C:\Drawings\2010\10001-Rue 21 Prototype 2010\Rue 21 Prototype

advertisement
KEY PLAN
DATE
08-19-09
JOB NO:
00000
DRAWN:
CM
CHECKED:
CM
SITE MAP
711 N. FIELDER RD.
TENANT
LOCATION
ARLINGTON, TX 76012
PH: (817) 635-5696
FAX: (817 635-5699
CENTER
LOCATION
GENERAL NOTES
2.
G.C. SHALL COORDINATE HIS WORK WITH THAT OF THE UTILITY
COMPANIES, AND ALSO COORDINATE THE WORK OF ALL TRADES,
PROVIDING ACCESS AS REQUIRED.
G.C. SHALL PAY FOR ALL TRASH SERVICES, BE RESPONSIBLE FOR
THE REMOVAL OF DEBRIS FOR ALL TRADES, AND FOR KEEPING THE
JOB SITE CLEAN AT ALL TIMES.
4.
SCHEDULE - PROVIDE A CONSTRUCTION TIME SCHEDULE SHOWING ALL
PHASES OF THE WORK INCLUDING THAT OF THE MILLWORK
CONTRACTOR, THE OWNER'S SUPPLIED MATERIAL AND ALL
SUBCONTRACTORS. A PRELIMINARY SCHEDULE SHOULD BE ATTACHED
TO BID SUBMITTAL.
MINIMUM INTERFERENCE - ALL WORK SHALL BE PERFORMED SO AS TO
CAUSE A MINIMUM OF INTERFERENCE WITH ANY OTHER TENANTS AND
THE OPERATION OF THE LANDLORD'S ENTIRE PREMISES. CONTRACTOR
SHALL TAKE ALL PRECAUTIONARY STEPS TO PROTECT THE FACILITIES
ON THE PREMISES AND THE FACILITIES OF OTHERS AFFECTED BY
PERFORMANCE OF THE WORK AND POLICE SAME PROPERLY.
7.
CONSTRUCTION EQUIPMENT AND MATERIALS ARE TO BE LOCATED IN
CONFINED AREAS AND TRUCK TRAFFIC IS TO BE ROUTED IN AND FROM
THE SITE AS DIRECTED BY THE LANDLORD. THE COST OF THE WORK
SHALL INCLUDE ANY OVERTIME NECESSITATED BY THESE
REQUIREMENTS.
8.
13. CUTTING AND REPAIR:
ALL CUTTING, DRILLING, OR REMOVALS REQUIRED TO REMOVE,
RELOCATE, ALTER OR INSTALL ANY WORK, EQUIPMENT, WIRING,
APPLIANCES, ETC., AND UPON COMPLETION, REPAIRING, PATCHING
AND FINISHING ALL SURFACES TO A NEW CONDITION SHALL BE DONE
BY THE CONTRACTOR PER THE SPECIFICATIONS.
ALL SURFACES, INCLUDING THOSE DAMAGED DURING THE WORK,
REQUIRING SAME SHALL BE PATCHED AND REFINISHED TO A NEW
CONDITION TO THE ARCHITECT'S OR TENANT'S APPROVAL.
15. CLEANING:
G.C.
SHALL
REMOVE
ALL CONSTRUCTION RUBBISH,
SCAFFOLDING, EQUIPMENT, TEMPORARY PROTECTION, TEMPORARY FIELD
STRUCTURES, AND ANYTHING ELSE THAT WAS REQUIRED IN CONNECTION
WITH THE CONSTRUCTION, BUT NOT A PERMANENT PART THEREOF.
T.G.C. SHALL MAINTAIN ORDERLY HOUSEKEEPING DURING THE PROCESS
OF CONSTRUCTION, AND UPON COMPLETION SHALL THOROUGHLY CLEAN
ALL AREAS. FINAL CLEANUP SHALL INCLUDE THE FOLLOWING:
SWEEP, DAMP MOP, AND WAX RESILIENT FLOORING. DUST, DIRT, PAINT
DRIPPINGS, OIL, GREASE, AND OTHER BLEMISHES SHALL BE REMOVED
FROM ALL SURFACES, INCLUDING PIPING AND EQUIPMENT. WINDOWS,
GLASS UNITS, GLASS DOORS AND MIRRORS SHALL BE WASHED. PAINT
OVERRUNS AND PUTTY SMEARS SHALL BE REMOVED. HARDWARE SHALL
BE RUBBED CLEAN WITH A FLANNEL CLOTH.
22. ANY DISCREPANCIES, ERRORS, OR OMISSIONS DISCOVERED IN THE
CONTRACT DOCUMENTS BY THE CONTRACTOR SHALL BE BROUGHT TO THE
ATTENTION OF THE TENANT & LAMI-GRUBB BEFORE PROCEEDING WITH
RELATED WORK. OTHERWISE, THE CORRECTION OF SUCH ITEMS WILL
BE THE RESPONSIBILITY OF THE CONTRACTOR.
23. TIME IS OF THE ESSENCE AND THE CONTRACTOR SHALL KEEP
SUFFICIENT PERSONNEL ON THE JOB AT ALL TIMES TO PERFORM THE
WORK IN THE MOST EXPEDITIOUS MANNER CONSISTENT WITH GOOD
WORKMANSHIP, AND SOUND BUSINESS PRACTICE. THE CONTRACTOR
A. PROGRESS SCHEDULE
B. LIST OF ALL SUBCONTRACTORS
C. COPIES OF BUILDING PERMIT AND ANY OTHER REQUIRED
AUTHORIZATIONS AND LICENSES BY GOVERNING
AUTHORITIES. ARCHITECT WILL OBTAIN AND PAY FOR THE STATE
PERMIT, THE GC WILL OBTAIN AND PAY FOR THE BUILDING PERMIT
ABBREVIATIONS
(100'-0")
FINISH FLOOR
(ELEVATION)
EXISTING PARTITION TO BE REMOVED
LANDLORD COLUMN
LINE
B.1
ELEVATION NUMBER AND
DIRECTION INDICATION
LEASE LINE
NEW DOOR
DETAIL OR SECTION NUMBER
EXISTING DOOR
DIRECTION DETAIL IS TAKEN
2
DOOR NUMBER
AB1
FINISH NUMBER
4
FIXTURE NUMBER
3
PARTITION TYPE
SHEET DETAIL IS DRAWN ON
LINE OF VENEER PANELING
SHALL CONFIRM THAT ALL ITEMS WILL BE ORDERED, FABRICATED,
AND INSTALLED PRIOR TO THE AGREED COMPLETION DATE.
EXCEPTIONS WILL NOT BE ALLOWED WITHOUT WRITTEN AUTHORIZATION
OF THE OWNER PRIOR TO PLACEMENT OF ORDER.
24. THERE SHALL BE NO SUBSTITUTION OF MATERIALS WHERE A
MANUFACTURER IS SPECIFIED. WHERE THE TERM "OR APPROVED
EQUAL" IS USED, THE ARCHITECT ALONE SHALL DETERMINE
SUITABILITY BASED UPON INFORMATION SUPPLIED BY CONTRACTOR.
25. ALL WORK SHALL BE ERECTED AND INSTALLED PLUMB, LEVEL,
SQUARE, AND TRUE, AND IN PROPER ALIGNMENT.
26. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE FURNISHING
AND INSTALLATION OF ALL BRACING AND BLOCKING OF WALLS,
RECEIVING WOODWORK, SHELVING, ETC. GENERAL CONTRACTOR TO
COORDINATE THE LOCATION OF SAID BRACING AND BLOCKING WITH
OWNER.
27. GENERAL CONTRACTOR TO PROVIDE BLOCKING AT BASE OF STORE
FIXTURES, FILES, FREESTANDING WOODWORK, ETC. TO ALIGN THESE
ITEMS WHERE THERE ARE DIFFERENCES IN THE FLOOR LEVEL.
28. THESE GENERAL CONDITIONS SHALL APPLY TO ALL WORK AND ALL
DRAWINGS IN THIS SET, AND SHALL EXTEND TO ANY CHANGES, EXTRAS,
OR ADDITIONS AGREED TO DURING THE COURSE OF THE WORK.
29. THE G.C. SHALL MEET WITH AN AUTHORIZED REPRESENTATIVE OF THE
LANDLORD AND SHALL REVIEW LANDLORD CONSTRUCTION REQUIREMENTS.
G.C. SHALL COORDINATE HIS WORK WITH THE LANDLORD WITH REGARD
TO TEMPORARY UTILITIES, ALLOWABLE MATERIAL, TRAFFIC ROUTES,
STORAGE OF TOOLS AND MATERIALS, USE OF TOILET FACILITIES,
HOURS IN WHICH WORK IS ALLOWED, NOISE AND DUST CONTROL,
CLEANUP AND OTHER MATTERS REQUIRING ADHERENCE TO LANDLORD
REQUIREMENTS.
30. G.C. SHALL REVIEW WITH THE LANDLORD'S REPRESENTATIVE THE
MANNER IN WHICH ALL CONNECTIONS TO STRUCTURE WILL BE MADE. ANY
PENETRATIONS IN THE BUILDING ENVELOPE OR STRUCTURE SHALL BE
REVIEWED WITH THE LANDLORD AND APPROVED IN WRITING. IF THE
LANDLORD REQUIRES THAT PORTIONS OF WORK BE PERFORMED BY IT'S
OWN CONTRACTOR, G.C. SHALL INCUR ALL COSTS ASSOCIATED WITH
THAT PORTION OF THE WORK UNLESS STATED OTHERWISE IN WRITING BY
THE OWNER.
31. G.C. SHALL BE RESPONSIBLE TO THE LANDLORD FOR ANY DAMAGE
OCCURRING TO ANY OF THE LANDLORD'S FACILITIES BEFORE DURING OR
AFTER CONSTRUCTION PROCEDURES CAUSED BY THE CONTRACTOR, HIS
EMPLOYEES OR HIS SUBCONTRACTORS.
