Water TowerPlace - General Growth Properties

advertisement
Water Tower Place
Tenant Criteria Manual
Architectural
835 North Michigan Chicago, IL 60611
September 2008
TABLE OF CONTENTS
INTRODUCTION
ARCHITECTURAL DESIGN CRITERIA
Building Description ........................................1
Architectural Drawing Requirements ............13
Tenant Design Criteria Introduction ................2
Landlord Supplied Architectural Items ..........14
Directory..........................................................3
General Design Criteria ................................17
Location Map ..................................................4
Structure........................................................21
PLANS
Lighting..........................................................22
Ground & Mezzanine Floor Plans...................5
Storefront Design Criteria .............................24
Second & Third Floor Plans............................6
Display Zone .................................................28
Fourth and Fifth Floor Plans ...........................7
DIAGRAMS
Sixth & Seventh Floor Plans ...........................8
Store Design Plan Diagram ..........................30
TENANT SUBMISSIONS & PERMIT
REQUIREMENTS
Storefront Criteria..........................................31
Design Submissions .......................................9
Building Code Information ............................11
Required Permits & Inspections ...................12
Storefront Section .........................................32
Storefront Section at Well .............................33
Storefront Detail Section ...............................34
Storefront Reflected Ceiling Plan..................35
Typical Neutral Pier Detail ............................36
Neutral Pier Detail at Existing Store .............37
Neutral Pier Detail at a Corner......................38
Neutral Pier Detail at Corridor.......................39
Typical Neutral Pier Elevations.....................40
Typical Neutral Pier Elevations.....................41
Tenant Storefront at Mall Column.................42
Typical Tenant Demising Wall ......................43
Tenant Service Corridor Door .......................44
Construction Barricade .................................45
SIGNAGE DESIGN CRITERIA
Signage Submittal Requirements .................46
Tenant Signage.............................................47
Blade Sign Elevation.....................................51
Blade Sign Detail ..........................................52
Water Tower Place
i
TABLE OF CONTENTS
MECHANICAL DESIGN CRITERIA
CONSTRUCTION REQUIREMENTS
HVAC Drawing Requirements ......................53
Preconstruction Meeting .................................. 90
Tenant Work .................................................54
Site Access ...................................................... 91
Tenant VAV Box Detail .................................57
General Contractor Requirements................... 93
ELECTRICAL DESIGN CRITERIA
INSURANCE.................................................... 95
Electrical Drawing Requirements..................58
LANDLORD PUNCH LIST .............................. 96
Electrical Construction Requirements...........59
Electrical Service Diagram............................61
Emergency Lighting Diagram .......................62
PLUMBING DESIGN CRITERIA
Plumbing Drawing Requirements .................63
Public and Employee Toilets ........................63
Work by Tenant.............................................64
Floor Penetration Details ..............................67
Plumbing Riser Diagram ...............................68
Water Meter Diagram....................................69
Dishwasher Moisture Eliminator ...................70
FIRE PROTECTION DESIGN CRITERIA
Sprinkler System Design Criteria..................71
Sprinkler Drawing Requirements ..................73
Building Fire Riser Diagram..........................76
Equivalent Lengths .......................................77
Tenant Sprinkler Water Supply Data ............80
Tenant Sprinkler Efficiency/ GPM Supply
Curve ............................................................83
Tenant Sprinkler Pressure/ GPM Supply
Curve ............................................................84
Tenant Sprinkler Riser Diagram 1 ................85
Tenant Sprinkler Riser Diagram 2 ................86
Tenant Sprinkler Riser Diagram 3 ................87
Sprinkler Riser Number for Tenant Spaces..88
FIRE ALARM DESIGN CRITERIA
Existing Fire Alarm System...........................89
Emergency Message System .......................89
Future Alarm System ....................................89
Water Tower Place
ii
INTRODUCTION
Building Description
Water Tower Place is a mixed-use, cast-in-place concrete mega-structure built in 1975. It combines
eight floors of retail shopping, an office floor, the Drury Lane Theatre, The Ritz-Carlton Hotel and some
of Chicago’s premier residential condominiums. Located diagonally across Michigan Avenue from
Chicago’s Historic Water Tower, Water Tower Place is the best-known shopping destination in the
metropolitan area. It is the intent of these criteria to permit a wide range of design opportunities, to
encourage excitement in the retail environment and to maintain the high standards of retail design and
construction that have been a hallmark of Water Tower Place.
The building includes a diverse mix of Tenants that combine an entertainment factor as part of their
overall appeal. Minimum restraints are imposed on the Tenant’s creativity and imagination. However, the
Landlord reserves the right to reject any Tenant design proposals in part or in whole if it is determined
that they would not contribute to the design quality of Water Tower Place
Vision of the Design Team
Exciting and unique storefronts and merchandising designs create a shopping and entertaining
environment that attracts customers and results in increased sales. Tenants are encouraged to create
innovative and dramatic storefronts, shop interiors and graphics. Classic interior materials of marble,
chrome and brass create an ideal, neutral palate for great store design.
Water Tower Place
1
INTRODUCTION
Tenant Design Criteria Manual Introduction
The requirements of this Manual are referenced and included in Tenant leases, and has been prepared
to guide you, as well as your architect, store designer, and contractor in guiding the expediting the
design and construction of your lease premises. This information describes the Landlord’s obligations,
the Tenant’s design responsibilities, and the Contractor’s requirements.
General Design Criteria pertaining to storefront design, materials, colors, signage, interiors and lighting
must be addressed by all Tenants. In addition, stores must adhere to specific criteria which are
determined by their location and their specific architectural context. In this way, each store will be
reviewed on an individual basis in context to ensure diverse and creative design solutions.
Through the criteria in this Manual, the Landlord has set certain quality and design standards, which will
help the Tenants to create stores that are compatible with the overall design quality of Water Tower
Place. The General Growth encourages designs that shall add richness to the built environment.
Nationally or regionally recognized merchants may creatively interpret these criteria as it applies to their
prototype design.
The Tenant Print Package (“Print Package”) consists of:
x
Tenant Design Criteria Manual
x
Exhibits A, A-1, B or Lease Outline Drawing (L.O.D.)
x
Record drawings of the previous Tenant build-out (if available)
The lease agreement requires that all Tenant plans be prepared by an architect and engineer(s) licensed
by the State of Illinois. Tenants are encouraged to retain an architect familiar with the City of Chicago’s
Self Certification Process. Contact the Tenant Coordinator for information for contacts of firms that can
offer this service.
Note: This Manual is also available on General Growth’s web site at www.ggp.com
Water Tower Place
2
INTRODUCTION
Directory
Water Tower Place
835 North Michigan Avenue
Chicago, Illinois 60611-2218
Landlord
General Growth Properties, Inc.
110 North Wacker Drive
Chicago, IL 60606-1511
(312) 960-5000
www.ggp.com
Operations Manager
General Growth Properties, Inc.
Suite 987W
845 North Michigan Avenue
Chicago, IL 60611-2218
(312) 440-3580
(312) 440-1259 Fax
www.shopwatertower.com
Tenant Coordination
General Growth Properties, Inc.
110 North Wacker Drive
Chicago, IL 60606-1511
(312) 960-5000
(312) 960-5064 Fax
Building Engineer
Johnson Controls, Inc.
845 North Michigan Avenue
Chicago, IL 60611-2218
(312) 440-3590
(312) 440-1980 Fax
Building Security
(312) 440-3594
Building Dock Manager
(312) 440-3160
Building Permits
City of Chicago
Department of Buildings
9th Floor
121 North LaSalle Street
Chicago, IL 60602
(312) 744-3449
www.cityofchicago.org
Health Department
City of Chicago Department of Public Health
Food Protection Division
2133 West Lexington
Chicago, IL 60612
(312) 747-3663
(312) 746-8099 Fax
www.cityofchicago.org
Construction Inspections
City of Chicago Department of Buildings
120 North Racine
Chicago, IL 60607
(312) 743-3600
42nd Ward Alderman
Brendan Reilly
Suite 212
311 West Superior
Chicago, IL 60610
(312) 642-4242
www.reillyforchicago.com
Electric Utility
ComEd
Customer Care Center
P.O. Box 805379
Chicago, IL 60680-5379
866-639-3532
Gas Utility
Peoples Gas
130 East Randolph Drive
Chicago, IL 60601
(866) 556 - 6001
Building Telephone Service
AT&T
219 South Dearborn
Chicago, IL 60604
(312) 786-0794
www.att.com
Water Tower Place
3
INTRODUCTION
Location Plan
Water Tower Place
4
INTRODUCTION
Ground Floor & Mezzanine Plans
Water Tower Place
5
INTRODUCTION
Second and Third Floor Plans
Water Tower Place
6
INTRODUCTION
Fourth and Fifth Floor Plans
Water Tower Place
7
INTRODUCTION
Sixth and Seventh Floor Plans
Water Tower Place
8
TENANT DESIGN SUBMISSION AND BUILDING PERMIT REQUIREMENTS
Design Submissions
Prior to starting construction, the Tenant shall prepare and submit a preliminary design package (2 sets)
and subsequently a final submission package (3 sets) for review and approval.
Submissions are to be made to General Growth Tenant Coordination.
Preliminary Design Submission
The preliminary design submission should communicate the design intent to the Tenant Coordinator.
Drawings submitted shall include a comprehensive floor plan, ceiling plan, storefront elevations, interior
elevations and necessary wall sections. Color renderings, representative photos and material sample
boards should be prepared. Documents in compliance with the Tenant Design Criteria will have the best
opportunity for a prompt review and approval returned to the Tenant.
Final Submission
The final submission shall consist of complete project construction drawings and specifications.
Reference the Architectural and Engineering Design Criteria for drawing requirements.
Final Design Approval
Landlord, upon final review and approval of the final submission, shall forward to the Tenant (1) one
copy of the documents with the Landlord’s comments and conditions of approval in paper or digital
format. Tenant’s contractor shall have one (1) Landlord-approved set at the job site at all times and may
not commence work until said approved plans are physically within the demised premises.
Code Requirements
It is the Tenant’s responsibility to ensure compliance with all relevant codes, obtain all approvals, acquire
all permits, and pay all fees in connection therewith. Landlord’s review of Tenant submittals does not
signify review and/or approval of the submittals for code compliance. It is the Tenant and/or Tenant’s
architect who shall be solely responsible for compliance with applicable code requirements.
Additional Submittals
x
Fire Protection Submittals
Reference the Fire Protection Design Criteria for sprinkler shop drawing requirements. The
sprinkler contractor is required to submit sprinkler shop drawings to the Operations Manager and
to the Landlord’s insurance underwriter for review and approval.
Drawings and hydraulic calculations must be sealed and signed by a registered fire protection
engineer from the State of Illinois.
x
HVAC Submittals
Reference the HVAC Design Criteria for testing & balancing and exhaust submittals.
x
Signage Submittals
Reference the Signage Design Criteria for sign submittals for signage shop drawings and Blade
sign artwork.
