EXL 1000 Uninterruptible Power System Installation and User’s Guide IMPORTANT SAFETY INSTRUCTION SAVE THESE INSTRUCTIONS — This manual contains important instructions for models EXL 1050 (PNs 891050-44, 891050-84), EXL 1075 (PNs 891075-44, 891075-84) and EXL 1100 (PNs 891100-44, 891100-84) that must be followed during installation, operation and maintenance of the UPS and batteries. Tightening torque for all input and output terminal blocks shall be 10.6 - 12.3 in-lbs (1.2 - 1.4 Nm). The nominal battery voltage ratings are: EXL 1050 - 180 Vdc EXL 1075 - 180 Vdc EXL 1100 - 240 Vdc. A power output disconnect switch must be provided by the user if the EXL 1000 distribution cabinet is not installed. Input power cables and output power cables for the 5 kVA model shall be rated for 10 AWG, 75°C or 10 AWG, 90°C. Input power cables and output power cables for 7.5 kVA and 10 kVA models shall be rated for 6 AWG, 75°C or 6 AWG, 90°C copper wire. The EXL 1000 series UPS is intended for installation in a temperature controlled, indoor area free of conductive contaminants. Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. When replacing batteries, replace with the same number of batteries. Use Yuasa NP7-12 FR CAUTION - Do not dispose of battery or batteries in a fire. The battery may explode. CAUTION - Do not dispose or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic. CAUTION - A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed when working on batteries. Remove watches, rings, or other metal objects. Use tools with insulated handles. Wear rubber gloves and boots. Do not lay tools or metal parts on top of batteries. Important Safety Instructions 86-891000-00 Installation and User’s Manual Disconnect charging source prior to connecting or disconnecting battery terminals (if applicable). Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source of a ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock will be reduced if such grounds are removed during installation and maintenance. Interconnecting cables - Flexible cord or flexible cable assemblies used for external interconnection between parts of equipment or between components of a system are not provided. Internal Wiring - (AVLV2), Style Nos. 1015, 1061, 2464, 2690, 2768, type SIS. Building wire type THHN and XHHW and ribbon cable style 2651. All wiring is routed away from sharp edges and moving parts. Smooth and well-rounded surfaces are provided for wiring to bear upon when passing through sheet metal walls. Where wires are bundled or run in ducts, 300 V insulated wires are bundled and physically separated from 600 V rated wire or occupy separate ducts. All multi-conductor style 2464 wires are rated 300 V. Size of Branch Circuit Overcurrent Protection - CAUTION To reduce the risk of fire, connect only to a circuit provided with 60 amperes maximum branch circuit overprotection in accordance with the National Electrical Code, ANSI/NFPA 70. Operating temperature - 0° - 30°C at rated output. 40°C for 8 hours max. WARNING High voltages are present inside the EXL 1000 system. Any servicing requiring removal of the protective covers may be undertaken only by qualified personnel certified by MGE UPS Systems. WARNING OPENING ENCLOSURES EXPOSES HAZARDOUS VOLTAGES. ALWAYS REFER SERVICE TO QUALIFIED PERSONNEL ONLY. 86-891000-00 Important Safety Instructions EXL 1000 Uninterruptible Power System NOTE As standards, specifications and designs are subject to change, please ask for confirmation of the information given in this publication. This manual is a controlled document. Pages should not be removed individually from this binder. NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. Important Safety Instructions 86-891000-00 prepared for: EXL 1000 Uninterruptible Power System Installation and User’s Guide For service call 1-800-438-7373 86-891000-00 C01 06/98 Copyright © 1997 MGE UPS Systems, Inc.. All rights reserved. Printed in U.S.A. MGE UPS Systems 1660 Scenic Avenue Costa Mesa, CA 92626 (714) 557-1636 86-891000-00 EXL 1000 Uninterruptible Power System Installation and User’s Guide Warranty The liability of MGE UPS Systems, Inc. hereunder is limited to replacing or repairing at MGE UPS Systems, Inc.’s factory or on the job site at MGE UPS Systems, Inc.’s option, any part or parts which are defective, including labor, for a period of 24 months from the date of purchase. MGE UPS Systems, Inc. shall have the sole right to determine if the parts are to be repaired at the job site or whether they are to be returned to the factory for repair or replacement. All items returned to MGE UPS Systems, Inc. for repair or replacement must be sent freight prepaid to its factory. Purchaser must obtain MGE UPS Systems, Inc.’s Return Materials Authorization prior to returning items. The above conditions must be met if warranty is to be valid. MGE UPS Systems, Inc. will not be liable for any damage done by unauthorized repair work, unauthorized replacement parts, from any misapplication of the item, or for damage due to accident, abuse, or Act of God. In no event shall MGE UPS Systems, Inc. be liable for loss, damage, or expense directly or indirectly arising from the use of the units, or from any other cause, except as expressly stated in this warranty. MGE UPS Systems, Inc. makes no warranties, express or implied, including any warranty as to merchantability or fitness for a particular purpose or use. MGE UPS Systems, Inc. is not liable for and Purchaser waives any right of action it has or may have against MGE UPS Systems, Inc. for any consequential or special damages arising out of any breach of warranty, and for any damages Purchaser may claim for damage to any property or injury or death to any person arising out of its purchase of, or the use, operation or maintenance of the product. MGE UPS Systems, Inc. will not be liable for any labor subcontracted or performed by Purchaser for preparation of warranted item for return to MGE UPS Systems, Inc.’s factory or for preparation work for field repair or replacement. Invoicing of MGE UPS Systems, Inc. for labor either performed or subcontracted by Purchaser will not be considered as a liability by MGE UPS Systems, Inc. This warranty shall be exclusive of any and all other warranties express or implied and may be modified only by a writing signed by an officer of MGE UPS Systems, Inc. This warranty shall extend to the Purchaser but to no one else. Accessories supplied by MGE Systems, Inc., but manufactured by others, carry any warranty the manufacturers have made to MGE UPS Systems, Inc. and which can be passed on to Purchaser. MGE UPS Systems, Inc. makes no warranty with respect to whether the products sold hereunder infringe any patent, U.S. or foreign, and Purchaser represents that any specially ordered products do not infringe any patent. Purchaser agrees to indemnify and hold MGE UPS Systems, Inc. harmless from any liability by virtue of any patent claims where Purchaser has ordered a product conforming to Purchaser’s specifications, or conforming to Purchaser’s specific design. Purchaser has not relied and shall not rely on any oral representation regarding the Product sold hereunder and any oral representation shall not bind MGE UPS Systems, Inc. and shall not be part of any warranty. There are no warranties which extend beyond the description on the face hereof. In no event shall MGE UPS Systems, Inc. be responsible for consequential damages or for any damages except as expressly stated herein. Service and Factory Repair - Call 1 - 800 - 523 - 0142 Direct questions about the operation, repair, or servicing of this equipment to MGE UPS Systems, Inc. Technical Support Services. Include the part number and serial number of the unit in any correspondence. Should you require factory service for your equipment, contact MGE UPS Systems, Inc. Technical Support Services and obtain a Return Materials Authorization (RMA) prior to shipping your unit. Never ship equipment to MGE UPS Systems, Inc. without first obtaining an RMA. Proprietary Rights Statement The information in this manual is the property of MGE UPS Systems, Inc., and represents a proprietary article in which MGE UPS Systems, Inc. retains any and all patent rights, including exclusive rights of use and/or manufacture and/or sale. Possession of this information does not convey any permission to reproduce, print, or manufacture the article or articles shown herein. Such permission may be granted only by specific written authorization, signed by an officer of MGE UPS Systems, Inc. IBM, PC-AT, ES/9000, and AS/400 are trademarks of International Business Machines Corporation. MGE and MGE UPS Systems are trademarks of MGE UPS Systems, Inc. Other trademarks that may be used herein are owned by their respective companies and are referred to in an editorial fashion only. Revision History EXL 1000 Uninteruptible Power System Installation and User’s Guide 86-891000-00 Copyright © 1997 MGE UPS Systems. All rights reserved. Printed in U.S.A. Revision: A00 New Release 01/97 B00 ECN 289-93 10/97 C00 ECN 291-79 2/98 C01 ECN 293-49 06/98 86-891000-00 Contents Introduction 1.0 . . . . . . . . . . . . . . . Scope 1.1 . . . . . . . . . . . . . . . General Description 1.1.1 Description of UPS Module 1.2 . . . . . . . . . . . . . . . Configuration 1 1 1 1 — — — — 1 2 2 4 2 2 2 2 2 2 2 — — — — — — — 1 1 1 4 4 5 5 Installation 2.0 2.1 2.2 2.3 2.4 2.5 2.6 . . . . . . . . . . . . . . ..... ..... ..... ..... ..... ..... ..... 