1277 Perimeter Parkway Virginia Beach VA 23454 Phone: 757 499 7223 Fax: 757 301 6060 E-01 Revised Version SHOP DRAWING TRANSMITTAL COMPANY: Tymoff + Moss Architects DATE: 7/22/14 512 Botetourt Street Norfolk, VA 23510 ATTENTION: Michael Schnekser Reviewer: Robert Weise, EIT REFERENCE: HRT BUS TRANSFER FACILITY PACE Project: 13165 DOWNTOWN NORFOLK WE TRANSMIT THE FOLLOWING: Copies Date Received Description email 7/14/14 Electrical Materials Action A&R THESE ITEMS ARE TRANSMITTED: COMMERCIAL: GOVERNMENT: (NET) NO EXCEPTIONS TAKEN (MCN) MAKE CORRECTIONS NOTED (A&R) AMEND & RESUBMIT (R) REJECTED - SEE REMARKS (RA) RECEIPT ACKNOWLEDGED (A) APPROVED (AN) APPROVED AS NOTED (R) REVISE & RESUBMIT (D) DISAPPROVED (RA) RECEIPT ACKNOWLEDGED REVIEW COMMENTS: 1. General: a. Revised shop drawings should be submitted individually according to the specification section for which they are required 2. Panelboards a. Provide verification of the available fault current from DVP to ensure equipment is properly rated b. Ensure circuit breaker for the FACP is provided with red markings and provisions to be locked in the on position c. Coordinate circuit breaker ratings for all mechanical loads with approved shop drawing submittals 3. Surge Protection Devices a. Include copy of UL certifications and OCPD requirements per 264313 (1.2)(A)(2) b. Coordinate circuit breaker rating in Panel “LV1” c. The peak surge current shall be 200kA per 264313 (2.3)(B) d. Provide additional documentation to demonstrate compliance with 264313 (2.3)(C-E) 4. Safety Switches a. Coordinate safety switch and fuse ratings for all mechanical loads with approved shop drawing submittals b. Fusible switches shall have a neutral kit and Class-R fuse kit per 262816 (2.1)(B) 5. Occupancy Sensors: a. Include additional information for ceiling mounted occupancy sensors b. Coordinate wall plate finish selection with Architect Color to be White 6. Lighting Fixtures: a. General: i. Luminaire quantities not reviewed Color to be Aluminum b. Type-EBU i. Coordinate housing color with Architect ii. Coordinate trim finish for remote power supply with Architect iii. Fixtures shall be mullion mounted Remote power supply to c. Type-A2 & A2-em be located in adjacent i. Coordinate shielding selection with Architect ceiling. Color to be White ii. Provide performance reflector iii. Provide flange kit as required Shielding type to be Rail iv. Provide programmed start ballasts per 265100 (2.3)(B) d. Type-A4 & A4-em i. Coordinate shielding selection with Architect Shielding type to be Rail ii. Provide performance reflector iii. Provide programmed start ballasts per 265100 (2.3)(B) e. Type-C & C-em i. Provide prismatic lens f. Type-D i. Provide high impact pearlescent acrylic lens ii. Provide programmed start ballasts per 265100 (2.3)(B) g. Type-E & E-em Provide physical finish i. Provide programmed start ballasts per 265100 (2.3)(B) samples for coordination h. Type-S1 i. Coordinate finish selection with Architect i. Type-S1 (VE) i. The Erco "Light Scoop" fixture was used as a basis of design and used for site plan approval from the City of Norfolk. Provide calculations for approval by the Engineer to ensure lighting levels and uniformity ratios are equivalent to those submitted to the City. ii. Confirm NEMA distribution type is equivalent to the basis of design fixture iii. Coordinate finish selection with Architect Provide physical finish j. Type-S2 samples for coordination i. Coordinate finish selection with Architect k. Type-S2 (VE) i. The Hess "Canto G" fixture was used as a basis of design and used for site plan approval from the City of Norfolk. Provide calculations for approval by the Engineer to ensure lighting levels and uniformity ratios are equivalent to those submitted to the City. ii. Confirm lumen output and NEMA distribution type is equivalent to the basis of design fixture iii. Coordinate finish selection with Architect l. VE Poles for Type-S2, S3, and S4 i. Ensure poles are rated to withstand winds of 110mph Provide physical finish ii. Coordinate finish selection with Architect samples for coordination m. Type-S3 i. Coordinate finish selection with Architect n. Type-S4 i. Coordinate finish selection with Architect o. Type-S5 i. Coordinate finish selection with Architect p. Type-S5 (VE) i. The Forms and Surfaces "Lightscale Bollard" fixture was used as a basis of design and used for site plan approval from the City of Norfolk. Provide calculations for approval by the Engineer to ensure lighting levels and uniformity ratios are equivalent to those submitted to the City. FILE: SHOP DRAWINGS ii. VE fixture does not appear to provide an equivalent lumen output as the basis of design fixture iii. Coordinate finish selection with Architect SHOP DRAWING REVIEW Review is for general compliance with contract documents. No responsibility is assumed for correctness of dimensions or details. NO EXCEPTIONS TAKEN MAKE CORRECTIONS NOTED AMEND & RESUBMIT X REJECTED SEE REMARKS RECEIPT ACKNOWLEDGED PACE Collaborative, P.C. Date: 8/7/14 BY (P/M): Date: 8/7/14 BY (E): RTW/mlm FILE: SHOP DRAWINGS NA RTW The owner's current direction is to provide the "as specified" lighting package. Comments for the VE options have been included in the event that the direction changes. Lighting Virginia East Lighting Submittals 596 Central Drive Suite 110 Project # 14040 HRT Bus Transfer Station Virginia Beach, VA 23454 Norfolk, VA 757 463 1100 T www.LightingVirginia.com 800 316 6113 T www.FirstLightVA.com Date: To: From: First Light 757 463 0010 F Type Qty Manufacturer May 16, 2014 11:20 Mayer - Del Slaughter Mike Bivens Catalog Number Volts .os clg 5 HBA OMNIDT2000 .os clg pp 5 HBA UVPP 120/277 .os wall 4 HBA LHMTS1 (A,B,G,I,W) (please select a standard finish) 120/277 .ebu 9 SignTex MUE BB 10 X X (please select color and mounting) .ebu 9 SignTex RPS BB ML X (please select color) 120/277 .exit1 6 Exitronix S902-WB-SR-RC-BA 120/277 Exitronix S903-WB-SR-RM-BA 120/277 .exit2 - 24 12/24V .control panel 1 HBA CX082S083LM 120/277 .light sensor 1 HBA LUXSTATLSO 24 A2 2 Columbia SER22-217G-(X)(X)-EU (X=please select shielding & reflector) 120/277 A2 em 3 Columbia SER22-217G-(X)(X)-EU-EL141ST (X=please select shielding & reflector) 120/277 A4 5 Columbia SER24-232G-(X)(X)-EU (X=please select shielding & reflector) 120/277 A4 em 1 Columbia SER24-232G-(X)(X)-EU-EL141ST (X=please select shielding & reflector) 120/277 B 18 Prescolite MD8LED 3L 35K 8 8MD 3L MD25 SL B24 120/277 C 12 Vantage 8HF132E1/2 / 8611SCL 120/277 C em 4 Vantage 8HF132E1/2EM / 8611SCL 120/277 D 4 Kenall RHL7 24 MW PP 217 IS 1 DV 120/277 E 7 Columbia KL4 232 U EU S18 120/277 E em 4 Columbia KL4 232 U EU S18 EL141ST 120/277 G LF 27 iLight T24 W35 S CL27' NC 00 S1 54 Erco 33237.023 (please confirm finish) 120/277 S1 ve 54 Spaulding ARF2-K-20L-4K-070-W-U-PS (please confirm finish) 120/277 S2 18 CC450 2LV NW ME UNV A 17RC X oDEG (X = please select finish) 120/277 HessAmerica 120/24 Lighting Virginia East Lighting Submittals 596 Central Drive Suite 110 Project # 14040 HRT Bus Transfer Station Virginia Beach, VA 23454 Norfolk, VA 757 463 1100 T www.LightingVirginia.com 800 316 6113 T www.FirstLightVA.com Date: To: From: First Light 757 463 0010 F Type Qty Manufacturer May 16, 2014 11:20 Mayer - Del Slaughter Mike Bivens Catalog Number S2 ve 18 Spaulding CL1S A 32L U 4K 5W PS RPA4 (please confirm finish) S2 ve pole 18 Nafco RSS16-404C (please confirm finish) S3 6 Kim 1SA ALT3P35 96L 4K 120-277 X VSF-1SA (please select finish) S3 pole 6 Nafco RSS30-505D (with 2-3/8" X 4" tenon) (please select finish) S4 2 Kim 2SB ALT3P35 96L 4K 120-277 X VSF-2SB (please select finish) S4 pole 1 Nafco RSS30-505D (with 2-3/8" X 4" tenon) (please select finish) Volts 120/277 120/277 120/277 S5 22 Forms & Surfaces LBLSC-CF (please advise finish selection) 120/277 S5 ve 22 Trace-Lite 120/277 TLED B 24 DT X (please advise finish selection) TYPE .os clg pp - 120/277-24V Power Packs and Relays Universal Voltage Power Pack KEY FEATURES • Universal voltage (100–277 VAC; 50/60Hz) • Automatic voltage detection • Electrical load switching capablity: maximum of 20 Amps • Regulated 24 VDC current; 150mA output; short circuit protected • Zero Arc Point Switching • Plenum rated • Mounts: inside or outside a junction box; inside a fluorescent ballast cavity • Available with exclusive Quick to Install (QTI) connector • UL and cUL listed • 5-year warranty UVPP OVERVIEW The Universal Voltage Power Pack is a self-contained transformer and relay (an ON/OFF switch controlled by a circuit) designed for low-voltage 24 VDC occupancy sensors. The power pack supports and automatically detects the line-voltage input within the 100–277 VAC range. This eliminates the need for voltage-specific power packs. This power pack is capable of switching 20A loads and features Zero Arc Point Switching, minimizing relay-contact wear from high inrush loads. A single power pack can power either 4 sensors or 3 sensors and the MPSA auxiliary relay for multiple circuits. The Universal Voltage Power Pack is plenum rated and easily mounts either inside or outside a junction box or inside a fluorescent ballast cavity. FEATURES and BENEFITS Features Universal voltage (100–277VAC; 50/60Hz) Automatic voltage detection Zero Arc Point Switching Plenum rated Optional Quick To Install (QTI) connector Benefits • Eliminates the need for specific power packs • No “specialized wiring” required. It wires the same for all applications and automatically detects the line voltage being used • Minimizes relay-contact wear from high inrush loads • Complies with requirements for use in a plenum area • Dramatically reduces installation costs by removing the timeconsuming process of manually wiring a sensor to a power pack • Easy to install; fast and efficient; no cutting, stripping, or wire nuts required Hubbell Building Automation, Inc. | 9601 Dessau Road | Building One | Austin, Texas 78754 | {512} 450-1100 | {512} 450-1215 fax hubbell-automation.com 1.2009 TYPE .os clg pp - 120/277-24V SPECIFICATIONS Power requirements • • • • • • • • • • • • • • • • Output Relay contact rating Construction Plenum rated Operating environment Size Color Certifications Warranty How To Order Catalog Number UVPP 100–277 VAC; 50/60Hz Single phase only 24 VDC; 150mA nominal, isolated, and regulated 20A: 120 VAC Incandescent 20A: 120 or 277 VAC Ballast 1HP: 120 or 277 VAC Motor Load High-impact UL 94-5V plastic Complies with requirements for use in a plenum area Plenum rated for external junction box mounting Indoor use only Operating temperature: 32o–104o F (0o–40o C) Relative humidity (non-condensing): 0%–95% 3.69” x 2.33” x 1.36” Black UL and cUL listed 5 years Description Universal Voltage Power Pack, 100-277VAC, 50/60Hz * Add QTI to end of catalog number for optional Quick To Install connector. WIRING DIAGRAM UVPP Power Pack Hubbell Building Automation, Inc. 9601 Dessau Road | Building One | Austin, Texas 78754 {512} 450-1100 | {512} 450-1215 fax hubbell-automation.com (please select color) TYPE .os wall - 120/277V Wall Switch Occupancy Sensors LightHawk™ Multi-Technology Wall Switch Sensor featuring IntelliDAPT® KEY FEATURES • All-digital dual technology (ultrasonic [US] and passive infrared [PIR]) sensor • IntelliDAPT self-adaptive technology—no manual adjustment required • Auto-on and manual-on operating modes (depending on model) • 1,000 square-foot, 180° coverage area • Built-in photocell with SuperSaver™ mode • RhinoTuff™ lens • Dual 120/277 VAC operation • No minimum load requirement • Zero Arc Point Switching • ETL, UL, and cUL listed • Five-year warranty LHMTS1 LHMTS0 OVERVIEW LHMTS sensors combine ultrasonic (US) and passive infrared (PIR) technologies for unequaled occupancy detection and false trip immunity. These sensors feature Hubbell Building Automation’s patented IntelliDAPT technology, which makes all the sensor adjustment decisions automatically. Throughout the product’s lifespan, smart software analyzes the controlled area and makes digital adjustments to sensitivity and timer settings. Occupancy sensors with IntelliDAPT provide a maintenance-free install-and-forget operation. With selectable operating modes—automatic ON/OFF or manual ON/automatic OFF—and a builtin photosensor for automatic daylight harvesting, LHMTS sensors are the most capable choice in today’s market place. FEATURES and BENEFITS Features IntelliDAPT technology All-digital dual technology (ultrasonic [US] and passive infrared [PIR]) sensor) Auto-on and manual-on operating modes (depending on model) Tamper-proof automatic-only version available RhinoTuff lens Built-in photocell with optional SuperSaver mode Benefits • Sensor automatically determines the ideal setting for an area • No manual sensitivity or timer adjustments required • Provides a maintenance-free install-and-forget operation • Superior US minor-motion detection with excellent PIR longrange major-motion detection • Provides auto-on/auto-off and manual-on/auto-off operations • Automatically turns lighting on and off without requiring the user to push a button • Impact-resistant infrared (IR) lens • Increases energy savings by preventing lights from turning on when there is sufficient natural light • Optional SuperSaver mode—turns lights off during periods of occupancy if there is enough natural light to illuminate the area Hubbell Building Automation, Inc. | 9601 Dessau Road | Building One | Austin, Texas 78754 | {512} 450-1100 | {512} 450-1215 fax hubbell-automation.com 9.2011 (please select color) SPECIFICATIONS IntelliDAPT technology Timer timeout Ultrasonic (US) output Passive infrared (PIR) Photocell Coverage Power requirements Electrical ratings Load requirements Operating environment Construction Size and weight Color Mounting Certifications Warranty TYPE .os wall - 120/277V • Self-adjusting timer • Self-adjusting ultrasonic (US) and passive infrared (PIR) sensitivity • Automatic false-on/false-off corrections • No manual adjustments required • Auto mode: 4–30 minutes; self-adjusts based on occupancy • Fixed mode: 4, 8, 15, and 30 minutes • Test mode: 5 seconds • 40kHz output • Dual-element pyrometer and 12-element cylindrical RhinoTuff lens • Natural light override range: 10–500 foot-candles • 1,000 square-foot, 180° coverage area • 120/277 VAC; 50/60Hz • 120 VAC: 800W Incandescent; 1,000W Fluorescent; 1/6 HP • 277 VAC: 1,800W Fluorescent; 1/6 HP • None • Indoor use only • Operating temperature: 32°–104°F (0°–40°C) • Relative humidity (non-condensing): 0–95% • Casing—high-impact injection-molded plastic (UL-94-5V) • Impact-resistant lens • Color-coded leads are 6” long • Size: 4.2” x 1.8” x 2.1”; .37” extension • Weight: 2.9 oz • White; Ivory; Light Almond; Gray; Black • Single-gang NEMA-style switch box (average switch box) • Decorator-style wall plate not included • ETL, UL, and cUL listed • Five years ORDERING INFORMATION Catalog Number Description LHMTS1* Ultrasonic and PIR Wall Switch Sensor with IntelliDAPT and Automatic/Manual Control, 120/277VAC LHMTS0* Ultrasonic and PIR Wall Switch Sensor with IntelliDAPT and Automatic Only Control, 120/277VAC * = W – White, I – Ivory, A – Light Almond, G – Gray, B – Black WIRING DIAGRAM RANGE DIAGRAM *Refer to Application Guide. Hubbell Building Automation, Inc. 9601 Dessau Road | Building One | Austin, Texas 78754 {512} 450-1100 | {512} 450-1215 fax hubbell-automation.com TYPE .ebu - 12/24V (please select color & mounting) Moonlite LED™ Mullion Mount Emergency Light Outdoor Egress Series MUE MUE.02.13.09 The Brightest Idea is Emergency Lighting with LEDs GENERAL DESCRIPTION Operating in either normal-on or emergency mode, this fixture is designed to mount directly on structural mullion beams used in typical glass-fronted entrances, with vertical surface as small as 2”. This fixture has full 90° cut-off and will provide efficient emergency lighting in front of egress doorways, or along extended pathways. series MUE CONSTRUCTION • Rugged extruded aluminum housing with stainless hardware is corrosion proof. • Wet location listed UL 924. Certified IP66. • Uniform, high brightness lighting over the path of egress. • Full 90° cut- off. ENERGY EFFICIENT OPERATION • Dual function operation for normally on night or security lighting as well as emergency lighting. • Very low power consumption in night/ security mode. The security lighting circuit is independent of emergency lighting and may be switched manually, by an exterior photocell, or other automatic means. • Three versions are available: • Over 50,000 hour lamp life in normal use. RE= Central Battery System Series CBS or other qualified source 12V- 24 VDC. BB= Battery backup from Remote Battery Supply Series RPS. AC= 120VAC supply: 277 VAC option. • IES photometric data available for all models. CODES ELECTRONICS • Manufactured and tested to UL Standard 924 and NFPA Life Safety Code 101. • Dual operation from either a battery or normally on power source. WARRANTY • Lamps are connected in parallel-series strings, as required to meet requirements of NEC and Life Safety Codes. Lighting continues even after failure of One lamp or circuit. • 5 year total customer satisfaction warranty. For Details see product catalog technical data section. D E S I G N E D & M A D E I N E INT RTEK CM US LISTED FIXTURE SCHEDULE MODEL CATALOG NO APPROVAL JOB INFORMATION T H E U S A 2003529 Signtex Inc LIGHTING SPECIFIED EMERGENCY LIGHTING TYPE .ebu - 12/24V (please select color & mounting) Moonlite LED™ Mullion Mount Emergency Light Outdoor Egress Series MUE MUE.02.13.09 SPACING GUIDE SUGGESTED SPECIFICATIONS: Supply and install the MOONLITE LED Series MUE Mullion Mount emergency lighting fixture manufactured by Signtex Lighting Inc. The MUE assembly shall be listed for installation in wet locations in compliance with UL 924 and IP66 standards and shall be capable of operating from Signtex remote power supply Series RPS, the Signtex central battery system Series CBS, or from other remote power sources supplying 12-24 VDC or VAC. Upon loss of AC building power, emergency models shall operate for a minimum of 90 minutes in compliance with UL Standard 924 and NFPA LSC 101. 2 5' 12' MOUNTING DATA & DIMENSIONS: MULLION MOUNT L Average Illuminance 1 Fc Model Shown: MUE 10 Watts NOTE: FOR REFERENCE ONLY. STANDARD REFLECTANCES 80/50/20. SIGNTEX IS NOT RESPONSIBLE FOR SPECIFIC CONDITIONS THAT MAYALTER THE RESULTS. 5" CONTACT SIGNTEX FOR LAYOUT ASSISTANCE 1 1/2" 2 1/2" Code Compliant Emergency lighting layouts provided free of charge! BATTERY & AC ONLY MODELS 2 1/4" TOP MOUNT 2 3/4" MOUNT SCREW LOCATIONS INPUT 120/277 VAC GLASS PANEL MUE MULLION RPS See RPS Data Sheet OUTPUT 4.8V - 24V MAX WIRING LENGTH FROM RPS TO FIXTURE LENGTH (FT) WIRING SIZE AWG BB & AC BB and AC Models: 4 Conductors RE Models: 3 Conductors Emergency Power Rating (EPR): 10 WATTS Security Power Rating (SPR): 10 WATTS #20 100 #18 170 RPS SELF- TEST DIAGNOSTIC FUNCTIONS #16 225 BB MODELS WITH DG FUNCTION STATUS LENGTH TABLE L POWER 10 Watts 10" 20 Watts* LED DISPLAY NORMAL FULL CHARGE NORMAL FAST CHARGE FAILED BATTERY FAILED LAMP FAILED TRANSFER FAILED CHARGER 21" WIRING Typical Specification: UL AWM Style: Control Cable #20 AWG 300V 2 conductors. GREEN ON ORANGE ON RED FLASH FAST GREEN FLASH ORANGE FLASH RED FLASH SLOW *RE and AC models only SECURITY / NIGHT LIGHTING BB Models with SW Option RE Models (All) EM Watts SEC Power- Watts 10 20 10 20 SW OPTION CONTROL WIRING Standard BB = Connect ORANGE & GREEN wires together to turn ON BB with DG Option= Connect BLUE wire to voltage source from 10V to 300V AC or DC to turn ON FIXTURE ORDERING INFORMATION: EXAMPLE: MUEBB10AW-DG MUE BB BB MODEL SERIES OPERATION RE= Central Battery or other 12- 24 VDC Remote Source BB= Battery Backup (Requires RPS) AC= No Battery (Requires RPS) MUE 10 10 X A X W -DG EMERGENCY POWER RATING HOUSING COLOR MOUNT OPTIONS 10= 10 Watts 20= 20 Watts* *RE and AC models only. See Length Table. W= Satin White A= Aluminum X= Custom T= Top W= Wall DG= Battery Diagnostics* SW= Security Lighting with Control Switch* 2HT= 2" Canopy Height Signtex Inc LIGHTING SUITABLE FOR WET LOCATIONS *BB Models Only AMBIENT TEMPERATURE LIMITS: Standard "BB" models: -20º C to +40º C Remote models: -40º C to +50º C DISTRIBUTOR: 220 VFWAvenue, Grasonville,MD21638 TEL:(410)827-8300 Fax:(410)827- 8866 Specifications and Dimensions subject to change without notice. sales@signtexinc.com www.signtexinc.com TYPE .ebu - 120/277V (please select color) Remote Power Supply For Moonlite Emergency Fixtures & Exit Signs Series RPS RPS.06.12.05 GENERAL DESCRIPTION The Remote Power Supply is capable of powering any MOONLITE LED or LED Exit sign manufactured by Signtex Lighting, Inc. The RPS can be mounted in any accessible wall or ceiling. A removable cover allows easy access to the electronics for service. Available with battery backup or AC supply only. INPUT 120/277 VAC REMOTE EXIT RPS ELECTRONICS • Isolated, all solid state power supply with 2- wire universal input from 120 VAC to 277 VAC with precise current and voltage regulation. • Power supply is surge and spike protected, with a low voltage disconnect. • The complete power supply module with optional NICAD battery pack is sealed within a phenolic plastic enclosure. AC and DC wiring is quickly attached with plug connectors. BB Models: 3 Conductors AC Models: 2 Conductors INPUT 120/277 VAC MOONLITE LED RPS DIAGNOSTICS OPTION • An advanced microprocessor monitors all charger functions and battery condition continuously and automatically performs all tests and visual indications required by UL Standard 924. BB and AC Models: 2 Conductors CODES • Manufactured and tested to UL Standard 924. Conforms to NFPA Life Safety Code 101, UBC and NEC. WARRANTY • 5 year total customer satisfaction warranty. For details see product catalog technical data section. D E S I G N E D & M A N U F A C T U R E D ERTEK INT CM US LISTED I N FIXTURE SCHEDULE MODEL APPROVAL T H E U S A 2003529 CATALOG NO JOB INFORMATION Signtex Inc LIGHTING SPECIFIED EMERGENCY LIGHTING TYPE .ebu - 120/277V (please select color) Remote Power Supply For Moonlite Emergency Fixtures & Exit Signs Series RPS RPS.06.12.05 SUGGESTED SPECIFICATIONS: Supply and install the Remote Power Supply Series RPS manufactured by Signtex Lighting Inc. The RPS will be capable of operating any exit sign or MOONLITE LED emergency fixture manufactured by Signtex Lighting Inc. and shall be available with a NICAD battery and charger with universal 120/277 VAC input, to supply emergency lighting operation for a minimum of 90 minutes in compliance with UL Standard 924 and NFPA LSC 101, or as a power supply without battery. The RPS shall also be capable of operating MOONLITE LED fixtures manufactured by Signtex in normally- on or continuous mode, from 120/277VAC power input. MOUNTING DATA & DIMENSIONS: INPUT 120/ 277 VAC MAX WIRING LENGTH FROM RPS TO FIXTURE LENGTH (FT) WIRING SIZE AWG BB & AC 8 1/2” STATUS INDICATOR PUSH TO TEST #20 100 #18 170 #16 225 5” 3 3/4” 0UTPUT 5 V - 24 V 7 3/8” BACK BOX ACCESS COVER SELF- TEST DIAGNOSTIC FUNCTIONS STATUS 3 1/2" STANDARD MASONRY BOX 3 3/4" X 3 1/2" X 7 3/8" (SUPPLIED BY OTHERS) TYPICAL STOCK MODELS: CROUSE HINDS #TP693 RACO # 698 ORDERING INFORMATION: EXAMPLE: RPSBBMLW-DG RPS ML BB LED DISPLAY NORMAL FULL CHARGE NORMAL FAST CHARGE FAILED BATTERY FAILED LAMP FAILED TRANSFER FAILED CHARGER X W GREEN ON ORANGE ON RED FLASH FAST GREEN FLASH ORANGE FLASH RED FLASH SLOW -DG MODEL SERIES OPERATION FIXTURE TRIM FINISH OPTIONS RPS=REMOTE POWER SUPPLY BB= Battery Backup NB=No Battery ML= Moonlite LED EX= Exit LED W= White A= Aluminum X= Custom DP = Damp Location DG = Battery Diagnostics DAC= Dual AC Input (120 VAC) SW = Security Lighting Control Switch HS = High Power Security Lighting Signtex Inc LIGHTING DISTRIBUTOR: 220 VFWAvenue, Grasonville,MD21638 TEL:(410)827-8300 Fax:(410)827- 8866 Specifications and Dimensions subject to change without notice. sales@signtexinc.com www.signtexinc.com TYPE .exit1 - 120/277V S900 Series universal swivel mount led edge-lit exit sign Model Number: Accessories: Job:Type: Approvals: Features •Pivoting design for simple installation in any application, including wall, ceiling, sloped ceiling or recessed mounting in single or double face configurations •Truly universal (“SR”) model includes surface mounting canopy as well as back box for recessed mounting applications •Die-cast aluminum housing with high-grade, optically true, acrylic panel •Compact, low profile design Wall •Low energy consumption Ceiling •Mirror panel supplied as a standard on all double-faced signs •ETL listed 90 minute emergency run time, 24 hour recharge time •Low voltage disconnect eliminates deep discharge •Optional Guardian Self-Test/Self-Diagnostics (G2) available •Constant, uniform illumination by long-life, high intensity, red or green LEDs •Fully-illuminated 6” characters with 3/4” stroke End •Field applicable chevrons provided Sloped Ceiling •120/277V dual primary, 60Hz input •Standard finishes: White or brushed aluminum •Suitable for damp location Recessed Warranty Any component that fails due to manufacturers defect is guaranteed for 5 years with a separate 3 year pro-rated warranty on the battery. The warranty does not cover physical damage, abuse or acts of God. Manufacturer reserves the right to charge for such repairs if deemed necessary. SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE ORDERING INFORMATIONExample: S902-WB-SR-RM-BA-G2 Series Power Source Mounting Panel Color Finish Options (Factory Installed) S902 = Single Face LB = AC Only S = Surface Single Face WH = White G2 = Self-Test/Self-Diagnostics S903 = Double Face WB = With Battery SR1 = Universal RC = Red Letters/Clear Panel BA = Brushed Alum. GC = Green