Water Tower Place
9
TENANT DESIGN SUBMISSION AND BUILDING PERMIT REQUIREMENTS
Construction barricade graphics must be submitted to the Operations Manager for approval prior
to application.
All Tenant improvements are subject to the Landlord’s approval and shall conform to all design
criteria and lease agreement.
No deviation from the approved drawings will be permitted. Any deviation shall be resubmitted
for Landlord approval.
Tenants should discuss specific thoughts about their design concept and raise any questions about
these criteria with the Landlord’s Tenant Coordinator before beginning preliminary design work.
Any requested deviations from the Tenant Design Criteria must be approved by the Landlord’s Tenant
Coordinator.
Each Tenant is required to retain an architect registered in Illinois to prepare design and construction
documents.
It is imperative that all the requirements outlined above be strictly adhered to by the Tenant and Tenant’s
architect. Failure to do so will only result in unnecessary and costly delays in the approval of drawings.
Design Submissions are to be sent to:
General Growth Properties, Inc.
Attn: Water Tower Place Tenant Coordination
110 North Wacker Drive
Chicago, IL 60606
Information to be included:
Store Name & Space No.
Tenant Name and Contact Information (Mailing address, telephone, fax and email)
Architect and Contact Information
Water Tower Place
10
TENANT DESIGN SUBMISSION AND BUILDING PERMIT REQUIREMENTS
Building Code Information
It is the sole responsibility of the Tenant’s architect, engineer(s) and general contractor to comply with all
applicable federal, state, and local codes and ordinances for their occupancy type.
Height - 74 Story Mixed Use
•
•
•
•
•
8 story Retail with Mezzanine
1 story Office
20 story Hotel
40 story Condominiums
5 story Mechanical
Gross Building Area - Retail
Ground Floor
MezzanineFloor 2Floor 3 Floor 4 Floor 5Floor 6 Floor 7 Floor 8 `
Total
Type of Construction
•
87,754 square feet
68,994 square feet
110,179 square feet
111,076 square feet
111,238 square feet
110,299 square feet
111,242 square feet
111,105 square feet
113,772 square feet
935,659 square feet
Type 1A, Fire Resistive, Fully Sprinklered
Primary Occupancy Classification
•
Mercantile - Group F
Required Occupancy Separation / Tenant Separation
•
Mercantile to Assembly - 2 hour
•
Tenant to Tenant / Tenant to Corridor - 2 hour
Applicable Codes:
•
Current City of Chicago Building Code (Issued Annually), including Energy Conservation
Ordinance
•
Current Chicago Zoning Ordinance (Issued Annually)
•
1997 Illinois Accessibility Code
•
2005 Illinois Plumbing Code
•
Illinois Energy Conservation Code (IBC 2006)
•
2000 National Fire Protection Association (NFPA 1)
•
2006 Life Safety Code
Water Tower Place
11
TENANT DESIGN SUBMISSION AND BUILDING PERMIT REQUIREMENTS
Required Permits & Inspections
A building permit issued by the City of Chicago must be presented to the Operations Manager prior to
work start. It is the responsibility of the Tenant to obtain required approvals from the City of Chicago and
to pay for and secure all applicable permits. City website: www.cityofchicago.org.
City of Chicago Self Certification Permit Process
The City of Chicago Department of Buildings (DOB) has established a program to expedite the
permitting process for “Tenant Improvement Projects”. The majority of retailers can benefit from the
program. Major features and requirements of the Self Certification Program are:
•
Project must meet DOB Self Certification eligibility requirements.
•
Owner/Tenant, design professionals and the general contractor certify that the Project meets
applicable codes and so only a cursory review of the documents is performed.
•
Design professionals must be certified by DOB for the Commercial Self Certification Program. A
list of certified architects is available on the City website.
•
Permit application information must be entered online.
•
Application information includes the General Contractor and all major sub-contractors; all must
be licensed to perform work in the City of Chicago.
•
The request for a permit Intake Appointment is submitted via fax. The meeting date is usually
within two to four weeks after the application is received.
•
Zoning review and approval is required before the Intake Appointment.
•
Written aldermanic acknowledgement is required for the issuance of a permit without a
mandatory ten business day review period after the Intake Appointment.
•
Upon submission of the permit application and all required documents, a permit is usually issued
within one (1) week.
Chicago Energy Conservation Code
Compliance with the City of Chicago Energy Conservation Code is mandatory. Plans submitted for
permit must include a compliance statement by a City of Chicago Registered Energy Professional.
•
The Chicago Energy Conservation Code (Chapter 18-13) is published as a part of the twovolume Chicago Building Code.
•
The code and a list of Registered Energy Professionals are available at the City website at
www.cityofchicago.org at the Department of Construction and Permits.
Other Permits
The City of Chicago requires sign permits for signs visible to the public. These must be obtained through
a City-licensed Sign Contractor. Note that documents for all Tenant store signage must be submitted to
the Landlord for review; approval must be issued prior to sign installation.
Construction Inspections
It is the responsibility of the Tenant’s general contractor to arrange all field inspections required by the
City of Chicago Department of Buildings. Final inspections and the issuance of an Occupancy Certificate
are required for projects exceeding $400,000 in construction cost.
Water Tower Place
12
ARCHITECTURAL DESIGN CRITERIA
Architectural Drawing Requirements
The following is a list of design information required to expedite plan approval by the Landlord. We urge
you to read this Manual in its entirety in order to fully understand the requirements needed to generate
an acceptable set of construction documents.
Lease Outline Document
Landlord will provide Tenant with a Lease Outline Document (LOD) or Lease Exhibits. The Tenant is
responsible to field verify the dimensions of the space and other existing conditions prior to
starting construction documents. Contact the Operations Manager to gain access to the space.
Drawing and Specification Submission Requirements
Tenant’s working drawings and specifications shall be prepared in strict compliance with these design
criteria. Drawings and specifications shall be submitted to Landlord for approval in the form of three (3)
sets of prints and specifications. Working drawings and specifications shall include, but not be limited to
the following: Note that scales indicated are minimums.
x
Key plan showing location of the premises.
x
Floor plan at 1/8 = 1’-0.
x
Furnishings, fixtures and equipment plan at 1/8 = 1’-0.
x
Floor finishes plan at 1/8 = 1’-0.
x
Reflected ceiling plan at 1/8 = 1’-0.
x
Overall sections at 1/4 = 1’-0.
x
Plan, elevations, and section of storefront at 1/4 = 1’-0.
x
Interior elevations at 1/4 = 1’-0.
x
Full sections of types of partitions used at 1-1/2 = 1’-0.
x
Descriptive drawings of store display fixtures.
x
Details of storefront at 1-1/2 = 1’-0.
x
Door schedule with jamb details at 1-1/2 = 1’-0.
x
HVAC, electrical, sprinkler, and plumbing plans at 1/8= 1’-0.
x
Mechanical details at 1-1/2 = 1’-0.
x
Lighting plan at 1/8 = 1’-0.
x
Emergency & exit lighting plan at 1/8 = 1’-0 (required for DCAP permit review).
x
Electrical details, fixture schedules, and one-line electrical load tabulations.
x
Structural plans (if required) at 1/8 = 1’-0.
x
Load tabulations and calculation if structural work is included.
x
Specifications covering all of Tenant’s work, including, but not limited to, architectural, HVAC,
electrical, plumbing, fire protection; and other plans and specifications as may be required by the
local fire and building authorities or other governing bodies.
Water Tower Place
13
ARCHITECTURAL DESIGN CRITERIA
Landlord Required Notes
The following notes must appear on the cover sheet of all Tenant final construction documents:
•
The Tenant’s general contractor must conduct a pre-construction meeting with the General
Growth Properties, Inc. Operations Manager prior to work start.
•
The Tenant’s contractor shall perform first-class workmanship. Acceptance of workmanship is
contingent upon Landlord approval.
•
The Tenant’s contractor will repaint and/or repair Landlord’s property (bulkhead, neutral piers,
rear corridor, etc.) damaged during Tenant improvement.
•
All materials used in the construction of Tenant space must be asbestos free.
•
Supports for Tenant construction must not be connected to any of the Landlord’s electrical,
plumbing, fire protection piping or mechanical equipment.
•
Any penetration or modifications to structural concrete deck must be coordinated and approved
by the General Growth Properties, Inc. Operations Manager prior to performing work.
•
All slab penetrations must be sleeved, sealed liquid tight and firestopped.
•
No trenching of structural slabs (i.e. for electrical conduit, etc.) is allowed.
•
Waterproof membrane water tested to be performed; approval of the test by the Operations
Manager or Building Engineer is required.
•
Tenant storefront must be self-supported. Storefront cannot be suspended from the building
structure.
•
Demising partitions must be of 2-hour fire-rated construction, taped and sealed airtight to deck
above.
•
The ceiling systems are to be constructed using materials with class “A” Fire Rating, but only
require fire rating as an assembly in exit corridors and any other locations required by code.
•
Access panels in ceilings must be located to provide access to Landlord’s mechanical
equipment as determined by the Building Engineer.
•
All reused material and equipment must be refurbished to “like new” condition.
•
Sign contractor to supply an insurance certificate to the Operations Manager prior to sign
installation.
•
All electrical devices and conduit systems above the finish ceiling are to be Chicago plenum
rated.
•
Only emergency lighting and exit lights are to be connected to the Landlord emergency power
system. No battery-powered emergency lighting is allowed.
•
The Tenant must submit four (4) copies of sprinkler contractor’s shop drawings for approval by
Landlord’s risk consultant for approval or Tenant may not be allowed to open.
Water Tower Place
14
ARCHITECTURAL DESIGN CRITERIA
Landlord Supplied Architectural Items
Walls
x
Demising Walls
New partitions dividing the premises from adjacent Tenant spaces may be installed by the
Landlord; these will consist of 3-5/8” metal stud framing and shall run from floor to underside of
deck above as shown on the Lease Outline Drawing. The wall type, typical spacing and
dimensions will be such as to provide adequate fire separations and sound barriers. These walls
are not designed to support additional loads. Tenant is required to install in-wall blocking if
Tenant wishes to place additional loads on these walls. Drywall and acoustic insulation shall be
provided by Tenant.
Partitions dividing the premises from service corridors or similar areas may be constructed by
Landlord consisting of concrete masonry units or of gypsum board and metal studs. Acoustic
insulation and gypsum board at the interior (Tenant) face of the metal studs shall be provided by
the Tenant.
x
Exterior Walls
The building is constructed of a reinforced concrete frame with stone façade and concrete or
masonry back-up.
x
Neutral Piers
A variety of neutral pier configurations exist in the project. Refer to Architectural Details for
general storefront conditions for particular criteria and neutral pier details.
