KEY PLAN DATE 08-19-09 JOB NO: 00000 DRAWN: CM CHECKED: CM SITE MAP 711 N. FIELDER RD. TENANT LOCATION ARLINGTON, TX 76012 PH: (817) 635-5696 FAX: (817 635-5699 CENTER LOCATION GENERAL NOTES 2. G.C. SHALL COORDINATE HIS WORK WITH THAT OF THE UTILITY COMPANIES, AND ALSO COORDINATE THE WORK OF ALL TRADES, PROVIDING ACCESS AS REQUIRED. G.C. SHALL PAY FOR ALL TRASH SERVICES, BE RESPONSIBLE FOR THE REMOVAL OF DEBRIS FOR ALL TRADES, AND FOR KEEPING THE JOB SITE CLEAN AT ALL TIMES. 4. SCHEDULE - PROVIDE A CONSTRUCTION TIME SCHEDULE SHOWING ALL PHASES OF THE WORK INCLUDING THAT OF THE MILLWORK CONTRACTOR, THE OWNER'S SUPPLIED MATERIAL AND ALL SUBCONTRACTORS. A PRELIMINARY SCHEDULE SHOULD BE ATTACHED TO BID SUBMITTAL. MINIMUM INTERFERENCE - ALL WORK SHALL BE PERFORMED SO AS TO CAUSE A MINIMUM OF INTERFERENCE WITH ANY OTHER TENANTS AND THE OPERATION OF THE LANDLORD'S ENTIRE PREMISES. CONTRACTOR SHALL TAKE ALL PRECAUTIONARY STEPS TO PROTECT THE FACILITIES ON THE PREMISES AND THE FACILITIES OF OTHERS AFFECTED BY PERFORMANCE OF THE WORK AND POLICE SAME PROPERLY. 7. CONSTRUCTION EQUIPMENT AND MATERIALS ARE TO BE LOCATED IN CONFINED AREAS AND TRUCK TRAFFIC IS TO BE ROUTED IN AND FROM THE SITE AS DIRECTED BY THE LANDLORD. THE COST OF THE WORK SHALL INCLUDE ANY OVERTIME NECESSITATED BY THESE REQUIREMENTS. 8. 13. CUTTING AND REPAIR: ALL CUTTING, DRILLING, OR REMOVALS REQUIRED TO REMOVE, RELOCATE, ALTER OR INSTALL ANY WORK, EQUIPMENT, WIRING, APPLIANCES, ETC., AND UPON COMPLETION, REPAIRING, PATCHING AND FINISHING ALL SURFACES TO A NEW CONDITION SHALL BE DONE BY THE CONTRACTOR PER THE SPECIFICATIONS. ALL SURFACES, INCLUDING THOSE DAMAGED DURING THE WORK, REQUIRING SAME SHALL BE PATCHED AND REFINISHED TO A NEW CONDITION TO THE ARCHITECT'S OR TENANT'S APPROVAL. 15. CLEANING: G.C. SHALL REMOVE ALL CONSTRUCTION RUBBISH, SCAFFOLDING, EQUIPMENT, TEMPORARY PROTECTION, TEMPORARY FIELD STRUCTURES, AND ANYTHING ELSE THAT WAS REQUIRED IN CONNECTION WITH THE CONSTRUCTION, BUT NOT A PERMANENT PART THEREOF. T.G.C. SHALL MAINTAIN ORDERLY HOUSEKEEPING DURING THE PROCESS OF CONSTRUCTION, AND UPON COMPLETION SHALL THOROUGHLY CLEAN ALL AREAS. FINAL CLEANUP SHALL INCLUDE THE FOLLOWING: SWEEP, DAMP MOP, AND WAX RESILIENT FLOORING. DUST, DIRT, PAINT DRIPPINGS, OIL, GREASE, AND OTHER BLEMISHES SHALL BE REMOVED FROM ALL SURFACES, INCLUDING PIPING AND EQUIPMENT. WINDOWS, GLASS UNITS, GLASS DOORS AND MIRRORS SHALL BE WASHED. PAINT OVERRUNS AND PUTTY SMEARS SHALL BE REMOVED. HARDWARE SHALL BE RUBBED CLEAN WITH A FLANNEL CLOTH. 22. ANY DISCREPANCIES, ERRORS, OR OMISSIONS DISCOVERED IN THE CONTRACT DOCUMENTS BY THE CONTRACTOR SHALL BE BROUGHT TO THE ATTENTION OF THE TENANT & LAMI-GRUBB BEFORE PROCEEDING WITH RELATED WORK. OTHERWISE, THE CORRECTION OF SUCH ITEMS WILL BE THE RESPONSIBILITY OF THE CONTRACTOR. 23. TIME IS OF THE ESSENCE AND THE CONTRACTOR SHALL KEEP SUFFICIENT PERSONNEL ON THE JOB AT ALL TIMES TO PERFORM THE WORK IN THE MOST EXPEDITIOUS MANNER CONSISTENT WITH GOOD WORKMANSHIP, AND SOUND BUSINESS PRACTICE. THE CONTRACTOR A. PROGRESS SCHEDULE B. LIST OF ALL SUBCONTRACTORS C. COPIES OF BUILDING PERMIT AND ANY OTHER REQUIRED AUTHORIZATIONS AND LICENSES BY GOVERNING AUTHORITIES. ARCHITECT WILL OBTAIN AND PAY FOR THE STATE PERMIT, THE GC WILL OBTAIN AND PAY FOR THE BUILDING PERMIT ABBREVIATIONS (100'-0") FINISH FLOOR (ELEVATION) EXISTING PARTITION TO BE REMOVED LANDLORD COLUMN LINE B.1 ELEVATION NUMBER AND DIRECTION INDICATION LEASE LINE NEW DOOR DETAIL OR SECTION NUMBER EXISTING DOOR DIRECTION DETAIL IS TAKEN 2 DOOR NUMBER AB1 FINISH NUMBER 4 FIXTURE NUMBER 3 PARTITION TYPE SHEET DETAIL IS DRAWN ON LINE OF VENEER PANELING SHALL CONFIRM THAT ALL ITEMS WILL BE ORDERED, FABRICATED, AND INSTALLED PRIOR TO THE AGREED COMPLETION DATE. EXCEPTIONS WILL NOT BE ALLOWED WITHOUT WRITTEN AUTHORIZATION OF THE OWNER PRIOR TO PLACEMENT OF ORDER. 24. THERE SHALL BE NO SUBSTITUTION OF MATERIALS WHERE A MANUFACTURER IS SPECIFIED. WHERE THE TERM "OR APPROVED EQUAL" IS USED, THE ARCHITECT ALONE SHALL DETERMINE SUITABILITY BASED UPON INFORMATION SUPPLIED BY CONTRACTOR. 25. ALL WORK SHALL BE ERECTED AND INSTALLED PLUMB, LEVEL, SQUARE, AND TRUE, AND IN PROPER ALIGNMENT. 26. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE FURNISHING AND INSTALLATION OF ALL BRACING AND BLOCKING OF WALLS, RECEIVING WOODWORK, SHELVING, ETC. GENERAL CONTRACTOR TO COORDINATE THE LOCATION OF SAID BRACING AND BLOCKING WITH OWNER. 27. GENERAL CONTRACTOR TO PROVIDE BLOCKING AT BASE OF STORE FIXTURES, FILES, FREESTANDING WOODWORK, ETC. TO ALIGN THESE ITEMS WHERE THERE ARE DIFFERENCES IN THE FLOOR LEVEL. 28. THESE GENERAL CONDITIONS SHALL APPLY TO ALL WORK AND ALL DRAWINGS IN THIS SET, AND SHALL EXTEND TO ANY CHANGES, EXTRAS, OR ADDITIONS AGREED TO DURING THE COURSE OF THE WORK. 29. THE G.C. SHALL MEET WITH AN AUTHORIZED REPRESENTATIVE OF THE LANDLORD AND SHALL REVIEW LANDLORD CONSTRUCTION REQUIREMENTS. G.C. SHALL COORDINATE HIS WORK WITH THE LANDLORD WITH REGARD TO TEMPORARY UTILITIES, ALLOWABLE MATERIAL, TRAFFIC ROUTES, STORAGE OF TOOLS AND MATERIALS, USE OF TOILET FACILITIES, HOURS IN WHICH WORK IS ALLOWED, NOISE AND DUST CONTROL, CLEANUP AND OTHER MATTERS REQUIRING ADHERENCE TO LANDLORD REQUIREMENTS. 30. G.C. SHALL REVIEW WITH THE LANDLORD'S REPRESENTATIVE THE MANNER IN WHICH ALL CONNECTIONS TO STRUCTURE WILL BE MADE. ANY PENETRATIONS IN THE BUILDING ENVELOPE OR STRUCTURE SHALL BE REVIEWED WITH THE LANDLORD AND APPROVED IN WRITING. IF THE LANDLORD REQUIRES THAT PORTIONS OF WORK BE PERFORMED BY IT'S OWN CONTRACTOR, G.C. SHALL INCUR ALL COSTS ASSOCIATED WITH THAT PORTION OF THE WORK UNLESS STATED OTHERWISE IN WRITING BY THE OWNER. 