SECTION 16435 BRANCH CIRCUIT PANELBOARDS PART 1 - GENERAL 1.01 REQUIREMENTS A. 1.02 SCOPE A. 1.03 The general provisions of the Contract, including General and Supplementary Conditions and General Requirements, apply to the work specified in this Section. The work covered under this Section shall include furnishing and installing circuit breaker type branch circuit panelboards complete for all systems as shown on the Drawings and herein specified. QUALITY ASSURANCE A. All equipment, materials, and their installation shall conform to the requirements of the National Electrical Code (NEC), local code requirements, and these Specifications. B. All equipment and materials shall be listed by Underwriter's Laboratories, Inc. (UL) for their intended use and shall bear the UL label. C. Equipment shall be constructed in accordance with National Electrical Manufacturer's Association (NEMA) standards. D. Submittals are required in accordance with SECTION 16010 of these Specifications. The manufacturer shall furnish, but not be limited to the following: 1. Circuit breaker layout with dimensions and nameplate designation. 2. Circuit breaker trip ratings and frame sizes. 3. Component list. 4. Conduit entry/exit locations. 5. Assembly ratings, including short-circuit rating, voltage, and continuous current rating. 6. Bus material, including ground bar. 16435-1 11/13 BRANCH CIRCUIT PANELBOARDS 1.04 SECTION 16435 7. Cable terminal sizes. 8. Product data for each type of panelboard. DELIVERY, STORAGE AND HANDLING A. Deliver material and products in factory labeled packages. Store and handle in strict compliance with manufacturer’s instructions and recommendations. B. Each panelboard section shall be delivered in individual shipping cases and individually wrapped for protection. C. Store in a clean, dry space. Maintain factory protection and /or provide an additional heavy canvas or heavy plastic cover to protect panelboards from dirt, water, construction debris, and traffic. Where applicable, provide adequate heating within enclosures to prevent condensation. D. Handle in accordance with NEMA PB1.1 and manufacturer’s written instructions. Handle carefully to avoid damage to panelboards internal components, enclosure and finish. PART 2 - PRODUCTS 2.01 MANUFACTURERS A. 2.02 The branch circuit panelboards shall be as manufactured by CUTLER-HAMMER, GENERAL ELECTRIC, SIEMENS, or SQUARE D. PANELBOARDS A. This Contractor shall furnish and install where indicated on the Drawings, deadfront branch circuit panelboards incorporating switching and branch circuit protective devices of the number, ratings, and type noted herein or as shown on the Drawings. Branch circuit panelboards shall have NEMA 1 general purpose enclosures and shall be surface or flush mounted as noted. All branch circuit panelboards shall be rated for the intended voltage and shall be in accordance with UL's "Standard for Panelboards" and "Standard for Cabinets and Boxes" and shall be so labeled. Branch circuit panelboards shall also comply with NEMA "Standard PB1 for Panelboards" and the NEC. B. Ratings: [ENGINEER, EDIT OUT SHORT-CKT STUDY IF NOT IN PROJECT] 1. Panelboards rated 240 Vac or less shall have short-circuit ratings as shown on the drawings or as determined by the Short-Circuit Coordination Study whichever is higher, but not less than 10,00016435-2 11/13 BRANCH CIRCUIT PANELBOARDS SECTION 16435 amperes RMS symmetrical. 2. Panelboards rated 480 Vac shall have short-circuit ratings as shown on the drawings or as determined by the Short-Circuit Coordination Study whichever is higher, but not less than 14,000-amperes RMS symmetrical. 3. (ENGINEER, DELETE THIS PARAGRAPH IF NOT USING SERIES CONNECTED RATINGS) Panelboards shall have a fully rated or series connected short-circuit rated interrupting ratings as indicated on the drawings and shall be labeled with a UL short-circuit rating. When series connected ratings are applied with integral or remote upstream devices, a label shall be provided. It shall state the conditions of the UL series connected ratings including: a. b. c. C. Size and type of upstream device. Branch devices that can be used. UL series short-circuit rating. Interiors: 1. All interiors shall be completely factory assembled with switching and protective devices, wire connectors, etc. All conductor connectors, except screw terminals, shall be of the anti-turn solderless type and all shall be suitable for copper conductors of the sizes indicated on the Drawings. 