Letters/Clear Panel Double Face RM = Red Letters/Mirror Panel GM = Green Letters/Mirror Panel 1 SR option includes kits for surface & recessed mounting 10800157 02/13 TYPE .exit1 - 120/277V CONSTRUCTION Housing Available in either a powder coated or brushed aluminum finish. INSTALLATION Surface Mounting: Completely universal canopy provides for side, ceiling or flush mounting. All hardware is included. Surface Mounting Engineering grade aluminum extrusion with mounting canopy Recessed Mounting: Recessed ceiling mount, accessible above the plenum. Electronics and battery contained in housing. Plug-in battery connector supplied for easy installation. All hardware is included. Recessed Mounting Extruded aluminum housing supplied with galvanized steel adjustable bar hanger assembly. Panels Constructed of high quality, optically true, clear acrylic with beveled lettering for maximum light output. Exit letters are 6" high with a 3/4" stroke. Double face panels are supplied with a mirror insert. Units are supplied with press-on directional arrows for placement in all applications. Stencil letters are 6” high with 3/4” stroke, with minimum of 100 ft viewing distance rating as required by UL924 standard. ILLUMINATION High output red or green LEDs provide superior brightness. Energy consumption of less than 3 watts for AC only or less than 5 watts for battery back-up units. LEDs are a maintenance-free solution, providing up to 100,000 hours of use without failure. ELECTRICAL Input Dual-voltage input 120 or 277VAC @ 60Hz OPTIONS Guardian Self-Test/Self-Diagnostics (Option: G2) The Guardian circuit continuously monitors the operating condition of the AC power, battery supply voltage, emergency lamp continuity and charging circuit. The purpose of this option is to provide visual signaling in response to a fault at the EXIT sign battery and/or battery charger. If a failure is detected, visual status will occur immediately via the CHARGER LED and/or the BATTERY FAULT LED. The LEDs will stay illuminated until the fault is corrected. The Guardian circuit also monitors the transfer circuit as well as performing automatic code compliant testing. The Guardian circuit will perform a 30 second discharge and self-test every 28-30 days. A 90 minute discharge and self-test is performed every 6 months. CONFORMANCE TO CODES & STANDARDS The S900 Series is ETL listed and meets or exceeds the following: UL 924, NEC requirements and NFPA 101. DIMENSIONS Sealed Nickel Cadmium Battery - NiCad (With Battery Only) Exitronix sealed nickel cadmium batteries are maintenance-free with a life expectancy of 15 years. Nickel cadmium batteries offer high discharge rates and continue to perform in a vast temperature range from 0-40 degrees C. NiCad technology provides long lasting, safe and reliable performance by utilizing the jelly-roll design and allows a Ni-Cad cell to deliver a much higher maximum current than an equivalent size alternative battery. As a relatively larger area of the electrode is in contact with the active material in each cell, the internal resistance for an equivalent sized NiCad cell is lower which increases the maximum current that can be delivered. Brownout Circuit The brownout circuit monitors the flow of AC current to the unit and triggers the emergency lighting system once a set reduction of AC power occurs. This dip in the voltage will cause many fixtures to extinguish causing loss of normal lighting even though a total power failure has not occurred. Low Voltage Disconnect When the battery’s terminal voltage falls below predetermined levels, the low-voltage circuit disconnects the emergency lighting load. The disconnect remains in effect until normal power is restored, preventing deep battery discharge and improving the life of the battery. The disconnect will also automatically reconnect the load circuit once the battery voltage returns to a normal value after charging. 3.5” 13” 1.63” 9.63” 8.68” 3.13” 14.96” 2.81” 4” Solid-State Transfer The unit features a solid-state switching transistor which eliminates damaged contacts or mechanical failures associated with relays. The switching circuit is designed to detect a loss of AC power and automatically energizes the lamps. Upon restoration of the AC voltage, the emergency lamps will switch off and the charger will automatically recharge the battery. Overload and Short-Circuit Protection The solid-state overload monitoring system in the DC circuit disconnects the lamp load from the battery should excessive wattage demands be made and automatically resets when the overload or short-circuit is removed. This overload current protective characteristic eliminates the need for fuses or circuit breakers for the DC load. Test Button Our easily located test button allows for manual verification of proper operation of the transfer circuit and emergency lamps. 1911 W. Parkside Lane • Phoenix, AZ 85027 (800) 533-3948 • Fax: (623) 580-8948 www.exitronix.com • www.barronltg.com 7.5” 12.69” TYPE .exit2 - 120/277V S900 Series universal swivel mount led edge-lit exit sign Model Number: Accessories: Job:Type: Approvals: Features •Pivoting design for simple installation in any application, including wall, ceiling, sloped ceiling or recessed mounting in single or double face configurations •Truly universal (“SR”) model includes surface mounting canopy as well as back box for recessed mounting applications •Die-cast aluminum housing with high-grade, optically true, acrylic panel •Compact, low profile design Wall •Low energy consumption Ceiling •Mirror panel supplied as a standard on all double-faced signs •ETL listed 90 minute emergency run time, 24 hour recharge time •Low voltage disconnect eliminates deep discharge •Optional Guardian Self-Test/Self-Diagnostics (G2) available •Constant, uniform illumination by long-life, high intensity, red or green LEDs •Fully-illuminated 6” characters with 3/4” stroke End •Field applicable chevrons provided Sloped Ceiling •120/277V dual primary, 60Hz input •Standard finishes: White or brushed aluminum •Suitable for damp location Recessed Warranty Any component that fails due to manufacturers defect is guaranteed for 5 years with a separate 3 year pro-rated warranty on the battery. The warranty does not cover physical damage, abuse or acts of God. Manufacturer reserves the right to charge for such repairs if deemed necessary. SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE ORDERING INFORMATIONExample: S902-WB-SR-RM-BA-G2 Series Power Source Mounting Panel Color Finish Options (Factory Installed) S902 = Single Face LB = AC Only S = Surface Single Face WH = White G2 = Self-Test/Self-Diagnostics S903 = Double Face WB = With Battery SR1 = Universal RC = Red Letters/Clear Panel BA = Brushed Alum. GC = Green Letters/Clear Panel Double Face RM = Red Letters/Mirror Panel GM = Green Letters/Mirror Panel 1 SR option includes kits for surface & recessed mounting 10800157 02/13 TYPE .exit2 - 120/277V CONSTRUCTION Housing Available in either a powder coated or brushed aluminum finish. INSTALLATION Surface Mounting: Completely universal canopy provides for side, ceiling or flush mounting. All hardware is included. Surface Mounting Engineering grade aluminum extrusion with mounting canopy Recessed Mounting: Recessed ceiling mount, accessible above the plenum. Electronics and battery contained in housing. Plug-in battery connector supplied for easy installation. All hardware is included. Recessed Mounting Extruded aluminum housing supplied with galvanized steel adjustable bar hanger assembly. Panels Constructed of high quality, optically true, clear acrylic with beveled lettering for maximum light output. Exit letters are 6" high with a 3/4" stroke. Double face panels are supplied with a mirror insert. Units are supplied with press-on directional arrows for placement in all applications. Stencil letters are 6” high with 3/4” stroke, with minimum of 100 ft viewing distance rating as required by UL924 standard. ILLUMINATION High output red or green LEDs provide superior brightness. Energy consumption of less than 3 watts for AC only or less than 5 watts for battery back-up units. LEDs are a maintenance-free solution, providing up to 100,000 hours of use without failure. ELECTRICAL Input Dual-voltage input 120 or 277VAC @ 60Hz OPTIONS Guardian Self-Test/Self-Diagnostics (Option: G2) The Guardian circuit continuously monitors the operating condition of the AC power, battery supply voltage, emergency lamp continuity and charging circuit. The purpose of this option is to provide visual signaling in response to a fault at the EXIT sign battery and/or battery charger. If a failure is detected, visual status will occur immediately via the CHARGER LED and/or the BATTERY FAULT LED. The LEDs will stay illuminated until the fault is corrected. The Guardian circuit also monitors the transfer circuit as well as performing automatic code compliant testing. The Guardian circuit will perform a 30 second discharge and self-test every 28-30 days. A 90 minute discharge and self-test is performed every 6 months. CONFORMANCE TO CODES & STANDARDS The S900 Series is ETL listed and meets or exceeds the following: UL 924, NEC requirements and NFPA 101. DIMENSIONS Sealed Nickel Cadmium Battery - NiCad (With Battery Only) Exitronix sealed nickel cadmium batteries are maintenance-free with a life expectancy of 15 years. Nickel cadmium batteries offer high discharge rates and continue to perform in a vast temperature range from 0-40 degrees C. NiCad technology provides long lasting, safe and reliable performance by utilizing the jelly-roll design and allows a Ni-Cad cell to deliver a much higher maximum current than an equivalent size alternative battery. As a relatively larger area of the electrode is in contact with the active material in each cell, the internal resistance for an equivalent sized NiCad cell is lower which increases the maximum current that can be delivered. Brownout Circuit The brownout circuit monitors the flow of AC current to the unit and triggers the emergency lighting system once a set reduction of AC power occurs. This dip in the voltage will cause many fixtures to extinguish causing loss of normal lighting even though a total power failure has not occurred. Low Voltage Disconnect When the battery’s terminal voltage falls below predetermined levels, the low-voltage circuit disconnects the emergency lighting load. The disconnect remains in effect until normal power is restored, preventing deep battery discharge and improving the life of the battery. The disconnect will also automatically reconnect the load circuit once the battery voltage returns to a normal value after charging. 3.5” 13” 1.63” 9.63” 8.68” 3.13” 14.96” 2.81” 4” Solid-State Transfer The unit features a solid-state switching transistor which eliminates damaged contacts or mechanical failures associated with relays. The switching circuit is designed to detect a loss of AC power and automatically energizes the lamps. Upon restoration of the AC voltage, the emergency lamps will switch off and the charger will automatically recharge the battery. Overload and Short-Circuit Protection The solid-state overload monitoring system in the DC circuit disconnects the lamp load from the battery should excessive wattage demands be made and automatically resets when the overload or short-circuit is removed. This overload current protective characteristic eliminates the need for fuses or circuit breakers for the DC load. Test Button Our easily located test button allows for manual verification of proper operation of the transfer circuit and emergency lamps. 1911 W. Parkside Lane • Phoenix, AZ 85027 (800) 533-3948 • Fax: (623) 580-8948 www.exitronix.com • www.barronltg.com 7.5” 12.69” TYPE .control panel - 120/277V CX Lighting Control Panels - 4 and 8 Relays TITLE 24 COMPLIANT CALIFORNIA CX COMMERCIAL LIGHTING CONTROL PANELS 120 277 VAC PROJECT INFORMATION Project Name Catalog No.Date The Hubbell Building Automation CX Commercial Lighting Control Panels provide feature-rich and cost-effective lighting control for maximum energy savings. The LCD User interface is located in the door and utilized simple and intuitive scrolling menus to program, check status or update the panel. The easy-to-use Pre-Programmed Scenarios Menu makes project commissioning simple and fast. The CX Panels can save up to 50% in labor and materials when used in place of conventional time clock and contactor combinations. The use of the astronomical clock instead of roof-mounted photocells increases cost savings, lowers maintenance, and improves reliability. PRODUCT FEATURES • Two Relay panel sizes – 4 and 8 relay spaces • Four types of relays – 20A/1P, N/O, 20A/2P, N/O, N/C (14K SSCR) 14.5” and 30A/1P latching (18K SCCR) • LCD user interface with keypad • 365 day programming with 64 schedules • Astronomical and real time clock • 12 Programmable dry contact inputs for 8 relay panel; • 6 programmable dry contact inputs for 4 relay panel 17” • Selectable pre-programmed scenarios • Programmable inputs accept low voltage switches, photocells, or motion sensors • Two low voltage dry contact output relays on 8 relay panel • Program uploads via removable SD memory card • Listed to UL916, UL924 and cUL • Five -year limited warranty 4” TYPE .control panel - 120/277V General Specifications Programming and configuration Programmable via user interface mounted on door Fully programmable by users with door closed and locked Physical NEMA 1 surface enclosure Pre-drilled mounting holes for mounting to wall, KOs provided on top and bottom 4 and 8 relay enclosures with hinged locking door Electrical input 120-277VAC Standard, 347/480 Optional Relays 120 and 277VAC 20 Amp Single Pole Relays (14K SCCR) 120 and 277VAC 30 Amp Single Pole Relays (18K SCCR) 347 VAC, 20A, IP Relay (14K SCCR) 208, 240, and 480VAC 20 Amp Double Pole Relays (14K SCCR) Operating environment Location: interior space Operating temperature: 0° to 50°C (32° to 112°F) Relative humidity (non-condensing): 10% to 90% Certifications Listed to UL916, UL924 and cUL Warranty Five-years limited Ordering Information CX MODEL CX CX Lighting Control Panel 08 SPACES 04 4 Relay Spaces 08 8 Relay Spaces 2 S INPUT VOLTAGE 2 120/277V ENCLOSURE S NEMA 1 Universal Surface 3 347/480V 08 M RELAY QUANTITY 00 No Relays Spaces Only 04 4 Relays Installed 08 8 Relays Installed NOTES: 1. 2-Pole relays take the same amount of space as 1-Pole relays. 2. Installed relays must be all of the same type. Relay Type TC not available in fully populate panels and must be ordered separately to be installed in the field. 3. “00” option has no relays, all must be installed in the field. 4. Secondary panel includes (2) master/secondary panel interface cards. 5. Master/Secondary available in 8 relay only. 9601 Dessau Road | Building One | Austin, Texas 78754 | 512-450-1100 | 512-450-1215 fax | www.hubbell-automation.com RELAY TYPE SP Space Only 2N 20A Electrically Held N/O 120-277V 3L Latching 120-277-347V TN 20A Electrically Held N/O 208480V OPTIONS N Stand Alone Panel M Master Panel S Secondary Panel (Note 4 & 5) 3300A 1.2.2014 TYPE .light sensor - 24V Luxstat Light Sensor TITLE 24 LOW COMPLIANT CALIFORNIA DAYLIGHTING CONTROLS 24 PROJECT INFORMATION Project Name VDC VOLTAGE Catalog No.Date The Luxstat Light Sensor by Servodan provides the necessary daylight-level information to the Luxstat daylight harvesting control modules. Using a photodiode element, this sensor continuously measures daylight levels and sends the information to the selected Luxstat daylight harvesting control module. In order to operate as a true Open Loop controller, the sensor must be positioned to see only daylight (no artificial light). You select the applicable foot-candle range by using a jumper beneath the front cover. LUXSTATLS PRODUCT FEATURES DAYLIGHT HARVESTING • Daylight sensor for Luxstat Daylight Harvesting System • Architecturally attractive design • Indoor and outdoor versions • Open loop operation • Foot-candle range: 3-6,000 fc • Mounts vertically or horizontally • Color coded, plug-and-play installation • UL and cUL listed • California Title 24 Compliant • Five-year limited warranty 1.2” 2” TYPE .light sensor - 24V Lux Light sensor 0-10V 1 2 3 45º Luxstat Control A B 17 23 45 68 91 01 11 2 30º A 17 23 78-050 45 68 91 01 11 2 B 30º Luxstat Control DIM General Specifications Electrical Four jumper-selectable foot-candle ranges: .03-30FC; 3-300FC; 30-3,000FC; 60-6,000FC 24VDC Low Votage Class 2 Device 3-conductor 22 AWG twisted cable—equal to Belden 8443 Construction Protective hard plastic cover and housing Dimension 2” diameter x 1.2” height (50.8 diameter x 30.5mm height) Certifications UL and cUL listed Warranty Five years Ordering Information LUXSTATLSO LUXSTATLS LUXSTATLSO MODEL Luxstat Light Sensor - Indoor Luxstat Light Sensor - Outdoor 9601 Dessau Road | Building One | Austin, Texas 78754 | 512-450-1100 | 512-450-1215 fax | www.hubbell-automation.com 5601A 12.23.2013 TYPE A2 em - 120/277V (please advise shielding & reflector) SER22 2' × 2' High Efficiency, Serrano® Architectural Luminaire / 1, 2, 3-Lamp T5, T5HO, T8, TT PROJECT INFORMATION FEATURES • • • • • • • • • • Architecturally enhanced triple lens design Full distribution provides controlled high angle light for visual comfort and more inviting spaces Advanced optics produce high efficiencies Hinged optical system allows easy access to lamps and electrical from below the ceiling Lenses interlock for structural integrity Two optional lens aesthetics Exclusive optional T8 EnergyMax® tuned 1.04 ballast factor ballast Step and full dimming options for both T5 and T8 expand energy savings opportunities Most configurations produce low W/ft2 to meet the most restrictive lighting power density codes Available with exclusive wiHUBB technology preinstalled Made with 90% recycled steel Made of 80% recyclable materials by weight Job pack available for minimizing amount of packaging material at job site Individual cartons made of 100% recycled corrugated Please go to http://www.hsi/productsustain.com for Hubbell Sustainable Design Solutions Feature Criteria. * ORDERING INFORMATION SER 22 – 2 17 MODEL G CEILING TYPE G Grid SM Surface Mount For hard ceilings use flange kit. SIZE ACCESSORIES (ORDER SEPARATELY) FK22 2' × 2' Single Flange Kit FKCR Flange Kit Row Adaptor ELECTRICAL Standard class “P”, thermally protected, autoresetting HPF ballast, sound rated A. CEE NEMA Premium compliant. All ballast leads extend a minimum of 6" through access location. NEC/CEC-compliant ballast disconnect is standard. FINISH All visible parts are custom formulated soft, non-glare high-reflectance white powder coat finish, painted after fabrication. EMERGENCY Field installation of battery packs requires use of remote test switch. INSTALLATION An access plate is furnished with each recessed fixture for fast wiring connections without the necessity to open the fixture or wireway. BALLASTS Energy efficient, thermally protected, automatic resetting, Class P, high power factor, sound rated A, magnetic or electronic ballasts. CEE NEMA Premium compliant. X SHIELDING C Contour R Rail LAMP TYPE 14 17 24 40TT 2', T5: 14 Watt 2', T8: 17 Watt 2', T5HO: 24 Watt Twin Tube Compact, 2G11 Base: 40 Watt CEILING COMPATIBILITY Luminaire is available to fit exposed grid ceilings, or hard ceilings when a flange kit is ordered. Some options may increase fixture depth. For information on compatibility with specific ceilings, or where plenum depth is a problem, contact your Columbia Lighting representative. Four integral T-bar clips are standard. CERTIFICATION All luminaires are built to UL 1598 standards and bear appropriate UL and cUL or CSA labels. IC Rating optional for some configurations. Damp location labeling is standard. Emergency-equipped fixtures labeled UL 924. – X E REFLECTOR P Performance F Full – U EP95 EP115 ESD115 ETT EPTT Electronic T8, 0.88 Ballast Factor, Instant Start Electronic T8, T5, T5HO Dimming, Programmed Start 1 Electronic T8, 0.88 Ballast Factor, Step Dimming, Programmed Start Electronic T8, 0.77 Ballast Factor, Low Wattage, Instant Start Electronic T8, 1.18 Ballast Factor, High Wattage, Instant Start Electronic T8, 1.04 Ballast Factor, Instant Start (N/A 1-Lamp) Electronic T8, 1.04 Ballast Factor, Step Dimming, Programmed Start Electronic T8, 1.04 Ballast Factor, Programmed Start Electronic T5, T5HO, 1.0 Ballast Factor or T8, 0.88 Ballast Factor, Programmed Start Electronic T5, 0.95 Ballast Factor , Programmed Start (N/A T5HO, 1-Lamp) Electronic T5, 0.95 Ballast Factor, Step Dimming, Programmed Start (N/A T5HO, 1-Lamp) Electronic T5, 1.15 Ballast Factor, Programmed Start (N/A T5HO, 1-Lamp) Electronic T5, 1.15 Ballast Factor, Step Dimming, Programmed Start (N/A T5HO) Electronic Twin Tube, Instant Start Electronic Twin Tube, Programmed Start Page 1/3 Rev. 01/02/14 © 2014 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd. Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com – VOLTAGE EL141ST OPTIONS C388 3-Wire Flex C488 4-Wire Flex C588 5-Wire Flex EL141 Emergency Battery Pack (self test) GLR Fast Blow Fuse GMF Slow Blow Fuse NYC NYC Compliant WIH wiHUBB Enabled 2 IC IC Rating U 120V-277V 347 347V2 BALLAST E ED ESD ELW EHL E104 ESD104 EP104 EP ESD95 Damp Label - standard 1 Where available. 2 Not available with surface mount. Date CONSTRUCTION Luminaire housing, end caps, and reflectors are die-formed code-gauge cold-rolled steel. Optical system hinges for easy access to lamps and electrical components. Mechanical light trap prevents light leaks. Latches are spring loaded. – 1 One (N/A 17, 14, 24) 2 Two 3 Three (N/A TT) 22 2' × 2' Catalog No. EXAMPLE SER22-314G-CP-EPU NO. OF LAMPS SER Serrano® Recessed Architectural Luminaire Type SHIELDING Lenses are high transmission extruded acrylic. HUBBELL SUSTAINABLE DESIGN SOLUTION FEATURES* • • • • Project Name LAMPS FO730 FO735 FO741 FO830 FO835 FO841 F5830 F5835 F5841 FTT830 FTT835 FTT841 30K 75CRI T8 Lamps Installed 35K 75CRI T8 Lamps Installed 41K 75CRI T8 Lamps Installed 30K 82CRI T8 Lamps Installed 35K 82CRI T8 Lamps Installed 41K 82CRI T8 Lamps Installed 30K 85CRI T5 or T5HO Lamps Installed 35K 85CRI T5 or T5HO Lamps Installed 41K 85CRI T5 or T5HO Lamps Installed 30K Twin Tube Lamps Installed 35K Twin Tube Lamps Installed 41K Twin Tube Lamps Installed RECESSED ARCHITECTURAL / SER22 TYPE A2 em - 120/277V (please advise shielding & reflector) SER22 2' × 2' High Efficiency, Serrano® Architectural Luminaire / 1, 2, 3-Lamp T5, T5HO, T8, TT PHOTOMETRIC DATA Ballast Ballast Factor Lamp Lumens per Lamp Watts Mounting Shielding Angle Spacing Criterion Luminous Opening in Feet SER22-217G-CP-EU SER Serrano, Recessed Architectural 2 x 2 2-lamp with Contour center lens, linear prismed side lenses, and performance reflector ICN-2P32-SC 0.88 F17T8 1325 31 Recessed 0° = 90 90° = 90 0° = 1.21 90° = 1.54 Length:1.79 Width:1.83 Height:0.00 AVG. LUMINANCE (Candela/Sq. M.) COEFFICIENTS OF UTILIZATION (%) 0.0 22.5 45.0 67.5 90.0 0 30 40 45 50 55 60 65 70 75 80 85 2238 2098 2003 1938 1840 1684 1505 1322 1163 1003 814 641 2238 2265 2226 2114 1953 1776 1604 1446 1287 1143 984 754 2238 2595 2544 2389 2214 2040 1880 1734 1604 1473 1325 943 2238 2838 2720 2556 2382 2217 2064 1921 1787 1651 1438 754 2238 2925 2775 2602 2428 2269 2116 1983 1854 1714 1457 679 Total Luminaire Efficiency 76.8% Luminaire Efficacy Rating (LER) ANSI/IESNA RP-1-2004 Compliance Comparative Yearly Lighting Energy Cost per 1000 Lumens 58 Yes-VDT Normal Use $4.14 based on 3000 hrs. and $0.08 per KWH ZONAL LUMEN SUMMARY 0-30 0-40 0-60 0-90 0-180 RC RW 1 2 3 4 5 6 7 8 9 10 70 84 77 70 64 59 55 51 47 44 41 80 50 30 80 77 70 65 62 56 55 49 49 43 44 38 40 34 37 30 34 27 31 25 10 74 61 51 43 38 33 29 26 23 21 70 82 75 68 62 57 53 49 46 43 40 70 50 30 79 76 69 64 61 55 54 48 48 42 44 37 40 33 36 30 33 27 31 25 10 73 60 51 43 37 33 29 26 23 21 50 75 66 59 52 47 42 38 35 32 30 50 30 73 62 54 47 41 37 33 30 27 25 0 0 65 55 46 40 34 30 27 24 21 19 RCR = Room Cavity Ratio RC = Effective Ceiling Cavity Reflectance RW = Wall Reflectance 75 400 Lumens % Lamp % Fixt. 575 971 1671 2033 2035 10 71 59 50 43 37 32 29 26 23 21 INDOOR CANDELA PLOT ENERGY DATA Zone RCR Luminaire Average Luminance Angle LUMINAIRE DATA Test 4431 Test Date 9/9/2011 21.7 36.6 63.1 76.7 76.8 60 28.3 47.7 82.1 99.9 100.0 800 0 15 0.0 Page 2/3 Rev. 01/02/14 © 2014 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd. Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com 30 Horiz 0-180 45.0 45 90.0 RECESSED ARCHITECTURAL / SER22 (please advise shielding & reflector) TYPE A2 em - 120/277V SER22 2' × 2' High Efficiency, Serrano® Architectural Luminaire / 1, 2, 3-Lamp T5, T5HO, T8, TT DIMENSIONAL DATA - GRID CEILING COMPATIBILITY Type G FKCR 45/16" 24" Side End For lay-in installation in exposed grid ceilings. Maximum tee widths of 1" and maximum tee heights of 2" allowed. 24" For flanged fixtures in row configurations, the FKCR adapter bracket kit is required in addition to the FK22 kit. Order one less FKCR than the total number of fixtures in row. (Example: Row of two, order (2) FK22 & (1) FKCR) FK22 Flange Kit 24" DIMENSIONAL DATA - SURFACE MOUNT Side 25" 81⁄2" O End For hard ceiling applications, order FK22 flange kit. Flange kit wires directly into concealed ceiling opening for a clean, finished appearance. 1⁄2" Row cut out dimensions using FK22s & FKCR adapters: Width 243/8", Length [24" × (# in row)] + 3/8". Example: (24" × 2) + 3/8" = 483/8" Flange kit cut out dimension for single unit only: 243/8" × 243/8" 25" 81⁄2" 4" 1113⁄32" 23⁄4" 7" O 11⁄2" 25" 45⁄8" NOTE: All dimensions are in inches; dimensions and specifications are subject to change without notice. Please consult factory or check sample for verification. Page 3/3 Rev. 01/02/14 © 2014 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd. Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com RECESSED ARCHITECTURAL / SER22 Electrical Options TYPE A2 em - 120/277V Emergency Battery Packs Installed Technical Luminaires with factory installed battery packs will bear the UL Emergency equipment label. Dry location labeling standard. Standard inverter options below are not suitable for cold temperature starting, damp or wet location labeling. Optional inverters available for these applications. Consult factory or specify vendor’s catalog number. EL EL61 EL71 EL72 350-450 lumens for one 2'-4' lamp (T8, T12, U-Bent, TT) 500-600 lumens for one 2'-4' lamp (T8, T12, U-Bent, TT) 600-700 lumens for one 2'-8' lamp (T8, T12, U-Bent, TT) 600-700 total lumens for two 2'-8' lamps (T8, T12, U-Bent) EL141 EL142 EL5* EL5H* 1100-1400 lumens for one 2'-8' lamp (T8, T12, U-Bent, TT) 1100-1400 total lumens for two 2'-4' lamps 390-700 lumens for one 2'-4' T5/T5HO 725-1250 lumens for one 2'-4' T5/T5HO *These inverters not available in some 2' fixtures due to space constraints. Remote mounting using accessory enclosure (by others) recommended. Fusing Fusing is available on all fixtures to prevent over current from being transmitted upstream through the fixture as may be possible due to a dead short fault in a ballast. Specify GLR (fast blow) or GMF (slow blow) fusing options. Fuses are not UL listed to break under load and therefore are not a substitute for the in-fixture ballast disconnects supplied standard where required by the National Electric Code. Fixture Flex and Leads Fixture flex (also called pre-wire or whip) is a UL listed lighting component for recessed fixtures to provide the electrical wiring between the junction box and recessed fixture. Flex may be no longer than 6'. Typical cables use ⅜" flexible conduit and three or four 18 gauge leads. Three wires provides one line voltage hot lead. Add a wire for each separate hot lead required including separately switched ballasts, switch dim ballast or battery pack to be powered through the flex cable. Flex cables are shipped pre-wired to the recessed fixture. Add option designation to catalog number after ballast options. Eg. C388. Wire colors will be coded black/white/red/yellow plus a ground for line voltages. 588DIMM is available with black/white violet, grey and ground for use with low voltage dimming leads. Cable No. of Wires C Cable Cable Diameter 3 3 4 4 5 5 8 ⅜" 2 ½" Wire gauge 8 18 gauge 4 14 gauge 2 12 gauge Miscellaneous Fixtures and Electrical Options (add As Suffix on end of Catalog string) Fixture/Option Cat. No. PSW PSWD 4PSW Description Pull switch, one circuit, 120V only Pull switch, wired to the downlight circuit on a two circuit unit, 120V only Four-way pull switch for two circuit, two lamp unit, 120V only For Use With Selected strips, surface units and industrials. Contact factory for applications NL Medium base lampholder for 15W, 25W, 40W, or 60W T10 lamp. Lamp not included. 120V only AWN, SM units Fluorescent Night Light for 7W, T-4, G23 lamp Fluorescent Night Light for 9W, T-4, G23 lamp Fluorescent Night Light for 13W, T-4, GX23 lamp Lamp not included. PL ballast will default to fixture voltage unless specified Grounded convenience outlet (120V only) 4PS, SM, and WAL series PL7 PL9 PL13 GCO C6P15_ 6' Cord and Straight Blade, NEMA 5-15P, 15A (Add Voltage: 1 = 120) C6TL15_ 6' Cord and Twist-Lock Plug, NEMA L5-15P (120V) NEMA L7-15P (277V), 15A (Add Voltage: 1 = 120, 2 =277) C6TL20_ 6' Cord and Twist-Lock Plug, NEMA L5-20P (120V) NEMA L7-20P (277V), 20A (Add Voltage: 1 = 120, 2 =277) F3C_ 3-Conductor feed cord, 18ga stranded wire (Add length needed: 5 = 5', 10 = 10', or 15 = 15') F4C_ 4-Conductor feed cord, 18ga stranded wire (Add length needed: 5 = 5', 10 = 10', or 15 = 15') GLR Fast blow fuse, fuse amps based on fixture ordered 112 WPM, WM, WAL, UCS and UC Standard on SA, W All industrial fixtures All industrial fixtures All fixtures TYPE A2 - 120/277V (please advise shielding & reflector) SER22 2' × 2' High Efficiency, Serrano® Architectural Luminaire / 1, 2, 3-Lamp T5, T5HO, T8, TT PROJECT INFORMATION FEATURES • • • • • • • • • • Architecturally enhanced triple lens design Full distribution provides controlled high angle light for visual comfort and more inviting spaces Advanced optics produce high efficiencies Hinged optical system allows easy access to lamps and electrical from below the ceiling Lenses interlock for structural integrity Two optional lens aesthetics Exclusive optional T8 EnergyMax® tuned 1.04 ballast factor ballast Step and full dimming options for both T5 and T8 expand energy savings opportunities Most configurations produce low W/ft2 to meet the most restrictive lighting power density codes Available with exclusive wiHUBB technology preinstalled Made with 90% recycled steel Made of 80% recyclable materials by weight Job pack available for minimizing amount of packaging material at job site Individual cartons made of 100% recycled corrugated Please go to http://www.hsi/productsustain.com for Hubbell Sustainable Design Solutions Feature Criteria. * ORDERING INFORMATION SER 22 – 2 17 MODEL G CEILING TYPE G Grid SM Surface Mount For hard ceilings use flange kit. SIZE ACCESSORIES (ORDER SEPARATELY) FK22 2' × 2' Single Flange Kit FKCR Flange Kit Row Adaptor ELECTRICAL Standard class “P”, thermally protected, autoresetting HPF ballast, sound rated A. CEE NEMA Premium compliant. All ballast leads extend a minimum of 6" through access location. NEC/CEC-compliant ballast disconnect is standard. FINISH All visible parts are custom formulated soft, non-glare high-reflectance white powder coat finish, painted after fabrication. EMERGENCY Field installation of battery packs requires use of remote test switch. INSTALLATION An access plate is furnished with each recessed fixture for fast wiring connections without the necessity to open the fixture or wireway. BALLASTS Energy efficient, thermally protected, automatic resetting, Class P, high power factor, sound rated A, magnetic or electronic ballasts. CEE NEMA Premium compliant. X SHIELDING C Contour R Rail LAMP TYPE 14 17 24 40TT 2', T5: 14 Watt 2', T8: 17 Watt 2', T5HO: 24 Watt Twin Tube Compact, 2G11 Base: 40 Watt CEILING COMPATIBILITY Luminaire is available to fit exposed grid ceilings, or hard ceilings when a flange kit is ordered. Some options may increase fixture depth. For information on compatibility with specific ceilings, or where plenum depth is a problem, contact your Columbia Lighting representative. Four integral T-bar clips are standard. CERTIFICATION All luminaires are built to UL 1598 standards and bear appropriate UL and cUL or CSA labels. IC Rating optional for some configurations. Damp location labeling is standard. Emergency-equipped fixtures labeled UL 924. – X E REFLECTOR P Performance F Full – U EP95 EP115 ESD115 ETT EPTT Electronic T8, 0.88 Ballast Factor, Instant Start Electronic T8, T5, T5HO Dimming, Programmed Start 1 Electronic T8, 0.88 Ballast Factor, Step Dimming, Programmed Start Electronic T8, 0.77 Ballast Factor, Low Wattage, Instant Start Electronic T8, 1.18 Ballast Factor, High Wattage, Instant Start Electronic T8, 1.04 Ballast Factor, Instant Start (N/A 1-Lamp) Electronic T8, 1.04 Ballast Factor, Step Dimming, Programmed Start Electronic T8, 1.04 Ballast Factor, Programmed Start Electronic T5, T5HO, 1.0 Ballast Factor or T8, 0.88 Ballast Factor, Programmed Start Electronic T5, 0.95 Ballast Factor , Programmed Start (N/A T5HO, 1-Lamp) Electronic T5, 0.95 Ballast Factor, Step Dimming, Programmed Start (N/A T5HO, 1-Lamp) Electronic T5, 1.15 Ballast Factor, Programmed Start (N/A T5HO, 1-Lamp) Electronic T5, 1.15 Ballast Factor, Step Dimming, Programmed Start (N/A T5HO) Electronic Twin Tube, Instant Start Electronic Twin Tube, Programmed Start Page 1/3 Rev. 01/02/14 © 2014 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd. Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com – VOLTAGE EL141ST OPTIONS C388 C488 C588 EL GLR GMF NYC WIH IC U 120V-277V 347 347V2 BALLAST E ED ESD ELW EHL E104 ESD104 EP104 EP ESD95 Damp Label - standard 1 Where available. 2 Not available with surface mount. Date CONSTRUCTION Luminaire housing, end caps, and reflectors are die-formed code-gauge cold-rolled steel. Optical system hinges for easy access to lamps and electrical components. Mechanical light trap prevents light leaks. Latches are spring loaded. – 1 One (N/A 17, 14, 24) 2 Two 3 Three (N/A TT) 22 2' × 2' Catalog No. EXAMPLE SER22-314G-CP-EPU NO. OF LAMPS SER Serrano® Recessed Architectural Luminaire Type SHIELDING Lenses are high transmission extruded acrylic. HUBBELL SUSTAINABLE DESIGN SOLUTION FEATURES* • • • • Project Name 3-Wire Flex 4-Wire Flex 5-Wire Flex Emergency Battery Pack Fast Blow Fuse Slow Blow Fuse NYC Compliant wiHUBB Enabled 2 IC Rating LAMPS FO730 FO735 FO741 FO830 FO835 FO841 F5830 F5835 F5841 FTT830 FTT835 FTT841 30K 75CRI T8 Lamps Installed 35K 75CRI T8 Lamps Installed 41K 75CRI T8 Lamps Installed 30K 82CRI T8 Lamps Installed 35K 82CRI T8 Lamps Installed 41K 82CRI T8 Lamps Installed 30K 85CRI T5 or T5HO Lamps Installed 35K 85CRI T5 or T5HO Lamps Installed 41K 85CRI T5 or T5HO Lamps Installed 30K Twin Tube Lamps Installed 35K Twin Tube Lamps Installed 41K Twin Tube Lamps Installed RECESSED ARCHITECTURAL / SER22 TYPE A2 - 120/277V (please advise shielding & reflector) SER22 2' × 2' High Efficiency, Serrano® Architectural Luminaire / 1, 2, 3-Lamp T5, T5HO, T8, TT PHOTOMETRIC DATA Ballast Ballast Factor Lamp Lumens per Lamp Watts Mounting Shielding Angle Spacing Criterion Luminous Opening in Feet SER22-217G-CP-EU SER Serrano, Recessed Architectural 2 x 2 2-lamp with Contour center lens, linear prismed side lenses, and performance reflector ICN-2P32-SC 0.88 F17T8 1325 31 Recessed 0° = 90 90° = 90 0° = 1.21 90° = 1.54 Length:1.79 Width:1.83 Height:0.00 AVG. LUMINANCE (Candela/Sq. M.) COEFFICIENTS OF UTILIZATION (%) 0.0 22.5 45.0 67.5 90.0 0 30 40 45 50 55 60 65 70 75 80 85 2238 2098 2003 1938 1840 1684 1505 1322 1163 1003 814 641 2238 2265 2226 2114 1953 1776 1604 1446 1287 1143 984 754 2238 2595 2544 2389 2214 2040 1880 1734 1604 1473 1325 943 2238 2838 2720 2556 2382 2217 2064 1921 1787 1651 1438 754 2238 2925 2775 2602 2428 2269 2116 1983 1854 1714 1457 679 Total Luminaire Efficiency 76.8% Luminaire Efficacy Rating (LER) ANSI/IESNA RP-1-2004 Compliance Comparative Yearly Lighting Energy Cost per 1000 Lumens 58 Yes-VDT Normal Use $4.14 based on 3000 hrs. and $0.08 per KWH ZONAL LUMEN SUMMARY 0-30 0-40 0-60 0-90 0-180 RC RW 1 2 3 4 5 6 7 8 9 10 70 84 77 70 64 59 55 51 47 44 41 80 50 30 80 77 70 65 62 56 55 49 49 43 44 38 40 34 37 30 34 27 31 25 10 74 61 51 43 38 33 29 26 23 21 70 82 75 68 62 57 53 49 46 43 40 70 50 30 79 76 69 64 61 55 54 48 48 42 44 37 40 33 36 30 33 27 31 25 10 73 60 51 43 37 33 29 26 23 21 50 75 66 59 52 47 42 38 35 32 30 50 30 73 62 54 47 41 37 33 30 27 25 0 0 65 55 46 40 34 30 27 24 21 19 RCR = Room Cavity Ratio RC = Effective Ceiling Cavity Reflectance RW = Wall Reflectance 75 400 Lumens % Lamp % Fixt. 575 971 1671 2033 2035 10 71 59 50 43 37 32 29 26 23 21 INDOOR CANDELA PLOT ENERGY DATA Zone RCR Luminaire Average Luminance Angle LUMINAIRE DATA Test 4431 Test Date 9/9/2011 21.7 36.6 63.1 76.7 76.8 60 28.3 47.7 82.1 99.9 100.0 800 0 15 0.0 Page 2/3 Rev. 01/02/14 © 2014 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd. Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com 30 Horiz 0-180 45.0 45 90.0 RECESSED ARCHITECTURAL / SER22 (please advise shielding & reflector) TYPE A2 - 120/277V SER22 2' × 2' High Efficiency, Serrano® Architectural Luminaire / 1, 2, 3-Lamp T5, T5HO, T8, TT DIMENSIONAL DATA - GRID CEILING COMPATIBILITY Type G FKCR 45/16" 24" Side End For lay-in installation in exposed grid ceilings. Maximum tee widths of 1" and maximum tee heights of 2" allowed. 24" For flanged fixtures in row configurations, the FKCR adapter bracket kit is required in addition to the FK22 kit. Order one less FKCR than the total number of fixtures in row. (Example: Row of two, order (2) FK22 & (1) FKCR) FK22 Flange Kit 24" DIMENSIONAL DATA - SURFACE MOUNT Side 25" 81⁄2" O End For hard ceiling applications, order FK22 flange kit. Flange kit wires directly into concealed ceiling opening for a clean, finished appearance. 1⁄2" Row cut out dimensions using FK22s & FKCR adapters: Width 243/8", Length [24" × (# in row)] + 3/8". Example: (24" × 2) + 3/8" = 483/8" Flange kit cut out dimension for single unit only: 243/8" × 243/8" 25" 81⁄2" 4" 1113⁄32" 23⁄4" 7" O 11⁄2" 25" 45⁄8" NOTE: All dimensions are in inches; dimensions and specifications are subject to change without notice. Please consult factory or check sample for verification. Page 3/3 Rev. 01/02/14 © 2014 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd. Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com RECESSED ARCHITECTURAL / SER22 TYPE A4 em - 120/277V (please advise shielding & reflector) SER24 2' × 4' High Efficiency, Serrano® Architectural Luminaire / 1, 2, 3-Lamp T5, T5HO, T8 PROJECT INFORMATION FEATURES • • • • • • • • • • Architecturally enhanced triple lens design Full distribution provides controlled high angle light for visual comfort and more inviting spaces Advanced optics produce high efficiencies Hinged optical system allows easy access to lamps and electrical from below the ceiling Lenses interlock for structural integrity Two optional lens aesthetics Exclusive optional T8 EnergyMax® tuned 1.04 ballast factor ballast Step and full dimming options for both T5 and T8 expand energy savings opportunities Most configurations produce low W/ft2 to meet the most restrictive lighting power density codes Available with exclusive wiHUBB technology preinstalled HUBBELL SUSTAINABLE DESIGN SOLUTION FEATURES* • • • • Project Name Type Catalog No. Date CONSTRUCTION Luminaire housing, end caps, and reflectors are die-formed code-gauge cold-rolled steel. Optical system hinges for easy access to lamps and electrical components. Mechanical light trap prevents light leaks. Latches are spring loaded. ELECTRICAL Standard class “P”, thermally protected, autoresetting HPF ballast, sound rated A. CEE NEMA Premium compliant. All ballast leads extend a minimum of 6" through access location. NEC/CEC-compliant ballast disconnect is standard. FINISH All visible parts are custom formulated soft, non-glare high-reflectance white powder coat finish, painted after fabrication. EMERGENCY Field installation of battery packs requires use of remote test switch. SHIELDING Lenses are high transmission extruded acrylic. INSTALLATION An access plate is furnished with each recessed fixture for fast wiring connections without the necessity to open the fixture or wireway. Made with 90% recycled steel Made of 80% recyclable materials by weight BALLASTS Job pack available for minimizing amount of packaging material at job site Energy efficient, thermally protected, automatic Individual cartons made of 100% recycled corrugated resetting, Class P, high power factor, sound rated A, Please go to http://www.hsi/productsustain.com for Hubbell Sustainable Design Solutions Feature Criteria. * ORDERING INFORMATION SER 24 – 2 17 MODEL NO. OF LAMPS SER Serrano® Recessed Architectural Luminaire SIZE 24 2' × 4' 1 One 2 Two 3 Three 28 4', T5: 28 Watt 32 4', T8: 32, 30, 28, or 25 Watt 54 4', T5HO: 54 or 51 Watt ACCESSORIES (ORDER SEPARATELY) FK24 2' × 4' Single Flange Kit FKCR Flange Kit Row Adaptor EP95 EP115 Not compatible with T8 25, 28, or 30 watt energy savings lamps. 2 Where available. 3 Not recommended for use with step or full dimming. 4 Not available with surface mount. – X SHIELDING C Contour R Rail X – E REFLECTOR ESD115 1 ESD80 Electronic T8, 0.88 Ballast Factor, Instant Start Electronic T8, T5, T5HO Dimming, Programmed Start1, 2 Electronic T8, 0.88 Ballast Factor, Step Dimming, Programmed Start 1 Electronic T8, 0.77 Ballast Factor, Low Wattage, Instant Start Electronic T8, 1.18 Ballast Factor, High Wattage, Instant Start Electronic T8, 1.04 Ballast Factor, Instant Start (N/A 1-Lamp) Electronic T8, 1.04 Ballast Factor, Step Dimming, Programmed Start1 Electronic T8, 1.04 Ballast Factor, Programmed Start Electronic T5, T5HO, 1.0 Ballast Factor or T8, 0.88 Ballast Factor, Programmed Start Electronic T5, 0.95 Ballast Factor , Programmed Start (N/A T5HO, 1-Lamp) Electronic T5, 0.95 Ballast Factor, Step Dimming, Programmed Start (N/A T5HO, 1-Lamp) Electronic T5, 1.15 Ballast Factor, Programmed Start (N/A T5HO, 1-Lamp) Electronic T5, 1.15 Ballast Factor, Step Dimming, Programmed Start (N/A T5HO) Electronic T5HO, 0.80 Ballast Factor, Step Dimming, Programmed Start (2-Lamp 54W only) Page 1/3 Rev. 01/02/14 © 2014 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd. Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com U – – VOLTAGE P Performance F Full LAMPS FO730 FO735 FO741 FO830 FO835 FO841 F028830 F028835 F028841 FOH830 FOH835 FOH841 F5830 F5835 F5841 F5H830 F5H835 F5H841 EL141ST OPTIONS C388 C488 C588 EL141 U 120V-277V 347 347V2 BALLAST ESD95 Damp Label - standard G G Grid SM Surface Mount For hard ceilings use flange kit. E ED ESD ELW EHL E104 ESD104 EP104 EP CERTIFICATION All luminaires are built to UL 1598 standards and bear appropriate UL and cUL or CSA labels. IC Rating optional for some configurations. Damp location labeling is standard. Emergency-equipped fixtures labeled UL 924. EXAMPLE SER24-232G-RF-E104U-F0835 CEILING TYPE LAMP TYPE magnetic or electronic ballasts. CEE NEMA Premium compliant. CEILING COMPATIBILITY Luminaire is available to fit exposed grid ceilings, or hard ceilings when a flange kit is ordered. Some options may increase fixture depth. For information on compatibility with specific ceilings, or where plenum depth is a problem, contact your Columbia Lighting representative. Four integral T-bar clips are standard. 30K 75CRI T8 Lamps Installed 35K 75CRI T8 Lamps Installed 41K 75CRI T8 Lamps Installed 30K 82CRI T8 Lamps Installed 35K 82CRI T8 Lamps Installed 41K 82CRI T8 Lamps Installed 30K 82CRI 28W T8 Lamps Installed 3 35K 82CRI 28W T8 Lamps Installed 3 41K 82CRI 28W T8 Lamps Installed 3 30K High Lumen T8 Lamps Installed 35K High Lumen T8 Lamps Installed 41K High Lumen T8 Lamps Installed 30K 85CRI T5 or T5HO Lamps Installed 35K 85CRI T5 or T5HO Lamps Installed 41K 85CRI T5 or T5HO Lamps Installed 30K High Lumen T5 Lamps Installed 35K High Lumen T5 Lamps Installed 41K High Lumen T5 Lamps Installed GLR GMF NYC WIH IC 3-Wire Flex 4-Wire Flex 5-Wire Flex Emergency (self test) Battery Pack Fast Blow Fuse Slow Blow Fuse NYC Compliant wiHUBB Enabled 4 IC Rating RECESSED ARCHITECTURAL / SER24 TYPE A4 em - 120/277V (please advise shielding & reflector) SER24 2' × 4' High Efficiency, Serrano® Architectural Luminaire / 1, 2, 3-Lamp T5, T5HO, T8 PHOTOMETRIC DATA Ballast Ballast Factor Lamp Lumens per Lamp Watts Mounting Shielding Angle Spacing Criterion Luminous Opening in Feet SER24-232G-CP-EU SER Serrano, Recessed Architectural 2 x 4 2-lamp with Contour center lens, linear prismed side lenses, and performance reflector ICN-2P32-SC 0.88 F28T8 2725 50 Recessed 0° = 90 90° = 90 0° = 1.23 90° = 1.55 Length:1.83 Width:3.83 Height:0.00 AVG. LUMINANCE (Candela/Sq. M.) COEFFICIENTS OF UTILIZATION (%) 0.0 22.5 45.0 67.5 90.0 0 30 40 45 50 55 60 65 70 75 80 85 2417 2309 2229 2183 2119 2005 1843 1653 1464 1276 1061 811 2417 2451 2476 2415 2289 2126 1963 1802 1639 1478 1318 1145 2417 2761 2821 2711 2559 2396 2239 2093 1949 1816 1707 1198 2417 3022 3007 2867 2700 2533 2374 2228 2079 1940 1689 811 2417 3105 3047 2891 2717 2544 2383 2224 2070 1923 1574 634 ZONAL LUMEN SUMMARY Zone 0-30 0-40 0-60 0-90 0-180 24.1 41.0 72.5 89.5 89.5 RC RW 1 2 3 4 5 6 7 8 9 10 70 98 89 81 74 68 63 58 54 51 47 80 50 30 93 90 82 76 72 64 64 56 57 49 51 43 46 38 42 34 39 31 36 28 10 86 71 59 50 43 37 33 29 26 24 70 95 87 79 72 66 61 57 53 49 46 70 50 30 91 88 80 74 70 64 62 55 56 48 50 43 45 38 41 34 38 31 35 28 10 85 70 58 49 43 37 33 29 26 24 50 88 77 68 60 54 49 44 40 37 34 50 30 85 72 62 54 47 42 37 34 31 28 INDOOR CANDELA PLOT 10 82 68 57 49 42 37 32 29 26 24 RCR = Room Cavity Ratio RC = Effective Ceiling Cavity Reflectance RW = Wall Reflectance 0 0 75 63 53 45 39 34 30 27 24 22 90 75 900 60 1800 0 15 0.0 ENERGY DATA Lumens % Lamp % Fixt. 1314 2237 3951 4879 4879 RCR Luminaire Average Luminance Angle LUMINAIRE DATA Test 4460 Test Date 9/19/2011 26.9 45.8 81.0 100.0 100.0 Total Luminaire Efficiency 89.5% Luminaire Efficacy Rating (LER) ANSI/IESNA RP-1-2004 Compliance Comparative Yearly Lighting Energy Cost per 1000 Lumens 86 Noncompliant $2.79 based on 3000 hrs. and $0.08 per KWH 30 Horiz 0-180 45.0 45 90.0 Test 4540 Test Date 10/25/2011 Ballast Ballast Factor Lamp Lumens per Lamp Watts Mounting Shielding Angle Spacing Criterion Luminous Opening in Feet SER24-228G-CP-EPU SER Serrano, Recessed Architectural 2 x 4 2-lamp with Contour center lens, linear prismed side lenses, and performance reflector ICN-2S28-N 1.00 F28T5 2625 62 Recessed 0° = 90 90° = 90 0° = 1.22 90° = 1.51 Length:3.83 Width:1.83 Height:0.00 AVG. LUMINANCE (Candela/Sq. M.) COEFFICIENTS OF UTILIZATION (%) 0.0 22.5 45.0 67.5 90.0 0 30 40 45 50 55 60 65 70 75 80 85 2459 2321 2215 2146 2069 1944 1769 1599 1423 1234 1017 775 2459 2451 2442 2370 2236 2072 1898 1737 1581 1424 1247 1093 2459 2727 2757 2648 2506 2348 2184 2039 1899 1774 1636 1093 2459 2961 2949 2808 2645 2471 2297 2148 2003 1869 1592 740 2459 3043 2977 2819 2645 2466 2294 2144 2003 1845 1486 564 ZONAL LUMEN SUMMARY Zone 0-30 0-40 0-60 0-90 0-180 Lumens % Lamp % Fixt. 1316 2224 3899 4796 4796 25.1 42.4 74.3 91.4 91.4 27.4 46.4 81.3 100.0 100.0 RCR Luminaire Average Luminance Angle LUMINAIRE DATA RC RW 70 1 100 2 91 3 83 4 76 5 70 6 64 7 60 8 56 9 52 10 49 80 50 30 95 92 83 77 73 66 65 57 58 50 52 44 47 39 43 35 40 32 37 29 10 88 72 60 51 44 38 34 30 27 24 70 97 88 81 74 68 63 58 54 51 47 70 50 30 93 90 82 76 72 65 64 56 57 49 51 44 47 39 43 35 39 32 36 29 10 87 71 60 51 44 38 34 30 27 24 50 90 78 69 62 55 50 45 41 38 35 50 30 87 74 63 55 48 43 38 35 31 29 INDOOR CANDELA PLOT 10 84 70 59 50 43 38 33 30 27 24 RCR = Room Cavity Ratio RC = Effective Ceiling Cavity Reflectance RW = Wall Reflectance 0 0 77 65 55 47 40 35 31 28 25 22 90 75 900 60 1800 15 0 0.0 30 Horiz 0-180 45.0 45 90.0 ENERGY DATA Total Luminaire Efficiency 91.4% Luminaire Efficacy Rating (LER) ANSI/IESNA RP-1-2004 Compliance Comparative Yearly Lighting Energy Cost per 1000 Lumens 77 Noncompliant $3.12 based on 3000 hrs. and $0.08 per KWH Page 2/3 Rev. 01/02/14 © 2014 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd. Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com RECESSED ARCHITECTURAL / SER24 (please advise shielding & reflector) TYPE A4 em - 120/277V SER24 2' × 4' High Efficiency, Serrano® Architectural Luminaire / 1, 2, 3-Lamp T5, T5HO, T8 DIMENSIONAL DATA CEILING COMPATIBILITY Type G FKCR 45/16" 24" Side End For lay-in installation in exposed grid ceilings. Maximum tee widths of 1" and maximum tee heights of 2" allowed. 24" 24" For flanged fixtures in row configurations, the FKCR adapter bracket kit is required in addition to the FK24 kit. Order one less FKCR than the total number of fixtures in row. (Example: Row of two, order (2) FK24 & (1) FKCR) FK24 Flange Kit 48" 48" DIMENSIONAL DATA - SURFACE MOUNT 81⁄2" 25" Side End For hard ceiling applications, order FK24 flange kit. Flange kit wires directly into concealed ceiling opening for a clean, finished appearance. O 1⁄2" Row cut out dimensions using FK24s & FKCR adapters: Width 243/8", Length [48" × (# in row)] + 3/8". Example: (48" × 2) + 3/8" = 963/8" Flange kit cut out dimension for single unit only: 243/8" × 483/8" 49" 193⁄4" 221⁄2" 23⁄4" 4" 71⁄2" O 11⁄2" 25" 45⁄8" NOTE: All dimensions are in inches; dimensions and specifications are subject to change without notice. Please consult factory or check sample for verification. Page 3/3 Rev. 01/02/14 © 2014 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd. Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com RECESSED ARCHITECTURAL / SER24 Electrical Options TYPE A4 em - 120/277V Emergency Battery Packs Installed Technical Luminaires with factory installed battery packs will bear the UL Emergency equipment label. Dry location labeling standard. Standard inverter options below are not suitable for cold temperature starting, damp or wet location labeling. Optional inverters available for these applications. Consult factory or specify vendor’s catalog number. EL EL61 EL71 EL72 350-450 lumens for one 2'-4' lamp (T8, T12, U-Bent, TT) 500-600 lumens for one 2'-4' lamp (T8, T12, U-Bent, TT) 600-700 lumens for one 2'-8' lamp (T8, T12, U-Bent, TT) 600-700 total lumens for two 2'-8' lamps (T8, T12, U-Bent) EL141 EL142 EL5* EL5H* 1100-1400 lumens for one 2'-8' lamp (T8, T12, U-Bent, TT) 1100-1400 total lumens for two 2'-4' lamps 390-700 lumens for one 2'-4' T5/T5HO 725-1250 lumens for one 2'-4' T5/T5HO *These inverters not available in some 2' fixtures due to space constraints. Remote mounting using accessory enclosure (by others) recommended. Fusing Fusing is available on all fixtures to prevent over current from being transmitted upstream through the fixture as may be possible due to a dead short fault in a ballast. Specify GLR (fast blow) or GMF (slow blow) fusing options. Fuses are not UL listed to break under load and therefore are not a substitute for the in-fixture ballast disconnects supplied standard where required by the National Electric Code. Fixture Flex and Leads Fixture flex (also called pre-wire or whip) is a UL listed lighting component for recessed fixtures to provide the electrical wiring between the junction box and recessed fixture. Flex may be no longer than 6'. Typical cables use ⅜" flexible conduit and three or four 18 gauge leads. Three wires provides one line voltage hot lead. Add a wire for each separate hot lead required including separately switched ballasts, switch dim ballast or battery pack to be powered through the flex cable. Flex cables are shipped pre-wired to the recessed fixture. Add option designation to catalog number after ballast options. Eg. C388. Wire colors will be coded black/white/red/yellow plus a ground for line voltages. 