31. G.C. SHALL BE RESPONSIBLE TO THE LANDLORD FOR ANY DAMAGE OCCURRING TO ANY OF THE LANDLORD'S FACILITIES BEFORE DURING OR AFTER CONSTRUCTION PROCEDURES CAUSED BY THE CONTRACTOR, HIS EMPLOYEES OR HIS SUBCONTRACTORS. 33. SAFETY SCAFFOLDING SHALL BE BUILT IN ACCORDANCE WITH REQUIREMENTS OF ALL FEDERAL, STATE, AND LOCAL LAWS. ALL TEMPORARY SHORING REQUIRED FOR THE REMOVAL OF EXISTING WORK FOR THE INSTALLATION OF NEW WORK SHALL BE INCLUDED IN THE CONTRACT. CONTRACTOR SHALL BE RESPONSIBLE FOR THIS WORK AND SHALL MAKE GOOD ANY DAMAGE CAUSED BY IMPROPER SUPPORT OR FAILURE OF SHORING IN ANY RESPECT. DURING PERFORMANCE OF WORK, G.C. IS RESPONSIBLE FOR PROVISION AND MAINTENANCE OF WARNING SIGNS, LIGHT SIGNAL DEVICES, GUARD LIGHTS, BARRICADES, GUARD RAILS, FENCES AND OTHER DEVICES AS APPROPRIATELY LOCATED ON AND AROUND THE JOB SITE WHICH WILL GIVE PROPER AND UNDERSTANDABLE WARNING TO ALL PERSONS WITH REGARD TO HAZARDOUS CONDITIONS, EQUIPMENT AND OPERATIONS BEING PERFORMED IN CONJUNCTION WITH THE G.C.'S WORK. ALL WARNING DEVICES SHALL COMPLY WITH O.S.H.A. AND OTHER APPLICABLE GOVERNMENTAL REGULATIONS AS REQUIRED FOR THE CONSTRUCTION PROCEDURES AND CONDITIONS ENCOUNTERED. INSOFAR AS JOB SITE SAFETY IS CONCERNED, THE ARCHITECT IS RESPONSIBLE SOLELY FOR HIS OWN AND HIS EMPLOYEES ACTIVITIES ON THE JOB SITE, BUT THIS SHALL NOT BE CONSTRUED TO RELIEVE THE OWNER OR ANY CONSTRUCTION CONTRACTORS FROM THEIR RESPONSIBILITIES FOR MAINTAINING A SAFE JOB SITE. NEITHER THE PROFESSIONAL ACTIVITIES OF THE ARCHITECT, NOR THE PRESENCE OF THE ARCHITECT OR HIS EMPLOYEES AND SUBCONTRACTORS, SHALL BE CONSTRUED TO IMPLY THE ARCHITECT HAS ANY RESPONSIBILITY FOR METHODS OF WORK PERFORMANCE, SUPERINTENDENT, SEQUENCING OF CONSTRUCTION, OR SAFETY IN, ON OR ABOUT THE JOB SITE. THE OWNER AGREES THAT THE G.C. IS SOLELY RESPONSIBLE FOR JOB SITE SAFETY AND WARRANTS THAT THE ARCHITECT SHALL BE MADE AN ADDITIONAL INSURED UNDER THE G.C.'S GENERAL LIABILITY INSURANCE POLICY. 34. G.C. TO COORDINATE ALL WORK WITH LAMI - GRUBB. 35. G.C. SHALL BE RESPONSIBLE FOR ANY CONSTRUCTION DEPOSITS REQUIRED BY THE LANDLORD WHETHER REFUNDABLE OR NOT. 36. G.C. TO VERIFY LEASE SPACE DIMENSIONS & EXISTING BUILDING ELEMENTS FOR COMPLIANCE WITH THE DRAWINGS BEFORE COMMENCING CONSTRUCTION. ANY DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT OR ENGINEER FOR RESOLUTION OF DIMENSIONAL CONFLICTS AND COMPONENT LOCATIONS. NO CHANGE ORDERS WILL BE ISSUED FOR CHANGES REQUIRED IN THE WORK AFTER CONSTRUCTION HAS COMMENCED UNLESS SPECIFICALLY AUTHORIZED BY THE ARCHITECT/ENGINEER AND THE OWNER. 32. APPLICABLE STANDARDS OF CONSTRUCTION INDUSTRY HAVE SAME FORCE AND EFFECT ON PERFORMANCE OF THE WORK AS IF COPIED DIRECTLY INTO CONTRACT DOCUMENTS OR BOUND AND PUBLISHED THEREWITH. COMPLY WITH STANDARDS IN EFFECT AS OF THE DATE OF CONTRACT DOCUMENTS, UNLESS OTHERWISE INDICATED. D. COPY OF INSURANCE COVERAGE TO TENANT AND LANDLORD'S REP. SYMBOLS 1 A2 21. VERIFY ALL DIMENSIONS AS THEY APPLY TO EXISTING CONDITIONS WITH PARTICULAR EMPHASIS ON DIMENSIONS MARKED "VERIFY" OR VERIFY IN FIELD (V.I.F.). NOTIFY TENANT & LAMI - GRUBB IMMEDIATELY OF ANY DISCREPANCIES BETWEEN THE DRAWINGS AND EXISTING CONDITIONS. BEFORE START OF CONSTRUCTION, THE GENERAL CONTRACTOR IS TO SUBMIT THE FOLLOWING: CONTRACTOR TO PROVIDE ARCHITECT, TENANT, AND LANDLORD'S REPRESENTATIVE WITH A COMPLETE & ACCURATE SET OF AS-BUILT 1 A1 20. LAYOUT WORK AND BE RESPONSIBLE FOR ALL LINES, ELEVATIONS, MEASUREMENTS OF THE BUILDING, UTILITIES, AND OTHER WORK EXECUTED UNDER THE CONTRACT. 17. SCHEDULE OF REQUIRED SUBMITTALS: 10. CONTRACTOR TO PROVIDE ALL SUBCONTRACTORS WITH A COMPLETE SET OF THE MOST CURRENT CONSTRUCTION DOCUMENTS. REVISION NUMBER BY UNIT VALUES BASED ON THE ITEMIZED COST BREAKDOWN BY COST PLUS A PERCENTAGE FEE. 19. LOCATE ALL EXISTING UTILITY SERVICE LINES (INCLUDING TELEPHONE LINES) AND PROTECT THEM THROUGHOUT THE CONSTRUCTION PERIOD. CLEARLY MARK ALL SUBMISSIONS WITH DATE, PROJECT, CONTACT, AND SUBCONTRACTOR AND ALLOW SPACE FOR APPROVAL DRAWING AND SPECIFICATIONS: A COMPLETE SET OF THE DRAWINGS INCLUDING APPROVED SHOP DRAWINGS SHALL BE KEPT AT THE SITE FOR THE DURATION OF THE WORK. COPIES, OR ORIGINALS IF REQUIRED, OF ALL PERMITS AND APPROVALS SHALL ALSO BE KEPT AT THE SITE. STOREFRONT CLOSURE OR COLUMN LINE A. B. 16. SHOP DRAWINGS AND SAMPLES: WHERE CALLED FOR IN THE DOCUMENTS, SUBMIT TO LAMI - GRUBB FOR APPROVAL. THE ENCLOSURE BARRICADE WILL BE CONSTRUCTED BY THE LANDLORD PRIOR TO START OF CONSTRUCTION, OR WILL INSTALL STOREFRONT TO BE USED AS THE CLOSURE NEW PARTITION (ARCHITECTURAL PLAN) THE UNDERSIGNED AGREES THAT THERE MAY BE CHANGES, OMISSIONS, OR MODIFICATIONS IN THE WORK AND THAT APPROPRIATE ADJUSTMENTS WILL BE MADE IN THE CONTRACT PRICE. THE UNDERSIGNED ALSO AGREES THAT THE CHARGES FOR ALL EXTRA WORK OR CREDITS SHALL BE DETERMINED, AT OWNER'S CHOICE, IN ONE OF THE FOLLOWING WAYS: UPON COMPLETION OF THE WORK, ALL SURFACES, INCLUDING FLOORS, WALLS, GLASS, FIXTURES AND FITTINGS SHALL BE CLEAN AND READY TO USE. G.C. TO PROVIDE AN OPERATIONAL FACSIMILE MACHINE ON SITE OR HAVE A FAX AVAILABLE, LOCATED CLOSE TO SITE, PRIOR TO THE START OF CONSTRUCTION. 1 NOTE: ALL SUBSTITUTIONS ARE TO BE APPROVED BY LAMI - GRUBB AND THE OWNER. 18. CHANGES: TEMPORARY FACILITIES: EXISTING PARTITION TO REMAIN SUBMIT CATALOGUE CUTS OR SAMPLES OF ANY SUBSTITUTIONS. 