . 2 Where automatic shutdown after automatic start is permitted, a minimum run timer set for at least 10 minutes shall be used. Statement of Problem and Substantiation for Public Comment No good reason has been given for eliminating automatic stopping for pumps which are not sole source pumps. This will cause any number of pumps to burn up, which is why Chicago requires automatic stopping of ALL electric fire pumps. While I feel that sole source pumps should require manual stopping, this seems excessive where multiple pumps are involved. The net result will be to REDUCE the reliability of fire protection on many of these cases rather than either maintaining or enhancing said reliability. Related Item First Revision No. 59-NFPA 20-2013 [Section No. 10.5.4.2] Submitter Information Verification Submitter Full Name: James Nasby Organization: Columbia Engineering Street Address: City: State: Zip: Submittal Date: Wed Apr 16 18:55:40 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 24 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 32-NFPA 20-2014 [ New Section after 10.8.2.2 ] Add new paragraph to the end of 10.8.2.2 10.8.2.2(7) The transfer switch shall be the delayed transition type with a maximum delay time of 3 seconds. Statement of Problem and Substantiation for Public Comment The delayed transition transfer switch eliminates the higher than normal in-rush currents when transferring the fire pump motor from one source to the other. This is a transfer switch listed for emergency systems (NFPA 70 Article 700). Related Public Comments for This Document Related Comment Relationship Public Comment No. 31-NFPA 20-2014 [Section No. 10.8.3.10.1] Related Item First Revision No. 101-NFPA 20-2013 [Section No. 10.8.2.2] Submitter Information Verification Submitter Full Name: William Stelter Organization: Master Control Systems, Inc. Street Address: City: State: Zip: Submittal Date: Wed May 07 05:32:21 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 25 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 47-NFPA 20-2014 [ New Section after 10.8.2.2 ] 10.8.2.2.1 Listed Complete Power Transfer Unit The separate transfer switch unit shall be Listed for fire protection service as a complete unit. It shall include all of the items in (1) thru (6) above and include field wiring terminals for the required alarm circuitry and generator start control wiring. It shall meet all of the requirements in 10.8.3. [Renember extant text as 10.8.2.2.2.] Statement of Problem and Substantiation for Public Comment Extent text does not require nor name a single entity or who is to be responsible for Arrangement II power transfer equipment, although the fire pump controller is covered. Extent text allows a potpourri of various components to be mounted and installed which may or may not be coordinated, safe or reliable. The power transfer equipment should be by a single entity, and listed as such, as is the fire pump controller and as the combination unit is in Arrangement I in 10.8.2.1. Related Item Public Input No. 101-NFPA 20-2013 [New Section after 11.4.4.2] Submitter Information Verification Submitter Full Name: James Nasby Organization: Columbia Engineering Street Address: City: State: Zip: Submittal Date: Wed May 14 15:57:52 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 26 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 31-NFPA 20-2014 [ Section No. 10.8.3.10.1 ] 10.8.3.10.1 The use of an “in-phase monitor” or an intentional delay via an open neutral position of the transfer switch to comply with the requirements of 10.8.3.10 shall be prohibited. Statement of Problem and Substantiation for Public Comment A delayed transition transfer switch eliminates the need for an interface between the transfer switch and fire pump controller. Also, UL 1008-7, paragraph E2.16 only restricts the use of the "In-phase monitor". Related Item First Revision No. 101-NFPA 20-2013 [Section No. 10.8.2.2] Submitter Information Verification Submitter Full Name: William Stelter Organization: Master Control Systems, Inc. Street Address: City: State: Zip: Submittal Date: Wed May 07 03:51:47 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 27 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 48-NFPA 20-2014 [ New Section after 10.8.3.12 ] 10.8.3.12.3 Fault Tolerance The generator starting circuit shall meet the requirements of Clause 10.5.2.6. Acceptable means, among others are below: 10.8.3.12.3(1) Supervise the voltage at the normally open contacts, if these are used to start the generator. 