Introduction A power system can be subdivided into three major parts before supplying electrical energy to consumers : • Generation • Transmission and Subtransmission • Distribution A generation of electric power is done by using a generators where one of the essential components of power systems is the three phase ac generator known as synchronous generator or alternator ac generators can generate high power at high voltage. typically 30 kV the size of generators can vary from 50 MW to 1500 MW. In a power station several generators are operated in parallel in the power grid to provide the total power needed. They are connected at a common point called a bus. After the electric power is generated by a generators a step-up transformers are used for transmission of power to reduce the power losses . These transformers connecting to the transmission network is used to transfer electric energy from generating units at various locations to the distribution system which ultimately supplies the load .Transmission voltage lines operating at more than 60kV are standardized at 69 kV, 115 kV, 138 kV, 161 kV, 230 kV,345 kV, 500 kV, and 765 kV line-to-line. Transmission voltages above 230 kV are usually referred to as extra-high voltage (EHV). At the receiving end of the transmission lines step-down transformers are used to reduce the voltage to suitable values for distribution or utilization. The distribution system is that part which connects the distribution substations to the consumers ' service entrance equipment. Loads of power systems are divided into industrial, commercial, and residential. In addition to generators, transformers, and transmission lines, other devices are required for the satisfactory operation and protection of a power system. Some of the protective devices directly connected to the circuits are called switchgear. They include instrument transformers, circuit breakers, disconnect switches, fuses and lightning arresters. These devices are necessary to deenergize either for normal operation or on the occurrence of faults. The associated control equipment and protective relays are placed on switchboard in control houses. For a power system to be practical it must be safe, reliable, and economical. Thus many analyses must be performed to design and operate an electrical system. However, before going into system analysis we have to model all components of electrical power systems Power system representation The complete circuit diagram for a three phase system is seldom necessary to convey even the most detailed information about a system. Therefore the interconnection among the components of the power system may be shown in a simplified diagram is called a single line diagram. Single line diagram A single-line diagram of a power system shows the main connections and arrangements of components . Power system networks are represented by single-line diagrams using suitable symbols as shown below : The impedance diagram on single-phase basis for use under balanced operating conditions can be easily drawn from the single-line diagram such as shown The impedance diagram can be abbreviated to reactance diagram when the resistances and capacitors are neglected. The per unit quantities (pu) Because of the large amount of power transmitted , kilowatts or megawatts and kilovolt-ampere or megavolt-ampere are the common terms. However, these quantities as well as amperes and ohms are often expressed as a percent or per unit of a base or reference value specified for each. In the per-unit system, all quantities are represented as a fraction of the base value: actualvalue Quantityin per unit basevalueof quantity For example V(pu) = actual value of voltage (v) base value of voltage (v) I(pu) = actual value of current (A) base value of current (A) Z(pu) = S(pu) = actual value of impedance(Ω) base value of impedance(Ω) actual value of appearant power(VA) base value of appearant power(VA) If any two of the four base quantities are specified, the other base values can be calculated. Usually, base apparent power and base voltage are specified at a point in the circuit, and the other values are calculated from them. The base voltage varies by the voltage ratio of each transformer in the circuit but the base apparent power stays the same through the circuit. Real power systems are convenient to analyze