Floors
x
Floor Slab
The slab is reinforced, cast-in-place concrete. Construction includes areas of flat-plate
construction with drop panels and areas with concrete beams. Care must be taken to avoid
damage to existing reinforcing.
x
Floor Loading
Design Floor Live Load: 100 pounds per square foot
Design Floor Fill Allowance: 20 pounds per square foot
x
Floor Depressions
Tenant shall fill all floor depressions, if any, in the premises greater than 1/2" with 4000 psi
minimum structural lightweight concrete topping on Landlord's structural slab. Where the
depression is greater than 1” in depth, the Tenant shall fill floor depressions prior to the
performance of any other Tenant's Work.
Water Tower Place
15
ARCHITECTURAL DESIGN CRITERIA
Acoustic Considerations
Landlord construction has been designed to provide general protection to guard against typical sound
and vibration transmission between spaces.
Tenant is responsible to ensure that sound generated in their premises produce no more sound that
transmits through the Landlord’s demising wall and floor structure design. If, in the Landlord’s opinion,
additional sound attenuation is needed to sufficiently isolate sound from within the demised premises,
Tenant shall design and provide sound attenuation as required.
Existing Construction within the Premises
All existing conditions shall be verified by the Tenant. Failure to verify the existing conditions shall not
relieve Tenant of any expenses or responsibilities resulting from that failure. It is the responsibility of the
Tenant to field check all dimensions, utilities, locations and conditions prior to and during construction.
Demolition
Demolition of existing construction is the responsibility of the Tenant, including flooring and floor topping.
Tenant may reuse portions of existing improvements subject to Landlord's prior written approval. Reuse
of existing improvements shall be clearly indicated on the Store Layout and Working Drawings. Landlord
makes no warranty or representation as to the condition or suitability of existing improvements reused by
Tenant.
Reference the Construction Requirements section of this document for additional demolition information.
Water Tower Place
16
ARCHITECTURAL DESIGN CRITERIA
General Design Criteria
Overview
These criteria are a basic “set of tools” that the Tenant is required to work with and expand upon. Criteria
are written to allow freedom of individual expression and to provide a common point of departure for all
Tenants.
Construction Requirements
x
Landlord’s building shell is constructed as Type I-A, fire-resistive, fully sprinklered construction.
Tenant’s work must conform to this construction type and will use only noncombustible materials
within the demised premises except where treated, fire-resistant materials are permitted in
accordance with local codes.
x
Only new, first-class materials, equipment, fixtures (including trade fixtures) and furnishings shall
be used in the premises.
x
All finishes shall have a flame spread rating as required by applicable codes.
x
Interior wood doors shall be solid-core. Interior hardware shall be of appropriate commercial
grade.
x
All entrances into Tenant premises must remain open and clear of any permanent structural
elements.
x
All Tenant work, with the exception of approved sign installation and approved work performed
above and below the space, shall be done from within the demised premises.
x
Tenant is obligated to verify conditions pertaining to the demised premises from time to time
prior to and after the commencement of Tenant’s work. Tenant shall coordinate its work with the
Landlord and other Tenants and with existing conditions above and below the demised
premises, and shall make changes from time to time as required to accommodate such work or
conditions. Any proposed adjustments to the work arising due to field conditions not apparent on
drawings, other building documents and previous site surveys shall be submitted to the
Operations Manager and receive written approval prior to execution.
Architectural/Engineering Fee
Architectural or engineering fees incurred by the Landlord as a result of investigating or planning work to
be performed on Tenant’s behalf will be paid by the Tenant.
Storefronts
Tenant’s storefronts are a critical component of Water Tower Place, therefore all storefronts must
complement and enhance the ambiance of common retail areas. Storefronts should emphasize a “sense
of entry”, and the display of merchandise. National or regional Tenants who have a typical or
recognizable storefront design are expected to review this design criterion and adjust their designs
accordingly to ensure compatibility and compliance. They will work closely with the Landlord to achieve a
high level of quality. Storefront Design Criteria is a separate section within this document.
In addition to the storefronts, the area inside within 5’-0 of storefronts have been identified as Tenant
Display Zones and special design criteria apply to these areas.
Water Tower Place
17
ARCHITECTURAL DESIGN CRITERIA
Store Interiors
x
All storefronts and interior areas of the store which are visible to the public are subject to design
approval by the Landlord.
x
The vibrancy of rich merchandising concepts should not be relegated simply to the storefronts,
but as total experiences, where entire stores become showcases of well-crafted merchandise
and Tenant identity.
x
The Store Layout, fixtures etc., must be designed to comply with handicapped accessible
requirements as defined by local, state or national codes or laws.
x
Interior Finishes are to be high quality, long lasting and, durable. All finishes shall comply with
building code and the Landlord’s insurance underwriter requirements for appropriate fire
resistance and flame spread ratings. All trade fixtures shall be first class new fixtures with
durable finishes consistent with the anticipated public exposure.
x
All Exposed, Finished Wood shall be millwork quality kiln dried wood with a durable protective
finish where exposed to public contact. Wood blocking, decking, and framing is permitted below
the ceiling line and must be stamped fire retardant. All raised platforms shall be constructed of
non-combustible materials.
Walls
All interior partitions, including column covers, within the demised premises shall be metal stud
construction and shall have one layer of gypsum board (5/8” minimum) finish on both sides with taped
and sanded joints.
x
Demising Walls: Shall provide a 2-hour fire rating as required by code and shall comply with
one of the following two conditions:
In existing spaces which are not reconfigured, demising walls are existing and the Tenant shall
be responsible for maintaining and performing any necessary modifications or repairs to
maintain the required fire rating.
In reconfigured spaces, metal stud framing only shall be provided by the Landlord at all new wall
locations. The Tenant shall provide acoustic insulation and two layers of 5/8” fire code gypsum
board, taped and sanded and finished on the Tenant side of the metal studs to achieve the code
required wall rating. The gypsum board shall extend full height from the floor to the underside of
the structural floor above.
x
Exterior Walls: Where the demised premises include an exterior wall, the Tenant shall provide
and install board insulation with an R-19 rating (minimum), an interior vapor barrier up to the
structure above.
x
Interior Walls:
All walls visible to the public must be finished in an appropriate manner. If painted, walls must
receive two finish coats of paint, minimum.
Concrete masonry unit or other masonry construction shall not be permitted within the demised
premises without Landlord’s prior written consent.
Tenant shall provide fire dampers and stops as required by local codes.
All painting, decorating, paneling, wallpapering and all other finishes on walls and columns
located in the demised premises shall have a minimum flame spread rating as required by local
codes.
Penetration of exterior walls will not be permitted without Landlord’s prior written approval.
Water Tower Place
18
ARCHITECTURAL DESIGN CRITERIA
Tenants with “wet” uses abutting Landlord’s demising partition are required to install adequate
moisture protection on walls.
Floors
Tenants must provide a finished floor within the sales area of the demised premises and areas
accessible to the general public. Tenant’s finished floor is to be at the same elevation as adjacent
common areas. Tenants shall install a high-quality, highly-durable floor covering in areas accessible to
the public which conforms to the following:
x
Wood flooring installations shall be hard wood with wear-resistant finish.
x
Ceramic, quarry and stone tiles and exposed colored concrete installations must be commercial
grade with nonslip surfaces.
x
Carpet must be commercial grade and must have proper flame spread ratings to meet local
codes. Carpet will not be permitted where color, quality or weave is not suitable for high-traffic
areas.
x
Finished floor elevations at the store entrance must align with the border paver’s elevation at
common areas. Vinyl or rubber transitions are not permitted in the sales area; metal, terrazzotype transition strips are required.
x
All floor surfaces must comply with the requirements of local codes and the ADA. Samples of all
flooring materials must be submitted to Landlord for approval.
x
Floors areas where water is present shall receive a waterproof membrane extending a minimum
of 6” up adjoining partitions. The Tenant’s Contractor will be required to provide a flood test of
waterproofed areas prior to finishes being applied; the test is to be observed by the Operations
Manager.
x
Floors typically have a 2 ½” dimension from public common area flooring to the structural slab.
Ceilings
x
Ceiling work shall include but not be limited to ceiling treatments, light coves, soffits, suspended
ceilings, exposed ceilings, acoustical treatment, ornamental specialties, and other related items.
x
Interior ceilings shall be of noncombustible construction and shall be plaster; painted gypsum
wallboard; metal or cloth baffle system; concealed spline; or lay-in acoustical grid incorporating
no greater than a 2’x2’ acoustic tile. Other “lay-in” or exposed-structure ceiling systems may be
permitted but require Landlord’s written approval prior to installation. A lay-in ceiling can not be
utilized throughout the public store area. Ceiling drops and decorative ceiling treatments are
encouraged to break up a lay-in ceiling system. A lay-in ceiling is not allowed in the Display
Zone at the storefront.
x
If acoustical tile systems are used, tile material is strictly allowed on horizontal surfaces only. For
transitions to other ceiling heights, Tenant is to use an appropriate hard finish (gypsum board,
wood, etc.).
x
No combustible materials or equipment are allowed above the ceiling (i.e. transformer, water
heaters, etc.). All furring, framing and blocking above the ceiling shall be of noncombustible
construction that satisfies local code requirements. Construction is to be consistent with return
air plenum usage whether the space is used as a plenum or not.
x
Areas with exposed structure at the ceiling will require extra coordination with mechanical, fire
protection, lighting, and structural system requirements in order to provide an acceptable level of
appearance. If Tenant elects to utilize the exposed structure, all visible elements must receive a
painted finish.
Water Tower Place
19
ARCHITECTURAL DESIGN CRITERIA
x
All ceiling systems must allow for access via removable lay-in panels, tabbed concealed spline
panels or access panels of sufficient size to allow adequate access.
x
Ceiling surfaces within the Display Zone shall be gypsum board, wood, or other type of hard
surface material, and must extend a minimum of 10’-0” beyond the point of entry. Acoustical tile
will not be allowed in the Display Zone.
x
Store exit signs should be located so as not be seen from the center’s common area.
x
Sprinkler heads in hard ceilings must be fully recessed. The cover plates are to be chrome
finished or coordinated to match the ceiling color.
Stockroom and Exit Access
x
Tenant shall meet all Building Code requirements for exiting through a stock room. Tenant shall
also meet all requirements for general lighting and for emergency lighting requirements for exits
through stockrooms. The service door must be recessed so as not to reduce the width of the
service corridor when the door is opened. The Tenant must match the service corridor finishes
established by Landlord throughout the corridor side of the alcove.
x
Provide 2” high black lettering at the door indicating the store space number and name.
x
Stock room walls must be painted.
x
Stock room floors must have a finished floor material. Exposed concrete flooring is prohibited.
x
Tenants with direct access to Landlord’s service corridors shall install at least one (1) “B Label”;
18-gauge hinged 3’-6” x 7’-0” x 1 3/4” hollow metal exterior service door and 16-gauge hollow
metal, welded door frame, including commercial-grade hardware, consisting of a surfacemounted closer, one and one-half pair of butt hinges, wall or floor stops, 18” high kick plates,
and one push-bar type exit device.