2.6.1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Scope Storage Unpacking General Final positioning Special Precautions Connections Electrical Diagram for Power Connections 2—5 Operation 3.1 . . . . . . . 3.1.1 3.1.2 3.2 . . . . . . . 3.3 . . . . . . . 3.4 . . . . . . . 3.5 . . . . . . . 3.6 . . . . . . . 3.7 . . . . . . . 3.8 . . . . . . . 3.9 . . . . . . . 3.10 . . . . . . 3.11 . . . . . . 3.12 . . . . . . 3.13 . . . . . . 3.14 . . . . . . 3.15 . . . . . . . . . . . . . . Controls and indicators 3—1 Basic controls and indicators 3—1 Controls and Diagnostic Display 3—4 . . . . . . . . Checks before Start-up 3—5 . . . . . . . . Powering up the EXL 1000 3—6 . . . . . . . . Manual Inverter Start-up 3—6 . . . . . . . . Shutting down the inverter 3—6 . . . . . . . . Powering down the inverter 3—7 . . . . . . . . Normal Operation 3—7 . . . . . . . . Operation on battery power 3—8 . . . . . . . . Battery duration 3—8 . . . . . . . . Return of AC input power 3—9 . . . . . . . . Battery Monitoring Tests 3—9 . . . . . . . . Overload 3—9 . . . . . . . . Alarms 3 — 10 . . . . . . . . Diagnostics display messages 3 — 11 . . . . . . . . Manual Bypass 3 — 14 Communications 4.0 . . . . . . . . . . . . . . . Standard Functions 4.1 . . . . . . . . . . . . . . . Options 86-891000-00 4—1 4—2 iii EXL 1000 Uninterruptible Power System Maintenance and Service 5.0 . . . . . . . . . . . . . . . Scope 5.1 . . . . . . . . . . . . . . . User Preventive Maintenance 5.2 . . . . . . . . . . . . . . . Maintenance by Certified MGE Representatives 5.2.1 Battery Maintenance 5.2.2 Environmental Protection 5.2.3 Annual Check 5.2.4 Customer Training 5.2.5 Maintenance Contracts 5—1 5—1 5 5 5 5 5 5 — — — — — — 1 1 2 2 2 2 Options 6.1 . . . . . . . . . . . . . . . Extended battery cabinet 6.2 . . . . . . . . . . . . . . . Connection of an additional battery cabinet 6.3 . . . . . . . . . . . . . . . Emergency Power Off (EPO) 6.4 . . . . . . . . . . . . . . . Battery circuit breaker shunt trip connection 6.5 . . . . . . . . . . . . . . . Combined options 6—1 7.1 . . . . . . . . . . . . . . . Introduction 7.1.1 Storage 7.1.2 Safety Recommendation 7.2 . . . . . . . . . . . . . . . Installation of the U-Talk board 7.2.1 Powering down the EXL 1000 UPS 7.2.2 Installing the U-Talk RS232 board 7.2.3 Returning power to the EXL 1000 UPS 7.3 . . . . . . . . . . . . . . . Description of RS232 board 7.3.1 Function 7.3.2 Configuring the RS232 board 7.4 . . . . . . . . . . . . . . . Configuration for UPS Manager software 7.5 . . . . . . . . . . . . . . . U-Talk data format 7 7 7 7 6—2 6—4 6—4 6—5 U-Talk iv Contents — — — — 1 1 1 2 7—2 7—2 7 7 7 7 — — — — 3 3 3 3 7—4 7—5 86-891000-00 Installation and User’s Manual Appendices A.0 . . . . . . . . . . . . . . . General Characteristics A.1 . . . . . . . . . . . . . . . Range Characteristics a—1 a—1 Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . g — 1 Illustrations figure description page number 1-1 . . . . . . . . . . . . . . . Identification Plate 1—4 1-2 . . . . . . . . . . . . . . . EXL 1000 5kVA front and rear view 1—5 1-3 . . . . . . . . . . . . . . . EXL 1000 7.5 & 10 kVA front and rear view 1—5 1-4 . . . . . . . . . . . . . . . Functional diagram 1—6 2-1 . . . . . . . . . . . . . . . Unpacking the EXL 1000 UPS 2—2 2-2 . . . . . . . . . . . . . . . Removing stabilizing material from under EXL 1000 UPS 2—3 2-3 . . . . . . . . . . . . . . . Using supplied ramp to bring EXL 1000 off of shipping base 2—3 2-4 . . . . . . . . . . . . . . . Installation clearanc es as seen from above 2—4 2-5 . . . . . . . . . . . . . . . Connection diagram for a single AC input 2—5 2-6 . . . . . . . . . . . . . . . Removal of conduit landing cover panel (5 kVA) 2—7 2-7 . . . . . . . . . . . . . . . Cable connections (5 kVA) 2—7 2-8 . . . . . . . . . . . . . . . Removal of maintenance bypass switch knob and conduit landing cover panel (7.5 & 10 kVA) 2—8 2-9 . . . . . . . . . . . . . . . Cable Connections (7.5 & 10 kVA) 2—8 3-1 . . . . . . . . . . . . . . . Location of Controls and indicators on cabinet 3—1 3-2 . . . . . . . . . . . . . . . Close-up of Controls and indicators 3—2 3-3 . . . . . . . . . . . . . . . “Load protected” LED 3—2 3-4 . . . . . . . . . . . . . . . “Battery Status” LED 3—2 3-5 . . . . . . . . . . . . . . . “Fault” LED 3—3 3-6 . . . . . . . . . . . . . . . “Load Not Protected” LED 3—3 3-7 . . . . . . . . . . . . . . . Audible Alarm 3—3 3-8 . . . . . . . . . . . . . . . “Inverter On” button 3—3 3-9 . . . . . . . . . . . . . . . “Inverter Off” button 3—4 3-10 . . . . . . . . . . . . . . Controls and Diagnostics Display 3—4 3-11 . . . . . . . . . . . . . . Manual Maintenance Bypass circuit breaker 3—5 3-12 . . . . . . . . . . . . . . EXL 1000 power-up 3—6 86-891000-00 Contents v EXL 1000 Uninterruptible Power System figure description page 3-13 . . . . . . . . . . . . . . Indicators during normal operation 3-14 . . . . . . . . . . . . . . Diagram of normal operation on utility power 3-15 . . . . . . . . . . . . . . Indicators when on battery power 3-16 . . . . . . . . . . . . . . Diagram of operation on battery power 3-17 . . . . . . . . . . . . . . Inverter overload curve 3-18 . . . . . . . . . . . . . . Static Bypass overload curve 3-19 . . . . . . . . . . . . . . Relationship of fault codes to EXL 1000 subsystems 3-20 . . . . . . . . . . . . . . Manual Bypass Switch 4-1 . . . . . . . . . . . . . . . Electrical connections of 15 pin D connector 4-2 . . . . . . . . . . . . . . . 15 pin D connector 6-1 . . . . . . . . . . . . . . . Connection of an additional battery cabinet (5kVA Model) Covers Removed 6-2 . . . . . . . . . . . . . . . Connection of an additional battery cabinet (7.5 & 10 kVA Models) 6-3 . . . . . . . . . . . . . . . Connection diagram for battery circuit breaker shunt trip on terminal block XR3 6-4 . . . . . . . . . . . . . . . XR3 terminal block for EXL 1050, EXL 1075 and EXL 1100 7-1 . . . . . . . . . . . . . . . Inserting the U-Talk board into the groove 7-2 . . . . . . . . . . . . . . . Overview of RS232 board 7-3 . . . . . . . . . . . . . . . Close-up of figure 7-2, section A 7-4 . . . . . . . . . . . . . . . Factory settings of U-Talk board jumpers 7-5 . . . . . . . . . . . . . . . Configuring the Transmission Speed 7-6 . . . . . . . . . . . . . . . Configuring the Transmission Format 7-7 . . . . . . . . . . . . . . . Configuring the Hx and Ix Signals Format vi Contents number 3—7 3—7 3—8 3—8 3 — 10 3 — 10 3 — 13 3 — 14 4—1 4—1 6—3 6—3 6—5 6—5 7—2 7—3 7—3 7—4 7—4 7—5 7—5 86-891000-00 Installation and User’s Manual Tables table description page number 1-1 . . . . . . . . . . . . . . . Model and Part numbers for installation of 5 kVA, 7.5kVA and 10kVA 1—2 2-1 . . . . . . . . . . . . . . . Battery cabinet for an overall operating time of 30 minutes (7.5 & 10 kVA) or 24 minutes (5 kVA) at rated output power with a power factor of 0.6 6—1 2-2 . . . . . . . . . . . . . . . Battery cabinet for an overall operating time of 50 minutes (7.5 & 10 kVA) or 40 minutes (5 kVA) at rated output power with a power factor of 0.6 6—2 3-1 . . . . . . . . . . . . . . . Maximum current ratings a—4 3-2 . . . . . . . . . . . . . . . Minimum cable size a—4 86-891000-00 Contents vii EXL 1000 Uninterruptible Power System This manual has been designed to provide you with all the information you need to install and use your EXL 1000 UPS system. How to use this manual This manual is designed for ease of use and easy location of information. This manual uses Noteboxes to convey information. Noteboxes come in four varieties: WARNING CAUTION A WA R N I N G n o t e b ox indicates information p rov i d e d t o p ro t e c t the user and service personnel against safety hazards and/or possible equipment damage . A C AU T I O N n o t e b ox indicates information provided to protect the user and ser vice personnel against possible equipment damage . IMPORTANT NOTE An IMPORTANT notebox indicates information provided as an operating instruction or as an operating tip. A N OT E n o t e b ox indicates information provided as an operating tip or an equipment feature. Safety Recommendations viii important If you encounter a problem while following the instructions in this manual, we recommend that you contact our Customer Support Services. On request, our customer support personnel can carry out the complete installation of your equipment. 86-891000-00 Introduction 1.0 Scope This manual provides technical information required for operation and maintenance of the EXL 1000 series uninterruptible power system (UPS). Please read this manual before operating the EXL 1000 equipment. Please retain this manual for future reference. The manual is divided into seven100 sections: Section I — General Description This section introduces the EXL1000 family of uninterruptible power systems, including a general description of the system and its internal components, a description of available options, and system specifications. Section II — Installation This section describes the installation procedures for the EXL 1000. Section III — Operation This section describes operating information for EXL 1000 UPS single-module systems, including an overview of the system, its components, and their functions; a description of the indicators and controls and their functions; and operational sequences to be followed for all conditions of normal, emergency, and maintenance operation. Section IV — Communication This section describes communication options availabel for the EXL 1000. Section V — Maintenance and Service This section describes user level maintenance and service practices for the EXL 1000. Section VI — Options This section describes available add on options for the EXL1000. Section VII — U-Talk This section describes installation and usage of the optional U-Talk board which allows computer systems to monitor and controll the EXL 1000 remotely. An appendix near the rear of this manual provides information on specifications of the EXL 1000. 