48TF,TM004-014 3 to 121/2 Tons Gas Heating/Electric Cooling Units Wiring Diagrams DIAGRAM INDEX Unit 48TF,TM 004,005 006 007 008-014 UNIT LABEL DIAGRAM Type Schematic/Component Arrangement Schematic/Component Arrangement Schematic/Component Arrangement Schematic/Component Arrangement Schematic/Component Arrangement Schematic/Component Arrangement Schematic/Component Arrangement Schematic/Component Arrangement Schematic/Component Arrangement Schematic/Component Arrangement Schematic/Component Arrangement Schematic/Component Arrangement Schematic/Component Arrangement Schematic/Component Arrangement Schematic/Component Arrangement Schematic/Component Arrangement Schematic/Component Arrangement Schematic/Component Arrangement Voltage-Phase-Hertz 208/230-1-60 208/230-3-60 460-3-60 575-3-60 208/230-3-60* 460-3-60* 208/230-1-60 208/230-3-60 460-3-60 575-3-60 208/230-3-60* 460-3-60* 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 Label Diagram 50DK508460 50DK508515 50DK508518 50DK508522 50DK509082 50DK509084 50DK508514 50DK508516 50DK508519 50DK508522 50DK509083 50DK509085 50DK508517 50DK508520 50DK508523 50DK508790 50DK508791 50DK508792 Figure No. 1 2 3 4 5 6 7 8 9 4 10 11 12 13 14 15 16 17 *Low NOx/California compliant units. OPTION AND ACCESSORY WIRING DESCRIPTION Apollo Controls Wiring Including Indoor Air Quality Apollo Thermostat Wiring – Typical Convenience Outlet Schematic Durablade Economizer Wiring Differential Enthalpy Control (Durablade) Solid-State Enthalpy Control (Durablade) EconoMi$er Wiring EconoMi$er Dry Bulb Sensor Wiring EconoMi$er Enthalpy Sensor Wiring EconoMi$er Power Exhaust Wiring with the Switch in the Actuator EconoMi$er Power Exhaust Wiring with the Switch Outside the Actuator EconoMi$er2 Wiring Differential Enthalpy Wiring (EconoMi$er2) Fire and Smoke Control Wiring (EconoMi$er2) Indoor Air Quality Sensor Wiring (EconoMi$er2) Power Exhaust, 208/230, 575 V Units (Economi$er2) Power Exhaust for 460 V Units (Economi$er2) Economi$er2 with PremierLink™ or 4-20 mA Control Factory-Installed Non-fused Disconnect Motormaster® I Control Wiring Details Motormaster II Control Wiring Schematic Motormaster IV Control Wiring Schematic Novar Controls Wiring (EMT3051) Novar Controls Wiring (EMT2024) PremierLink Controls Wiring PremierLink Controls Wiring with Dual Terminal Block PremierLink Controls Wiring with Dual Terminal Block and 62AQ Energy$Recycler Smoke Detector Shutdown — Single-Phase Smoke Detector Shutdown — Three-Phase Time Guard II Device Two-Position Damper Wiring Field-Installed 62AQ Energy$Recycler Accessory Wiring (Typical) 48TF,TM UNIT SIZE FIG NO. 004-014 004-007 008-014 004-014 004-014 004-014 004-014 004-014 004-014 004-014 004-014 004-014 004-014 004-014 004-014 004-014 004-014 004-014 004-014 004-014 004-014 004-007 008-014 004-007 008-014 004-014 004-014 004-014 004-014 004-014 004-014 004-014 004-014 004-014 004-014 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 BASE UNIT SERIAL NUMBER FOR FACTORY-INSTALLED OPTIONS From 2492Gxxxxx From 0395Gxxxxx From 0798Gxxxxx From 3295Gxxxxx* From 3295Gxxxxx* From 3295Gxxxxx* 2099Gxxxxx — 0702Gxxxxx†** 2099Gxxxxx — 0702Gxxxxx 2099Gxxxxx — 0702Gxxxxx 2099Gxxxxx — 4501Gxxxxx 4501Gxxxxx — 0702Gxxxxx From 0802Gxxxxx** From 0802Gxxxxx From 0802Gxxxxx From 0802Gxxxxx From 0802Gxxxxx From 0802Gxxxxx From 0802Gxxxxx From 0395Gxxxxx Accessory Only From 2900Gxxxxx From 2900Gxxxxx From 4601Gxxxxx** From 4002Gxxxxx** From 2102Gxxxxx** From 0802Gxxxxx From 0802Gxxxxx Accessory Only *Durablade Economizer was a factory-installed option (FIOP) until 2/15/02, it is currently available only as a field-installed accessory. †EconoMi$er wiring in Fig. 25 is generic (for units produced from 5/99 – 2/02) with the exception of the way the power exhaust switch is wired. Refer to Fig. 28 and 29 for more detailed power exhaust switch information. **Can be factory-installed or field-installed; wiring is the same for both. Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. PC 111 Catalog No. 534-80110 Printed in U.S.A. Form 48T-1W Pg 1 7-03 Replaces: 48TF-1W Book 1 4 Tab 1a 6a SEQUENCE OF OPERATION After a 30-second delay, the IFM shuts off. If the thermostat fan selector switch is in the ON position, the IFM will run continuously. Cooling, Units Without Economizer — When thermostat calls for cooling, terminals G and Y1 are energized. The indoor (evaporator) fan contactor (IFC) and compressor contactor no. 1 (C1) are energized, and evaporator-fan motor (IFM), compressor no. 1, and condenser fan(s) start. On 2-compressor units, outdoor-fan contactor (OFC) is energized staring both outdoor fans. The fans continue to run until Y1 is satisfied. The condenser-fan motor(s) runs continuously while unit is cooling. For units with 2 stages of cooling, if the thermostat calls for a second stage of cooling by energizing Y2, compressor contactor no. 2 (C2) is energized and compressor no. 2 starts. Cooling, Units With EconoMi$er2 — When free cooling is not available, the compressors will be controlled by the zone thermostat. When free cooling is available, the outdoor-air damper is positioned through the use of a Proportional-Integral (PI) control process to provide a 55 F supply-air temperature into the zone. If the mixed-air temperature is below the lower end of the set point of 50 F, then the outside-air dampers will modulate to minimum position. If the measured temperature is within the range of 50 to 56 F, then the outside dampers will hold their current position. If the mixed air temperature is above 56 F, then the outside-air dampers will modulate open until the temperature is within range or they modulate to the fully open position. If outdoor air alone cannot satisfy the cooling requirements of the conditioned space, and the OAT is above the outdoor air mechanical lockout temperature set point (fixed; opens at 35 F, closes at 50 F), the EconoMi$er2 integrates free cooling with mechanical cooling as follows: Y1 = 1st stage cooling using EconoMi$er2 damper for free cooling Y2 = 1st stage cooling using EconoMi$er2 damper for free cooling plus compressor no. 1 NOTE: During EconoMi$er operation (damper above minimum position) compressor no. 2 will not operate (sizes 008-014). High ambient temperature (dry bulb) lockout (fixed): opens at 76 F, closes at 52 F. If the enthalpy of the outside air is too high, the outside-air dampers will modulate to minimum position. If mechanical cooling is utilized with free cooling, the outdoor-air damper will be locked into its current position at the time the compressor is started. If the increase in cooling capacity causes the supply-air temperature to drop below 45 F, then the outdoor-air damper position will be decreased to the minimum position. If the supply temperature continues to fall, the outdoor-air damper will close. If optional power exhaust is installed, as the outdoor-air damper opens and closes, the power exhaust fans will be energized and deenergized. If field-installed accessory CO2 sensors are connected to the EconoMi$er2 control, a PI-controlled demand ventilation strategy will begin to operate. As the CO2 level in the zone increases above the CO2 set point, the minimum position of the damper will be increased proportionally. As the CO2 level decreases because of the increase in fresh air, the outdoor-air damper will be proportionally closed. Heating, Units Without Economizer — When the thermostat calls for heating, terminal W1 is energized. In order to prevent thermostat short-cycling, the unit is locked into the Heating mode for at least 1 minute when W1 is energized. The induced-draft motor (IDM) is then energized 20 seconds before the burner ignition sequence begins. The indoor (evaporator) fan motor (IFM) is energized 45 seconds after a flame is proven. On units equipped for two stages of heat, when additional heat is needed, W2 is energized and the high-fire solenoid on the main gas valve (MGV) is energized. When the thermostat is satisfied and W1 is deenergized, the IFM stops after a 45-second