33. SAFETY
SCAFFOLDING SHALL BE BUILT IN ACCORDANCE WITH REQUIREMENTS
OF ALL FEDERAL, STATE, AND LOCAL LAWS. ALL TEMPORARY SHORING
REQUIRED FOR THE REMOVAL OF EXISTING WORK FOR THE INSTALLATION
OF NEW WORK SHALL BE INCLUDED IN THE CONTRACT. CONTRACTOR
SHALL BE RESPONSIBLE FOR THIS WORK AND SHALL MAKE GOOD ANY
DAMAGE CAUSED BY IMPROPER SUPPORT OR FAILURE OF SHORING IN ANY
RESPECT.
DURING PERFORMANCE OF WORK, G.C. IS RESPONSIBLE FOR
PROVISION AND MAINTENANCE OF WARNING SIGNS, LIGHT SIGNAL
DEVICES, GUARD LIGHTS, BARRICADES, GUARD RAILS, FENCES AND
OTHER DEVICES AS APPROPRIATELY LOCATED ON AND AROUND THE JOB
SITE WHICH WILL GIVE PROPER AND UNDERSTANDABLE WARNING TO ALL
PERSONS WITH REGARD TO HAZARDOUS CONDITIONS, EQUIPMENT AND
OPERATIONS BEING PERFORMED IN CONJUNCTION WITH THE G.C.'S
WORK. ALL WARNING DEVICES SHALL COMPLY WITH O.S.H.A. AND
OTHER APPLICABLE GOVERNMENTAL REGULATIONS AS REQUIRED FOR THE
CONSTRUCTION PROCEDURES AND CONDITIONS ENCOUNTERED.
INSOFAR AS JOB SITE SAFETY IS CONCERNED, THE ARCHITECT IS
RESPONSIBLE SOLELY FOR HIS OWN AND HIS EMPLOYEES ACTIVITIES ON
THE JOB SITE, BUT THIS SHALL NOT BE CONSTRUED TO RELIEVE THE
OWNER OR ANY CONSTRUCTION CONTRACTORS FROM THEIR
RESPONSIBILITIES FOR MAINTAINING A SAFE JOB SITE. NEITHER THE
PROFESSIONAL ACTIVITIES OF THE ARCHITECT, NOR THE PRESENCE OF
THE ARCHITECT OR HIS EMPLOYEES AND SUBCONTRACTORS, SHALL BE
CONSTRUED TO IMPLY THE ARCHITECT HAS ANY RESPONSIBILITY FOR
METHODS OF WORK PERFORMANCE, SUPERINTENDENT, SEQUENCING OF
CONSTRUCTION, OR SAFETY IN, ON OR ABOUT THE JOB SITE. THE
OWNER AGREES THAT THE G.C. IS SOLELY RESPONSIBLE FOR JOB
SITE SAFETY AND WARRANTS THAT THE ARCHITECT SHALL BE MADE AN
ADDITIONAL INSURED UNDER THE G.C.'S GENERAL LIABILITY
INSURANCE POLICY.
34. G.C. TO COORDINATE ALL WORK WITH LAMI - GRUBB.
35. G.C. SHALL BE RESPONSIBLE FOR ANY CONSTRUCTION DEPOSITS
REQUIRED BY THE LANDLORD WHETHER REFUNDABLE OR NOT.
36. G.C. TO VERIFY LEASE SPACE DIMENSIONS & EXISTING BUILDING ELEMENTS
FOR COMPLIANCE WITH THE DRAWINGS BEFORE COMMENCING CONSTRUCTION.
ANY DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT OR ENGINEER FOR RESOLUTION OF DIMENSIONAL CONFLICTS AND
COMPONENT LOCATIONS. NO CHANGE ORDERS WILL BE ISSUED FOR CHANGES
REQUIRED IN THE WORK AFTER CONSTRUCTION HAS COMMENCED UNLESS
SPECIFICALLY AUTHORIZED BY THE ARCHITECT/ENGINEER AND THE OWNER.
32. APPLICABLE STANDARDS OF CONSTRUCTION INDUSTRY HAVE SAME FORCE
AND EFFECT ON PERFORMANCE OF THE WORK AS IF COPIED DIRECTLY
INTO CONTRACT DOCUMENTS OR BOUND AND PUBLISHED THEREWITH.
COMPLY WITH STANDARDS IN EFFECT AS OF THE DATE OF CONTRACT
DOCUMENTS, UNLESS OTHERWISE INDICATED.
D. COPY OF INSURANCE COVERAGE TO TENANT AND LANDLORD'S REP.
SYMBOLS
1
A2
21. VERIFY ALL DIMENSIONS AS THEY APPLY TO EXISTING CONDITIONS
WITH PARTICULAR EMPHASIS ON DIMENSIONS MARKED "VERIFY" OR
VERIFY IN FIELD (V.I.F.). NOTIFY TENANT & LAMI - GRUBB IMMEDIATELY
OF ANY DISCREPANCIES BETWEEN THE DRAWINGS AND EXISTING CONDITIONS.
BEFORE START OF CONSTRUCTION, THE GENERAL CONTRACTOR IS TO
SUBMIT THE FOLLOWING:
CONTRACTOR TO PROVIDE ARCHITECT, TENANT, AND LANDLORD'S
REPRESENTATIVE WITH A COMPLETE & ACCURATE SET OF AS-BUILT
1
A1
20. LAYOUT WORK AND BE RESPONSIBLE FOR ALL LINES, ELEVATIONS,
MEASUREMENTS OF THE BUILDING, UTILITIES, AND OTHER WORK
EXECUTED UNDER THE CONTRACT.
17. SCHEDULE OF REQUIRED SUBMITTALS:
10. CONTRACTOR TO PROVIDE ALL SUBCONTRACTORS WITH A COMPLETE SET
OF THE MOST CURRENT CONSTRUCTION DOCUMENTS.
REVISION NUMBER
BY UNIT VALUES BASED ON THE ITEMIZED COST BREAKDOWN
BY COST PLUS A PERCENTAGE FEE.
19. LOCATE ALL EXISTING UTILITY SERVICE LINES (INCLUDING TELEPHONE
LINES) AND PROTECT THEM THROUGHOUT THE CONSTRUCTION PERIOD.
CLEARLY MARK ALL SUBMISSIONS WITH DATE, PROJECT, CONTACT,
AND SUBCONTRACTOR AND ALLOW SPACE FOR APPROVAL
DRAWING AND SPECIFICATIONS:
A COMPLETE SET OF THE DRAWINGS INCLUDING APPROVED SHOP
DRAWINGS SHALL BE KEPT AT THE SITE FOR THE DURATION OF THE
WORK. COPIES, OR ORIGINALS IF REQUIRED, OF ALL PERMITS AND
APPROVALS SHALL ALSO BE KEPT AT THE SITE.
STOREFRONT CLOSURE
OR COLUMN LINE
A.
B.
16. SHOP DRAWINGS AND SAMPLES:
WHERE CALLED FOR IN THE DOCUMENTS, SUBMIT TO LAMI - GRUBB
FOR APPROVAL.
THE ENCLOSURE BARRICADE WILL BE CONSTRUCTED BY THE LANDLORD PRIOR
TO START OF CONSTRUCTION, OR WILL INSTALL STOREFRONT TO BE USED
AS THE CLOSURE
NEW PARTITION
(ARCHITECTURAL PLAN)
THE UNDERSIGNED AGREES THAT THERE MAY BE CHANGES, OMISSIONS,
OR MODIFICATIONS IN THE WORK AND THAT APPROPRIATE
ADJUSTMENTS WILL BE MADE IN THE CONTRACT PRICE. THE
UNDERSIGNED ALSO AGREES THAT THE CHARGES FOR ALL EXTRA WORK
OR CREDITS SHALL BE DETERMINED, AT OWNER'S CHOICE, IN ONE OF
THE FOLLOWING WAYS:
UPON COMPLETION OF THE WORK, ALL SURFACES, INCLUDING FLOORS,
WALLS, GLASS, FIXTURES AND FITTINGS SHALL BE CLEAN AND READY
TO USE.
G.C. TO PROVIDE AN OPERATIONAL FACSIMILE MACHINE ON SITE OR
HAVE A FAX AVAILABLE, LOCATED CLOSE TO SITE, PRIOR TO THE START
OF CONSTRUCTION.
1
NOTE: ALL SUBSTITUTIONS ARE TO BE APPROVED BY LAMI - GRUBB
AND THE OWNER.
18. CHANGES:
TEMPORARY FACILITIES:
EXISTING PARTITION TO REMAIN
SUBMIT CATALOGUE CUTS OR SAMPLES OF ANY SUBSTITUTIONS.
14. PATCHING:
CONTRACTOR SHALL ARRANGE AND PAY FOR AND MAINTAIN ANY NEEDED
TEMPORARY FACILITIES AT THE PREMISES INCLUDING ELECTRICAL
SERVICE, TRASH REMOVAL, PROTECTION, ENCLOSURE BARRICADE, USE
OF ELEVATORS, AIR CONDITIONING AND HEATING, TELEPHONE & FAX AT THE
PREMISES FOR THE DURATION OF THE WORK.
9.
A. SIGN SHOP DRAWINGS
B. SHOP DRAWINGS SHOWING CONSTRUCTION, DETAILS, AND
PROFILES
C. EVIDENCE OF COMPLIANCE WITH FIRE RETARDANT ASSEMBLY
D. BUILDERS HARDWARE: HARDWARE SCHEDULE
E. SIGN WORK: SAMPLE OF ALL LETTERING
F. SPRINKLERS:
SHOP DRAWING SHOWING SPRINKLER HEAD
LOCATIONS, PIPING AND VALVES.