10.8.3.12.3(2) Supervise the current flowing thrugh the normally closed contacts, if these are used to start the generator. 10.8.3.12.3(3) Add a drop-out relay in the generator control panel wired to the normally closed transfer switch generator start contacts powered by the generator battery when the normally open contacts are used to start the generator. Normally closed contacts of this relay shall be wired to the generator normally open start cricuit. 10.8.3.12.3(4) Add a pick-up relay in the generator control panel wired to the normally closed transfer switch generator start contacts powered by the generator battery when the normally closed contacts are used to start the generator. Normally open contacts of this relay shall be wired in series with the generator normally closed start cricuit. Statement of Problem and Substantiation for Public Comment The requirements of 10.5.2.6 are moot if the combination controller or if the Arrangement II transfer switch unit looses control of the stand-by generator due to an open circuit in a normally open circuit control loop, or a short circuit in a normally closed loop or a ground which may also inhibit the generator from starting, depending on where it occurs. Related Item Public Input No. 101-NFPA 20-2013 [New Section after 11.4.4.2] Submitter Information Verification Submitter Full Name: James Nasby Organization: Columbia Engineering Street Address: City: State: Zip: Submittal Date: Wed May 14 16:32:35 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 28 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 18-NFPA 20-2014 [ Section No. 11.2.4.3.4.1.1 ] 11.2.4.3.4.1.1 * Pressure sensing line(s) shall be installed with a connection to the pipe that is in horizontal orientation to the pressure source Delete this proposed new clause or move it to the Annex A . Statement of Problem and Substantiation for Public Comment It's not clear what "horizontal orientation to the pressure source" means. I don't know what the proposed piping will look like. No reason has been given to force this arrangement on all variable speed engine and engine manufacturers. Related Item First Revision No. 72-NFPA 20-2013 [New Section after 11.2.4.3.4.1] Submitter Information Verification Submitter Full Name: James Nasby Organization: Columbia Engineering Street Address: City: State: Zip: Submittal Date: Wed Apr 16 19:08:27 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 29 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 36-NFPA 20-2014 [ Section No. 11.2.4.3.4.1.1 ] 11.2.4.3.4.1.1 * Pressure sensing line(s) shall be installed with a connection to the pipe that is in horizontal orientation to the pressure source. Statement of Problem and Substantiation for Public Comment The term "horizontal orientation to the pressure source" is difficult to understand and enforce. A vertical sensing line would work from underneath with a drop leg to allow sediment to drop down and be cleaned out. Related Item First Revision No. 72-NFPA 20-2013 [New Section after 11.2.4.3.4.1] Submitter Information Verification Submitter Full Name: Kenneth Isman Organization: National Fire Sprinkler Association Affilliation: E&S Committee Street Address: City: State: Zip: Submittal Date: Thu May 08 16:54:37 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 30 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 38-NFPA 20-2014 [ New Section after 11.4.1.6.3 ] 11.4.1.6.4 Vents from interstitial spaces of double-wall tanks shall meet 11.4.1.6.2 and 11.4.1.6.3 and shall not be manifolded together with a vent from the primary portion of the tank. Statement of Problem and Substantiation for Public Comment NFPA 20 needs to clarify that the rules for the vent from the main portion of the tank also apply to the vent from the interstitial space. Also, the standard needs to clarify that the vents cannot be manifolded