nt® pressure transducer user guide

advertisement
NT® PRESSURE TRANSDUCER
4000 Series User Guide
ENTEGRIS, INC.
Corporate Headquarters
3500 Lyman Boulevard
Chaska, Minnesota 55318 USA
Customer Service Tel. 763-502-0200
Toll Free 877-503-0200
Customer Service Fax 763-502-0300
www.entegris.com
www.entegrisfluidhandling.com
Entegris ® and Flaretek® are registered trademarks of Entegris, Inc.
NT® is a registered trademark of NT International, an Entegris Company.
© 2004 Entegris, Inc.
Printed in USA
P/N 2283 (Rev C 03/04)
3960-1586MAX0304
The materials integrity management company
NT® PRESSURE TRANSDUCER USER GUIDE
Table of Contents
Introduction .................................. 2
Reference .................................... 13
Nonstandard Product
Configurations ........................... 3
Physical Specifications ............ 13
Electrical Specifications ......... 13
Performance Specifications .... 13
Identifying Nonstandard
Product Configurations .......... 3
Installation .................................... 4
Mechanical Installation ............. 4
Electrical Installation ................ 5
Power Supply Requirements ..... 5
Unit Operation .............................. 7
Operating Environment ............. 7
Process Connections .................. 7
Pressure Transducer
Cover Assembly ....................... 7
Pressure and Temperature
Requirements .......................... 7
Pressure Limits ........................... 8
Pressure Reference
Accuracy .................................. 8
Linear Output Signal ................. 9
Troubleshooting .......................... 10
Maintenance ............................... 11
Certifications .............................. 14
CE Compliance ......................... 14
UL Standard 1604 for Class 1,
Division II Hazardous
Environments ........................ 14
UL Standard 2279 for Class 1,
Zone 0, 1 and 2
Hazardous Locations ............ 14
Ordering Information ................ 15
Model 4100 Single-Port ............ 15
Model 4210 Flow-Through ....... 16
Model 4130 Single-Port ............ 17
Model 4230 Flow-Through ....... 17
Installation Drawings ............... 18
Model 4100 Single-Port ............ 18
Model 4210 Flow-Through ....... 20
Model 4130 Single-Port ............ 22
Model 4230 Flow-Through ....... 23
Repair and Warranty Service .... 24
Zero and Span Adjustment ...... 11
ENTEGRIS, INC.
Customer Service Tel. 763-502-0200 Customer Service Fax 763-502-0300
1
NT® PRESSURE TRANSDUCER USER GUIDE
NT® PRESSURE TRANSDUCER USER GUIDE
Introduction
Nonstandard Product Configurations
This manual is for use with the
following standard NT® Pressure
Transducers 4000 Series Models
4100, 4130, 4210 and 4230. These
instruments have been designed for
use in high purity applications in the
semiconductor industry.
WARNING!
Attempting to install or operate
NT® standard 4000 Series Pressure
Transducers without reviewing the
instructions contained in this
manual could result in personal
injury or equipment damage.
These products feature no moving
parts and no filled cavities, which
reduces the possibility of a contaminated process. The wetted parts of
these nonmetallic transducers are
constructed with PTFE, PFA or other
similar high purity inert materials.
Identifying Nonstandard
Product Configurations
This User Guide applies to product
manufactured as standard NT®
Pressure Transducers, Models 4100,
4130, 4210 and 4230. Entegris
also manufactures nonstandard
product to meet the needs of specific
applications. Nonstandard product
may have different materials of construction, accuracy specifications,
performance and other specifications
that differentiate the nonstandard
product from the standard offering.
Nonstandard flow-through pressure
transducers, Model 4210 product
line, are identified with a “T” followed by a number code.
For example, part number
4210-030G-F02-B06-A-T02
the “T02” designates the product as a
nonstandard product manufactured
to certain specifications designated
under the “T02” code.
NOTE: Nonstandard pressure
transducers may be identified by
the model number found on the
product label. Specifications for
nonstandard pressure transducers
are available by contacting
Entegris.
Cut-away Example:
NT® Single-Port Pressure Transducer
Polypropylene electrical
connector option
Signal conditioning circuit
Nonstandard single-port pressure
transducers, Model 4100 product
line, are identified with a “P” followed by a number code.
Electronic pressure sensor
Solid PTFE
For example, part number:
4100-030G-F02-B06-A-P04
the “P04” designates the product as a
nonstandard product manufactured
to certain specifications designated
under the “P04” code.
Process connection
Cut-away Example:
NT® Flow-Through Pressure Transducer
Polypropylene electrical
connector option
Signal conditioning circuit
Electronic pressure sensor
Solid PTFE
Process connection
2
Customer Service Tel. 763-502-0200 Customer Service Fax 763-502-0300
ENTEGRIS, INC.