14. PATCHING: CONTRACTOR SHALL ARRANGE AND PAY FOR AND MAINTAIN ANY NEEDED TEMPORARY FACILITIES AT THE PREMISES INCLUDING ELECTRICAL SERVICE, TRASH REMOVAL, PROTECTION, ENCLOSURE BARRICADE, USE OF ELEVATORS, AIR CONDITIONING AND HEATING, TELEPHONE & FAX AT THE PREMISES FOR THE DURATION OF THE WORK. 9. A. SIGN SHOP DRAWINGS B. SHOP DRAWINGS SHOWING CONSTRUCTION, DETAILS, AND PROFILES C. EVIDENCE OF COMPLIANCE WITH FIRE RETARDANT ASSEMBLY D. BUILDERS HARDWARE: HARDWARE SCHEDULE E. SIGN WORK: SAMPLE OF ALL LETTERING F. SPRINKLERS: SHOP DRAWING SHOWING SPRINKLER HEAD LOCATIONS, PIPING AND VALVES. G. HVAC: SHOP DRAWINGS AND CATALOGUE CUTS SHOWING DUCTWORK AND ALL HVAC EQUIPMENT, INCLUDING REGISTERS AND DIFFUSERS. 12. G.C. SHALL BE RESPONSIBLE FOR A SMOOTH TRANSITION BETWEEN THE STORE FLOOR AND THE MALL FLOOR. SHOULD THE GENERAL CONTRACTOR REQUIRE THE WOODWORK CONTRACTORS TO FIELD MEASURE, ANY COSTS SHALL BE BORNE BY THE GENERAL CONTRACTOR. 6. THE GENERAL CONTRACTOR IS TO SUBMIT SHOP DRAWINGS, SAMPLES AND/OR CATALOGUE CUTS OF ALL ITEMS REQUIRED, INCLUDING THE FOLLOWING: CONTRACTOR SHALL, FOR THE DURATION OF THE WORK, KEEP ON THE PREMISES A COMPETENT FULL-TIME GENERAL FOREMAN OR SUPERINTENDENT SATISFACTORY TO THE OWNER. G.C. SHALL EXAMINE THE EXISTING UTILITY CONDITIONS STUB-INS OR ACCESS TO UTILITIES AND VERIFY WITH INFORMATION SHOWN ON THESE DRAWINGS. ANY DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT OR ENGINEER PRIOR TO THE BID SUBMITTAL. 3. 5. 11. SUPERVISION: SHOPPING CENTER TENANT SPACE ANYWHERE USA 1. Project Coordination By: BUILD TO SUIT EXTERIOR STRIP CENTER ANYWHERE USA ACT ADJ AFF ALUM ARCH BD BLDG BLKG CLG CL CLR COL CONC CONST CONT DEMO DTL DIA DIM DN DWG DF EA ELEC EQ. EWH EQUIP EXIST EXT FC FCIC FT FL FLUOR FOIC FRT ACOUSTICAL TILE ADJUSTABLE ABOVE FINISHED FLOOR ALUMINUM ARCHITECT(URAL) BOARD BUILDING BLOCKING CEILING CENTER LINE CLEAR COLUMN CONCRETE CONSTRUCTION CONTINUOUS DEMOLITION DETAIL DIAMETER DIMENSION DOWN DRAWING DRINKING FOUNTAIN EACH ELECTRIC(AL) EQUAL ELECTRIC WATER HEATER EQUIPMENT EXISTING EXTERIOR FIXTURE CONTRACTOR FURNISHED BY CONTRACTOR INSTALLED BY CONTRACTOR FEET FLOOR FLUORESCENT FURNISHED BY OWNER INSTALLED BY CONTRACTOR FIRE RETARDANT TREATED FURN FURN/INST GA GC GWB GYP BD HDWE HT HC HM HR HWH IC IN INSUL INT LAV LL LT LTG LIN MFR MAX MECH MTL MEZZ MIN MISC MTD NIC NTS OC PTN PL PL LAM PLG PLYWD PROV FURNISH FURNISHED/INSTALLED GAUGE GENERAL CONTRACTOR GYPSUM WALL BOARD GYPSUM BOARD HARDWARE HEIGHT HOLLOW CORE HOLLOW METAL HOUR HOT WATER HEATER INSTALLED BY CONTRACTOR INCH INSULATION INTERIOR LAVATORY LANDLORD LIGHT LIGHTING LINEAR MANUFACTURE(R) MAXIMUM MECHANICAL METAL MEZZANINE MINIMUM MISCELLANEOUS MOUNTED NOT IN CONTRACT NOT TO SCALE ON CENTER PARTITION PLASTIC LAMINATE PLASTIC LAMINATE PLUMBING PLYWOOD PROVIDE(D) BUILDING REVIEW QTY R REQ RES REV RTU SCHED SECT SF SFC SHT SIM SC SPECS STD STRUCT SUSP TBD TEMP TGC T&G TYP UNO VCT VIF VERT WC W/ W/O WD PROJECT DATA DRAWING INDEX SITE LOCATION QUANTITY RADIUS REQUIRED RESILIENT REVISION ROOFTOP UNIT SCHEDULE SECTION SQUARE FEET STOREFRONT CONTRACTOR SHEET SIMILAR SOLID CORE SPECIFICATION(S) STANDARD STRUCTURAL SUSPENDED TO BE DETERMINED TEMPERED TENANT'S GENERAL CONTRACTOR TONGUE & GROOVE TYPICAL UNLESS NOTED OTHERWISE VINYL COMPOSITION TILE VERIFY IN FIELD VERTICAL WALLCOVER WITH WITHOUT WOOD RUE 21 VANILLA BOX DRAWING EXTERIOR STRIP CENTER ANYWHERE USA TENANT RUE 21 800 COMMONWEALTH DRIVE WARRENDALE, PA 15086 TEL: (724) 776-7475 FAX: (724) 776-3580 CONTACT: SKIP MERRITT TENANT COORDINATOR LANDLORD LANDLORD STREET ADDRESS LANDLORD CITY, STATE ZIP CONTACT: LANDLORD CONTACT TEL: LANDLORD TEL NUMBER PROJECT COORDINATION LAMI - GRUBB PROJECT MANAGEMENT, INC. 100 EAST SWISSVALE AVE. PITTSBURGH, PA 15218 TEL: (412) 243-3430 FAX: (412) 371-1586 CONTACT: MARC SIDES (603-778-3840) APPLICABLE CODES: Building Code Mechanical Code Plumbing Code Electrical Code Fire/Life Safety Code Fuel and Gas Code Accessibility Code 2006 INTERNATIONAL BUILDING CODE 2006 INTERNATIONAL MECHANICAL CODE 2006 INTERNATIONAL PLUMBING CODE 2005 NATIONAL ELECTRIC CODE 2006 INTERNATIONAL FIRE CODE 2006 INTERNATIONAL FUEL AND GAS CODE ANSI A117.1/ADAAG REQUIREMENTS T1 TITLE SHEET DS DATA SHEET A1 A2 A3 A4 FLOOR PLAN AND MISC NOTES FLOOR FINISH PLAN AND DETAILS CEILING PLAN AND MISC NOTES INTERIOR ELEVATIONS F1 F2 F3 F4 FITTING ROOM DETAILS CASH WRAP DETAILS BACK OF HOUSE DETAILS FIXTURE DETAILS M0 M1 M2 M3 MECHANICAL TITLE SHEET MECHANICAL PLAN PLUMBING PLANS MECHANICAL SPECIFICATIONS E0 E1 E2 E3 ELECTRICAL TITLE SHEET LIGHTING PLAN POWER PLAN ELECTRICAL SPECIFICATIONS NOT FOR CONSTRUCTION REVISIONS TITLE SHEET SHEET NUMBER T1 AMTICO TECHNO ZINC STUD DP38 WITH VINYL 'GROUT' ECO SURFACES #3598 CUSTOM BLEND OF ECO NIGHTS RUBBER SHEET GOODS, ADHESIVES PROVIDED BY TENANT'S VENDOR CONGOLEUM ALTERNATIVES 12x12 VINYL TILE, MULTI-BERRY, ADHESIVES PROVIDED BY TENANT'S VENDOR ARMSTRONG -ORMANNINGTON CONCRETE STAIN AMTICO GZ11 STARDUST WHITE AMTICO MR30 MARCASITE N/A POLISHED CONCRETE FINISH, ACHIEVE A HIGH GLOSS FINISH ARTCRETE (318-379-2000) APPLY (2) COATS ARTCRETE FAUX BRICK DC2500 CLEAR SEALER APPLIED OVER EX'G CONCRETE SLAB PAINT (APPLY PRIMER AND 2 COATS OF PAINT) WALLCOVERING ARMSTRONG or USG 3 B 2'-10 3/4"x5'-0" WD WD 4 B 2'-10 3/4"x5'-0" WD WD 5 B 2'-10 3/4"x5'-0" WD WD 6 EXG 3'-0"x7'-0" H.M. H.M. -- 7 A 3'-0"x7'-0" H.M. H.M. -- 8 A 3'-0"x7'-0" H.M. H.M. -- 9 A 3'-0"x7'-0" H.M. H.M. -- 10 11 A -- 3'-0"x7'-0" H.M. H.M. -- 