using their per-phase (since the system is three-phase) per-unit (since there are many transformers) equivalent circuits. The per-phase base voltage, current, apparent power, and impedance are I base S1 ,base VLN ,base Zbase VLN ,base I base V LN ,base 2 S1 ,base Where VLN,base is the line-to-neutral base voltage in the three-phase circuit S1,base is the base apparent power of a single phase in the circuit. The base current and impedance in a per-unit system can also be expressed in terms of the three-phase apparent power (which is 3 times the apparent power of a single phase) and line-to-line voltages (which is √3 times the lineto-neutral voltage): I base Zbase S3 ,base 3VLL ,base VLL ,base 3I base V LL ,base 2 S3 ,base Change base impedance The per-unit impedance may be transformed from one base to another as: 2 Per unitZ new Vold Snew per unitZ old V S new old Example : a power system consists of one synchronous generator and one synchronous motor connected by two transformers and a transmission line. Create a per-phase, per-unit equivalent circuit of this power system using a base apparent power of 100 MVA and a base line voltage of the generator G1 of 13.8 kV. Given that: G1 ratings: 100 MVA, 13.8 kV, R = 0.1 pu, Xs = 0.9 pu; T1 ratings: 100 MVA, 13.8/110 kV, R = 0.01 pu, Xs = 0.05 pu; T2 ratings: 50 MVA, 120/14.4 kV, R = 0.01 pu, Xs = 0.05 pu; M ratings: 50 MVA, 13.8 kV, R = 0.1 pu, Xs = 1.1 pu; L1 impedance: R = 15 , X = 75 . Solution: To create a per-phase, per-unit equivalent circuit, we need first to calculate the impedances of each component in the power system in per-unit to the system base. The system base apparent power is Sbase = 100 MVA everywhere in the power system. The base voltage in the three regions will vary as the voltage ratios of the transformers that delineate the regions. These base voltages are: Vbase,1 13.8kV Region 1 110 110kV Region 2 13.8 14.4 Vbase,2 13.2kV Region 2 120 Vbase,2 Vbase,1 Vbase,3 The corresponding base impedances in each region are: Z base,1 Z base,2 Z base,3 VLL ,base 2 S3 ,base 13.8kV VLL ,base 2 S3 ,base VLL ,base 2 S3 ,base 2 100MVA 1.904Region1 110kV 121Region1 100MVA 2 13.2kV 2 100MVA 1.743Region1 The impedances of G1 and T1 are specified in per-unit on a base of 13.8 kV and 100 MVA, which is the same as the system base in Region 1. Therefore, the per-unit resistances and reactances of these components on the system base are unchanged: RG1,pu = 0.1 per unit XG1,pu = 0.9 per unit RT1,pu = 0.01 per unit XT1,pu = 0.05 per unit There is a transmission line in Region 2 of the power system. The impedance of the line is specified in ohms, and the base impedance in that region is 121 . Therefore, the per-unit resistance and reactance of the transmission line are: 15 Rline, system 0.124 perunit 121 75 X line, system 0.620 perunit 121 The impedance of T2 is specified in per-unit on a base of 14.4 kV and 50 MVA in Region 3. Therefore, the per-unit resistances and reactances of this component on the system base are: per unitZ new per unitZ given Vgiven Vnew Snew S given 2 RT 2, pu 0.0114.4 13.2 100 50 0.238 perunit 2 X T 2, pu 0.05 14.4 13.2 100 50 0.119 perunit 2 The impedance of M2 is specified in per-unit on a base of 13.8 kV and 50 MVA in Region 3. Therefore, the per-unit resistances and reactances of this component on the system base are: per unitZ new per unitZ given Vgiven Vnew Snew S given 2 RM 2, pu 0.114.8 13.2 100 50 0.219 perunit 2 X M 2, pu 1.114.8 13.2 100 50 2.405 perunit 2 Therefore, the per-phase, per-unit equivalent circuit of this power system is shown: node equation When the per-unit equivalent circuit of a power system is created, it can be used to find the voltages, currents, and powers present at various points in a power system. The most common technique used to solve such circuits is nodal analysis. In nodal analysis, we use Kirchhoff’s current law equations to determine the voltages at each node (each bus) in the power system, and then use the resulting voltages to calculate the currents and power flows at various points in the system. For example a simple three-phase power system bellow The per-unit equivalent circuit of this power system: Note that the per-unit series impedances of the transformers and the transmission lines between each pair of busses have been added up, and the resulting impedances were expressed