time-off delay. Cooling, Units With Durablade Economizer — When the outdoor-air temperature is above the OAT (outdoorair thermostat) setting and the room thermostat calls for cooling, compressor contactor no. 1 is energized to start compressor no. 1 and the outdoor (condenser) fan motor (OFM). The indoor (evaporator) fan motor (IFM) is energized and the economizer damper moves to the minimum position. Upon a further call for cooling, compressor contactor no. 2 will be energized, starting compressor no. 2 (sizes 008-014 only). On 2-compressor units, outdoor-fan contactor (OFC) is energized staring both outdoor fans. The fans continue to run until Y1 is satisfied. After the thermostat is satisfied, the damper moves to the fully closed position when using an auto fan or to the minimum position when using a continuous fan. When the outdoor-air temperature is below the OAT setting and the thermostat calls for cooling, the economizer dampers move to the minimum position. If the supply-air temperature is above 57 F, the damper continues to open until it reaches the fully open position or until the supply-air temperature drops below 52 F. When the supply-air temperature falls to between 57 F and 52 F, the damper will remain at an intermediate open position. If the supply-air temperature falls below 52 F, the damper will modulate closed until it reaches the minimum position or until the supply-air temperature is above 52 F. When the thermostat is satisfied and the indoor-fan motor is still in operation, the damper will move to the minimum open setting. If the thermostat is satisfied and the indoor-fan motor is deenergized, the damper will move to the fully closed position. If the outdoor air alone cannot satisfy the cooling requirements of the conditioned space, economizer cooling is integrated with mechanical cooling, providing second-stage cooling. Compressor no. 1 and the condenser fan will be energized and the position of the economizer damper will be determined by the supply-air temperature. Compressor no. 2 is locked out. When the second stage of cooling is satisfied, the compressor and OFM will be deenergized. The damper position will be determined by the supply-air temperature. Heating, Units With Economizer — When the thermostat calls for heating, terminal W1 is energized. In order to prevent thermostat short-cycling, the unit is locked into the Heating mode for at least 1 minute when W1 is energized. The induced-draft motor is then energized and the burner ignition sequence begins. The indoor (evaporator) fan motor (IFM) is energized 45 seconds after a flame is ignited and the damper moves to the minimum position. On units equipped for two stages of heat, when additional heat is needed, W2 is energized and the high-fire solenoid on the main gas valve (MGV) is energized. When the thermostat is satisfied and W1 is deenergized, the IFM stops after a 45-second time-off delay. The economizer damper then moves to the fully closed position. When using continuous fan, the damper will remain in the minimum position. 2 LEGEND AHA C CAP. CB CC COMP D DAT DX EC ECON EPS — — — — — — — — — — — — EQUIP — ER — FPT — GND — HPS — HS — I — IAQ — IDM — IFC — IFM — IFMOVL — IGC — LED — LPS — LS — MGV — MTR — OAT — OFC — OFM — OLR — P — PL — QT — Adjustable Heat Anticipator Contactor, Compressor Capacitor Circuit Breaker Cooling Compensator Compressor Motor Diode Discharge Air Thermistor Direct Expansion Enthalpy Control Economizer Emergency Power Supply (Nine-Volt Battery) Equipment Economizer Relay Freeze-Up Protection Thermostat Ground High-Pressure Switch Hall Effect Sensor Ignitor Indoor Air Quality Induced-Draft Motor Indoor-Fan Contactor Indoor-Fan Motor Indoor-Fan Motor Overload Integrated Gas Unit Controller Light-Emitting Diode Low-Pressure Switch Limit Switch Main Gas Valve Motor Outdoor-Air Thermostat Outdoor-Fan Contactor Outdoor-Fan Motor Overload Relay Plug Plug Assembly Quadruple Terminal R RS SAT SEN ST SW1 SW2 SW3 SW4 TC TDR TH TRAN VVT — — — — — — — — — — — — — — Relay