48TF,TM Wiring Schematic - Cul-tech

advertisement
48TF,TM004-014
3 to 121/2 Tons
Gas Heating/Electric Cooling Units
Wiring Diagrams
DIAGRAM INDEX
Unit 48TF,TM
004,005
006
007
008-014
UNIT LABEL DIAGRAM
Type
Schematic/Component Arrangement
Schematic/Component Arrangement
Schematic/Component Arrangement
Schematic/Component Arrangement
Schematic/Component Arrangement
Schematic/Component Arrangement
Schematic/Component Arrangement
Schematic/Component Arrangement
Schematic/Component Arrangement
Schematic/Component Arrangement
Schematic/Component Arrangement
Schematic/Component Arrangement
Schematic/Component Arrangement
Schematic/Component Arrangement
Schematic/Component Arrangement
Schematic/Component Arrangement
Schematic/Component Arrangement
Schematic/Component Arrangement
Voltage-Phase-Hertz
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60*
460-3-60*
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60*
460-3-60*
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
Label Diagram
50DK508460
50DK508515
50DK508518
50DK508522
50DK509082
50DK509084
50DK508514
50DK508516
50DK508519
50DK508522
50DK509083
50DK509085
50DK508517
50DK508520
50DK508523
50DK508790
50DK508791
50DK508792
Figure No.
1
2
3
4
5
6
7
8
9
4
10
11
12
13
14
15
16
17
*Low NOx/California compliant units.
OPTION AND ACCESSORY WIRING
DESCRIPTION
Apollo Controls Wiring Including Indoor Air Quality
Apollo Thermostat Wiring – Typical
Convenience Outlet Schematic
Durablade Economizer Wiring
Differential Enthalpy Control (Durablade)
Solid-State Enthalpy Control (Durablade)
EconoMi$er Wiring
EconoMi$er Dry Bulb Sensor Wiring
EconoMi$er Enthalpy Sensor Wiring
EconoMi$er Power Exhaust Wiring with the Switch in the Actuator
EconoMi$er Power Exhaust Wiring with the Switch Outside the Actuator
EconoMi$er2 Wiring
Differential Enthalpy Wiring (EconoMi$er2)
Fire and Smoke Control Wiring (EconoMi$er2)
Indoor Air Quality Sensor Wiring (EconoMi$er2)
Power Exhaust, 208/230, 575 V Units (Economi$er2)
Power Exhaust for 460 V Units (Economi$er2)
Economi$er2 with PremierLink™ or 4-20 mA Control
Factory-Installed Non-fused Disconnect
Motormaster® I Control Wiring Details
Motormaster II Control Wiring Schematic
Motormaster IV Control Wiring Schematic
Novar Controls Wiring (EMT3051)
Novar Controls Wiring (EMT2024)
PremierLink Controls Wiring
PremierLink Controls Wiring with Dual Terminal Block
PremierLink Controls Wiring with Dual Terminal Block and 62AQ Energy$Recycler
Smoke Detector Shutdown — Single-Phase
Smoke Detector Shutdown — Three-Phase
Time Guard II Device
Two-Position Damper Wiring
Field-Installed 62AQ Energy$Recycler Accessory Wiring (Typical)
48TF,TM UNIT SIZE FIG NO.
004-014
004-007
008-014
004-014
004-014
004-014
004-014
004-014
004-014
004-014
004-014
004-014
004-014
004-014
004-014
004-014
004-014
004-014
004-014
004-014
004-014
004-007
008-014
004-007
008-014
004-014
004-014
004-014
004-014
004-014
004-014
004-014
004-014
004-014
004-014
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
BASE UNIT SERIAL NUMBER FOR
FACTORY-INSTALLED OPTIONS
From 2492Gxxxxx
From 0395Gxxxxx
From 0798Gxxxxx
From 3295Gxxxxx*
From 3295Gxxxxx*
From 3295Gxxxxx*
2099Gxxxxx — 0702Gxxxxx†**
2099Gxxxxx — 0702Gxxxxx
2099Gxxxxx — 0702Gxxxxx
2099Gxxxxx — 4501Gxxxxx
4501Gxxxxx — 0702Gxxxxx
From 0802Gxxxxx**
From 0802Gxxxxx
From 0802Gxxxxx
From 0802Gxxxxx
From 0802Gxxxxx
From 0802Gxxxxx
From 0802Gxxxxx
From 0395Gxxxxx
Accessory Only
From 2900Gxxxxx
From 2900Gxxxxx
From 4601Gxxxxx**
From 4002Gxxxxx**
From 2102Gxxxxx**
From 0802Gxxxxx
From 0802Gxxxxx
Accessory Only
*Durablade Economizer was a factory-installed option (FIOP) until 2/15/02, it is currently available only as a field-installed accessory.
†EconoMi$er wiring in Fig. 25 is generic (for units produced from 5/99 – 2/02) with the exception of the way the power exhaust switch is wired.
Refer to Fig. 28 and 29 for more detailed power exhaust switch information.
**Can be factory-installed or field-installed; wiring is the same for both.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111
Catalog No. 534-80110
Printed in U.S.A.
Form 48T-1W
Pg 1
7-03
Replaces: 48TF-1W
Book 1 4
Tab 1a 6a
SEQUENCE OF OPERATION
After a 30-second delay, the IFM shuts off. If the thermostat
fan selector switch is in the ON position, the IFM will run
continuously.