6'-0"x7'-0" H.M./GL. H.M. -- TENANT'S VENDOR LANDLORD CONTRACTOR GENERAL CONTRACTOR INSTALL WD PROVIDE WD INSTALL 2'-10 3/4"x5'-0" PROVIDE B INSTALL 2 PROVIDE WD NOT APPLICABLE EXISTING TENANT'S VENDOR TENANT GC INSTALL PROVIDE INSTALL WD BY TENANT'S BY TENANT'S BY TENANT'S BY TENANT'S BY TENANT'S GENERAL BUILDING PERMIT OTHER PERMITS, FEES, INSURANCE CLEAN-UP & FINAL CLEANING TRASH REMOVAL & DUMPSTER CONCRETE SLAB - STRUCTURAL TEMPORARY BARRICADES PAINT DOOR AND FRAME PT3 (GRAY) PAINT DOOR AND FRAME PT3 (GRAY) PAINT DOOR AND FRAME PT3 (GRAY) PAINT DOOR AND FRAME PT3 (GRAY) 2x4 #533 CIRRUS SQUARE EDGE, COLOR: WHITE --OR-2X4 #2310 RADAR SQUARE EDGE, COLOR: WHITE INSTALLED IN NEW 15/16" GRID, WHITE ALL HARDWARE IS "SCHLAGE" IF NOT NOTED OTHERWISE + (3)Ea. Self Closing Hinges + (1)Ea. Lockset AL80PD-SAT 11-05 10-001 626 (Keyed Alike) GENERAL CONSTRUCTION DEMOLITION TRENCHING OF EXISTING SLAB DEMISING WALL STUDS DEMISING WALL GWB GWB, METAL STUDS, ETC. CARPENTRY, ROUGH AND FINISH Door # 1: * REFER TO SHEET F1 FOR JAMB/BLOCKING DETAILS + (3)Ea. Butt Hinges ARMSTRONG NEW 2x4 LAY-IN TILE #533 CIRRUS, COLOR: WHITE INSTALLED IN NEW 15/16" GRID, WHITE ICI PAINTS EUROPEAN WHITE #30YY 67/084, EGGSHELL FINISH, SEMI-GLOSS FINISH AT DOORS/TRIM + (1)Ea. 36" Grab Bar - Bobrick - B - 5806x36 SHERWIN WILLIAMS SW 6993 BLACK OF NIGHT, SEMI-GLOSS FINISH SHERWIN WILLIAMS SW 7073 NETWORK GRAY, SEMIGLOSS FINISH AT TRIMS, EGGSHELL ON WALLS Door # 6: + (1)Ea. Panic Bar CUSTOM RUE 21 GREEN BENJAMIN MOORE #782 BLUE BELLE, SEMIGLOSS FINISH AT TRIMS, EGGSHELL ON WALLS TOWER CONTRACT CUSTOM VINYL WALLCOVERING, METEOR TYPE 1, COLOR: V-14508 (GREEN) COMMAND VINYL WALLCOVERING, BRUSHED METAL CM36-9916 COLOR: SLATE (BLUE) TOWER CONTRACT VINYL WALLCOVERING, METEOR TYPE 1, COLOR: PLATINUM (GRAY) ARC COM VERGANO ACW-51294 #14 BLACK ONYX (MENS) SURFACE MATERIALS CUSTOM VINYL WALLCOVERING, V-43482 (JUNIORS) 711 N. FIELDER RD. FORMICA BLACK FORMICA #6909-58 GLASS PLASTIQUE MATTE FINISH LIRI #V35 ESSE FORGET ME NOT LIRI #314 ESSE ALPINE GREEN + (1)Ea. Lockset AL80PD-SAT 11-05 10-001 626 (Keyed Alike) BLOCKING AND FURRING SALES AREA ACOUSTIC TILE CEILING SALES AREA DRYWALL CEILING & APPLICABLE FRAMING MIRRORS DOORS & FRAMES DOOR HARDWARE FITTING ROOM DOORS AND TRIM FITTING ROOM DOOR HARDWARE FITTING ROOM PARTITIONS PAINTING COLORED WALLCOVERINGS WALL GRAPHICS SUSPENDED GRAPHIC ELEMENT (AT CASH WRAP) REDUCER STRIP ADHESIVES, ETC. FLOOR PREPARATION FLOOR PROTECTION VINYL BASE RESTROOM FLOORING TOILET ACCESSORIES FIRE EXTINGUISHERS-TAGGED BY INSPECTION COMPANY WALL TOGGLERS/TOGGLE BOLTS + (1)Ea. Door Closer 1460-H AL (LCN) + (1)Ea. Peep hole 700B26D (IVES) + (1)Ea. Door Buzzer LA201 (NUTONE) + (1)Ea. Cover Plate/Blank on Exterior + (1)Ea. Kickplate K1062 16"x34"xUS32D (Rockwood Mfg.) + (1)Provide exterior tenant identification sign per LL standards + (1) Pryguard + (1) Weatherstripping (exterior doors only) + (1) Door Sweep (exterior doors only) Door # 7 & 10: + (1)Ea. Push/Pull Plate 73CLx(4"x16")xUS32D (Rockwood Mfg.) FAX: (817 635-5699 ELECTRIC SERVICE TO SIGN BY EC REFER TO DOOR SCHEDULE REFER TO PARTITION LEGEND REFER TO PARTITION LEGEND REFER TO PARTITION LEGEND REFER TO FINISH SCHEDULE REFER REFER REFER REFER REFER REFER TO TO TO TO TO TO APPLY DAP CLEAR CAULK AT ALL EXPOSED EDGES DOOR SCHEDULE DOOR HARDWARE SCHEDULE DOOR SCHEDULE ***BLOCKING PROVIDED/INSTALLED BY GC*** DOOR HARDWARE SCHEDULE PARTITION LEGEND FINISH SCHEDULE REFER TO FINISH SCHEDULE (2) MIN., COORDINATE FINAL LOCATIONS WITH LOCAL ENFORCEMENT REFER TO DETAIL 6/A4 JOHNSONITE VINYL BASE TRIM, #28 MEDIUM GRAY + (1)Ea. Kickplate K1062 16"x34"xUS32D (Rockwood Mfg.) + (1)Ea. Door Stop 517xUS26D (Rockwood Mfg.) Door # 8 & 9: + (3)Ea. Butt Hinges + (1)Ea. Privacy AL40s-SAT 2-3/4" ASA 626 + (1)Ea. Door Closer 1461-H-AL (LCN) Door 11: + (2)Ea. Kickstand door stops #460 (Rockwood Mfg.) CITY LIGHTING CHRIS SCHMALZRIED 800-257-2922 412-366-7609 FAX ICS PAT O'DEA (440) 951-9919 (440) 951-6978 FAX 102 103 104 2" 7'-0" Typical New Frame GENERAL CONTRACTOR INSTALL TAG 101 INSTALL SENSORMATIC GARY 800-241-6678 724-746-1627 FAX EXISTING ROOM FINISH SCHEDULE TENANT'S VENDOR C PROVIDE ECONOCO HANK 800-645-7032 X338 877-279-3300 FAX B INSTALL GERBERT LIMITED /ECO SURFACES STAN STEFANSKI 800-522-0980 724-935-4539 FAX A PROVIDE VECTOR SECURITY CHIP MARKOWSKY 703-369-1444 X51146 5'-0" DECOR GROUP DAVE COOLEY (248) 307-2430 (248) 307-2435 FAX 1'-0" AMTICO TILE DIANE FRANKOWSKI 440-356-1184 216-956-2747 404-267-1901 404-267-1900 LANDLORD CONTRACTOR R & B ELECTRONICS BOX 782 IMPERIAL, PA 15126 724-695-1705 724-695-7306 FAX PROVIDE SURFACE MATERIALS DWIGHT SEABRIGHT 800-231-3223 412-654-5227 440-519-1950 2" 3'-0" NOT APPLICABLE KARNDEAN INTERNATIONAL LLC MIKE SULLIVAN 412-877-9282 888-266-4343 800-887-7043 FAX MOHAWK/BIGELOW COMMERCIAL CARPET MEGAN KELLY/JOYCE BEARSS 800-553-6045 X63054 877-244-8054 FAX 2" 3'-0" 7'-0" BASE ROOM NAME FINISHES JUNIORS WALLS: PAINT PT1, WALL TRIM BASE: B1 REFER TO A1/A4 FOR TRIM LOCATIONS GRAPHICS/WALLCOVERING (WC1/WC5) REFER TO A2/A4 FOR W/C, GRAPHIC LOCATIONS WALLS: PAINT PT1, WALL TRIM BASE: B1 REFER TO A1/A4 FOR TRIM LOCATIONS GRAPHICS/WALLCOVERING (WC4/WC2) REFER TO A2/A4 FOR W/C, GRAPHIC LOCATIONS WALLS: PAINT PT1, WALL TRIM BASE: B1 REFER TO A1/A4 FOR TRIM LOCATIONS GRAPHICS REFER TO A2/A4 FOR GRAPHIC LOCATIONS WALLS: PAINT PT1, WALL TRIM BASE: B1 REFER TO A1/A4 FOR TRIM LOCATIONS GRAPHICS REFER TO A2/A4 FOR GRAPHIC LOCATIONS MENS ACCESSORIES FITTING 201 