ENTEGRIS, INC.
Customer Service Tel. 763-502-0200 Customer Service Fax 763-502-0300
3
NT® PRESSURE TRANSDUCER USER GUIDE
NT® PRESSURE TRANSDUCER USER GUIDE
Installation
CAUTION!
The pressure transducer has
been factory sealed. Do not
attempt to remove the cover
of the pressure transducer.
Any attempt at removal of the
pressure transducer cover will
void the warranty and damage
the unit.
NOTE: NT® Pressure Transducers
for DI water applications, Models
4130 and 4230, are built with
a removable grommet to allow
adjustment of the zero and span
potentiometers.
CAUTION!
Do not tighten the nuts that
protect the process connections
during shipment. Do not tighten
the nuts unless the proper tubing
has been installed. Tightening
these nuts may result in damage
to the pressure transducer process
connections.
4
Electrical Installation
Mechanical Installation
Standard NT® Pressure Transducers
utilize flared tube connections and
must be used with the proper tubing
size and coupling nut.
When installing flared tubing to the
pressure transducer, the flared tube
is pushed over the transducer’s
fitting until the fitting reaches the
smaller tube diameter. The amount
of torque required to tighten the
coupling nut is dependent upon
the size of the fitting.
FITTING SIZE
1/4˝ 3/8˝ 1/2˝ 3/4˝ 1˝
Torque (in•lbs) 5
8
11
14
30
The pressure transducer provides
an analog (0-5 VDC, 0-10 VDC or
4-20 mA) electrical output proportional to the pressure measured.
NOTE: The white wire is not
required for the 4-20 mA output
configuration, please refer to the
wiring diagrams below.
+24 VDC
GND
Pressure transducer
4-20 mA output version
BLACK
Customer Service Tel. 763-502-0200 Customer Service Fax 763-502-0300
ENTEGRIS, INC.
display or
PLC
4-20 mA pressure signal
Pressure Transducer
0-5 VDC, 0-10 VDC output version
WHITE
Care should be taken when installing
flared tubing onto the pressure transducer. Do not use excessive torque or
subject the transducer to high heat
during installation. The transducer
should be firmly mounted to a solid
surface to ensure stability. Verify that
the pressure transducer and the signal cable are free from mechanical
stress or excessive bending from the
surrounding equipment.
no connection
WHITE
RED
voltage pressure signal
RED
display or
PLC
BLACK
Power Supply Requirements
The pressure transducer requires a
12-30 volt DC power supply with less
than 2% ripple at 100 or 120 Hz. The
required power supply voltage varies
with the load resistance (RLoad),
please refer to the formulas on page
6. The power supply must provide
clean power and must be used only
to power similar measurement-type
devices. The power supply must not
be used to power inductive loads,
such as motors, relays or solenoids.
These devices may produce transients that may affect the pressure
transducer measurements when the
inductive device is powered-up or
powered down.
ENTEGRIS, INC.
NOTE: Be sure to ground the
shield of the cable to local ground.
Customer Service Tel. 763-502-0200 Customer Service Fax 763-502-0300
5
NT® PRESSURE TRANSDUCER USER GUIDE
NT® PRESSURE TRANSDUCER USER GUIDE
Figure 1. Power Required for a 4-20 mA Loop
Unit Operation
Operating Environment
850
RLoad (Ohms)
The pressure transducer is to be
mounted in a well vented and controlled environment. Refer to the
Reference section on page 13 for
additional specifications.
Operating
region
Process Connections
To avoid possible pressure leaks,
make sure all process connections
have been performed in accordance
with the Mechanical Installation
guidelines on page 4.
0
Power supply voltage
(VPS)
12
24
29
Load Resistance: Current Output
(4-20 mA Configuration)
Load Resistance: Voltage Output
(0-5, 0-10 VDC)
If a load resistor, RLoad, is used in
series with the current output, the
value of RLoad is dependent on the
supply voltage and the meter resistance and is calculated from the
following formula:
The output impedance is 1k-ohm.
The input impedance should be ≥1
Meg-ohm for ±0.1% load impedance
error.
R Load =
VPS - 12 V
- Rmeter
20 mA
6
= maximum load
resistance (ohms)
VPS
= power supply
voltage (volts)
Rmeter
= meter resistance (ohms)
(theoretically = 0)
Customer Service Tel. 763-502-0200 Customer Service Fax 763-502-0300
Standard NT® Pressure Transducer
covers are factory sealed and should
not be tampered with or opened.
Opening the cover shall void the
product warranty. The NT® Pressure
Transducers for DI water applications, Models 4130 and 4230, are
built with a removable grommet to
allow adjustment of the zero and
span potentiometers.