Cooling, Units Without Economizer — When thermostat calls for cooling, terminals G and Y1 are energized. The
indoor (evaporator) fan contactor (IFC) and compressor
contactor no. 1 (C1) are energized, and evaporator-fan motor
(IFM), compressor no. 1, and condenser fan(s) start. On
2-compressor units, outdoor-fan contactor (OFC) is energized
staring both outdoor fans. The fans continue to run until Y1 is
satisfied. The condenser-fan motor(s) runs continuously while
unit is cooling. For units with 2 stages of cooling, if the
thermostat calls for a second stage of cooling by energizing Y2,
compressor contactor no. 2 (C2) is energized and compressor
no. 2 starts.
Cooling, Units With EconoMi$er2 — When free
cooling is not available, the compressors will be controlled by
the zone thermostat. When free cooling is available, the
outdoor-air damper is positioned through the use of a
Proportional-Integral (PI) control process to provide a 55 F
supply-air temperature into the zone. If the mixed-air temperature is below the lower end of the set point of 50 F, then the
outside-air dampers will modulate to minimum position. If the
measured temperature is within the range of 50 to 56 F, then the
outside dampers will hold their current position. If the mixed
air temperature is above 56 F, then the outside-air dampers will
modulate open until the temperature is within range or they
modulate to the fully open position.
If outdoor air alone cannot satisfy the cooling requirements
of the conditioned space, and the OAT is above the outdoor air
mechanical lockout temperature set point (fixed; opens at 35 F,
closes at 50 F), the EconoMi$er2 integrates free cooling with
mechanical cooling as follows:
Y1 = 1st stage cooling using EconoMi$er2 damper for free
cooling
Y2 = 1st stage cooling using EconoMi$er2 damper for free
cooling plus compressor no. 1
NOTE: During EconoMi$er operation (damper above minimum
position) compressor no. 2 will not operate (sizes 008-014).
High ambient temperature (dry bulb) lockout (fixed): opens
at 76 F, closes at 52 F.
If the enthalpy of the outside air is too high, the outside-air
dampers will modulate to minimum position.
If mechanical cooling is utilized with free cooling, the
outdoor-air damper will be locked into its current position at
the time the compressor is started. If the increase in cooling
capacity causes the supply-air temperature to drop below 45 F,
then the outdoor-air damper position will be decreased to the
minimum position. If the supply temperature continues to fall,
the outdoor-air damper will close.
If optional power exhaust is installed, as the outdoor-air
damper opens and closes, the power exhaust fans will be
energized and deenergized.
If field-installed accessory CO2 sensors are connected to the
EconoMi$er2 control, a PI-controlled demand ventilation
strategy will begin to operate. As the CO2 level in the zone
increases above the CO2 set point, the minimum position of the
damper will be increased proportionally. As the CO2 level
decreases because of the increase in fresh air, the outdoor-air
damper will be proportionally closed.
Heating, Units Without Economizer — When the
thermostat calls for heating, terminal W1 is energized. In order
to prevent thermostat short-cycling, the unit is locked into the
Heating mode for at least 1 minute when W1 is energized. The
induced-draft motor (IDM) is then energized 20 seconds before
the burner ignition sequence begins. The indoor (evaporator)
fan motor (IFM) is energized 45 seconds after a flame is
proven. On units equipped for two stages of heat, when
additional heat is needed, W2 is energized and the high-fire
solenoid on the main gas valve (MGV) is energized. When the
thermostat is satisfied and W1 is deenergized, the IFM stops
after a 45-second time-off delay.
Cooling, Units With Durablade Economizer —
When the outdoor-air temperature is above the OAT (outdoorair thermostat) setting and the room thermostat calls for
cooling, compressor contactor no. 1 is energized to start
compressor no. 1 and the outdoor (condenser) fan motor
(OFM). The indoor (evaporator) fan motor (IFM) is energized
and the economizer damper moves to the minimum position.
Upon a further call for cooling, compressor contactor no. 2 will
be energized, starting compressor no. 2 (sizes 008-014 only).
On 2-compressor units, outdoor-fan contactor (OFC) is energized staring both outdoor fans. The fans continue to run until
Y1 is satisfied. After the thermostat is satisfied, the damper
moves to the fully closed position when using an auto fan or to
the minimum position when using a continuous fan.
When the outdoor-air temperature is below the OAT setting
and the thermostat calls for cooling, the economizer dampers
move to the minimum position. If the supply-air temperature is
above 57 F, the damper continues to open until it reaches the
fully open position or until the supply-air temperature drops
below 52 F.
When the supply-air temperature falls to between 57 F and
52 F, the damper will remain at an intermediate open position.
If the supply-air temperature falls below 52 F, the damper will
modulate closed until it reaches the minimum position or until
the supply-air temperature is above 52 F. When the thermostat
is satisfied and the indoor-fan motor is still in operation, the
damper will move to the minimum open setting. If the thermostat is satisfied and the indoor-fan motor is deenergized, the
damper will move to the fully closed position.
If the outdoor air alone cannot satisfy the cooling requirements of the conditioned space, economizer cooling is integrated
with mechanical cooling, providing second-stage cooling.
Compressor no. 1 and the condenser fan will be energized and
the position of the economizer damper will be determined by the
supply-air temperature. Compressor no. 2 is locked out.
When the second stage of cooling is satisfied, the compressor and OFM will be deenergized. The damper position will be
determined by the supply-air temperature.
Heating, Units With Economizer — When the thermostat calls for heating, terminal W1 is energized. In order to
prevent thermostat short-cycling, the unit is locked into the
Heating mode for at least 1 minute when W1 is energized. The
induced-draft motor is then energized and the burner ignition
sequence begins. The indoor (evaporator) fan motor (IFM) is
energized 45 seconds after a flame is ignited and the damper
moves to the minimum position. On units equipped for two
stages of heat, when additional heat is needed, W2 is energized
and the high-fire solenoid on the main gas valve (MGV) is
energized. When the thermostat is satisfied and W1 is deenergized, the IFM stops after a 45-second time-off delay. The
economizer damper then moves to the fully closed position.
When using continuous fan, the damper will remain in the
minimum position.
2
LEGEND
AHA
C
CAP.
CB
CC
COMP
D
DAT
DX
EC
ECON
EPS
—
—
—
—
—
—
—
—
—
—
—
—
EQUIP —
ER
—
FPT
—
GND
—
HPS
—
HS
—
I
—
IAQ
—
IDM
—
IFC
—
IFM
—
IFMOVL —
IGC
—
LED
—
LPS
—
LS
—
MGV
—
MTR
—
OAT
—
OFC
—
OFM
—
OLR
—
P
—
PL
—
QT
—
Adjustable Heat Anticipator
Contactor, Compressor
Capacitor
Circuit Breaker
Cooling Compensator
Compressor Motor
Diode
Discharge Air Thermistor
Direct Expansion
Enthalpy Control
Economizer
Emergency Power Supply
(Nine-Volt Battery)
Equipment
Economizer Relay
Freeze-Up Protection Thermostat
Ground
High-Pressure Switch
Hall Effect Sensor
Ignitor
Indoor Air Quality
Induced-Draft Motor
Indoor-Fan Contactor
Indoor-Fan Motor
Indoor-Fan Motor Overload
Integrated Gas Unit Controller
Light-Emitting Diode
Low-Pressure Switch
Limit Switch
Main Gas Valve
Motor
Outdoor-Air Thermostat
Outdoor-Fan Contactor
Outdoor-Fan Motor
Overload Relay
Plug
Plug Assembly
Quadruple Terminal
R
RS
SAT
SEN
ST
SW1
SW2
SW3
SW4
TC
TDR
TH
TRAN
VVT
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Relay
Rollout Switch
Supply-Air Thermostat
Sensor
Start Thermistor
Switch Fully Open
Switch Fully Closed
Switch Minimum Vent Position
Switch Maximum Vent Position
Thermostat, Cooling
Time-Delay Relay
Thermostat, Heating
Transformer
Variable Volume/Variable Temperature
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
To indicate common potential only.
Not to represent wiring.
Ground
|(
Capacitor
NOTES FOR FIG. 1, 7
3. Set heat anticipator at .14 amp for units with 2 stages of heating.
Set stage two anticipator at .14 amps.
4. Use copper conductors only.
5. TRAN is wired for 230-v unit. If unit is to be run with 208-v power
supply, disconnect BLK wire from 230-v tap and connect to 208-v
tap (RED). Insulate end of 230-v tap (ORN).
1. If any of the original wire furnished must be replaced, it must be
replaced with Type 90 C wire or its equivalent.
2. Thermostat:
HH07AT170, 172, 174, and P272-2783
Subbase:
HH93AZ176, 178, and P272-1882, 1883
NOTES FOR FIG. 2, 5, 8, 10, 12, 15
1. If any of the original wire furnished must be replaced, it must be
replaced with Type 90 C wire or its equivalent.
2. Three-phase motors are protected under primary single-phasing
conditions.
3. Thermostat:
HH07AT170, 172, 174, and P272-2783
Subbase:
HH93AZ176, 178, and P272-1882, 1883
4. Set heat anticipator at .14 amp for units with 2 stages of heating.
Set stage two anticipator at .14 amps.
5. Use copper conductors only.
6. TRAN is wired for 230-v unit. If unit is to be run with 208-v power
supply, disconnect BLK wire from 230-v tap (ORN) and connect
to 208-v (RED). Insulate end of 230-v tap.
NOTES FOR FIG. 3, 4, 6, 9, 11, 13, 14, 16, 17
1. If any of the original wire furnished must be replaced, it must be
replaced with Type 90 C wire or its equivalent.
2. Three-phase motors are protected under primary single-phasing
conditions.
3. Thermostat:
HH07AT170, 172, 174, and P272-2783
Subbase:
HH93AZ176, 178, and P272-1882, 1883
4. Set heat anticipator at .14 amp for units with 2 stages of heating.
Set stage two anticipator at .14 amps.
5. Use copper conductors only.
3
Fig. 1 — Schematic/Component Arrangement; 48TF,TM004,005; 208/230-1-60
4
Fig. 2 — Schematic/Component Arrangement; 48TF,TM004,005; 208/230-3-60
5
Fig. 3 — Schematic/Component Arrangement; 48TF,TM004,005; 460-3-60
6
Fig. 4 — Schematic/Component Arrangement; 48TF,TM004-006; 575-3-60
7
Fig. 5 — Schematic/Component Arrangement; Low NOx 48TF,TM004,005;
California Compliant 48TF,TM004,005; 208/230-3-60
8
Fig. 6 — Schematic/Component Arrangement; Low NOx 48TF,TM004,005;
California Compliant 48TF,TM004,005; 460-3-60
9
Fig. 7 — Schematic/Component Arrangement; 48TF,TM006; 208/230-1-60
10
Fig. 8 — Schematic/Component Arrangement; 48TF,TM006; 208/230-3-60
11
Fig. 9 — Schematic/Component Arrangement; 48TF,TM006; 460-3-60
12
Fig. 10 — Schematic/Component Arrangement; Low NOx 48TF,TM006;
California Compliant 48TF,TM006; 208/230-3-60
13
Fig. 11 — Schematic/Component Arrangement; Low NOx 48TF,TM006;
California Compliant 48TF,TM006; 460-3-60
14
Fig. 12 — Schematic/Component Arrangement; 48TF,TM007; 208/230-3-60
15
Fig. 13 — Schematic/Component Arrangement; 48TF,TM007; 460-3-60
16
Fig. 14 — Schematic/Component Arrangement; 48TF,TM007; 575-3-60
17
Fig. 15 — Schematic/Component Arrangement; 48TF,TM008-014; 208/230-3-60
18
Fig. 16 — Schematic/Component Arrangement; 48TF,TM008-014; 460-3-60
19
Fig. 17 — Schematic/Component Arrangement; 48TF,TM008-014; 575-3-60
20
21
GRN
BLK
GRN
BLK
See Legend on page 3.