Rollout Switch Supply-Air Thermostat Sensor Start Thermistor Switch Fully Open Switch Fully Closed Switch Minimum Vent Position Switch Maximum Vent Position Thermostat, Cooling Time-Delay Relay Thermostat, Heating Transformer Variable Volume/Variable Temperature Field Splice Marked Wire Terminal (Marked) Terminal (Unmarked) Terminal Block Splice Splice (Marked) Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring To indicate common potential only. Not to represent wiring. Ground |( Capacitor NOTES FOR FIG. 1, 7 3. Set heat anticipator at .14 amp for units with 2 stages of heating. Set stage two anticipator at .14 amps. 4. Use copper conductors only. 5. TRAN is wired for 230-v unit. If unit is to be run with 208-v power supply, disconnect BLK wire from 230-v tap and connect to 208-v tap (RED). Insulate end of 230-v tap (ORN). 1. If any of the original wire furnished must be replaced, it must be replaced with Type 90 C wire or its equivalent. 2. Thermostat: HH07AT170, 172, 174, and P272-2783 Subbase: HH93AZ176, 178, and P272-1882, 1883 NOTES FOR FIG. 2, 5, 8, 10, 12, 15 1. If any of the original wire furnished must be replaced, it must be replaced with Type 90 C wire or its equivalent. 2. Three-phase motors are protected under primary single-phasing conditions. 3. Thermostat: HH07AT170, 172, 174, and P272-2783 Subbase: HH93AZ176, 178, and P272-1882, 1883 4. Set heat anticipator at .14 amp for units with 2 stages of heating. Set stage two anticipator at .14 amps. 5. Use copper conductors only. 6. TRAN is wired for 230-v unit. If unit is to be run with 208-v power supply, disconnect BLK wire from 230-v tap (ORN) and connect to 208-v (RED). Insulate end of 230-v tap. NOTES FOR FIG. 3, 4, 6, 9, 11, 13, 14, 16, 17 1. If any of the original wire furnished must be replaced, it must be replaced with Type 90 C wire or its equivalent. 2. Three-phase motors are protected under primary single-phasing conditions. 3. Thermostat: HH07AT170, 172, 174, and P272-2783 Subbase: HH93AZ176, 178, and P272-1882, 1883 4. Set heat anticipator at .14 amp for units with 2 stages of heating. Set stage two anticipator at .14 amps. 5. Use copper conductors only. 3 Fig. 1 — Schematic/Component Arrangement; 48TF,TM004,005; 208/230-1-60 4 Fig. 2 — Schematic/Component Arrangement; 48TF,TM004,005; 208/230-3-60 5 Fig. 3 — Schematic/Component Arrangement; 48TF,TM004,005; 460-3-60 6 Fig. 4 — Schematic/Component Arrangement; 48TF,TM004-006; 575-3-60 7 Fig. 5 — Schematic/Component Arrangement; Low NOx 48TF,TM004,005; California Compliant 48TF,TM004,005; 208/230-3-60 8 Fig. 6 — Schematic/Component Arrangement; Low NOx 48TF,TM004,005; California Compliant 48TF,TM004,005; 460-3-60 9 Fig. 7 — Schematic/Component Arrangement; 48TF,TM006; 208/230-1-60 10 Fig. 8 — Schematic/Component Arrangement; 48TF,TM006; 208/230-3-60 11 Fig. 9 — Schematic/Component Arrangement; 48TF,TM006; 460-3-60 12 Fig. 10 — Schematic/Component Arrangement; Low NOx 48TF,TM006; California Compliant 48TF,TM006; 208/230-3-60 13 Fig. 11 — Schematic/Component Arrangement; Low NOx 48TF,TM006; California Compliant 48TF,TM006; 460-3-60 14 Fig. 12 — Schematic/Component Arrangement; 48TF,TM007; 208/230-3-60 15 Fig. 13 — Schematic/Component Arrangement; 48TF,TM007; 460-3-60 16 Fig. 14 — Schematic/Component Arrangement; 48TF,TM007; 575-3-60 17 Fig. 15 — Schematic/Component Arrangement; 48TF,TM008-014; 208/230-3-60 18 Fig. 16 — Schematic/Component Arrangement; 48TF,TM008-014; 460-3-60 19 Fig. 17 — Schematic/Component Arrangement; 48TF,TM008-014; 575-3-60 20 21 GRN BLK GRN BLK See Legend on page 3. FILTER STATUS HUMIDITY SENSOR 2 1 87654321 BLK RED BLK RED GRN #11 #10 #10 #11 NC COM NO OAT SAT COOL 2 RELAY SINGLE ZONE RELAY PACK CIRCUIT BOARD 1 13 12 11 10 9 8 7 4 3 FAN RV 6 FIELDHEAT INSTALLED 5 JUMPERS†† 4 3 SINGLE ZONE 2 RELAY PACK 1 WITH AUXILARY YEL WHT BLK AO COM Y1 Y2 G B1 LED COM DAT COM REM POT COM CO2 COM CO2+ OAT COM OAH +15V CLG1 RAT CLG2 COM CONTROLLER RAH +15V 24 VAC 24 COM GND VIO PNK TAN VIO WHT RED DAT