Toilet Rooms
Tenants may be required to provide restrooms in accordance with Landlord requirements and the
Chicago Building Code. Reference the Plumbing Criteria section of this Manual for additional
requirements.
x
Ceramic tile or F.R.P. panels are required to be installed on all walls to a minimum height of 72”
above finished floor.
x
A waterproof membrane shall be installed at the floor.
x
A raised, accessible threshold must be installed at all toilet room doors to retain water spills.
x
Floor drains are required at all toilet rooms.
Water Tower Place
20
ARCHITECTURAL DESIGN CRITERIA
Structure
Any alterations, additions, reinforcements, or modifications to Landlord’s structure, piping, conduit, or
ductwork that are needed to accommodate Tenant’s work and vertical transportation connections shall
not be performed without in each instance obtaining Landlord’s prior written approval. Tenant shall leave
Landlord’s structure as strong as or stronger than the original design with finishes unimpaired. Landlord
may require that approved structural or mechanical/electrical modifications be performed by Landlord’s
contractor under contract to Tenant at Tenant’s expense and Landlord will require that engineering
analysis, review or design be performed by Landlord’s engineer at Tenant’s expense.
x
The structural system of the Center has been designed to support a live load of one hundred
(100) pounds per square foot excluding required concrete floor topping. This capacity shall not
be exceeded by any of Tenant's Work on a temporary or permanent basis without the prior
written consent of Landlord in each instance.
x
A 2-1/2" finish floor depression extending the full width and depth of the store may be unfilled or
a lightweight concrete topping may have been installed by a previous Tenant. The total weight of
existing and/or additional or replacement concrete fill combined with finish flooring is not-toexceed twenty (20) pounds per square foot.
x
Supplemental structural support framing shall be installed by the Tenant to adequately support
suspended equipment within the premises. Where unusually heavy loads are applied to either
the structural floor slab or to the building’s structural deck, specific details must be developed by
the Tenant and submitted for Landlord review and approval. All storefront construction shall be
floor supported only with an appropriate structural system, with appropriate lateral bracing back
to the building structure as required. No vertical load shall be suspended from the Landlord’s
storefront bulkhead system.
x
Mezzanine structures or staircases within any Tenant space shall require review and approval in
writing by the Landlord’s structural engineer at the Tenant’s expense. All mezzanines shall be
designed to be self-supporting. The area of Tenant mezzanines will be added to the Tenant’s
total leasable area.
x
Channeling of the structural concrete slab on any level shall not be permitted.
x
Coring may be permitted for installing piping and conduit through the slab, with concrete repairs
installed in accordance with building requirements.
A drawing submittal must be made to the Operations Manager prior to any slab penetrations
being made. Sonar investigations (X-Raying is not allowed) must be performed to locate existing
reinforcing and a drawing prepared; then proposed cores must be located within the reinforcing.
Drawing is to be dimensioned and to scale.
Allow ten business days for the review of the coring submittal. No coring work is to be performed
without approval from the Operations Manager.
Water Tower Place
21
ARCHITECTURAL DESIGN CRITERIA
Lighting
Tenants are encouraged to use lighting as an integral part of their storefront and interior store design. In
recent years, a wealth of lighting fixtures and techniques has come on the market, and innovative
lighting should be explored. Lighting can play an important role in attracting customers and enhancing
merchandising strategies.
All storefronts and general store lighting must be reviewed and approved by the Landlord, subject to the
following basic guidelines:
x
Tenant is responsible for lighting within the entire demised premises. All lighting must be
indicated on Tenant’s design submissions to the Landlord.
x
Lighting within the Tenant’s premises is to be designed to accentuate the merchandise and
product display within the Storefront show windows as well as the general sales area of the
store.
x
The Tenant shall provide a high level and quality of illumination above the Display Zone and
entrances.
x
All signs, logos, and Display Zone lighting at show windows shall be illuminated during Water
Tower Place operating hours, the period of which will be determined by the Landlord. These will
be controlled by a calendar time clock, with minimum 7-day, 24-hour capability, and connected
to the Tenant’s power supply.
x
All showcase and display cases must be adequately lighted and ventilated. Direct visual
exposure of incandescent bulbs and/or fluorescent tubes is prohibited.
x
A mixture of lighting types is encouraged in the Sales Area.
x
All light fixtures shall be the glare-free type. Light sources shall not be visible from outside the
store.
x
Troffer-type fluorescent fixtures used in public areas shall be fitted with parabolic diffusers.
x
Exit signs to be glass, edge-lit type.
x
Track light type lighting should be unobtrusive.
x
All lighting is subject to Landlord on-site review and approval.
x
All lighting is subject to City of Chicago energy conservation requirements.
Water Tower Place
22
ARCHITECTURAL DESIGN CRITERIA
Display Zone Lighting
x
Fixtures shall utilize lamps which have appropriate color rendering characteristics. All lamps
within the fixtures shall not be directed to shine into or be visible from common areas.
x
Track lighting must be recessed or else located so as to have minimal exposure to public view.
x
No lamp shall extend below the ceiling line or below the window head at show windows within
the Design Control Area.
Light Fixtures
Fixtures shall be high quality commercial grade. The fixtures shall be constructed and installed to be
glare free and shall comply with all applicable code requirements. Specific fixture requirements are as
follows:
x
Exposed fluorescent tube fixtures are to be used in non-public storage areas only.
x
Recessed incandescent or fluorescent can type fixtures must have specular or semi-specular
Alzak reflectors, coilex baffles, or other glare free shielding devices.
x
Specific Landlord approval is required for the use of coated metal halide lighting. For
consideration, information must be submitted which documents the quality of the light. (Color
rendering index rating, etc.)
x
All ceiling lighting fixtures above the ceiling must be City of Chicago plenum rated.
Lighting Not Permitted
x
Exposed lamps unless in an approved track light fixture.
x
Colored lamps.
x
Mercury vapor or high pressure sodium lamps.
x
Luminous ceiling, chandeliers and glitter strips.
x
Exposed, unshielded neon tube lighting of any kind.
x
Strobe, spinner, or chase type lighting. Animated flashing or intermittent lights, black lights.
x
Battery-powered emergency and exit lighting.
x
Luminous, internally-illuminated panels at the storefront.
x
Storefront lighting in the common area ceiling outside the lease line.
Exit Signs and Emergency Lights
Fixtures shall be installed to serve their intended function, but also be as inconspicuous as possible. The
quantity and location of exit signs and emergency lights shall be installed as required by code and the
Chicago Fire Department.
Only these lights can be connected to the Building emergency power system.
Water Tower Place
23
ARCHITECTURAL DESIGN CRITERIA
Storefront Design Criteria
Overview
Water Tower Place is the premier shopping center in the Chicago area. The quality of today’s retail
environment demands distinctive and high quality storefronts and presentations to enhance the shopping
environment.
Storefront Design
The unique characteristics and quality Tenant mix of Water Tower Place calls for innovative and modern
storefronts. Critical to the design integrity and success of the shopping center’s image are the individual
contributions of each Tenant’s store. It is essential that proper attention be paid to proportion, scale,
color, and detailing so that the Tenants can both enhance their image and that of Water Tower Place.
The Landlord has established general criteria for the storefronts, signage, and interiors intended to give
Tenants maximum design flexibility while maintaining a consistent and high quality environment.
Storefronts shall be designed, fabricated, and installed by Tenant at Tenant’s sole expense. The design
objective is to create a sophisticated, urban landscape that expresses a sense of scale and features
transparency, texture, and thoughtful response to Landlord provided architecture. All storefront designs
shall be carefully reviewed and approved by the Landlord.
x
Special lighting effects such as cove lights or up-lights are subject to approval by the Landlord’s
representative and will be reviewed on an individual basis.
x
In some cases, building columns occur along Tenant’s lease line and are exposed to public
view. Tenant shall incorporate these columns into their Storefront design.
x
Finished, ½” x ½” black reglets are to be installed at revels between Tenant storefront
construction and building neutral piers and ceilings.
Neutral Piers
If not already existing, it will be the Tenant’s responsibility to install the neutral pier(s). Front and side
panels are available from the Landlord at the Tenant’s expense. The Tenant shall install a 1’-0” deep x
1’-0” wide minimum recess between the neutral pier and the Tenant’s storefront.
Field Verification of Existing Conditions
Because of varying conditions throughout this center, Tenants and their architects should field verify the
existing conditions before drawings are completed. Items to be verified that critically affect the store
construction include, but are not limited to, the following:
x
Storefront opening boundary conditions (heights, width, floor slope conditions).
x
Conditions of the neutral piers.
x
Bulkhead construction above the existing storefront.
x
Exact location of the storefront lease line.
Storefront Transparency
At the storefront, Tenants shall maximize the use of glass to maintain a show window type concept in the
design of the storefront. Storefronts shall be a minimum of 70% transparent.
Full height opaque areas on the storefront shall not exceed 12 feet in width. Opaque areas exceeding 8’0 in width must be illuminated; note that Tenant light fixtures may not be located outside the lease line.
Water Tower Place
24
ARCHITECTURAL DESIGN CRITERIA
Storefront Entry Door Closure Line
May be recessed from the lease line to create visual identification at each storefront. Swinging entry
doors shall be recessed at least three feet from the lease Line, or as necessary to ensure that when
open the doors do not swing beyond the lease line.
Storefront Entry Opening Widths
x
Storefront openings shall be limited to six feet in width for storefronts with 30’ or less of frontage.
x
Storefront openings (combined frontage) of more than 30’ but less than 60’ shall have one
entrance of 10’ maximum width.
x
For stores with more than one elevation facing public common areas, one entry will be allowed
for each distinct storefront elevation which is 20 feet or greater in width. The general opening
width restrictions noted above shall apply for each individual elevation. The total combined
opening width for all openings shall not exceed 12 feet.
Storefront Entry Element
x
Storefronts should be designed to incorporate an entry feature at the entrance into each leased
space.
x
For the intent of this criteria, the term “entry” shall be described as a grand or imposing entrance
and shall encompass the whole architectural composition surrounding and including the
doorway.
x
Recessed storefront entry elements are permitted.. Floor finishes on the outside of any
storefront setback are to be finished with the building’s ‘black’ granite border material and
terrazzo pavers.