together. Manifolding the tanks might allow pressure to build up in a portion of the tank rather than vent properly. Related Item First Revision No. 147-NFPA 20-2013 [Global Input] First Revision No. 149-NFPA 20-2013 [Global Input] Submitter Information Verification Submitter Full Name: Kenneth Isman Organization: National Fire Sprinkler Association Affilliation: NFSA E&S Committee Street Address: City: State: Zip: Submittal Date: Thu May 08 17:13:04 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 31 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 45-NFPA 20-2014 [ Section No. 12.7.2.1.1.2 ] 12.7.2.1.1.2 For multistage multiport pumps a separate pressure-actuated switch or electronic pressure sensor as described in 12.7.2.1.1.1 shall be provided for each discharge port of the pump as part of the controller. 12.7.2.1.1.3 For multistage multiport pumps, a separate pressure recorder as described in 12.4.4.1 shall be provided for each discharge port of the pump as part of the controller. Statement of Problem and Substantiation for Public Comment This will add a requirement to monitor the pressure in each zone as is the case with individual pumps in each zone. Related Item First Revision No. 127-NFPA 20-2013 [Sections 12.7.2.1.1.1, 12.7.2.1.1.2] Submitter Information Verification Submitter Full Name: William Stelter Organization: Master Control Systems, Inc. Street Address: City: State: Zip: Submittal Date: Sat May 10 11:20:44 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 32 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 5-NFPA 20-2014 [ Section No. 12.7.2.7.1 ] 12.7.2.7.1 The Where permitted by the AHJ, the controller equipment shall be arranged to automatically start, run, and shut down the engine at the minimum no-flow test frequency and duration required by NFPA 25. Statement of Problem and Substantiation for Public Comment The proposed wording circumvents of the AHJ’s authority by allowing an automatic start then shutdown in the first circumstance even when the AHJ has decided that it must be manual. There are compelling reasons for an AHJ to require manual shutdown under all circumstances and it is the AHJ prerogative to enforce the arrangement that he deems appropriate. The Standard should not be dictating the AHJ as how fire pumps are to be arranged in his jurisdiction. The AHJ is still the final word on accepting an installation. NFPA 25 requires a person to be in attendance when a fire pump is running. Related Item First Revision No. 66-NFPA 20-2013 [Section No. 12.7.5.2] Submitter Information Verification Submitter Full Name: John Chartier Organization: Northeastern Regional Fire Cod Street Address: City: State: Zip: Submittal Date: Mon Apr 07 12:12:19 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 33 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 19-NFPA 20-2014 [ Section No. 12.7.5.2 [Excluding any Sub-Sections] ] Automatic shutdown shall not be permitted if starting and running causes are present. Delete this clause and revert to extant text of 12.7.5.2 Statement of Problem and Substantiation for Public Comment No good reason has been given for eliminating automatic stopping for pumps which are not sole source pumps. Based on filet experience this will cause any number of pumps to burn up for no good reason. While sole source pumps should require manual stopping, the proposed text is excessively restrictive where multiple pumps are involved. The net result will be to REDUCE, rather than enhance, the reliability of fire protection on many of these cases rather than either maintaining or enhancing said reliability. Also, the proposed wording allows an automatic shutdown in one circumstance even when the AHJ may decide that it must be manual. This is a direct circumvent of the AHJ’s authority as defined in 3.2.2. Indeed, there may be compelling reasons for automatic shutdown during automatic testing and if the AHJ agrees, then so be it. However, if the AHJ has other reasons to require it to be manually shutdown or if the reasoning to shut down automatically is not compelling, the AHJ is still the final word on accepting an installation Related Item First Revision No. 66-NFPA 20-2013 [Section No. 