EC ACCESSORY ONLY OAT GROUND FAN HEAT 2 HEAT 1 NC HEAT 1 HEAT/FAN COM COOL 2 COOL 1 COOL COM R 24 VAC/10 VA C AUXILIARY RELAY** TO CARRIER HVAC UNIT FIELD SUPPLIED WIRING *Filter status switch and humidity sensor cannot function simultaneously. Only one sensor can be wired. †Such as a CO2 sensor. **Set auxiliary option to ‘‘2’’ — IAQ Control per VTS or VVT Installation Instructions. ††Field-installed Jumpers between 3,4 and 5,7. NOTE: When single zone relay pack is used on a VVT Monitor Only System, the monitor thermostat cannot control a damper. DM Fig. 18 — Apollo Controls Wiring — Including Indoor-Air Quality DX FAN STATUS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 ALARM RELAY CONTACTS + 2-10VDC - SIG COM (J5-3) + 4-20mA (J5-2) WHT RED BLU YEL GRN IAQ STATUS† INDOOR AIR QUALITY (CO2) SENSOR (33ZCSENCO2) TYPICAL WIRING DIAGRAM H G 24 VAC OR + - 24 VDC ADDITIONAL SENSORS* TSP01 TERMINAL NUMBER WHT #1 RED #2 REMOTE ROOM TEMP. SENSOR NETWORK GROUND 24 V TRAN 24 VAC 20 VA (FIELD SUPPLIED) RED BRN GRN BLU PNK ECONOMI$ER OPTION/ACCESSORY Fig. 19 — Apollo Thermostat Wiring — 48TF,TM004-007 (Typical) Fig. 20 — Apollo Thermostat Wiring — 48TF,TM008-014 (Typical) 22 Fig. 21 — Convenience Outlet Schematic Fig. 22 — Durablade Economizer Schematic 23 A B TR C D SO TR1 SR + 2 + 24 VAC SUPPLY FROM 24 VAC SUPPLY FROM ECONOMIZER CONTROL SECTION (RED TO TR, BRN TO TR1) A TO SENSOR MOUNTED ON BACK OF CONTROL B S (HH57AC078 + SENSOR) 3 1 GRAY WIRE FROM ECONOMIZER HARNESS TR TR1 C SO D + SR + 2 3 CONTROL } ECONOMIZER SECTION (RED TO TR, BRN TO TR1) SENSOR MOUNTED } TO ON BACK OF CONTROL 620 ohm JUMPER GRAY WIRE FROM ECONOMIZER HARNESS 1 LED LED RED WIRE FROM ECONOMIZER SWITCH 3 (NORMALLY CLOSED) RED WIRE FROM ECONOMIZER SWITCH 3 (NORMALLY CLOSED) See Legend on page 3. NOTE: Switches shown in the high enthalpy state. Terminals 2 and 3 close on enthalpy decrease. See Legend on page 3. NOTES: 1. Remove factory-installed jumper across SR and + before connecting wires from HH57AC078 sensor. 2. Switches shown in high outdoor-air enthalpy state. Terminals 2 and 3 close on low outdoor air enthalpy relative to indoor air enthalpy. Fig. 24 — Wiring Connections for Solid-State Enthalpy Control (Durablade Economizer) Fig. 23 — Wiring Connections for Differential Enthalpy Control (Durablade Economizer) *Wiring is generic for all EconoMi$ers with the exception of the power exhaust switch (if used). Refer to Fig. 28 and 29 for specific power exhaust switch usage and production dates. See Legend on page 3. Fig. 25 — EconoMi$er Wiring for Units Produced 5/16/1999 through 2/15/2002* 24 ECONOMI$ER CONTROLLER BROWN VIOLET OAT WHITE RED COM OAH +15 V RAT COM RAH +15 V CO2 (+) CO2 COM DAT COM REM POT COM LED COM BROWN VIOLET WHITE RED TEMP TEMP COM OUT PWR OUTDOOR AIR SENSOR TEMP TEMP COM OUT PWR RETURN AIR SENSOR CO2 SENSOR 24 V+ COM VAC SUPPLY AIR TEMPERATURE SENSOR PINK TEMP VIOLET TEMP Fig. 26 — EconoMi$er Dry Bulb Sensor Wiring Fig. 27 — Wiring Diagram for Field-Installed Enthalpy Sensors 25 RED GRAY H1 H2 X4 X2 X3 RED YEL BLU GRAY HT01AH850 (460 VAC) HT01AH859 (575 VAC) TO FUSED DISCONNECT X1 H1 H3 H2 H4 X4 X2 X3 X1 SECONDARY 230VAC SECONDARY 230VAC FIELD SUPPLIED WIRING BLACK BLACK COMPRESSOR 1 CONTACTOR OR 11 LT. BLUE 21 230VAC 13 BROWN 23 FAN 1 C1 GREEN/ YELLOW 4-PIN CONNECTOR PLUG 2 x 4 IN. HANDY BOX BLACK L1 1 BLUE L2 2 GREEN GND 3 4 3 6 9 2 5 8 1 4 7 B BLACK R1 24 VAC A BLUE L1 1 L2 2 GND 3 4 230 VAC 1 PHASE 3-PIN CONNECTOR PLUG ORANGE 1 YELLOW 2 BROWN BLACK BLACK BLUE LT. BLUE GREEN BROWN FAN 2 3 6 9 2 5 8 1 4 7 B BLACK C1 GREEN/ YELLOW R2 24 VAC A BLUE Fig. 28 — EconoMi$er Power Exhaust with the Switch Inside the Actuator (Units Produced 5/16/1999 - 11/5/2001) TOP SWITCH CAM POSITION INDICATOR TOP SWITCH WIRE TIE ANCHOR HOLE BOTTOM SWITCH CONNECTS TO 2-PIN CONNECTOR IN ECONOMIZER 2 1 +24 VAC RED TOP SWITCH NC NO COM COM RED BOTTOM SWITCH NC NO ORANGE YELLOW BROWN 1 2 CONNECTS TO THE 3-PIN CONNECTOR PLUG ON POWER EXHAUST 3 COM Fig. 29 — EconoMi$er Power Exhaust with