Storefront Materials and Colors
x
Tenants are required to employ high quality, richly finished materials in the construction of
storefront to promote high quality.
x
Metal storefronts shall have factory finished components with baked enamel or anodized
finished.
x
Clear anodized aluminum is the minimum acceptable finish for metal systems.
x
The return on any projecting architectural element must be finished with storefront material to
avoid a thin “stage set” look.
x
Rich, visually dramatic hardwoods are acceptable. All wood and wood panels must be book or
color matched. For Landlord approval, submit an actual sample (9” x 9” minimum) of the
intended material and finish for review as part of the required material sample board.
x
Natural stones that are rich, elegant and/or visually dramatic are preferred. All stone materials
(including marbles, granites and tiles) must be color and grain matched. All edge and corners
must be mitered; no unfinished corners or edge allowed. Tile may be used as a decorative
application.
Water Tower Place
25
ARCHITECTURAL DESIGN CRITERIA
x
The Storefront Base shall be a minimum of six (6”) inches in height. The base must be a highly
durable material such as stone, tile, substantial gauge metal with an anodized finish or other
material that can withstand contact with cleaning equipment and solutions. Storefronts shall be
designed to resist damage at potential impact areas such as outside corners.
Storefront Construction
All storefronts shall be self-supporting unless otherwise approved by the Landlord. The storefront may
be braced to the base building. No gravity loads may be suspended from the Landlord’s structure or light
cove bulkhead framing without the written approval of the Landlord’s structural engineer. No attachment
will be allowed to the Landlord’s vertical neutral pier.
Common Area Flooring Border at Tenant Storefronts
The Tenant is to install a decorative black granite border at the storefront. The Tenant shall be required
to purchase the stone from the Landlord; contact the Operations Manager for procurement of materials.
Prohibited Storefront Materials
x
Painted drywall.
x
Vinyl or fabric wall coverings.
x
Plexiglas type materials.
x
Stucco or similar finishes.
x
Slat wall or pegboard.
x
Plastic laminates.
x
Mill finished aluminum.
x
Field painted metal.
x
Thin gauge metal or metal laminate finishes which will warp.
x
Artificial ‘faux’ finishes.
x
Mirror finishes.
x
Wood veneer except for commercial grade veneer products that are recommended for use in
high traffic locations. Solid wood must be used at all corners and edges. Wood must have a
durable finish. Excessive graining patterns in any wood will not be allowed.
Recessed Storefront Configurations
The Tenant shall be allowed to recess the storefront construction behind the lease line. Common area
stone flooring shall be installed at the floor of recesses to continue the pattern and installation quality of
the adjacent common area flooring. The 6” wide black border granite and travertine flooring must be
purchased from the Landlord; contact the Operations Manager for procurement of materials.
Water Tower Place
26
ARCHITECTURAL DESIGN CRITERIA
Entries/ Doors
x
Tenant must recess entry doors such that they do not swing into the common area or beyond
lease line. At the entry door recess, Tenant shall install paving, extending from the lease line to
the door closure line. Tenant must install the Landlord’s standard granite border and terrazzo
pavers; contact the Operations Manager to arrange the purchase of the stone pavers.
x
Tenant’s doors are encouraged to be substantially glass and must be a minimum of 8’-0” high.
x
Storefront doors may incorporate decorative features that enhance the overall storefront. Tenant
designers should strive to specify doors that become an integral aesthetic feature to the overall
storefront design.
Door Closure Types Permitted
x
Swinging doors that project beyond the lease line.
x
Frameless glass sliding doors.
x
Sliding glass doors that are concealed from view when the store is open. The sliding doors must
be hidden in a storage pocket with a door. The storage pocket must be creatively incorporated
into the design of the storefront and storefront display zone to be as inconspicuous as possible.
Overhead or side-coiling grilles are NOT allowed in the storefront!
Display Windows/ Glazing
x
Display windows should be unique and individual. Window displays should thus be integrated
into the architectural design and character of the entire storefront. A variety of textures in display
and window treatment should be explored, as well as innovative lighting and window designs
(see Signage Criteria). Display windows shall be transparent and open to the store. No
backdrops behind displays will be allowed unless approved by the Landlord.
x
For greater transparency, a storefront glazing system with a minimum use of mullions or frames
is required.
x
Corner Tenants must install display windows and/or store openings on both elevations. Solid
walls will not be permitted along the lease line without approval from the Landlord.
x
All textured, patterned or obscure glazing must be reviewed and approved by Landlord.
Water Tower Place
27
ARCHITECTURAL DESIGN CRITERIA
Display Zone
The Display Zone for the purposes of these criteria is defined as the area of the store extending from the
storefront glass and entry door lines into the store a minimum of 5 feet across the entire width of the
store. In this zone, design solutions and materials are expected to be of the highest quality. The Display
Zone includes all display windows and retail graphics, display fixtures, signs, materials, finishes, colors,
and lighting.
x
The Landlord will closely review all elements in the Display Zone.
x
The soffit at the storefront entrances may be finished in the same material as the storefront. The
soffit height shall not be greater than the required storefront opening height. Acoustical tile is not
an acceptable ceiling for any part of the Design Control Area.
x
Floor finishes in this zone shall be hard surface, high quality, durable materials such as wood,
stone, or ceramic tile shall be provided throughout this zone. Carpeting will not be allowed.
x
The finished floor elevations at the premises entrance must match exactly the floor elevation of
the common area. No tripping hazards such as reducer strips, thresholds or other noticeable
transition devices shall be permitted.
x
All walls within this zone shall be provided with high quality finish materials. Materials such as
stone tile, wood panels, high quality wall coverings, and the use of trim and other decorative
treatments shall be utilized. Slatwall is not permitted.
x
Refer to the Lighting Criteria for Display Zone lighting requirements.
Water Tower Place
28
ARCHITECTURAL DESIGN CRITERIA
High Quality Show Window Displays
The Tenant shall utilize distinctive, high quality and appropriate display techniques which best showcase
the Tenant’s merchandise, including but not limited to the use of mannequins, platforms, tables, etc.
x
The sidewalls of the store Display Zone shall be dedicated to storefront display, and the
storefront show windows shall not contain “sale” merchandise.
x
At the storefront entry, display fixtures or merchandise, either temporary or permanent, shall not
be placed closer than three feet inside the Tenant’s premises, measured from the point of
storefront closure.
Video Monitors
Monitors installed within the Display Zone or that are visible from common areas require specific
approval by the Landlord. Monitors within the Display Zone shall be integrated into the overall show
window design. The monitors, if allowed, may not emit any sound that can be heard from outside the
store.
Sound Systems
No sound systems are to be audible in common areas or in adjacent Tenant spaces.
Storefront Security Systems
Systems must be indicated on the Tenant design submittal drawings and reviewed and approved by the
Landlord in shop drawing form prior to installation. Tenants shall not place a security system into
operation without first receiving Landlord’s prior written approval as to size, location, design and
appearance. All wiring to security systems must be concealed from view. Any security system installed
shall be generally compatible with the finishes of the Storefront Display/Entry Zone. Trenching of the
topping layer only must be first coordinated and approved by the Operations Manager.
Security Systems Permitted:
x
Concealed systems not visible to the customer (under floor system), within the topping layer
only. Power poles or wiring channels exposed to view are not permitted.
x
Suspended overhead “bar” type systems concealed behind a storefront soffit above the entry.
x
Small pod type systems on each side of the storefront opening.
x
Tower tied into the storefront as part of the architecture.
Security Systems Not Permitted:
x
Free standing tower or wall-mounted type exposed security devices.
Sprinkler Heads
Display Zone heads shall be the fully recessed type with cover plates.
A sprinkler water curtain is required by the building-specific agreements with the City of Chicago. Heads
must be spaced a minimum of 6’-0” apart and within 4’-0 of the storefront. Sprinklers at that spacing in
common areas must not be blocked from the storefront.
Water Tower Place
29
ARCHITECTURAL DESIGN CRITERIA
Store Design Plan Diagram
Water Tower Place
30
ARCHITECTURAL DESIGN CRITERIA
Storefront Criteria
Water Tower Place
31
ARCHITECTURAL DESIGN CRITERIA
Storefront Section
Water Tower Place
32
ARCHITECTURAL DESIGN CRITERIA
Storefront Section at Well
Water Tower Place
33
ARCHITECTURAL DESIGN CRITERIA
Storefront Detail Section
Water Tower Place
34
ARCHITECTURAL DESIGN CRITERIA
Storefront Reflected Ceiling Plan
Water Tower Place
35
ARCHITECTURAL DESIGN CRITERIA
Typical Neutral Pier Detail
Water Tower Place
36
ARCHITECTURAL DESIGN CRITERIA
Neutral Pier at Existing Store
Water Tower Place
37
ARCHITECTURAL DESIGN CRITERIA
Neutral Pier at a Corner
Water Tower Place
38
ARCHITECTURAL DESIGN CRITERIA
Neutral Pier Detail at Corridor
Water Tower Place
39
ARCHITECTURAL DESIGN CRITERIA
Typical Neutral Pier Elevations
Water Tower Place
40
ARCHITECTURAL DESIGN CRITERIA
Typical Neutral Pier Elevations
Water Tower Place
41
ARCHITECTURAL DESIGN CRITERIA
Tenant Storefront at Mall Column
Water Tower Place
42
ARCHITECTURAL DESIGN CRITERIA
Typical Tenant Demising Wall
UL U411 - 2HR
Water Tower Place
43
ARCHITECTURAL DESIGN CRITERIA
Typical Service Corridor Door
Water Tower Place
44
ARCHITECTURAL DESIGN CRITERIA
Construction Barricade
Water Tower Place
45
SIGNAGE DESIGN CRITERIA
Signage Drawing Requirements
Overview
The primary purpose of this exhibit is to ensure that project and tenant signage within Water Tower
Place enhance the “urban” character of the property, create a lively and provocative atmosphere,
establish the identities of Tenants, and provide clear, functional information.
The Sign Criteria/Master Sign Plan will ensure that signage used by individual businesses will contribute
to the vitality and interest of Water Tower Place. Special considerations were taken to ensure signing
becomes an extension of the architecture. The Water Tower Place program will allow for flexibility in size
and number of signs. The criteria for tenant signage are divided into sections which align with the scale
and variety of leasable zones on the site. The following descriptions outline design goals and
functionality for the differing zones within the development.
Drawing Submission Requirements
•
Incorporate signage into storefront elevation.
•
Indicate letter height.
•
Provide typical sign section(s).
•
Indicates methods for wiring and mounting.
•
Indicate color and materials.
•
Provide blade sign graphics (if applicable).
General Requirements
•
To verify compliance with the design intent of these criteria and local codes, the Landlord
reserves the right to review and approve or disapprove all proposed signs and/or graphic
treatment governed by these criteria per the Landlord’s interpretation of these criteria, and to
require revisions of any sign design which the owner/Landlord judges to be not in compliance.
•
Sign fabrication and installation shall comply with any applicable building codes and the National
Electrical Code, and all internal and external wiring, lighting, and other electrical devices shall
bear the U.L. symbol. It is the Tenant’s responsibility to verify that its sign and installation are in
accordance with these requirements and with local signage ordinances.