FILTER
STATUS
HUMIDITY
SENSOR
2 1
87654321
BLK
RED
BLK
RED
GRN
#11
#10
#10
#11
NC
COM
NO
OAT
SAT
COOL
2
RELAY
SINGLE ZONE RELAY PACK CIRCUIT BOARD
1
13
12
11
10
9
8
7
4
3
FAN
RV
6
FIELDHEAT
INSTALLED 5
JUMPERS†† 4
3
SINGLE ZONE
2
RELAY PACK
1
WITH AUXILARY
YEL
WHT
BLK
AO
COM
Y1
Y2
G
B1
LED
COM
DAT
COM
REM POT
COM
CO2 COM
CO2+
OAT
COM
OAH
+15V
CLG1
RAT
CLG2
COM
CONTROLLER
RAH
+15V
24 VAC
24 COM
GND
VIO
PNK
TAN
VIO
WHT
RED
DAT
EC
ACCESSORY
ONLY
OAT
GROUND
FAN
HEAT 2
HEAT 1 NC
HEAT 1
HEAT/FAN COM
COOL 2
COOL 1
COOL COM
R
24 VAC/10 VA
C
AUXILIARY
RELAY**
TO CARRIER
HVAC UNIT
FIELD SUPPLIED
WIRING
*Filter status switch and humidity sensor cannot function simultaneously. Only one sensor can be wired.
†Such as a CO2 sensor.
**Set auxiliary option to ‘‘2’’ — IAQ Control per VTS or VVT Installation
Instructions.
††Field-installed Jumpers between 3,4 and 5,7.
NOTE: When single zone relay pack is used on a VVT Monitor Only
System, the monitor thermostat cannot control a damper.
DM
Fig. 18 — Apollo Controls Wiring — Including Indoor-Air Quality
DX
FAN STATUS
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
ALARM
RELAY
CONTACTS
+ 2-10VDC
- SIG COM (J5-3)
+ 4-20mA (J5-2)
WHT
RED
BLU
YEL
GRN
IAQ STATUS†
INDOOR AIR QUALITY (CO2) SENSOR
(33ZCSENCO2) TYPICAL WIRING DIAGRAM
H G 24 VAC
OR
+ - 24 VDC
ADDITIONAL SENSORS*
TSP01
TERMINAL
NUMBER
WHT #1
RED #2
REMOTE ROOM
TEMP. SENSOR
NETWORK
GROUND
24 V
TRAN
24 VAC
20 VA
(FIELD
SUPPLIED)
RED
BRN
GRN
BLU
PNK
ECONOMI$ER OPTION/ACCESSORY
Fig. 19 — Apollo Thermostat Wiring — 48TF,TM004-007 (Typical)
Fig. 20 — Apollo Thermostat Wiring — 48TF,TM008-014 (Typical)
22
Fig. 21 — Convenience Outlet Schematic
Fig. 22 — Durablade Economizer Schematic
23
A
B
TR
C
D SO
TR1
SR
+
2
+
24 VAC SUPPLY FROM
24 VAC SUPPLY FROM
ECONOMIZER CONTROL
SECTION (RED TO TR,
BRN TO TR1)
A
TO SENSOR MOUNTED
ON BACK OF CONTROL
B
S (HH57AC078
+ SENSOR)
3
1
GRAY WIRE FROM
ECONOMIZER HARNESS
TR
TR1
C SO
D
+
SR
+
2
3
CONTROL
} ECONOMIZER
SECTION (RED TO TR,
BRN TO TR1)
SENSOR MOUNTED
} TO
ON BACK OF CONTROL
620 ohm
JUMPER
GRAY WIRE FROM
ECONOMIZER HARNESS
1
LED
LED
RED WIRE FROM
ECONOMIZER SWITCH 3
(NORMALLY CLOSED)
RED WIRE FROM
ECONOMIZER SWITCH 3
(NORMALLY CLOSED)
See Legend on page 3.
NOTE: Switches shown in the high enthalpy state. Terminals 2 and 3 close on enthalpy decrease.
See Legend on page 3.
NOTES:
1. Remove factory-installed jumper across SR and +
before connecting wires from HH57AC078 sensor.
2. Switches shown in high outdoor-air enthalpy state.
Terminals 2 and 3 close on low outdoor air enthalpy
relative to indoor air enthalpy.
Fig. 24 — Wiring Connections for
Solid-State Enthalpy Control
(Durablade Economizer)
Fig. 23 — Wiring Connections for
Differential Enthalpy Control
(Durablade Economizer)
*Wiring is generic for all EconoMi$ers with the exception of the power exhaust switch (if used). Refer to Fig. 28 and 29 for specific power exhaust
switch usage and production dates. See Legend on page 3.