Switch Outside of Actuator (Units Produced 11/5/2001 - 2/15/2002) 26 3 ECONOMISER2 CONTROLLER ACTUATOR NOTE 9 RED 24 VAC HOT BLACK 24 VAC COM BROWN BLACK TR TAN RUN SO + SR + 820 OHM NOTE 6 RESISTOR VIOLET NOTE 1 ECONOMIZER DRY BULB SENSOR 620 OHM RESISTOR NOTE 5 BLACK 5 1K 1S + WHITE NOTE 4 + - 1 2 3 4 T T1 P P1 WHITE Compressor Lockout N.C. 2K 2-10V OUT 4 BROWN 3 BLACK GRAY 5 GRAY BLUE 2 BLUE YELLOW 8 YELLOW VIOLET 6 VIOLET PINK 7 PINK 1 RED 10 WHITE 11 BROWN 9 ORANGE TR1 NOTE 7 1S1 - MINIMUM POSITION ADJUSTMENT FREE COOL Q MAXIMUM POSITION ADJUSTMENT AQ Q1 AQ1 - SD1 AC AC1 PG PG1 HARNESS AND PLUG NOTE 3 UNIT CONTROL EXHAUST FAN INDOOR FAN 12 } + SD 2-10 VDC NOTE 2 CO2 SENSOR NOTE 8 See Legend on page 3. NOTES: 1. The standard EconoMi$er2 is shipped with a fixed dry bulb sensor. (Open 67 F — Close 52 F.) An adjustable dry bulb or enthalpy sensor can replace the fixed dry bulb. (See Note 6.) 2. CO2 sensor is optional. Field-installed accessory. See rooftop price pages for ordering data and pricing. Power for CO2 sensor should be provided by field-supplied transformer. 3. The HVAC unit is shipped with a jumper plug attached to the EconoMi$er2 harness. Remove the jumper plug and save for future use if economizer is removed. Connect the male side of plug (shown above) to the female side in HVAC unit. 4. 1S is an electronic switch that closes when powered by a 24 vac input. 5. Factory-installed 620-ohm, 1 watt, 5% resistor should be removed only when a HH57AC078 enthalpy sensor or CROASENR001A00 adjustable dry bulb is added to SR and + for differential sensing. 6. When replacing the fixed dry bulb sensor with an enthalpy or adjustable dry bulb, remove the 820-ohm resistor. 7. Compressor lockout (Open 35 F — Close 50 F). 8. See EconoMi$er2 Installation Instructions for details on locating and wiring supply air (mixed air) sensor. 9. Switch on actuator must be in run position for economizer to operate. 10. A 2-stage thermostat is recommended. 11. Before troubleshooting wiring, ensure that all the correct sensors have been installed (refer to EconoMi$er2 Installation Instructions). Fig. 30 — EconoMi$er2 Wiring (For Units Produced 2/18/02 - Present) ECONOMISER2 CONTROLLER TAN VIOLET SO + + S SR + TAN VIOLET + S HH57AC078 ENTHALPY OR CROASENPOO1A00 ADJUSTABLE DRY BULB (NOTE 1) HH57AC078 DIFFERENTIAL ENTHALPY OR CROASENPOO1A00 DIFFERENTIAL ADJUSTABLE DRY BULB (NOTE 2) See Legend on page 3. NOTES: 1. Violet wire from SO terminal has a factory-installed 820-ohm in-line resistor. This resistor must be removed when replacing the standard fixed dry bulb with an optional enthalpy or adjustable dry bulb. 2. The standard economizer has a 620-ohm resistor between terminals SR and +. This resistor must be removed when adding differential enthalpy or differential adjustable dry bulb. Fig. 31 — Differential Enthalpy Wiring for EconoMi$er2 27 ECONOMISER2 ACTUATOR ECONOMISER2 CONTROLLER RED 24 VAC HOT BLACK 24 VAC COM BROWN BLACK TR TR1 SO + 4 BROWN 3 BLACK GRAY 5 GRAY BLUE 2 BLUE YELLOW 8 YELLOW VIOLET 6 VIOLET PINK 7 PINK 1 RED 10 WHITE 11 BROWN 9 ORANGE TAN SR + BLACK 820 OHM RESISTOR VIOLET ECONOMISER2 DRY BULB SENSOR 620 OHM RESISTOR 5 1K 1S + WHITE + 2 3 4 T T1 P P1 WHITE Compressor Lockout N.C. 2K 2-10V OUT - 1 1S1 - MINIMUM POSITION ADJUSTMENT FREE COOL MAXIMUM POSITION ADJUSTMENT Q1 AQ AQ1 SD SD1 UNIT CONTROL EXHAUST FAN INDOOR FAN 12 FIRE AND SMOKE CONTROL SHUTDOWN AC AC1 PG PG1 AIR CHANGE PURGE Fig. 32 — Fire and Smoke Control Wiring for EconoMi$er2 Fig. 33 — Indoor Air Quality Sensor Wiring for EconoMi$er2 28 } Q HARNESS AND PLUG TO HVAC UNIT CONTROL BOX (SEE NOTE 4) BLACK EXH. FAN #1 BLUE C2 BLACK BLACK BLUE C1 GREEN - YELLOW GREEN - YELLOW GRD. BLACK EXH. FAN #2 POWER LINE PLUG 1 1 2 2 4 4 GREEN BROWN BLACK RED 3 4 6 7 9 A BROWN END SWITCH PLUG B TAN OR 3 GRAY 1 2 1 1 2 2 3 3 4 4 ECONOMISER2 CONTROLLER (SEE NOTE 2) 24 VAC HOT 24 VAC COM GRAY 3 RELAY 1 TAN 3 WHITE GRD. BLACK RED TO ECONOMISER2 ACTUATOR (SEE NOTE 2) TAN GRAY (SEE NOTE 3) + EXH FAN 4 FIELD SUPPLIED 2 x 4 JUNCTION BOX TO 575V POWER 575V GROUND PRIMARY FOR 575-V POWER SUPPLY FOR 208/230-V SEPARATE POWER SUPPLY RED 220V TRANSFORMER NO. HT01AH859 BLACK SECONDARY FIELD SUPPLIED FUSED DISCONNECT See Legend on page 3. NOTES: 1. 