•
Tenant is responsible for maintaining its sign in a good state of repair including prompt
replacement of burned out lighting or damaged pieces. Tenant has 24 hours to make repairs
after being notified by Landlord.
Water Tower Place
46
SIGNAGE DESIGN CRITERIA
Tenant Signage
Signage Design Requirements
•
The Landlord requires that all signage at this center be of the highest design and material quality
in order to maintain an appropriate, upscale atmosphere. The Landlord encourages innovation of
design and sophistication of materials (i.e. polished brass, etc.).
•
All Tenant identity signs shall be illuminated.
•
A mix of sign styles and materials is encouraged, though all signs remain subject to Landlord’s
approval and must comply with applicable, local code requirements.
•
Tenant’s signage shall be installed on Tenant’s storefront surface and shall be designed as part
of the overall storefront design.
•
Tenant is required to design, fabricate, install and maintain all Tenant signage with the exception
of the blade sign (if applicable).
•
The Tenant’s sign shall be limited to the Tenant’s approved trade name as stated in the lease.
The use of a corporate logo or other established corporate insignia shall be permitted only if
specifically approved in writing by the Landlord. Taglines or identification of specific products or
services are not permitted.
•
One sign is allowed per storefront elevation. A second sign may be provided at elevations
exceeding 90’-0 in length.
•
The power source for Tenant Display Zone lighting, storefront signs and blade sign must
originate in Tenant’s electrical panels and must be regulated by Tenant’s seven-day, twentyfour-hour calendar time clock, set in accordance with the Landlord’s operating hours.
Signage Location Criteria
Storefront signage shall not be located closer than two feet from the edge of each neutral pier, less than
three feet from the floor or project over the lease line.
Signage Size Criteria
•
In all cases, the Tenant’s storefront signage shall be proportional to the scale of the overall
storefront design.
•
Upper case letter size for storefront signs using all upper case letters shall be limited to a
maximum height of 14 inches.
•
Upper case / lower case and script letter sizes shall have a maximum height of 18 inches for
ascending or descending letters. Lower case letters without ascending or descending letters
shall have a maximum height of 12 inches.
•
The length of horizontal lettering shall not exceed 50% of the horizontal storefront length. The
proportional ratio of the proposed signage length to the overall horizontal storefront length shall
be left to the sole discretion of Landlord.
Permitted Signage Types
•
Silhouette (Halo Type) illuminated individual reverse channel letters.
•
Open faced channel letters with internal tube neon illumination.
•
Internally illuminated fully recessed cabinet sign with push through letters.
•
Non-internally illuminated individual letters.
Water Tower Place
47
SIGNAGE DESIGN CRITERIA
Signage Types Not Permitted
•
Internally-illuminated sign boxes with translucent faces are not permitted.
•
Internally illuminated individual letters with translucent faces.
•
Exposed, surface mounted, box or cabinet type signs.
•
Cloth, paper, cardboard and other similar stickers or decals on or around the storefront surfaces.
•
Freestanding, moving, rotating, flashing, noise making or odor producing signs.
•
LED signs where individual LED ‘dots’ are visible.
•
Signs which are not professional in appearance.
Permitted Sign Type Criteria
•
•
•
•
Halo Type Illuminated Signs
o
The background surface for the sign is to be opaque and not reflect the illumination or image
of the lamps within the letters.
o
All lamps must be fully concealed within the letter to not be visible to the public.
o
The rear face of the letter shall not be more than one inch from the background surface.
o
Standoff brackets shall be mounted in the least visible location to support the letters.
o
Visible standoff brackets and fasteners shall be painted to match the background surface.
Reverse Channel Letters with Tube Neon Illumination
o
Sign letters are to be fabricated of metal or aluminum faces, returns and backs.
o
If trim caps are used they are to match the letter returns.
o
Fasteners shall be concealed from view and painted to match the surrounding sign letter.
o
PK Housings shall be used.
Internally Illuminated, Fully Recessed, Cabinet Signs
o
Signs shall be fully recessed into the storefront construction with the face of the cabinet sign
flush with the surrounding storefront material.
o
The size of the sign cabinet and the design of the face materials are to be integrally
designed into the appearance of the storefront.
o
Letters only shall be translucent on the sign face. The background must be opaque.
o
Signs must be of the highest quality, design and construction.
o
Seams are not permitted in the face of the sign cabinet.
Individual Letter Signs with External Illumination
o
Included types are: non-dimensional and dimensional letters or graphics applied directly to
the face of the storefront area. Techniques include painting, silk-screening, pressure
sensitive vinyl, metal appliqué, glass etching or wood, metal and acrylic letters.
o
Signs shall not be placed on a background material which detracts from the sign’s
appearance.
o
Supplemental lighting inside the lease line is required for signage mounted on opaque
surfaces.
o
Dimensional letter signs applied directly to transparent storefront glass will have matching
dimensional letters on each side of the glass to create a finished appearance from both
sides of the storefront glazing.
Water Tower Place
48
SIGNAGE DESIGN CRITERIA
Tenant Blade Signs
A single, internally illuminated, fully recessed, cabinet-type blade sign must be installed at Tenant
spaces not in or directly adjacent to the center Atrium area; Tenants at the Atrium cannot install blade
signs. The sign will be adjacent to the neutral pier closest to the center Atrium. Proposed blade sign
graphics are to be included in the Tenant design submittal.
•
•
Graphics Requirements:
o
Graphics are limited to Tenant trade name and logos; see page 47.
o
Minimum height of trade name upper case letter is 3”.
o
Translucent graphics must be within the 9” by 20” illuminated area of the sign body.
o
Sign graphics may be layered if necessary, but three-dimensional graphics are not allowed.
o
Translucent graphics are to push-through the face panel between ¼” to ½”.
o
If the Tenant logo or logotype is too fine for push-through fabrication, the cut-out graphics
may be flush with the opaque face panel.
Color Requirements:
o
Colors of translucent graphics and opaque face panels are determined by the Tenant; the
Landlord reserves the right to review and approve/ disapprove all proposed sign colors.
o
The blade sign design concept consists of light-colored, translucent, back-illuminated
graphics on a darker, opaque face panel. White or light-colored face panels are not allowed.
o
Tenants that have corporate colors may use those colors for graphics and face panels,
subject to Landlord approval.
•
Blade signs will be furnished and installed by the Landlord's sign contractor; this excludes power
wiring from the sign to the Tenant power panel to be provided by the Tenant. The blade sign is
to be switched with the Display Zone.
•
The cost of sign fabrication and installation is to be paid by the Tenant. Tenant to provide digital
artwork in EPS format and Pantone color specifications for fabrication by the Landlord's sign
contractor.
•
The sign contractor will submit a shop drawing to the Tenant for review & approval prior to sign
fabrication.
Repetitive Safety Symbols
Graphics may be applied to the storefront glass for identifying transparent storefront surfaces for
customer safety purposes. This lettering shall not be more than three inches in height and shall be
centered at 3’-6 above the floor.
Signage Construction Requirements
•
Shop fabrication and painting is required.
•
All signs shall be mounted according to Landlord approved drawings. All fasteners shall be of
non-corrosive material and concealed.
•
Sign company names or stamps shall be concealed if permitted by code. All attachments,
labels, fasteners, mounting brackets, wiring, clips, transformers, disconnects, lamps (except
exposed neon tubes) and other mechanisms required for all signage will be concealed from
public view.
•
Light leaks visible to the public, including drain holes, are not permitted.
•
Sintra will not be permitted for Tenant storefront signage.
Water Tower Place
49
SIGNAGE DESIGN CRITERIA
Submittals & Approvals
It is the Tenant’s responsibility to obtain approval by the local government agencies. Approval of the
Tenant’s design or working drawings by the Landlord shall not constitute review and approval of the
Tenant’s signage. Tenant shall submit one set of sign shop drawings for review and approval by
Landlord. Fabrication or installation of the Tenant’s signage shall not commence before the Landlord’s
approval of the sign shop drawings. Note that only written approvals from the Landlord are valid.
Each Tenant submittal shall include the following:
•
Scaled elevations (minimum 1/8” = 1’-0) with sign materials noted and graphics superimposed
on storefront construction.
•
Color and material board.
•
Shop Drawings of signs, which must include a cross-section showing methods of installation.
•
Photographs of similar signs should be submitted wherever possible.
City Sign Permit
The Tenant is responsible to obtain City of Chicago sign permits. Note that only licensed sign
contractors can apply for the permit. The permit process has been known to take up to six months.
Water Tower Place
50
HVAC DESIGN CRITERIA
The following is a list of minimum design information required to expedite plan approval by Landlord. It is
not intended to be a complete listing of all requirements, but should serve as a minimum checklist to be
used by Tenant’s design consultants to complete the construction documents. All mechanical designs
must conform to City of Chicago Building Code groups 13 Energy Conservation and 28 Mechanical
Systems. The code is issued annually.
We urge designers to read this manual in its entirety in order to fully understand the requirements needed
to generate an approvable set of construction documents.
HVAC Submittal Requirements
•
Heating and cooling design calculations are required for City permit and for Landlord approval.
Submit permit-required heating and cooling load calculations.
•
At spaces with exterior heat loss, also provide a Non-Operating Hours Heating Calculation with
the following conditions: Building air system non-operational, space unoccupied and lighting off. A
Tenant heating system independent of the building fan system may be required.
•
Plenum return air system indicated.
•
Mechanical symbol list and equipment schedules. Include VAV control sequence numbers.
•
Location of HVAC equipment, including air terminals, heating devices, ductwork, thermostats,
control wiring and other equipment intended for installation.
•
Duct sizes and heights above finished floor, including existing building ductwork and connections
to same. Include required damper locations with required fire ratings.
•
Diffuser and grille schedule.
•
Insulation specification.
•
Typical hanger detail from concrete slab.
•
Control wiring diagram.
•
Toilet exhaust detail (if required).
•
Condensate collection with P-trap (if required).
•
Exhaust fans and related ductwork (if required).
Additional Drawing Requirements for Food Related Tenants
•
Exhaust airflow analysis of Tenant kitchen exhaust system and its effect on Landlord risers.
Obtain existing conditions (duct sizes and fan airflow) from the Building Engineer.
•
Specifications of exhaust equipment.
•
Equipment locations and structural support details.
•
Cooking hood details and equipment. Exhaust fans and hoods must have an approved “grease
guard” filter system.
•
Automatic fire extinguishing equipment.
•
Control/fire alarm wiring interface diagram.
•
Details of grease exhaust ducts including method of construction, access and connection to
existing building exhaust riser.
•
Make-up air unit details and specifications (if required).
•
Note that direct-fired make up air units and evaporative pans at refrigeration equipment are not
permitted.