12.7.5.2] Submitter Information Verification Submitter Full Name: James Nasby Organization: Columbia Engineering Street Address: City: State: Zip: Submittal Date: Wed Apr 16 19:27:21 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 34 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 20-NFPA 20-2014 [ Section No. 12.7.5.2.1 ] Delete this clause and revert to extant text of 12.7.5.2 .1 Automatic shutdown shall be permitted only in the following circumstances: (1) * During automatic testing in accordance with 12.7.2.7 . (2) When the engine overspeed shutdown device operates: (3) The controller shall remove power from the engine running devices, prevent further cranking, energize the overspeed fire pump alarm, and lock out until manually reset. (4) Resetting of the overspeed circuit shall be required at the engine and by resetting the controller main switch to the off position. (5) The controller shall not be capable of being reset until the engine overspeed shutdown device is manually reset. (6) Where approved by the authority having jurisdiction. Statement of Problem and Substantiation for Public Comment No good reason has been given for eliminating automatic stopping for pumps which are not sole source pumps. Based on filet experience this will cause any number of pumps to burn up for no good reason. While sole source pumps should require manual stopping, the proposed text is excessively restrictive where multiple pumps are involved. The net result will be to REDUCE, rather than enhance, the reliability of fire protection on many of these cases rather than either maintaining or enhancing said reliability. Also, the proposed wording allows an automatic shutdown in one circumstance even when the AHJ may decide that it must be manual. This is a direct circumvent of the AHJ’s authority as defined in 3.2.2. Indeed, there may be compelling reasons for automatic shutdown during automatic testing and if the AHJ agrees, then so be it. However, if the AHJ has other reasons to require it to be manually shutdown or if the reasoning to shut down automatically is not compelling, the AHJ is still the final word on accepting an installation Related Item First Revision No. 66-NFPA 20-2013 [Section No. 12.7.5.2] Submitter Information Verification Submitter Full Name: James Nasby Organization: Columbia Engineering Street Address: City: State: Zip: Submittal Date: Wed Apr 16 19:33:56 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 35 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 21-NFPA 20-2014 [ Section No. 12.7.5.2.1 ] Delete this clause and revert to extant text of 12.7.5.2. 1 Automatic shutdown shall be permitted only in the following circumstances: (1) * During automatic testing in accordance with 12.7.2.7 . (2) When the engine overspeed shutdown device operates: (3) The controller shall remove power from the engine running devices, prevent further cranking, energize the overspeed fire pump alarm, and lock out until manually reset. (4) Resetting of the overspeed circuit shall be required at the engine and by resetting the controller main switch to the off position. (5) The controller shall not be capable of being reset until the engine overspeed shutdown device is manually reset. (6) Where approved by the authority having jurisdiction. Statement of Problem and Substantiation for Public Comment No good reason has been given for eliminating automatic stopping for pumps which are not sole source pumps. Based on filet experience this will cause any number of pumps to burn up for no good reason. While sole source pumps should require manual stopping, the proposed text is excessively restrictive where multiple pumps are involved. The net result will be to REDUCE, rather than enhance, the reliability of fire protection on many of these cases rather than either maintaining or enhancing said reliability. Also, the proposed wording allows an automatic shutdown in one circumstance even when the AHJ may decide that it must be manual. This is a direct circumvent of the AHJ’s authority as defined in 3.2.2. Indeed, there may be compelling reasons for automatic shutdown during automatic testing and if the AHJ agrees, then so be it. However, if the AHJ has other reasons to require it to be manually shutdown or if the reasoning to shut down automatically is not compelling, the AHJ is still the final word on accepting an installation Related Item First Revision No. 66-NFPA 20-2013 [Section No. 12.7.5.2] Submitter Information Verification Submitter Full Name: James Nasby Organization: Columbia Engineering Street Address: City: State: Zip: Submittal Date: Wed Apr 16 19:35:55 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 36 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 6-NFPA 20-2014 [ Section No. 12.7.5.2.1 ] 12.7.5.2.1 Automatic shutdown shall be permitted only in the following circumstances: (1) * During automatic testing in accordance with 12.7.2.7 , when permitted by the AHJ . (2) When the engine overspeed shutdown device operates: (a) The controller shall remove power from the engine running devices, prevent further cranking, energize the overspeed fire pump alarm, and lock out until manually reset. (b) Resetting of the overspeed circuit shall be required at the engine and by resetting the controller main switch to the off position. (c) The controller shall not be capable of being reset until the engine overspeed shutdown device is manually reset. (3) Where approved by the authority having jurisdiction. Statement of Problem and Substantiation for Public Comment The proposed wording circumvents of the AHJ’s authority by allowing an automatic start then shutdown in the first circumstance even when the AHJ has decided that it must be manual. There are compelling reasons for an AHJ to require manual shutdown under all circumstances and it is the AHJ prerogative to enforce the arrangement that he deems appropriate. The Standard should not be dictating the AHJ as how fire pumps are to be arranged in his jurisdiction. The AHJ is still the final word on accepting an installation. NFPA 25 requires a person to be in attendance when a fire pump is running. Related Public Comments for This Document Related Comment Relationship Public Comment No. 5-NFPA 20-2014 [Section No. 12.7.2.7.1] Related Item First Revision No. 66-NFPA 20-2013 [Section No. 12.7.5.2] Submitter Information Verification Submitter Full Name: John Chartier Organization: Northeastern Regional Fire Cod Street Address: City: State: Zip: Submittal Date: Mon Apr 07 12:16:14 EDT 2014 6/4/2014 9:15 AM National Fire Protection Association Report 37 of 37 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Comment No. 37-NFPA 20-2014 [ Section No. A.11.2.4.3.4.1.1 ] A.11.2.4.3.4.1.1 The pressure sensing line could be installed in a vertical orientation in either the top or bottom of the pipe, however, if it is installed at the bottom it has the opportunity to gather debris, and if it is installed at the top it has the opportunity to receive air. Statement of Problem and Substantiation for Public Comment The section that this is tied to has been proposed for elimination. Even if the section stays, telling people that they can install something vertically when the main body of the standard says that it must be horizontal is wrong. Related Public Comments for This Document Related Comment Relationship Public Comment No. 36-NFPA 20-2014 [Section No. 11.2.4.3.4.1.1] Related Item First Revision No. 72-NFPA 20-2013 [New Section after 11.2.4.3.4.1] Submitter Information Verification Submitter Full Name: Kenneth Isman Organization: National Fire Sprinkler Association Affilliation: NFSA E&S Committee Street Address: City: State: Zip: Submittal Date: Thu May 08 16:57:57 EDT 2014 6/4/2014 9:15 AM Attachment #3: Committee Roster 09/18/2014 Chad Duffy FIM-AAA Address List No Phone Fire Pumps Gayle Pennel Chair Aon Fire Protection Engineering 4 Overlook Point Lincolnshire, IL 60069-4302 Michael E. Aaron Principal Hughes Associates/RJA Group 600 West Fulton Street, Suite 500 Chicago, IL 60661-1241 Alternate: Timothy J. LaRose I 4/17/1998 R. T. Leicht FIM-AAA Secretary State of Delaware Office of State Fire Marshal 4 Drummond Drive Wilmington, DE 19808 International Fire Marshals Association Alternate: Michael R. Moran SE 10/28/2008 Timothy Ballengee FIM-AAA Principal Peerless Pump Company 2500 Regency Parkway Cary, NC 27518 Alternate: Timothy