Fig. 25 — EconoMi$er Wiring for Units Produced 5/16/1999 through 2/15/2002*
24
ECONOMI$ER
CONTROLLER
BROWN
VIOLET
OAT
WHITE
RED
COM
OAH
+15 V
RAT
COM
RAH
+15 V
CO2 (+)
CO2 COM
DAT
COM
REM POT
COM
LED
COM
BROWN
VIOLET
WHITE
RED
TEMP
TEMP
COM
OUT
PWR
OUTDOOR
AIR
SENSOR
TEMP
TEMP
COM
OUT
PWR
RETURN
AIR
SENSOR
CO2 SENSOR
24
V+
COM VAC
SUPPLY AIR
TEMPERATURE SENSOR
PINK
TEMP
VIOLET
TEMP
Fig. 26 — EconoMi$er Dry Bulb Sensor Wiring
Fig. 27 — Wiring Diagram for Field-Installed Enthalpy Sensors
25
RED
GRAY
H1
H2
X4
X2 X3
RED YEL BLU GRAY
HT01AH850
(460 VAC)
HT01AH859
(575 VAC)
TO FUSED
DISCONNECT
X1
H1
H3 H2
H4
X4
X2 X3
X1
SECONDARY
230VAC
SECONDARY
230VAC
FIELD SUPPLIED
WIRING
BLACK
BLACK
COMPRESSOR 1
CONTACTOR
OR
11
LT. BLUE
21
230VAC
13
BROWN
23
FAN 1
C1
GREEN/
YELLOW
4-PIN
CONNECTOR
PLUG
2 x 4 IN.
HANDY BOX
BLACK L1
1
BLUE
L2 2
GREEN GND
3
4
3
6
9
2
5
8
1
4
7
B
BLACK
R1
24 VAC
A
BLUE
L1
1
L2
2
GND
3
4
230 VAC
1 PHASE
3-PIN
CONNECTOR
PLUG
ORANGE
1
YELLOW
2
BROWN
BLACK
BLACK
BLUE
LT. BLUE
GREEN
BROWN
FAN 2
3
6
9
2
5
8
1
4
7
B
BLACK
C1
GREEN/
YELLOW
R2
24 VAC
A
BLUE
Fig. 28 — EconoMi$er Power Exhaust with the Switch Inside the Actuator
(Units Produced 5/16/1999 - 11/5/2001)
TOP SWITCH
CAM
POSITION
INDICATOR
TOP
SWITCH
WIRE TIE
ANCHOR HOLE
BOTTOM
SWITCH
CONNECTS TO
2-PIN CONNECTOR
IN ECONOMIZER
2
1
+24 VAC
RED
TOP
SWITCH
NC
NO
COM
COM
RED
BOTTOM
SWITCH
NC
NO
ORANGE
YELLOW
BROWN
1
2
CONNECTS TO THE
3-PIN CONNECTOR
PLUG ON POWER EXHAUST
3
COM
Fig. 29 — EconoMi$er Power Exhaust with Switch Outside of Actuator
(Units Produced 11/5/2001 - 2/15/2002)
26
3
ECONOMISER2 CONTROLLER
ACTUATOR
NOTE 9
RED
24 VAC HOT
BLACK
24 VAC COM
BROWN
BLACK
TR
TAN
RUN
SO
+
SR
+
820 OHM NOTE 6
RESISTOR
VIOLET
NOTE 1
ECONOMIZER
DRY BULB
SENSOR
620 OHM
RESISTOR NOTE 5
BLACK
5
1K
1S
+
WHITE
NOTE 4
+
-
1
2
3
4
T
T1
P
P1
WHITE
Compressor Lockout N.C.
2K
2-10V
OUT
4
BROWN
3
BLACK
GRAY
5
GRAY
BLUE
2
BLUE
YELLOW
8
YELLOW
VIOLET
6
VIOLET
PINK
7
PINK
1
RED
10
WHITE
11
BROWN
9
ORANGE
TR1
NOTE 7
1S1
-
MINIMUM
POSITION
ADJUSTMENT
FREE
COOL
Q
MAXIMUM
POSITION
ADJUSTMENT
AQ
Q1
AQ1
-
SD1
AC
AC1
PG
PG1
HARNESS
AND PLUG NOTE 3
UNIT
CONTROL
EXHAUST
FAN
INDOOR
FAN
12
}
+
SD
2-10 VDC
NOTE 2
CO2 SENSOR
NOTE 8
See Legend on page 3.
NOTES:
1. The standard EconoMi$er2 is shipped with a fixed dry bulb sensor. (Open 67 F — Close 52 F.) An adjustable dry bulb or enthalpy sensor can
replace the fixed dry bulb. (See Note 6.)
2. CO2 sensor is optional. Field-installed accessory. See rooftop price pages for ordering data and pricing. Power for CO2 sensor should be provided by field-supplied transformer.
3. The HVAC unit is shipped with a jumper plug attached to the EconoMi$er2 harness. Remove the jumper plug and save for future use if economizer is removed. Connect the male side of plug (shown above) to the female side in HVAC unit.
4. 1S is an electronic switch that closes when powered by a 24 vac input.
5. Factory-installed 620-ohm, 1 watt, 5% resistor should be removed only when a HH57AC078 enthalpy sensor or CROASENR001A00 adjustable dry bulb is added to SR and + for differential sensing.