Water Tower Place
53
HVAC DESIGN CRITERIA
Design Parameters
•
Outdoor Temperature
94.2 FDB/76.5 FWB Summer (ASHRAE 1%)
(-10) FDB Winter (ASHRAE 99.6%)
•
Indoor Temperature
76 FDB Summer/ 50% RH
70 FDB Winter
50 FDB Winter during non-operating hours
•
Outside Air
Minimum Code Requirement provided by Landlord.
•
“U” Factors
Exterior Wall 0.1
Glass 0.70
SHGC 0.50
•
Supply Air: Maximum of 1.25 CFM/SF.
Winter: Minimum 50°F
Summer: Maximum 55°F
•
Static Pressure: Maximum 4.0 WC” and Minimum 0.75 WC”.
•
Hours of supply air system operation: Coincides with Mall operating hours.
•
Lighting and People Load: Per Tenant design and City of Chicago Energy Code.
•
Equipment Load: Per Tenant design and industry standards.
•
Water Tower Place is a high-rise building; roof and exterior wall access are extremely restricted.
Work by Landlord
•
The Landlord provides the following in or near the Tenant’s Leased Premises: supply air main
duct (tap by Tenant if not existing); return air main duct (tap and volume damper by Tenant if not
existing); toilet exhaust main duct (tap and volume damper by Tenant if not existing). Point-ofconnection to Landlord main ducts shall be as specified by the Landlord. Connections shall be by
a Landlord approved contractor.
•
The Landlord provides a building smoke evacuation system. Smoke detectors at return air ducts
and sprinkler flow alarms send the fan system to 100% exhaust. Alterations to and interface with
Landlord’s life safety/smoke exhaust system, if required, shall be by Landlord’s contractor at
Tenant’s sole expense.
•
2.0 Watts per square foot is available for electrical heating.
Work by Tenant:
•
The Tenant shall provide VAV boxes, thermostats and controllers conforming to Building
specifications. Reference the Tenant VAV Box Detail, page 57.
•
The Tenant shall provide all ductwork, grilles, volume control devices, fire dampers, etc. within
the Tenant’s Leased Premises in accordance with Landlord’s criteria stated herein, Code
requirements and good engineering practices.
Water Tower Place
54
HVAC DESIGN CRITERIA
•
Tenants at spaces with exterior exposure must provide HVAC systems that maintain minimum
temperature during non-operating hours.
•
Tenant energy usage will be based on total supply air CFM provided by Building Systems. BTU
meters will be required at Tenants utilizing Building conditioned water for heating and/or cooling.
•
Ductwork shall be galvanized sheet metal designed, fabricated and installed in accordance with
the Sheet Metal and Air Conditioning Contractors National Association, Inc. (SMACNA) design
practices and standards for low pressure, low velocity ductwork. Maximum flexible duct length
allowed: 5 feet fully extended. All ductwork from the Landlord’s supply air main to the Tenant’s
VAV box shall be pressure class: 4.0 inch / seal class A (flexible duct is not allowed). Balancing
devices shall be installed in accordance with Associated Air Balance Council standards and
Landlord requirements.
•
Ductwork Insulation: The minimum installed R-value shall be 3.6, or greater where required by
Code. Duct wrap shall have a FRK foil vapor barrier. For exposed supply air ductwork, minimum
installed R-value shall be 2.0 so as to prevent condensation.
•
Fire dampers shall be provided where required by code, but shall not interfere with the Building
smoke evacuation system. Provisions shall be made for sufficient access to each fire damper. All
fire dampers must carry evidence of UL approval and appropriate fire ratings.
•
Air distribution devices shall be ceiling or side-wall mounted registers or diffusers installed as
required to achieve draft-free air distribution in accordance with good engineering practices. A
manual volume damper shall be installed upstream (minimum 3 feet) of registers or diffusers in all
sales areas. Residential grade devices are not acceptable.
•
In areas with an inaccessible ceiling, provide access panels for adjusting volume dampers and air
terminal devices.
•
Air balancing shall be by an independent Landlord approved NEBB or AABC certified balancing
contractor. The report shall include VAV box airflow sensor differential pressure reading at
maximum and minimum cooling, return air at tap to main and at toilet exhaust (if applicable). If
additional types of exhaust systems have been installed, these must be included.
•
Contractor shall provide the Operations Manager with a copy of a certified HVAC Air Balance
Report prior to close out of construction.
•
The building has been designed for Tenants to use the area above the ceiling as a return air
plenum. No ducted returns are allowed. All work above ceiling must meet and comply with City of
Chicago plenum requirements.
•
All demising wall penetrations must be reviewed and approved by the Landlord.
•
All proposed pipe penetrations through concrete slabs must be documented and submitted on a
dimensioned drawing submitted to the Operations Manager for review and approval.
•
Flexible duct is allowed downstream of VAV boxes only and cannot exceed 5’-0 in length.
•
The building is transitioning from a pneumatic temperature control system to electrical controls.
Selective demolition of pneumatic piping must maintain the integrity of the existing system.
Tenant HVAC equipment cannot be connected to the pneumatic system.
•
The Tenant shall provide a conduit system connecting thermostats and VAV box controllers to
support a future, central Energy Management System. Terminate the Tenant conduit at a
location within the nearest Building Service Corridor.
•
Coordinate the possible salvage of existing VAV boxes and accessories with the Building
Engineer prior to their demolition.
Water Tower Place
55
HVAC DESIGN CRITERIA
•
No insulation may be installed on top of suspended ceilings.
•
Thermostat set points are to be programmed by the Tenant in accordance with Building Design
Parameters. Evidence of conformance is to be provided to the Building Engineer prior to the
occupancy of any Tenant space.
Exhaust Requirements
•
Exhaust systems are required for any Tenant occupancy that may produce odors, such as nail
salons, beauty shops, photo processing stores, or stores with demonstration cooking facilities or
food preparation and cooking areas. The required exhaust system shall be designed in
conjunction with the HVAC system to provide and maintain a negative airflow relative to the mall
and adjacent Tenant spaces to prevent the migration of odors and other contaminates out into the
mall and adjacent Tenant spaces. The Landlord shall determine the required negative airflow.
•
Tenants may exhaust to the outside a maximum of 10% of the total Building supply air provided
to the space. Additional make-up air shall be provided by the Tenant.
•
At kitchen exhaust systems, Tenant shall maintain required exhaust airflow and air velocity in the
Building exhaust risers in accordance with applicable codes, including NFPA 96.
Tenant fire detection system must be connected with Building alarm system for automatic fan
shutdown in case of fire.
VAV Box Requirements
•
VAV boxes, thermostats and controllers to be as specified on the Tenant VAV Box Detail.
Water Tower Place
56
HVAC DESIGN CRITERIA
Tenant VAV Box Detail
Water Tower Place
57
ELECTRICAL DESIGN CRITERIA
Electrical Drawing Requirements
The following is a list of minimum design information required to expedite plan approval by Landlord. It is
not intended to be a complete listing of all requirements, but should serve as a minimum checklist to be
used by Tenant’s design consultants to complete the construction documents. Tenant’s electrical service
has provisions for monitoring electrical usage.
We urge you to read this manual in its entirety in order to fully understand the requirements needed to
generate an approvable set of construction documents.
•
Floor and wall receptacles, location and type.
•
Fans, motors and all electrical equipment, location and type.
•
Floor and wall voice/data outlets, location and type.
•
POS outlets (voice/data outlets and isolated ground receptacles), location and type.
•
Lighting fixture layout (including lamp type and voltage).
•
Lighting fixture schedule (with make and model numbers).
•
Emergency exit and emergency lighting fixture layout.
•
Branch circuit, wire size and layout.
•
One-line diagram, including conduit and wire sizing.
•
Conduit and wire as required for extension of the building emergency messaging system.
•
Building Fire Detection/Emergency Voice Communication appliances and wiring.
•
Electrical service layout (i.e. panel(s), transformer, time clock, etc.); plan must be 1/2” =1’0”.
•
Conduit and wire sizing for HVAC equipment and panel; indicate over current protective device
type disconnect type and size for equipment and panel.
•
Complete electrical panel schedule(s) and MEP tabulation sheet.
•
Transformer size, type and location if needed for retail build-out.
•
Specifications.
Landlord Supplied Electrical and Voice/Data Services
The Landlord has designed and installed an electrical distribution system originating from the electrical
service rooms located throughout the premises. A main breaker for Tenant use is located in Landlord’s
distribution panel.
Design Parameters
•
Electrical Service: 208Y/120V-3Ph, 4W, 60Hz
•
Retail Tenant: 13.5 watts/square foot.
•
Free standing kiosk or micro salon shall be furnished with (2) - 20 Amps circuits.
•
Restaurant Tenant: 40 watts/square foot.
Water Tower Place
58
ELECTRICAL DESIGN CRITERIA
x
Telephone/Communication Service: The Tenant shall install telephone service wiring as required
by the phone company. The Tenant shall be required to coordinate the connection at the base
building backboard with the phone company directly.
x
All conduits shall be concealed where possible. Exposed conduits shall be in straight lines
parallel with or at right angles to column lines or beams and separated at least twelve (12”)
inches from water lines wherever they run alongside or cross such lines.
x
Emergency lighting shall be based upon 0.1 watts per square foot.
x
Tenant Heating: 2.0 watts per square foot.
x
Tenant electrical service requirements which exceed these criteria will require written permission
from the Landlord. If modifications to the Landlord’s distribution system are required to
accommodate Tenant’s service requirements in excess of the capacities indicated above, such
modifications will be at Tenant expense.
Work by Tenant
The Tenant shall provide a complete electrical system originating from Landlord’s main distribution
switchgear. Extension from the stub-in conduit to its final desired location and all wire from Landlord’s
main switchgear to within the leased premises including, but not limited to all necessary labor, Tenant
panel main and branch circuit breaker panels, conduit, wire, etc., necessary for the satisfactory operation
of the electrical system, is furnished and installed by Tenant.
Water Tower Place
59
ELECTRICAL DESIGN CRITERIA
Electrical Construction Requirements
•
All Tenants must comply with IECC, 2003 Edition.
•
All Tenants shall comply with City of Chicago and State of Illinois energy conservation code
requirements.
•
Electrical equipment and material shall be new, in accordance with the Chicago Electrical Code
and National Electrical Code (NEC) whichever is more stringent and shall bear the Underwriter’s
Laboratory label.
•
Final connection of Tenant’s conductors at Landlord’s main switchgear shall be performed by the
Landlord’s electrical contractor at Tenant’s expense.
•
Electric meters may be located at existing sockets at Landlord switchgear or may be required to
be located within Tenant premises; the Tenant is to confirm the meter location available for their
space.
•
Electrical panel(s) to be provided with bolt-on breakers and copper bus bars (10,000 AIC
minimum rating), and Tenant’s engineer to verify that AIC is adequate for available fault current at
120/208V.
•
Provide single disconnecting means in Tenant space.