STORAGE WALLS: PAINT PT1, BASE: B1 202 CORRIDOR WALLS: PAINT PT1, BASE: B1 203 WOMEN WALLS: PAINT PT1, BASE: B1 204 MEN WALLS: PAINT PT1, BASE: B1 ARLINGTON, TX 76012 IF REQUIRED BY LANDLORD + (1)Ea. Door Closer 1460-HxAL (LCN) PLASTIC LAMINATE (SLATWALL) CM PH: (817) 635-5696 STORE FRONT DEMOLITION STOREFRONT SIGNAGE NEUTRAL PIERS & LANDLORD BULKHEAD STOREFRONT SYSTEM STOREFRONT GLASS STOREFRONT DOORS NOTE: AT ANY EXISTING DOORS TO BE REUSED, RE-PAINTED TO MATCH THE OTHERS. ADD A NOTE TO REPAIR DOORS (FILL HOLES, ADJUST HINGES AND STRIKES, REPLACE CLOSERS, ETC.) TO LIKE NEW CONDITION AND OPERATION. NOTE: AT EXPOSED/STAINED CONCRETE FLOORS INSTALL UGL DRYLOK MASONRY CRACK FILLER IN ALL CONTROL JOINTS AND FILL CRACKS, CHIPS, HOLES, ETC. 1/8” OR WIDER/DEEPER PRIOR TO POLISHING ACOUSTIC TILE CEILING PROVIDE LANDLORD CONTRACTOR EXCELON VINYL TILE, COLOR: COOL WHITE 51899 -ORESSENTIALS TILE, COLOR: SILVER WHITE #121 3'-0"x5'-0" CM CHECKED: NOTES MECHANICAL - REFER TO MECHANICAL SHEETS (IF PROVIDED) FOR ADDITIONAL INFORMATION HVAC UNITS ROOF WORK HVAC UNIT CURB HVAC DISTRIBUTION - DUCTWORK, DIFFUSERS, ETC. AIR BALANCING EXHAUST FAN & VENTING RETURN AIR GRILLES HVAC SERVICE CALLS LANDLORD TO WARRANT NEW EQUIPMENT FOR 1 YEAR FROM TURNOVER SMOKE DETECTION AS REQUIRED BY LOCAL ENFORCEMENT HEAT DETECTION SMOKE EVACUATION SYSTEM FIRE SPRINKLER SHUT-OFF SPRINKLER SYSTEM MODIFICATION PLUMBING FIXTURES (HC ACCESSIBLE) WATER & SEWER STUB/PIPING ELECTRICAL - REFER TO ELECTRICAL SHEETS (IF PROVIDED) FOR ADDITIONAL INFORMATION ELECTRICAL SERVICE ELECTRICAL PANELS WIRING, CIRCUITING, RECEPTACLES, SWITCHES, ETC. EMERGENCY LIGHTING REFER TO LIGHT FIXTURE SCHEDULE INSTALL BREAKER LOCKS ON EMERGENCY CIRCUITS LIGHT FIXTURES REFER TO LIGHT FIXTURE SCHEDULE LAMPS REFER TO LIGHT FIXTURE SCHEDULE EXIT SIGNS INSTALL BREAKER LOCKS ON EMERGENCY CIRCUITS REFER TO LIGHT FIXTURE SCHEDULE METER SOCKET TRANSFORMER CONNECTION & WIRING OF CASHWRAP CONNECTION & WIRING OF BACKWRAP FIRE ALARM AS REQUIRED BY LOCAL ENFORCEMENT TELECOM/DATA LINES 11 CAT 5 LINES AS SHOWN TELEPHONE, P.O.S. SYSTEM CONDUIT TELEPHONE SYSTEM POS SYSTEM PANEL ALARM DEVICE AT REAR DOOR REFER TO DOOR HARDWARE SCHEDULE DOOR BUZZER AT STOCKROOM REFER TO DOOR HARDWARE SCHEDULE DOOR BUZZER CONTACT AT SALES FLOOR REFER TO DOOR HARDWARE SCHEDULE SENSORMATIC SOUND SYSTEM MAIN SIGN WHIP SECONDARY SIGN WHIP SIGN TIME SWITCH FIXTURES WALL STANDARDS WALL MOUNTED SLATWALL PERIMETER FIXTURE/WALL SYSTEM HARDWARE CASHWRAP & BACKWRAP CASH REGISTERS & EQUIPMENT FREE STANDING FIXTURES FITTING ROOM ACCESSORIES FITTING ROOM BENCH FITTING ROOM GRAB BARS VISUAL FIXTURE/MANNEQUINS, ETC. RESTROOM SHELVING KITS ALL NON-SALES SHELVING/STANDARDS SAFE SHOPPING CENTER TENANT SPACE ANYWHERE USA DAVINCI TILE COLLECTION, METALLIC BLUE MET11 BLUE. 12x12 TILE WITH VINYL 'GROUT' FRAME B 00000 DRAWN: Project Coordination By: KARNDEAN INTERNATIONAL FIRE RATING NOTES DOOR AND TRIM PROVIDED -VENDOR-BLOCKING BY GC DOOR AND TRIM PROVIDED -VENDOR-BLOCKING BY GC DOOR AND TRIM PROVIDED -VENDOR-BLOCKING BY GC DOOR AND TRIM PROVIDED -VENDOR-BLOCKING BY GC DOOR AND TRIM PROVIDED -VENDOR-BLOCKING BY GC DOOR 1 08-19-09 JOB NO: SUPPLY TENANT'S INSTALL GC NOVA MATRIX, FRESCO SKY DOOR TYPE SIZE SUPPLY TENANT'S INSTALL VENDOR MOHAWK INDUSTRIES INSTALL MOHAWK INDUSTRIES NOVA MATRIX, EARTHEN LAPIS, INSTALLER TO PROVIDE REQUIRED ADHESIVES MATERIAL RESPONSIBILITY SCHEDULE SUPPLY LANDLORD'S INSTALL CONTRACTOR VINYL TILE/ RUBBER FLOORING DESCRIPTION DOOR SCHEDULE & DOOR/FRAME TYPES EXISTING NOT APPLICABLE CARPET MANUFACTURER PROVIDE KEY NOT APPLICABLE MATERIAL EXISTING FINISH SCHEDULE DATE NOT FOR CONSTRUCTION REVISIONS WALL TOGGLES AND HARDWARE BY GC MILLWORK PACKAGE MILLWORK PACKAGE MILLWORK PACKAGE MILLWORK PACKAGE MILLWORK PACKAGE DATA SHEET MILLWORK PACKAGE MILLWORK PACKAGE FASTENED TO STOCK ROOM FLOOR, COORD. LOCATION WITH TENANT SHEET NUMBER DS DATE 08-19-09 JOB NO: 00000 DRAWN: CM CHECKED: CM 711 N. FIELDER RD. ARLINGTON, TX 76012 PH: (817) 635-5696 SHOPPING CENTER TENANT SPACE ANYWHERE USA Project Coordination By: FAX: (817 635-5699 1 D1 DEMOLITION PLAN Scale: 1/4" = 1'-0" NOT FOR CONSTRUCTION • • • • Remove all pipes, tubes, bolts, conduit, etc. protruding from the floor. Remove all flooring materials (except mastic/glue) before polishing starts. Large surface repair (patching) using Mapei (800-426-2734) Mapecem Quickpatch ($25/bag). Trowel the Mapecem Quickpatch to a dense and smooth finish suitable for polishing. Old repairs (patches) may need to be redone as well using the Mapecem Quickpatch for better polishing results. Provide temporary lighting and water to jobsite. REVISIONS DEMOLITION PLAN & NOTES SHEET NUMBER D1 18'-7 1 " 2 WOMEN 204 203 08-19-09 JOB NO: 00000 DRAWN: CM CHECKED: CM FIRST WALL STANDARD 5'-0" MEN DATE 2213 SF 12'-0" WALL STANDARDS AT 2'-0" ON CENTER JUNIORS G.C. IS REQUIRED TO COMPLETE A SITE VISIT PRIOR TO ANY BID SUBMISSION FOR RUE 21 PROJECTS. NOTIFY LAMI GRUBB OR RUE 21 CONSTRUCTION DEPARTMENT OF SCOPE OMISSIONS OR DISCREPENCIES CORRIDOR 202 14 12'-4" 101 35 G.C. TO VERIFY LEASED SPACE DIMENSIONS AND EXISTING BUILDING ELEMENTS FOR COMPLIANCE WITH DRAWINGS BEFORE COMMENCING CONSTRUCTION. ANY DISCREPANCIES SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF LAMI GRUBB FOR RESOLUTION. 