Jordan James A. Beals Principal Jacobs Engineering 1100 North Glebe Road, Suite 500 Arlington, VA 22201 SE 11/2/2006 Thomas R. Boccetti FIM-AAA Principal The DuPont Company, Inc. Brandywine 7211 1007 Market Street Wilmington, DE 19898 NFPA Industrial Fire Protection Section Marinus Both Principal Western States Fire Protection Company d.b.a. Statewide Fire Protection 3130 Westwood Drive Las Vegas, NV 89109 Alternate: Michael Koska IM 7/28/2006 Pat D. Brock FIM-AAA Principal Oklahoma State University Fire Protection & Safety Technology 1424 West Liberty Avenue Stillwater, OK 74075 Alternate: Floyd Luinstra Hugh D. Castles Principal Entergy Services, Inc. 213 Travis Trail Madison, MS 39110 Edison Electric Institute Mohammad Dadgardoust Principal Leber/Rubes Inc. (LRI) 2300 Yonge Street, Suite 2100 Toronto, ON M4P 1E4 Canada Alternate: A. M. Fred Leber U 10/3/2002 Stephen A. Clark, Jr. FIM-AAA Principal Allianz Risk Consulting, LLC 1003 Reece Drive Hoschton, GA 30548 Alternate: Andrew C. Higgins SE 08/09/2012 Alan A. Dorini FIM-AAA Principal Gulfstream Pump & Equipment, Inc. PO Box 14543 Fort Lauderdale, FL 33302 Alternate: Jerald G. Huff E 1/1/1990 FIM-AAA M 3/15/2007 FIM-AAA U 4/3/2003 FIM-AAA SE 7/1/1996 FIM-AAA I 3/4/2008 FIM-AAA IM 1/1/1990 FIM-AAA 1 09/18/2014 Chad Duffy FIM-AAA Address List No Phone Fire Pumps David B. Fuller Principal FM Global 1151 Boston Providence Turnpike PO Box 9102 Norwood, MA 02062-9102 Alternate: Matthew Paine David R. Hague Principal Liberty Mutual Insurance 20 Riverside Road Weston, MA 02493-2231 Alternate: Joseph R. Sanford Hatem Ezzat Kheir Principal Kheir Group 24B Anwer El Mofty Street Nasr City, Cairo, Egypt Alternate: Mohamed Ezzat Kheir Jennifer A. McGrath Principal Pentair 800 Airport Road North Aurora, IL 60542 Alternate: Leroy Franklin James S. Nasby Principal Columbia Engineering 8210 Karlov Avenue Skokie, IL 60076-2736 Milosh T. Puchovsky Principal Worcester Polytechnic Institute Department of Fire Protection Engineering 100 Institute Road Worcester, MA 01609 I 10/6/2000 Dana R. Haagensen FIM-AAA Principal Framingham Fire Department 10 Loring Drive Framingham, MA 01702-8767 Alternate: Bradford T. Cronin I 3/4/2009 Bill M. Harvey FIM-AAA Principal Harvey & Associates, Inc. PO Box 818 Fountain Inn, SC 29644 American Fire Sprinkler Association Alternate: Thomas G. Wellen IM 7/22/1999 John R. Kovacik FIM-AAA Principal UL LLC 333 Pfingsten Road Northbrook, IL 60062-2096 Alternate: Kerry M. Bell M 3/1/2011 Charles W. McKnight FIM-AAA Principal Battelle Energy Alliance PO Box 1625, Mail Stop 3425 Idaho Falls, ID 83415 SE 10/28/2008 Peter Placidus Petrus FIM-AAA Principal Indonesian Fire & Rescue Foundation Indonesian Fire Service Association Jalan Alam Asri 1/TK. 33 Jakarta, 12310 Indonesia SE 8/2/2010 Jeffrey R. Roberts FIM-AAA Principal XL Global Asset Protection Services 128 Twin Oaks Drive Brandon, MS 39047 Alternate: Brandon W. Frakes E 01/14/2005 FIM-AAA IM 7/20/2000 FIM-AAA RT 1/1/1990 FIM-AAA U 7/29/2005 FIM-AAA E 10/18/2011 FIM-AAA I 7/12/2001 FIM-AAA 2 09/18/2014 Chad Duffy FIM-AAA Address List No Phone Fire Pumps Michael A. Rothmier L 03/05/2012 Principal FIM-AAA UA Joint Apprenticeship Committee LU 669 1315 Berrytree Drive Sugarland, TX 77479 United Assn. of Journeymen & Apprentices of the Plumbing & Pipe Fitting Industry Alternate: Gregory A. Bartels Richard Schneider M 1/1/1990 Principal FIM-AAA Joslyn Clark Controls 1202 W. Manor Drive Lancaster, SC 29720 National Electrical Manufacturers Association Alternate: William F. Stelter Darrell A. Snyder Principal Patterson Pump Company 2129 Ayersville Road PO Box 790 Toccoa, GA 30577 Hydraulic Institute Alternate: John P. Kahren M 4/3/2003 Hansford Stewart FIM-AAA Principal Xylem/A-C Fire Pump Systems Dallas Integrated Solutions 10661 Newkirk Street Dallas, TX 75220 Alternate: Brian Buscher Jim Vanden Boogard Principal Cummins NPower, LLC 875 Lawrence Drive De Pere, WI 54115-3910 Alternate: John Laka M 8/5/2009 Terry L. Victor FIM-AAA Principal Tyco/SimplexGrinnell 705 Digital Drive, Suite N Linthicum, MD 21090-2267 National Fire Sprinkler Association Alternate: Kenneth E. Isman John Whitney Principal Clarke Fire Protection Products, Inc. 100 