575 V transformer No. HT01AH859 is ordered separately from power exhaust. 2. EconoMi$er2 actuator and controller are shipped with the EconoMi$er2 — not with power exhaust. 3. Connections from End Switch plug to the EconoMi$er2 controller are made by installer. 4. If a single power source is to be used, size wire to include power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered through the unit. Determine the new MCA including the power exhaust using the following formula: MCA New = MCA unit only + MCA of Power Exhaust For example, using a 48TFD006---5 unit with MCA = 28.9 and MOCP = 35, with CRPWREXH030A00 power exhaust. MCA New = 28.9 amps + 1.6 amps = 30.5 amps If the new MCA does not go over the MOCP published, then MOCP would not change. The MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is OK. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC. Fig. 34 — EconoMi$er2 Power Exhaust Wiring — 208/230 V and 575 V Units 29 BL UE 2 3 1 2 3 4 5 6 4 5 6 7 8 9 7 8 9 B BLACK A POWER LINE PLUG 1 2 2 3 3 4 4 ECONOMISER2 CONTROLLER (NOTE 1) 24V HOT END SWITCH PLUG B WHITE TAN BLACK WHITE RED GREEN A BLACK 1 WHITE RELAY #1 RUN TO HVAC UNIT CONTROL BOX. (NOTE 3) TO ECONOMISER2 ACTUATOR (NOTE 1) RELAY #2 BLACK RED A L GRD B GRAY GRAY 1 1 2 2 3 3 4 4 24V COM GRAY CK GRAY BROWN BL UE BROWN CK A BL EXH. FAN #2 TAN GREEN-YELLOW GRAY GRAY EXH. FAN #1 GRAY + EXH FAN (NOTE 2) 1 WHITE RED GREEN OR 1 2 3 4 FIELD SUPPLIED 2 x 4 JUNCTION BOX GROUND FIELD SUPPLIED FUSED DISCONNECT SEPARATE POWER SOURCE See Legend on page 3. NOTES: 1. EconoMi$er2 actuator and controller are shipped with the EconoMi$er2 — not with power exhaust. 2. Connections from End Switch Plug to the EconoMi$er2 controller are made by installer. 3. If a single power source is to be used, size wire to include power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered through the unit. Determine the new MCA including the power exhaust using the following formula: MCA New = MCA unit only + MCA of Power Exhaust For example, using a 48TFD006---5 unit with MCA = 28.9 and MOCP = 35, with CRPWREXH030A00 power exhaust. MCA New = 28.9 amps + 1.6 amps = 30.5 amps If the new MCA does not go over the MOCP published, then MOCP would not change. The MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is OK. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC. Fig. 35 — EconoMi$er2 Power Exhaust Wiring — 460 V Units 30 BLACK 4 3 5 BLUE 500 OHM RESISTOR 8 VIOLET 6 NOTE 1 PINK 7 RUN RED + NOTE 3 2 1 YELLOW 10 50HJ540573 ACTUATOR ASSEMBLY OPTIONAL CO 2 SENSOR 4 - 20 mA OUTPUT 11 9 WHITE DIRECT DRIVE ACTUATOR 12 ECONOMISER2 PLUG See Legend on page 3. NOTES: 1. Switch on actuator must be in run position for economizer to operate. 2. PremierLink™ control requires that the standard 50HJ540569 outside-air sensor be replaced by either the CROASENR001A00 dry bulb sensor or HH57A077 enthalpy sensor. 3. 50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500-ohm resistor. Fig. 36 — EconoMi$er2 Wiring (With PremierLink or 4-20 mA Control) See Legend on page 3. Fig. 37 — Factory-Installed Non-Fused Disconnect Wiring 31 48TF,TM004-007 48TF,TM008-014 Fig. 38 — Motormaster® I Control Wiring Details NOTE: Motormaster II transformer is wired for 460-v supply; it must be rewired for 208/230-v application. Be sure to insulate unused tap. Refer to color code. Fig. 39 — Motormaster II Control Wiring Schematic Size 004-007 Units 32 NOTE: Motormaster® II transformer is wired for 460-v supply; it must be rewired for 208/230-v application. Be sure to insulate unused tap. Refer to color code. Fig. 40 — Motormaster II Control Wiring Schematic Size 008-014 Units OFM MM IV OUTDOOR FAN CONTACTOR OUTDOOR FAN CONTACTOR YEL 23 13 BLK 21 11 1 3 BLK 4 6 YEL OFM BRN BRN MM IV BLK BLK YEL YEL BRN YEL BLK H C