34 13 711 N. FIELDER RD. ARLINGTON, TX 76012 PH: (817) 635-5696 3'-0" FAX: (817 635-5699 6 16 15 17 18 Project Coordination By: G.C. SHALL VERIFY ALL FIELD CONDITIONS AND SHALL HAVE SOLE RESPONSIBILTY FOR VERIFICATION OF CLEAR HEIGHTS AND CONDITIONS. LAMP POST 531 SF DED. CIRCUIT 11 7 STORAGE 6 DED. CIRCUIT 201 LAMP POST 5 6 31 DED. CIRCUIT 976 SF 3'-0" 10'-0" WALL STANDARDS AT 2'-0" ON CENTER MENS 10'-4" 102 ACCESSORIES 5'-0" 103 1 WALL MOUNTED STANDARDS SEE MOUNTING SCHED., REFER TO TOGGLE DETAIL 6/A4. SCREWS BY GC 18 PROVIDE (1) DUPLEX RECEPTACLE 2 PAINT WALLS PT1, INSTALL BASE B1 REFER TO INTERIOR ELEVATIONS 19 RESTROOM(S) TENANT'S VENDOR LANDLORD CONTRACTOR GENERAL CONTRACTOR INSTALL PROVIDE INSTALL PROVIDE DESCRIPTION INSTALL TAG PROVIDE NOTES NOT APPLICABLE PARTITION LEGEND EXISTING TENANT'S VENDOR LANDLORD CONTRACTOR GENERAL CONTRACTOR INSTALL PROVIDE INSTALL PROVIDE DESCRIPTION Scale: 1/4" = 1'-0" INSTALL TAG PROVIDE NOTES # NOT APPLICABLE KEY NOTES EXISTING TENANT'S VENDOR LANDLORD CONTRACTOR GENERAL CONTRACTOR INSTALL PROVIDE INSTALL PROVIDE INSTALL PROVIDE NOT APPLICABLE DESCRIPTION EXISTING TAG # CROSS-HATCHING DENOTES NEW PARTITIONS NOTES 6" METAL STUDS, 16" O.C. TO STRUCTURE ABOVE 20 GA TO HEIGHTS OF 18' 16 GA FOR ABOVE 18' HEIGHT COMPLY WITH ALL APPLICABLE ACCESSIBILITY CODES, SEE SHEET A4 5/8" DRYWALL, TYPE 'X' TO STRUCTURE ABOVE, AS NEEDED FOR 1 HOUR SEPERATION PER UL U465 TAPE, SPACKLE, AND SAND SMOOTH, READY FOR FINISH 3 SLATWALL SAWTOOTHS AND DISPLAY PANELS 20 HI-LO DRINKING FOUNTAIN COMPLY WITH ALL APPLICABLE ACCESSIBILITY CODES (1) COAT OF PRIMER, REFER TO SHEETS A2/A4 FOR FINISHES 4 CASH WRAP CENTER CASH WRAP ON DISPLAY WALL BEHIND CASH DESK 21 MOP SINK COMPLY WITH ALL APPLICABLE ACCESSIBILITY CODES MASONRY WALL PAINT PT1, APPLY BASE B1 5 POWER/TELECOM FOR NEW CASH DESK FROM ABOVE VIA MILLWORK RACEWAY SEE SHEET F2 FOR WIRING LAYOUT: TELECOM LINES BY TEN. VENDOR 22 WALL MOUNTED GRAB BARS- GC TO INSTALL BLOCKING IN WALL AS NEEDED COMPLY WITH ALL APPLICABLE ACCESSIBILITY CODES 3-5/8" METAL STUDS, 16" O.C. TO STRUCTURE ABOVE 20 GA TO HEIGHTS OF 18' 16 GA FOR ABOVE 18' HEIGHT 6 PROVIDE POWER ON DEDICATED CIRCUIT(S), PROVIDE ORANGE RECEPTACLES 23 6'-0"x30"x3'-0"h FOLDING TABLE 5/8" DRYWALL TO STRUCTURE ABOVE, BOTH SIDES TAPE, SPACKLE, AND SAND SMOOTH, READY FOR FINISH 7 TENANT'S SENSORMATIC SYSTEM-FULLY DEDICATED CIRCUIT, NO SHARED NEUTRAL, LINE OR GROUND LABEL BREAKERS AT PANEL, INSTALL BREAKER LOCKS PROVIDE A RECEPTACLE ABOVE THE CEILING FOR POWER 24 PROVIDE (1) QUAD RECEPTACLE, COORDINATE LOCATION WITH TENANT (1) COAT OF PRIMER, REFER TO SHEETS A2/A4 FOR FINISHES 8 SWITCH BANK LOCATION-SWITCHES FOR ALL SALES FLOOR LIGHTING CIRUITS 25 12" DEEP ADJUSTABLE SHELVES ABOVE TABLE 3-5/8" METAL STUDS, 16" O.C. TO CEILING GRID BRACE TO STRUCTURE ABOVE AS NEEDED 9 STOREFRONT SYSTEM 5/8" DRYWALL ON ALL EXPOSED SURFACES TAPE, SPACKLE, AND SAND SMOOTH, READY FOR FINISH (1) COAT OF PRIMER, REFER TO SHEETS A2/A4 FOR FINISHES APPLY BASE B1 TO WALL AFTER FINISHING 26 MUZAK EQUIPMENT 10 INSTALL THERMOSTAT(S) ON MILLWORK RACEWAY RELOCATE IF ALREADY EXISTING PRIOR TO INSTALLING WALL FINISHES 27 EQUIPMENT RACK 11 MIRROR 60" TALL MIRROR AT 12" AFF, TYPICAL APPLY DAP CLEAR CAULK AT ALL EXPOSED EDGES 28 POSTER HOLDER 12 ELECTRICAL RECEPTACLES (20'+/- O.C. IN SALES AREA) AS SHOWN, WHITE COVERS/PLUGS) 29 1 1/4" ROUND (RIGID PIPE) x8' LONG HANGING ROD INSTALL IN DATA CABINET APPLY BASE B1 BOLT DOWN TO FLOOR, INSTALL UNDER DATA CABINET 50X100 ETC PROTOTYPE VERSION 2010, 01-01-10 JUNIORS (SF) MENS (SF) 2213 SF (44%) 976 SF (19%) 2213 SF (44%) ACCESSORIES (SF) 795 SF (16%) 795 SF (16%) FITTING (SF) STOCK ROOM (SF) 275 SF (6%) 531 SF (11%) 275 SF (6%) 531 SF (11%) 976 SF (19%) RESTROOMS/CORRIDOR (SF) 210 SF (4%) 5000 SF (100%) TOTAL AREA (SF) 210 SF (4%) 5000 SF (100%) JUNIORS STANDARDS (LF) 138 LF 46 LF 138 LF 46 LF 68 LF 68 LF 8 LF 8 LF MENS STANDARDS (LF) SLATWALL (LF) ETC STANDARDS (LF) REVISIONS LESS THAN 9'-4" AFF TOP OF STANDARD AT CEILING HEIGHT CUT DOWN AS NEEDED 9'-4" TO 11'-0" AFF TOP OF STANDARD AT CEILING HEIGHT 9'-0" LONG STANDARDS 11'-6" AFF AND HIGHER TOP OF STANDARD AT 11'-0" AFF INSTALL TRIM AT 11'-0" AFF* (1) COAT OF PRIMER, REFER TO SHEETS A2/A4 FOR FINISHES APPLY BASE B1 TO WALL AFTER FINISHING CREATE FRT PLYWOOD PLATFORM ABOVE RESTROOMS WALL STANDARDS TO BE INSTALLED AT 2'-0" O.C. U.N.O. SEE INTERIOR ELEVATIONS FOR ADDITIONAL CLARIFICATION TAPE, SPACKLE, AND SAND SMOOTH, READY FOR FINISH 14 SET TIMER PRIOR TO TURNOVERCOORDINATE TIMES W/TENANT 31 BASE TRIM B1 AT BASE OF CASH WRAP 3-5/8" METAL STUDS, 16" O.C. TO 8'-0" AFF 15 TELEPHONE PUNCH BOARD LOCATION TENANT TO GET TELEPHONE COMPANY TO INSTALL LINES TO THIS LOCATION 32 CLEAN/SAND COLUMNS SMOOTH, PAINT PT3 (GRAY) 5/8" WATER RESISTANT DRYWALL TO CEILING, ALL EXPOSED SURFACES 16 RUN INTERIOR LINES TO BOARD, USE PLENUM RATED WIRE WHERE REQUIRED GC TO PROVIDE 4'X4' FIRE RETARDANT TREATED PLYWOOD BD. 33 DATA CABINET-PROVIDE POWER TO LOCATION SHOWN @ 48" AFF, SEE SHEET F3 17 TENANT'S BURGLAR ALARM SYSTEM PANEL 34 RETRIEVER HOOKS-MOUNT AT 84" AFF, SEE SHEET F4 MOUNTING WITH TOGGLES, REFER TO TOGGLE DETAIL, SHEET A4 35 DOOR BUZZER RING ON SALES FLOOR (ABOVE C/W) AND STOCK ROOM (ABOVE DESK) (1) COAT OF PRIMER, (2) COATS OF PAINT PT1 APPLY BASE B1 3-5/8" METAL STUDS, 16" O.C. TO 8'-0" AFF APPLY 1x6 PAINT GRADE CAP, PAINT PT3 5/8" DRYWALL TO 8'-0" AFF, BOTH SIDES TAPE, SPACKLE, AND SAND SMOOTH, READY FOR FINISH (1) COAT OF PRIMER, REFER TO SHEETS A2/A4 FOR FINISHES APPLY BASE B1 NOT FOR CONSTRUCTION WALL STANDARD MOUNTING SCHEDULE: TAPE, SPACKLE, AND SAND SMOOTH, READY FOR FINISH SIGN TIME SWITCH (PARAGON 7000 SERIES OR APPROVED EQUAL) 