The minimum pressure required
is atmospheric pressure. The pressure transducer may be damaged if
subjected to vacuum pressure (pressure that is less than atmospheric
pressure).
The pressure transducer is rated for
use with fluids at process temperatures between 50°-149°F (10°-65°C)
under normal operating conditions.
CAUTION!
NT® Pressure Transducers, Models
4100, 4130, 4210 and 4230,
may be damaged if the sensor is
subjected to any level of vacuum
pressure (pressure less than
atmospheric pressure).
CAUTION!
Any attempt to remove or
tamper with the transducer
cover will void the warranty
and damage the unit.
where:
RLoad
Pressure Transducer Cover
Assembly
Pressure and Temperature
Requirements
ENTEGRIS, INC.
ENTEGRIS, INC.
Customer Service Tel. 763-502-0200 Customer Service Fax 763-502-0300
7
NT® PRESSURE TRANSDUCER USER GUIDE
NT® PRESSURE TRANSDUCER USER GUIDE
Pressure Limits
MAX. PRESSURE LIMIT
@ 73°F (23°C)
MAX. PRESSURE LIMIT
@ 149°F (65°C)
0-3 PSIG
5 PSIG (34 kPa)
5 PSIG (34 kPa)
0-6 PSIG
9 PSIG (62 kPa)
9 PSIG (62 kPa)
0-10 PSIG
15 PSIG (103 kPa)
15 PSIG (103 kPa)
0-15 PSIG
25 PSIG (172 kPa)
25 PSIG (172 kPa)
0-30 PSIG
100 PSIG (690 kPa)
100* PSIG (690 kPa)
0-60 PSIG
150 PSIG (1034 kPa)
100* PSIG (690 kPa)
0-100 PSIG
150 PSIG (1034 kPa)
100* PSIG (690 kPa)
0-150 PSIG
190 PSIG (1310 kPa)
N/A
*Maximum limit is 75 PSIG (517 kPa) for
3⁄4˝
and 1˝
Flaretek®
fitting types.
WARNING!
The pressure limits for standard
NT® Pressure Transducers (4000
Series) decrease significantly
for temperatures above 149°F
(65°C). Exceeding these limits
may result in personal injury or
equipment damage. Please
consult the factory.
The output signal of the pressure
transducer is a linear function proportional to the applied pressure.
20 mA
Current output
(mA)
TRANSDUCER RANGE
Linear Output Signal
4 mA
0 PSIG
Full scale
Pressure measurement
10 V
or 5 V
Pressure Reference Accuracy
Voltage output
(V)
The accuracy of the pressure transducer output is ±1% of full scale.
This accuracy includes the effects of
linearity, hysteresis and repeatability, measured at room temperature.
For accuracy specifications for nonstandard product configurations,
please consult the factory.
0V
0 PSIG
Full scale
Pressure measurement
8
Customer Service Tel. 763-502-0200 Customer Service Fax 763-502-0300
ENTEGRIS, INC.
ENTEGRIS, INC.
Customer Service Tel. 763-502-0200 Customer Service Fax 763-502-0300
9
NT® PRESSURE TRANSDUCER USER GUIDE
NT® PRESSURE TRANSDUCER USER GUIDE
Maintenance: (NT ® Pressure Transducers for DI
Water Applications, Models 4130 and 4230 Only)
Troubleshooting
Troubleshooting the NT® Pressure
Transducers (4000 Series) may be
accomplished by measuring the output signal of the pressure transducer
with a battery powered current/
voltage meter. The meter may be
placed in series with the pressure
transducer to measure the current
output or it may be used to directly
measure the voltage output.
Zero and Span Adjustment
Unit Calibration Steps:
1. Remove pressure transducer
from service.
Diagram A
2. Connect the pressure transducer
to a calibrated pressure source.
3. Connect the pressure transducer
to a power source.
Using the battery powered current/
volt meter is an effective method to
determine whether the device or the
on-site data acquisition system is not
functioning properly.
4. Connect the pressure transducer
to a display to monitor the mA or
voltage output.
5. Remove the access grommet, see
Diagram A.
6. Locate the zero and span adjustment screws, see Diagram B.
Diagram B
Span
Pot
10
Customer Service Tel. 763-502-0200 Customer Service Fax 763-502-0300
ENTEGRIS, INC.
ENTEGRIS, INC.