F BRN QT CAP 1 Fig. 41 — Motormaster IV Control Wiring Schematic — Sizes 004-007 Fig. 42 — Motormaster IV Control Wiring Schematic — Sizes 008-014 33 OFM Fig. 43 — Novar Controls Wiring, EMT3051 Fig. 44 — Novar Controls Wiring, EMT2024 34 PNK PNK 7 7 6 6 VIO OAT 11 10 11 BLK 10 RED YEL SAT 8 2 2 3 3 INDOOR AIR QUALITY SENSOR WHT BLK 4 1 1 BLU RED ORN GRA BLU 5 5 PNK 9 GRA GRA ORN YEL 9 12 J6 PremierLink L2 ORN W WHT G L2 5 AMP FU R J5 L2 IFO RT RS CR RS LS BR FAN LOGIC GVR SAFETY LOGIC J4 LS CS YEL GVR CS J1 PWR PNK WHT J2 IGC GAS HEATING UNIT ONLY YEL DISCRETE 4 L1 BM 0-20mA IN 8 BLU BLU BRN BLK BRN ORN PNK VIO BRN RED BLU ANALOG OPTIONAL ACCESSORY CM HK50AA039 SPACE TEMP./ SET POINT ADJUSTMENT VIO J2 COMMS J9 J7 J8 RELAYS 0-20mA PP/MP GV GV HV TRAN 12 FS 1 2 3 BRN WHT GRA PNK BLK RED 2 TR1 3 RED PNK ORN C J1 C ORN GRA TR ORN ORN BRN } WHT WHT ORN IFR WHT COMMUNICATIONS 3 GRA ACCUSENSOR 1 X LOGIC FIELD COMMON 2 CLO 1 GRA P.S. ECONOMISER2 3 1 X LOGIC OFC;C1 2 CLO 2 (004-007) (008-014) ORN P.S. POWER EXHAUST/ENERGY RECYCLER 5 6 2 4 WHT BLK } ORN PNK T WHT VIO } T K1 D R TIMER A VIO VIO B BLK 3 ORN ORN IFC VIO BLK 1 COOLING UNIT ONLY 2 TB4 CONNECTION BOARD DDC CONTROL CONNECTION BOARD R 24 VAC G Y2 W1 THERMOSTAT CONTROL CONNECTION BOARD R R RMTOCC Y1 Y1 CMPSAFE Y2 Y2 FSD W1 W1 SFS W2 W2 NOT USED G G C C C C X X X RED R YEL Y1 BLU Y2 9 * 8 6 BLK ORN W2 WHT G BRN C 4 MGV W1 PNK DEFROST BOARD OF1 OF2 DR DR R BLU R 7 D1/P D2 W1/M C1 W2/H C2/C PNK X 5 BLK 3 ORN 2 GRA TL „HP ONLY… DFT C Y BLU HR1 O C C1 HR1 C2 ORN 3 HR2 1 ORN C GAS HEATING UNIT ONLY C VIO *When connecting DDC or thermostat controls, wire to connection board. Do not wire directly to PremierLink™ board. Fig. 45 — Typical PremierLink Controls Wiring 35 DR 1 W2 C BLK RED PNK VIO OAT VIO TB - 2 7 6 6 11 11 10 10 HK50AA039 BLU PNK 7 BRN 1 BLU 2 BRN VIO BRN ORN J6 ANAL OG SAT BLK RED BLU YEL WHT 2 3 3 4 Indoor Air Quality Sensor 1 5 5 9 9 12 12 TR TR1 BRN 5 RED BRN BLU YEL BLU 6 BRN 7 BLU 8 ORN WHT Outdoor Air Quality Sensor 4 1 4 GRN 8 2 BLK J4 DISCRETE BLK 8 J5 0 - 20 mA IN YEL BLU RED 3 PremierLink PNK BRN Space Temp./ Set Point Adjustment Power Exhaust/Energy Recycler PNK J9 0-20 mA J2 J1 PWR COMMS GRA GRA J7 PP/MP J8 Relays GRA TB - 3 ORN RMTOCC PNK 3 ACCUSENSOR EconomiSer2 4 - 20mA PNK GRN GRA WHT GRA BRN BLK TB - 1 1 R RED GRA FSD 3 BLU 2 Y1 SFS 4 WHT 3 Y2 5 PNK 4 W1 ORN 6 RED 5 W2 PNK 7 WHT 6 G 8 BLK 7 C 8 X GRA CCN Comm. PNK RED YEL GRA ORN ORN ORN RED 2 CMPSAFE 2 1 BRN ORN WHT RTU Terminal Board Fig. 46 — PremierLink™ Controls with Dual Terminal Block (Units Produced 10/02 - Present) Fig. 47 — PremierLink Controls with Dual Terminal Block and 62AQ Energy$Recycler 36 TERMINAL BOARD THERMOSTAT RED RC R SMOKE DETECTOR NOTE: Break the Red wire from terminal “RC” on thermostat to terminal “R” on the terminal board. IGC BOARD BLACK BM BLACK IFM SMOKE DETECTOR See Legend on page 3. NOTE: Break the Black wire from terminal “BM” on the IGC board to the indoor-fan motor (IFM). Fig. 48 — Smoke Control Unit — Shutdown Wiring (48HJ004-014 Single-Phase Units) TERMINAL BOARD THERMOSTAT RED RC R SMOKE DETECTOR NOTE: Break the Red wire from terminal “RC” on thermostat to terminal “R” on the terminal board. IGC BOARD BLACK IFO BLACK SMOKE DETECTOR See Legend on page 3. NOTE: Break the Black wire from terminal “IFO” on the IGC board to the “IFC” terminal. Fig. 49 — Smoke Control Unit — Shutdown Wiring (48HJ004-014 3-Phase Units) 37 IFC BRN BRN TIME GUARD II T1 T3 T2 2 3 1 CLO FROM THERMOSTAT “Y1” OR ECONOMIZER COMPRESSOR SAFETIES C or CR SINGLE COMPRESSOR UNITS BRN TIME GUARD II T1 T3 T2 FROM THERMOSTAT “Y2” OR ECONOMIZER COMPRESSOR SAFETIES DUAL COMPRESSOR UNITS Fig. 50 — Time Guard II Control Wiring Fig. 51 — Two-Position Damper Wiring 38 CR Fig. 52 — Typical Wiring Schematic for 62AQ Energy$Recycler as a Field-Installed Accessory 39 Copyright 2003 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. PC 111 Catalog No. 534-80110 Printed in U.S.A. Form 48T-1W Pg 40 7-03 Replaces: 48TF-1W Book 1 4 Tab 1a 6a