86-891000-00 1—1 EXL 1000 Uninterruptible Power System A Glossary in the rear of this manual provides definitions of terms used within the text. 1.1 General Description The EXL1000 series are a family of Uninterruptible Power Supplies (UPS) designed for safe reliable VAC backup power for the computer room, office or industrial environments. This manual describes the function and installation of the 5kVA, 7.5kVA, and 10kVA members of the EXL1000 UPS family. The following are the model numbers and part numbers respectively: Table 1-1 1.1.1 M o d e l a n d Pa r t n u m b e rs fo r i n s t a l l a t i o n o f 5 k VA , 7 . 5 k VA a n d 1 0 k VA Description Model Number Part Number UPS 4.7 kVA/3.8 kw, 208 VAC in/out EXL 1050 891050-84 UPS 5 kVA/4 kw, 240 VAC in/out EXL 1050 891050-44 UPS 7.1 kVA/5.7 kw, 208 VAC in/out EXL 1075 891075-84 UPS 7.5 kVA/6 kw, 240 VAC in/out EXL 1075 891075-44 UPS 9.5 kVA/7.6 kw, 208 VAC in/out EXL 1100 891100-84 UPS 10 kVA/8kw, 240 VAC in/out EXL 1100 891100-44 Description of There are 7 major components within the EXL1000 UPS and they are as follows: UPS Module 1. Input EMI filter - This is an electonic filter which prevents electrical noise (EMI) generated by the UPS from conducting or radiating back onto the AC input power lines. It also incorporates lightning strike protection for the UPS. 2. Input rectifier - This module takes AC input line to line voltage and converts it to a rectified DC voltage which is fed to the input of the “chopper” module. 3 Chopper - The chopper module has two voltage inputs. A rectified AC input and a battery DC voltage. The chopper module outputs + and - 385 Vdc which is fed to the inverter module. When AC input is present the chopper takes power from this input. When the AC input fails or is removed the chopper automatically will transfer to battery and take power from the battery source in order to continue to power the inverter module. 4. 1—2 Battery - A 180 Vdc (5 or 7.5 kVA models) or 240Vdc (10 kVA model) source is used to power the chopper Introduction 86-891000-00 Installation and User’s manual module which powers the inverter module which powers a user’s output load. This happens only when the AC input fails, is out of tolorance or is removed. 86-891000-00 5. Inverter - This power module converts the + and 385Vdc output from the chopper to 208 or 240VAC line to line which continually outputs and powers the user’s load. 6. Static bypass switch - Solid state switch. When the inverter is overloaded, fails or is turned off, the UPS automatically transfers it’s output load to the AC input of the UPS via this solid state switch called the static bypass switch. This automatic power transfer mechanism allows for no loss of output power to the user’s load. The load’s power is never interrupted with this type of power transfer. The inverter output, although off or disabled, is still physically connected to the load. 7. Maintenance bypass switch - A manual hard switch. This switch is used when maintenance is required on the UPS without interrupting power to the load. Turning this switch to “bypass” internally connects the AC input directly to the AC output of the UPS, while at the same time physically disconnecting the inverter output from the load. By also turning off the input circuit breaker, the internal electronics are now physically isolated from input and output, enabling a service technician to open the UPS and service it without fear of electrocution. At the same time, the load is still being powered directly by the AC input via the maintenance bypass switch. Introduction 1—3 EXL 1000 Uninterruptible Power System Figure 1-1 Identification Plate PULSAR EXL 1000 Article - Article - Artikel NT 6762690 01 N° Série - Serial Number - Artikel + - PB02 CEAC Volt : Ah : YUA Model Number Serial Number Sales Order No. AC Input: 891100-84 L1 L2 + GND Input Voltage: Input Current: 208V 47 Frequency: 60 Hz AC Output: Vrms L — L Arms L1 L2 + GND Output Voltage: Output Current: 208V 46 Frequency: 60 Hz Vrms L — L Arms Output Power: 9.5KVA/7.6KW Batt Voltage: 240VDC Batt Current: 46 Adc LISTED 55K6 E87247 UNINTERRUPTIBLE POWER SUPPLY 1.2 1—4 Configuration The configuration sheet, included with the UPS, indicates all the factory settings. Keep the sheet in a safe place as it may be required by the after-sales support technicians if you wish to modify parameters. Introduction 86-891000-00 Installation and User’s Manual Figure 1-2 E X L 1 0 0 0 5 k VA f ro n t a n d r e a r v i ew ! Basic control and indication panel Location of optional communications ports Special command and diagnostic display Diagnostics and configuration connector (reserved for after-sales support) Standard communication port ! fault Input circuit breaker "manual maintenance bypass" switch Utility connection cover panel Figure 1-3 Battery connection panel Fan E X L 1 0 0 0 7 . 5 & 1 0 k VA f ro n t a n d r e a r v i ew Basic control and indication panel ! Special command and diagnostic display ! Location of optional communications ports Battery circuit breaker fault Diagnostics and configuration connector (reserved for after-sales support) Standard communication port Fans "manual maintenance bypass" switch Input circuit breaker Connection cover panel 86-891000-00 Introduction 1—5 EXL 1000 Uninterruptible Power System Figure 1-4 Functional diagram "static bypass" module AC input load Input circuit breaker "manual maintenance bypass" switch Rectifier module Inverter module Battery circuit breaker Charger module Battery 1—6 Introduction 86-891000-00 Installation 2.0 Scope This section describes installation of the EXL 1000 UPS. 2.1 Storage The equipment must always be stored in its original packaging. IMPORTANT The battery is of the sealed type. Battery storage or prolonged shutdown of EXL 1000 should never exceed 6 months at 68°F (20°C) without recharging, for a battery initially at 100% charge. Battery recharge requires system start-up. The battery warranty is void if the 6 month recharge interval is not respected. 2.2 Unpacking The equipment must be unpacked close to the installation location. NOTE After unpacking, check the overturn indicator at the back of the device. If it is red (or otherwise indicates that the unit has been tipped over during shipping), contact the after-sales department. 86-891000-00 2—1 EXL 1000 Uninterruptible Power System Figure 2-1 U n p a ck i n g t h e E X L 1 0 0 0 U P S remove ramp ramp for 7.5 & 10 kVA UPS ramp for 5kVA UPS remove packing corners remove box unbolt from base 2—2 Installation 86-891000-00 Installation and User’s manual Figure 2-2 R e m ov e s t a b i l i z i n g m a t e r i a l f ro m u n d e r E X L 1 0 0 0 U P S Figure 2-3 Use supplied ramp to bring EXL 1000 off of shipping base levelling screws in the raised position ramp (7.5/10kVA) ramp (5kVA) 86-891000-00 Installation 2—3 EXL 1000 Uninterruptible Power System 2.3 General EXL 1000 cabinets are equipped with 4 wheels for moving over short distances and with jacks to immobilize the unit. The jacks must be raised prior to repositioning the unit. Since operating temperature range is 32°F to 86°F (0°C to 30°C) at rated output, a location with appropriate ventillation and cooling should be chosen for installation. Battery life is extended when it is installed in a room with an ambient temperature of 59°F to 77°F (15°C to 25°C). Above 77°F (25°C), battery life is reduced by 50% for every additional 18°F (10°C). Heat generatedfrom EXL 1000 operation must be taken into account when sizing the ventilation system. See the Appendices. Power cable connections are made through the bottom section in the back of the EXL 1000. 2.4 Final positioning Figure 2-4 I n s t a l l a t i o n cl e a r a n c e s a s s e e n f ro m a b ov e Ensure that service clearance to the left of EXL 1000 is greater than 16 inches (400 mm) for side access to the battery cells. Ensure that there is greater than 4 inches (100 mm) on the left for ventilation. Ensure that front clearance is greater than 22 inches (550 mm) for servicing. Ensure that there is at least 4 inches (100 mm) behind the cabinet for ventilation. 4 inches minimum (for ventilation) 12 in. min. 15.75 inches service clearance 10.5 inches 15.75 inches 4 in. ventilation clearance 4 in. air exhaust ventilation clearance P EXL1000 transformer/ distribution cabinet extended battery option other option 22 in. min. service clearance Additional cabinets (extended battery, distribution/ transformer, etc.) must be placed to the right of EXL 1000. If the above installation conditions are not respected, maintenance and servicing of the unit may require system shutdown. 