Zero
Pot
Customer Service Tel. 763-502-0200 Customer Service Fax 763-502-0300
11
NT® PRESSURE TRANSDUCER USER GUIDE
7. At ambient pressure (no pressure
applied), rotate the zero adjustment screw (see Diagram C)
clockwise or counterclockwise
until the display reads 4.0 mA or
0 Volts.
NT® PRESSURE TRANSDUCER USER GUIDE
Reference
Diagram C
The following lists the specifications
for the NT® Pressure Transducer
product line. Please consult the
factory for product specifications
manufactured for non-standard
applications.
8. Apply full scale pressure to the
unit, rotate the span adjustment
screw clockwise or counterclockwise until the display reads the
full scale value (i.e., depending
upon configuration: 20.0 mA, 10
Volts or 5 Volts).
NOTE: Specifications are subject to
change without notice. Please
consult the factory for the most
current information.
Physical Specifications
PART
CONSTRUCTION MATERIALS
Wetted parts:
Body:
Sensor interface:
9. To obtain best accuracy, repeat
steps 7 and 8.
10. The calibration procedure is
complete. Reinstall the access
grommet.
O-ring:
Nonwetted parts:
11. Safely vent any applied pressure,
disconnect the display and disconnect the power.
Connection type:
PTFE
CTFE or PFA (Models 4100 and 4210)
PFA (Models 4130 and 4230)
Kalrez® (Models 4100 and 4210)
EPDM (Models 4130 and 4230)
Polypropylene
Polyethylene
PVDF (In addition to materials listed above)
Flared tube, NPT
Electrical Specifications
12. Return the pressure transducer
to service.
Input power:
Pressure signal output ranges:
Electrical connection:
24 VDC (12-30 VDC)
4-20 mA, 0-5 VDC, 0-10 VDC
6´, 12´, 30´ FEP coated pigtail or
polypropylene 3-pin connector
(Models 4100 and 4210)
12´ PVC-jacketed pigtail (Models 4130 and 4230)
Performance Specifications
Reference accuracy:
Process temperature:
12
Customer Service Tel. 763-502-0200 Customer Service Fax 763-502-0300
ENTEGRIS, INC.
ENTEGRIS, INC.
±1% of full scale (includes linearity, hysteresis
and repeatability) at 73°F (23°C)
50° to 149°F (10°C to 65°C)
Customer Service Tel. 763-502-0200 Customer Service Fax 763-502-0300
13
NT® PRESSURE TRANSDUCER USER GUIDE
NT® PRESSURE TRANSDUCER USER GUIDE
Ordering Information
Certifications
CE Compliance
Entegris products have been tested
to various test standards required
by the EMC 89/336/EEC directive.
The results of this testing are on
file at Entegris and are available
upon request.
Please contact the factory for the
latest information. The most current
specifications may be found on
Entegris’ Web site at:
http://www.nt-intl.com/ce_etl-info.cfm.
UL Standard 1604 for
Class 1, Division II Hazardous
Environments
Entegris has tested our standard
products to the UL Standard 1604
for use in Class 1, Division II, Group
A, B, C, D and T6 hazardous environments. The results of this testing are
on file at Entegris and are available
upon request. The products that are
in compliance to this standard are:
Refer to the following for the desired configuration.
The following standard products
have been approved to UL Standard
2279 for use in Class 1, Zone 0, 1 and
2 Hazardous (Classified) Locations:
CODE
PRESSURE RANGE
030G
060G
100G
150G
30 PSIG (207 kPa)
60 PSIG (414 kPa)
100 PSIG (690 kPa)
150 PSIG (F02, F03, F04 types only) (1034 kPa)
•
NT® Single-Port Pressure
Transducer, Model 4100*
•
NT® Flow-Through Pressure
Transducer, Model 4210*
* These products are labeled
“Ex ia IIA T6” and may only be
operated in hazardous locations
with a 12-28 VDC power supply at
ambient to 149°F (65°C) temperatures and installed per applicable
standards.
The above specifications are for
standard production units with
4-20 mA electrical output. All
specifications are subject to change.
Please contact the factory for the
latest information.