6. When replacing the fixed dry bulb sensor with an enthalpy or adjustable dry bulb, remove the 820-ohm resistor.
7. Compressor lockout (Open 35 F — Close 50 F).
8. See EconoMi$er2 Installation Instructions for details on locating and wiring supply air (mixed air) sensor.
9. Switch on actuator must be in run position for economizer to operate.
10. A 2-stage thermostat is recommended.
11. Before troubleshooting wiring, ensure that all the correct sensors have been installed (refer to EconoMi$er2 Installation Instructions).
Fig. 30 — EconoMi$er2 Wiring (For Units Produced 2/18/02 - Present)
ECONOMISER2
CONTROLLER
TAN
VIOLET
SO +
+
S
SR +
TAN
VIOLET
+
S
HH57AC078 ENTHALPY OR
CROASENPOO1A00
ADJUSTABLE
DRY BULB
(NOTE 1)
HH57AC078 DIFFERENTIAL
ENTHALPY OR
CROASENPOO1A00
DIFFERENTIAL
ADJUSTABLE DRY BULB
(NOTE 2)
See Legend on page 3.
NOTES:
1. Violet wire from SO terminal has a factory-installed 820-ohm in-line
resistor. This resistor must be removed when replacing the standard
fixed dry bulb with an optional enthalpy or adjustable dry bulb.
2. The standard economizer has a 620-ohm resistor between terminals SR
and +. This resistor must be removed when adding differential enthalpy
or differential adjustable dry bulb.
Fig. 31 — Differential Enthalpy Wiring for EconoMi$er2
27
ECONOMISER2
ACTUATOR
ECONOMISER2 CONTROLLER
RED
24 VAC HOT
BLACK
24 VAC COM
BROWN
BLACK
TR
TR1
SO
+
4
BROWN
3
BLACK
GRAY
5
GRAY
BLUE
2
BLUE
YELLOW
8
YELLOW
VIOLET
6
VIOLET
PINK
7
PINK
1
RED
10
WHITE
11
BROWN
9
ORANGE
TAN
SR
+
BLACK
820 OHM
RESISTOR
VIOLET
ECONOMISER2
DRY BULB
SENSOR
620 OHM
RESISTOR
5
1K
1S
+
WHITE
+
2
3
4
T
T1
P
P1
WHITE
Compressor Lockout N.C.
2K
2-10V
OUT
-
1
1S1
-
MINIMUM
POSITION
ADJUSTMENT
FREE
COOL
MAXIMUM
POSITION
ADJUSTMENT
Q1
AQ
AQ1
SD
SD1
UNIT
CONTROL
EXHAUST
FAN
INDOOR
FAN
12
FIRE AND SMOKE CONTROL
SHUTDOWN
AC
AC1
PG
PG1
AIR CHANGE
PURGE
Fig. 32 — Fire and Smoke Control Wiring for EconoMi$er2
Fig. 33 — Indoor Air Quality Sensor Wiring for EconoMi$er2
28
}
Q
HARNESS
AND PLUG
TO HVAC UNIT
CONTROL BOX
(SEE NOTE 4)
BLACK
EXH.
FAN #1
BLUE
C2
BLACK
BLACK
BLUE
C1
GREEN - YELLOW
GREEN - YELLOW
GRD.
BLACK
EXH.
FAN #2
POWER LINE
PLUG
1
1
2
2
4
4
GREEN
BROWN
BLACK
RED
3
4
6
7
9
A
BROWN
END
SWITCH
PLUG
B
TAN
OR
3
GRAY
1
2
1
1
2
2
3
3
4
4
ECONOMISER2
CONTROLLER
(SEE NOTE 2)
24 VAC
HOT
24 VAC
COM
GRAY
3
RELAY
1
TAN
3
WHITE
GRD.
BLACK
RED
TO ECONOMISER2
ACTUATOR
(SEE NOTE 2)
TAN
GRAY
(SEE
NOTE 3)
+
EXH FAN
4
FIELD SUPPLIED
2 x 4 JUNCTION BOX
TO 575V POWER
575V
GROUND
PRIMARY
FOR 575-V POWER SUPPLY
FOR 208/230-V SEPARATE
POWER SUPPLY
RED
220V
TRANSFORMER
NO. HT01AH859
BLACK
SECONDARY
FIELD
SUPPLIED
FUSED
DISCONNECT
See Legend on page 3.
NOTES:
1. 575 V transformer No. HT01AH859 is ordered separately from power exhaust.
2. EconoMi$er2 actuator and controller are shipped with the EconoMi$er2 — not with power exhaust.
3. Connections from End Switch plug to the EconoMi$er2 controller are made by installer.
4. If a single power source is to be used, size wire to include power exhaust MCA and MOCP.
Check MCA and MOCP when power exhaust is powered through the unit. Determine the new MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 48TFD006---5 unit with MCA = 28.9 and MOCP = 35, with CRPWREXH030A00 power exhaust.
MCA New = 28.9 amps + 1.6 amps = 30.5 amps
If the new MCA does not go over the MOCP published, then MOCP would not change. The MOCP in this example is 35 amps, the MCA New
is below 35, therefore the MOCP is OK. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate
power, the MOCP for the power exhaust will be 15 amps per NEC.
Fig. 34 — EconoMi$er2 Power Exhaust Wiring — 208/230 V and 575 V Units
29
BL
UE
2
3
1
2
3
4
5
6
4
5
6
7
8
9
7
8
9
B
BLACK
A
POWER
LINE
PLUG
1
2
2
3
3
4
4
ECONOMISER2
CONTROLLER
(NOTE 1)
24V
HOT
END
SWITCH
PLUG
B
WHITE
TAN
BLACK
WHITE
RED
GREEN
A
BLACK
1
WHITE
RELAY #1
RUN TO HVAC UNIT
CONTROL BOX.