588DIMM is available with black/white violet, grey and ground for use with low voltage dimming leads. Cable No. of Wires C Cable Cable Diameter 3 3 4 4 5 5 8 ⅜" 2 ½" Wire gauge 8 18 gauge 4 14 gauge 2 12 gauge Miscellaneous Fixtures and Electrical Options (add As Suffix on end of Catalog string) Fixture/Option Cat. No. PSW PSWD 4PSW Description Pull switch, one circuit, 120V only Pull switch, wired to the downlight circuit on a two circuit unit, 120V only Four-way pull switch for two circuit, two lamp unit, 120V only For Use With Selected strips, surface units and industrials. Contact factory for applications NL Medium base lampholder for 15W, 25W, 40W, or 60W T10 lamp. Lamp not included. 120V only AWN, SM units Fluorescent Night Light for 7W, T-4, G23 lamp Fluorescent Night Light for 9W, T-4, G23 lamp Fluorescent Night Light for 13W, T-4, GX23 lamp Lamp not included. PL ballast will default to fixture voltage unless specified Grounded convenience outlet (120V only) 4PS, SM, and WAL series PL7 PL9 PL13 GCO C6P15_ 6' Cord and Straight Blade, NEMA 5-15P, 15A (Add Voltage: 1 = 120) C6TL15_ 6' Cord and Twist-Lock Plug, NEMA L5-15P (120V) NEMA L7-15P (277V), 15A (Add Voltage: 1 = 120, 2 =277) C6TL20_ 6' Cord and Twist-Lock Plug, NEMA L5-20P (120V) NEMA L7-20P (277V), 20A (Add Voltage: 1 = 120, 2 =277) F3C_ 3-Conductor feed cord, 18ga stranded wire (Add length needed: 5 = 5', 10 = 10', or 15 = 15') F4C_ 4-Conductor feed cord, 18ga stranded wire (Add length needed: 5 = 5', 10 = 10', or 15 = 15') GLR Fast blow fuse, fuse amps based on fixture ordered 112 WPM, WM, WAL, UCS and UC Standard on SA, W All industrial fixtures All industrial fixtures All fixtures TYPE A4 - 120/277V (please advise shielding & reflector) SER24 2' × 4' High Efficiency, Serrano® Architectural Luminaire / 1, 2, 3-Lamp T5, T5HO, T8 PROJECT INFORMATION FEATURES • • • • • • • • • • Architecturally enhanced triple lens design Full distribution provides controlled high angle light for visual comfort and more inviting spaces Advanced optics produce high efficiencies Hinged optical system allows easy access to lamps and electrical from below the ceiling Lenses interlock for structural integrity Two optional lens aesthetics Exclusive optional T8 EnergyMax® tuned 1.04 ballast factor ballast Step and full dimming options for both T5 and T8 expand energy savings opportunities Most configurations produce low W/ft2 to meet the most restrictive lighting power density codes Available with exclusive wiHUBB technology preinstalled HUBBELL SUSTAINABLE DESIGN SOLUTION FEATURES* • • • • Project Name Type Catalog No. Date CONSTRUCTION Luminaire housing, end caps, and reflectors are die-formed code-gauge cold-rolled steel. Optical system hinges for easy access to lamps and electrical components. Mechanical light trap prevents light leaks. Latches are spring loaded. ELECTRICAL Standard class “P”, thermally protected, autoresetting HPF ballast, sound rated A. CEE NEMA Premium compliant. All ballast leads extend a minimum of 6" through access location. NEC/CEC-compliant ballast disconnect is standard. FINISH All visible parts are custom formulated soft, non-glare high-reflectance white powder coat finish, painted after fabrication. EMERGENCY Field installation of battery packs requires use of remote test switch. SHIELDING Lenses are high transmission extruded acrylic. INSTALLATION An access plate is furnished with each recessed fixture for fast wiring connections without the necessity to open the fixture or wireway. Made with 90% recycled steel Made of 80% recyclable materials by weight BALLASTS Job pack available for minimizing amount of packaging material at job site Energy efficient, thermally protected, automatic Individual cartons made of 100% recycled corrugated resetting, Class P, high power factor, sound rated A, Please go to http://www.hsi/productsustain.com for Hubbell Sustainable Design Solutions Feature Criteria. * ORDERING INFORMATION SER 24 – 2 17 MODEL NO. OF LAMPS SER Serrano® Recessed Architectural Luminaire SIZE 24 2' × 4' 1 One 2 Two 3 Three 28 4', T5: 28 Watt 32 4', T8: 32, 30, 28, or 25 Watt 54 4', T5HO: 54 or 51 Watt ACCESSORIES (ORDER SEPARATELY) FK24 2' × 4' Single Flange Kit FKCR Flange Kit Row Adaptor EP95 EP115 Not compatible with T8 25, 28, or 30 watt energy savings lamps. 2 Where available. 3 Not recommended for use with step or full dimming. 4 Not available with surface mount. – X SHIELDING C Contour R Rail X – E REFLECTOR ESD115 1 ESD80 Electronic T8, 0.88 Ballast Factor, Instant Start Electronic T8, T5, T5HO Dimming, Programmed Start1, 2 Electronic T8, 0.88 Ballast Factor, Step Dimming, Programmed Start 1 Electronic T8, 0.77 Ballast Factor, Low Wattage, Instant Start Electronic T8, 1.18 Ballast Factor, High Wattage, Instant Start Electronic T8, 1.04 Ballast Factor, Instant Start (N/A 1-Lamp) Electronic T8, 1.04 Ballast Factor, Step Dimming, Programmed Start1 Electronic T8, 1.04 Ballast Factor, Programmed Start Electronic T5, T5HO, 1.0 Ballast Factor or T8, 0.88 Ballast Factor, Programmed Start Electronic T5, 0.95 Ballast Factor , Programmed Start (N/A T5HO, 1-Lamp) Electronic T5, 0.95 Ballast Factor, Step Dimming, Programmed Start (N/A T5HO, 1-Lamp) Electronic T5, 1.15 Ballast Factor, Programmed Start (N/A T5HO, 1-Lamp) Electronic T5, 1.15 Ballast Factor, Step Dimming, Programmed Start (N/A T5HO) Electronic T5HO, 0.80 Ballast Factor, Step Dimming, Programmed Start (2-Lamp 54W only) Page 1/3 Rev. 01/02/14 © 2014 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd. Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com U – – VOLTAGE P Performance F Full LAMPS FO730 FO735 FO741 FO830 FO835 FO841 F028830 F028835 F028841 FOH830 FOH835 FOH841 F5830 F5835 F5841 F5H830 F5H835 F5H841 EL141ST OPTIONS C388 C488 C588 EL U 120V-277V 347 347V2 BALLAST ESD95 Damp Label - standard G G Grid SM Surface Mount For hard ceilings use flange kit. E ED ESD ELW EHL E104 ESD104 EP104 EP CERTIFICATION All luminaires are built to UL 1598 standards and bear appropriate UL and cUL or CSA labels. IC Rating optional for some configurations. Damp location labeling is standard. Emergency-equipped fixtures labeled UL 924. EXAMPLE SER24-232G-RF-E104U-F0835 CEILING TYPE LAMP TYPE magnetic or electronic ballasts. CEE NEMA Premium compliant. CEILING COMPATIBILITY Luminaire is available to fit exposed grid ceilings, or hard ceilings when a flange kit is ordered. Some options may increase fixture depth. For information on compatibility with specific ceilings, or where plenum depth is a problem, contact your Columbia Lighting representative. Four integral T-bar clips are standard. 30K 75CRI T8 Lamps Installed 35K 75CRI T8 Lamps Installed 41K 75CRI T8 Lamps Installed 30K 82CRI T8 Lamps Installed 35K 82CRI T8 Lamps Installed 41K 82CRI T8 Lamps Installed 30K 82CRI 28W T8 Lamps Installed 3 35K 82CRI 28W T8 Lamps Installed 3 41K 82CRI 28W T8 Lamps Installed 3 30K High Lumen T8 Lamps Installed 35K High Lumen T8 Lamps Installed 41K High Lumen T8 Lamps Installed 30K 85CRI T5 or T5HO Lamps Installed 35K 85CRI T5 or T5HO Lamps Installed 41K 85CRI T5 or T5HO Lamps Installed 30K High Lumen T5 Lamps Installed 35K High Lumen T5 Lamps Installed 41K High Lumen T5 Lamps Installed GLR GMF NYC WIH IC 3-Wire Flex 4-Wire Flex 5-Wire Flex Emergency Battery Pack Fast Blow Fuse Slow Blow Fuse NYC Compliant wiHUBB Enabled 4 IC Rating RECESSED ARCHITECTURAL / SER24 TYPE A4 - 120/277V (please advise shielding & reflector) SER24 2' × 4' High Efficiency, Serrano® Architectural Luminaire / 1, 2, 3-Lamp T5, T5HO, T8 PHOTOMETRIC DATA Ballast Ballast Factor Lamp Lumens per Lamp Watts Mounting Shielding Angle Spacing Criterion Luminous Opening in Feet SER24-232G-CP-EU SER Serrano, Recessed Architectural 2 x 4 2-lamp with Contour center lens, linear prismed side lenses, and performance reflector ICN-2P32-SC 0.88 F28T8 2725 50 Recessed 0° = 90 90° = 90 0° = 1.23 90° = 1.55 Length:1.83 Width:3.83 Height:0.00 AVG. LUMINANCE (Candela/Sq. M.) COEFFICIENTS OF UTILIZATION (%) 0.0 22.5 45.0 67.5 90.0 0 30 40 45 50 55 60 65 70 75 80 85 2417 2309 2229 2183 2119 2005 1843 1653 1464 1276 1061 811 2417 2451 2476 2415 2289 2126 1963 1802 1639 1478 1318 1145 2417 2761 2821 2711 2559 2396 2239 2093 1949 1816 1707 1198 2417 3022 3007 2867 2700 2533 2374 2228 2079 1940 1689 811 2417 3105 3047 2891 2717 2544 2383 2224 2070 1923 1574 634 ZONAL LUMEN SUMMARY Zone 0-30 0-40 0-60 0-90 0-180 24.1 41.0 72.5 89.5 89.5 RC RW 1 2 3 4 5 6 7 8 9 10 70 98 89 81 74 68 63 58 54 51 47 80 50 30 93 90 82 76 72 64 64 56 57 49 51 43 46 38 42 34 39 31 36 28 10 86 71 59 50 43 37 33 29 26 24 70 95 87 79 72 66 61 57 53 49 46 70 50 30 91 88 80 74 70 64 62 55 56 48 50 43 45 38 41 34 38 31 35 28 10 85 70 58 49 43 37 33 29 26 24 50 88 77 68 60 54 49 44 40 37 34 50 30 85 72 62 54 47 42 37 34 31 28 INDOOR CANDELA PLOT 10 82 68 57 49 42 37 32 29 26 24 RCR = Room Cavity Ratio RC = Effective Ceiling Cavity Reflectance RW = Wall Reflectance 0 0 75 63 53 45 39 34 30 27 24 22 90 75 900 60 1800 0 15 0.0 ENERGY DATA Lumens % Lamp % Fixt. 1314 2237 3951 4879 4879 RCR Luminaire Average Luminance Angle LUMINAIRE DATA Test 4460 Test Date 9/19/2011 26.9 45.8 81.0 100.0 100.0 Total Luminaire Efficiency 89.5% Luminaire Efficacy Rating (LER) ANSI/IESNA RP-1-2004 Compliance Comparative Yearly Lighting Energy Cost per 1000 Lumens 86 Noncompliant $2.79 based on 3000 hrs. and $0.08 per KWH 30 Horiz 0-180 45.0 45 90.0 Test 4540 Test Date 10/25/2011 Ballast Ballast Factor Lamp Lumens per Lamp Watts Mounting Shielding Angle Spacing Criterion Luminous Opening in Feet SER24-228G-CP-EPU SER Serrano, Recessed Architectural 2 x 4 2-lamp with Contour center lens, linear prismed side lenses, and performance reflector ICN-2S28-N 1.00 F28T5 2625 62 Recessed 0° = 90 90° = 90 0° = 1.22 90° = 1.51 Length:3.83 Width:1.83 Height:0.00 AVG. LUMINANCE (Candela/Sq. M.) COEFFICIENTS OF UTILIZATION (%) 0.0 22.5 45.0 67.5 90.0 0 30 40 45 50 55 60 65 70 75 80 85 2459 2321 2215 2146 2069 1944 1769 1599 1423 1234 1017 775 2459 2451 2442 2370 2236 2072 1898 1737 1581 1424 1247 1093 2459 2727 2757 2648 2506 2348 2184 2039 1899 1774 1636 1093 2459 2961 2949 2808 2645 2471 2297 2148 2003 1869 1592 740 2459 3043 2977 2819 2645 2466 2294 2144 2003 1845 1486 564 ZONAL LUMEN SUMMARY Zone 0-30 0-40 0-60 0-90 0-180 Lumens % Lamp % Fixt. 1316 2224 3899 4796 4796 25.1 42.4 74.3 91.4 91.4 27.4 46.4 81.3 100.0 100.0 RCR Luminaire Average Luminance Angle LUMINAIRE DATA RC RW 70 1 100 2 91 3 83 4 76 5 70 6 64 7 60 8 56 9 52 10 49 80 50 30 95 92 83 77 73 66 65 57 58 50 52 44 47 39 43 35 40 32 37 29 10 88 72 60 51 44 38 34 30 27 24 70 97 88 81 74 68 63 58 54 51 47 70 50 30 93 90 82 76 72 65 64 56 57 49 51 44 47 39 43 35 39 32 36 29 10 87 71 60 51 44 38 34 30 27 24 50 90 78 69 62 55 50 45 41 38 35 50 30 87 74 63 55 48 43 38 35 31 29 INDOOR CANDELA PLOT 10 84 70 59 50 43 38 33 30 27 24 RCR = Room Cavity Ratio RC = Effective Ceiling Cavity Reflectance RW = Wall Reflectance 0 0 77 65 55 47 40 35 31 28 25 22 90 75 900 60 1800 15 0 0.0 30 Horiz 0-180 45.0 45 90.0 ENERGY DATA Total Luminaire Efficiency 91.4% Luminaire Efficacy Rating (LER) ANSI/IESNA RP-1-2004 Compliance Comparative Yearly Lighting Energy Cost per 1000 Lumens 77 Noncompliant $3.12 based on 3000 hrs. and $0.08 per KWH Page 2/3 Rev. 01/02/14 © 2014 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd. Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com RECESSED ARCHITECTURAL / SER24 (please advise shielding & reflector) TYPE A4 - 120/277V SER24 2' × 4' High Efficiency, Serrano® Architectural Luminaire / 1, 2, 3-Lamp T5, T5HO, T8 DIMENSIONAL DATA CEILING COMPATIBILITY Type G FKCR 45/16" 24" Side End For lay-in installation in exposed grid ceilings. Maximum tee widths of 1" and maximum tee heights of 2" allowed. 24" 24" For flanged fixtures in row configurations, the FKCR adapter bracket kit is required in addition to the FK24 kit. Order one less FKCR than the total number of fixtures in row. (Example: Row of two, order (2) FK24 & (1) FKCR) FK24 Flange Kit 48" 48" DIMENSIONAL DATA - SURFACE MOUNT 81⁄2" 25" Side End For hard ceiling applications, order FK24 flange kit. Flange kit wires directly into concealed ceiling opening for a clean, finished appearance. O 1⁄2" Row cut out dimensions using FK24s & FKCR adapters: Width 243/8", Length [48" × (# in row)] + 3/8". Example: (48" × 2) + 3/8" = 963/8" Flange kit cut out dimension for single unit only: 243/8" × 483/8" 49" 193⁄4" 221⁄2" 23⁄4" 4" 71⁄2" O 11⁄2" 25" 45⁄8" NOTE: All dimensions are in inches; dimensions and specifications are subject to change without notice. Please consult factory or check sample for verification. Page 3/3 Rev. 01/02/14 © 2014 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd. Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com RECESSED ARCHITECTURAL / SER24 TYPE B - 120/277V 8" High Lumen LED Downlight Date:type: firm name: MD8LED PROJECT: 120 - 277V, 347V 0-10V Dimming APPLICATIONS: Architektur MD8LED Series is a 8” specification grade high output LED downlight capable of delivering 12,000+ lumens designed for ceiling heights from 20 to 60 feet. Combining energy savings, long life, low maintenance cost & controllability, it is an excellent alternative to metal halide (up to 250 watts) and quartz (up to 500 watts) fixtures. ENERGY STAR® qualified. Rated for a minimum of 50,000 hours life with 70% Lumen maintenance up to 40C (104F) when free airflow is available around the fixture. Rated for a minimum of 60,000 hours life with 85% lumen maintenance up to 30C (86F) when free airflow is available around the fixture and no lens is present HOUSING: 18 gauge corrosion protected steel platform designed for accessibility. Pre-wired J-box with snap-on covers. Separate power supply module serviceable and removable from above or below the ceiling. Power supply module is connected to the LED light engine using a locking plug-in connector. Approved for 8 (4 in/4 out) No. 12 AWG conductors rated for 90 C through wiring. Variable light engine mounts allow reflectors to be interchanged in the field. Reflector: High purity spun aluminum self-flanged reflector with iridescence suppressed Alzak anodized finish. Available in specular, semi-specular, and Prescolite’s American Matte finish in a variety of anodized colors as well as painted trim options. Offered in 25º, 35º, 45º, and 55º optical distributions as well as lens options for wet location applications. Easy to install yoke mounting system with safety tether included. LED Light Engine: The MD8LED uses up to 480 individual Nichia LEDs specifically mixed to provide a minimum of 80 CRI with 3 SCDM color consistency. The LED light engine is available in multiple lumen packages and color temperatures to Ceiling Cutout: 81/4" Maximum Ceiling Thickness 11/4" Consult factory for ceiling thickness to 2" For conversion to millimeters, multiply inches by 25.4 Not to Scale accommodate any design requirement. The use of individual LEDs to achieve these lumen packages enables optimal thermal management while creating a visually pleasing diffuse appearance in the ceiling. The LED light engine is coupled to a passive heat sink utilizing innovative heat pipe technology, and is protected with a self resetting thermal protector. 20-3/4" LED DRIVER: Each string of 120 LEDs is powered by a single 40 watt, constant current Thomas Research Products LED driver (up for 4 drivers per fixture). The driver is UL8750 and Class 2 compliant. Lutron Series A drivers also available 11-3/4" DIMMING: Standard 0-10v dimming provides flicker-free dimming to 10%. For sizing of the circuit control, the dimming circuit may require up to 1.2mA of sink current. See list of compatible dimmers on page 4. 15-3/8" Lutron 2-wire, 3-wire, and EcoSystem dimming available to 1%. Installation: Universal adjustable mounting brackets accommodate 1.5” or ¾” lathing channel or ½” EMT (by others) or Prescolite B24 or B6 bar hangers. certificationS: CSA certified to US and Canadian safety standards. Suitable for damp locations, or wet locations with a lens. ENERGY STAR® qualified. Product is marked spacing and must be installed with the following minimum spacings: "A"** 12" 13-1/4"** 7-3/4" 9" REFLECTOR* 25° 35° 45° 55° Center to Center of adjacent luminaires : 36” Minimum Overhead Clearance: 19” (To bottom of metal pan) HEIGHT (A) 18" 15" 11" 10" *WITH LENS ASSEMBLY **Dimension “A” may or may not be limiting vertical dimension depending upon chosen reflector. Center of Luminaire to Side of Building Member : 18” Warranty: 5 Year Warranty. See www.prescolite.com for details. Order housing, reflector, and accessories separately Catalog Number: MD8LED3L35K8-8MD3LMD25SLB24 Housing OUTPUT LED COLOR TEMP CRI VOLTAGE OPTIONS TRIM AperturE ❑27K ❑8 ❑Blank ❑Blank ❑8MD ❑MD8LED ❑3L2 3000 Standard 2700 80+ 120 thru 8" Alzak 8" High 277 CRI Delivered 0-10V Kelvin Reflector output Volt Lumens dimming ❑30K LED 2 3 ❑6L ❑347 3000 ❑HDM housing 6000 347 Volt Kelvin Lutron Delivered ❑35K 3-wire/ Lumens 3500 EcoSystem 2 ❑9L Kelvin to 1% 9000 ❑40K ❑2DM Delivered 4000 Lutron 2-wire Lumens Kelvin Leading ❑12L2 ❑50K Edge to 1% 12000 5000 (120v only) Delivered Kelvin ❑WIH Lumens WiHUBB enabled Must specify either WT or BT for painted cone Housing and reflector output must be consistent 3 Available in standard 0-10V dimming only. 1 2 A Division of Hubbell Lighting, Inc. output ❑3L2 Suitable for 3000 Lumen Housings ❑6L2 Suitable for 6000 Lumen Housings ❑9L2 Suitable for 9000 Lumen Housings ❑12L2 Suitable for 12000 Lumen Housings Example: MD8LED12L35K8-8MD12LWFL45 BEAM ANgle REFLECTOR FINISH Reflector COLORS ❑MD25 ❑Blank ❑Blank Specular Nominal Clear Alzak 25 ❑SS ❑CG Degree SemiChampagne Cutoff Specular Gold Alzak ❑FL35 ❑MFC ❑BL Nominal American Black Alzak 35 Matte ❑WE Degree Wheat Alzak Cutoff ❑LW ❑WFL45 Light Wheat Nominal Alzak 45 ❑PW Degree Pewter Alzak Cutoff ❑BC1 ❑XFL55 Painted Black Nominal Cone 55 ❑WC1 Degree Painted Cutoff White Cone Reflector OPTIONS In a continuing effort to offer the best product possible we reserve the right to change, without notice, specifications or materials that in our opinion will not alter the function of the product. Web: www.prescolite.com • Tech Support: (888) 777-4832 ACCESSORIES ❑B24 ❑CL Set of two(2) 24" Clear bar Lens over hangers for T-bar LED's ceilings (wet location) ❑B6 Set of two (2) bar ❑SL hangers for ceiling Solite joist up to 24" Softening centers Lens over LED's ❑SCA8D_ (wet Sloped ceiling location) adapter (see ❑WT note on page 4) Painted White Flange ❑BT Painted Black Flange ARCH-LED-013 TYPE B - 120/277V PHOTOMETRIC DATA DRIVER DATA Architektur- 8" High Lumen MD8LED MD8LED3L MD8LED6L MD8LED9L MD8LED12L Lumen Multiplier Table Input Voltage 120-277V 120-277V 120-277V 120-277V Input Frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz Input Current 0.35 (120v) 0.70 (120v) 1.05 (120v) 1.40 (120v) 0.15 (277v) 0.30 (277v) 0.45 (277v) 0.61 (277v) Input Power 42W 84W 126W 168W Constant Current Output 1100mA 1100mA 1100mA 1100mA Power Factor ≥0.90 ≥0.90 ≥0.90 ≥0.90 THD <25% <20% <20% <20% EMI Filtering FCC 47CFR FCC 47CFR FCC 47CFR FCC 47CFR Photometrics for the MD8LED are published below at a nominal 3500 Kelvin temperature. This table may be used to approximate the lumen values at different Kelvin temperatures. Power consumption would stay the same. 5000 Kelvin 4000 Kelvin 3500 Kelvin 3000 Kelvin 2700 Kelvin Solite Lens OF 15, 4 Class APart 15, Class APart 15, Class APart 15, Class A Part Operating Temperature -20ºC to 40ºC -20ºC to 40ºC -20ºC to 40ºC -20ºC to 40ºC Dimming 0-10V 0-10V 0-10V t 0-10V 1.14 1.03 1.00 1.00 0.91 0.87 Over-voltage, over-current, short-circuit protected **347V: t L D Utilizes Driver step-down transformer with 7% power loss for all 347V models *See application notes on page 1 for details MD8LED12L35K8-8MD12LXFL55 LED Light Engine: 3500K, 80+ CRI System Wattage: 168.2W Fixture Delivered Lumens: 12789 Fixture Efficacy: 76.0 Spacing Criteria: 1.4 2050 60˚ 4100 45˚ 6150 0˚ 15˚ 30˚ 8345 0-60 12545 3000 60˚ 6000 45˚ 9000 0˚ 15˚ 30˚ 65.3 98.1 0-90 12789 100.0 0-180 12789 100.0 CANDELA DISTRIBUTION DEG CANDELA 0 5 15 25 35 45 55 65 75 85 90 6016 5998 5596 6011 5526 4057 1269 105 31 6 0 MD8LED12L35K8-8MD12LWFL45 LED Light Engine: 3500K, 80+ CRI System Wattage: 167.8W Fixture Delivered Lumens: 12240 Fixture Efficacy: 72.9 Spacing Criteria: 1.2 75˚ %FIXT 0-40 80% 70% 50% 30% 7401 7616 8276 7997 6025 1888 155 48 18 4 0 Test No. 6231 Tested at 25ºC Ambient in accordance to IESNA LM-79-2008 10% 20% Effective Floor Cavity Reflectance % Wall Reflectance 30 10 50 30 112 109 105 103 109 106 104 101 102 100 98 104 98 93 89 102 96 92 88 93 89 86 70 50 30 10 70 98 90 97 87 95 84 95 87 94 84 92 82 3 97 82 78 74 80 76 73 90 89 80 82 73 77 68 95 88 50 87 79 30 10 50 30 10 50 81 77 73 67 85 80 77 71 75 67 75 70 66 73 68 10 65 5 84 73 66 60 82 72 65 60 70 64 59 68 63 59 67 62 58 6 78 67 59 53 76 66 58 53 64 58 53 62 57 52 61 56 52 7 73 61 53 48 71 60 53 48 59 52 47 57 51 47 56 51 47 8 68 56 48 43 66 55 48 43 54 47 43 53 47 43 52 46 42 9 10 63 60 51 48 44 40 39 36 62 58 51 47 44 40 39 35 50 46 43 40 39 35 49 45 43 39 39 35 48 44 42 39 38 MD8LED12L35K8 8MD12LXFL55 LUMENS 35 Test No. 6234 Luminance Data in Candela/m2 Angle in Vertical Average - 0º 45° 87700 55° 8876 %FIXT 0-40 10452 0-60 12166 85.4 99.4 0-90 12240 100.0 65° 3731 0-180 12240 100.0 75° 85° 2284 1507 CANDELA DISTRIBUTION CANDELA 3934 2261 1 2 4 ZONE 0 5 15 25 35 45 55 65 75 85 90 8161 75° 85° % Effective Ceiling Cavity Reflectance ZONAL LUMEN SUMMARY DEG 65° Zonal Cavity Method COEFFICIENTS OF UTILIZATION Test No. 6234 Tested at 25ºC Ambient in accordance to IESNA LM-79-2008 90˚ LUMENS Room Cavity Ratio 75˚ ZONE Zonal Cavity Method COEFFICIENTS OF UTILIZATION Room Cavity Ratio 90˚ Luminance Data in Candela/ Sq. Meter Average - 0º Angle in Vertical 45° 188452 55° 72670 ZONAL LUMEN SUMMARY % Effective Ceiling Cavity Reflectance 80% 70% 50% 30% 10% 20% Effective Floor Cavity Reflectance % Wall Reflectance 30 10 50 30 1 2 113 110 107 105 110 108 105 103 104 102 100 100 98 107 101 97 93 104 99 95 92 96 93 90 93 90 97 88 96 90 95 88 94 86 3 100 93 80 84 81 79 4 70 50 30 10 70 94 86 88 80 83 75 98 93 50 92 85 30 87 79 10 50 30 10 50 83 75 89 83 85 78 81 74 87 81 83 76 73 79 75 10 72 5 89 79 73 68 87 79 72 68 77 71 67 75 70 67 73 69 66 6 84 74 67 62 82 73 66 62 71 66 61 70 65 61 68 64 61 7 79 68 62 57 77 68 61 57 66 61 56 65 60 56 64 59 56 8 74 64 57 52 73 63 57 52 62 56 52 61 55 52 60 55 51 9 10 70 66 59 55 53 49 48 45 69 65 59 55 52 49 48 44 58 54 52 48 48 44 57 53 51 48 48 44 56 52 51 48 48 MD8LED12L35K8 8MD12LWFL45 Web: www.prescolite.com • Tech Support: (888) 777-4832 701 Millennium Boulevard • Greenville, SC 29607 U.S.A. • Phone (864) 678-1000 Copyright ©2014 Prescolite, Inc., a division of Hubbell Lighting, Inc. All Rights Reserved Specifications subject to change without notice. • Printed in U.S.A. • LFR-LED-013 • 2/14/14 44 Test No. 6231 TYPE B - 120/277V PHOTOMETRIC DATA ct r MD8LED12L35K8-8MD12LFL35 LED Light Engine: 3500K, 80+ CRI System Wattage: 167.4W Fixture Delivered Lumens: 11657 Fixture Efficacy: 69.6 Spacing Criteria: 1.0 ZONE 75˚ 3500 60˚ 7000 45˚ 10500 15˚ Luminance Data in Candela/m2 Angle in Vertical Average - 0º 45° 15375 55° 4524 ZONAL LUMEN SUMMARY 90˚ 0˚ Architektur- 8" High Lumen MD8LED ff manual chuc LUMENS 0-40 11273 96.7 0-60 11682 100.2 0-90 11657 100.0 65° 2098 0-180 11657 100.0 75° 85° 1269 754 CANDELA DISTRIBUTION DEG CANDELA 0 5 15 25 35 45 55 65 75 85 90 9792 10086 10492 8868 5821 331 79 27 10 2 0 Zonal Cavity Method COEFFICIENTS OF UTILIZATION Room Cavity Ratio irst re % Effective Ceiling Cavity Reflectance 80% 70% 50% 30% 10% 20% Effective Floor Cavity Reflectance % Wall Reflectance 30 10 50 30 1 2 113 111 108 106 111 108 106 104 104 103 101 101 99 108 103 99 95 106 101 97 94 98 95 92 95 92 98 90 97 92 96 90 95 88 3 102 96 83 87 84 82 4 70 50 30 10 70 97 89 91 84 50 87 100 94 79 95 88 30 90 83 10 50 30 10 50 86 79 92 86 88 81 85 89 78 84 86 80 77 82 79 10 76 5 92 83 77 73 90 82 77 73 81 76 72 79 75 71 77 74 71 6 87 78 72 68 86 77 71 67 76 71 67 74 70 66 73 69 66 7 83 73 67 63 81 72 67 62 71 66 62 70 65 62 69 65 61 8 78 69 62 58 77 68 62 58 67 62 58 66 61 58 65 61 57 9 10 74 71 65 61 58 55 54 51 73 70 64 60 58 55 54 51 63 60 58 54 54 51 62 59 57 54 54 51 61 58 57 54 54 MD8LED12L35K8 8MD12LFL35 50 Test No. 6233 30˚ Test No. 6233 Tested at 25ºC Ambient in accordance to IESNA LM-79-2008 ZONE 75˚ 5000 60˚ 10000 45˚ 0˚ 15˚ LUMENS %FIXT 0-40 6539 0-60 6602 99.8 0-90 6616 100.0 65° 699 0-180 6616 100.0 75° 85° 508 377 98.8 CANDELA DISTRIBUTION DEG CANDELA 0 5 15 25 35 45 55 65 75 85 90 13273 13813 12329 3491 201 54 20 9 4 1 0 Zonal Cavity Method COEFFICIENTS OF UTILIZATION Room Cavity Ratio 90˚ 15000 Luminance Data in Candela/m2 Angle in Vertical Average - 0º 45° 2508 55° 1145 ZONAL LUMEN SUMMARY MD8LED12L35K8-8MD12LMD25 LED Light Engine: 3500K, 80+ CRI System Wattage: 167.4W Fixture Delivered Lumens: 6616 Fixture Efficacy: 39.5 Spacing Criteria: 0.6 % Effective Ceiling Cavity Reflectance 80% 70% 50% 30% 10% 20% Effective Floor Cavity Reflectance % Wall Reflectance 10 50 30 1 2 115 112 110 108 112 110 108 107 106 105 103 102 101 100 110 106 103 100 108 105 102 99 102 99 97 99 97 95 70 50 30 10 70 99 96 98 94 97 93 3 106 101 97 93 91 89 4 102 97 92 50 30 94 104 100 96 89 101 95 91 10 50 30 10 50 93 88 97 93 94 90 92 87 95 92 30 93 89 90 86 90 87 10 85 5 99 92 88 84 97 91 87 84 90 86 83 88 85 83 87 84 82 6 95 88 84 80 94 88 83 80 86 82 80 85 82 79 84 81 79 7 92 85 80 77 91 84 80 76 83 79 76 82 79 76 81 78 76 8 89 82 77 74 88 81 77 73 80 76 73 79 76 73 78 75 73 9 10 86 83 78 76 74 71 71 68 85 82 78 75 74 71 70 68 77 75 73 71 70 68 76 74 73 70 70 68 76 73 72 70 70 MD8LED12L35K8 8MD12LMD25 30˚ Test No. 6232 Tested at 25ºC Ambient in accordance to IESNA LM-79-2008 Web: www.prescolite.com • Tech Support: (888) 777-4832 701 Millennium Boulevard • Greenville, SC 29607 U.S.A. • Phone (864) 678-1000 Copyright ©2014 Prescolite, Inc., a division of Hubbell Lighting, Inc. All Rights Reserved Specifications subject to change without notice. • Printed in U.S.A. • LFR-LED-013 • 2/14/14 67 Test No. 6232 TYPE B - 120/277V PHOTOMETRIC DATA Dimming compatibility table *0-10V Only. See www.lutron.com for HDM & 2DM Compatibility Control Manufacturer Wallbox Dimmer Douglas Lighting Controls WPC 5721 Entertainment Technology Tap Glide TG600FAM120 (120V) Tap Glide Heatsink TGH1500fam120 (120V) Oasis DA200OFAMU (120/277V) Honeywell, Inc. EL731A1019 and EL7315A1009 HUNT Dimming Preset Slide: PS-010-IV-120V and PS-010-WH-120V Preset Slide: PS-010-3W-IV-120V and PS-010-3W-WH-120V Preset Slide: PS-010-IV-277V and PS-010-WH-277V Preset Slide: PS-010-3W-IV-277V and PS-010-3W-WH-277V Preset Slide, controls FD-010: PS-1FC-010-IV- and PS-IFC-010-32-WH-120/277V Preset Slide, controls FD-010: PS-IFC-010-32-IV- and PS-IFC-010-3W-WH-120/277V Remoted mounted unit: FD-010120V and FD-010-277V Lehigh Electric Products Co. Leviton Lighting Controls Div. Lutron Electronics Co., Inc. PDM Electrical products Starfield Controls The Watt Stopper, Inc. Power Booster Available EL7305A1010 Solitaire PBX Leviton Centura Fluorescent Control System IllumaTechTM IP7 Series CN100 PE300 Visit www.lutron.com/advance for the latest control information and selection WPC-5721 TR61 with DALI Interface port RT03 DALInet Router LS-4 used with LCD-101 and LCD-103 wiHUBB® Fixture comes with a pre-installed In-Fixture Module (1 relay, 0-10V) compatible with the HBA wiHUBB system. Actual dimming requires the selection of 0-10V dimming ballast as well. Consult factory for compatibility with EM fixtures. SCA8D_ When ordering a sloped ceiling adapter, specify the degree of slope in 5º increments, maximum of 35º. For a more precise degree or wet ceiling applications, please contact factory. Sloped ceiling adapter and housing must be installed at the same time. Web: www.prescolite.com • Tech Support: (888) 777-4832 701 Millennium Boulevard • Greenville, SC 29607 U.S.A. • Phone (864) 678-1000 Copyright ©2014 Prescolite, Inc., a division of Hubbell Lighting, Inc. All Rights Reserved Specifications subject to change without notice. • Printed in U.S.A. • LFR-LED-013 • 2/14/14 TYPE C em - 120/277V Type: Project Name: 8HF D I M E N S I O N S R E F L E C T O R K I T L E N S E D 8˝ Aperture 8611 Tempered Clear Tempered Prismatic 8614 8616Fresnel 6 7/8˝ 6 7/8˝ Reflector standard Clear “Alzak”. Other options consult factory. 