2—4 Installation 86-891000-00 Installation and User’s manual 2.5 Special Precautions Load cables must be run separately from all other cables (power supply or computer system interconnection cables). They should not pass near interference-emitting equipment or sensitive loads. 2.6 Connections Connection cables should enter at the bottom rear of the 7.5/10kVA. Connection cables for the 5kVA model must be 10 AWG 75°C minimum. Connection cables for the 7.5 kVA and 10 kVA must be 6 AWG 75°C minimum. Cables must be enclosed in a .75 inch flexible conduit. Cables should be sufficiently long to enable forward movement of EXL 1000 without disconnection. Allow an extra 5 feet (1.5 meters) slack in the cables. Conduit shall be terminated to a conduit landing via a 3/4 inch flexible metal conduit fitting. 2.6.1 Electrical Diagram for Figure 2-5 shows a single-line electrical diagram for a typical installation. The power cables requiring connection are shown as bold lines (see the appendices for information on selecting cable gauges). Power Connections Figure 2-5 C o n n e c t i o n d i a g r a m fo r a s i n g l e AC i n p u t EXL1000 AC input XR1 XR2 load XR3 XR3 extended battery cabinets (optional) Make sure the unit is powered down and disconnected from all input power before making connections to the terminal blocks at the back of the cabinet. For protection of life and property, ground wires should always be connected first. Neutral system: identical upstream and downstream neutral systems (no galvanic isolation). EXL 1000 can be used with all types of neutral systems, on the condition that standard practices be respected. Check that AC input power circuit breaker, installed upstream on the low voltage switchboard, is in off (O) position; Check that the input circuit breaker and the battery circuit breaker are in off (O) position. 86-891000-00 Installation 2—5 EXL 1000 Uninterruptible Power System Connection sequence: • Remove maintenance bypass switch knob using a narrow flathead screwdriver (7.5 & 10 kVA models only). • Remove the conduit landing cover panel that is secured with six torx screws. • Connect flexible conduit to conduit landing. • Connect the AC input cables to Mains 1 terminal block XR1. Observe phase 1 (L1), phase 2 (L2) and ground correspondence as indicated on the label (figure 2-7 for 5 kVA and figure 2-9 for 7.5 & 10 kVA). NOTE There are two phases and one ground. There is no neutral connection. • Connect the AC load cables to terminal block XR2. Observe phase 1 (L1), phase 2 (L2) and ground correspondence as indicated on the label (figure 2-7 for 5 kVA and figure 2-9 for 7.5 & 10 kVA). • Connect the various options as indicated in the corresponding sections of this manual. • Reattach the conduit landing cover panel and maintenance bypass switch knob (7.5 & 10 kVA models). NOTE 5 kVA UPS conduit landings are shipped loose. Installation should be done by authorized personnel only. 2—6 Installation 86-891000-00 Installation and User’s Manual Figure 2-6 R e m ova l o f c o n d u i t l a n d i n g c ov e r p a n e l ( 5 k VA ) Figure 2-7 C a b l e c o n n e c t i o n s ( 5 k VA ) detail of connection terminal blocks L- L+ to load (two-phase + ground) L2 L1 XR3 battery XR2 load L2 L1 XR1 Mains 1 from LV switchboard (two-phase + ground) 86-891000-00 Installation 2—7 EXL 1000 Uninterruptible Power System Figure 2-8 R e m ova l o f m a i n t e n a n c e by p a s s sw i t c h k n o b a n d c o n d u i t l a n d i n g c ov e r p a n e l ( 7 . 5 & 1 0 k VA ) maintenance bypass switch knob conduit landing cover panel Figure 2-9 C a b l e C o n n e c t i o n s ( 7 . 5 & 1 0 k VA ) L– L+ 1 2 3 4 L1 L2 XR1 Mains 1 XR3 battery EPO connector (optional) from LV switchboard (two-phase + ground) 2—8 L1 L2 Installation XR2 load to load (two-phase + ground) 86-891000-00 Operation 3.1 Controls and EXL 1000 operating controls include basic controls and indicators (figure 3-1), concerning the overall operating status of the UPS and the special command and diagnostic display panel (figure 3-10), which includes specific controls and a 2-digit display for the UPS fault numbers. These numbers provide UPS diagnostics. indicators Figure 3-1 L o c a t i o n o f C o n t ro l s a n d i n d i c a t o rs o n c a b i n e t basic controls and indicators panel ! ! ! ! fault fault special command and diagnostic display 3.1.1 Basic controls and indicators The basic controls and indicators are located in the upper left-hand corner of the front panel. This panel provides information on the operating status of the system (see figure 3-2). Interpretation of the LEDs is very easy and requires no special training. The LEDs indicate normal operation (load protected), UPS fault, load not protected and operation on battery power. 86-891000-00 3—1 EXL 1000 Uninterruptible Power System Figure 3-2 C l o s e - u p o f C o n t ro l s a n d i n d i c a t o rs ! ! I +– O audible alarm "load not protected" light "fault" light "battery status or operation on battery power" light "load protected" light "inverter on" button "inverter off" button The “Load protected” LED indicates that the EXL 1000 is operating normally. The load is supplied by the inverter output. This LED also goes on during normal start-up of EXL 1000. Figure 3-3 “ L o a d p ro t e c t e d ” L E D ! ! +– I O “Load Protected” LED The “Battery Status” LED can be on continuously or may flash repeatedly. If continuously lit, the “Battery Status” LED indicates that the inverter is operating on battery power following an AC input failure or detection of an AC input voltage outside tolerances. When flashing, it indicates that the low battery shutdown warning level has been reached. If the LED flashes when the battery is not in self-operating phase, this indicates that the battery status should be checked by an After-Sales representative. Figure 3-4 “Battery Status” LED ! ! +– I O “Battery Status” LED Continuously on — Inverter on battery power Flashing — low battery shutdown or check batteries 3—2 Operation 86-891000-00 Installation and User’s manual The “Fault” LED indicates an operating fault or an environment fault. However, the load continues to be supplied by the inverter. Figure 3-5 “ Fa u l t ” L E D ! ! I + – O “Fault” LED The “Load Not Protected” LED indicates that the load is supplied through the "static bypass" because of inverter shutdown (voluntary or following an overload or an internal fault), or that battery power is not available because the battery circuit breaker is in "off" position. Figure 3-6 “ L o a d N o t P ro t e c t e d ” L E D ! ! I +– O “Load Not Protected” LED The audible alarm is activated when the load is supplied directly by AC input power via the “static bypass,” the inverter is operating on battery power, or when there is an operating fault. It beeps softly and slowly for minor faults and during inverter operation on battery power. When the low battery shutdown warning level has been reached, the beeps get louder and more frequent. In the event of an inverter shutdown, a continuous loud alarm is emitted. An audible alarm reset button is provided on the controls and diagnostics display panel. Detection of a new fault will reactivate audible alarm. Figure 3-7 Au d i b l e A l a r m beep...beep... ! ! +– I O “Audible alarm” LED The green “inverter on” button is used to start the inverter. Figure 3-8 “ I nv e r t e r O n ” bu t t o n ! ! +– I O “Inverter on” button 86-891000-00 Operation 3—3 EXL 1000 Uninterruptible Power System The grey “inverter off” button is used to stop the inverter. Figure 3-9 “ I nv e r t e r O f f ” bu t t o n ! ! +– I O “Inverter off” button 3.1.2 Controls and Diagnostic Display Figure 3-10 The controls and diagnostics display panel (figure 3-10) includes an LED display for environment and subassembly faults and buttons for specific controls. Faults are displayed only when the user presses (once) one of the control buttons. C o n t ro l s a n d D i a g n o s t i c s D i s p l ay fault diagnostics display fault reset security button audible alarm reset The audible alarm reset button enables the user to quiet the audible alarm. Detection of a new alarm will set the audible alarm off again. The fault reset button clears the faults stored in memory. Clearing of alarms in memory is accepted only if the alarm conditions themselves have been cleared. The security button authorizes forced operation or shutdown of the inverter. There are three tasks that can be done using the security button. Forced shutdown Forced operation Battery manual test 3—4 press the security button and the "inverter off" button (figure 3-9) simultaneously for three seconds. press the security button and the "inverter on" button (figure 3-8) simultaneously for three seconds. press the security button and the audible alarm reset button simultaneously for three seconds. Operation 86-891000-00 Installation and User’s manual IMPORTANT The batery manual test function causes the battery to discharge completely in order to update the battery monitoring parameters. Do not enable test during normal work hours because battery back-up will be lessened or unavailable during this test. In the event of a network power cut, the uninterrupted battery power supply returns to normal operation. The self-operating time is thus reduced. Alarm, fault and status messages are displayed as numerical codes. See section 3.14 for the meaning of the codes. The alarm-code equivalence table is also displayed at the back of EXL 1000. 