NT® Single-Port Pressure
Transducer, Model 4100
•
•
UL Standard 2279 for
Class 1, Zone 0, 1 and 2
Hazardous Environments
NT® Flow-Through Pressure
Transducer, Model 4210
Model 4100 Single-Port Pressure Transducer
Example model number: 4100-100G-F02-D06-A-P1-U1
CODE
INLET/OUTLET PORT CONNECTION
F02
F03
F04
N02
N04
M02
1/4˝ Flaretek®
3/8˝ Flaretek®
1/2˝ Flaretek®
1/4˝ FNPT
1/2˝ FNPT
1/4˝ MNPT
CODE
ELECTRICAL CONNECTOR TYPE
B06
B12
B30
D00
D06
D12
D30
FEP-jacketed 6´ pigtail electrical cable
FEP-jacketed 12´ pigtail electrical cable
FEP-jacketed 30´ pigtail electrical cable
Polypropylene connector (cable not included)
Polypropylene connector and 6´ PVC cable
Polypropylene connector and 12´ PVC cable
Polypropylene connector and 30´ PVC cable
CODE
ELECTRICAL OUTPUTS
A
B
C
4-20 mA (12-30 VDC input)*
0-10 VDC (12-30 VDC input)
0-5 VDC (12-30 VDC input)
CODE
SENSOR INTERFACE
P1
P2
CTFE sensor interface (default)
PFA sensor interface
CODE
PRIMARY/SECONDARY SEAL
U1
U2
U3
S1
S2
S3
Kalrez® 4079 / Viton® (default)
Kalrez® 1050 / Viton®
Kalrez® 6375 UP / Viton®
Kalrez® 4079 / Kalrez® 4079
Kalrez® 1050 / Kalrez® 1050
Kalrez® 6375 UP / Kalrez® 6375 UP
* The 4-20 mA electrical output, rated 12-28 VDC, is also ETL listed for conformance to
UL Standard 2279, Class 1, Zone 0, 1 and 2, Ex ia IIA T6.
14
Customer Service Tel. 763-502-0200 Customer Service Fax 763-502-0300
ENTEGRIS, INC.
ENTEGRIS, INC.
Customer Service Tel. 763-502-0200 Customer Service Fax 763-502-0300
15
NT® PRESSURE TRANSDUCER USER GUIDE
NT® PRESSURE TRANSDUCER USER GUIDE
Model 4210 Flow-Through Pressure Transducer
Example model number: 4210-100G-F02-D06-A-P1-U1
Model 4130 Single-Port Pressure Transducer
Example model number: 4130-100G-F02-A
CODE
PRESSURE RANGE
CODE
PRESSURE RANGE
030G
060G
100G
30 PSIG (207 kPa)
60 PSIG (414 kPa)
100 PSIG (690 kPa)
030G
060G
100G
150G
30 PSIG (207 kPa)
60 PSIG (414 kPa)
100 PSIG (690 kPa)
150 PSIG (F02, F03, F04 types only) (1034 kPa)
CODE
INLET/OUTLET PORT CONNECTION
F02
F03
F04
F06
F08
1/4˝ Flaretek®
3/8˝ Flaretek®
1/2˝ Flaretek®
3/4˝ Flaretek®
1˝ Flaretek® (030G, 060G types only)
CODE
ELECTRICAL CONNECTOR TYPE
B06
B12
B30
D00
D06
D12
D30
FEP-jacketed 6´ pigtail electrical cable
FEP-jacketed 12´ pigtail electrical cable
FEP-jacketed 30´ pigtail electrical cable
Polypropylene connector (cable not included)
Polypropylene connector and 6´ PVC cable
Polypropylene connector and 12´ PVC cable
Polypropylene connector and 30´ PVC cable
CODE
ELECTRICAL OUTPUTS
A
B
C
4-20 mA (12-30 VDC input)*
0-10 VDC (12-30 VDC input)
0-5 VDC (12-30 VDC input)
CODE
SENSOR INTERFACE
P1
P2
CTFE sensor interface (default)
PFA sensor interface
CODE
PRIMARY/SECONDARY SEAL
U1
U2
U3
S1
S2
S3
Kalrez® 4079 / Viton® (default)
Kalrez® 1050 / Viton®
Kalrez® 6375 UP / Viton®
Kalrez® 4079 / Kalrez® 4079
Kalrez® 1050 / Kalrez® 1050
Kalrez® 6375 UP / Kalrez® 6375 UP
CODE
INLET/OUTLET PORT CONNECTION
F02
F03
F04
N02
N04
M02
1/4˝ Flaretek®
3/8˝ Flaretek®
1/2˝ Flaretek®
1/4˝ FNPT
1/2˝ FNPT
1/4˝ MNPT
CODE
ELECTRICAL OUTPUTS
A
B
C
4-20 mA (12-28 VDC input)
0-10 VDC (12-28 VDC input)
0-5 VDC (12-28 VDC input)
Model 4230 Flow-Through Pressure Transducer
Example model number: 4230-100G-F02-A
CODE
PRESSURE RANGE
030G
060G
100G
30 PSIG (207 kPa)
60 PSIG (416 kPa)
100 PSIG (690 kPa)
CODE
INLET/OUTLET PORT CONNECTION
F02
F03
F04
F06
F08
1/4˝ Flaretek®
3/8˝ Flaretek®
1/2˝ Flaretek®
3/4˝ Flaretek®
1˝ Flaretek®
CODE
ELECTRICAL OUTPUTS
A
B
C
4-20 mA (12-28 VDC input)
0-10 VDC (12-28 VDC input)
0-5 VDC (12-28 VDC input)
* The 4-20 mA electrical output, rated 12-28 VDC, is also ETL listed for conformance to
UL Standard 2279, Class 1, Zone 0, 1 and 2, Ex ia IIA T6.