7 1/4˝ Splay/Lens Holder Finish Options 7 1/4 8 1/2˝ 8 1/2˝ Specular Clear “Alzak” SCL SGC Soft Glow Clear Etch Clear ECL WHTWhite Options 14 1/2˝ Polished Flange PF Ceiling Cut Out 7 7/8˝ 14 7/8˝ L E N S E D B A F F L E D F E A T U R E S 8˝ Aperture 8˝ COMMER CI AL H O R I ZO N TAL FL UO R ESCENT Electrogalvanized steel frame components with spring steel reflector clips for fast assembly of reflector. Innovative, rigid bar hangers incorporate formed cross sections, joist positioning tabs, integral nails, auxiliary nailholes, T-Bar slots and holes for locking bars to T-Bar using #8 self-tapping screws (supplied by others). Bars extend 14˝-24˝. Frame will also accept Caddy Bar #517B for fast installation in drop-in ceilings, bars extend 27˝. 8621 Tempered Clear Tempered Prismatic 8624 8626Fresnel Electronic ballast, Class P, 50/60 HZ-120-277, Programmed Start, thermally protected, 98% Power Factor, 1.00 Ballast Factor, <10% THD, Class A sound rated. Minimum starting temperature -18°C/0°F. UL Listed component. BL WH Heavy gauge electrogalvanized steel junction box, prewired and grounded with easy access from below. Listed for through branch circuit wiring. Aluminum socket housing with quick a­ ssembly hardware for fast assembly. UL Listed socket and electrical connectors. Heavy gauge spun aluminum low iridescent reflector with self trimming white painted flange. Polished Flange available. 6 7/8˝ Reflector standard Clear “Alzak”. Other options consult factory. 7 1/4˝ Baffled Finish Options 8 1/2˝ Black Baffle White Baffle T U R B O L O U V E R 8˝ Aperture Turbo Louver 8676 Finish Options 6 7/8˝ Specular Clear “Alzak” Soft Glow Clear Etch Clear White Reflector SCL SGC ECL WHT 7 1/2˝ 8 3/4˝ Options Polished Flange PF Features Manufactured and Listed to UL 1598, ETL and CSA standards. Suitable for Damp Locations. Wet location under covered ceiling. ORDERING INFORMATION Lamps and Wattage Quad and Triple Tube 1x13 1x18 DTT 2x13 2x18 DTT 2x26 DTT TRT 1 Lamp Only 1x18 TRT 1x26, 1x32, 1x42 TRT EXAMPLE: 8HF113E1-2-8611-SCL Housing Ballast Reflector Finish Options 8HF113 8HF118 8HF213 8HF218 8HF226 E1-2 E3 DL DAX1 DAX2 DA7 8611 8614 8616 SCL SGC ECL WHT F EM PF TR DGSK 8HF118 8HF132 Baffled 8621 8624 8626 Baffle BL WH Turbo Louver 8676 Ballast Options Electronic 120-277 volt is standard E1-2 -Electronic (120-277V) E3 -Electronic (347V) Dimming Ballast Options DL - Lutron Eco System (120-277V) DAX1 - Advance Mark X (120V) DAX2 - Advance Mark X (277V) DA7 - Advance Mark VII (120-277V) Vantage reserves the right to change components, finishes or design details in any manner which does not alter the installed appearance or reduce performance and intended function. Options Descriptions F - Fused EM - Emergency Battery PF - Polished Flange TR - Tamper Resistant DGSK - Silicone-Sealed Lens & Gasketing s See Options pages for other options and finishes. Vantage recommends the use of Philips or Sylvania lamps. Rev 01/14 16 V A N T A G E L I G H T I N G I N C V A N T A G E L T G . C O M TYPE C - 120/277V Project Name: 8HF Type: D I M E N S I O N S R E F L E C T O R K I T L E N S E D 8˝ Aperture 8611 Tempered Clear Tempered Prismatic 8614 8616Fresnel 6 7/8˝ 6 7/8˝ Reflector standard Clear “Alzak”. Other options consult factory. 7 1/4˝ Splay/Lens Holder Finish Options 7 1/4 8 1/2˝ 8 1/2˝ Specular Clear “Alzak” SCL SGC Soft Glow Clear Etch Clear ECL WHTWhite Options 14 1/2˝ Polished Flange PF Ceiling Cut Out 7 7/8˝ 14 7/8˝ L E N S E D B A F F L E D F E A T U R E S 8˝ Aperture 8˝ COMMER CI AL H O R I ZO N TAL FL UO R ESCENT Electrogalvanized steel frame components with spring steel reflector clips for fast assembly of reflector. Innovative, rigid bar hangers incorporate formed cross sections, joist positioning tabs, integral nails, auxiliary nailholes, T-Bar slots and holes for locking bars to T-Bar using #8 self-tapping screws (supplied by others). Bars extend 14˝-24˝. Frame will also accept Caddy Bar #517B for fast installation in drop-in ceilings, bars extend 27˝. 8621 Tempered Clear Tempered Prismatic 8624 8626Fresnel Electronic ballast, Class P, 50/60 HZ-120-277, Programmed Start, thermally protected, 98% Power Factor, 1.00 Ballast Factor, <10% THD, Class A sound rated. Minimum starting temperature -18°C/0°F. UL Listed component. BL WH Heavy gauge electrogalvanized steel junction box, prewired and grounded with easy access from below. Listed for through branch circuit wiring. Aluminum socket housing with quick a­ ssembly hardware for fast assembly. UL Listed socket and electrical connectors. Heavy gauge spun aluminum low iridescent reflector with self trimming white painted flange. Polished Flange available. 6 7/8˝ Reflector standard Clear “Alzak”. Other options consult factory. 7 1/4˝ Baffled Finish Options 8 1/2˝ Black Baffle White Baffle T U R B O L O U V E R 8˝ Aperture Turbo Louver 8676 Finish Options 6 7/8˝ Specular Clear “Alzak” Soft Glow Clear Etch Clear White Reflector SCL SGC ECL WHT 7 1/2˝ 8 3/4˝ Options Polished Flange PF Features Manufactured and Listed to UL 1598, ETL and CSA standards. Suitable for Damp Locations. Wet location under covered ceiling. ORDERING INFORMATION Lamps and Wattage Quad and Triple Tube 1x13 1x18 DTT 2x13 2x18 DTT 2x26 DTT TRT 1 Lamp Only 1x18 TRT 1x26, 1x32, 1x42 TRT EXAMPLE: 8HF113E1-2-8611-SCL Housing Ballast Reflector Finish Options 8HF113 8HF118 8HF213 8HF218 8HF226 E1-2 E3 DL DAX1 DAX2 DA7 8611 8614 8616 SCL SGC ECL WHT F EM PF TR DGSK 8HF118 8HF132 Baffled 8621 8624 8626 Baffle BL WH Turbo Louver 8676 Ballast Options Electronic 120-277 volt is standard E1-2 -Electronic (120-277V) E3 -Electronic (347V) Dimming Ballast Options DL - Lutron Eco System (120-277V) DAX1 - Advance Mark X (120V) DAX2 - Advance Mark X (277V) DA7 - Advance Mark VII (120-277V) Vantage reserves the right to change components, finishes or design details in any manner which does not alter the installed appearance or reduce performance and intended function. Options Descriptions F - Fused EM - Emergency Battery PF - Polished Flange TR - Tamper Resistant DGSK - Silicone-Sealed Lens & Gasketing s See Options pages for other options and finishes. Vantage recommends the use of Philips or Sylvania lamps. Rev 01/14 16 V A N T A G E L I G H T I N G I N C V A N T A G E L T G . C O M TYPE D - 120/277V PROJECT INFORMATION ROUGH-HOUSE™ Job Name Fixture Type RHL7 SERIES Catalog Number PRODUCT FEATURES: Approved by »»Surface mount – ceiling or wall; 7"×24", 7"×36" or 7"×48" »»18-gauge cold rolled steel housing »»UV-Stabilized high impact acrylic lens »»ADA Compliant »»One year guarantee SPECIFICATIONS: HOUSING: 18-gauge CRS. TGIC polyester powder coat finished – 5-step pre-treatment. REFLECTOR: Full reflector/wire cover – 92% reflectivity. LENS: UV-stabilized, high impact pearlescent acrylic. Smooth exterior, linear prismatic interior. Nominal thickness .156". Lens locked in place with tamper-resistant stainless steel Torx® with center pin fasteners. END CAPS: High impact resistant, injection molded black or white polycarbonate. HARDWARE: Stainless steel, tamper-resistant Torx fasteners. ELECTRICAL: Class P ballasts. Fluorescent electronic 120/277/347 and dual voltage ballasts high power factor. INSTALLATION: Standard four-point (24" and 36" housing) or six-point (48" housing) mounting required for One Year Guarantee. For surface conduit installation, end cap interior is provided with drill points for field drilling. LISTINGS: UL and CUL listed for Damp Location. ADA Compliant. ADA ORDERING INFORMATION (Ex: RHL7-48-MW-PIA-2-32-IS-1-347) Model RHL7 Length 24 Finish Lens Type MW Lamp Qty PP 2 Length 242' 363' 484' Lens Type PIA Pearlescent High Impact Acrylic CP Clear Polycarbonate PP Pearlescent Polycarbonate Finish MW Matte White MB Matte Black Lamp Quantity (Cross Section) 1One 2Two Lamp Type 17 Ballast Type Ballast Qty IS Voltage 1 Options DV EL* 500 Minimum Lumen Battery Pack (90 Minutes; 32°F Starting Temperature) FS Single Fuse & Holder ● PEL* 1100 Minimum Lumen Battery Pack (90 Minutes; 32°F Starting Temperature) PH Phillips Head Lens Retention Screw ■ Ballast Type IS Instant Start Electronic <10% THD (T8) RS Rapid Start Electronic <10% THD (T8,T5) SB Specified Ballast Ballast Quantity 1One 2Two Lamp Type 2' Lengths 14F14T5 17F17T8 * Dry Location only (EL option). One lamp maximum in emergency mode ■ 2' and 3' fixtures available in one lamp cross section only; have minimum 350-450 lumen battery pack ● 4' fixtures only Voltage 120 120 Volts 277 277 Volts 347 347 Volts (T8 only) DV 120-277 Volts 3' Lengths 21F21T5 25F25T8 Options 4' Lengths 28F28T5 32F32T8 DIMENSIONAL DATA CROSS SECTION MOUNTING HOLES B 7.04" C 0.312" Dia. Mounting Holes 4.50" 2.87" A DIMENSIONAL DATA (IN INCHES) A B 4' – T8 4' – T5 3' – T8 3' – T5 2' – T8 2' – T5 48.8044.00 46.8442.00 36.8032.00 35.0330.00 24.8020.00 23.2218.00 C 22.00 21.00 n/a n/a n/a n/a www.kenall.com P: 800-4-Kenall F: 847-360-1781 1020 Lakeside Drive Gurnee, Illinois 60031 When you see this image, you will know the Kenall product shown or described is designed and manufactured in the USA with components purchased from US suppliers, and meets the Buy American requirements under the ARRA. Kenall has not determined the origin of its domestically purchased components or the subcomponents thereof. Content of specification sheets is subject to change; please consult www.kenall.com for current product details. © 2013 Kenall Mfg. Co. All rights reserved. RHL7-120313 TYPE E em - 120/277V KL Bi-pin Premium Industrial / 2, 3, or 4-Lamp T5, T5HO, T8 Project Information Project Name Type Catalog No. Date Construction Features • • • • • • • Available in 4' and 8' lengths Apertured reflectors have 15% uplight Spring loaded turret lampholders 6' lamp spacing For individual or continuous row mounting Channel ends double as joiners Full depth end closures available Heavy steel housing with longitudinal reinforcing ribs for extra strength. Reflector die-embossed with transverse ribs for maximum rigidity. Solid top or 15% uplight versions with extruded openings available. Finish White painted parts are treated with a five stage phosphate bonding process and finished with a high reflectance baked enamel. LSR and M4R reflectors specular room side, Mill finish aluminum top surface. Ballasts Energy efficient, thermally protected, automatic resetting, Class P, high power factor, sound rated Ordering Information KL 4 Model Size KL Premium Industrial 4 4' 8 8' – 2 No. of Lamps in cross section 2 Two 3 Three 4 Four Accessories (Order Separately) KZT Zip Tee Hanger - 1½" spacer on T-bar ceiling KTH Slide Clamp Tong Hanger S18 18" Stem, canopy and 8° aligner SS18 18", 45° Swivel Stem & Canopy KHC 24" Chain Hanging Assembly KLEC Full Depth End Closure KLWG4 Wire Guard 4' lg. - 2 required per 8' fixture KLEGG White Straight Blade Egg Crate Louver 4' - 2 required per 8' fixture OS1K Occupancy Sensor Kit, 120/277/347V, One Relay1 A, unless otherwise specified. CEE NEMA Premium compliant. Electrical Standard class “P”, thermally protected, autoresetting HPF ballast, sound rated A. CEE NEMA Premium compliant. All ballast leads extend a minimum of 6" through access location. NEC/CECcompliant ballast disconnect is standard. Certification All luminaires are built to UL 1598 standards and bear appropriate UL and cUL or CSA labels. Damp location labeling is standard. Emergency-equipped fixtures labeled UL 924. Example KL4-232-U-EU-GLR-PAF 17 – E – U U Lamp Type Reflector Type Voltage 28 4', T5: 28 Watt 32 4', T8: 32, 30, 28 or 25 Watt 54 4', T5HO: 54 or 51 Watt U Apertured Reflector for Uplight ST Solid Top (No Uplight) M4RST Solid Top Reflector with 95% Reflective Specular Silver Finish M4RU Apertured Reflector with 95% Reflective Silver Finish U 120V-277V 347 347V EL141ST – Options GLR GMF El141 BC Fast Blow Fuse Slow Blow Fuse Emergency Battery Pack (self test) Branch Circuit Plug-on Wiring System (See options section for details.) PAF Paint After Fabrication NYC NYC Compliant NYCU NYC Compliant, Union Label Ballast E Electronic T8, Instant Start 4E 4-Lamp Electronic T8, Instant Start EP Electronic, Program Start 4EP 4-Lamp Electronic, Program Start For others available, see Ballast Options. Use programmed start ballast. Not recommended for use with instant start. For more occupancy/daylight harvesting sensor accessories see Technical section. 1 Page 1/2 Rev. 07/15/13 © 2013 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd. Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com Industrials / KL bi-pin TYPE E em - 120/277V KL Bi-pin Premium Industrial / 2, 3, or 4-Lamp T5, T5HO, T8 Photometric Data Zonal Lumen Summary Zone Luminaire Data 0-30 0-40 0-60 0-90 90-120 90-130 90-150 90-180 0-180 KL4-232-U KL Industrial 1' × 4' 2-Lamp Industrial with Apertured White Reflector R2P32 0.95 FO32/41K 2900 74 N/A 0º = 1.27 90º = 1.30 Length: 4.00 Width: 1.02 Height: 0.00 Ballast Ballast Factor Lamp Lumens per Lamp Watts Shielding Angle Spacing Criterion Luminous Opening in Feet 1090 1807 3314 4396 179 263 518 817 5212 18.8 31.1 57.1 75.8 3.1 4.5 8.9 14.1 89.9 Energy Data 20.9 34.7 63.6 84.3 3.4 5.0 9.9 15.7 100.0 Indoor Candela Plot RCR 70 94 85 77 71 65 60 55 51 48 45 80 50 30 90 86 78 71 68 60 60 52 53 45 48 39 43 35 39 31 36 28 33 26 10 82 66 54 46 39 34 30 26 23 21 70 90 81 74 67 62 57 53 49 46 43 70 50 30 86 83 75 69 65 58 58 50 51 44 46 38 42 34 38 31 35 28 32 25 10 79 64 53 45 38 33 29 26 23 21 50 80 69 60 53 48 43 39 35 33 30 50 30 77 64 55 47 41 36 32 29 26 24 10 74 61 50 42 36 32 28 25 22 20 89.9% Luminaire Efficacy Rating (LER) IESNA RP-1-1993 Compliance Comparative Yearly Lighting Energy Cost per 1000 Lumens 67 Non-Compliant $3.58 based on 3000 hrs. and $0.08 per KWH AVG. LUMINANCE (Candela/Sq. M.) Coefficients of Utilization (%) RC RW 1 2 3 4 5 6 7 8 9 10 Total Luminaire Efficiency Average Luminance Angle Luminaire Test 10183 Test Date 1/8/03 Lumens % Lamp % Fixt. 0 0 62 51 42 36 31 27 24 21 19 17 0 30 40 45 50 55 60 65 70 75 80 85 0.0 22.5 45.0 67.5 90.0 3654 3616 3578 3544 3509 3459 3387 3296 3155 2956 2674 2149 3654 3622 3595 3582 3579 3569 3493 3477 3595 3374 3464 2967 3654 3671 3706 3712 3776 3923 3894 3652 3718 4210 3342 2876 3654 3726 3788 3921 4104 3905 3704 3839 4327 4353 2370 2785 3654 3717 3833 4000 4059 3827 3667 3964 4536 3955 2355 2815 RCR = Room Cavity Ratio RC = Effective Ceiling Cavity Reflectance RW = Wall Reflectance Dimensional Data Mounting Accessories 9813/16" 887/8" 2" 2" 11/8" 15/16" 431/32" 4913/32" NOTE: Fixtures with T5/T5HO lamping are 48" and 98" in length. 2" 497/16" 39½" 2" 15/16" 11/8" 39½" 431/32" KHC S18 43/16" 61/8" 35/8" 6" 133/8" KZT KTH A: 7/8" Diameter knockout B: .570" × .656" Strain Relief knockout E: 11/8" Diameter knockout NOTE: All dimensions are in inches; dimensions and specifications are subject to change without notice. Please consult factory or check sample for verification. Page 2/2 Rev. 07/15/13 © 2013 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd. Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com Industrials / KL bi-pin Electrical Options TYPE E em - 120/277V Emergency Battery Packs Installed Technical Luminaires with factory installed battery packs will bear the UL Emergency equipment label. Dry location labeling standard. Standard inverter options below are not suitable for cold temperature starting, damp or wet location labeling. Optional inverters available for these applications. Consult factory or specify vendor’s catalog number. EL EL61 EL71 EL72 350-450 lumens for one 2'-4' lamp (T8, T12, U-Bent, TT) 500-600 lumens for one 2'-4' lamp (T8, T12, U-Bent, TT) 600-700 lumens for one 2'-8' lamp (T8, T12, U-Bent, TT) 600-700 total lumens for two 2'-8' lamps (T8, T12, U-Bent) EL141 EL142 EL5* EL5H* 1100-1400 lumens for one 2'-8' lamp (T8, T12, U-Bent, TT) 1100-1400 total lumens for two 2'-4' lamps 390-700 lumens for one 2'-4' T5/T5HO 725-1250 lumens for one 2'-4' T5/T5HO *These inverters not available in some 2' fixtures due to space constraints. Remote mounting using accessory enclosure (by others) recommended. Fusing Fusing is available on all fixtures to prevent over current from being transmitted upstream through the fixture as may be possible due to a dead short fault in a ballast. Specify GLR (fast blow) or GMF (slow blow) fusing options. Fuses are not UL listed to break under load and therefore are not a substitute for the in-fixture ballast disconnects supplied standard where required by the National Electric Code. Fixture Flex and Leads Fixture flex (also called pre-wire or whip) is a UL listed lighting component for recessed fixtures to provide the electrical wiring between the junction box and recessed fixture. Flex may be no longer than 6'. Typical cables use ⅜" flexible conduit and three or four 18 gauge leads. Three wires provides one line voltage hot lead. Add a wire for each separate hot lead required including separately switched ballasts, switch dim ballast or battery pack to be powered through the flex cable. Flex cables are shipped pre-wired to the recessed fixture. Add option designation to catalog number after ballast options. Eg. C388. Wire colors will be coded black/white/red/yellow plus a ground for line voltages. 588DIMM is available with black/white violet, grey and ground for use with low voltage dimming leads. Cable No. of Wires C Cable Cable Diameter 3 3 4 4 5 5 8 ⅜" 2 ½" Wire gauge 8 18 gauge 4 14 gauge 2 12 gauge Miscellaneous Fixtures and Electrical Options (add As Suffix on end of Catalog string) Fixture/Option Cat. No. PSW PSWD 4PSW Description Pull switch, one circuit, 120V only Pull switch, wired to the downlight circuit on a two circuit unit, 120V only Four-way pull switch for two circuit, two lamp unit, 120V only For Use With Selected strips, surface units and industrials. Contact factory for applications NL Medium base lampholder for 15W, 25W, 40W, or 60W T10 lamp. Lamp not included. 120V only AWN, SM units Fluorescent Night Light for 7W, T-4, G23 lamp Fluorescent Night Light for 9W, T-4, G23 lamp Fluorescent Night Light for 13W, T-4, GX23 lamp Lamp not included. PL ballast will default to fixture voltage unless specified Grounded convenience outlet (120V only) 4PS, SM, and WAL series PL7 PL9 PL13 GCO C6P15_ 6' Cord and Straight Blade, NEMA 5-15P, 15A (Add Voltage: 1 = 120) C6TL15_ 6' Cord and Twist-Lock Plug, NEMA L5-15P (120V) NEMA L7-15P (277V), 15A (Add Voltage: 1 = 120, 2 =277) C6TL20_ 6' Cord and Twist-Lock Plug, NEMA L5-20P (120V) NEMA L7-20P (277V), 20A (Add Voltage: 1 = 120, 2 =277) F3C_ 3-Conductor feed cord, 18ga stranded wire (Add length needed: 5 = 5', 10 = 10', or 15 = 15') F4C_ 4-Conductor feed cord, 18ga stranded wire (Add length needed: 5 = 5', 10 = 10', or 15 = 15') GLR Fast blow fuse, fuse amps based on fixture ordered 112 WPM, WM, WAL, UCS and UC Standard on SA, W All industrial fixtures All industrial fixtures All fixtures TYPE E - 120/277V KL Bi-pin Premium Industrial / 2, 3, or 4-Lamp T5, T5HO, T8 Project Information Project Name Type Catalog No. Date Construction Features • • • • • • • Available in 4' and 8' lengths Apertured reflectors have 15% uplight Spring loaded turret lampholders 6' lamp spacing For individual or continuous row mounting Channel ends double as joiners Full depth end closures available Heavy steel housing with longitudinal reinforcing ribs for extra strength. Reflector die-embossed with transverse ribs for maximum rigidity. Solid top or 15% uplight versions with extruded openings available. Finish White painted parts are treated with a five stage phosphate bonding process and finished with a high reflectance baked enamel. LSR and M4R reflectors specular room side, Mill finish aluminum top surface. Ballasts Energy efficient, thermally protected, automatic resetting, Class P, high power factor, sound rated Ordering Information KL 4 Model Size KL Premium Industrial 4 4' 8 8' – 2 No. of Lamps in cross section 2 Two 3 Three 4 Four Accessories (Order Separately) KZT Zip Tee Hanger - 1½" spacer on T-bar ceiling KTH Slide Clamp Tong Hanger S18 18" Stem, canopy and 8° aligner SS18 18", 45° Swivel Stem & Canopy KHC 24" Chain Hanging Assembly KLEC Full Depth End Closure KLWG4 Wire Guard 4' lg. - 2 required per 8' fixture KLEGG White Straight Blade Egg Crate Louver 4' - 2 required per 8' fixture OS1K Occupancy Sensor Kit, 120/277/347V, One Relay1 A, unless otherwise specified. CEE NEMA Premium compliant. Electrical Standard class “P”, thermally protected, autoresetting HPF ballast, sound rated A. CEE NEMA Premium compliant. All ballast leads extend a minimum of 6" through access location. NEC/CECcompliant ballast disconnect is standard. Certification All luminaires are built to UL 1598 standards and bear appropriate UL and cUL or CSA labels. Damp location labeling is standard. Emergency-equipped fixtures labeled UL 924. Example KL4-232-U-EU-GLR-PAF 17 – E – U U Lamp Type Reflector Type Voltage 28 4', T5: 28 Watt 32 4', T8: 32, 30, 28 or 25 Watt 54 4', T5HO: 54 or 51 Watt U Apertured Reflector for Uplight ST Solid Top (No Uplight) M4RST Solid Top Reflector with 95% Reflective Specular Silver Finish M4RU Apertured Reflector with 95% Reflective Silver Finish U 120V-277V 347 347V EL141ST – Options GLR GMF EL BC Fast Blow Fuse Slow Blow Fuse Emergency Battery Pack Branch Circuit Plug-on Wiring System (See options section for details.) PAF Paint After Fabrication NYC NYC Compliant NYCU NYC Compliant, Union Label Ballast E Electronic T8, Instant Start 4E 4-Lamp Electronic T8, Instant Start EP Electronic, Program Start 4EP 4-Lamp Electronic, Program Start For others available, see Ballast Options. Use programmed start ballast. Not recommended for use with instant start. For more occupancy/daylight harvesting sensor accessories see Technical section. 1 Page 1/2 Rev. 07/15/13 © 2013 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd. Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com Industrials / KL bi-pin TYPE E - 120/277V KL Bi-pin Premium Industrial / 2, 3, or 4-Lamp T5, T5HO, T8 Photometric Data Zonal Lumen Summary Zone Luminaire Data 0-30 0-40 0-60 0-90 90-120 90-130 90-150 90-180 0-180 KL4-232-U KL Industrial 1' × 4' 2-Lamp Industrial with Apertured White Reflector R2P32 0.95 FO32/41K 2900 74 N/A 0º = 1.27 90º = 1.30 Length: 4.00 Width: 1.02 Height: 0.00 Ballast Ballast Factor Lamp Lumens per Lamp Watts Shielding Angle Spacing Criterion Luminous Opening in Feet 1090 1807 3314 4396 179 263 518 817 5212 18.8 31.1 57.1 75.8 3.1 4.5 8.9 14.1 89.9 Energy Data 20.9 34.7 63.6 84.3 3.4 5.0 9.9 15.7 100.0 Indoor Candela Plot RCR 70 94 85 77 71 65 60 55 51 48 45 80 50 30 90 86 78 71 68 60 60 52 53 45 48 39 43 35 39 31 36 28 33 26 10 82 66 54 46 39 34 30 26 23 21 70 90 81 74 67 62 57 53 49 46 43 70 50 30 86 83 75 69 65 58 58 50 51 44 46 38 42 34 38 31 35 28 32 25 10 79 64 53 45 38 33 29 26 23 21 50 80 69 60 53 48 43 39 35 33 30 50 30 77 64 55 47 41 36 32 29 26 24 10 74 61 50 42 36 32 28 25 22 20 89.9% Luminaire Efficacy Rating (LER) IESNA RP-1-1993 Compliance Comparative Yearly Lighting Energy Cost per 1000 Lumens 67 Non-Compliant $3.58 based on 3000 hrs. and $0.08 per KWH AVG. LUMINANCE (Candela/Sq. M.) Coefficients of Utilization (%) RC RW 1 2 3 4 5 6 7 8 9 10 Total Luminaire Efficiency Average Luminance Angle Luminaire Test 10183 Test Date 1/8/03 Lumens % Lamp % Fixt. 0 0 62 51 42 36 31 27 24 21 19 17 0 30 40 45 50 55 60 65 70 75 80 85 0.0 22.5 45.0 67.5 90.0 3654 3616 3578 3544 3509 3459 3387 3296 3155 2956 2674 2149 3654 3622 3595 3582 3579 3569 3493 3477 3595 3374 3464 2967 3654 3671 3706 3712 3776 3923 3894 3652 3718 4210 3342 2876 3654 3726 3788 3921 4104 3905 3704 3839 4327 4353 2370 2785 3654 3717 3833 4000 4059 3827 3667 3964 4536 3955 2355 2815 RCR = Room Cavity Ratio RC = Effective Ceiling Cavity Reflectance RW = Wall Reflectance Dimensional Data Mounting Accessories 9813/16" 887/8" 2" 2" 11/8" 15/16" 431/32" 4913/32" NOTE: Fixtures with T5/T5HO lamping are 48" and 98" in length. 2" 497/16" 39½" 2" 15/16" 11/8" 39½" 431/32" KHC S18 43/16" 61/8" 35/8" 6" 133/8" KZT KTH A: 7/8" Diameter knockout B: .570" × .656" Strain Relief knockout E: 11/8" Diameter knockout NOTE: All dimensions are in inches; dimensions and specifications are subject to change without notice. Please consult factory or check sample for verification. Page 2/2 Rev. 07/15/13 © 2013 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice. 701 Millennium Blvd. Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com Industrials / KL bi-pin TYPE G LF - 120/24V www.ilight-tech.com Plexineon White 1X Series PRODUCT SUMMARY PRODUCT FEATURES • Three Kelvin temperatures • Energy efficient • Long lifetime • Stable and consistent color temperature • Low voltage • Easy to install • Cool to the touch • For use as exterior or interior accent lighting, direct view or indirect view applications, coves, signage & more Color Temperatures (+/- 10%) Power Supply • 3500°K • 4500°K • 6500°K • • • • Diffuser Color Class 2 24 VDC, 100 Watts - must be supplied by iLight Primary voltage: 120 or 120-277 depending on model Secondary voltage: 24VDC 4.1 A Max Maximum illumination length of a single LED power supply: 32 feet (9.75m) • Light amber hue (when not illuminated) Power Supply Tips Lengths Available • 2’, 4’, 6’, 8’ (610 mm, 1219 mm, 1830 mm, 2438 mm) • 2’ (610mm) field cuttable pieces • Illuminated outside corner pieces • Factory custom lengths available to the 1 nearest 1/2” (13mm) +/- 0.25’’ (6mm) • Factory convex or concave bends to minimum 1 inside radius of 5’’ (127mm) 1 • Factory “easy bends” to 3/16” (5mm) radius 2 • Gentle field bends to a 48”(1219mm) radius • 20% maximum overage for breaker for primary current draw • Do not plug multiple power supplies into one run of Plexineon • All iLight power supplies should be on an independent circuit • Recommend surge protection upstream from power supply • Verify correct voltage prior to wiring to non-switching power supplies Low Voltage Cable Maximum distance of low voltage cable in any given run: • 14 AWG: 40 feet (12.19m) • 12 AWG: 60 feet (18.29m) • 10 AWG: 100 feet (30.48m) 1. Drawing required for production 2. Field bending allowed only on fixtures without C-channel ORDERING INFORMATION CLASS VOLTAGE COLOR HOUSING LENGTH CHANNEL T 24 W35 S CL 27' NC T = Trim 24 = 24V • 118 South Clinton, Suite 370 • Chicago, IL 60661 00 2F = 2 Feet 00 SC = Stainless 4F = 4 Feet Steel Channel 6F = 6 Feet NC = No Channel 8F = 8 Feet CL = Custom Length TT = 2 Foot Cuttable PC = Outside Corner BE = Bend - Easy BN = Bend - Convex BV = Bend - Concave W35 = White 1X S = Silver 3500°K W45 = White 1X 4500°K W65 = White 1X 6500°K Specification sheets are subject to change without notice. For the most recent version, please refer to www.ilight-tech.com. iLight Technologies VERSION • T 312.876.8630 • F 312.876.8631 • MK-0110 www.ilight-tech.com TYPE G LF - 120/24V www.ilight-tech.com Plexineon White 1X Series MECHANICAL TECHNICAL INFORMATION Width & Height Housing Mounting • • • • • Stainless steel spring mounted clips • Clips to be 2” (51mm) in from end of piece and no more than 2’ (610mm) maximum between clips 0.55”(14mm)w x 1.35’’(34mm)h with C-channel UV and impact resistant acrylic diffuser UV resistant plastic channel Stainless steel C-channel for mechanical support • Electronic (Advance) Power Supply is 2 lbs. (0.9kg) • Outdoor Magnetic Hybrid Power Supply is 9 lbs. (4 kg) Minimum Piece Spacing • Linear (end to end) = 3/8” (10mm) • Parallel (edge to edge) = 1” (25mm) *The minimum space for ventilation surrounding the Plexineon product is 1.0”. This distance should be maintained on the three sides, left and right of the product as well as in front of product. Other configurations subject to specific application testing. ELECTRICAL • Electronic (Advance) = 9.50’’ x 1.18” x 1.70” (242mm X 30mm X 43mm) • Outdoor Magnetic Hybrid= 11.25” x 3.25” x 3.36” (286mm x 83mm X 85mm) 108 mA/foot at 24VDC (354 mA/meter) 2.59 watts/foot (8.50 watts/meter) • 14 AWG, PVC/Nylon Type TC 600 Volt power and control cable or equivalent • FT-4 fire rating • Class 2 wiring system • Connectors: Molex Splashproof - JIS D0203 S2 Maximum Run Length Electrical Tips 24 V DC ENVIRONMENTAL Power Supply Dimensions DC Cable Load Voltage 2 Power Supply Weight Load Current 32 feet (9.75m) with an iLight approved power supply • Only use iLight approved power supplies • Do not cut non-cuttable pieces Operating Temperature Range Certification -25°C to 50°C (-13°F to 122°F) • Plexineon is MetLabs listed. MetLabs is a Nationally Recognized Testing Laboratory (NRTL). Complies with UL 1598 and CSA c22.2 No. 250 in Luminaire,Wet location listed. • Power Supplies are RU listed. RU stands for Recognized Components by Underwriters Laboratory. Storage Temperature Range -25°C to 75°C (-13°F to 167°F) iLight Technologies MK-0110 • 118 South Clinton, Suite 370 • Chicago, IL 60661 • T 312.876.8630 • F 312.876.8631 • www.ilight-tech.com TYPE G LF - 120/24V Plexineon White 1X Series www.ilight-tech.com MOUNTING CLIPS PLEXINEON CROSS SECTIONS PLEXINEON PROFILE TECHNICAL INFORMATION iLight Technologies • 118 South Clinton, Suite 370 • Chicago, IL 60661 • T 312.876.8630 • F 312.876.8631 • www.ilight-tech.com MK-0110 3 TYPE G LF - 120/24V Plexineon White 1X Series www.ilight-tech.com TECHNICAL INFORMATION ELECTRONIC (ADVANCE) POWER SUPPLY Plexineon Power Supplies MAGNETIC HYBRID POWER SUPPLY IN 3R ENCLOSURE DRY MAGNETIC HYBRID 3-OUTLET POWER SUPPLY IN 3R ENCLOSURE DRY DAMP 4 iLight Technologies MK-0110 DRY DAMP • 118 South Clinton, Suite 370 • Chicago, IL 60661 • T 312.876.8630 • F 312.876.8631 • www.ilight-tech.com TYPE G LF - 120/24V Plexineon White 1X Series www.ilight-tech.com INSIDE CORNER OUTSIDE CORNER TECHNICAL INFORMATION iLight Technologies • 118 South Clinton, Suite 370 • Chicago, IL 60661 • T 312.876.8630 • F 312.876.8631 • www.ilight-tech.com MK-0110 5 TYPE G LF - 120/24V Plexineon White 1X Series www.ilight-tech.com PLEXINEON FIELD BENDING1-3 TECHNICAL INFORMATION PLEXINEON FACTORY BENDING Note 1: Field bending shown in easy direction. Cannot field bend into convex or concave bends. Note 2: Easy direction refers to bend axis parallel to light direction. Note 3: Field bending allowed only on fixtures without C-channel. Convex Concave Easy Bend2 6 iLight Technologies MK-0110 • 118 South Clinton, Suite 370 • Chicago, IL 60661 • T 312.876.8630 • F 312.876.8631 • www.ilight-tech.com (please confirm finish) TYPE S1 ve - 120/277V Cat.# ARF2 LED Type Job DECORATIVE FLOOD Approvals PRODUCT IMAGE(S) SPECIFICATIONS Intended Use: Compact flood with a variety of NEMA distributions for lighting applications such as safety/security, accent, flag pole, columns, facade, area, or signs; Operating temperature of -35˚C to 40˚C Construction: • Rugged die-cast aluminum housing with powder coat finish • High impact UV stabilized acrylic outer lens protects LEDs and allows for cleaning and debris removal • Vented housing isolates LED module from driver, maximizing product life and performance • Visor and vandal lens available LED: • 20 high powered LEDs deliver up to 4,692 lumens • 5100K CCT 67 CRI, 4200K 70 CRI, 3000K 80 CRI • Driver RoHS compliant and IP66 • 0-10V dimming driver • 20KA surge protector (over current device) option available Installation: • Traditional ½” x 14 NPS threaded adjustable knuckle mounting • Easy maintenance access to electrical components with removal of 4 screws from back of fixture housing Listings: • IP65 Knuckle aiming detail • Listed to UL1598 for use in wet locations • DLC Qualified (4200K and 5100K models only); Consult DLC website for more details: http://www.designlights.org/QPL Warranty: 5 year limited warranty, for more information visit: http://www.hubbelloutdoor.com/resources/warranty/ Optical/Electrical • Variety of NEMA distributions - N (3x3), M (4x4), RM (5x4) and W (6x6) - for wide range of lighting applications • 120-277V operation, 50/60Hz, 52w, 700mA, 81 LPW DIMENSIONS B C A A B C Weight 6.68”9.63”4.53” 8.5 lbs. 169 mm 244 mm 115 mm 3.8 kg SHIPPING INFORMATION CERTIFICATIONS/LISTINGS Catalog Number IP65 Carton Dimensions G.W(kg)/ CTN ARF2 (Single carton 1 pc.) 3.81 Length Inch (cm) Width Inch (cm) Height Inch (cm) 11.81" 9.45" 7.48" Carton dimensions for shipping purposes only LED Product Partner ORDERING INFORMATION ARF2 K FAMILY ARF2 Arceos Flood Medium MOUNTING K Knuckle 1 DLC qualification 4K and 5K models only 2 Custom colors available, contact factory 20L 4K # LEDS LED CCT 20L 20 LEDS 3K1 3000K 4K 4200K 5K 5100K 070 DRIVE CURRENT 070 700mA W PS U BEAM VOLTAGE 3x3 U 120V-277V DB Bronze M 4x4 1 120V BL Black RM 5x4 2 208V WH White W 3 240V GR Gray 4 277V PS Platinum FG Forest Green RD Red CC2 Custom Color 6x6 CONTROL OPTION MOUNTING N OPTIONS F PC Photocontrol (voltage specified and determined by voltage field) Fusing, 120 or 277V only (voltage specified and determined by voltage field) SP 20KA/ KV Surge Protector Spaulding Lighting • 701 Millennium Boulevard • Greenville, SC 29607 • Phone: 864-678-1000 Due to our continued efforts to improve our products, product specifications are subject to change without notice. © 2014 SPAULDING LIGHTING, All Rights Reserved • For more information visit our website: www.spauldinglighting.com • Printed in USA SPA14-SPEC 2/14 TYPE S1 ve - 120/277V (please confirm finish) ACCESSORIES/REPLACEMENT PARTS - Order Separately Catalog Number FML-SPC FML-VISOR-XX1 93047961AC 93043808 20750110264 Description Polycarbonate lens (Replaces existing acrylic outer frame) Top/Bottom visor (Tap holes in lens frame for field installation) Acrylic lens w/ gasket 25w, 120-277V Dimming driver Knuckle mount Dark Bronze finish. Contact factory for additional finishes Top or Bottom Visor Mount Detail 1 Specify finish color to match fixture, e.g. DB - Bronze. FRAME & LENS FML-SPC FML-VISOR – 3/4 View Front View PERFORMANCE DATA # OF DRIVE SYSTEM LEDS CURRENT WATTS 20 700mA 52w DIST. TYPE N M RM W NEMA 3x3 4x4 5x4 6x6 FIELD ANGLE H˚ X V˚ 32 x 32 54 x 54 83 x 66 107 x 107 5K 4K 3K (5100K nominal, 67 CRI) (4200K nominal, 70 CRI) (3000K nominal, 80 CRI) MAX BEAM MAX BEAM MAX BEAM LUMENS LPW1 CANDLEPOWER LUMENS LPW1 CANDLEPOWER LUMENS LPW1 CANDLEPOWER 4692 91.5 37,587 4231 87 35,025 3274 67 28,248 4600 89 13,625 4265 88 12,313 3274 67 9,411 3926 76 6,582 3636 75 5,921 2835 58 5,002 4486 87 2,978 4119 85 2,851 3234 66 2,306 1 - Lumen values are from photometric tests performed in accordance with IESNA LM-79-08. Data is considered to be representative of the configurations shown. Actual performance may differ as a result of end-user environment and application. PROJECTED LUMEN MAINTENANCE LUMINAIRE AMBIENT TEMPERATURE FACTOR (LATF) OPERATING HOURS 1TM-21-11 AMBIENT TEMP. 0 25,000 50,000 60,000 100,000 25°C / 77°F 1.00 0.98 0.96 0.96 0.94 40°C / 104°F 0.99 0.96 0.95 0.94 AMBIENT TEMPERATURE 0°C 32°F 10°C 50°F 68°F 20°C 25°C 77°F 30°C 86°F 40°C 104°F 50°C 122°F Calculated L70 (HOURS) >696,000 0.92 >565,000 ELECTRICAL DATA NUMBER OF DRIVE CURRENT INPUT VOLTAGE CURRENT DRIVERS (mA) (V) (Amps) 120 0.56 2 700mA 277 0.26 # OF LEDS 20 SYSTEM POWER (W) 50 50 LUMEN MULTIPLIER 1.02 1.01 1.00 1.00 1.00 0.99 0.98 Use these factors to determine relative lumen output for average ambient temperatures from 0-50°C (32-122°F). PHOTOMETRICS For additional photometric information and IES downloads, visit our web site at www.spauldinglighting.com 30' 15' 20' 15' 30' 10' 10' 20' 5' 5' 10' 10' fc 10 10' 2fc 1fc .5fc 30' 20' 10' 10' 10' 20' 5' 15' 3x3 Narrow fc 20 fc 10 5fc 15' 10' 10' 20' 2fc 1fc fc .5 1fc .5fc 30' 20' 5' 5' 15' 20fc 10fc 5fc 2fc 10' fc 50 10' 5' 30' 6x6 Wide 5' .5fc 15' 10' 15' 100fc fc 50 fc 20 c f 10 c 5f 2fc 1fc 5' 5fc 20' 15' 10' 10' 10' 15' 4x4 Medium 15' 5 x 4 Rectangular Medium Spaulding Lighting • 701 Millennium Boulevard • Greenville, SC 29607 • Phone: 864-678-1000 Due to our continued efforts to improve our products, product specifications are subject to change without notice. © 2014 SPAULDING LIGHTING, All Rights Reserved • For more information visit our website: www.spauldinglighting.com • Printed in USA SPA14-SPEC 2/14 20' 30' E TYPE S1 - 120/277V Lightscoop Ceiling washlights (please confirm finish) with mounting plate and LED 13 3/8" 18 1/8" 13 3/8" 464mm 340mm 155mm 6 1/8" d240mm 9 1/2" 340mm LED Nä ö ü Dry Damp Wet ÖOutdoor 33237.023 Graphit m LED 48W 6000lm 4000K neutral white Version 2 Spherolit lens, wide beam Product description Housing: corrosion-resistant, cast aluminum, No-rinse surface treatment. Double powder-coated. Optimized surface for reduced accumulation of dirt. Luminaire rotatable throught 240°. Mounting plate: corrosion-resistant aluminum. Electronic control gear 120V/277V, 60Hz. 2 cable entries. Through-wiring possible. 3-pole terminal block. LED module: high-power LEDs on metal-core PCB. SDCM<2. CRI>80. L80/B10 50000h. Collimating lens made of optical polymer. Screw-mounted cover frame with safety glass: corrosion-resistant cast aluminum, double powder-coated. Suitable for wet location (IP65): dustproof and water jet-proof. Weight 20.50lbs / 9.30kg Maximum wind load area 1.40ft2 ERCO Lighting Inc. 160 Raritan Center Parkway Suite 10 Edison, NJ 08837 USA Tel.: +1 732 225 8856 Fax: +1 732 225 8857 info.us@erco.com 135° 3000 cd 105° C0-C180 C90 -C270 h=4ft MF=1.00 ft 12 0.1 2 6 0.5 20 0 10 ft 24 18 12 6 6 Technical region: 120V/277V, 60Hz We reserve the right to make technical and design changes. Edition: 04.03.2014 Current version under www.erco.com/33237.023 1/2 E TYPE S1 - 120/277V Lightscoop Ceiling washlights (please confirm finish) Accessories 34991.000 Spacer for surface-mounted cables. Corrosion-resistant cast aluminum, No-Rinse surface treatment. Graphit m, double powder-coated. Weight 0.51lbs / 0.23kg 33974.000 Ground socket Metal, hot-dip galvanised. Cable entry. Weight 5.07lbs / 2.30kg 4 1/2" 666666 36664 153 mm 6" 4666663 600 mm 23 5/8" 4666666663 ∅ 115 mm 13/16" 2 3/8" 6666364 20 mm 666663664 ∅ 60 mm 200 mm 7 7/8" 46666 3 33981.000 Concrete anchor Mounting plate with threaded bar and fixing nuts M10. Individual parts to be assembled on-site. Weight 1.68lbs / 0.76kg 4 7/8" 366664 ∅ 124 mm Lightscoop Ceiling washlights 33237.023 2/2 TYPE S2 ve pole (please confirm finish) International Round Straight Steel Light Poles POLE SHAFT: Fabricated from hot rolled welded steel tubing with minimum yield strength of 42,000 PSI. ANCHOR BASE: Structural quality ASTM A-36. The base is provided with bolt slots to accommodate a 7" – 9" bolt circle. ANCHOR BOLTS: Carbon steel conforming to AASHTO M314 grade-55 or ASTM F1554 grade-55. Bolts are "L" shaped and are galvanized a minimum of 12" on the threaded end. Each pole includes four bolts each with two nuts and two flat washers. FULL BASE COVER (optional): Two piece cover fabricated from ABS plastic. MOUNTING HEIGHT HANDHOLE: Covered 2 1/2" x 5" reinforced handhole. A nut holder is provided near the handhole and includes a 1/2"-13 UNC hex head bolt and nut. HARDWARE: All structural fasteners are galvanized high strength carbon steel. All other fasteners are galvanized or zinc plated or stainless steel. REINFORCED HANDHOLE W/COVER AND GROUNDING STANDARD FINISH: Galvanized or powder coated. Consult factory for standard or custom colors. MOUNTINGS OPTIONS: Tenons- standard 2 3/8" x 4" or 4" x 6" or removable pole cap used in conjunction with side mounted fixtures. 4 - ANCHOR BOLTS WITH THREADED END GALVANIZED 12” MIN. EACH BOLT FURNISHED WITH 2 HEX NUTS AND 2 FLATWASHERS NAFCO International, Fond du Lac, WI 1-800-558-4810 Fax 1-920-921-0781 Serving our customers and the industry with quality products since 1973. www.nafcointernational.com 8.5 (please confirm finish) TYPE S2 ve pole Round Straight Steel Light Poles POLE CATALOG NUMBER RSS10-303C NOMINAL MOUNTING HEIGHT (ft) 10 Max EPA AT: (Allows for 1.3 Gust Factor) POLE O.D. INCHES WALL THICKNESS INCHES 80 MPH 90 MPH 100 MPH 3.0 120 10.0 7.7 6.0 RSS10-404C 10 4.0 .120 19.1 15.0 12.2 RSS10-4545C 10 4.5 .120 24.5 19.5 15.8 RSS12-303C 12 3.0 .120 7.7 5.8 4.4 RSS12-404C 12 4.0 .120 15.0 11.8 9.5 RSS12-4545C 12 4.5 .120 19.8 15.7 12.7 RSS14-303C 14 3.0 .120 6.0 4.4 3.3 RSS14-404C 14 4.0 .120 12.2 9.4 7.6 RSS14-4545C 14 4.5 .120 16.2 12.8 10.3 RSS16-303C 16 3.0 .120 4.6 3.2 2.3 RSS16-404C 16 4.0 .120 9.6 7.4 5.9 RSS16-4545C 16 4.5 .120 13.1 10.2 8.2 RSS18-303C 18 3.0 .120 3.4 2.3 1.4 RSS18-404C 18 4.0 .120 7.6 5.7 4.5 RSS18-4545C 18 4.5 .120 10.5 8.2 6.5 RSS20-303C 20 3.0 .120 2.4 1.4 - RSS20-404C 20 4.0 .120 6.0 4.4 3.4 RSS20-4545C 20 4.5 .120 8.5 6.6 5.2 RSS20-505C 20 5.0 .120 11.7 9.1 7.2 RSS25-404C 25 4.0 .120 2.8 1.9 1.3 RSS25-4545C 25 4.5 .120 4.8 3.6 2.7 RSS25-505C 25 5.0 .120 7.2 5.5 4.2 RSS25-505D 25 5.0 .180 12.1 9.4 7.4 RSS30-4545C 30 4.5 .120 2.3 1.5 1.0 RSS30-505C 30 5.0 .120 4.2 3.0 2.2 RSS30-505D 30 5.0 .180 8.0 6.5 4.7 1. All designs utilize .75" x 17" x 3" anchor bolts. 2. Pole base plate dimensions are the same for all designs. See pole base detail drawing for dimensions. 3. Wind load includes 1.3 gust factor. Variations in mounting heights listed are available. POLE BASE AND HANDHOLE DETAIL Dimensions and Specifications subject to change without notice. NAFCO International, Fond du Lac, WI 1-800-558-4810 Fax 1-920-921-0781 www.nafcointernational.com 8.6 (please confirm finish) CIMARRON LED CL1S TYPE S2 ve - 120/277V Cat.# Approvals Type Job 4.000 SPECIFICATIONS Construction: •Stylish vertically finned die-cast solid top housing for maximum heat dissipation; Stops collection of unsightly debris •Rugged lower die-cast aluminum heat sink accelerates thermal management and optimizes PCB and optical performance • One piece die-cut silicone gasket with mechani- cally compressed stainless steel bezel ensures weather proof seal around each individual LED for IP65 rating •Backlight Control (BC) option available for 85% spill light reduction, doesn’t change fixture appearance or EPA, recommended for Type III and Type IV distributions • Complements the Cimarron LED CL1 in the Hubbell Southwest series of outdoor fixtures •Weight - 19 pounds, EPA - .45 ft2 • Features exclusive wiHUBB technology -Wireless system for On/Off and 0-10VDC dimming protocol with functional range of 10-100% -Programmable autonomous operation Optics: • Choice of 54 high brightness LED configurations with individual acrylic lenses specially designed for IES Type II, III, IV and V distributions • 3000K, 80 CRI; 4200K, 70 CRI; 5100K, 67 CRI Electrical: • Universal input voltage 120-277 VAC, 50/60 Hz •Ambient operating temperature -30˚ C to 40˚ C •Automatic thermal self-protection •Drivers have greater than 90% power factor and less than 10% THD •Optional 0-10VDC continuous dimming to 10% 4.500 • LED drivers have output power over-voltage, over-current protection and short circuit protection with auto recovery • LED electrical assembly, including PR devices, consumes no power in the ‘off’ state • Surge protection of 10KA 8/20 µSec wave; clamping voltage of 320V & surge rating of 273J 2014 3.000 16.312 48 LED 3/4 VIEW 3.000 12.000 32 LED 48 LED DIMENSIONS A D A VOLTAGE CL1S Cimarron LED 16L 16 High brightness LEDs 32L 32 High brightness LEDs 48L 48 High brightness LEDs U Universal 120V-277V, 3 50/60 Hz 11 21 31 41 5 F E4 120V 208V C C D G E B C D E F G 12" 305mm 16.312" 414mm 4" 102mm 4.5" 114mm 3" 76mm 20.312" 515mm 4.13" 105mm 5W 3K 3000K, 80 CRI 4K 4200K, 70 CRI 5K 5100K, 67 CRI PS Leave blank for 700mA (standard) 2 Type II 3 Type III Type IV Type V Medium Type V Short Type V Wide Type II rotated left Type III rotated left OPTIONS BC CD2,7 Continuous dimming F(X)3,4 Fusing (replace X with voltage: 5 Backlight control 1-120V, 2-208V, 3-240V, 4-277V, 5-480V, 6-347V) White RPA3 RPA4 TB WB WHB6 Gray WIH2,8 In-fixture wireless control module Platinum Silver PR(X)2 NEMA Photo cell receptacle COLOR DISTRIBUTION H 5.625" 143mm RPA4 DRIVE CURRENT 480V, 60 Hz 4 5M 5S 5W 2L 3L 4L 2R 3R 4R E A CCT 347V, 60 Hz G H 277V Notes: 1 - Select only when using voltage specific options F, WIH 2 - WIH cannot be combined with CD or PR(X) 3 - Fuse option not available with U voltage 4 - Select F3 fusing option for 220V 5 - Not recommended for Type 5S, 5M or 5W 6 - Order to match larger Cimarron CL1 with white bezels 7 - Dimming leads accessible for connection to third party dimming systems 8 - Only available with 120V or 277V input 9 - 0-10V fully adjustable dimming with automatic daylight calibration and different time delay settings, must order minimum of one remote control to program dimming settings, consult factory for details B Weight 240V 220V, 50 Hz B E F • IES Progress Award Winner - 2013 NO. OF LEDS 3.000 4.500 ORDERING INFORMATION ORDERING EXAMPLE: CL1S-A-48LU-5K-3-DB-RPA3 CL1S A 32L U 4K complete with quick-mount plate 16 LED 16.312 4.000 Listings: • Listed to UL1598 and CSA C22.2#250.0-24 for wet locations •DesignLights Consortium (DLC) qualified • IDA approved • IP66 LED Product Partner A 4” straight arm attached to housing 5.625 Warranty: Five year limited warranty, for more information visit: http://www.hubbelloutdoor.com/resources/ warranty/ SERIES 4.130 5.625 19 lbs. 8.62 kgs. MOUNTING 12.000 4.130 CERTIFICATIONS/LISTINGS Pedestrian Scale 12.000 20.312 Installation: • Quick-mount plate included for easy installation • The decorative integral arm houses two stage hinge mechanism •Safety latch holds luminaire door to prevent “free swing” • Quick-connect wiring for simplified, hassle-free installation • Suitable for applications requiring 3G testing prescribed by ANSI @136.31 Finish: • TGIC thermoset polyester powder paint finish applied at nominal 2.5 mil thickness 16.312 PRODUCT IMAGE(S) DB BL WH GR PS RD Dark Bronze Black Red (premium color) FG Forest Green (premium color) CC Custom Color Type IV rotated left Type II rotated right Type III rotated right 3” Round pole adapter 4” Round pole adapter Terminal block Wall bracket White LED bezel (replace X with voltage: U=120-277, 5=480, 6 =347) MOTION CONTROL OPTIONS SC09 Motion sensor On/Off control, No light output when no motion detected SCP9 Programmable motion control, factory default is 50% Type IV rotated right Spaulding Lighting • 701 Millennium Boulevard • Greenville, SC 29607 • Phone: 864-678-1000 Due to our continued efforts to improve our products, product specifications are subject to change without notice. © 2014 SPAULDING LIGHTING, All Rights Reserved • For more information visit our website: www.spauldinglighting.com • Printed in USA CL1SLED-SPEC 3/14 (please confirm finish) PERFORMANCE DATA NUMBER OF LEDS 5K (5100K NOMINAL, 67 CRI) DRIVE CURRENT (MILLIAMPS) 16 32 TYPE S2 ve - 120/277V SYSTEM WATTS 38w 700mA 76w 48 110w DISTRIBUTION TYPE 2 3 4 5S 5M 5W 2 3 4 5S 5M 5W 2 3 4 5S 5M 5W LUMENS 3053 3075 3113 3457 3731 3166 6527 6574 6654 7391 7327 6704 9864 9935 10056 11169 11073 10132 LPW* 80 81 82 91 98 83 86 86 88 97 96 88 87 90 92 101 101 92 4K (4200K NOMINAL, 70 CRI) B U G 2 0 0 3 0 1 2 2 2 3 3 4 2 1 1 0 1 1 2 2 2 0 2 2 LUMENS 3077 3099 3136 3484 3454 3160 6042 6085 6159 6841 6782 6206 9131 9593 9309 10339 10250 9379 LPW* 81 82 83 92 91 83 79 80 81 90 89 82 87 90 85 94 91 85 B U 3K (3000K NOMINAL, 80 CRI) G 2 0 2 3 0 2 LUMENS 2438 2456 2486 2761 2737 2725 4788 4823 4881 5422 5375 4918 7236 7288 7377 8193 8123 9662 LPW* 64 65 65 73 72 72 63 63 64 71 71 84 66 66 67 74 74 85 B U G 2 0 1 3 4 1 0 1 2 Lumen values are from photometric tests performed in accordance with IESNA LM-79-08. Data is considered to be representative of the configurations shown. Actual performance may differ as a result of end-user environment, application and inherent performance tolerances of the electrical components. PROJECTED LUMEN MAINTENANCE LUMINAIRE AMBIENT TEMPERATURE FACTOR (LATF) AMBIENT TEMP. 0 25,000 50,000 25°C / 77°F 40°C / 104°F 1.00 0.98 0.98 0.96 0.96 0.95 *TM-21-11 60,000 0.96 0.94 100,000 0.94 0.92 CALCULATED L70 (hours) >675,000 >556,000 * Nichia 219B, 700mA, 85°C Ts, 10,000hrs ELECTRICAL DATA NUMBER OF LED’s 16 32 48 NUMBER INPUT Drive Current OF VOLTAGE [milliamps] DRIVERS (VOLTS) 120 277 1 347 480 120 277 std. 2 (700mA) 347 480 120 277 3 347 480 OPER. CURRENT [AMPS] 0.32 0.15 37.8 37.5 0.63 0.29 75.5 74.8 0.95 0.44 110.5 110.9 ACCESSORIES PHOTOCONTROL EQUIPMENT CATALOG NUMBER PTL-1 PTL-8 PTL-5 PTL-6 PSC SYSTEM POWER IN-RUSH [WATTS] CURRENT (AMPS) DESCRIPTION Photocontrol - twist-lock cell (120V) Photocontrol - twist-lock cell (120-277V) Photocontrol - twist-lock cell (480V) Photocontrol - twist-lock cell (347V) Shorting cap - twist-lock 0°C 10°C 20°C 25°C 30°C 40°C 50°C AMBIENT DATA TEMP LUMEN MULT. 32°F 1.02 50°F 1.01 68°F 1.00 77°F 1.00 86°F 1.00 104°F 0.98 122°F 0.98 MOUNTING ACCESSORIES CATALOG NUMBER CL1S-RPA3-XX1 CL1S-RPA4-XX1 WB-CR-XX DESCRIPTION Round pole adapter for straight arm (31⁄4 - 33⁄4”) Round pole adapter for straight arm (37⁄8 - 41⁄ 2”) Wall bracket 1 Replace XX with color choice, eg.: DB for Dark Bronze TENON TOP POLE BRACKET ACCESSORIES (2 3/8” OD tenon, RSS version requires 4” round pole adapter) Catalog Number SETA-XX1 RETA-XX1 TETA-XX1 Description Square pole tenon adapter (4 at 90 degrees) Round pole tenon adapter (4 at 90 degrees) Triangular pole tenon adapter (3 at 120 degrees) 1 Replace XX with color choice, eg.: DB for Dark Bronze Spaulding Lighting • 701 Millennium Boulevard • Greenville, SC 29607 • Phone: 864-678-1000 Due to our continued efforts to improve our products, product specifications are subject to change without notice. © 2014 SPAULDING LIGHTING, All Rights Reserved • For more information visit our website: www.spauldinglighting.com • Printed in USA CL1SLED-SPEC 3/14 #2 DRILL PATTERN F (please confirm finish) TYPE S2 ve - 120/277V FIXTURE MOUNTING POLE COVER FIXTURE CAST ARM FIXTURE POLE TOP POLE COVER POLE COVER POLE COVER MOUNTING CASTBOLTS ARM MOUNTING BOLTS 2.25 NUT PLATE NUT PLATE CAST ADAPTER CAST ADAPTER NUT PLATE NUT PLATE SET SCREW SQUARE POLE 3.5 Ø .875 Ø .875 HOLE HOLE QUICK-MOUNT SQUARE POLE PLATE QUICK-MOUNT 2.25 .875 .875.875 ROUND POLE ROUND POLE SET SCREW .579 POLE TOP 3.5 3.5 Ø .563 2 HOLESØ .563 2 HOLES #2 DRILL PATTERN FOR POLES PLATE 4.962 4.962 2.625 #2 DRILL PATTERN FOR POLES QUICK-MOUNT PLATE .579 FIXTURE MOUNTING – FACTORY ROTATED OPTICS For proper light distribution.875 and performance, rotated .579 optics must be mounted as referenced in illustration. Consult instruction sheet included when mounting. .875 3.5 2L Type II rotated 90˚ left 3L Type III rotated 90˚ left 4L Type IV rotated 90˚ left 2R 3R 4R Type II rotated 90˚ right Type III rotated 90˚ right Type IV rotated 90˚ right 4.962 4.962 3.5 4.962 4.962 QUICK MOUNT INSTALLATION 1 2.625 The Cimarron CL1S installation features: 1 2 QUICK-MOUNT PLATE 1 Quick-mount plate attaches to pole with two 3/4” bolts 2 4 - slot hex 1/4” captured screws secure luminaire door to top 2.625 3 Safety-latch holds luminaire door to prevent “free swing” door QUICK-MOUNT PLATE 4 Two stage hinge mechanism built into integral arm 5 Quick-connect wiring for a simplified, hassle-free installation For installation video scan this code or visit link below: 3 4 5 http://www.youtube.com/user/hubbelloutdoorbrands LIGHTING FACTS Spaulding Lighting • 701 Millennium Boulevard • Greenville, SC 29607 • Phone: 864-678-1000 Due to our continued efforts to improve our products, product specifications are subject to change without notice. © 2014 SPAULDING LIGHTING, All Rights Reserved • For more information visit our website: www.spauldinglighting.com • Printed in USA CL1SLED-SPEC 3/14 (please select finish) CANTO G 450 LED TYPE S2 - 120/277V Specification The smoothly engineered shape of the CANTO combined with its gracefully arching pole creates a unique appearance. The gentle curvature allows the pole to spatially define paths or roadways. Two luminaire sizes and three pole heights are available to meet proportional requirements of large or small scale applications. The heavy cast aluminum housing is fitted with a flat tempered glass lens with a quarter-turn fastener for easy relamping. Hinged reflector assembly allows access to the ballast tray. Mounting bracket and steel pole with flush handhole are hot-dip galvanized prior to being finished in high quality, finely textured paint. Base cover is spun aluminum. All hardware is stainless steel. Standard colors; matte silver grey metallic or graphite grey. Special colors available. Color Model LED Module Temperature 2LV - 2 LEVO CC450GModules WW -3000K 3LV - 3 LEVO Modules NW - 4000K Distribution ME - Type III Volt Mounting Pole Finish UNV A - Single 17RC - 17' SG - Silver 120-277V Mount Round Curved Grey GG Graphite Grey S - Type II DIM - 0-10vDC Dimming CC - Custom Color N - None CW - 5600K Ordering Information CC450G Option 0DEG - 0 degree tilt for full cutoff classification UNV A 17RC Specifications are subject to change without notification HessAmerica > Products > Lighting Products > Pole Mounted Luminaire > CANTO G http://www.hessamerica.com/Products/Lighting/Pole_Mounted_Luminaire/CANTO_G/ Page 1 (please select finish) CANTO G 450 LED TYPE S2 - 120/277V Specification HOUSING One-piece domed housing is heavy cast aluminum. Hinged frameless tempered glass lens opens with single quarter-turn fastener for easy relamping. Lens is sealed to the housing with one-piece closed cell silicone gasketing. Hinged reflector plate, painted with high reflectance white paint, swings down allowing access to ballast components. Housing is fitted with stainless steel weather-tight strain relief bushing for the power cable exiting the rear of the housing. Luminaire installs onto bracket mounting plate with four socket head cap screws. All hardware is stainless steel. OPTICS Optics may be specified with 2 or 3 individual LED modules. Each module consists of a field replaceable aluminum core PCB with fourteen high-power LEDs and a single piece prismatic lens molded from optical quality acrylic. The prismatic lens redirects light output from the individual LEDs and is available in two distributions as a Type II Full Cutoff distribution (S optics) or Type III Full Cutoff distribution (ME optics) when selecting the zero degree tilt option (0DEG) . Luminaire is suitable for use in all LEED lighting zones. Available color temperatures are 3000K, 4000K, or 5600K. ELECTRICAL Electronic LED driver supplies 500mA drive current to LED modules with input voltage range from 120v to 277v at 50/60Hz. LED DELIVERED LUMEN OUTPUT / POWER CONSUMPTION 2 Modules: 46 watts 3000K - Type II = 2698 lumens / Type III = 2652 lumens 4000K - Type II = 3076 lumens / Type III = 3023 lumens 5600K - Type II = 3277 lumens / Type III = 3221 lumens 3 Modules: 71 watts 3000K - Type II = 3909 lumens / Type III = 3865 lumens 4000K - Type II = 4457 lumens / Type III = 4407 lumens 5600K - Type II = 4750 lumens / Type III = 4696 lumens NOTE : Due to rapid and continuous advances in LED technology, LED luminaire data is subject to change without notice and at the discretion of HessAmerica. Consult factory for current technical data. POLE Fabricated aluminum bracket arm bolts to the pole 2.5' from the top with two stainless steel fasteners. Square tubing welded to the underside of the bracket arm acts as a wire way for the luminaire power cable. Round and curved steel pole is manufactured from cold drawn over mandrel, electric-weld, mechanical round steel tubing with nominal wall thickness of 0.157''. Pole curvature projects centerline of pole top 1.7' from the base. Flush mounted handhole cover is plasma cut with kerf not to exceed 1/8'' and includes triangular tamper-resistant locking device. Pole is hot-dip galvanized with coating inside and out, then lightly sanded prior to painting. Two-piece base cover with tamper-proof fasteners is fabricated from 0.080'' spun aluminum and finished to match the pole. Nominal pole height is 17'. FINISH Housing is ultrasonically cleaned prior to painting. Standard finish is finely textured matte silver grey metallic or graphite grey. Special colors available on request. CERTIFICATION UL Listed for Wet Locations WARRANTY Limited product warranty period including LEDs is three years. Driver shall carry the manufacturer's limited warranty. Specifications are subject to change without notification HessAmerica > Products > Lighting Products > Pole Mounted Luminaire > CANTO G http://www.hessamerica.com/Products/Lighting/Pole_Mounted_Luminaire/CANTO_G/ Page 2 (please select finish) TYPE S2 - 120/277V Additional information Dimensions Mounting Detail Specifications are subject to change without notification HessAmerica > Products > Lighting Products > Pole Mounted Luminaire > CANTO G http://www.hessamerica.com/Products/Lighting/Pole_Mounted_Luminaire/CANTO_G/ Page 3 TYPE S3 pole (please advise finish) International Round Straight Steel Light Poles POLE SHAFT: Fabricated from hot rolled welded steel tubing with minimum yield strength of 42,000 PSI. ANCHOR BASE: Structural quality ASTM A-36. The base is provided with bolt slots to accommodate a 7" – 9" bolt circle. ANCHOR BOLTS: Carbon steel conforming to AASHTO M314 grade-55 or ASTM F1554 grade-55. Bolts are "L" shaped and are galvanized a minimum of 12" on the threaded end. Each pole includes four bolts each with two nuts and two flat washers. FULL BASE COVER (optional): Two piece cover fabricated from ABS plastic. MOUNTING HEIGHT HANDHOLE: Covered 2 1/2" x 5" reinforced handhole. A nut holder is provided near the handhole and includes a 1/2"-13 UNC hex head bolt and nut. HARDWARE: All structural fasteners are galvanized high strength carbon steel. All other fasteners are galvanized or zinc plated or stainless steel. REINFORCED HANDHOLE W/COVER AND GROUNDING STANDARD FINISH: Galvanized or powder coated. Consult factory for standard or custom colors. MOUNTINGS OPTIONS: Tenons- standard 2 3/8" x 4" or 4" x 6" or removable pole cap used in conjunction with side mounted fixtures. 4 - ANCHOR BOLTS WITH THREADED END GALVANIZED 12” MIN. EACH BOLT FURNISHED WITH 2 HEX NUTS AND 2 FLATWASHERS NAFCO International, Fond du Lac, WI 1-800-558-4810 Fax 1-920-921-0781 Serving our customers and the industry with quality products since 1973. www.nafcointernational.com 8.5 (please advise finish) TYPE S3 pole Round Straight Steel Light Poles POLE CATALOG NUMBER RSS10-303C NOMINAL MOUNTING HEIGHT (ft) 10 Max EPA AT: (Allows for 1.3 Gust Factor) POLE O.D. INCHES WALL THICKNESS INCHES 80 MPH 90 MPH 100 MPH 3.0 120 10.0 7.7 6.0 RSS10-404C 10 4.0 .120 19.1 15.0 12.2 RSS10-4545C 10 4.5 .120 24.5 19.5 15.8 RSS12-303C 12 3.0 .120 7.7 5.8 4.4 RSS12-404C 12 4.0 .120 15.0 11.8 9.5 RSS12-4545C 12 4.5 .120 19.8 15.7 12.7 RSS14-303C 14 3.0 .120 6.0 4.4 3.3 RSS14-404C 14 4.0 .120 12.2 9.4 7.6 RSS14-4545C 14 4.5 .120 16.2 12.8 10.3 RSS16-303C 16 3.0 .120 4.6 3.2 2.3 RSS16-404C 16 4.0 .120 9.6 7.4 5.9 RSS16-4545C 16 4.5 .120 13.1 10.2 8.2 RSS18-303C 18 3.0 .120 3.4 2.3 1.4 RSS18-404C 18 4.0 .120 7.6 5.7 4.5 RSS18-4545C 18 4.5 .120 10.5 8.2 6.5 RSS20-303C 20 3.0 .120 2.4 1.4 - RSS20-404C 20 4.0 .120 6.0 4.4 3.4 RSS20-4545C 20 4.5 .120 8.5 6.6 5.2 RSS20-505C 20 5.0 .120 11.7 9.1 7.2 RSS25-404C 25 4.0 .120 2.8 1.9 1.3 RSS25-4545C 25 4.5 .120 4.8 3.6 2.7 RSS25-505C 25 5.0 .120 7.2 5.5 4.2 RSS25-505D 25 5.0 .180 12.1 9.4 7.4 RSS30-4545C 30 4.5 .120 2.3 1.5 1.0 RSS30-505C 30 5.0 .120 4.2 3.0 2.2 RSS30-505D 30 5.0 .180 8.0 6.5 4.7 1. All designs utilize .75" x 17" x 3" anchor bolts. 2. Pole base plate dimensions are the same for all designs. See pole base detail drawing for dimensions. 3. Wind load includes 1.3 gust factor. Variations in mounting heights listed are available. POLE BASE AND HANDHOLE DETAIL Dimensions and Specifications subject to change without notice. NAFCO International, Fond du Lac, WI 1-800-558-4810 Fax 1-920-921-0781 www.nafcointernational.com 8.6 (please select finish) TYPE S3 - 120/277V ALT96 ALTITUDE™ LED 3/13/14 • kl_alt96_spec.pdf Type: Job: Catalog number: Approvals: 2SB ALT3P35 96L4K120/277 MW Mtg. Fixture Finish Electrical Module See page 2 Options See pages 3-4 Ordering Example: 1SA / ALT3P35/ 96L5K277/ WH/ A26 Select pole from Kim’s Arms and Poles Selection Guide. If pole is provided by others indicate O.D. for arm fitting. Specifications ALT96 Approx. Wt. = 30 lbs. 7L" (197 mm) 26L" (680 mm) 2" (51 mm) 17" (432 mm) Speed Mount Adapter TOP SIDE BOTTOM 4B" (105 mm) FRONT 3E" (98 mm) US Patent Numbers D674,950 S and D674,965 S. Other Patents Pending. Date: Page: 1 of 5 Housing: One piece, low copper, aluminum extrusion is mechanically secured with stainless steel fasteners to low copper aluminum die-cast electrical compartment and end cap. The electrical compartment includes an integral support arm for mounting directly to a surface mount pole adaptor or a horizontal slipfitter. A solid barrier wall separates the optical and electrical compartment for thermal control. Electrical compartment and end cap covers are securely fastened with with two hinges and a single latch at each cover. One piece silicone gaskets seal the compartments at the barrier surface. Optical Module: The high performance optic utilizes the IP66 rated PicoPrism™ technology securely attached to internal heat sink modules producing incredible uniformity and visual comfort. This PicoPrism optic utilizes a canted prism lens aimed toward the task and spreads horizontally to produce high lumen output as well as great uniformity. All the optical modules are fastened to the body of the luminaire across the center as well as around the perimeter. Electrical Compartment: Available in voltages from 120V through 480V @ 50/60Hz.Class 2 output with power factor >0.9 at full load in accordance with the National Electrical Code, ANSI/NFPA 70. Integral 10kV surge suppression protection standard. To address inrush current, slow blow fuse or type C/D breaker should be used. All electronic components are UL and CSA recognized and mounted directly to a driver tray for maximum heat dissipation and modularity. Module includes a driver, LifeShield® temperature control device and surge protector. Driver is rated for -40°C starting and has a 0-10V dimming interface for multi-level illumination options. All electronic components are IP66 rated. 347V and 480V currents may have a step-down transformer. Support Arm: Die-cast, low copper aluminum with splice access cover and tool-less entry. A die-cast pole adaptor and an internal reinforcing plate are provided with wire strain relief. The arm adaptor is square or circular cut for specified pole size and shape. For field wire connections, a terminal block is mounted in the arm cavity and accessible behind the splice access cover. The block accepts #14 to #8 wire sizes and is factory prewired to the electrical module quick-disconnect plug inside the electrical compartment. Optional Horizontal Slip-fitter: Cast low copper aluminum with stamped, splice access cover. A die-cast adaptor plate is provided to secure the luminaire to 1-1/4” to 2” IPS pipe size arms. For field wire connections, a terminal block is mounted in the arm cavity and accessible behind the splice access cover. Accepts #14 to #8 wire sizes and is factory prewired to electrical module quick-disconnect plug inside the electrical compartment. Optional Wall Mount: The Altitude easily mounts to the wall. A cast aluminum mounting plate is attached to the wall over the junction box. Bolt the Speed Mount to the cover plate. Then install the assembly over the mounting plate. Slide the luminaire into place for hands free wiring and finishing. Finish: Each luminaire receives a fade and abrasion resistant, electrostatically applied, thermally cured, triglycidal isocyanurate (TGIC) polyester powdercoat finish. Standard colors include (BL) Black, (DB) Dark Bronze, (WH) White, (PS) Platinum Silver, (SG) Stealth Gray, (LG) Light Gray, and (CC) Custom Color (Include RAL#). Listed to: UL 1598 Standard for Luminaires - UL 8750 Standard for Safety for Light Emitting Diode (LED) Equipment for use in Lighting Products and CSA C22.2#250.0 Luminaires. RoHS compliant. Meets Buy American provisions within ARRA. Suitable for wet locations. CAUTION: Fixtures must be grounded in accordance with national, state and/or local electrical codes, Failure to do so may result in serious personal injury. Kim Lighting reserves the right to change specifications without notice. © 2014 KIM LIGHTING • 16555 East Gale Avenue, City of Industry, CA 91745-1788 • TEL: 626/968-5666 • FAX: 626/968-5716 TYPE S3 - 120/277V (please select finish) ALT96 ALTITUDE™ LED 3/13/14 • kl_alt96_spec.pdf Type: Job: Page: 2 of 5 Standard Features Mounting 3SY configuration is available for round poles only. Cat. No.: 1SA 2SB 2SL 3ST 3SY 4SC 1SW 0.97 1.61 1.61 1.78 n/a EPA (Effective Projected Area) ALT96 Fixture Cat. No. designates fixture and light distribution. 0.64 1.28 ALT 3x P Housing: Optic: P = PicoPrism™ ALT= Altitude Distribution: 1= Type I 2= Type II 3= Type III 4= Type IV 5 = Type V x 35 R = Type R Right L = Type L Left Current: 35 = 350 mA 70 = 700 mA Light Distribution: TYPE I Electrical Module TYPE TYPE III TYPEIIIII I TYPE TYPE TYPE RNFO TYPE TYPE II TYPE TYPE TYPE TYPE IV - NFO TYPE TYPE IV-IV NFO IV-V TYPE V TYPE TYPE TYPE TYPE III -III NFO TYPE III -NFO IIIIV TYPE IIIIV -NFO TYPE L RV TYPETYPE L R Right Right Forward Forward Forward Square Square Square LeftRight Left Throw Throw Throw 96L x Source: 96L =17"W x 26K"L 1 For 4K x Color Temperature:1 2K = 580nm Amber2 3K=3000K 4K=4000K 5K=5000K 120/277 x Voltage: 120=120V 208=208V 240=240V 277=277V 347=347V 480=480V custom optics and color temperature configurations, contact factory. Friendly. 2 Turtle © 2014 KIM LIGHTING • 16555 East Gale Avenue, City of Industry, CA 91745-1788 • TEL: 626/968-5666 • FAX: 626/968-5716 TYPE L Left TYPE S3 - 120/277V (please select finish) ALT96 ALTITUDE™ LED 3/13/14 • kl_alt96_spec.pdf Type: Job: Page: 3 of 5 Optional Features Finish TGIC powder coat. Black Color: Cat. No.: BL Dark Bronze DB Stealth Gray SG Platinum Silver White PS WH Custom Color1 CC Custom colors subject to additional charges, minimum quantities and extended lead times. Consult representative. Custom color description: 1 Wall Mounting Cat. No. 1SW Select from Mounting on page 2. The Altitude™ easily mounts to the wall. A cast aluminum wall bracket is attached to the wall over the junction box. Bolt the Speed Mount to the cover plate. Then install the assembly over the wall mount bracket. Side the luminaire into place for hands free wiring and finishing. Cover Plate 6J" x 11K" Splice Access Cover Speed Mount Adapter 5K" (140 mm) 4J" (108 mm) 10D" (270 mm) 8L" (222 mm) 11K" (292 mm) N" (14 mm) Mounting Plate 2L" (70 mm) Fusing (internal only): Cat. No. (see chart at right) No Option High temperature fuse holders factory installed inside the fixture housing. Fuse is included. Cat. No.: SF for 120, 277 and 347 Line Volts DF for 208, 240 and 480 Line Volts Photocell Receptacle Cat. No. A26 No Option Rotatable photocell receptacle provided for NEMA base photocell (by others). Receptacle Lenses Cat. No. FGL (Glass) FPL (Polycarbonate) No Option One-piece flat glass or polycarbonate lens slips into reveal. Extra silicone gasketing will be provided to retain a clear optical compartment. (Only available for 350mA systems). CAUTION: Use only when vandalism is anticipated to be high. Neighbor Friendly Optic: Cat. No. NFO No Option Integrated Neighbor Friendly Optic on each PicoPrism™ module to completely control unwanted backlight. Most effective with Type III and IV distibutions. Polycarbonate Lens TYPE I TYPE I II TYPE TYPE II III TYPE TYPE IV TYPE III -NFO TYPE III -NFO Forward Throw © 2014 KIM LIGHTING • 16555 East Gale Avenue, City of Industry, CA 91745-1788 • TEL: 626/968-5666 • FAX: 626/968-5716 TYPE TYPE IV IV- NFO TYPE IV - NFO TYPE V Forward Square Throw TYPE S3 - 120/277V (please select finish) ALT96 ALTITUDE™ LED 3/13/14 • kl_alt96_spec.pdf Type: Job: Page: 4 of 5 Optional Features Horizontal Slipfitter Mount Cat. No. HSF No Option Replaces standard mounting arm with a cast aluminum fitter to adapt to a horizontal 1J" to 2" pipe-size mounting end (1D" to 2C" OD). The casting has a +/- 5° adjustment to accommodate davit arms that are not horizontal. Vertical Slipfitter Mounts Cat. No. includes Mounting Cat. No. (See right) No Option Allows fixture or fixtures with standard mounting arm to mount to a pole with a 2" pipe-size tenon (2C" OD). Minimum 4" tenon length required. Horizontal Slipfitter for 1J" to 2" Pipe-Size Mount Specify configuration (1SA, 2SB, 2SL, 3ST, 3SY, 4SC) 4" round or square aluminum with flush cap. Finish to match fixture and arm. NOTE: 3Y only available on round slipfitter. Cat. No. VSF-1SA VSF-2SB VSF-2SL VSF-3ST VSF-3SY VSF-4SC Round Cat. No. SVSF-1SA SVSF-2SB SVSF-2SL SVSF-3ST SVSF-4SC Mounting Configuration 1SA-single arm mount 2SB-2 at 180° 2SL -2 at 90° 3ST -3 at 90° 3SY-3 at 120° 4SC-4 at 90° Square Wireless Control Cat. No. WIH-M No Option In fixture WiHubb® wireless control module features on/off/variable and step dimming, SNAP protocol mesh network, AES-128 encryption detection, occupancy sensor interface and intuitive, user-friendly software. The most comprehensive and up to date information can be found at http://www.hubbell-automation.com/products/wihubb_infixture_module/. 0-10V Dimming Interface Driver has a 0-10V dimming interface with a dimming range of 10-100%. Is compatible with most control systems including Hubbell Building Automation wiHUBB™. Approved dimmers include Lutron Diva AVTV, Lutron Nova NFTV and NTFTV. Note: Not compatible with current sourcing dimmers. Controls compatible via Gray and Purple dimming lead. Warranty Standard Input Black (+) White (-) Green (GND) Gray Dimming Lead (-) Fixture Housing Purple Dimming Lead (+) 30 mA Max Kim Lighting warrants Altitude™ products (“Product(s)”) sold by Kim Lighting to be free from defects in material and workmanship for (i) a period of five (5) years for metal parts, (ii) a period of ten (10) years for exterior housing paint finish(s), (iii) a period of six (6) years for LED Light Engines (PicoPrisms™) and, (iv) a period of five (5) years for LED power components (LED Driver, LifeShield® device), from the date of sale of such goods to the buyer as specified in Kim Lighting shipment documents for each product. Occupancy sensors, Surge Protector, dimmers and relay wiring components are covered by the manufacturer’s warranty. © 2014 KIM LIGHTING • 16555 East Gale Avenue, City of Industry, CA 91745-1788 • TEL: 626/968-5666 • FAX: 626/968-5716 TYPE S3 - 120/277V (please select finish) ALT96 ALTITUDE™ LED 3/13/14 • kl_alt96_spec.pdf Type: Job: Page: 5 of 5 Performance Data Projected Lumen Maintenance Spectroradiometric 3000K Average Correlated Color Temp. CCT (K) 4200K Average 5100K Average mA 50,000 hrs 100,000 hrs 350 N/A N/A 700 93.52% 89.80% 2800K-3175K 3800K-4600K 4600K-5600K Color Rendering Index (CRI) ≥75 ≥70 ≥65 Power Factor >.90 >.90 >.90 Electrical - Drive Current @350mA Volts - AC Electrical - Drive Current @700mA Amps - AC System Watts Volts - AC Amps - AC System Watts 120 0.87 104 120 1.87 224 208 0.50 104 208 1.08 224 240 0.43 104 240 0.93 224 277 0.38 104 277 0.81 224 347 0.30 104 347 0.65 224 480 0.22 104 480 0.47 224 Current - 350mA B.U.G. Rating (TM15) in Lumens where B = Backlight, U = Uplight, G = Glare Temperature TYPE 1 TYPE 2 TYPE 3 TYPE 3 NFO TYPE 4 TYPE 4 NFO TYPE 5 TYPE L/R 3000K N/A B2 U0 G3 B2 U0 G3 B2 U0 G3 B1 U0 G3 B0 U0 G3 B3 U0 G2 B3 U0 G3 4200K N/A B3 U0 G3 B3 U0 G3 B2 U0 G3 B1 U0 G3 B0 U0 G3 B4 U0 G2 B3 U0 G3 5100K N/A B3 U0 G3 B3 U0 G3 B3 U0 G3 B1 U0 G3 B0 U0 G3 B4 U0 G2 B3 U0 G3 Temperature TYPE 1 TYPE 2 TYPE 3 TYPE 3 NFO TYPE 4 TYPE 4 NFO TYPE 5 TYPE L/R 3000K N/A 8113 8191 7006 7669 6723 7906 7980 4200K N/A 10367 10467 8951 9800 8591 10103 10196 5100K N/A 11268 11377 9730 10652 9338 10981 11083 Absolute Lumens Current - 700mA B.U.G. Rating (TM15) in Lumens where B = Backlight, U = Uplight, G = Glare Temperature TYPE 1 TYPE 2 TYPE 3 TYPE 3 NFO TYPE 4 TYPE 4 NFO TYPE 5 TYPE L/R 3000K N/A B3 U0 G3 B3 U0 G3 B3 U0 G3 B1 U0 G3 B1 U0 G4 B4 U0 G2 B4 U0 G4 4200K N/A B3 U0 G3 B3 U0 G4 B3 U0 G3 B1 U0 G4 B1 U0 G4 B4 U0 G3 B4 U0 G4 5100K N/A B3 U0 G3 B3 U0 G4 B3 U0 G3 B1 U0 G4 B1 U0 G4 B4 U0 G3 B4 U0 G4 TYPE 1 TYPE 2 TYPE 3 TYPE 3 NFO TYPE 4 TYPE 4 NFO TYPE 5 TYPE L/R Absolute Lumens Temperature 3000K N/A 13902 13884 11874 13296 11395 13401 13524 4200K N/A 17763 17740 15172 16631 14561 17123 17282 5100K N/A 19308 19283 16491 18467 15827 18612 18784 LED performance and lumen output continues to improve at a rapid pace. Log onto www.kimlighting.com to download the most current photometric files from Kim Lighting’s IES File Library. For custom optics and color temperature configurations, contact factory. © 2014 KIM LIGHTING • 16555 East Gale Avenue, City of Industry, CA 91745-1788 • TEL: 626/968-5666 • FAX: 626/968-5716 TYPE S4 pole (please advise finish) International Round Straight Steel Light Poles POLE SHAFT: Fabricated from hot rolled welded steel tubing with minimum yield strength of 42,000 PSI. ANCHOR BASE: Structural quality ASTM A-36. The base is provided with bolt slots to accommodate a 7" – 9" bolt circle. ANCHOR BOLTS: Carbon steel conforming to AASHTO M314 grade-55 or ASTM F1554 grade-55. Bolts are "L" shaped and are galvanized a minimum of 12" on the threaded end. Each pole includes four bolts each with two nuts and two flat washers. FULL BASE COVER (optional): Two piece cover fabricated from ABS plastic. MOUNTING HEIGHT HANDHOLE: Covered 2 1/2" x 5" reinforced handhole. A nut holder is provided near the handhole and includes a 1/2"-13 UNC hex head bolt and nut. HARDWARE: All structural fasteners are galvanized high strength carbon steel. All other fasteners are galvanized or zinc plated or stainless steel. REINFORCED HANDHOLE W/COVER AND GROUNDING STANDARD FINISH: Galvanized or powder coated. Consult factory for standard or custom colors. MOUNTINGS OPTIONS: Tenons- standard 2 3/8" x 4" or 4" x 6" or removable pole cap used in conjunction with side mounted fixtures. 