G. HVAC:
SHOP DRAWINGS AND CATALOGUE CUTS SHOWING
DUCTWORK AND ALL HVAC EQUIPMENT, INCLUDING
REGISTERS AND DIFFUSERS.
12. G.C. SHALL BE RESPONSIBLE FOR A SMOOTH TRANSITION BETWEEN
THE STORE FLOOR AND THE MALL FLOOR.
SHOULD THE GENERAL CONTRACTOR REQUIRE THE WOODWORK
CONTRACTORS TO FIELD MEASURE, ANY COSTS SHALL BE BORNE BY
THE GENERAL CONTRACTOR.
6.
THE GENERAL CONTRACTOR IS TO SUBMIT SHOP DRAWINGS, SAMPLES
AND/OR CATALOGUE CUTS OF ALL ITEMS REQUIRED, INCLUDING THE
FOLLOWING:
CONTRACTOR SHALL, FOR THE DURATION OF THE WORK, KEEP ON THE
PREMISES A COMPETENT FULL-TIME GENERAL FOREMAN OR
SUPERINTENDENT SATISFACTORY TO THE OWNER.
G.C. SHALL EXAMINE THE EXISTING UTILITY CONDITIONS STUB-INS
OR ACCESS TO UTILITIES AND VERIFY WITH INFORMATION SHOWN ON
THESE DRAWINGS. ANY DISCREPANCIES SHALL BE BROUGHT TO THE
ATTENTION OF THE ARCHITECT OR ENGINEER PRIOR TO THE BID SUBMITTAL.
3.
5.
11. SUPERVISION:
SHOPPING CENTER
TENANT SPACE
ANYWHERE USA
1.
Project Coordination By:
BUILD TO SUIT
EXTERIOR STRIP CENTER
ANYWHERE USA
ACT
ADJ
AFF
ALUM
ARCH
BD
BLDG
BLKG
CLG
CL
CLR
COL
CONC
CONST
CONT
DEMO
DTL
DIA
DIM
DN
DWG
DF
EA
ELEC
EQ.
EWH
EQUIP
EXIST
EXT
FC
FCIC
FT
FL
FLUOR
FOIC
FRT
ACOUSTICAL TILE
ADJUSTABLE
ABOVE FINISHED FLOOR
ALUMINUM
ARCHITECT(URAL)
BOARD
BUILDING
BLOCKING
CEILING
CENTER LINE
CLEAR
COLUMN
CONCRETE
CONSTRUCTION
CONTINUOUS
DEMOLITION
DETAIL
DIAMETER
DIMENSION
DOWN
DRAWING
DRINKING FOUNTAIN
EACH
ELECTRIC(AL)
EQUAL
ELECTRIC WATER HEATER
EQUIPMENT
EXISTING
EXTERIOR
FIXTURE CONTRACTOR
FURNISHED BY CONTRACTOR
INSTALLED BY CONTRACTOR
FEET
FLOOR
FLUORESCENT
FURNISHED BY OWNER
INSTALLED BY CONTRACTOR
FIRE RETARDANT TREATED
FURN
FURN/INST
GA
GC
GWB
GYP BD
HDWE
HT
HC
HM
HR
HWH
IC
IN
INSUL
INT
LAV
LL
LT
LTG
LIN
MFR
MAX
MECH
MTL
MEZZ
MIN
MISC
MTD
NIC
NTS
OC
PTN
PL
PL LAM
PLG
PLYWD
PROV
FURNISH
FURNISHED/INSTALLED
GAUGE
GENERAL CONTRACTOR
GYPSUM WALL BOARD
GYPSUM BOARD
HARDWARE
HEIGHT
HOLLOW CORE
HOLLOW METAL
HOUR
HOT WATER HEATER
INSTALLED BY CONTRACTOR
INCH
INSULATION
INTERIOR
LAVATORY
LANDLORD
LIGHT
LIGHTING
LINEAR
MANUFACTURE(R)
MAXIMUM
MECHANICAL
METAL
MEZZANINE
MINIMUM
MISCELLANEOUS
MOUNTED
NOT IN CONTRACT
NOT TO SCALE
ON CENTER
PARTITION
PLASTIC LAMINATE
PLASTIC LAMINATE
PLUMBING
PLYWOOD
PROVIDE(D)
BUILDING REVIEW
QTY
R
REQ
RES
REV
RTU
SCHED
SECT
SF
SFC
SHT
SIM
SC
SPECS
STD
STRUCT
SUSP
TBD
TEMP
TGC
T&G
TYP
UNO
VCT
VIF
VERT
WC
W/
W/O
WD
PROJECT DATA
DRAWING INDEX
SITE LOCATION
QUANTITY
RADIUS
REQUIRED
RESILIENT
REVISION
ROOFTOP UNIT
SCHEDULE
SECTION
SQUARE FEET
STOREFRONT
CONTRACTOR
SHEET
SIMILAR
SOLID CORE
SPECIFICATION(S)
STANDARD
STRUCTURAL
SUSPENDED
TO BE DETERMINED
TEMPERED
TENANT'S GENERAL
CONTRACTOR
TONGUE & GROOVE
TYPICAL
UNLESS NOTED
OTHERWISE
VINYL COMPOSITION
TILE
VERIFY IN FIELD
VERTICAL
WALLCOVER
WITH
WITHOUT
WOOD
RUE 21
VANILLA BOX DRAWING
EXTERIOR STRIP CENTER
ANYWHERE USA
TENANT
RUE 21
800 COMMONWEALTH DRIVE
WARRENDALE, PA 15086
TEL: (724) 776-7475 FAX: (724) 776-3580
CONTACT: SKIP MERRITT
TENANT COORDINATOR
LANDLORD
LANDLORD STREET ADDRESS
LANDLORD CITY, STATE ZIP
CONTACT: LANDLORD CONTACT
TEL: LANDLORD TEL NUMBER
PROJECT COORDINATION
LAMI - GRUBB PROJECT MANAGEMENT, INC.
100 EAST SWISSVALE AVE.
PITTSBURGH, PA 15218
TEL: (412) 243-3430 FAX: (412) 371-1586
CONTACT: MARC SIDES (603-778-3840)
APPLICABLE CODES:
Building Code
Mechanical Code
Plumbing Code
Electrical Code
Fire/Life Safety Code
Fuel and Gas Code
Accessibility Code
2006 INTERNATIONAL BUILDING CODE
2006 INTERNATIONAL MECHANICAL CODE
2006 INTERNATIONAL PLUMBING CODE
2005 NATIONAL ELECTRIC CODE
2006 INTERNATIONAL FIRE CODE
2006 INTERNATIONAL FUEL AND GAS CODE
ANSI A117.1/ADAAG REQUIREMENTS
T1
TITLE SHEET
DS
DATA SHEET
A1
A2
A3
A4
FLOOR PLAN AND MISC NOTES
FLOOR FINISH PLAN AND DETAILS
CEILING PLAN AND MISC NOTES
INTERIOR ELEVATIONS
F1
F2
F3
F4
FITTING ROOM DETAILS
CASH WRAP DETAILS
BACK OF HOUSE DETAILS
FIXTURE DETAILS
M0
M1
M2
M3
MECHANICAL TITLE SHEET
MECHANICAL PLAN
PLUMBING PLANS
MECHANICAL SPECIFICATIONS
E0
E1
E2
E3
ELECTRICAL TITLE SHEET
LIGHTING PLAN
POWER PLAN
ELECTRICAL SPECIFICATIONS
NOT FOR
CONSTRUCTION
REVISIONS
TITLE SHEET
SHEET NUMBER
T1
AMTICO
TECHNO ZINC STUD DP38 WITH VINYL 'GROUT'
ECO SURFACES
#3598 CUSTOM BLEND OF ECO NIGHTS RUBBER SHEET
GOODS, ADHESIVES PROVIDED BY TENANT'S VENDOR
CONGOLEUM
ALTERNATIVES 12x12 VINYL TILE, MULTI-BERRY,
ADHESIVES PROVIDED BY TENANT'S VENDOR
ARMSTRONG -ORMANNINGTON
CONCRETE STAIN
AMTICO
GZ11 STARDUST WHITE
AMTICO
MR30 MARCASITE
N/A
POLISHED CONCRETE FINISH, ACHIEVE A HIGH GLOSS
FINISH
ARTCRETE
(318-379-2000)
APPLY (2) COATS ARTCRETE FAUX BRICK DC2500
CLEAR SEALER APPLIED OVER EX'G CONCRETE SLAB
PAINT
(APPLY PRIMER
AND 2 COATS OF
PAINT)
WALLCOVERING
ARMSTRONG
or
USG
3
B
2'-10 3/4"x5'-0"
WD
WD
4
B
2'-10 3/4"x5'-0"
WD
WD
5
B
2'-10 3/4"x5'-0"
WD
WD
6
EXG
3'-0"x7'-0"
H.M.
H.M.
--
7
A
3'-0"x7'-0"
H.M.
H.M.
--
8
A
3'-0"x7'-0"
H.M.
H.M.
--
9
A
3'-0"x7'-0"
H.M.
H.M.
--
10
11
A
--
3'-0"x7'-0"
H.M.
H.M.
--
6'-0"x7'-0"
H.M./GL. H.M.
