e3 eMerge Access Control System Wiring Diagram

advertisement
e3 eMerge Access Control System Wiring Diagram
Wire Connections for Wiegand
for Level I (controlled) Installations
12V LED BUZZ IN D0 IN D1 OUT D0 OUT D1 GND
RELAY MAX. RATING
24V AC OR DC @ 2A
-
DOOR 4
D0 IN
D1 IN
D0 OUT
D1 OUT
12V
RED
BLK
GRN WHT
2
INPUT
GND
INPUT
AUX IN
GND
AUX IN
D0 IN
D1 IN
D0 OUT
D1 OUT
INPUT
GND
INPUT
+
REX
GND
DOOR
CONTACT
REX
GND
DOOR
CONTACT
-
IN READER OUT READER
AUX INPUT 4
GND
AUX INPUT 3
OUT READER IN READER
SILVER
EARTH
GROUND &
READER
SHIELD LEAD
4
DOOR 3
D9
NO
WHT BLK
SILVER
IN READER
OUT READER
Use UL294 listed Wiegand Reader 12VDC@100mA max.
Twisted shielded 22 AWG (250 ft.) or 18 AWG (500 ft.)
Belden #9535 (5 conductor) or equivalent.
LAN LED
Wire Connections for Door Strikes
DL19
DL18
NC
C
NC
AUX RELAY 4
C
LED BANK
NO
NC
AUX RELAY 3
DL17
DL16
DL15
DL14
DL13
DL12
DL11
DL10
DL9
C
NO
NC
AUX RELAY 2
C
NO
C
NC
DOOR 2 LOCK
TMP TMP +
FLT FLT +
DIODE 1N4933
OR
EQUIVALENT
-
TAMPER
C
+
Micro SD
SLOT
DOOR 1 LOCK
JP1
3
DOOR 2
12V
+
D0 IN
D1 IN
D0 OUT
D1 OUT
INPUT
GND
INPUT
D0 IN
D1 IN
D0 OUT
D1 OUT
INPUT
GND
INPUT
-
AUX IN
GND
AUX IN
DOOR 1
12V
+
Normally Open
Normally Closed
-
Relay Wire Gauge
-
Power system with a Class 2
power supply 12VDC@ 2A
SUPERVISED
Minimum 16AWG
Max wire length 6ft
Resistor Value = 1k Ohm
C
NO
+
+
DC POWER
SUPPLY
-
+
DIODE 1N4933
OR
EQUIVALENT
-
Wire Connections for Inputs
NO
NC
Fail Safe
DC Door Strike
PWR FAULT
+ 12VDC
-
S1
CONTROL PANEL’S
DOOR LOCK RELAY
Fail Secure
DC Door Strike
+
S2
S2: Hardware reset
S1: Factory default
NO
CONTROL PANEL’S
DOOR LOCK RELAY
DC POWER
SUPPLY
RESET
NC
AUX RELAY 1
DL8
DL7
DL6
DL5
DL4
DL3
DL2
DL1
RJ45 Ethernet, note
for UL installations
the maximum length
of cable connection is
30m (98.5 FT).
NC
C
NO
1
NC
C
NO
ETHERNET
NO
UNSUPERVISED
Normally Closed
Normally Open
18
20
1000 ft
600 ft
375 ft
1.00 A
800 ft
500 ft
300 ft
200 ft
2.00 A
400 ft
240 ft
150 ft
60 ft
LED
Condition
➀ DL17
Red On = Power On Middle Board
➁ D9
Red On = Power On Bottom Board
➂ DL1
Blue On = System is Rebooted
DL1 to DL16
Blue On = System is Booting
➃ DL19, DL18 Blue Blink = Network Connection
NOTE: System start up time is approx. 60 secs.
IN READER OUT READER
Attribute
Door Status Inputs
REX Inputs
Auxiliary Inputs
Door Lock Outputs
Aux Outputs
Default State
Normally Open, Unsupervised, 8 Sec. Held Open Time
Normally Open, Momentary, Unsupervised
Normally Open, Unsupervised
Not Energized, Single Pulse, 3 Second Unlock Time
Not Energized, Single Pulse, 3 Seconds On
REX
GND
DOOR
CONTACT
16
1500 ft
AUX INPUT 2
GND
AUX INPUT 1
14
.5 A
REX
GND
DOOR
CONTACT
JP1 - Power Input
Wiring Gauges and Distance
Attribute
Door Status Inputs
REX Inputs
Auxiliary Inputs
Door Lock Outputs
Aux Outputs
GRN
RED
C
DOOR 4 LOCK
Amps @ 12V
12V LED BUZZ IN D0 IN D1 OUT D0 OUT D1 GND
+
12V
NC
DOOR 3 LOCK
NOTE: A green wire
pigtail for earth ground
is provided in all
enclosures. Reader
shields must be
properly grounded per
manufacturers installation requirements
POE
External
+12VDC
(Default)
IN READER OUT READER
Optional Battery Connection
NOTICE
Default State
CERTIFIED
TECHNICIAN
Normally
Open, Unsupervised,
8 Sec. HeldSHOULD
Open Time REPLACE BATTERY EVERY 2 TO 3 YEARS, SEE
INSTRUCTIONS FOR SAFE REPLACEMENT OF BATTERY
NormallyINSTALLATION
Open, Momentary, Unsupervised
REPLACE ONLY WITH 12V 7Ah RATED SEALED LEAD ACID BATTERY
Normally Open, Unsupervised
CHARGE RATE: 650mA. DO NOT EXCEED MANUFACTURER SPECIFICATIONS.
Not Energized, Single Pulse, 3 Second Unlock Time
Not Energized, Single Pulse, 3 Seconds On
SINGLE BATTERY INSTALLATION
DUAL BATTERY INSTALLATION
Connect Batteries in Parallel !!!
BATTERY #1
BATTERY #1
BATTERY #2
NOTE
BEFORE REMOVING POWER,
BACKUP THE SYSTEM DATABASE
OR YOU WILL LOSE CONFIGURATION INFORMATION
NOTICE
THIS UNIT CONTAINS NO USER REPLACEABLE PARTS.
DO NOT ALTER OR TAMPER WITH THIS DEVICE
Contains Class 2 Circuits
Refer to installation manual 620-100531 for additional information
For supplemental manuals and other documentation, visit www.e3links.com
To Power Supervisor &
Battery Charger Module
BLACK
RED
To Power Supervisor &
Battery Charger Module
BLACK
BLACK
RED
RED
Use minimum of 12GA stranded wire
Use insulated terminals on battery terminals
620-100537 A