3.2 Check the settings of the protection devices: Start-up • Input circuit breaker is in the off (O) position. • Battery circuit breaker is in the off (O) position, • "Manual bypass" circuit breaker is set to "NORMAL" position (see figure 3-11) • Check that nothing is blocking the ventilation system (air entry through the bottom and, where applicable, through the side vents) • Check that there is a minimum of 4 inches (100mm) clearance at the back for ventilation • Check that the EXL 1000 no longer rests on its 4 wheels (leveling screws in place) • Check that the load-circuit circuit breakers (where applicable) are in the off (O) position. M a n u a l M a i n t e n a n c e B y p a s s c i rc u i t b r e a k e r BY-PASS TEST 1 NORMAL Figure 3-11 Checks before TEST 2 86-891000-00 Operation 3—5 EXL 1000 Uninterruptible Power System 3.3 Powering up the EXL 1000 First put the input circuit breaker in the “on” position, then put the battery circuit breaker in the "on" position. The audible alarm will sound and the green “load protected” LED will light. The rectifier and the battery charger will start up. If the transfer conditions (AC input power within tolerances) are correct, the inverter comes on line and supplies the load unless the system is in "manual start-up" mode (optional, section 3.4). The green "load protected" LED will now be on. Figure 3-12 E X L 1 0 0 0 p ow e r- u p beep...beep ! ! + – I O "load protected" LED "inverter on" button In the event of a fault, the red "load not protected" light goes on. See the Alarms section (section 3.13). 3.4 Manual Inverter To manually start the inverter,use the following steps: Start-up Press the green "inverter on" button The green "load protected" LED will flash The inverter will start and if the transfer conditions are correct, the load will be transferred to the inverter. The red "load not protected" LED will go off and the green "load protected" LED will light. 3.5 Shutting down the inverter Press and hold the "inverter off" button for three seconds. The green "load protected" LED will go off and the red "load not protected" LED will light. The audible alarm will sound. If the transfer conditions are correct, the inverter will stop and the load will be supplied directly by AC input power via the "static bypass." In the event of fault, see the Alarms section (section 3.13). 3—6 Operation 86-891000-00 Installation and User’s manual 3.6 Powering down Powering down the EXL 1000 for long periods is not recommended because the battery should remain charged. However, to carry out a power down, proceed as follows: the inverter • Shutdown the inverter (section 3.5) • Put the battery circuit breaker in the "off" position; • Turn off the input circuit breaker All the LEDs on the control panel will go off. WARNING The load is still supplied by AC input power via the "static bypass". • 3.7 Normal Operation Put the upstream circuit breaker(s) on the low voltage switchboard in "off" position. The AC input power supply is present: the green "load protected" light (figure 3-13) is on; the power drawn by the load is supplied by AC input power via the rectifier and inverter modules. The battery charger float charges or recharges the battery. The DC output voltage of the battery charger is temperature regulated to ensure an optimal charge voltage. Figure 3-13 I n d i c a t o rs d u r i n g n o r m a l o p e r a t i o n ! ! +– I O “Load Protected” LED Figure 3-14 Diagram of normal operation on utility power AC input load inverter rectifier charger 86-891000-00 battery Operation 3—7 EXL 1000 Uninterruptible Power System 3.8 Operation on When AC input power fails or exceeds tolerances, the rectifier and the battery charger shut down. The battery supplies the power required by the inverter to supply the load. battery power The battery discharges. The green "load protected" light is on. The user is warned of operation on battery power by the audible alarm and by the orange "battery status" light (figure 3-15). This information is also available via the standard communication connector. Figure 3-15 I n d i c a t o rs w h e n o n b a t t e r y p ow e r beep...beep... ! ! I +– O audible alarm "battery status" LED "load protected" LED Figure 3-16 D i a g r a m o f o p e r a t i o n o n b a t t e r y p ow e r static bypass AC input load rectifier inverter charger 3.9 Battery duration battery EXL 1000 has a battery monitoring function that calculates the remaining backup time. This function may be implemented with a communications option. A low battery shutdown warning signal is available via the standard communication connector for remote indications. It warns the user of upcoming battery shutdown at a userdetermined level of remaining power. On the UPS itself, the audible alarm beeps louder and more rapidly, and the orange "battery status" light flashes. 3—8 Operation 86-891000-00 Installation and User’s manual The end of battery power occurs when the battery is fully discharged. At this point, the inverter shuts down. The recharge time required to restore the battery of a 5 kVA model to its rated backup power is 12 hours maximum. The recharge time required to restore the battery of a 7.5 kVA or 10 kVA model is 5 hours maximum. 3.10 Return of AC input power If the end of battery backup power was not reached when the AC input power failure ends or power returns to within tolerances; EXL 1000 returns to normal operating status where the inverter will receive power from the rectifier and not the battery. If the end of battery backup power was reached, the rectifier, the battery charger and the inverter automatically start up (the inverter must be manually started if the system is in manual start mode). 3.11 Battery Monitoring Tests The battery is automatically checked every month. The message "17" on the diagnostics display (figure 3-10) tells the user that the battery is in this operating mode. It is recommended to carry out a complete discharge test on the battery once a year in order to update the battery monitoring parameters. This test is activated by the "battery manual test" control. See section 3.1.2. The message "18" on the diagnostics display tells the user that the battery is in this operating mode. In these operating modes, total battery failure is indicated by the alarm message "15" on the diagnostics display. 3.12 Overload During a major temporary overload (greater than 150%), the load is supplied by AC input power via the static bypass. Return to the inverter is automatic, following elimination of the overload. The inverter can handle a minor overload for a given duration depending on the size of the overload (see figure 3-17). When an overload occurs, the audible alarm sounds, the orange "fault" LED goes on, and the inverter shuts down at the end of its corresponding overload time. When the inverter shuts down, the load receives its AC input power via the static bypass. To indicate that the inverter is no longer protecting the load, the green "load protected" light goes off and the red "load not protected" light goes on. 86-891000-00 Operation 3—9 EXL 1000 Uninterruptible Power System If the overload continues during operation via the static bypass, the supply of power to the load is interrupted after a specified time. See figure 3-18. When the EXL 1000 has shut down because of an overload, the fault reset button must be pressed prior to return to normal operation. Figure 3-17 I nv e r t e r ov e r l o a d c u r v e time 10 min 1 min 10 sec 1 sec rated load current In 0.15 sec 1.05 1.1 Figure 3-18 1.3 1.5 1.7 1.9 2 S t a t i c B y p a s s ov e r l o a d c u r v e time 10 mn 1 mn 10 sec 1 sec rated load current In 0.15 sec 1.05 1.1 3.13 Alarms 1.3 1.5 1.7 1.9 2 The status of the EXL 1000 can be determined by the status LEDs and the audible alarm (see section 3.14). Any state other than normal operation (green “load protected” LED on) is considered a fault by the diagnostics system. Before undertaking any servicing or other action, note the status of the LEDs and the number(s) of the fault(s) indicated on the diagnostics display. If the "Monitor Plus" option is installed, also note the messages in the list on the screen. Certain faults may result in the display not functioning. If the load still functions, it is supplied via the "static bypass;" it is not protected by the inverter. 3 — 10 Operation 86-891000-00 Installation and User’s manual 3.14 Diagnostics display messages 86-891000-00 The diagnostics display shows numeric codes for alarms, faults and status messages. Following is a list of the numeric codes and their meanings. Figure 3-19 is a diagram of the EXL 1000’s major components and shows which subsystems are responsible or affected by various fault codes. 11 battery circuit breaker in "off" position indicates that the battery circuit is open (battery circuit breaker is in "off" position). The load is no longer protected because battery power is no longer available in the event of an AC input power failure. In the case of the "battery-free frequency converter" option, it is normal for the "11" message to remain on. 12 check battery indicates that the battery should be checked (see Battery maintenance section 5.2.1). 