16
Customer Service Tel. 763-502-0200 Customer Service Fax 763-502-0300
ENTEGRIS, INC.
ENTEGRIS, INC.
Customer Service Tel. 763-502-0200 Customer Service Fax 763-502-0300
17
NT® PRESSURE TRANSDUCER USER GUIDE
NT® PRESSURE TRANSDUCER USER GUIDE
Installation Drawings
4100 Single-Port Pressure Transducer with NPT Connection
3 conductor Teflon®-jacketed
cable, pigtail connection (BXX)
(Cable length up to 30 feet)
4100 Single-Port Pressure Transducer with Flared Connection
ELECTRICAL CONNECTOR INFORMATION
4-20 mA
OUTPUT
VERSION
VOLTAGE
OUTPUT
VERSION
Red
24 VDC (+)
4-20 mA
+24 VDC
+12 - +30 VDC
Black
Ground (-)
4-20 mA
Ground
White
Not used
0-5 VDC signal
0-10 VDC signal
WIRE
3 conductor FEP-jacketed cable,
pigtail connection (BXX)
(Cable length up to 30 feet)
ELECTRICAL CONNECTOR INFORMATION
4-20 mA
OUTPUT
VERSION
VOLTAGE
OUTPUT
VERSION
Red
24 VDC (+)
4-20 mA
+24 VDC
+12 - +30 VDC
Black
Ground (-)
4-20 mA
Ground
White
Not used
0-5 VDC signal
0-10 VDC signal
WIRE
1.00˝ (25.4 mm)
1.00” (25.4 mm)
Ø1.88˝ (47.8 mm)
Ø1.88” (47.8 mm)
Dim A
Dim A
Dim B
Dim B
INLET/OUTLET
PORT CONNECTION
DIM A
DIM B
1/4˝ Flaretek®
2.90˝ (73.7 mm)
0.99˝ (25.2 mm)
3/8˝ Flaretek®
2.90˝ (73.7 mm)
1.06˝ (26.9 mm)
1/2˝ Flaretek®
2.90˝ (73.7 mm)
1.14˝ (29.0 mm)
3 conductor connector/cable (DXX)
(Cable length up to 30 feet)
3 conductor connector/cable (DXX)
(Cable length up to 30 feet)
ELECTRICAL CONNECTOR INFORMATION
4-20 mA
OUTPUT
VERSION
VOLTAGE
OUTPUT
VERSION
Black
Ground (-)
4-20 mA
Ground
11
Red
24 VDC (+)
4-20 mA
+24 VDC
+12 - +30 VDC
12
White
Not used
0-5 VDC signal
0-10 VDC signal
PIN
WIRE
10
3.00” (76.2 mm)
3.00˝ (76.2 mm)
Dim A
INLET/OUTLET
PORT CONNECTION
DIM A
DIM B
1/4˝ Flaretek®
2.90˝ (73.7 mm)
0.99˝ (25.2 mm)
3/8˝ Flaretek®
2.90˝ (73.7 mm)
1.06˝ (26.9 mm)
1/2˝ Flaretek®
2.90˝ (73.7 mm)
1.14˝ (29.0 mm)
DIM A
DIM B
1/4˝ NPT MALE
2.90˝ (73.7 mm)
0.59˝ (15.0 mm)
1/4˝ NPT FEMALE
3.24˝ (82.3 mm)
—
1/2˝ NPT FEMALE
3.50˝ (88.9 mm)
—
ELECTRICAL CONNECTOR INFORMATION
4-20 mA
OUTPUT
VERSION
VOLTAGE
OUTPUT
VERSION
PIN
WIRE
10
Black
Ground (-)
4-20 mA
Ground
11
Red
24 VDC (+)
4-20 mA
+24 VDC
+12 - +30 VDC
12
White
Not used
0-5 VDC signal
0-10 VDC signal
Ø1.88˝ (47.8 mm)
Dim A
Ø1.88” (47.8 mm)
INLET/OUTLET
PORT CONNECTION
INLET/OUTLET
PORT CONNECTION
DIM A
DIM B
1/4˝ MNPT
2.90˝ (73.7 mm)
0.59˝ (15.0 mm)
1/4˝ FNPT
3.07˝ (78.0 mm)
—
1/2˝ FNPT
3.33˝ (84.6 mm)
—
Dim B
Dim B
18
Customer Service Tel. 763-502-0200 Customer Service Fax 763-502-0300
ENTEGRIS, INC.