2" CONDUIT IN WALL FROM WALL BOX TO 12'-6" AFF AND TURN OUT TO FRONT STORE CHARACTERISTICS: 5/8" DRYWALL ON ALL EXPOSED SURFACES ELECTRICAL EQUIPMENT SAFE APPLY BASE B1 6" METAL STUDS TO CEILING GRID SUSPEND FROM ABOVE USING ALLTHREAD MOUNTED AT 10'-0" AFF, SEE F4 13 30 FIRST WALL STANDARD FLOOR PLAN 1 A1 KEY NOTES SHOPPING CENTER TENANT SPACE ANYWHERE USA 4 * TRIM PROVIDED BY TENANT'S VENDOR, INSTALLED BY GC, SEE SHEET A4 FOR LOCATIONS AND FINISHES CONSTRUCTION PLAN & PARTITION INDEX SHEET NUMBER A1 DATE 08-19-09 JOB NO: 00000 DRAWN: CM CHECKED: CM 711 N. FIELDER RD. ARLINGTON, TX 76012 PH: (817) 635-5696 FAX: (817 635-5699 5 1 A2 EXTENT OF TENANT FLOORING 4 GRAY VINYL TRANSITION STRIP 5 INSTALL CONTROL JOINT FILLER IN ALL CONTROL JOINTS IN SALES AREA 6 PREFINISHED TRIM AT EDGES OF GRAPHIC 7 PERMANENTLY DELINEATE 44" MIN. WIDE PATH OF EGRESS ON FLOOR 8 WALK-OFF MAT TENANT'S VENDOR LANDLORD CONTRACTOR Scale: 1/4" = 1'-0" BARE CONCRETE STOCK ROOM FLOORING BLACK VINYL TRANSITION STRIP NEW CARPET SALES AREA FLOORING NEW CARPET SALES AREA FLOORING EXISTING CONCRETE SLAB, PREPARE AS NEEDED FOR NEW FLOORING EXISTING CONCRETE SLAB, PREPARE AS NEEDED FOR NEW FLOORING STOREFRONT DOOR SADDLE NEW RUBBER FLOORING EXISTING CONCRETE SLAB, PREPARE AS NEEDED FOR NEW FLOORING GENERAL CONTRACTOR INSTALL 3 INSTALL RUN FLOORING INTO FITTING ROOMS PROVIDE 2 INSTALL WALL MOUNTED GRAPHICS/WALLCOVERINGS PROVIDE DESCRIPTION 1 PROVIDE TAG NOT APPLICABLE # EXISTING KEY NOTES FINISH PLAN BLACK TRANSITION STRIP (ROPPE #50 OR EQUAL) NEW RUBBER/VINYL FLOORING SHOPPING CENTER TENANT SPACE ANYWHERE USA WC2-BLUE 5 10'-4" TREES GRAPHIC 10'-4" WC2 Project Coordination By: 5 10'-4" STREET SCENE GRAPHIC 5 WC1-GREEN 10'-4" WC1 WC1-GREEN NOTES 2 A2 FLOOR TRANSITION DETAIL 3 A2 Scale: 6" = 1'-0" SEE INSTALLATION NOTE 4 A2 Scale: 6" = 1'-0" MALL DETAIL-CONCRETE SCHLUTER SCHIENE TRANSITION STRIP UGL DRYLOK MASONRY CRACK FILLER IN ALL CONTROL JOINTS PRIOR TO FINISHING FLOOR FLOOR TRANSITION DETAIL FEATHER DOWN FROM MALL FLOOR LEVEL TO STORE SLAB HEIGHT EXISTING MALL FLOOR NOT FOR CONSTRUCTION REVISIONS FLOOR TRANSITION DETAIL Scale: 6" = 1'-0" MALL DETAIL ZINC TRANSITION STRIP NEW RUBBER FLOORING EXISTING MALL FLOOR FLOOR COVERING PLAN AND DETAILS SHEET NUMBER MARK 'KEEP CLEAR AT ALL TIMES' EXISTING CONCRETE SLAB, PREPARE AS NEEDED FOR NEW FLOORING 2 A2 FLOOR TRANSITION DETAIL Scale: 6" = 1'-0" EXISTING CONCRETE SLAB, PREPARE AS NEEDED FOR NEW FLOORING 4 A2 FLOOR TRANSITION DETAIL Scale: 6" = 1'-0" A2 F DATE 08-19-09 JOB NO: 00000 DRAWN: CM CHECKED: CM F 711 N. FIELDER RD. ARLINGTON, TX 76012 PH: (817) 635-5696 TRACK=8' Cx4 TRACK=8' Cx4 Project Coordination By: FAX: (817 635-5699 A TR CK 4' = C A TR SHOPPING CENTER TENANT SPACE ANYWHERE USA x3 11 CK 4' = C x3 1 SUSPENDED CEILING ELEMENT, HUNG FROM SUSPENDED CEILING SYSTEM, SEE SHEET F4 2 COMPLETE HVAC SYSTEM 3 COMPLETE SPRINKLER SYSTEM 4 INSTALL TRACKS APPROXAMITELY 4IN. FROM STOREFRONT 5 TENANT'S BANNER HANGING SYSTEM, MUST BE MOUNTED HIGHER THAN STOREFRONT GLASS HT. 6 DRYWALL CEILING IN RESTROOM 7 OPEN TO STRUCTURE ABOVE INSTALL 75w or 16W CFL PAR 30 D 23W CFL E 23W CFL TENANT'S VENDOR LANDLORD CONTRACTOR GENERAL CONTRACTOR INSTALL C INSTALL (2) 32W T8 A PROVIDE B SYMBOL INSTALL A (3) 32W T8 4100 K PROVIDE LAMP PROVIDE TAG EXISTING TENANT'S VENDOR LANDLORD CONTRACTOR GENERAL CONTRACTOR PROVIDE INSTALL PROVIDE INSTALL PROVIDE NOT APPLICABLE DESCRIPTION EXISTING TAG # Scale: 1/4" = 1'-0" EXG=EXISTING TO REMAIN WHERE FIXTURES ARE EXISTING TO REMAIN, REPLACE FIXTURES/BALLASTS AS NEEDED FOR LIKE-NEW APPEARANCE AND OPERATION LIGHT FIXTURE SCHEDULE KEY NOTES CEILING PLAN NOT APPLICABLE 1 A3 TENANT'S VENDOR TO PROVIDE NEW 4100K LAMPS (VERIFY WITH GC IN FIELD EXACT STYLE/TYPE OF EXISTING LAMPS), TENANT GC TO INSTALL TYPE DESCRIPTION Lay-In Fluorescents 2'x4' 3-LAMP WITH ELECTRONIC BALLASTS ACRYLIC LENSES NOTES Strip Fluorescents 8' STRIP LIGHTING WITH ELECTRONIC BALLASTS. SURFACE MOUNTED TO CEILING Track lights HALO POWER TRAC LIGHTING SYSTEMS #L1730PX LINE VOLTAGE TRACKS & HEADS, CEILING MOUNTED 24 LINEAR FOOT OF TRACK PER EACH 20 AMP CIRCUIT MAXIMUM Wall Mounted Street Lights WALL SCONCES, INSTALL IN LOCATIONS SHOWN, PAINT ALL EXPOSED SCREW HEADS BLACK, INSTALL AFTER INSTALLATION OF WALLCOVERING/FIXTURING Lamp Post FLOOR MOUNTED LAMP POST FIXTURE PAINT ALL EXPOSED SCREW HEADS BLACK Combo Light/Fan COMBINATION LIGHT AND EXHAUST FAN, COLOR: WHITE Recessed Lights RECESSED LIGHT, WHITE TRIM, SPECULAR REFLECTOR NOT FOR CONSTRUCTION NOTES 40LBS TOTAL, HUNG WITH 6 MOUNTING CLIPS/WIRE CAPABLE OF 40LBS EACH MOUNT ON 6" CABLES AS REQ'D BY LOCAL ENFORCEMENT FOR REQUIRED COVERAGES HANGING RAILS MOUNTED TO CEILING, INSTALL ALL PROVIDED CLIPS B C# D E F 100W TYPE-A F 8 TENANT SIGNAGE GC TO PROVIDE BLOCKING AS NEEDED FOR INSTALLATION OF SIGNAGE 9 PROVIDE DEDICATED CIRCUIT ROUTED THROUGH TIME CLOCK TENANT GC TO PROVIDE ADDITIONAL CIRCUIT/POWER FOR INTERIOR SIGN 10 SECURITY CAMERA DOMES INSTALL IN CEILING TILE 11 SUSPENDED CEILING ELEMENT, REFER TO SHEET F4 MOUNT ON 6" CABLES 12 PROVIDE ACCESS PANEL FOR ACCESS/SERVICING OF HOT WATER HEATER ABOVE RESTROOMS FLUSH MOUNTED, SIZED FOR POTENTIAL REPLACEMENT OF HWH, PAINT PT1 13 METAL STUD BRACING BETWEEN WALLS ENCASED IN DRYWALL TO ALIGN WITH FITTING ROOM WALLS BELOW PAINT PT1 G X 75W PAR30 G LED X Y (2) ADJUSTABLE HEADS Y Y1 (2) ADJUSTABLE HEADS Y1 EXIT SIGN WITH BATTERY BACKUP INSTALL BREAKER LOCKS ONCIRCUITS FOR EMERGENCY LIGHTING Emergency Lights CEILING