13 low battery shutdown warning indicates that battery power will end after a user-set time period. The user must take the required measures to secure the load (load shedding, file saving and system shutdown, etc.). 14 end of battery power 15 battery fault indicates a problem with the battery (see "battery maintenance" in the "maintenance and servicing" section. 16 ambient temperature fault this display indicates that the ambient temperature is outside the tolerance range (<0°C or > 40°C). 17 battery periodic test this message indicates that the battery is in the process of being checked. 18 battery manual test this message indicates that the battery is in the process of being completely discharged in order to update the battery monitoring parameters. 21 inverter fault indicates a fault in the inverter module; contact the aftersales support department. Operation 3 — 11 EXL 1000 Uninterruptible Power System 3 — 12 22 inverter overtemperature indicates overheating inside the UPS; check that the EXL 1000 ventilation system is working and that the ambient temperature is within tolerances (see "appendices"). 25 inverter overload indicates an overload when the load is being supplied via the inverter. Reduce the load. 31 Mains 2 (bypass) voltage outside tolerance range this display indicates that the Mains 2 power supply voltage of the "static bypass" is outside the tolerance range. 32 phase shift outside tolerance range this display indicates that the phase between the Mains 2 power supply of the "static bypass" and the "inverter module" is outside the tolerance range 34 frequency of Mains 2 (bypass) power supply to "static bypass" outside tolerances the output inverter voltage is no longer synchronized with Mains 2. To force transfer of the load to the inverter, simultaniously press the security button and the green "inverter on" button and hold for three seconds. Transfer results in a 0.5 second break in the supply of power to the load. To force transfer of the load to the "static bypass", simultaniously press the security button and the grey "inverter off" button. Transfer results in a 0.5 second break in the supply of power to the load. 35 "static bypass" overload indicates an overload when the load is being supplied via the "static bypass". Reduce the load. 37 Mains 1 voltage outside tolerance range this display indicates that the voltage of the Mains 1 power supply of the "rectifier module" is outside the tolerance range. 39 installation fault indicates an incorrect connection at the frequency converter input; check the connection of the Mains 1 input source to terminal block XR1. 41 load supplied via "static bypass" this display indicates that the load is powered by the Mains 2 via the "static bypass" 51 battery charger fault indicates a fault in the battery charger module; contact the after-sales support department Operation 86-891000-00 Installation and User’s manual Figure 3-19 rectifier or chopper fault indicates a fault in the rectifier module; contact the after-sales support department 62 chopper overtemperature see fault "22". 63 fuse blown on Mains 1 input indicates that the fuse has blown in the rectifier module; contact the after-sales support department. 65 chopper overload indicates that the active power consumed is too high. Reduce the load 71 internal communication fault indicates an EXL 1000 internal fault; contact the after-sales support department 72 internal communication self-test fault see fault "71". 73 CPU board self-test fault see fault "71". Relationship of fault codes to EXL 1000 subsystems 35 31 33 34 41 39 61 16 37 63 Ambient Temp. 51 12 86-891000-00 61 62 65 32 21 22 25 71 72 73 11 13 14 15 17 18 Operation 3 — 13 EXL 1000 Uninterruptible Power System 3.15 Manual Bypass If the load is no longer supplied, a manual bypass operation enabling supply is possible, while waiting for the after-sales support personnel. Proceed as follows: Switch the input circuit breaker to the "off" position. • Switch the battery circuit breaker to "off" position. • Check that all lights are off. • Turn the "manual bypass" switch as indicated in figure 3-20 from the "NORMAL" position to the "BYPASS" position. Manual Bypass Switch BY-PASS TEST 1 NORMAL Figure 3-20 • TEST 2 IMPORTANT The TEST 1 and TEST 2 positions are reserved for the after-sales support personnel. Leave the switch set to the "BYPASS" position until the arrival of the after-sales support personnel. Use of the switch other than as indicated above may damage EXL 1000 and void the warranty. 3 — 14 Operation 86-891000-00 Communication 4.0 Standard Functions The communication connector, positioned on the back for EXL 1000 5/7.5/10kVA, supplies the following information: • operation on the "static bypass". • low battery shutdown warning. • load supplied by the inverter. • operation on battery power. This connector enables communication with the most common computer systems (AS400, NOVELL, etc.). Figure 4-1 indicates the pin-outs for the SUB-D 15-pin female connector (front view). Figure 4-1 Electrical connections of 15 pin D connector very low safety voltage signals: PIJO PC board 5 operation on inverter NO 8 NC NO contact switching capacities: P = 2.5VA V = 30V max. I = 0.1A max. NC 6 operation on "static bypass" 10 NO 9 NC operation on battery connector SUB-D 15-pin 11 13 NO 7 NC 12 14 4 Figure 4-2 UPS remote shutdown (signal between 3 and 15V DC) 15 pin D connector 8 7 6 5 4 3 15 14 13 12 11 10 86-891000-00 low battery shutdown warning 1 2 9 4—1 EXL 1000 Uninterruptible Power System NOTE The remote UPS shutdown command is valid when the inverter is supplied by the AC input source or the battery. The inverter shuts down after a two minute delay. 4.1 Options Three options may be used simultaneously on the EXL 1000, thus enabling communication with a wide number of computers and control devices. Monitor Plus Monitor Plus is a mini terminal for control and display of AC input power and system parameters. The Monitor Plus can be installed locally or remotely. This option, the U-Talk option and the JBUS option can be used with the battery monitoring function to provide information on available battery power during normal operation and remaining battery power during operation on battery power. Contact 5 This option offers communication of five different signals via dry relay contacts: • operation on battery • operation on "static bypass" • low battery shutdown warning • load supplied by the inverter • general alarm Relay-contact breaking capacities: 250V AC, 125V DC, 1A. 4—2 Communication 86-891000-00 Installation and User’s Manual U-Talk This option manages an RS232 serial interface using an ASCII protocol. This option is supplied with the "Solution Pac"™ CD-ROM which integrates a range of management software for MGE Uninterruptible Power Supplies under SNMP. Like the Monitor Plus and JBUS options, this option can be used with the battery monitoring function to provide information on available battery power during normal operation and remaining battery power during operation on battery power. More complete information on the U-Talk option can be found in chapter 6 of this manual. JBUS/RS232 and JBUS/RS485 These options enable remote monitoring of the EXL 1000. Like the Monitor Plus and U-Talk options, this option can be used with the battery monitoring function to provide information on available battery power during normal operation and remaining battery power during operation on battery power. 86-891000-00 Communication 4—3 EXL 1000 Uninterruptible Power System (this page left blank intentionally) 4—4 Communication 86-891000-00 Maintenance and Service 5.0 Scope Preventive maintenance for the EXL 1000 is limited to the strict minimum. However, this chapter indicates important procedures to ensure continuous and correct operation. WARNING High voltages are present inside the EXL 1000 system. Any servicing requiring removal of the protective covers may be undertaken only by qualified personnel certified by MGE UPS Systems. 5.1 User Preventive User maintenance of the EXL 1000 is limited. The following items may be checked to insure safe, efficient operation. Maintenance Check the installation and operating conditions: 5.2 Maintenance by Certified MGE • Distance from wall • Ventilation inlet and outlet vents unobstructed • Operating temperature, particularly for the batteries • No faults signalled by the LEDs Consult the after-sales support department for further information concerning the services presented below requiring special tools, in particular the "Soft Tunor" software. Representatives 5.2.1 Battery Maintenance Battery status is monitored by EXL 1000 When the orange "operation on battery" light flashes and fault number. “12” is indicated on the diagnostics display, the battery should be checked. When the red "load not protected" light flashes and fault number “15” is indicated on the diagnostics display, a battery fault is present. To clear these alarms, press the "security" and "fault reset" buttons at the same time. 86-891000-00 5—1 EXL 1000 Uninterruptible Power System CAUTION Clearing the alarms by pressing "security" and "fault reset" disables the battery monitoring and backup time calculation functions (Monitor Plus option); contact the after-sales support department to check the condition of the battery and replace it if necessary. The after-sales support technician will reactivate the battery monitoring and backup time calculation functions. 