2. Interiors shall be designed so that switching and protective devices can be replaced without disturbing adjacent units and without removing the main bus connectors and shall be so designed that circuits may be changed without matching, drilling, or tapping. D. Branch circuits shall be arranged using double row construction except where a narrow column width panelboard is required or noted on the Drawings. Branch circuits shall be numbered by the manufacturer. E. Furnish and install three (3), 3/4 inch and two (2), one inch empty conduits up through the wall and turned out above the ceiling; and three (3), 3/4 inch and two (2), one inch empty conduits down into the ceiling space below the floor for all flush mounted branch circuits panelboards. Where floor slab is on grade, provide only empty conduits to the ceiling. F. All surface mounted branch circuit panelboards shall be mounted on twelve (12) gauge formed steel channel having a cross section dimension at least 1-1/2 inches x 1-1/2 inches on walls. The channel and fittings shall have a hot dipped galvanized finish to resist rust formation. Channels shall be installed vertically 16435-3 11/13 BRANCH CIRCUIT PANELBOARDS SECTION 16435 and as detailed on the Drawings. G. H. Bus Bars: 1. Bus bars for the mains shall be of copper sized in accordance with UL 67 Standards for temperature rise to limit temperature rise on any current carrying part to a maximum of 65 degrees C above an ambient of 40 degrees C maximum. The bus bars shall be standard density rated for 1000 amperes per square inch copper. Bus bar taps for branch circuit panelboards with single pole branches shall be arranged for sequence phasing of the branch circuit devices. Busing shall be braced throughout to conform to industry standard practice governing short circuit stresses in panelboards. Phase busing shall be full height without reduction. Cross connectors shall be copper. A non-insulated copper ground bus shall be provided for each panelboard. 2. Phase busing shall be manufactured to accept bolt-on circuit breakers only. 3. Spaces for the addition of future switching and protective devices in branch circuit panelboards shall be bussed for the maximum number of devices possible complete with pre-drilled mounting holes and knockouts in the front cover. 4. A non-insulated copper ground bus shall be provided for each branch circuit panelboard. 5. Full size (100% rated) insulated neutral busing shall be included for panelboards shown with a neutral. Neutral busing shall have a suitable lug for each outgoing feeder or branch circuit requiring a neutral connection. 6. Lugs shall be rated for 75 degrees C terminations and shall bolt in place. Backboxes: 1. Backboxes shall be made from unpainted galvanized code gauge steel having no knockouts. 2. Boxes shall have gutter and wiring space sized as required per NEC but not less than four (4) inches on all sides. Where feeder cables supplying the mains of a panelboard are carried through the box to supply other electrical equipment, the box shall be so sized as to include this wiring space. This wiring space shall be in addition to the minimum gutter space specified above and the limiting width may be increased accordingly. 16435-4 11/13 BRANCH CIRCUIT PANELBOARDS I. SECTION 16435 3. Backboxes shall also have sufficient space to safely attach clamp-on or split-core current transformers to the feeders for future portable or permanent check metering. 4. Backboxes for multiple (two or more) sections shall be of the same dimensions. 5. Each backbox shall include at least four (4) interior mounting studs. 6. The branch circuit panelboard identification number shall be on the backbox. 7. Branch circuit panelboard backboxes shall be of one (1) piece construction. Trim: 1. Hinged doors shall be the door-in-door type covering all switching device handles and all live parts and shall be included in all branch circuit panelboard trims. 2. Doors in branch circuit panelboard trims shall conform to the following: 3. a. In making device handles accessible, inboard doors shall not uncover any live parts. Outboard doors shall allow hinged access to the interior panel wiring without removal of the panel door assembly. b. Doors shall have a semi-flush type cylinder lock and catch. Door hinges shall be concealed. Two (2) keys shall be furnished for each panelboard door and all locks shall be keyed as requested by the Owner to match current standard. The outer door shall be keyed separately. Directory frame and card, having a transparent cover, shall be furnished on the inside of each door. c. Directory cards shall be neatly typewritten indicating each branch circuit number and assignment. The assignment designation shall include the final room number(s) assigned by the Owner. Do not use the architectural room numbers shown on the Drawings. The director cards shall also include the source (switchboard, panelboard, etc. with circuit number) feeding the panel. The trims shall be fabricated from code gauge sheet steel. 