--
TENANT'S
VENDOR
LANDLORD
CONTRACTOR
GENERAL
CONTRACTOR
INSTALL
WD
PROVIDE
WD
INSTALL
2'-10 3/4"x5'-0"
PROVIDE
B
INSTALL
2
PROVIDE
WD
NOT APPLICABLE
EXISTING
TENANT'S
VENDOR
TENANT
GC
INSTALL
PROVIDE
INSTALL
WD
BY TENANT'S
BY TENANT'S
BY TENANT'S
BY TENANT'S
BY TENANT'S
GENERAL
BUILDING PERMIT
OTHER PERMITS, FEES, INSURANCE
CLEAN-UP & FINAL CLEANING
TRASH REMOVAL & DUMPSTER
CONCRETE SLAB - STRUCTURAL
TEMPORARY BARRICADES
PAINT DOOR AND FRAME PT3 (GRAY)
PAINT DOOR AND FRAME PT3 (GRAY)
PAINT DOOR AND FRAME PT3 (GRAY)
PAINT DOOR AND FRAME PT3 (GRAY)
2x4 #533 CIRRUS SQUARE EDGE, COLOR: WHITE --OR-2X4 #2310 RADAR SQUARE EDGE, COLOR: WHITE
INSTALLED IN NEW 15/16" GRID, WHITE
ALL HARDWARE IS "SCHLAGE" IF NOT NOTED OTHERWISE
+ (3)Ea. Self Closing Hinges
+ (1)Ea. Lockset AL80PD-SAT 11-05 10-001 626 (Keyed Alike)
GENERAL CONSTRUCTION
DEMOLITION
TRENCHING OF EXISTING SLAB
DEMISING WALL STUDS
DEMISING WALL GWB
GWB, METAL STUDS, ETC.
CARPENTRY, ROUGH AND FINISH
Door # 1: * REFER TO SHEET F1 FOR JAMB/BLOCKING DETAILS
+ (3)Ea. Butt Hinges
ARMSTRONG
NEW 2x4 LAY-IN TILE #533 CIRRUS, COLOR: WHITE
INSTALLED IN NEW 15/16" GRID, WHITE
ICI PAINTS
EUROPEAN WHITE #30YY 67/084, EGGSHELL
FINISH, SEMI-GLOSS FINISH AT DOORS/TRIM
+ (1)Ea. 36" Grab Bar - Bobrick - B - 5806x36
SHERWIN WILLIAMS
SW 6993 BLACK OF NIGHT, SEMI-GLOSS FINISH
SHERWIN WILLIAMS
SW 7073 NETWORK GRAY, SEMIGLOSS FINISH AT
TRIMS, EGGSHELL ON WALLS
Door # 6:
+ (1)Ea. Panic Bar
CUSTOM
RUE 21 GREEN
BENJAMIN MOORE
#782 BLUE BELLE, SEMIGLOSS FINISH AT TRIMS,
EGGSHELL ON WALLS
TOWER CONTRACT
CUSTOM VINYL WALLCOVERING, METEOR
TYPE 1, COLOR: V-14508 (GREEN)
COMMAND
VINYL WALLCOVERING, BRUSHED METAL
CM36-9916 COLOR: SLATE (BLUE)
TOWER CONTRACT
VINYL WALLCOVERING, METEOR TYPE 1,
COLOR: PLATINUM (GRAY)
ARC COM
VERGANO ACW-51294 #14 BLACK ONYX (MENS)
SURFACE MATERIALS
CUSTOM VINYL WALLCOVERING, V-43482
(JUNIORS)
711 N. FIELDER RD.
FORMICA
BLACK
FORMICA
#6909-58 GLASS PLASTIQUE MATTE FINISH
LIRI
#V35 ESSE FORGET ME NOT
LIRI
#314 ESSE ALPINE GREEN
+ (1)Ea. Lockset AL80PD-SAT 11-05 10-001 626 (Keyed Alike)
BLOCKING AND FURRING
SALES AREA ACOUSTIC TILE CEILING
SALES AREA DRYWALL CEILING & APPLICABLE FRAMING
MIRRORS
DOORS & FRAMES
DOOR HARDWARE
FITTING ROOM DOORS AND TRIM
FITTING ROOM DOOR HARDWARE
FITTING ROOM PARTITIONS
PAINTING
COLORED WALLCOVERINGS
WALL GRAPHICS
SUSPENDED GRAPHIC ELEMENT (AT CASH WRAP)
REDUCER STRIP ADHESIVES, ETC.
FLOOR PREPARATION
FLOOR PROTECTION
VINYL BASE
RESTROOM FLOORING
TOILET ACCESSORIES
FIRE EXTINGUISHERS-TAGGED BY INSPECTION COMPANY
WALL TOGGLERS/TOGGLE BOLTS
+ (1)Ea. Door Closer 1460-H AL (LCN)
+ (1)Ea. Peep hole 700B26D (IVES)
+ (1)Ea. Door Buzzer LA201 (NUTONE)
+ (1)Ea. Cover Plate/Blank on Exterior
+ (1)Ea. Kickplate K1062 16"x34"xUS32D (Rockwood Mfg.)
+ (1)Provide exterior tenant identification sign per LL standards
+ (1) Pryguard
+ (1) Weatherstripping (exterior doors only)
+ (1) Door Sweep (exterior doors only)
Door # 7 & 10:
+ (1)Ea. Push/Pull Plate 73CLx(4"x16")xUS32D (Rockwood Mfg.)
FAX: (817 635-5699
ELECTRIC SERVICE TO SIGN BY EC
REFER TO DOOR SCHEDULE
REFER TO PARTITION LEGEND
REFER TO PARTITION LEGEND
REFER TO PARTITION LEGEND
REFER TO FINISH SCHEDULE
REFER
REFER
REFER
REFER
REFER
REFER
TO
TO
TO
TO
TO
TO
APPLY DAP CLEAR CAULK AT ALL EXPOSED EDGES
DOOR SCHEDULE
DOOR HARDWARE SCHEDULE
DOOR SCHEDULE
***BLOCKING PROVIDED/INSTALLED BY GC***
DOOR HARDWARE SCHEDULE
PARTITION LEGEND
FINISH SCHEDULE
REFER TO FINISH SCHEDULE
(2) MIN., COORDINATE FINAL LOCATIONS WITH LOCAL ENFORCEMENT
REFER TO DETAIL 6/A4
JOHNSONITE
VINYL BASE TRIM, #28 MEDIUM GRAY
+ (1)Ea. Kickplate K1062 16"x34"xUS32D (Rockwood Mfg.)
+ (1)Ea. Door Stop 517xUS26D (Rockwood Mfg.)
Door # 8 & 9:
+ (3)Ea. Butt Hinges
+ (1)Ea. Privacy AL40s-SAT 2-3/4" ASA 626
+ (1)Ea. Door Closer 1461-H-AL (LCN)
Door 11:
+ (2)Ea. Kickstand door stops #460 (Rockwood Mfg.)
CITY LIGHTING
CHRIS SCHMALZRIED
800-257-2922
412-366-7609 FAX
ICS
PAT O'DEA
(440) 951-9919
(440) 951-6978 FAX
102
103
104
2"
7'-0"
Typical New Frame
GENERAL
CONTRACTOR
INSTALL
TAG
101
INSTALL
SENSORMATIC
GARY
800-241-6678
724-746-1627 FAX
EXISTING
ROOM FINISH SCHEDULE
TENANT'S
VENDOR
C
PROVIDE
ECONOCO
HANK
800-645-7032 X338
877-279-3300 FAX
B
INSTALL
GERBERT LIMITED /ECO SURFACES
STAN STEFANSKI
800-522-0980
724-935-4539 FAX
A
PROVIDE
VECTOR SECURITY
CHIP MARKOWSKY
703-369-1444 X51146
5'-0"
DECOR GROUP
DAVE COOLEY
(248) 307-2430
(248) 307-2435 FAX
1'-0"
AMTICO TILE
DIANE FRANKOWSKI
440-356-1184
216-956-2747
404-267-1901
404-267-1900
LANDLORD
CONTRACTOR
R & B ELECTRONICS
BOX 782
IMPERIAL, PA 15126
724-695-1705
724-695-7306 FAX
PROVIDE
SURFACE MATERIALS
DWIGHT SEABRIGHT
800-231-3223
412-654-5227
440-519-1950
2"
3'-0"
NOT APPLICABLE
KARNDEAN INTERNATIONAL LLC
MIKE SULLIVAN
412-877-9282
888-266-4343
800-887-7043 FAX
MOHAWK/BIGELOW COMMERCIAL CARPET
MEGAN KELLY/JOYCE BEARSS
800-553-6045 X63054
877-244-8054 FAX
2"
3'-0"
7'-0"
BASE
ROOM NAME
FINISHES
JUNIORS
WALLS: PAINT PT1, WALL TRIM
BASE: B1
REFER TO A1/A4 FOR TRIM
LOCATIONS
GRAPHICS/WALLCOVERING
(WC1/WC5)
REFER TO A2/A4 FOR W/C,
GRAPHIC LOCATIONS
WALLS: PAINT PT1, WALL TRIM
BASE: B1
REFER TO A1/A4 FOR TRIM
LOCATIONS
GRAPHICS/WALLCOVERING
(WC4/WC2)
REFER TO A2/A4 FOR W/C,
GRAPHIC LOCATIONS
WALLS: PAINT PT1, WALL TRIM
BASE: B1
REFER TO A1/A4 FOR TRIM
LOCATIONS
GRAPHICS
REFER TO A2/A4 FOR
GRAPHIC LOCATIONS
WALLS: PAINT PT1, WALL TRIM
BASE: B1
REFER TO A1/A4 FOR TRIM
LOCATIONS
GRAPHICS
REFER TO A2/A4 FOR
GRAPHIC LOCATIONS
MENS
ACCESSORIES
FITTING
201
STORAGE
WALLS: PAINT PT1,
BASE: B1
202
CORRIDOR
WALLS: PAINT PT1,
BASE: B1
203
WOMEN
WALLS: PAINT PT1,
BASE: B1
204
MEN
WALLS: PAINT PT1,
BASE: B1
ARLINGTON, TX 76012
IF REQUIRED BY LANDLORD
+ (1)Ea. Door Closer 1460-HxAL (LCN)
PLASTIC
LAMINATE
(SLATWALL)
CM
PH: (817) 635-5696
STORE FRONT
DEMOLITION
STOREFRONT SIGNAGE
NEUTRAL PIERS & LANDLORD BULKHEAD
STOREFRONT SYSTEM
STOREFRONT GLASS
STOREFRONT DOORS
NOTE: AT ANY EXISTING DOORS TO BE REUSED, RE-PAINTED TO MATCH THE OTHERS.