as admittances (Y=1/Z) to simplify nodal analysis. The voltages between each bus and neutral are represented by single subscripts (V1, V2) in the equivalent circuit, while the voltages between any two busses are indicated by double subscripts (V12). The generators and loads are represented by current sources injecting currents into the specific nodes. Conventionally, current sources always flow into a node meaning that the power flow of generators will be positive, while the power flow for motors will be negative. According to Kirchhoff’s current flow law (KCL), the sum of all currents entering any node equals to the sum of all currents leaving the node. KCL can be used to establish and solve a system of simultaneous equations with the unknown node voltages. Assuming that the current from the current sources are entering each node, and that all other currents are leaving the node, applying the KCL to the node (1) yields: V1 V2 Ya V1 V3 Yb V1Yd I1 Similarly, for the nodes (2) and (3): V2 V1 Ya V2 V3 Yc V2Ye I 2 V3 V1 Yb V3 V2 Yc V3Y f I3 Rearranging these equations, we arrive at: Ya Yb Yd V1 YaV2 YbV3 I1 YaV1 Ya Yc Ye V2 YcV3 I 2 YbV1 YcV2 Yb Yc Y f V3 I 3 In matrix form: Ya Yb Yd Ya Yb V1 I1 Ya Yb Ya Yc Ye Yc V2 I 2 Yc Yb Yc Y f V3 I 3 Which is an equation of the form: YbusV I where Ybus is the bus admittance matrix of a system, which has the form: Ybus Y11 Y12 Y13 Y21 Y22 Y23 Y31 Y32 Y33 Ybus has a regular form that is easy to calculate: 1) The diagonal elements Yii equal the sum of all admittances connected to node i. 2) Other elements Yij equal to the negative admittances connected to nodes I and j. 3) The diagonal elements of Ybus are called the self-admittance or driving-point admittances of the nodes; the off-diagonal elements are called the mutual admittances or transfer admittances of the nodes. 4) Inverting the bus admittance matrix Ybus yields the bus impedance matrix: Zbus Ybus 1 Simple technique for constructing Ybus is only applicable for components that are not mutually coupled. The technique applicable to mutually coupled components can be found elsewhere. Once Ybus is calculated, the solution to (10.15.1) is 1 bus V Y I V bus I A number of techniques can be used to solve systems of simultaneous linear equations, such as substitution, Gaussian elimination, LU factorization, etc. A system of n linear equations in n unknowns Ax b where A is an n x n matrix and b is and n-element column vector; the solution will be 1 xA b where A-1 is the n x n matrix inverse of A. Example 10.3: a power system consists of four busses interconnected by five transmission lines. It includes one generator attached to bus 1 and one synchronous motor connected to bus 3. The per-phase, per-unit equivalent circuit is shown. We observe that all impedances are considered as pure reactances to simplify the case since reactance is much larger than resistance in typical transformers, synchronous machines, and overhead transmission lines. Find the per-unit voltage at each bus in the power system and the per-unit current flow in line 1. The first step in solving for bus voltages is to convert the voltage sources into the equivalent current sources by using the Norton’s theorem. Next, we need to convert all of the impedance values into admittances and form the admittance matrix Ybus then use it to solve for the bus voltages, and finally use voltages on buses 1 and 2 to find the current in line 1. First, we need to find the Norton equivalent circuits for the combination of G1 and T1. The Thevenin impedance of this combination is ZTH = j1.1, and the short-circuit current is Voc 1.110 I sc 1.0 80 ZTH j1.1 The combination of M3 and T2 is shown. The Thevelin impedance of this combination is ZTH = j1.6, and the short-circuit current is I sc Voc 0.9 22 0.563 112 ZTH j1.6 I sc Voc 0.9 22 0.563 112 ZTH j1.6 The Norton’s equivalent circuit. The per-phase, per-unit circuit with the current sources included The resulting admittance matrix is: Ybus j 5.0 0 j 6.667 j12.576 j 5.0 j 12.5 j 5.0 j 2.5 0 j 5.0 10.625 j 5.0 j 6.667 j 2.5 j 5.0 j 14.167 The current vector for this circuit is: 1.0 80 0 I 0.563 112 0 The solution to the system of equations will be 0.989 0.60 0.981 1.58 1 V V Ybus I 0.974 2.62 0.982 1.48 The current in line 1 can be calculated from the equation: I1 V1 V2 Yline1 0.989 0.60 0.981 1.58 j5.0 0.092 25.16