(NOTE 3)
TO ECONOMISER2
ACTUATOR
(NOTE 1)
RELAY #2
BLACK
RED
A
L
GRD B
GRAY
GRAY
1
1
2
2
3
3
4
4
24V
COM
GRAY
CK
GRAY
BROWN
BL
UE
BROWN
CK
A
BL
EXH.
FAN #2
TAN
GREEN-YELLOW
GRAY
GRAY
EXH.
FAN #1
GRAY
+
EXH
FAN
(NOTE 2)
1
WHITE
RED
GREEN
OR
1
2
3
4
FIELD SUPPLIED
2 x 4 JUNCTION BOX
GROUND
FIELD
SUPPLIED
FUSED
DISCONNECT
SEPARATE
POWER
SOURCE
See Legend on page 3.
NOTES:
1. EconoMi$er2 actuator and controller are shipped with the EconoMi$er2 — not with power exhaust.
2. Connections from End Switch Plug to the EconoMi$er2 controller are made by installer.
3. If a single power source is to be used, size wire to include power exhaust MCA and MOCP.
Check MCA and MOCP when power exhaust is powered through the unit. Determine the new MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 48TFD006---5 unit with MCA = 28.9 and MOCP = 35, with CRPWREXH030A00 power exhaust.
MCA New = 28.9 amps + 1.6 amps = 30.5 amps
If the new MCA does not go over the MOCP published, then MOCP would not change. The MOCP in this example is 35 amps, the MCA New
is below 35, therefore the MOCP is OK. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate
power, the MOCP for the power exhaust will be 15 amps per NEC.
Fig. 35 — EconoMi$er2 Power Exhaust Wiring — 460 V Units
30
BLACK
4
3
5
BLUE
500 OHM
RESISTOR
8
VIOLET
6
NOTE 1
PINK
7
RUN
RED
+
NOTE 3
2
1
YELLOW
10
50HJ540573
ACTUATOR
ASSEMBLY
OPTIONAL CO 2
SENSOR 4 - 20 mA
OUTPUT
11
9
WHITE
DIRECT DRIVE
ACTUATOR
12
ECONOMISER2 PLUG
See Legend on page 3.
NOTES:
1. Switch on actuator must be in run position for economizer to operate.
2. PremierLink™ control requires that the standard 50HJ540569 outside-air sensor be replaced by either the CROASENR001A00 dry bulb sensor or HH57A077 enthalpy sensor.
3. 50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500-ohm resistor.
Fig. 36 — EconoMi$er2 Wiring (With PremierLink or 4-20 mA Control)
See Legend on page 3.
Fig. 37 — Factory-Installed Non-Fused Disconnect Wiring
31
48TF,TM004-007
48TF,TM008-014
Fig. 38 — Motormaster® I Control Wiring Details
NOTE: Motormaster II transformer is wired for 460-v supply; it must be rewired for 208/230-v application. Be sure to insulate unused tap. Refer to
color code.
Fig. 39 — Motormaster II Control Wiring Schematic Size 004-007 Units
32
NOTE: Motormaster® II transformer is wired for 460-v supply; it must be rewired for 208/230-v application. Be sure to insulate unused tap. Refer to
color code.
Fig. 40 — Motormaster II Control Wiring Schematic Size 008-014 Units
OFM
MM IV
OUTDOOR
FAN
CONTACTOR
OUTDOOR
FAN
CONTACTOR
YEL
23
13
BLK
21
11
1
3
BLK
4
6
YEL
OFM
BRN
BRN
MM IV
BLK
BLK
YEL YEL
BRN
YEL
BLK
H
C
F
BRN
QT CAP 1
Fig. 41 — Motormaster IV Control Wiring
Schematic — Sizes 004-007
Fig. 42 — Motormaster IV Control Wiring
Schematic — Sizes 008-014
33
OFM
Fig. 43 — Novar Controls Wiring, EMT3051
Fig. 44 — Novar Controls Wiring, EMT2024
34
PNK
PNK
7
7
6
6
VIO
OAT
11
10
11
BLK
10
RED
YEL
SAT
8
2
2
3
3
INDOOR AIR
QUALITY SENSOR
WHT
BLK
4
1
1
BLU
RED
ORN
GRA
BLU
5
5
PNK
9
GRA
GRA
ORN
YEL
9
12
J6
PremierLink
L2
ORN
W
WHT
G
L2
5 AMP
FU
R
J5
L2
IFO
RT
RS
CR
RS
LS
BR
FAN
LOGIC
GVR
SAFETY
LOGIC
J4
LS
CS
YEL
GVR
CS
J1
PWR
PNK
WHT
J2
IGC
GAS HEATING UNIT ONLY
YEL
DISCRETE
4
L1
BM
0-20mA IN
8
BLU
BLU
BRN
BLK
BRN
ORN
PNK
VIO
BRN
RED
BLU
ANALOG
OPTIONAL
ACCESSORY
CM
HK50AA039
SPACE TEMP./ SET
POINT ADJUSTMENT
VIO
J2
COMMS
J9
J7
J8
RELAYS
0-20mA PP/MP
GV
GV
HV
TRAN
12
FS
1 2 3
BRN
WHT GRA
PNK
BLK RED
2
TR1
3
RED
PNK
ORN
C
J1
C
ORN
GRA
TR
ORN ORN
BRN
}
WHT
WHT
ORN
IFR
WHT
COMMUNICATIONS
3
GRA
ACCUSENSOR
1
X
LOGIC
FIELD COMMON
2
CLO 1
GRA
P.S.