ADD A NOTE TO REPAIR DOORS (FILL HOLES, ADJUST HINGES AND STRIKES, REPLACE
CLOSERS, ETC.) TO LIKE NEW CONDITION AND OPERATION.
NOTE: AT EXPOSED/STAINED CONCRETE FLOORS INSTALL UGL DRYLOK MASONRY
CRACK FILLER IN ALL CONTROL JOINTS AND FILL CRACKS, CHIPS, HOLES, ETC. 1/8”
OR WIDER/DEEPER PRIOR TO POLISHING
ACOUSTIC TILE
CEILING
PROVIDE
LANDLORD
CONTRACTOR
EXCELON VINYL TILE, COLOR: COOL WHITE 51899 -ORESSENTIALS TILE, COLOR: SILVER WHITE #121
3'-0"x5'-0"
CM
CHECKED:
NOTES
MECHANICAL - REFER TO MECHANICAL SHEETS (IF PROVIDED) FOR ADDITIONAL INFORMATION
HVAC UNITS
ROOF WORK
HVAC UNIT CURB
HVAC DISTRIBUTION - DUCTWORK, DIFFUSERS, ETC.
AIR BALANCING
EXHAUST FAN & VENTING
RETURN AIR GRILLES
HVAC SERVICE CALLS
LANDLORD TO WARRANT NEW EQUIPMENT FOR 1 YEAR FROM TURNOVER
SMOKE DETECTION
AS REQUIRED BY LOCAL ENFORCEMENT
HEAT DETECTION
SMOKE EVACUATION SYSTEM
FIRE SPRINKLER SHUT-OFF
SPRINKLER SYSTEM MODIFICATION
PLUMBING FIXTURES (HC ACCESSIBLE)
WATER & SEWER STUB/PIPING
ELECTRICAL - REFER TO ELECTRICAL SHEETS (IF PROVIDED) FOR ADDITIONAL INFORMATION
ELECTRICAL SERVICE
ELECTRICAL PANELS
WIRING, CIRCUITING, RECEPTACLES, SWITCHES, ETC.
EMERGENCY LIGHTING
REFER TO LIGHT FIXTURE SCHEDULE
INSTALL BREAKER LOCKS ON EMERGENCY CIRCUITS
LIGHT FIXTURES
REFER TO LIGHT FIXTURE SCHEDULE
LAMPS
REFER TO LIGHT FIXTURE SCHEDULE
EXIT SIGNS
INSTALL BREAKER LOCKS ON EMERGENCY CIRCUITS
REFER TO LIGHT FIXTURE SCHEDULE
METER SOCKET
TRANSFORMER
CONNECTION & WIRING OF CASHWRAP
CONNECTION & WIRING OF BACKWRAP
FIRE ALARM
AS REQUIRED BY LOCAL ENFORCEMENT
TELECOM/DATA LINES
11 CAT 5 LINES AS SHOWN
TELEPHONE, P.O.S. SYSTEM CONDUIT
TELEPHONE SYSTEM
POS SYSTEM
PANEL ALARM DEVICE AT REAR DOOR
REFER TO DOOR HARDWARE SCHEDULE
DOOR BUZZER AT STOCKROOM
REFER TO DOOR HARDWARE SCHEDULE
DOOR BUZZER CONTACT AT SALES FLOOR
REFER TO DOOR HARDWARE SCHEDULE
SENSORMATIC
SOUND SYSTEM
MAIN SIGN WHIP
SECONDARY SIGN WHIP
SIGN TIME SWITCH
FIXTURES
WALL STANDARDS
WALL MOUNTED SLATWALL
PERIMETER FIXTURE/WALL SYSTEM HARDWARE
CASHWRAP & BACKWRAP
CASH REGISTERS & EQUIPMENT
FREE STANDING FIXTURES
FITTING ROOM ACCESSORIES
FITTING ROOM BENCH
FITTING ROOM GRAB BARS
VISUAL FIXTURE/MANNEQUINS, ETC.
RESTROOM SHELVING KITS
ALL NON-SALES SHELVING/STANDARDS
SAFE
SHOPPING CENTER
TENANT SPACE
ANYWHERE USA
DAVINCI TILE COLLECTION, METALLIC BLUE MET11
BLUE. 12x12 TILE WITH VINYL 'GROUT'
FRAME
B
00000
DRAWN:
Project Coordination By:
KARNDEAN
INTERNATIONAL
FIRE
RATING NOTES
DOOR AND TRIM PROVIDED
-VENDOR-BLOCKING BY GC
DOOR AND TRIM PROVIDED
-VENDOR-BLOCKING BY GC
DOOR AND TRIM PROVIDED
-VENDOR-BLOCKING BY GC
DOOR AND TRIM PROVIDED
-VENDOR-BLOCKING BY GC
DOOR AND TRIM PROVIDED
-VENDOR-BLOCKING BY GC
DOOR
1
08-19-09
JOB NO:
SUPPLY TENANT'S
INSTALL GC
NOVA MATRIX, FRESCO SKY
DOOR TYPE SIZE
SUPPLY TENANT'S
INSTALL VENDOR
MOHAWK INDUSTRIES
INSTALL
MOHAWK INDUSTRIES
NOVA MATRIX, EARTHEN LAPIS, INSTALLER TO
PROVIDE REQUIRED ADHESIVES
MATERIAL
RESPONSIBILITY SCHEDULE
SUPPLY LANDLORD'S
INSTALL CONTRACTOR
VINYL TILE/
RUBBER FLOORING
DESCRIPTION
DOOR SCHEDULE & DOOR/FRAME TYPES
EXISTING
NOT APPLICABLE
CARPET
MANUFACTURER
PROVIDE
KEY
NOT APPLICABLE
MATERIAL
EXISTING
FINISH SCHEDULE
DATE
NOT FOR
CONSTRUCTION
REVISIONS
WALL TOGGLES AND HARDWARE BY GC
MILLWORK PACKAGE
MILLWORK PACKAGE
MILLWORK PACKAGE
MILLWORK PACKAGE
MILLWORK PACKAGE
DATA SHEET
MILLWORK PACKAGE
MILLWORK PACKAGE
FASTENED TO STOCK ROOM FLOOR, COORD. LOCATION WITH TENANT
SHEET NUMBER
DS
DATE
08-19-09
JOB NO:
00000
DRAWN:
CM
CHECKED:
CM
711 N. FIELDER RD.
ARLINGTON, TX 76012
PH: (817) 635-5696
SHOPPING CENTER
TENANT SPACE
ANYWHERE USA
Project Coordination By:
FAX: (817 635-5699
1
D1
DEMOLITION PLAN
Scale: 1/4" = 1'-0"
NOT FOR
CONSTRUCTION
•
•
•
•
Remove all pipes, tubes, bolts, conduit, etc. protruding
from the floor.
Remove all flooring materials (except mastic/glue)
before polishing starts.
Large surface repair (patching) using Mapei
(800-426-2734) Mapecem Quickpatch ($25/bag). Trowel
the Mapecem Quickpatch to a dense and smooth finish
suitable for polishing. Old repairs (patches) may need to
be redone as well using the Mapecem Quickpatch for
better polishing results.
Provide temporary lighting and water to jobsite.
REVISIONS
DEMOLITION
PLAN & NOTES
SHEET NUMBER
D1
18'-7 1 "
2
WOMEN
204
203
08-19-09
JOB NO:
00000
DRAWN:
CM
CHECKED:
CM
FIRST WALL
STANDARD
5'-0"
MEN
DATE
2213 SF
12'-0" WALL STANDARDS
AT 2'-0" ON CENTER
JUNIORS
G.C. IS REQUIRED TO COMPLETE A SITE VISIT PRIOR TO ANY BID
SUBMISSION FOR RUE 21 PROJECTS. NOTIFY LAMI GRUBB OR RUE
21 CONSTRUCTION DEPARTMENT OF SCOPE OMISSIONS OR
DISCREPENCIES
CORRIDOR
202
14
12'-4"
101
35
G.C. TO VERIFY LEASED SPACE DIMENSIONS AND EXISTING
BUILDING ELEMENTS FOR COMPLIANCE WITH DRAWINGS BEFORE
COMMENCING CONSTRUCTION. ANY DISCREPANCIES SHALL BE
IMMEDIATELY BROUGHT TO THE ATTENTION OF LAMI GRUBB FOR
RESOLUTION.
34
13
711 N. FIELDER RD.
ARLINGTON, TX 76012
PH: (817) 635-5696
3'-0"
FAX: (817 635-5699
6
16
15
17
18
Project Coordination By:
G.C. SHALL VERIFY ALL FIELD CONDITIONS AND SHALL HAVE SOLE
RESPONSIBILTY FOR VERIFICATION OF CLEAR HEIGHTS AND
CONDITIONS.
LAMP
POST
531 SF
DED.
CIRCUIT
11
7
STORAGE
6
DED.
CIRCUIT
201
LAMP
POST
5
6
31
DED.