4 - ANCHOR BOLTS WITH THREADED END GALVANIZED 12” MIN. EACH BOLT FURNISHED WITH 2 HEX NUTS AND 2 FLATWASHERS NAFCO International, Fond du Lac, WI 1-800-558-4810 Fax 1-920-921-0781 Serving our customers and the industry with quality products since 1973. www.nafcointernational.com 8.5 (please advise finish) TYPE S4 pole Round Straight Steel Light Poles POLE CATALOG NUMBER RSS10-303C NOMINAL MOUNTING HEIGHT (ft) 10 Max EPA AT: (Allows for 1.3 Gust Factor) POLE O.D. INCHES WALL THICKNESS INCHES 80 MPH 90 MPH 100 MPH 3.0 120 10.0 7.7 6.0 RSS10-404C 10 4.0 .120 19.1 15.0 12.2 RSS10-4545C 10 4.5 .120 24.5 19.5 15.8 RSS12-303C 12 3.0 .120 7.7 5.8 4.4 RSS12-404C 12 4.0 .120 15.0 11.8 9.5 RSS12-4545C 12 4.5 .120 19.8 15.7 12.7 RSS14-303C 14 3.0 .120 6.0 4.4 3.3 RSS14-404C 14 4.0 .120 12.2 9.4 7.6 RSS14-4545C 14 4.5 .120 16.2 12.8 10.3 RSS16-303C 16 3.0 .120 4.6 3.2 2.3 RSS16-404C 16 4.0 .120 9.6 7.4 5.9 RSS16-4545C 16 4.5 .120 13.1 10.2 8.2 RSS18-303C 18 3.0 .120 3.4 2.3 1.4 RSS18-404C 18 4.0 .120 7.6 5.7 4.5 RSS18-4545C 18 4.5 .120 10.5 8.2 6.5 RSS20-303C 20 3.0 .120 2.4 1.4 - RSS20-404C 20 4.0 .120 6.0 4.4 3.4 RSS20-4545C 20 4.5 .120 8.5 6.6 5.2 RSS20-505C 20 5.0 .120 11.7 9.1 7.2 RSS25-404C 25 4.0 .120 2.8 1.9 1.3 RSS25-4545C 25 4.5 .120 4.8 3.6 2.7 RSS25-505C 25 5.0 .120 7.2 5.5 4.2 RSS25-505D 25 5.0 .180 12.1 9.4 7.4 RSS30-4545C 30 4.5 .120 2.3 1.5 1.0 RSS30-505C 30 5.0 .120 4.2 3.0 2.2 RSS30-505D 30 5.0 .180 8.0 6.5 4.7 1. All designs utilize .75" x 17" x 3" anchor bolts. 2. Pole base plate dimensions are the same for all designs. See pole base detail drawing for dimensions. 3. Wind load includes 1.3 gust factor. Variations in mounting heights listed are available. POLE BASE AND HANDHOLE DETAIL Dimensions and Specifications subject to change without notice. NAFCO International, Fond du Lac, WI 1-800-558-4810 Fax 1-920-921-0781 www.nafcointernational.com 8.6 (please select finish) TYPE S4 - 120/277V ALT96 ALTITUDE™ LED 3/13/14 • kl_alt96_spec.pdf Type: Job: Catalog number: Approvals: 1SA ALT3P35 96L4K120/277 MW Mtg. Fixture Finish Electrical Module See page 2 Options See pages 3-4 Ordering Example: 1SA / ALT3P35/ 96L5K277/ WH/ A26 Select pole from Kim’s Arms and Poles Selection Guide. If pole is provided by others indicate O.D. for arm fitting. Specifications ALT96 Approx. Wt. = 30 lbs. 7L" (197 mm) 26L" (680 mm) 2" (51 mm) 17" (432 mm) Speed Mount Adapter TOP SIDE BOTTOM 4B" (105 mm) FRONT 3E" (98 mm) US Patent Numbers D674,950 S and D674,965 S. Other Patents Pending. Date: Page: 1 of 5 Housing: One piece, low copper, aluminum extrusion is mechanically secured with stainless steel fasteners to low copper aluminum die-cast electrical compartment and end cap. The electrical compartment includes an integral support arm for mounting directly to a surface mount pole adaptor or a horizontal slipfitter. A solid barrier wall separates the optical and electrical compartment for thermal control. Electrical compartment and end cap covers are securely fastened with with two hinges and a single latch at each cover. One piece silicone gaskets seal the compartments at the barrier surface. Optical Module: The high performance optic utilizes the IP66 rated PicoPrism™ technology securely attached to internal heat sink modules producing incredible uniformity and visual comfort. This PicoPrism optic utilizes a canted prism lens aimed toward the task and spreads horizontally to produce high lumen output as well as great uniformity. All the optical modules are fastened to the body of the luminaire across the center as well as around the perimeter. Electrical Compartment: Available in voltages from 120V through 480V @ 50/60Hz.Class 2 output with power factor >0.9 at full load in accordance with the National Electrical Code, ANSI/NFPA 70. Integral 10kV surge suppression protection standard. To address inrush current, slow blow fuse or type C/D breaker should be used. All electronic components are UL and CSA recognized and mounted directly to a driver tray for maximum heat dissipation and modularity. Module includes a driver, LifeShield® temperature control device and surge protector. Driver is rated for -40°C starting and has a 0-10V dimming interface for multi-level illumination options. All electronic components are IP66 rated. 347V and 480V currents may have a step-down transformer. Support Arm: Die-cast, low copper aluminum with splice access cover and tool-less entry. A die-cast pole adaptor and an internal reinforcing plate are provided with wire strain relief. The arm adaptor is square or circular cut for specified pole size and shape. For field wire connections, a terminal block is mounted in the arm cavity and accessible behind the splice access cover. The block accepts #14 to #8 wire sizes and is factory prewired to the electrical module quick-disconnect plug inside the electrical compartment. Optional Horizontal Slip-fitter: Cast low copper aluminum with stamped, splice access cover. A die-cast adaptor plate is provided to secure the luminaire to 1-1/4” to 2” IPS pipe size arms. For field wire connections, a terminal block is mounted in the arm cavity and accessible behind the splice access cover. Accepts #14 to #8 wire sizes and is factory prewired to electrical module quick-disconnect plug inside the electrical compartment. Optional Wall Mount: The Altitude easily mounts to the wall. A cast aluminum mounting plate is attached to the wall over the junction box. Bolt the Speed Mount to the cover plate. Then install the assembly over the mounting plate. Slide the luminaire into place for hands free wiring and finishing. Finish: Each luminaire receives a fade and abrasion resistant, electrostatically applied, thermally cured, triglycidal isocyanurate (TGIC) polyester powdercoat finish. Standard colors include (BL) Black, (DB) Dark Bronze, (WH) White, (PS) Platinum Silver, (SG) Stealth Gray, (LG) Light Gray, and (CC) Custom Color (Include RAL#). Listed to: UL 1598 Standard for Luminaires - UL 8750 Standard for Safety for Light Emitting Diode (LED) Equipment for use in Lighting Products and CSA C22.2#250.0 Luminaires. RoHS compliant. Meets Buy American provisions within ARRA. Suitable for wet locations. CAUTION: Fixtures must be grounded in accordance with national, state and/or local electrical codes, Failure to do so may result in serious personal injury. Kim Lighting reserves the right to change specifications without notice. © 2014 KIM LIGHTING • 16555 East Gale Avenue, City of Industry, CA 91745-1788 • TEL: 626/968-5666 • FAX: 626/968-5716 TYPE S4 - 120/277V (please select finish) ALT96 ALTITUDE™ LED 3/13/14 • kl_alt96_spec.pdf Type: Job: Page: 2 of 5 Standard Features Mounting 3SY configuration is available for round poles only. Cat. No.: 1SA 2SB 2SL 3ST 3SY 4SC 1SW 0.97 1.61 1.61 1.78 n/a EPA (Effective Projected Area) ALT96 Fixture Cat. No. designates fixture and light distribution. 0.64 1.28 ALT 3x P Housing: Optic: P = PicoPrism™ ALT= Altitude Distribution: 1= Type I 2= Type II 3= Type III 4= Type IV 5 = Type V x 35 R = Type R Right L = Type L Left Current: 35 = 350 mA 70 = 700 mA Light Distribution: TYPE I Electrical Module TYPE TYPE III TYPEIIIII I TYPE TYPE TYPE RNFO TYPE TYPE II TYPE TYPE TYPE TYPE IV - NFO TYPE TYPE IV-IV NFO IV-V TYPE V TYPE TYPE TYPE TYPE III -III NFO TYPE III -NFO IIIIV TYPE IIIIV -NFO TYPE L RV TYPETYPE L R Right Right Forward Forward Forward Square Square Square LeftRight Left Throw Throw Throw 96L x Source: 96L =17"W x 26K"L 1 For 4K x Color Temperature:1 2K = 580nm Amber2 3K=3000K 4K=4000K 5K=5000K 120/277 x Voltage: 120=120V 208=208V 240=240V 277=277V 347=347V 480=480V custom optics and color temperature configurations, contact factory. Friendly. 2 Turtle © 2014 KIM LIGHTING • 16555 East Gale Avenue, City of Industry, CA 91745-1788 • TEL: 626/968-5666 • FAX: 626/968-5716 TYPE L Left TYPE S4 - 120/277V (please select finish) ALT96 ALTITUDE™ LED 3/13/14 • kl_alt96_spec.pdf Type: Job: Page: 3 of 5 Optional Features Finish TGIC powder coat. Black Color: Cat. No.: BL Dark Bronze DB Stealth Gray SG Platinum Silver White PS WH Custom Color1 CC Custom colors subject to additional charges, minimum quantities and extended lead times. Consult representative. Custom color description: 1 Wall Mounting Cat. No. 1SW Select from Mounting on page 2. The Altitude™ easily mounts to the wall. A cast aluminum wall bracket is attached to the wall over the junction box. Bolt the Speed Mount to the cover plate. Then install the assembly over the wall mount bracket. Side the luminaire into place for hands free wiring and finishing. Cover Plate 6J" x 11K" Splice Access Cover Speed Mount Adapter 5K" (140 mm) 4J" (108 mm) 10D" (270 mm) 8L" (222 mm) 11K" (292 mm) N" (14 mm) Mounting Plate 2L" (70 mm) Fusing (internal only): Cat. No. (see chart at right) No Option High temperature fuse holders factory installed inside the fixture housing. Fuse is included. Cat. No.: SF for 120, 277 and 347 Line Volts DF for 208, 240 and 480 Line Volts Photocell Receptacle Cat. No. A26 No Option Rotatable photocell receptacle provided for NEMA base photocell (by others). Receptacle Lenses Cat. No. FGL (Glass) FPL (Polycarbonate) No Option One-piece flat glass or polycarbonate lens slips into reveal. Extra silicone gasketing will be provided to retain a clear optical compartment. (Only available for 350mA systems). CAUTION: Use only when vandalism is anticipated to be high. Neighbor Friendly Optic: Cat. No. NFO No Option Integrated Neighbor Friendly Optic on each PicoPrism™ module to completely control unwanted backlight. Most effective with Type III and IV distibutions. Polycarbonate Lens TYPE I TYPE I II TYPE TYPE II III TYPE TYPE IV TYPE III -NFO TYPE III -NFO Forward Throw © 2014 KIM LIGHTING • 16555 East Gale Avenue, City of Industry, CA 91745-1788 • TEL: 626/968-5666 • FAX: 626/968-5716 TYPE TYPE IV IV- NFO TYPE IV - NFO TYPE V Forward Square Throw TYPE S4 - 120/277V (please select finish) ALT96 ALTITUDE™ LED 3/13/14 • kl_alt96_spec.pdf Type: Job: Page: 4 of 5 Optional Features Horizontal Slipfitter Mount Cat. No. HSF No Option Replaces standard mounting arm with a cast aluminum fitter to adapt to a horizontal 1J" to 2" pipe-size mounting end (1D" to 2C" OD). The casting has a +/- 5° adjustment to accommodate davit arms that are not horizontal. Vertical Slipfitter Mounts Cat. No. includes Mounting Cat. No. (See right) No Option Allows fixture or fixtures with standard mounting arm to mount to a pole with a 2" pipe-size tenon (2C" OD). Minimum 4" tenon length required. Horizontal Slipfitter for 1J" to 2" Pipe-Size Mount Specify configuration (1SA, 2SB, 2SL, 3ST, 3SY, 4SC) 4" round or square aluminum with flush cap. Finish to match fixture and arm. NOTE: 3Y only available on round slipfitter. Cat. No. VSF-1SA VSF-2SB VSF-2SL VSF-3ST VSF-3SY VSF-4SC Round Cat. No. SVSF-1SA SVSF-2SB SVSF-2SL SVSF-3ST SVSF-4SC Mounting Configuration 1SA-single arm mount 2SB-2 at 180° 2SL -2 at 90° 3ST -3 at 90° 3SY-3 at 120° 4SC-4 at 90° Square Wireless Control Cat. No. WIH-M No Option In fixture WiHubb® wireless control module features on/off/variable and step dimming, SNAP protocol mesh network, AES-128 encryption detection, occupancy sensor interface and intuitive, user-friendly software. The most comprehensive and up to date information can be found at http://www.hubbell-automation.com/products/wihubb_infixture_module/. 0-10V Dimming Interface Driver has a 0-10V dimming interface with a dimming range of 10-100%. Is compatible with most control systems including Hubbell Building Automation wiHUBB™. Approved dimmers include Lutron Diva AVTV, Lutron Nova NFTV and NTFTV. Note: Not compatible with current sourcing dimmers. Controls compatible via Gray and Purple dimming lead. Warranty Standard Input Black (+) White (-) Green (GND) Gray Dimming Lead (-) Fixture Housing Purple Dimming Lead (+) 30 mA Max Kim Lighting warrants Altitude™ products (“Product(s)”) sold by Kim Lighting to be free from defects in material and workmanship for (i) a period of five (5) years for metal parts, (ii) a period of ten (10) years for exterior housing paint finish(s), (iii) a period of six (6) years for LED Light Engines (PicoPrisms™) and, (iv) a period of five (5) years for LED power components (LED Driver, LifeShield® device), from the date of sale of such goods to the buyer as specified in Kim Lighting shipment documents for each product. Occupancy sensors, Surge Protector, dimmers and relay wiring components are covered by the manufacturer’s warranty. © 2014 KIM LIGHTING • 16555 East Gale Avenue, City of Industry, CA 91745-1788 • TEL: 626/968-5666 • FAX: 626/968-5716 TYPE S4 - 120/277V (please select finish) ALT96 ALTITUDE™ LED 3/13/14 • kl_alt96_spec.pdf Type: Job: Page: 5 of 5 Performance Data Projected Lumen Maintenance Spectroradiometric 3000K Average Correlated Color Temp. CCT (K) 4200K Average 5100K Average mA 50,000 hrs 100,000 hrs 350 N/A N/A 700 93.52% 89.80% 2800K-3175K 3800K-4600K 4600K-5600K Color Rendering Index (CRI) ≥75 ≥70 ≥65 Power Factor >.90 >.90 >.90 Electrical - Drive Current @350mA Volts - AC Electrical - Drive Current @700mA Amps - AC System Watts Volts - AC Amps - AC System Watts 120 0.87 104 120 1.87 224 208 0.50 104 208 1.08 224 240 0.43 104 240 0.93 224 277 0.38 104 277 0.81 224 347 0.30 104 347 0.65 224 480 0.22 104 480 0.47 224 Current - 350mA B.U.G. Rating (TM15) in Lumens where B = Backlight, U = Uplight, G = Glare Temperature TYPE 1 TYPE 2 TYPE 3 TYPE 3 NFO TYPE 4 TYPE 4 NFO TYPE 5 TYPE L/R 3000K N/A B2 U0 G3 B2 U0 G3 B2 U0 G3 B1 U0 G3 B0 U0 G3 B3 U0 G2 B3 U0 G3 4200K N/A B3 U0 G3 B3 U0 G3 B2 U0 G3 B1 U0 G3 B0 U0 G3 B4 U0 G2 B3 U0 G3 5100K N/A B3 U0 G3 B3 U0 G3 B3 U0 G3 B1 U0 G3 B0 U0 G3 B4 U0 G2 B3 U0 G3 Temperature TYPE 1 TYPE 2 TYPE 3 TYPE 3 NFO TYPE 4 TYPE 4 NFO TYPE 5 TYPE L/R 3000K N/A 8113 8191 7006 7669 6723 7906 7980 4200K N/A 10367 10467 8951 9800 8591 10103 10196 5100K N/A 11268 11377 9730 10652 9338 10981 11083 Absolute Lumens Current - 700mA B.U.G. Rating (TM15) in Lumens where B = Backlight, U = Uplight, G = Glare Temperature TYPE 1 TYPE 2 TYPE 3 TYPE 3 NFO TYPE 4 TYPE 4 NFO TYPE 5 TYPE L/R 3000K N/A B3 U0 G3 B3 U0 G3 B3 U0 G3 B1 U0 G3 B1 U0 G4 B4 U0 G2 B4 U0 G4 4200K N/A B3 U0 G3 B3 U0 G4 B3 U0 G3 B1 U0 G4 B1 U0 G4 B4 U0 G3 B4 U0 G4 5100K N/A B3 U0 G3 B3 U0 G4 B3 U0 G3 B1 U0 G4 B1 U0 G4 B4 U0 G3 B4 U0 G4 TYPE 1 TYPE 2 TYPE 3 TYPE 3 NFO TYPE 4 TYPE 4 NFO TYPE 5 TYPE L/R Absolute Lumens Temperature 3000K N/A 13902 13884 11874 13296 11395 13401 13524 4200K N/A 17763 17740 15172 16631 14561 17123 17282 5100K N/A 19308 19283 16491 18467 15827 18612 18784 LED performance and lumen output continues to improve at a rapid pace. Log onto www.kimlighting.com to download the most current photometric files from Kim Lighting’s IES File Library. For custom optics and color temperature configurations, contact factory. © 2014 KIM LIGHTING • 16555 East Gale Avenue, City of Industry, CA 91745-1788 • TEL: 626/968-5666 • FAX: 626/968-5716 (please advise finish) TYPE S5 ve - 120/277V TLED-b dome top led bollard Model Number: Accessories: Job:Type: Approvals: DESCRIPTION The TLED-B series bollard’s traditional design combined with a high performance LED light source and superior thermal management makes it an attractive, energy saving choice. Every aspect of the TLED-B series design has been engineered to provide a LED bollard that delivers optimum optical performance and longevity in an attractive, durable housing. The TLED-B housing uses a UV resistant powder coated finish to protect against the elements and is ETL listed for wet locations. Available 24 LED light engine with 27.5w total system watts while delivering over 1000 initial lumens output, the TLED-B bollard provides a wide spectrum of application options for lighting pedestrian walkways, retail entryways, as well as lighting sidewalks in schools, office buildings, and apartment complexes. SPECIFICATIONS Construction: An extruded aluminum housing features clean architectural lines with ample, integral mounting space for many optional accessories, the TLED-B’s most important construction feature is its integrated thermal management, which allows for optimum performance and durability of the LED light engine without sacrificing design aesthetics. The TLED-B is completely sealed and gasketed, is ETL listed for wet locations, and has tamper resistant hardware, making it a perfect choice for tamper resistant applications. TLED-B also incorporates a UV resistant, long lasting, polyester based powder coated finish. Optics: Our TLED-B series bollard delivers exceptional light quality, efficiency and light distribution with an optical design that provides even light distribution. The TLED-B’s textured silver, internal reflector is specifically designed to diffuse and distribute light where it is needed in the most efficient way possible. Electrical: The 24 LED SSL light engine in the TLED-B draws 27.5 watts total, including the driver. The TLED-B is powered by constant voltage control driver and provides a 100,000 hour rated life with 70% lumen maintenance, a 4700K CCT, and a CRI of ≥75. All drivers are Class 2 power supplies with input voltage range of 120VAC to 277VAC, providing a Class A EMI rating and a high power factor of ≥0.90. The TLED-B is suitable for operation in -40°C (-40°F) to 40°C (104°F) ambient conditions. Thermal Management: LEDLITElogic heat sinking technology moves heat away from the LEDs by utilizing a patent-pending “chimney” design that takes advantage of thermal convection dynamics maximizing system performance and delivering a 100,000 hour life with 70% lumen maintenance. SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE Environmentally Friendly Design: TLED-B luminaires consume very little energy and provide long life in comparison to traditional lamp technologies. Our manufacturing process utilizes no hazardous substances such as mercury or lead . The TLED-B is RoHS (Restriction of Hazardous Substances) compliant, 100% recyclable, and provides a significant reduction in Kw load and carbon emissions. Installation: The TLED-B series features a sturdy base plate that is anchored with three J-bolts. The bollard body easily attaches to the base plate by three tamperresistant fasteners and the bollard top is attached to the body using three more tamper-resistant fasteners. Transient Protection System (Option: TP): The LEDLITElogic optional transient protection device is designed to be used in conjunction with our LED drivers. The “-TP” option utilizes a 3-leaded device that protects Line-Ground, Line-Neutral, and Neutral-Ground in accordance with IEEE/ANSI C62.41.2 guidelines. The surge current rating of the “-TP” option is 10,000 amps. Testing & Compliance: The reliability and performance of the TLED-B is evaluated in accordance with the parameters outlined and reported by LM-79 and LM-80 documents. Photometric data is tested to IESNA LM-79-08 standard by an independent testing laboratory. Lumen maintenance, L70 a measure of long term reliability, is determined for the light source, which consists of the LED and PCB sub-assembly as installed in the luminaire, is determined using LM-80 in situ thermal and reliability data as provided by the LED manufacturer in accordance with DOE/EPA standards. 108002340 06/13 Listing: The TLED-B is ETL certified under UL1598 specifications and listed for wet locations. Warranty: Any component that fails due to manufacturer’s defect is guaranteed for 5 years. The warranty does not cover physical damage, abuse or acts of God. Manufacturer reserves the right to charge for such repairs if deemed necessary. (please advise finish) Fixture Performance TYPE S5 ve - 120/277V Sample Photometrics Part Number Initial Lumens Lumens per Watt (LPW) Total Watts L70 Hours @ 25°C BUG Ratings TLED-B-24-DT 1012 37 27.5 100,000 B1-U2-G1 TLED-B-24 (Type V Short Non-Cutoff) 20’ 15’ NOTE: Lumen maintenance and life (part of LM-80 data) are per published information from primary LED suppliers and is based on design operation at their specified thermal management and electrical design parameters. .1fc 10’ .5fc 1fc 5’ Dimensions 5fc 0 5’ 10’ 39.5” 15’ 20’ 0 5’ 10’ 15’ 20’ 6.9” Mounting Template 3/8" Diameter Bolt Hole 4.5" Diameter Circle Ordering Information Example: TLED-B-24-DT-SLV-TP Series TLED-B # of LEDs 24 = 24 LEDs Input Voltage DT = 120/277VAC Finish Options (Factory Installed) Accessories4 (Field Installed) BL = Black SZXXX1 TLED-347VST3 = 347VAC Step Down Transformer SLV = Silver TP = Transient Protection System Notes 1 Specify voltage 2 Consult factory for specific part number and details 3 Step down transformer installed by others (may affect UL listing) CC2 = Single Line Side Fuse (Specify 120 or 277V) TLED-480VST3 = 480VAC Step Down Transformer = Custom Color 1911 W. Parkside Lane • Phoenix, AZ 85027 (800) 533-3948 • Fax: (623) 580-8948 www.barronltg.com (please advise finish) TYPE S5 - 120/277V LIGHTSCALE™ BOLLARD PRODUCT DATA With its smooth, organic lines and subtly curved profile, the LightScale Bollard is designed to settle harmoniously into any natural setting. Originally conceived as a path light, its gentle arc allows mounting beside a walkway or street, providing light without taking up walk space. MATERIAL & CONSTRUCTION DETAILS INSTALLATION & MAINTENANCE COLUMN FINISH LAMP INSTALLATION • Column is made from a formed aluminum extrusion. • Standard powdercoat colors are Aluminum Texture and Slate Texture. Optional colors from the F+S color chart and custom RAL colors are available for an upcharge. • Linear fluorescent lamps are offered in 40W or 55W. See lamp information on page 2. • Standard 1/4" (6 mm) thick stainless steel mounting plate bolted to main body of extrusion in three places with 1/4-20 recessed security socket caps screws. 1/2-13 anchor bolts and template included. • Due to the inherent nature of metal castings, gloss powdercoats are not offered for cast components. TOP CAP WEIGHT BALLAST MAINTENANCE • Cast aluminum cap is attached with recessed security socket cap screws. • 27 lbs (12 kg) • Electronic, thermally protected, 120V or 277V ballast for 40W or 55W single twin tube 4-pin fluorescent lamp, instant start, -20 ºF starting temperature. • Metal surfaces can be cleaned as needed using a soft cloth or brush with warm water and a mild detergent. Avoid abrasive cleaners. NOMINAL DIMENSIONS BASE PLATE MOUNTING DETAIL top cap custom bent aluminum extrusion housing 42" (1058 mm) 0.63" (16 mm) dia. thru for 1/2-13 anchor bolts typ (3) holes 2.0" (51 mm) dia. thru for conduit opening 2.5" (63.5 mm) 5.0" (127 mm) UV-stabilized white acrylic lens 5.75" (146 mm) lamp 8.24" (209 mm) socket for 2G11 base ballast within waterproof enclosure conduit with wire whip (not shown) base plate with anchor bolts and cutout for conduit 18.0" (457 mm) min. for cast-inplace J-bolts cast-in-place J-bolt anchors (drop-in type anchors may also be used) poured concrete footer T 800.451.0410 | www.forms-surfaces.com © 2014 Forms+Surfaces® | All dimensions are nominal. Specifications and pricing subject to change without notice. For the most current version of this document, please refer to our website at www.forms-surfaces.com. page 1 of 3 | Rev. 01-10-14 (please advise finish) TYPE S5 - 120/277V LIGHTSCALE™ BOLLARD PRODUCT DATA LAMP DESCRIPTIONS LAMP DESCRIPTION BASE INITIAL LUMENS COLOR TEMPERATURE FT55 BX 55W single twin tube 4-pin fluorescent 2G11 4,800 4,100 FT40 BX 40W single twin tube 4-pin fluorescent 2G11 3,150 4,100 POLAR CANDELA PLOT 0-180º 90-270º ISOFOOTCANDLE PLOT 706 18.0' 529 12.0' 353 6.0' 176 0' 3 10 5 2 1 .5 .75 -6.0' .25 -12.0' -18.0' -12.0' 18.0' 12.0' 6.0' 0' -6.0' -18.0' Isofootcandle Plot shows light distribution pattern at ground level with 55W fluorescent 2G11 base lamp. Readings have been taken assuming the photometric center of the luminaire to be 2.40 feet above ground level. IES files for standard lamps are available on our website. Polar Candela Plot shows luminous intensity distribution (Cd/1000lm) for vertical plane through specified horizontal angles (above) with 55W fluorescent 2G11 base lamp. IES files for standard lamps are available on our website. CERTIFICATION • UL and C-UL listed for wet locations. ENVIRONMENTAL CONSIDERATIONS • Please refer to the LightScale Bollard Environmental Data Sheet for detailed environmental impact information. • Metal components have a long life cycle and are 100% recyclable. • 68% recycled content. • Powdercoat finishes are no- or low-VOC, depending on color. • Low maintenance; easy to disassemble. LAMP DESCRIPTIONS AND FOOTCANDLE MULTIPLIERS LAMP DESCRIPTION BASE INITIAL LUMENS COLOR TEMPERATURE FT55 BX 55W single twin tube 4-pin fluorescent 2G11 4700 4,100 FT40 BX 40W single twin tube 4-pin fluorescent 2G11 3150 4,100 T 800.451.0410 | www.forms-surfaces.com © 2014 Forms+Surfaces® | All dimensions are nominal. Specifications and pricing subject to change without notice. For the most current version of this document, please refer to our website at www.forms-surfaces.com. page 2 of 3 | Rev. 01-10-14 (please advise finish) TYPE S5 - 120/277V LIGHTSCALE™ BOLLARD PRODUCT DATA NET PRICING AND ORDERING INFORMATION (pricing does not include freight) MODEL LBLSC-CF DESCRIPTION LightScale Bollard Optional Powdercoat color from Forms+Surfaces standard color chart Custom RAL Powdercoat color NET PRICE please call for pricing + $200 per color/per order + minimum $500 per color/per order TO ORDER SPECIFY: quantity, powdercoat color, lamp, voltage. LEAD TIME: 6 to 8 weeks. Shorter lead times may be available upon request. Please contact us to discuss your specific timing requirements. T 800.451.0410 | www.forms-surfaces.com © 2014 Forms+Surfaces® | All dimensions are nominal. Specifications and pricing subject to change without notice. For the most current version of this document, please refer to our website at www.forms-surfaces.com. page 3 of 3 | Rev. 01-10-14