ENTEGRIS, INC.
Customer Service Tel. 763-502-0200 Customer Service Fax 763-502-0300
19
NT® PRESSURE TRANSDUCER USER GUIDE
NT® PRESSURE TRANSDUCER USER GUIDE
4210 Flow-Through Pressure Transducer with Flared Connection
1.75˝ (44.5 mm)
1.75˝
(44.5 mm)
1.75˝ (44.5 mm)
1.75˝ (44.5 mm)
2.36˝ (59.9 mm)
2.36˝ (59.9 mm)
1.86˝ (47.2 mm)
1.86˝ (47.2 mm)
0.20˝ (5.1 mm) (2)
3 conductor connector/cable (DXX)
(Cable length up to 30 feet)
0.20˝ (5.1 mm) (2)
3 conductor FEP-jacketed cable,
pigtail connection (BXX)
(Cable length up to 30 feet)
3.00˝ (76.2 mm)
1.00˝ (25.4 mm)
Dim A
Dim A
0.25˝ (6.4 mm)
Dim C
0.25˝ (6.4 mm)
Dim C
Dim B
Dim B
ELECTRICAL CONNECTOR INFORMATION
4-20 mA
OUTPUT
VERSION
VOLTAGE
OUTPUT
VERSION
ELECTRICAL CONNECTOR INFORMATION
Red
24 VDC (+)
4-20 mA
+24 VDC
+12 - +30 VDC
PIN
WIRE
10
Black
Ground (-)
4-20 mA
Ground
White
Not used
0-5 VDC signal
0-10 VDC signal
WIRE
INLET/OUTLET
PORT CONNECTION
DIM A
DIM B
DIM C
1/4˝ Flaretek®
3.53˝ (89.7 mm)
3.72˝ (94.5 mm)
0.73˝ (18.5 mm)
3/8˝ Flaretek®
3.53˝ (89.7 mm)
3.87˝ (98.3 mm)
0.67˝ (17.0 mm)
1/2˝ Flaretek®
3.78˝ (96.0 mm)
4.03˝ (102.4 mm)
0.85˝ (21.6 mm)
3/4˝ Flaretek®
4.11˝ (104.4 mm)
4.27˝ (108.5 mm)
1.00˝ (25.4 mm)
1˝ Flaretek®
4.43˝ (112.5 mm)
4.75˝ (120.7 mm)
1.20˝ (30.5 mm)
20
Customer Service Tel. 763-502-0200 Customer Service Fax 763-502-0300
ENTEGRIS, INC.
4-20 mA
OUTPUT
VERSION
VOLTAGE
OUTPUT
VERSION
Black
Ground (-)
4-20 mA
Ground
11
Red
24 VDC (+)
4-20 mA
+24 VDC
+12 - +30 VDC
12
White
Not used
0-5 VDC signal
0-10 VDC signal
INLET/OUTLET
PORT CONNECTION
DIM A
DIM B
DIM C
1/4˝ Flaretek®
3.53˝ (89.7 mm)
3.72˝ (94.5 mm)
0.73˝ (18.5 mm)
3/8˝ Flaretek®
3.53˝ (89.7 mm)
3.87˝ (98.3 mm)
0.67˝ (17.0 mm)
1/2˝ Flaretek®
3.78˝ (96.0 mm)
4.03˝ (102.4 mm)
0.85˝ (21.6 mm)
3/4˝ Flaretek®
4.11˝ (104.4 mm)
4.27˝ (108.5 mm)
1.00˝ (25.4 mm)
1˝ Flaretek®
4.43˝ (112.5 mm)
4.75˝ (120.7 mm)
1.20˝ (30.5 mm)
ENTEGRIS, INC.