CIRCUIT
976 SF
3'-0"
10'-0" WALL STANDARDS
AT 2'-0" ON CENTER
MENS
10'-4"
102
ACCESSORIES
5'-0"
103
1
WALL MOUNTED STANDARDS
SEE MOUNTING SCHED., REFER TO
TOGGLE DETAIL 6/A4. SCREWS BY GC
18
PROVIDE (1) DUPLEX RECEPTACLE
2
PAINT WALLS PT1, INSTALL BASE B1
REFER TO INTERIOR ELEVATIONS
19
RESTROOM(S)
TENANT'S
VENDOR
LANDLORD
CONTRACTOR
GENERAL
CONTRACTOR
INSTALL
PROVIDE
INSTALL
PROVIDE
DESCRIPTION
INSTALL
TAG
PROVIDE
NOTES
NOT APPLICABLE
PARTITION LEGEND
EXISTING
TENANT'S
VENDOR
LANDLORD
CONTRACTOR
GENERAL
CONTRACTOR
INSTALL
PROVIDE
INSTALL
PROVIDE
DESCRIPTION
Scale: 1/4" = 1'-0"
INSTALL
TAG
PROVIDE
NOTES
#
NOT APPLICABLE
KEY NOTES
EXISTING
TENANT'S
VENDOR
LANDLORD
CONTRACTOR
GENERAL
CONTRACTOR
INSTALL
PROVIDE
INSTALL
PROVIDE
INSTALL
PROVIDE
NOT APPLICABLE
DESCRIPTION
EXISTING
TAG
#
CROSS-HATCHING DENOTES NEW
PARTITIONS
NOTES
6" METAL STUDS, 16" O.C. TO
STRUCTURE ABOVE
20 GA TO HEIGHTS OF 18'
16 GA FOR ABOVE 18' HEIGHT
COMPLY WITH ALL APPLICABLE
ACCESSIBILITY CODES, SEE SHEET A4
5/8" DRYWALL, TYPE 'X' TO STRUCTURE ABOVE, AS
NEEDED FOR 1 HOUR SEPERATION PER UL U465
TAPE, SPACKLE, AND SAND SMOOTH,
READY FOR FINISH
3
SLATWALL SAWTOOTHS AND
DISPLAY PANELS
20
HI-LO DRINKING FOUNTAIN
COMPLY WITH ALL APPLICABLE
ACCESSIBILITY CODES
(1) COAT OF PRIMER, REFER TO
SHEETS A2/A4 FOR FINISHES
4
CASH WRAP
CENTER CASH WRAP ON DISPLAY
WALL BEHIND CASH DESK
21
MOP SINK
COMPLY WITH ALL APPLICABLE
ACCESSIBILITY CODES
MASONRY WALL
PAINT PT1, APPLY BASE B1
5
POWER/TELECOM FOR NEW CASH DESK
FROM ABOVE VIA MILLWORK RACEWAY
SEE SHEET F2 FOR WIRING LAYOUT:
TELECOM LINES BY TEN. VENDOR
22
WALL MOUNTED GRAB BARS- GC TO INSTALL
BLOCKING IN WALL AS NEEDED
COMPLY WITH ALL APPLICABLE
ACCESSIBILITY CODES
3-5/8" METAL STUDS, 16" O.C. TO
STRUCTURE ABOVE
20 GA TO HEIGHTS OF 18'
16 GA FOR ABOVE 18' HEIGHT
6
PROVIDE POWER ON DEDICATED CIRCUIT(S),
PROVIDE ORANGE RECEPTACLES
23
6'-0"x30"x3'-0"h FOLDING TABLE
5/8" DRYWALL TO STRUCTURE
ABOVE, BOTH SIDES
TAPE, SPACKLE, AND SAND SMOOTH,
READY FOR FINISH
7
TENANT'S SENSORMATIC SYSTEM-FULLY DEDICATED
CIRCUIT, NO SHARED NEUTRAL, LINE OR GROUND
LABEL BREAKERS AT PANEL, INSTALL
BREAKER LOCKS
PROVIDE A RECEPTACLE ABOVE THE
CEILING FOR POWER
24
PROVIDE (1) QUAD RECEPTACLE,
COORDINATE LOCATION WITH TENANT
(1) COAT OF PRIMER, REFER TO
SHEETS A2/A4 FOR FINISHES
8
SWITCH BANK LOCATION-SWITCHES FOR
ALL SALES FLOOR LIGHTING CIRUITS
25
12" DEEP ADJUSTABLE SHELVES ABOVE
TABLE
3-5/8" METAL STUDS, 16" O.C. TO
CEILING GRID
BRACE TO STRUCTURE ABOVE AS
NEEDED
9
STOREFRONT SYSTEM
5/8" DRYWALL ON ALL EXPOSED
SURFACES
TAPE, SPACKLE, AND SAND SMOOTH,
READY FOR FINISH
(1) COAT OF PRIMER, REFER TO
SHEETS A2/A4 FOR FINISHES
APPLY BASE B1 TO WALL AFTER
FINISHING
26
MUZAK EQUIPMENT
10
INSTALL THERMOSTAT(S) ON MILLWORK
RACEWAY
RELOCATE IF ALREADY EXISTING
PRIOR TO INSTALLING WALL FINISHES
27
EQUIPMENT RACK
11
MIRROR 60" TALL MIRROR AT 12" AFF,
TYPICAL
APPLY DAP CLEAR CAULK AT ALL
EXPOSED EDGES
28
POSTER HOLDER
12
ELECTRICAL RECEPTACLES (20'+/- O.C. IN SALES
AREA) AS SHOWN, WHITE COVERS/PLUGS)
29
1 1/4" ROUND (RIGID PIPE) x8' LONG HANGING ROD
INSTALL IN DATA CABINET
APPLY BASE B1
BOLT DOWN TO FLOOR, INSTALL
UNDER DATA CABINET
50X100 ETC PROTOTYPE
VERSION 2010, 01-01-10
JUNIORS (SF)
MENS (SF)
2213 SF (44%)
976 SF (19%)
2213 SF (44%)
ACCESSORIES (SF)
795 SF (16%)
795 SF (16%)
FITTING (SF)
STOCK ROOM (SF)
275 SF (6%)
531 SF (11%)
275 SF (6%)
531 SF (11%)
976 SF (19%)
RESTROOMS/CORRIDOR (SF) 210 SF (4%)
5000 SF (100%)
TOTAL AREA (SF)
210 SF (4%)
5000 SF (100%)
JUNIORS STANDARDS (LF)
138 LF
46 LF
138 LF
46 LF
68 LF
68 LF
8 LF
8 LF
MENS STANDARDS (LF)
SLATWALL (LF)
ETC STANDARDS (LF)
REVISIONS
LESS THAN
9'-4" AFF
TOP OF STANDARD
AT CEILING HEIGHT
CUT DOWN
AS NEEDED
9'-4" TO
11'-0" AFF
TOP OF STANDARD
AT CEILING HEIGHT
9'-0" LONG
STANDARDS
11'-6" AFF
AND HIGHER
TOP OF STANDARD
AT 11'-0" AFF
INSTALL TRIM AT
11'-0" AFF*
(1) COAT OF PRIMER, REFER TO
SHEETS A2/A4 FOR FINISHES
APPLY BASE B1 TO WALL AFTER
FINISHING
CREATE FRT PLYWOOD PLATFORM
ABOVE RESTROOMS
WALL STANDARDS TO BE INSTALLED AT 2'-0" O.C. U.N.O.
SEE INTERIOR ELEVATIONS FOR ADDITIONAL CLARIFICATION
TAPE, SPACKLE, AND SAND SMOOTH,
READY FOR FINISH
14
SET TIMER PRIOR TO TURNOVERCOORDINATE TIMES W/TENANT
31
BASE TRIM B1 AT BASE OF CASH WRAP
3-5/8" METAL STUDS, 16" O.C. TO
8'-0" AFF
15
TELEPHONE PUNCH BOARD LOCATION
TENANT TO GET TELEPHONE COMPANY
TO INSTALL LINES TO THIS LOCATION
32
CLEAN/SAND COLUMNS SMOOTH, PAINT PT3
(GRAY)
5/8" WATER RESISTANT DRYWALL TO
CEILING, ALL EXPOSED SURFACES
16
RUN INTERIOR LINES TO BOARD, USE
PLENUM RATED WIRE WHERE REQUIRED
GC TO PROVIDE 4'X4' FIRE
RETARDANT TREATED PLYWOOD BD.
33
DATA CABINET-PROVIDE POWER TO
LOCATION SHOWN @ 48" AFF, SEE SHEET F3
17
TENANT'S BURGLAR ALARM SYSTEM PANEL
34
RETRIEVER HOOKS-MOUNT AT 84" AFF, SEE
SHEET F4
MOUNTING WITH TOGGLES, REFER
TO TOGGLE DETAIL, SHEET A4
35
DOOR BUZZER
RING ON SALES FLOOR (ABOVE C/W)
AND STOCK ROOM (ABOVE DESK)
(1) COAT OF PRIMER, (2) COATS OF
PAINT PT1
APPLY BASE B1
3-5/8" METAL STUDS, 16" O.C. TO
8'-0" AFF
APPLY 1x6 PAINT GRADE CAP, PAINT
PT3
5/8" DRYWALL TO 8'-0" AFF, BOTH
SIDES
TAPE, SPACKLE, AND SAND SMOOTH,
READY FOR FINISH
(1) COAT OF PRIMER, REFER TO
SHEETS A2/A4 FOR FINISHES
APPLY BASE B1
NOT FOR
CONSTRUCTION
WALL STANDARD MOUNTING SCHEDULE:
TAPE, SPACKLE, AND SAND SMOOTH,
READY FOR FINISH
SIGN TIME SWITCH (PARAGON 7000 SERIES
OR APPROVED EQUAL)
2" CONDUIT IN WALL FROM WALL BOX
TO 12'-6" AFF AND TURN OUT TO FRONT
STORE CHARACTERISTICS:
5/8" DRYWALL ON ALL EXPOSED
SURFACES
ELECTRICAL EQUIPMENT
SAFE
APPLY BASE B1
6" METAL STUDS TO CEILING GRID
SUSPEND FROM ABOVE USING ALLTHREAD MOUNTED AT 10'-0" AFF, SEE F4
13
30
FIRST WALL
STANDARD
FLOOR PLAN
1
A1
KEY NOTES
SHOPPING CENTER
TENANT SPACE
ANYWHERE USA
4
* TRIM PROVIDED BY TENANT'S VENDOR, INSTALLED BY GC,
SEE SHEET A4 FOR LOCATIONS AND FINISHES
CONSTRUCTION
PLAN & PARTITION
INDEX
SHEET NUMBER
A1
DATE
08-19-09
JOB NO:
00000
DRAWN:
CM
CHECKED:
CM
711 N. FIELDER RD.
ARLINGTON, TX 76012
PH: (817) 635-5696
FAX: (817 635-5699
5
1
A2
EXTENT OF TENANT FLOORING
4
GRAY VINYL TRANSITION STRIP
5
INSTALL CONTROL JOINT FILLER IN
ALL CONTROL JOINTS IN SALES AREA
6
PREFINISHED TRIM AT EDGES OF
GRAPHIC
7
PERMANENTLY DELINEATE 44" MIN.