Progress Place Cincinnati, OH 45246-1718 Alternate: Kevin Kunkler Kerry M. Bell Alternate UL LLC 333 Pfingsten Road Northbrook, IL 60062-2096 Principal: John R. Kovacik Bradford T. Cronin Alternate Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Principal: Dana R. Haagensen M 10/10/1998 FIM-AAA IM 10/23/2003 FIM-AAA M 10/1/1996 Gregory A. Bartels L 03/05/2012 FIM-AAA Alternate FIM-AAA Sprinkler Fitters LU 669-JATC 7050 Oakland Mills Road, Suite 100 Columbia, MD 21046 United Assn. of Journeymen & Apprentices of the Plumbing & Pipe Fitting Industry Principal: Michael A. Rothmier RT 4/15/2004 Brian Buscher FIM-AAA Alternate AC Fire Pump Systems 8200 North Austin Avenue Morton Grove, IL 60053-3205 Principal: Hansford Stewart E 8/2/2010 Brandon W. Frakes FIM-AAA Alternate XL Global Asset Protection Services 196 Shady Grove Lane Advance, NC 27006 Principal: Jeffrey R. Roberts M 03/03/2014 FIM-AAA I 10/23/2003 FIM-AAA 3 09/18/2014 Chad Duffy FIM-AAA Address List No Phone Fire Pumps Leroy Franklin Alternate Pentair 800 Airport Road North Aurora, IL 60542 Principal: Jennifer A. McGrath Jerald G. Huff Alternate J&J Fire Protection Inc. 4628 North Hiatus Road Sunrise, FL 33351 Principal: Alan A. Dorini Timothy Jordan Alternate Grundfos/Peerless Pump Company 330 North Division Drive, Suite G Sugar Grove, IL 60554-9800 Principal: Timothy Ballengee Mohamed Ezzat Kheir Alternate Kheir Group 24B Anwer El Mofty Street Nasr City, Cairo, 11371 Egypt Principal: Hatem Ezzat Kheir M 10/23/2013 Andrew C. Higgins FIM-AAA Alternate Allianz Risk Consultants, LLC 38 Kilbride Drive Pinehurst, NC 28374 Principal: Stephen A. Clark, Jr. IM 10/27/2009 Kenneth E. Isman FIM-AAA Alternate National Fire Sprinkler Association, Inc. 40 Jon Barrett Road Patterson, NY 12563-2164 Principal: Terry L. Victor M 03/03/2014 John P. Kahren FIM-AAA Alternate SPP Pumps, Inc. 6716 Best Friend Road Norcross, GA 30071 Principal: Darrell A. Snyder I 03/05/2012 FIM-AAA IM 1/1/1990 FIM-AAA M 10/27/2009 FIM-AAA IM 10/29/2012 Michael Koska IM 08/11/2014 FIM-AAA Alternate FIM-AAA National Fire Suppression/Western States Fire Protection Company 501 Sunshine Road Kansas City, KS 66115-1239 Principal: Marinus Both Kevin Kunkler Alternate Clarke Fire Protection Products, Inc. 3133 East Kemper Road Cincinnati, OH 45241 Principal: John Whitney M 10/23/2013 John Laka FIM-AAA Alternate Cummins NPower, LLC 875 Lawrence Drive De Pere, WI 54115-3910 Principal: Jim Vanden Boogard Timothy J. LaRose Alternate Hughes Associates/RJA Group 6 Centerpointe Drive, Suite 760 LaPalma, CA 92646 Principal: Michael E. Aaron SE 7/29/2005 A. M. Fred Leber FIM-AAA Alternate Leber/Rubes Inc. (LRI) Yonge Eglinton Center 2300 Yonge Street, Suite 2100 PO Box 2372 Toronto, ON M4P 1E4 Canada Principal: Mohammad Dadgardoust M 7/23/2008 FIM-AAA SE 08/09/2012 FIM-AAA 4 09/18/2014 Chad Duffy FIM-AAA Address List No Phone Fire Pumps Floyd Luinstra Alternate Oklahoma State University 499 Cordell South Stillwater, OK 74078 Principal: Pat D. Brock Matthew Paine Alternate FM Global 1151 Boston-Providence Turnpike Norwood, MA 02062-9102 Principal: David B. Fuller SE 10/18/2011 Michael R. Moran FIM-AAA Alternate State of Delaware Office of the State Fire Marshal 2307 MacArthur Road New Castle, DE 19720 International Fire Marshals Association Principal: R. T. Leicht E 10/4/2001 FIM-AAA I 10/23/2013 Joseph R. Sanford FIM-AAA Alternate Liberty Mutual Property Risk Engineering 20 Riverside Road Weston, MA 02493-2231 Principal: David R. Hague I 8/5/2009 FIM-AAA William F. Stelter M 7/1/1993 Alternate FIM-AAA Master Control Systems, Inc. 910 North Shore Drive PO Box 276 Lake Bluff, IL 60044 National Electrical Manufacturers Association Principal: Richard Schneider Thomas G. Wellen Alternate American Fire Sprinkler Association, Inc. 12750 Merit Drive, Suite 350 Dallas, TX 75251 Principal: Bill M. Harvey Edward D. Leedy Member Emeritus 2033 Butterfly Lane, CC304 Naperville, IL 60563 1/1/1990 James W. Nolan FIM-AAA Member Emeritus James W. Nolan Company 633 Florence Drive Park Ridge, IL 60068 Chad Duffy Staff Liaison National Fire Protection Association 1 Batterymarch Park Quincy, MA 02169-7471 4/18/2011 FIM-AAA IM 11/2/2006 FIM-AAA 1/1/1965 FIM-AAA 5