ECONOMISER2
3
1
X
LOGIC
OFC;C1
2
CLO 2
(004-007)
(008-014)
ORN
P.S.
POWER EXHAUST/ENERGY RECYCLER
5
6
2
4
WHT
BLK
}
ORN
PNK
T
WHT
VIO
}
T
K1 D
R
TIMER
A
VIO
VIO
B
BLK
3
ORN
ORN
IFC
VIO
BLK
1
COOLING
UNIT ONLY
2
TB4
CONNECTION
BOARD
DDC CONTROL
CONNECTION
BOARD
R 24 VAC
G
Y2
W1
THERMOSTAT CONTROL
CONNECTION
BOARD
R
R
RMTOCC
Y1
Y1
CMPSAFE
Y2
Y2
FSD
W1
W1
SFS
W2
W2
NOT USED
G
G
C
C
C
C
X
X
X
RED
R
YEL
Y1
BLU
Y2
9
*
8
6
BLK
ORN
W2
WHT
G
BRN
C
4
MGV
W1
PNK
DEFROST BOARD
OF1
OF2
DR DR
R
BLU
R
7
D1/P
D2
W1/M
C1
W2/H
C2/C
PNK
X
5
BLK
3
ORN
2
GRA
TL
„HP ONLY…
DFT
C
Y
BLU
HR1
O
C
C1 HR1 C2
ORN
3 HR2 1
ORN
C
GAS HEATING UNIT ONLY
C
VIO
*When connecting DDC or thermostat controls, wire to connection board. Do not wire directly to PremierLink™ board.
Fig. 45 — Typical PremierLink Controls Wiring
35
DR
1
W2
C
BLK
RED
PNK
VIO
OAT
VIO
TB - 2
7
6
6
11
11
10
10
HK50AA039
BLU
PNK
7
BRN
1
BLU
2
BRN
VIO
BRN
ORN
J6
ANAL OG
SAT
BLK
RED
BLU
YEL
WHT
2
3
3
4
Indoor Air
Quality Sensor
1
5
5
9
9
12
12
TR
TR1
BRN
5
RED
BRN
BLU
YEL
BLU
6
BRN
7
BLU
8
ORN
WHT
Outdoor Air
Quality Sensor
4
1
4
GRN
8
2
BLK
J4
DISCRETE
BLK
8
J5
0 - 20 mA IN
YEL
BLU
RED
3
PremierLink
PNK
BRN
Space Temp./ Set
Point Adjustment
Power Exhaust/Energy Recycler
PNK
J9
0-20 mA
J2
J1
PWR COMMS
GRA
GRA
J7
PP/MP
J8
Relays
GRA
TB - 3
ORN
RMTOCC
PNK
3
ACCUSENSOR
EconomiSer2
4 - 20mA
PNK
GRN
GRA
WHT GRA
BRN
BLK
TB - 1
1
R
RED
GRA
FSD
3
BLU
2
Y1
SFS
4
WHT
3
Y2
5
PNK
4
W1
ORN
6
RED
5
W2
PNK
7
WHT
6
G
8
BLK
7
C
8
X
GRA
CCN
Comm.
PNK
RED
YEL
GRA
ORN ORN
ORN
RED
2
CMPSAFE
2
1
BRN
ORN
WHT
RTU Terminal
Board
Fig. 46 — PremierLink™ Controls with Dual Terminal Block (Units Produced 10/02 - Present)
Fig. 47 — PremierLink Controls with Dual Terminal Block and 62AQ Energy$Recycler
36
TERMINAL
BOARD
THERMOSTAT
RED
RC
R
SMOKE DETECTOR
NOTE: Break the Red wire from terminal “RC” on thermostat to terminal “R” on the terminal board.
IGC BOARD
BLACK
BM
BLACK
IFM
SMOKE DETECTOR
See Legend on page 3.
NOTE: Break the Black wire from terminal “BM” on the IGC board to the indoor-fan motor (IFM).
Fig. 48 — Smoke Control Unit — Shutdown Wiring
(48HJ004-014 Single-Phase Units)
TERMINAL
BOARD
THERMOSTAT
RED
RC
R
SMOKE DETECTOR
NOTE: Break the Red wire from terminal “RC” on thermostat to terminal “R” on the terminal board.
IGC BOARD
BLACK
IFO
BLACK
SMOKE DETECTOR
See Legend on page 3.
NOTE: Break the Black wire from terminal “IFO” on the IGC board to the “IFC” terminal.
Fig. 49 — Smoke Control Unit — Shutdown Wiring
(48HJ004-014 3-Phase Units)
37
IFC
BRN
BRN
TIME GUARD II
T1
T3
T2
2
3
1
CLO
FROM
THERMOSTAT
“Y1” OR
ECONOMIZER
COMPRESSOR
SAFETIES
C
or
CR
SINGLE COMPRESSOR UNITS
BRN
TIME GUARD II
T1
T3
T2
FROM
THERMOSTAT
“Y2” OR
ECONOMIZER
COMPRESSOR
SAFETIES
DUAL COMPRESSOR UNITS
Fig. 50 — Time Guard II Control Wiring
Fig. 51 — Two-Position Damper Wiring
38
CR
Fig. 52 — Typical Wiring Schematic for 62AQ Energy$Recycler as a Field-Installed Accessory
39
Copyright 2003 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111
Catalog No. 534-80110
Printed in U.S.A.
Form 48T-1W
Pg 40
7-03
Replaces: 48TF-1W
Book 1 4
Tab 1a 6a
Download