WIDE PATH OF EGRESS ON FLOOR
8
WALK-OFF MAT
TENANT'S
VENDOR
LANDLORD
CONTRACTOR
Scale: 1/4" = 1'-0"
BARE CONCRETE
STOCK ROOM
FLOORING
BLACK VINYL
TRANSITION STRIP
NEW CARPET SALES
AREA FLOORING
NEW CARPET SALES
AREA FLOORING
EXISTING CONCRETE
SLAB, PREPARE AS
NEEDED FOR NEW
FLOORING
EXISTING CONCRETE
SLAB, PREPARE AS
NEEDED FOR NEW
FLOORING
STOREFRONT DOOR
SADDLE
NEW RUBBER
FLOORING
EXISTING CONCRETE
SLAB, PREPARE AS
NEEDED FOR NEW
FLOORING
GENERAL
CONTRACTOR
INSTALL
3
INSTALL
RUN FLOORING INTO FITTING
ROOMS
PROVIDE
2
INSTALL
WALL MOUNTED
GRAPHICS/WALLCOVERINGS
PROVIDE
DESCRIPTION
1
PROVIDE
TAG
NOT APPLICABLE
#
EXISTING
KEY NOTES
FINISH PLAN
BLACK TRANSITION
STRIP (ROPPE #50
OR EQUAL)
NEW RUBBER/VINYL
FLOORING
SHOPPING CENTER
TENANT SPACE
ANYWHERE USA
WC2-BLUE
5
10'-4" TREES GRAPHIC
10'-4" WC2
Project Coordination By:
5
10'-4" STREET SCENE GRAPHIC
5
WC1-GREEN
10'-4" WC1
WC1-GREEN
NOTES
2
A2
FLOOR TRANSITION DETAIL
3
A2
Scale: 6" = 1'-0"
SEE INSTALLATION NOTE
4
A2
Scale: 6" = 1'-0"
MALL
DETAIL-CONCRETE
SCHLUTER SCHIENE
TRANSITION STRIP
UGL DRYLOK MASONRY CRACK FILLER IN ALL
CONTROL JOINTS PRIOR TO FINISHING FLOOR
FLOOR TRANSITION DETAIL
FEATHER DOWN
FROM MALL FLOOR
LEVEL TO STORE
SLAB HEIGHT
EXISTING MALL
FLOOR
NOT FOR
CONSTRUCTION
REVISIONS
FLOOR TRANSITION DETAIL
Scale: 6" = 1'-0"
MALL DETAIL
ZINC TRANSITION
STRIP
NEW RUBBER
FLOORING
EXISTING MALL
FLOOR
FLOOR COVERING
PLAN AND
DETAILS
SHEET NUMBER
MARK 'KEEP CLEAR AT ALL TIMES'
EXISTING CONCRETE
SLAB, PREPARE AS
NEEDED FOR NEW
FLOORING
2
A2
FLOOR TRANSITION DETAIL
Scale: 6" = 1'-0"
EXISTING CONCRETE
SLAB, PREPARE AS
NEEDED FOR NEW
FLOORING
4
A2
FLOOR TRANSITION DETAIL
Scale: 6" = 1'-0"
A2
F
DATE
08-19-09
JOB NO:
00000
DRAWN:
CM
CHECKED:
CM
F
711 N. FIELDER RD.
ARLINGTON, TX 76012
PH: (817) 635-5696
TRACK=8'
Cx4
TRACK=8'
Cx4
Project Coordination By:
FAX: (817 635-5699
A
TR
CK
4'
=
C
A
TR
SHOPPING CENTER
TENANT SPACE
ANYWHERE USA
x3
11
CK
4'
=
C
x3
1
SUSPENDED CEILING ELEMENT,
HUNG FROM SUSPENDED CEILING
SYSTEM, SEE SHEET F4
2
COMPLETE HVAC SYSTEM
3
COMPLETE SPRINKLER SYSTEM
4
INSTALL TRACKS APPROXAMITELY
4IN. FROM STOREFRONT
5
TENANT'S BANNER HANGING SYSTEM, MUST BE
MOUNTED HIGHER THAN STOREFRONT GLASS HT.
6
DRYWALL CEILING IN RESTROOM
7
OPEN TO STRUCTURE ABOVE
INSTALL
75w or 16W CFL
PAR 30
D
23W CFL
E
23W CFL
TENANT'S
VENDOR
LANDLORD
CONTRACTOR
GENERAL
CONTRACTOR
INSTALL
C
INSTALL
(2) 32W T8
A
PROVIDE
B
SYMBOL
INSTALL
A
(3) 32W T8
4100 K
PROVIDE
LAMP
PROVIDE
TAG
EXISTING
TENANT'S
VENDOR
LANDLORD
CONTRACTOR
GENERAL
CONTRACTOR
PROVIDE
INSTALL
PROVIDE
INSTALL
PROVIDE
NOT APPLICABLE
DESCRIPTION
EXISTING
TAG
#
Scale: 1/4" = 1'-0"
EXG=EXISTING TO REMAIN
WHERE FIXTURES ARE EXISTING TO REMAIN, REPLACE
FIXTURES/BALLASTS AS NEEDED FOR LIKE-NEW
APPEARANCE AND OPERATION
LIGHT FIXTURE SCHEDULE
KEY NOTES
CEILING PLAN
NOT APPLICABLE
1
A3
TENANT'S VENDOR TO PROVIDE NEW
4100K LAMPS (VERIFY WITH GC IN
FIELD EXACT STYLE/TYPE OF EXISTING
LAMPS), TENANT GC TO INSTALL
TYPE
DESCRIPTION
Lay-In Fluorescents
2'x4' 3-LAMP WITH ELECTRONIC
BALLASTS ACRYLIC LENSES
NOTES
Strip Fluorescents
8' STRIP LIGHTING WITH
ELECTRONIC BALLASTS. SURFACE
MOUNTED TO CEILING
Track lights
HALO POWER TRAC LIGHTING SYSTEMS
#L1730PX LINE VOLTAGE TRACKS &
HEADS, CEILING MOUNTED
24 LINEAR FOOT OF TRACK PER EACH
20 AMP CIRCUIT MAXIMUM
Wall Mounted
Street Lights
WALL SCONCES, INSTALL IN
LOCATIONS SHOWN,
PAINT ALL EXPOSED SCREW HEADS
BLACK, INSTALL AFTER INSTALLATION
OF WALLCOVERING/FIXTURING
Lamp Post
FLOOR MOUNTED LAMP POST
FIXTURE
PAINT ALL EXPOSED SCREW HEADS
BLACK
Combo Light/Fan
COMBINATION LIGHT AND EXHAUST
FAN, COLOR: WHITE
Recessed Lights
RECESSED LIGHT, WHITE TRIM,
SPECULAR REFLECTOR
NOT FOR
CONSTRUCTION
NOTES
40LBS TOTAL, HUNG WITH 6 MOUNTING
CLIPS/WIRE CAPABLE OF 40LBS EACH
MOUNT ON 6" CABLES
AS REQ'D BY LOCAL ENFORCEMENT
FOR REQUIRED COVERAGES
HANGING RAILS MOUNTED TO CEILING,
INSTALL ALL PROVIDED CLIPS
B
C#
D
E
F
100W TYPE-A
F
8
TENANT SIGNAGE
GC TO PROVIDE BLOCKING AS NEEDED
FOR INSTALLATION OF SIGNAGE
9
PROVIDE DEDICATED CIRCUIT
ROUTED THROUGH TIME CLOCK
TENANT GC TO PROVIDE ADDITIONAL
CIRCUIT/POWER FOR INTERIOR SIGN
10
SECURITY CAMERA DOMES
INSTALL IN CEILING TILE
11
SUSPENDED CEILING ELEMENT, REFER TO SHEET F4
MOUNT ON 6" CABLES
12
PROVIDE ACCESS PANEL FOR ACCESS/SERVICING
OF HOT WATER HEATER ABOVE RESTROOMS
FLUSH MOUNTED, SIZED FOR POTENTIAL
REPLACEMENT OF HWH, PAINT PT1
13
METAL STUD BRACING BETWEEN WALLS ENCASED
IN DRYWALL TO ALIGN WITH FITTING ROOM
WALLS BELOW
PAINT PT1
G
X
75W PAR30
G
LED
X
Y
(2) ADJUSTABLE
HEADS
Y
Y1
(2) ADJUSTABLE
HEADS
Y1
EXIT SIGN WITH BATTERY BACKUP
INSTALL BREAKER LOCKS
ONCIRCUITS FOR EMERGENCY
LIGHTING
Emergency Lights
CEILING MOUNTED EMERGENCY
LIGHTING WITH BATTERY BACKUP
INSTALL BREAKER LOCKS
ONCIRCUITS FOR EMERGENCY
LIGHTING
Emergency Lights
WALL MOUNTED EMERGENCY
LIGHTING WITH BATTERY BACKUP
INSTALL BREAKER LOCKS
ONCIRCUITS FOR EMERGENCY
LIGHTING
Exit Sign
REVISIONS
CEILING/LIGHTING
PLAN AND
SCHEDULES
SHEET NUMBER
A3
13
ANGLED
VIEW
ANGLED
VIEW
ANGLED
VIEW
08-19-09
JOB NO:
00000
DRAWN:
CM
CHECKED:
CM
12'-0" CEILING HEIGHT
7'-0"
8'-4"
11'-0"
2'-8"