MOUNTED EMERGENCY LIGHTING WITH BATTERY BACKUP INSTALL BREAKER LOCKS ONCIRCUITS FOR EMERGENCY LIGHTING Emergency Lights WALL MOUNTED EMERGENCY LIGHTING WITH BATTERY BACKUP INSTALL BREAKER LOCKS ONCIRCUITS FOR EMERGENCY LIGHTING Exit Sign REVISIONS CEILING/LIGHTING PLAN AND SCHEDULES SHEET NUMBER A3 13 ANGLED VIEW ANGLED VIEW ANGLED VIEW 08-19-09 JOB NO: 00000 DRAWN: CM CHECKED: CM 12'-0" CEILING HEIGHT 7'-0" 8'-4" 11'-0" 2'-8" STREET SCENE GRAPHIC DATE 711 N. FIELDER RD. ARLINGTON, TX 76012 PH: (817) 635-5696 CAULK ALL JOINTS, PUTTY NAIL HOLES, SAND SMOOTH, TOUCH-UP AFFECTED AREAS 2 WALL STANDARDS INSTALL PER SCHEDULE, SEE SHEET A1 AND TOGGLE DETAIL 3 WALL SCONCES SEE MOUNTING DETAIL, SHEET A4 4 WALL COVERINGS/GRAPHICS INSTALL PRIOR TO STANDARDS, INSTALLATION SIMILAR TO WALL PAPER 5 WALL MOUNTED SLATWALL/SAWTOOTHS CAULK ALL JOINTS, PUTTY NAIL HOLES, SAND SMOOTH, REPAINT AFFECTED AREAS 6 1X6 WOOD CAP ON TOP OF FITTING ROOM WALLS CAULK ALL JOINTS, PUTTY NAIL HOLES, SAND SMOOTH, REPAINT AFFECTED AREAS 7 INSTALL ALUMINUM KICKPLATE PAINT DOOR AND FRAME PT3 (GRAY) 8 LAMP POST 9 SENSORMATIC SYSTEM INTERIOR ELEVATION 9 A4 INTERIOR ELEVATION Scale: 1/4" = 1'-0" NOTES POWER TO BE RUN BY CONTRACTOR 10 STOREFRONT SYSTEM 11 1 1/2" CLEAR PLASTIC CORNER GUARDS, MOUNTED WITH SCREWS WALL PROTEX, OR EQUAL, INSTALL AT ALL EXPOSED CORNERS, 8' LENGTHS 12 MIRROR AT 12" AFF, 60" TALL 13 CUT DOWN GRAPHICS EQUALLY FROM TOP AND BOTTOM AS NEEDED TRIM PICTURES EQUALLY SO ALL ARE EQUAL, WHERE NEEDED INTERIOR ELEVATION 8 A4 Project Coordination By: INSTALL TENANT'S VENDOR GENERAL CONTRACTOR PROVIDE 1X4 PRE-FINISHED TRIM, MOUNTED AT 11'-0" AFF, SEE ELEVS. FOR COLOR LOCATIONS Scale: 1/4" = 1'-0" Scale: 1/4" = 1'-0" WALLCOVERING 4 4 4 4 2'-0" 3 A4 2 INSTALL WALL COVERING/GRAPHIC PRIOR TO INSTALLATION OF STANDARDS, JOINT IN MATERIALS TO ALIGN WITH CENTER OF WALL STANDARDS 12'-0" CEILING HEIGHT 7'-0" 2 3 2 1'-0" CL 1'-0" WALL STANDARDS, MOUNT AT 2'-0" O.C. WALL SCONCE, MOUNT WITH BOTTOM OF GLOBE AT 7'-0" AFF (6'-7" AFF TO CENTER OF J/BOX), INSTALL GRAPHIC PRIOR TO INSTALLATION OF SCONCES 2 INTERIOR ELEVATION 7 A4 Scale: 1/4" = 1'-0" GREEN TRIM GRAPHIC 4 TREES GRAPHIC 2 FAX: (817 635-5699 SHOPPING CENTER TENANT SPACE ANYWHERE USA 7 INSTALL DESCRIPTION 1 5 7'-0" AFF 12'-0" CEILING HEIGHT 7'-0" 3 7 5 TAG 4 RUE 21 GRAPHIC # LANDLORD CONTRACTOR KEY NOTES PROVIDE Scale: 1/4" = 1'-0" BLUE GRAPHIC 2 A4 5 INTERIOR ELEVATION 4 2 5 INSTALL 5 NOT APPLICABLE 1 A4 2 PROVIDE 3 EXISTING 2 WALL SCONCE DETAIL Scale: NOT TO SCALE NOT FOR CONSTRUCTION GREEN TRIM 3'-3" 1'-9" 36" GRAB BAR 6" 3'-0" 1'-5" 8" INTERIOR ELEVATION Scale: 1/4" = 1'-0" 1'-6" 5 A4 LEVER HANDLE FAUCET 6" BASE VINYL COVE BASE 8 4 A4 3'-4" 2'-9" 2'-4" TOILET 2'-9" 3'-3" TP HOLDER TOILET RESTROOM DETAILS Scale: 1/2" = 1'-0" REVISIONS 4' TALL FRP PANELS ON ALL WALLS (WHITE) 1'-0" 1'-6" 3'-6" ADA MIRROR ROLL PAPER TOWEL DISP. 3'-0" 8'-0" 42" GRAB BAR WALL STANDARDS WITH (2) WHITE MELAMINE SHELVES, PROVIDED BY TENANT'S VENDOR, INSTALLED BY TENANT GC 3'-6" ADA SINK PIPE WRAP 1'-6" MIN. CLEAR 3'-4" 4' TALL FRP PANELS ON ALL WALLS (WHITE) RUN ACROSS 2'-10" 10 TOGGLE BOLTS TO BE AS MANUFACTURED BY "THE TOGGLER". INSTALL (1) TOGGLE/SCREW IN EVERY HOLE IN EACH STANDARD (13 TOTAL) AND USE SCREWS WITH FLAT HEAD (NOT ROUNDED). TOGGLES AND SCREWS AVAILABLE FROM FASTENAL (WWW.FASTENAL.COM OR 507-454-5374: TOGGLES: FASTENAL #50955 SCREWS: FASTENAL #0149015 6 A4 TOGGLE BOLT DETAIL Scale: NOT TO SCALE INTERIOR ELEVATIONS AND DETAILS SHEET NUMBER A4 DATE 08-19-09 JOB NO: 00000 DRAWN: CM CHECKED: CM 711 N. FIELDER RD. ARLINGTON, TX 76012 PH: (817) 635-5696 SHOPPING CENTER TENANT SPACE ANYWHERE USA Project Coordination By: FAX: (817 635-5699 NOT FOR CONSTRUCTION REVISIONS FITTING ROOM DETAILS SHEET NUMBER F1 DATE 08-19-09 JOB NO: 00000 DRAWN: CM CHECKED: CM 711 N. FIELDER RD. ARLINGTON, TX 76012 PH: (817) 635-5696 SHOPPING CENTER TENANT SPACE ANYWHERE USA Project Coordination By: FAX: (817 635-5699 NOT FOR CONSTRUCTION REVISIONS CASH WRAP DETAILS SHEET NUMBER F2 DATE 08-19-09 JOB NO: 00000 DRAWN: CM CHECKED: CM 711 N. FIELDER RD. ARLINGTON, TX 76012 PH: (817) 635-5696 SHOPPING CENTER TENANT SPACE ANYWHERE USA Project Coordination By: FAX: (817 635-5699 NOT FOR CONSTRUCTION REVISIONS CASH WRAP DETAILS SHEET NUMBER F2 DATE 08-19-09 JOB NO: 00000 DRAWN: CM CHECKED: CM 711 N. FIELDER RD. ARLINGTON, TX 76012 PH: (817) 635-5696 SHOPPING CENTER TENANT SPACE ANYWHERE USA Project Coordination By: FAX: (817 635-5699 NOT FOR CONSTRUCTION REVISIONS BACK OF HOUSE LAYOUT AND DETAILS SHEET NUMBER F3 DATE 08-19-09 JOB NO: 00000 DRAWN: CM CHECKED: CM ROOF DECK 711 N. FIELDER RD. JOISTS ARLINGTON, TX 76012 PH: (817) 635-5696 FAX: (817 635-5699 UNISTRUT BETWEEN JOISTS 10'-0" AFF PIPE HANGER SUSPENDED GRAPHIC DETAILS 2 F4 Scale: N.T.S TRACK FASTENED TO BLOCKING ABOVE CEILING PIPE HANGER DETAIL Scale: 3" = 1'-0" SHOPPING CENTER TENANT SPACE ANYWHERE USA 1 F4 1 1/2" RIGID PIPE TIE-WIRE TO STRUCTURE ABOVE TO SUPPORT GRID/FIXTURES FIRE RETARDANT TREATED BLOCKING BETWEEN CEILING GRID MEMBERS 15/16" SUSPENDED CEILING GRID ACOUSTIC CEILING TILE ACOUSTIC CEILING TILE LIGHTING TRACK, FASTENED TO CEILING GRID USING ERICO 4G8WH TWIST ON TRACK LIGHTING CLIPS LIGHTING TRACK, FASTENED TO CEILING GRID USING ERICO 4G8WH TWIST ON TRACK LIGHTING CLIPS Project Coordination By: ALL-THREAD NOT FOR CONSTRUCTION 3 F4 TRACK LIGHT MOUNTING DETAIL Scale: 3" = 1'-0" 4 F4 RETRIEVER HOOK REVISIONS Scale: N.T.S. FIXTURE DETAILS SHEET NUMBER F4