5.2.2 Environmental The battery cells contain substances which are dangerous to the environment. Following replacement, the after-sales support department forwards old batteries to special organizations for recycling and disposal. Protection 5.2.3 Annual Check This complete check-up can be run only by qualified personnel certified by MGE UPS Systems. 5.2.4 Customer Training Training courses are offered by MGE UPS Systems which enable personnel to monitor the system and undertake basic maintenance. Contact your MGE UPS Systems distributor for the list of courses offered. 5.2.5 Maintenance Your MGE UPS Systems contact can supply you with the catalogue of maintenance contracts that indicate how you can transfer responsibility for maintenance to qualified technicians always on call. Contracts 5—2 Maintenance and Service 86-891000-00 Options 6.1 Extended battery cabinet As standard equipment, EXL 1000 comes with an internal 240 volt battery for the 10 kVA EXL 1100 and 180 volts for the 5 kVA EXL 1050 and 7.5 kVA EXL 1075. These provide a backup time (at full rated load and a power factor of 0.6) of 10 minutes for 7.5 kVA and 10 kVA models or 8 minutes for 5 kVA model. The backup time can be increased to 30 minutes or up to 50 minutes for the 7.5 kVA or 10 kVA models, 24 minutes or up to 40 minutes for the 5 kVA model, by the addition of an optional auxiliary battery cabinet. If EXL 1000 was not factory-set for the additional cabinets, the new configuration must be entered by an MGE UPS Systems after-sales support technician. Table 2-1 B a t t e r y c a b i n e t fo r a n ov e r a l l o p e r a t i n g t i m e o f 3 0 m i n u t e s ( 7 . 5 & 1 0 k VA ) o r 2 4 m i n u t e s ( 5 k VA ) a t r a t e d o u t p u t p ow e r w i t h a p ow e r f a c t o r o f 0 . 6 model number of UPS EXL1050 EXL1075 EXL1100 model number EXL 5-24 EXL 7.5-30 EXL10-30 891056 891076 891101 height (in/mm) 28.7/730 35.8/910 35.8/910 width (in/mm) 14.17/360 15.75/400 15.75/400 depth (in/mm) 16.5/420 21.65/550 21.65/550 weight (lb/kg) 147/66 262/118 331/149 part number Battery cabinet dimensions 86-891000-00 6—1 EXL 1000 Uninterruptible Power System Table 2-2 B a t t e r y c a b i n e t fo r a n ov e r a l l o p e r a t i n g t i m e o f 5 0 m i n u t e s ( 7 . 5 & 1 0 k VA ) o r 4 0 m i n u t e s ( 5 k VA ) a t r a t e d o u t p u t p ow e r w i t h a p ow e r f a c t o r o f 0 . 6 model number of UPS EXL1050 EXL1075 EXL1100 model number EXL 5-40 EXL 7.5-50 EXL10-50 891057 891077 891102 height (in/mm) 28.7/730 35.8/910 35.8/910 width (in/mm) 14.17/360 15.75/400 15.75/400 depth (in/mm) 16.5/420 21.65/550 21.65/550 weight (lb/kg) 242/109 477/215 613/276 part number Battery cabinet dimensions 6.2 Connection of Prior to installation of additional battery cabinets, check that the protection devices are in the following positions: an additional battery cabinet • upstream circuit breaker off • input circuit breaker off • battery circuit breaker off • "manual bypass" switch set to the "NORMAL" position Position the battery cabinet on the right side of EXL 1000. Connect the terminal block in the battery cabinet to the XR3 terminal block in EXL 1000 as follows: 6—2 • yellow/green cable (ground) to the yellow/green terminal on XR3 • red cable (+ pole) to the L+ terminal on XR3 • black cable (– pole) to the L– terminal on XR3 • position the two cabinets with the front panels aligned • turn on the circuit breaker in the battery cabinet Options 86-891000-00 Installation and User’s manual Figure 6-1 Connection of an additional battery cabinet ( 5 k VA M o d e l ) C ov e rs R e m ov e d connection terminal blocks of EXL 1000 5kVA battery cabinet terminal block L L+ L L+ flexible conduit from EXL 1000 to battery cabinet Figure 6-2 to a secondary battery cabinet (if available) Connection of an additional battery cabinet ( 7 . 5 & 1 0 k VA M o d e l s ) connection terminal blocks of EXL 1000 7.5 and 10 kVA XR1 Mains XR3 battery battery cabinet terminal block XR2 load XR3 battery L L+ L L+ flexible conduit from EXL 1000 to battery cabinet 86-891000-00 Options to a second battery cabinet (if applicable) 6—3 EXL 1000 Uninterruptible Power System 6.3 Emergency Power Off (EPO) The end user is responsible for the installation of an emergeny power off function. Installation must be carried out in compliance with local code regulations. To power down the entire installation via an emergency power off function, the action should perform the following via a single device: • sever the AC input power to the EXL 1000 • remotely trip off the battery circuit breaker on the EXL 1000 • remotely trip off the circuit breaker for the additional battery cabinet(s), if applicable CAUTION After the EPO function is activated, the UPS output remains live for approximately 3 seconds. 6.4 Battery circuit breaker shunt trip connection 6—4 To accomodate the EPO function, the EXL 1000 UPS and battery cabinets come equipped with battery circuit breakers with shunt trip mechanisms. By applying 24 Vdc or 24 VAC across the shunt trip coil, the circuit breaker will trip off, thereby disconnecting battery input to the inverter. • Check that the upstream circuit breaker on the low voltage switchboard, the input circuit breaker, and the battery circuit breaker are all in "off" position • Remove the connection cover panel from the EXL 1000 • Connect the 24Vdc or 24 VAC output of the EPO circuit to the shunt trip coil across terminals 1 and 4 • Once the connections are made, reposition the connection cover panel and reset all circuit breakers Options 86-891000-00 Installation and User’s Manual Figure 6-3 C o n n e c t i o n d i a g r a m fo r b a t t e r y c i rc u i t b r e a k e r s h u n t t r i p o n t e r m i n a l b l o ck X R 3 EXL 1000 1 4 2 3 not used not used emergency off button + – 24 VDC/VAC Figure 6-4 X R 3 t e r m i n a l b l o ck fo r E X L 1 0 5 0 , E X L 1 0 7 5 a n d E X L 1 1 0 0 battery L– L+ emergency off 1234 Secure the shielding of the cable to the stud provided on the connection cover panel (see appendicies.) 6.5 86-891000-00 Combined options If several option cabinets are combined, they must be placed to the right of the UPS cabinet. • distribution cabinet (including full galvanic isolation transformer) • battery cabinet(s) Options 6—5 EXL 1000 Uninterruptible Power System (this page left blank intentionally) 6—6 Options 86-891000-00 U-Talk 7.1 Introduction This chapter describes all the information you need to install and use your EXL 1000 U-TALK communications system. If you have purchased the UPS Manager 3.0 option, this chapter will give you the information required to install your board (ignore the "EXL 1000 U-TALK protocol" section). Feel free to contact us for any further information you may require concerning special applications beyond the scope of this chapter. 7.1.1 Storage If the U-Talk board must be stored prior to installation, leave your RS232 interface board in its original packaging in a dry location. 7.1.2 Safety If you encounter a problem while following the instructions in this chapter, we recommend that you contact our after-sales support service. On request, our after-sales support personnel can carry out the complete installation of your equipment. Recommendation IMPORTANT Instructions in this chapter must be followed strictly. Not adhering to these instructions may endanger personnel, result in damage to the EXL 1000 and render the manufacturer's warranty void. NOTE All repair or maintenance operations must be carried out by MGE aftersales support personnel. The U-TALK option may be installed and operated by any person as long as the indications presented in this chapter are complied with. 86-891000-00 7—1 EXL 1000 Uninterruptible Power System 7.2 Installation of the The EXL 1000 UPS includes the U-Talk communications board. Installation must be done by the user. U-Talk board 7.2.1 Powering down the EXL 1000 UPS 7.2.2 Installing the U-Talk RS232 board Powering down is necessary to avoid any danger during operations in the boards and/or communication cables area (installation and configuration). • press the "inverter off" button for three seconds • the inverter shuts down if the transfer conditions are correct • the "load protected" light goes off • the "load not protected" light goes on • the load is supplied by the mains via the "static bypass" • switch maintenance bypass switch to “bypass” • turn off input circuit breaker • load is now supplied by the mains via the maintenance bypass switch To locate the EXL 1000 UPSs communications ports for board installation, access the rear panel. The EXL 1000 communications port is located in the rear panel, along the top edge. Two torque screws hold each board or rear cover on. Next, insert the RS232 board into grooves. The EXL 1000 UPS can be equipped with up to three optional boards. It is immaterial which board is in which slot. Figure 7-1 7—2 Inserting the U-Talk board into the groove U-Talk 86-891000-00 Installation and User’s manual 7.2.3 Returning power to The system must be powered up following installation and connection of the RS232 board option and prior to any tests the EXL 1000 UPS Turn the manual bypass switch from the "By-pass" position to the "Normal" position. 