STREET SCENE GRAPHIC
DATE
711 N. FIELDER RD.
ARLINGTON, TX 76012
PH: (817) 635-5696
CAULK ALL JOINTS, PUTTY NAIL HOLES, SAND
SMOOTH, TOUCH-UP AFFECTED AREAS
2
WALL STANDARDS
INSTALL PER SCHEDULE, SEE SHEET
A1 AND TOGGLE DETAIL
3
WALL SCONCES
SEE MOUNTING DETAIL, SHEET A4
4
WALL COVERINGS/GRAPHICS
INSTALL PRIOR TO STANDARDS,
INSTALLATION SIMILAR TO WALL PAPER
5
WALL MOUNTED
SLATWALL/SAWTOOTHS
CAULK ALL JOINTS, PUTTY NAIL HOLES, SAND
SMOOTH, REPAINT AFFECTED AREAS
6
1X6 WOOD CAP ON TOP OF FITTING
ROOM WALLS
CAULK ALL JOINTS, PUTTY NAIL HOLES, SAND
SMOOTH, REPAINT AFFECTED AREAS
7
INSTALL ALUMINUM KICKPLATE
PAINT DOOR AND FRAME PT3 (GRAY)
8
LAMP POST
9
SENSORMATIC SYSTEM
INTERIOR ELEVATION
9
A4
INTERIOR ELEVATION
Scale: 1/4" = 1'-0"
NOTES
POWER TO BE RUN BY CONTRACTOR
10
STOREFRONT SYSTEM
11
1 1/2" CLEAR PLASTIC CORNER
GUARDS, MOUNTED WITH SCREWS
WALL PROTEX, OR EQUAL, INSTALL AT
ALL EXPOSED CORNERS, 8' LENGTHS
12
MIRROR
AT 12" AFF, 60" TALL
13
CUT DOWN GRAPHICS EQUALLY
FROM TOP AND BOTTOM AS NEEDED
TRIM PICTURES EQUALLY SO ALL ARE
EQUAL, WHERE NEEDED
INTERIOR ELEVATION
8
A4
Project Coordination By:
INSTALL
TENANT'S
VENDOR
GENERAL
CONTRACTOR
PROVIDE
1X4 PRE-FINISHED TRIM, MOUNTED AT 11'-0"
AFF, SEE ELEVS. FOR COLOR LOCATIONS
Scale: 1/4" = 1'-0"
Scale: 1/4" = 1'-0"
WALLCOVERING
4
4
4
4
2'-0"
3
A4
2
INSTALL WALL
COVERING/GRAPHIC
PRIOR TO
INSTALLATION OF
STANDARDS, JOINT IN
MATERIALS TO ALIGN
WITH CENTER OF
WALL STANDARDS
12'-0" CEILING HEIGHT
7'-0"
2
3
2
1'-0"
CL
1'-0"
WALL STANDARDS,
MOUNT AT 2'-0" O.C.
WALL SCONCE, MOUNT
WITH BOTTOM OF
GLOBE AT 7'-0" AFF
(6'-7" AFF TO CENTER
OF J/BOX), INSTALL
GRAPHIC PRIOR TO
INSTALLATION OF
SCONCES
2
INTERIOR ELEVATION
7
A4
Scale: 1/4" = 1'-0"
GREEN TRIM
GRAPHIC
4
TREES GRAPHIC
2
FAX: (817 635-5699
SHOPPING CENTER
TENANT SPACE
ANYWHERE USA
7
INSTALL
DESCRIPTION
1
5
7'-0" AFF
12'-0" CEILING HEIGHT
7'-0"
3
7
5
TAG
4
RUE 21 GRAPHIC
#
LANDLORD
CONTRACTOR
KEY NOTES
PROVIDE
Scale: 1/4" = 1'-0"
BLUE GRAPHIC
2
A4
5
INTERIOR ELEVATION
4
2
5
INSTALL
5
NOT APPLICABLE
1
A4
2
PROVIDE
3
EXISTING
2
WALL SCONCE DETAIL
Scale: NOT TO SCALE
NOT FOR
CONSTRUCTION
GREEN TRIM
3'-3"
1'-9"
36" GRAB
BAR
6"
3'-0"
1'-5"
8"
INTERIOR ELEVATION
Scale: 1/4" = 1'-0"
1'-6"
5
A4
LEVER
HANDLE
FAUCET
6" BASE
VINYL COVE
BASE
8
4
A4
3'-4"
2'-9"
2'-4"
TOILET
2'-9"
3'-3"
TP HOLDER
TOILET
RESTROOM DETAILS
Scale: 1/2" = 1'-0"
REVISIONS
4' TALL FRP
PANELS ON ALL
WALLS (WHITE)
1'-0"
1'-6"
3'-6"
ADA MIRROR
ROLL PAPER
TOWEL DISP.
3'-0"
8'-0"
42" GRAB BAR
WALL STANDARDS WITH
(2) WHITE MELAMINE
SHELVES, PROVIDED BY
TENANT'S VENDOR,
INSTALLED BY TENANT GC
3'-6"
ADA
SINK
PIPE
WRAP
1'-6"
MIN. CLEAR
3'-4"
4' TALL FRP
PANELS ON ALL
WALLS (WHITE)
RUN ACROSS
2'-10"
10
TOGGLE BOLTS TO BE AS MANUFACTURED
BY "THE TOGGLER". INSTALL (1)
TOGGLE/SCREW IN EVERY HOLE IN EACH
STANDARD (13 TOTAL) AND USE SCREWS
WITH FLAT HEAD (NOT ROUNDED).
TOGGLES AND SCREWS AVAILABLE FROM
FASTENAL (WWW.FASTENAL.COM OR
507-454-5374:
TOGGLES:
FASTENAL #50955
SCREWS:
FASTENAL #0149015
6
A4
TOGGLE BOLT DETAIL
Scale: NOT TO SCALE
INTERIOR
ELEVATIONS AND
DETAILS
SHEET NUMBER
A4
DATE
08-19-09
JOB NO:
00000
DRAWN:
CM
CHECKED:
CM
711 N. FIELDER RD.
ARLINGTON, TX 76012
PH: (817) 635-5696
SHOPPING CENTER
TENANT SPACE
ANYWHERE USA
Project Coordination By:
FAX: (817 635-5699
NOT FOR
CONSTRUCTION
REVISIONS
FITTING ROOM
DETAILS
SHEET NUMBER
F1
DATE
08-19-09
JOB NO:
00000
DRAWN:
CM
CHECKED:
CM
711 N. FIELDER RD.
ARLINGTON, TX 76012
PH: (817) 635-5696
SHOPPING CENTER
TENANT SPACE
ANYWHERE USA
Project Coordination By:
FAX: (817 635-5699
NOT FOR
CONSTRUCTION
REVISIONS
CASH WRAP
DETAILS
SHEET NUMBER
F2
DATE
08-19-09
JOB NO:
00000
DRAWN:
CM
CHECKED:
CM
711 N. FIELDER RD.
ARLINGTON, TX 76012
PH: (817) 635-5696
SHOPPING CENTER
TENANT SPACE
ANYWHERE USA
Project Coordination By:
FAX: (817 635-5699
NOT FOR
CONSTRUCTION
REVISIONS
CASH WRAP
DETAILS
SHEET NUMBER
F2
DATE
08-19-09
JOB NO:
00000
DRAWN:
CM
CHECKED:
CM
711 N. FIELDER RD.
ARLINGTON, TX 76012
PH: (817) 635-5696
SHOPPING CENTER
TENANT SPACE
ANYWHERE USA
Project Coordination By:
FAX: (817 635-5699
NOT FOR
CONSTRUCTION
REVISIONS
BACK OF HOUSE
LAYOUT AND
DETAILS
SHEET NUMBER
F3
DATE
08-19-09
JOB NO:
00000
DRAWN:
CM
CHECKED:
CM
ROOF DECK
711 N. FIELDER RD.
JOISTS
ARLINGTON, TX 76012
PH: (817) 635-5696
FAX: (817 635-5699
UNISTRUT BETWEEN
JOISTS
10'-0" AFF
PIPE HANGER
SUSPENDED GRAPHIC DETAILS
2
F4
Scale: N.T.S
TRACK FASTENED TO
BLOCKING ABOVE
CEILING
PIPE HANGER DETAIL
Scale: 3" = 1'-0"
SHOPPING CENTER
TENANT SPACE
ANYWHERE USA
1
F4
1 1/2" RIGID PIPE
TIE-WIRE TO
STRUCTURE ABOVE TO
SUPPORT
GRID/FIXTURES
FIRE RETARDANT TREATED
BLOCKING BETWEEN
CEILING GRID MEMBERS
15/16" SUSPENDED
CEILING GRID
ACOUSTIC CEILING
TILE
ACOUSTIC CEILING
TILE
LIGHTING TRACK,
FASTENED TO CEILING
GRID USING ERICO
4G8WH TWIST ON
TRACK LIGHTING CLIPS
LIGHTING TRACK,
FASTENED TO CEILING
GRID USING ERICO
4G8WH TWIST ON
TRACK LIGHTING CLIPS
Project Coordination By:
ALL-THREAD
NOT FOR
CONSTRUCTION
3
F4
TRACK LIGHT MOUNTING DETAIL
Scale: 3" = 1'-0"
4
F4
RETRIEVER HOOK
REVISIONS
Scale: N.T.S.
FIXTURE DETAILS
SHEET NUMBER
F4