16435-5 11/13 BRANCH CIRCUIT PANELBOARDS J. 2.03 SECTION 16435 4. All of the panelboard's steel surfaces, exterior and interior shall be properly cleaned and finished with the manufacturer's standard paint over a rust-inhibiting phosphatized coating. The finish paint shall be of a type to which field applied paint will adhere. 5. Trims for flush mounted branch circuit panelboards shall overlap the box by at least 3/4 inches on all sides. Surface trims shall be mountable by a screwdriver without the need for special tools. Conduit skirts shall be provided on surface mounted branch circuit panelboards, where shown on the drawings. Skirts shall be the same width and depth as the panelboard backbox. Screw on skirt covers shall be the same code gauge sheet steel as the panelboard trim and painted with the same finish and color as the panelboard. Skirts shall be from the top of the panelboard to the underside of the finished ceiling and/or from the bottom of the panelboard to the finished floor concealing all conduits. CIRCUIT BREAKERS A. Electrical circuits shall be protected by molded case circuit breakers as indicated on the Drawings. B. The circuit breakers shall be operated by a toggle type handle and shall have a quick-make, quick-break over-center switching mechanism that shall be mechanically trip free from the handle so that the contacts cannot be held closed against short circuits and abnormal currents. Tripping due to overload or short circuit shall be clearly indicated by the handle automatically assuming a position midway between the manual "ON" and "OFF" positions. All latch surfaces shall be ground and polished. All poles of a multi-pole breaker shall be so constructed that they open, close, and trip simultaneously. C. The circuit breakers shall be completely enclosed in a molded case. Noninterchangeable trip breakers shall have their covers sealed; interchangeable trip breakers shall have the trip unit sealed to prevent tampering. Ampere ratings shall be clearly visible. Contacts shall be non-welding silver alloy. Arc extinction shall be accomplished by means of arc chutes consisting of metal grids mounted in an insulating support. Breakers shall be of the bolt-on type; plug-in, plug-on, blow-on, and clamp-on circuit breakers shall not be acceptable. D. Circuit breakers shall be 80% rated unless indicated on the Drawings to be 100% rated. E. Circuit breakers shall have a minimum symmetrical interrupting capacity as indicated on the Drawings. The interrupting ratings of the circuit breakers shall be at least equal to, or greater than, the available short circuit at the line terminals and not less than those values shown on the Drawings and specified in 16435-6 11/13 BRANCH CIRCUIT PANELBOARDS SECTION 16435 this specification section or as determined by the Short-Circuit Coordination Study whichever is higher. [ENGINEER, EDIT OUT SHORT-CKT STUDY IF NOT IN PROJECT] F. Circuit breakers shall be listed with UL, conform to the applicable requirements of the latest issue of NEMA Standards Publication No. AB1. G. Circuit breakers shall have thermal-magnetic trip units, with inverse time-current characteristics, unless otherwise noted on the Drawings and/or specified herein. H. 1. Automatic operation of all circuit breakers shall be obtained by means of thermal-magnetic tripping devices located in each pole providing inverse time delay and instantaneous circuit protection. Instantaneous pick-up settings for each phase shall be adjustable on all frames 250A and above. 2. Circuit breakers shall be ambient compensating in that, as the ambient temperature increases over 40° C, the circuit breaker automatically derates itself to better protect its associated conductor. 3. Circuit breakers 250A and above shall have thermal magnetic interchangeable trip units, Circuit breaker frames 400 ampere and above shall have microprocessor-based RMS sensing trip units on 480 volt systems and on 208 volt systems where indicated on the Drawings. 1. Solid State sensing shall measure true RMS current with capability to st measure through to the 21 harmonic. Automatic operation of all circuit breakers shall be obtained by means of solid state tripping elements providing inverse time delay and instantaneous and short-time circuit protection. Continuous current rating shall be adjustable from 20% to 100% of trip unit rating. Long-time delay and instantaneous trip ratings shall also be adjustable. The short time pick-up trip shall have adjustable pick-up settings at definite times and with I2t delay. 