7.3 Description of RS232 board O v e r v i ew o f R S 2 3 2 b o a rd XM2 RS 232C B XM1 Figure 7-2 A Close-up of figure 7-2, section A OFF XM5 XM3 ON XM4 D2 D3 Figure 7-3 7.3.1 Function The RS232 communications board enables data concerning EXL 1000’s operating status to be sent to a computer. The system provides a communications channel with an RS232 interface. 7.3.2 Configuring the The D2 and D3 jumpers on the board must be positioned as in figure 7-3. RS232 board 86-891000-00 U-Talk 7—3 EXL 1000 Uninterruptible Power System 7.4 Configuration for When using UPS Manager software, and unless otherwise indicated in the software instruction manual, check that the positions of jumpers D1 to D8 of the RS232 board conform to figure 7-4. UPS Manager software Figure 7-4 Fa c t o r y s e t t i n g s o f U - Ta l k b o a rd j u m p e rs OFF XM5 XM3 ON XM4 D2 D3 D4 D5 D6 D7 Figure 7-5 C o n f i g u r i n g t h e Tr a n s m i s s i o n S p e e d ( fa c t o r y s e t t i n g s s h a d e d ) OFF XM5 OFF XM5 XM3 XM4 ON XM4 D4 D5 D4 D5 ON XM3 1200 bps 2400 bps OFF XM5 OFF XM5 XM3 XM4 ON 4800 bps 7—4 XM4 D4 D5 D4 D5 ON XM3 9600 bps U-Talk 86-891000-00 Installation and User’s Manual Figure 7-6 C o n f i g u r i n g t h e Tr a n s m i s s i o n F o r m a t ( fa c t o r y s e t t i n g s s h a d e d ) OFF XM5 OFF XM5 XM3 ON 8 bits, no parity and 1 stop bit OFF XM4 D6 D7 D7 XM4 D6 ON XM3 8 bits, evenparity and 1 stop bit XM5 OFF XM5 XM3 XM4 ON 7 bits, no parity and 1 stop bit 7.5 86-891000-00 7 bits, even parity and 1 stop bit XM6 XM7 XM6 C o n f i g u r i n g t h e H x a n d I x S i g n a l s F o r m a t ( fa c t o r y s e t t i n g s s h a d e d ) XM7 Figure 7-7 XM4 D6 D7 D6 D7 ON XM3 D8 D1 D8 D1 U-Talk data format The protocol U-TALK used enables reading or writing of physical measurements. The line parameters as well as the inverter’s slave number for the RS232 interface may be configured. For detailed information of the U-Talk protocol, refer to MGE manual "Lazarus U-Talk Protocol," part number 96-153293-00. U-Talk 7—5 EXL 1000 Uninterruptible Power System (this page left blank intentionally) 7—6 U-Talk 86-891000-00 Appendices A.0 General Characteristics EXL 1000 series are two-phase line to line input, two-phase line to line output, Uninterruptible Power Supplies. Each UPS may be configured in a number of ways via a special interface. A modification in the configuration requires on-site servicing by the after-sales support department. Except where indicated, the data provided are typical values corresponding to a rated line to line voltage of 240V at 0.8 power factor load. A.1 Range Characteristics agency standards design: IEC 146 safety: IEC 950 + national deviations EN 50091 - 1 UL 1778 CSA C22.2 protection: IEC 529 (IP 215) electromagnetic compliance: IEC 801 EN 55011 EN 55022 EN 50091-2 FCC VCCI environment conditions 86-891000-00 ambient temperature (1): < 25°C recommended 0°C to 30°C permanent 35°C up to 24 hours 40°C up to 8 hours relative humidity: 5% to 95% maximum altitude without derating: < 3280 ft (1000 m) a—1 EXL 1000 Uninterruptible Power System configuration low battery shutdown warning (minutes): 1, 2, 3, 4, 5, ...20 inverter start-up automatic or manual battery charger: internal or external transfer to bypass outside tolerances: yes / no standard color: RAL 9002 EXL 1050 EXL 1075 EXL 1100 220V, 230V and 240V output: 5 7.5 10 208V output: 4.7 7.1 9.5 200V output: 4.5 6.82 9.1 220V, 230V and 240V output: 4 6 8 208V output: 3.8 5.67 7.56 200V output: 3.6 5.46 7.27 efficiency (%): 91 91 91 heat losses (W): 445 668 890 on RL load: 45 46 46 on RCD load: 50 53 53 battery backup time (minutes) at rated load (power factor 0.6): 8 10 10 maximum leakage current (mA) directly grounded neutral system (TT): 10 23 23 apparent power (kVA): active power (kW): noise level (dBa): a—2 Appendeces 86-891000-00 Installation and User’s manual dimensions and weight EXL 1050 EXL 1075 EXL 1100 height: 28.7 in/730 mm 35.8 in/910 mm 35.8 in/910 mm width: 14.17 in/360 mm 15.75 in/400 mm 15.75 in/400 mm depth: 16.53 in/420 mm 21.65 in/550 mm 21.65 in/550 mm weight: 200 lbs/90 kg 422 lbs/190 kg 466 lbs/210 kg EXL 1050 EXL 1075 EXL 1100 current distortion (%): <6 < 3.5 < 3.5 inrush current: <23 A < 36 A <46 A EXL 1050 EXL 1075 EXL 1100 voltage tolerance (%): ±1.5 ±1 ±1 frequency (Hz): 50 / 60 frequency tolerance (free-running) (%): ± 0.1 frequency tolerance (synchronized) (%): ± 1 / ± 1.5 / ± 2 / ± 3 / ± 4 synchronization rate (Hz/s): 1/2 AC input number of phases: 2 + ground voltage (VAC L-L): 170 to 257 frequency (Hz): 47 to 63 power factor: > 0.99 AC output 86-891000-00 number of phases: 2 + ground voltage (VAC L-L): 208 / 240 Appendeces a—3 EXL 1000 Uninterruptible Power System Table 3-1 M a x i mu m c u r r e n t r a t i n g s absorbed line currents (A) Table 3-2 a—4 Model Number rated output (kVA) AC input current nominal (XR1) AC output current (XR2) battery option (XR3) EXL 1050 5 26 23 30 EXL 1075 7.5 40 35 48 EXL 1100 10 52 46 46 M i n i mu m c a b l e s i z e Model Number rated output (kVA) minimum stranded wire size (75°C) minimum solid wire size (75°C) EXL 1050 5 ≥ AWG 10 (≥ 6 mm2) ≥ AWG 10 (≥ 6 mm2) EXL 1075 7.5 ≥ AWG 8 (≥ 12 mm2) ≥ AWG 8 (≥ 12 mm2) EXL 1100 10 ≥ AWG 6 (≥ 16 mm2) ≥ AWG 6 (≥ 16 mm2) Appendeces 86-891000-00 Glossary backup time battery circuit breaker forced operation forced shutdown the period of time that the EXL 1000 can supply full rated load while running on battery without AC input power. This time will increase with installation of an auxilliary battery cabinet. DC-power circuit breaker that protects the battery circuit. user-initiated connection of the load to the inverter with a 0.5 second interruption in the supply of power. user-initiated shutdown of the inverter because of incorrect AC input characteristics (Mains 1 or Mains 2) and resulting in a 0.5 second interruption in the supply of power. input circuit breaker AC input power circuit breaker enabling rectifier shutdown. inverter module that transforms DC input power to AC output power. low battery shutdown warning signal indicating the upcoming end of battery power and the resulting inverter shutdown and interruption in the supply of power to the load. load all devices connected to EXL 1000 output terminals. LV switchboard low voltage (less than 600 VAC) switchboard. Power panel inside building that includes upstream circuit breakers and provides AC input power to the EXL 1000. manual bypass a manual transfer from inverter to utility power or back via a maintenance bypass switch. This allows for safe servicing of the UPS while maintaining utility power to the load. Mains 1 (AC input power) primary source of power for the rectifier and the inverter. 86-891000-00 output apparent power rated AC output volts multiplied by rated AC output amps, measured in VA output power output apparent power multiplied by power factor measured in Watts. overload power drawn by the load in excess of the EXL 1000 rated output. g—1 EXL 1000 Uninterruptible Power System powered down rated current g—2 no power is present on input and output of EXL 1000 (battery circuit breaker off, upstream circuit breaker off). rated output current of EXL 1000. rectifier electronic device or circuit that converts AC input power to DC power that supplies the inverter module and battery charger. "static bypass" an automatic transfer from inverter to utility power or back without an interruption to output load via an electronic solid state switch (static bypass switch). transfer to bypass load switching from the inverter to the static or manual bypass mechanism. transfer to inverter load switching from the static or manual bypass mechanism to the inverter. Glossary 86-891000-00 Reorder form 1660 Scenic Avenue Costa Mesa, CA 92626 Use this form to order additional copies of this document, or to report any errors, omissions, or other problems you have experienced. NAME ______________________________________________________________________ COMPANY __________________________________________________________________ STREET ADDRESS ___________________________________________________________ CITY __________________________________ STATE ___________ ZIP ______________ I would like to order ________ (quantity @ $50.00 each) additional copies of the: EXL 1000 Uninterruptible Power System Installation and User's Guide 86-891000-00 I would like to report the following problems with this document: ____________________________________________________________________________ ____________________________________________________________________________ ____________________________________________________________________________ ____________________________________________________________________________ ____________________________________________________________________________ ____________________________________________________________________________ ____________________________________________________________________________ ____________________________________________________________________________ Nothing will stop you now ™ 1660 Scenic Avenue, Costa Mesa, California 92626 • (714) 557-1636 • www.mgeups.com