Customer Service Tel. 763-502-0200 Customer Service Fax 763-502-0300
21
NT® PRESSURE TRANSDUCER USER GUIDE
NT® PRESSURE TRANSDUCER USER GUIDE
4230 Flow-Through Pressure Transducer
4130 Single-Port Pressure Transducer
1.75˝ (44.5 mm)
1.75˝ (44.5 mm)
3 conductor cable
Pigtail connection
2.36˝ (59.9 mm)
2.36˝ (59.9 mm)
1.00˝ (25.4 mm)
0.20˝ (5.1 mm)
Ø1.87˝ (47.5 mm)
S
3 conductor cable
Pigtail connection
(Cable length up to 30 feet)
Z
1.00˝ (25.4 mm)
Dim A
S
Z
Dim A
Dim B
Dim C
ELECTRICAL CONNECTOR INFORMATION
WIRE
Red
Black
White
4-20 mA
OUTPUT
VERSION
VOLTAGE
OUTPUT
VERSION
24 VDC (+)
4-20 mA
+24 VDC
+12 - +30 VDC
Ground (-)
4-20 mA
Not used
Ground
0-5 VDC signal
0-10 VDC signal
Dim B
INLET/OUTLET
PORT CONNECTION
DIM A
DIM B
1/4˝ Flaretek®
3.12˝ (79.2 mm)
0.99˝ (25.2 mm)
3/8˝ Flaretek®
3.12˝ (79.2 mm)
1.06˝ (26.9 mm)
1/2˝ Flaretek®
3.12˝ (79.2 mm)
1.14˝ (29.0 mm)
1/4˝ MNPT
3.12˝ (79.2 mm)
0.59˝ (15.0 mm)
1/4˝ FNPT
3.46˝ (87.9 mm)
—
1/2˝ FNPT
3.72˝ (94.5 mm)
—
ELECTRICAL CONNECTOR INFORMATION
4-20 mA
OUTPUT
VERSION
VOLTAGE
OUTPUT
VERSION
Red
24 VDC (+)
4-20 mA
+24 VDC
+12 - +30 VDC
Black
Ground (-)
4-20 mA
Ground
White
Not used
0-5 VDC signal
0-10 VDC signal
WIRE
INLET/OUTLET
PORT CONNECTION
22
Customer Service Tel. 763-502-0200 Customer Service Fax 763-502-0300
ENTEGRIS, INC.
DIM A
DIM B
DIM C
1/4˝ Flaretek®
3.75˝ (95.3 mm)
3.72˝ (94.5 mm)
0.73˝ (18.5 mm)
3/8˝ Flaretek®
3.75˝ (95.3 mm)
3.87˝ (98.3 mm)
0.67˝ (17.0 mm)
1/2˝ Flaretek®
4.00˝ (101.6 mm)
4.03˝ (102.4 mm)
0.85˝ (21.6 mm)
3/4˝ Flaretek®
4.33˝ (110.0 mm)
4.27˝ (108.5 mm)
1.00˝ (25.4 mm)
1˝ Flaretek®
4.65˝ (118.1 mm)
4.75˝ (120.7 mm)
1.20˝ (30.5 mm)
ENTEGRIS, INC.
Customer Service Tel. 763-502-0200 Customer Service Fax 763-502-0300
23
NT® PRESSURE TRANSDUCER USER GUIDE
Repair and Warranty
Service
Entegris, Inc. warrants each new product
against defects in materials and workmanship for 18 months of time from
shipment. Entegris makes no warranty,
express or implied, with respect to any
components, products, information or
services provided by any third party.
With respect to products specifically
manufactured to Buyer’s specifications,
Entegris warrants only that such products
have been manufactured, without testing,
to Buyer’s specifications but makes no
other warranty, express or implied. Upon
Entegris’ confirmation of defects, Entegris
agrees, as its EXCLUSIVE REMEDY to
repair or, in its discretion, replace defective product without charge. Entegris is
not responsible for product damage
resulting from accident, misuse or lack
of reasonable care. IMPORTANT: NO
OTHER WARRANTY, WRITTEN OR
VERBAL, IS AUTHORIZED BY ENTEGRIS.
ENTEGRIS IS NOT LIABLE FOR ANY
SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES. IMPLIED WARRANTIES
OF MERCHANTABILITY AND FITNESS
FOR A PARTICULAR PURPOSE ARE
SPECIFICALLY DISCLAIMED.
Repair and warranty service is available
at the Entegris factory. To expedite the
return and repair of the product, contact
Entegris at 877-503-0200. A Return
Materials Authorization (RMA) number
and a product packaging and return
procedure will be provided at that time.
WARNING!
All products returned to Entegris
must be accompanied by a list of
all chemicals that have been in
contact with the unit and the
corresponding Material Data
Safety Sheet (MSDS) for each
chemical. Returned products will
not be accepted without an
MSDS.
24
Customer Service Tel. 763-502-0200 Customer Service Fax 763-502-0300
ENTEGRIS, INC.
NT® PRESSURE TRANSDUCER
4000 Series User Guide
ENTEGRIS, INC.
Corporate Headquarters
3500 Lyman Boulevard
Chaska, Minnesota 55318 USA
Customer Service Tel. 763-502-0200
Toll Free 877-503-0200
Customer Service Fax 763-502-0300
www.entegris.com
www.entegrisfluidhandling.com
Entegris ® and Flaretek® are registered trademarks of Entegris, Inc.
NT® is a registered trademark of NT International, an Entegris Company.
© 2004 Entegris, Inc.
Printed in USA
P/N 2283 (Rev C 03/04)
3960-1586MAX-0304
The materials integrity management company