2. Long time current adjustment shall be possible without the need for a rating plug. 3. Main and feeder circuit breakers shall be provided with integral ground fault protection in 480 volt panels. Ground fault pick-up shall be adjustable from 20% to 70% of the breakers maximum continuous current rating, but in no case be greater than 1200A. Ground fault time delay shall be adjustable with three (3) I2t delay settings. 16435-7 11/13 BRANCH CIRCUIT PANELBOARDS 2.04 Solid State circuit breakers shall have built-in test ports for testing the long-time delay, instantaneous, and ground fault functions (if equipped) of the breaker by means of a test set. 5. Provide one test set capable of testing all circuit breakers with a built-in test port, unless previously provided under another section of these specifications. Circuit breaker accessories: Provide shunt trips, bell alarms and auxiliary switches, etc. as may be shown on the drawings. All accessories shall be UL Listed for field installation. J. Circuit breakers shall be manufactured by the same manufacturer as the panelboard and factory installed. K. Where indicated, circuit breakers shall be UL listed for series application. (ENGINEER TO EDIT OUT THIS PARAGRAPH IF NOT USING SERIES CONNECTED BREAKERS.) MULTIPLE SECTION PANELBOARDS Panelboards with two (2) or more panelboard sections, sub-feed lugs or thrufeed lugs shall be used in all but one (1) section of each panelboard, unless otherwise shown on the Drawings. Lugs shall have same capacity as incoming mains. Cable interconnections shall be field installed. NAMEPLATES A. 2.06 4. I. A. 2.05 SECTION 16435 Branch circuit panelboards shall have nameplates of 1/16 inch thick laminated plastic with 3/16 inch high white letters on a black background. Nameplates shall identify the branch circuit panelboard and shall be mounted on the front top of the enclosure. SURGE PROTECTIVE DEVICE (SPD) A. Provide surge protective devices (SPD) as specified in Section 16418. PART 3 - EXECUTION 3.01 INSTALLATION A. Before installing branch circuit panelboards, this Contractor shall check all of the Drawings for possible conflict of space and adjust the location of the branch circuit panelboard to prevent such conflict with other items. Panelboard locations in electrical rooms and other spaces shall closely follow the layouts shown on the Drawings, leaving sufficient space on walls for future installations of panelboards and/or other electrical equipment. 16435-8 11/13 BRANCH CIRCUIT PANELBOARDS 3.02 3.03 3.04 SECTION 16435 B. Surface mounted branch circuit panelboards shall be securely mounted to steel framing channel at locations shown on Drawings. Construction shall be such that additional conduits can be added for future requirements. C. The cabinets and enclosures shall be mounted in accordance with the NEC. This Contractor shall furnish all materials necessary for mounting the branch circuit panelboards. D. Install units plumb, level and rigid without distortion to the branch circuit panelboard. E. Branch circuit panelboard interiors shall be factory assembled with circuit breakers, wire connectors, etc. Circuit breakers shall be sequence numbered to correspond with the panelboard directory. F. Connect the SPD to the appropriate circuit breaker. G. Contractor shall install required safety labels. FIELD TESTS A. Check tightness of all accessible mechanical and electrical connections to assure they are torqued to the minimum acceptable manufacturer’s recommendations. B. Check all panelboards for proper grounding, fastening and alignment. FIELD ADJUSTMENTS A. This Contractor shall perform field adjustments of the protective devices as required to place the equipment in final operating condition. Necessary field settings of devices and adjustments and minor modifications to equipment shall be carried out by this Contractor at no additional cost to the Owner. B. (ENGINEER, DELETE THIS PARAGRAPH WHEN SECTION 16015 “SHORTCIRCUIT/COORDINATION STUDY” IS NOT USED) The settings shall be in accordance with the approved protective device coordination study or as directed by the Engineer. CLEANING A. Remove debris from panelboards and wipe dust and dirt from all components. B. Repaint marred and scratched surfaces with touch-up paint to match original finish. 16435-9 11/13 BRANCH CIRCUIT PANELBOARDS 3.05 SECTION 16435 EXISTING BRANCH CIRCUIT PANELBOARDS A. This Contractor shall clean, adjust, and tighten all feeder and branch circuit connections (new and existing) and provide new typewritten directories (as described above) in all existing branch circuit panelboards that are associated with work on this project. Panelboard’s not associated with work on this project are not subject to this requirement. END OF SECTION 16435-10 11/13