•
Provide 7-day time clock to control the storefront entry, signage and Display Zone lighting during
required hours designated by the Landlord. The time clock shall be the calendar type.
•
Lighting circuit breakers shall be rated for switching duty.
•
All slab penetrations shall be presented on a dimensioned drawing submitted to the Landlord for
review and approved by the Landlord’s structural engineer.
•
All electrical equipment shall be labeled. Provide permanent mounted panel numbers and
schedules. “Dymo” tape type identification is not permitted.
•
All electrical equipment light fixtures, conduit J-boxes and wiring above ceiling shall meet Chicago
Plenum Code requirements.
•
Conduit connections are to be compression type fittings.
•
Conductors shall be continuous with no splices between the switchgear in the distribution room
and panels within the Leased Premises.
•
All pre-existing, unused electrical equipment and conduit are to be removed.
•
Building Fire Detection/Emergency Voice Communication conduit and junction box covers to be
pre-finished with red color; box covers to have ‘FA’ alarm designation.
Water Tower Place
60
ELECTRICAL DESIGN CRITERIA
Electrical Service Diagram
Water Tower Place
61
ELECTRICAL DESIGN CRITERIA
Emergency Lighting Schematic
.
Water Tower Place
62
PLUMBING DESIGN CRITERIA
Plumbing Drawing Requirements
The following is a list of minimum design information required to expedite plan approval by the Landlord.
It is not intended to be a complete listing of all requirements, but should serve as a minimum checklist to
be used by Tenant’s design consultants to complete the construction documents.
All plumbing drawings must be prepared and sealed by State of Illinois licensed engineer and must
clearly show:
x
The location of all fixtures including water heater
x
Clean-out and floor drain locations
x
Domestic water distribution
x
Water heater detail with relief valve and piping to floor drain
x
Location of sanitary and vent connection
x
Location of existing drains as applicable
x
All connections to Landlord’s mains
x
Water meter location
x
Water, waste and vent riser diagrams
x
Line sizes
x
Control valve locations
x
Grease line connection
x
Gas meter locations
x
Complete gas piping layout as required for cooking equipment
Public and Employee Toilets
x
All Tenant spaces exceeding 900SF in area must provide employee toilets. Tenant spaces less
than 900 SF are not required to provide employee toilets if they are within 200 ft and one floor
above or below public facilities.
x
All retail Tenant spaces greater than 7,500 SF must provide toilets for both employees and
customers.
x
All food service Tenant spaces greater than 3,000 SF must provide toilets for both employees
and customers.
x
Provide accessible toilet facilities in accordance with Title III of the Americans with Disabilities Act
(ADA) and local codes.
Water Tower Place
63
PLUMBING DESIGN CRITERIA
Work by Tenant
Tenant shall provide a complete plumbing system from Landlord’s distribution point (supply stub-outs),
including but not limited to, all necessary labor, connections to supply stubs, piping, clean-outs, fixtures,
etc. necessary for the satisfactory operation of a plumbing system.
x
Connection to Landlord’s point of service and extend service according to Tenant’s requirements
and all applicable local codes.
x
Large water consumers such as food preparation establishments, barber shops, beauty salons,
etc. shall furnish and install a water meter conforming to American Water Works Association
specifications for domestic service. If a meter is required, it shall be installed within the premises
in an area easily accessible by Landlord’s personnel. The Landlord shall determine when a meter
is required.
x
All toilets must be flush tank operated, except restaurants and theaters.
x
Provide a minimum of one (1) 3” minimum floor drain in each toilet room, kitchen and/or wet area.
Provide drains with collars to accept waterproof protective membrane throughout all areas where
water is present.
x
All floor drains, floor sinks and cleanouts shall be compatible with the water proofing system and
membrane. All penetrations shall be sleeved, firestopped and sealed in accordance with the
Landlord’s standard project details. Tenants must perform flood test as required by Landlord.
x
Dimensioned drawing for all pipe penetrations through concrete slabs must be prepared and
submitted to the Operations Manager for review and approval. Structural reinforcing is to be
located by sonar or other approved means and is to be included on the plan
x
Hot water heaters to be electric type. Provide a code-required expansion tank. Water heaters
shall have a maximum 12-gallon tank unless required for Tenant’s operation. Provide relief valve
line from water heater to drain pan which routed to floor drain. Water heaters cannot be located in
plenum ceilings
x
Sediment and hair interceptors must be provided as required by Landlord at all sinks, drains, and
specialty sanitary units.
x
Tenants shall not introduce chemicals into the sanitary waste lines; if required, a Landlordapproved chemical dilution system shall be installed.
x
Dielectric isolation is required at all dissimilar piping connections and supports.
x
Insulation shall be provided at all domestic water piping. The horizontal runouts in the piping
chases need not be insulated, except where fixtures are located adjacent to exterior walls.
x
Any piping outside Tenant’s premises shall be installed as close to the underside of the slab as
possible.
x
Provide drain down pipe for fire protection system from fire protection cap to nearest floor drain.
x
Pipe Materials: Sanitary, Vent, Kitchen Waste:
3” and Larger: Service weight, hub & spigot cast iron pipe.
2/12” and Smaller: Type M copper and copper drainage fittings.
x
Work and materials above finish ceilings must conform to Chicago return air plenum
requirements.
Water Tower Place
64
PLUMBING DESIGN CRITERIA
Plumbing Venting
x
Tenant must connect to Landlord’s vent system.
Additional Food Related Tenant Requirements
x
The Tenant must comply with the requirements of the Chicago Health Department, including
providing hand sinks, three compartment sinks and mop sinks.
x
Individual grease traps are required for all food usage and grease generating Tenants. Grease
traps must be located within the respective Tenant space and sized in accordance with the
usage; provide calculations on final plumbing plans.
x
All restaurants must have water meters. Retail food service tenants may be required to provide
water meters if required by the Landlord.
x
Restaurants with high-volume dishwashing facilities may be required to provide a moisture
removal system if required by the Landlord.
Natural Gas Service
x
Natural gas is available from the local utility company at designated locations and may be used
for cooking purposes. Tenant shall arrange to obtain service from local utility company. Piping,
meter and all associated work for extension of service to the leased premises shall be provided
by Tenant, at Tenant’s expense and shall be subject to Landlord’s approval and code
requirements.
x
Each Tenant with natural gas service will supply solenoid valves in the gas supply line that will be
interconnected to the Landlord’s fire alarm system and Tenant’s kitchen exhaust hood
suppression equipment to ensure the emergency shut down of gas fired equipment. Interconnect
any pull stations with Landlord’s fire alarm system, where applicable.
x
All natural gas distribution systems shall conform to proper engineering practices and the
requirements of local governing authorities, the local gas company, Landlord and its insurance
underwriter.
x
Concealed gas piping is not permitted. All gas piping in Tenant spaces must be exposed. Gas
piping to be welded construction except connections to equipment.
x
Gas piping down into space for Food Tenants is to be run through plenum in a sleeve with the
sleeve vented to outside air.
x
Gas casing shall be scheduled 40, black steel, welded with welded fittings and meet requirements
of ASTM A53. Casing shall be one pipe size larger than O.D. of gas piping passing through it.
x
Exposed gas line to be painted.
x
If gas service is required for restaurant Tenant, Tenant shall contact Landlord’s Tenant
Coordinator to review service connection location and pipe routing requirements.
Domestic Water
x
Landlord shall provide a 3/4” domestic water line available for connection by the Tenant.
x
Hot and cold domestic water piping shall be type L copper with soldered fittings using 95/5 tin
antimony solder. Provide dielectric fittings for connections between dissimilar piping.
x
Hot and cold domestic water piping shall be insulated.
Water Tower Place
65
PLUMBING DESIGN CRITERIA
Sanitary Sewer
x
Plumbing risers and/or stub-ins are existing within or near the leased premises. Tenant will be
responsible for, extending the line as required by their layout.
x
All sanitary plumbing must be piped to the nearest vertical riser; generally, connections cannot be
made to existing horizontal lines connected to other Tenants. Existing conditions are to be
reviewed by the Building Engineer.
x
Tenant shall install accessible cleanouts, as required by applicable code and Landlord’s
requirements and they shall terminate flush with the finished floor.
x
The waste and vent connection when made to a building waste or vent line outside of the Tenant’s
premises shall include a full size plugged “wye” installed at the connection to serve future
connections.
x
Unused, below-floor sanitary piping under the Tenant space is to be removed by the Tenant to the
vertical riser.
Water Tower Place
66
PLUMBING DESIGN CRITERIA
Floor Penetration Details
Water Tower Place
67
PLUMBING DESIGN CRITERIA
Plumbing Riser Diagram
Water Tower Place
68
PLUMBING DESIGN CRITERIA
Dishwasher Moisture Eliminator
Water Tower Place
70
FIRE PROTECTION DESIGN CRITERIA
Tenant’s Sprinkler System
The following section includes minimum design information required to expedite plan approval by
Landlord. It is not intended to be a complete listing of all requirements, but should serve as a minimum
checklist to be used by Tenant’s design consultants to complete the construction documents.
We urge you to read this manual in its entirety in order to fully understand the requirements
needed to generate an approvable set of construction documents.
Sprinkler System Design Criteria
•
Codes and governing authorities require fire sprinkler protection for the premises. The entire mall
is protected by a code approved sprinkler system. Tenant shall, at Tenant’s expense, contract
with a licensed and bonded sprinkler contractor with minimum 5 years experience to modify the
existing sprinkler system as necessary to accommodate Tenant’s space and any adjacent areas
affected by Tenant’s modifications to Tenant’s space. Required changes may include, but not be
limited to cross mains, branch lines, control valves, arm-overs, drops, water flow indicators,
drains, test valves, sprinklers, drain piping, or other fire protection equipment (e.g., fire alarm
system components, fire extinguisher, hose cabinets, etc.) as may be required for the premises,
all of which shall comply with the requirements of Landlord’s fire casualty insurer, all applicable
codes, standards and ordinances, all referenced National Fire Protection Association standards
(e.g., NFPA 13), The Chicago Building Code, the Owner’s risk consultant, and Landlord’s Design
Criteria, whichever is more stringent.
•
Tenant’s system shall be hydrostatically tested in accordance with NFPA 13 in the presence of
the Building Engineer, Operations Manager and required local jurisdictional authorities.
•
Landlord’s fire risk consultant shall from time to time during the term of the lease have the right to
inspect the fire protection systems. Said system shall at all times comply with the requirements of
said underwriter and shall meet the conditions of its approval. Any alterations, improvements,
repairs, or maintenance required by such consultant shall be Tenant’s sole responsibility and
shall be performed promptly at Tenant’s expense upon notice of such conditions.
•
Before any construction begins, temporary fire extinguishers shall be provided and installed in
type, number, and locations as required by authorities having jurisdiction.
•
Tenant shall be responsible for supervision and integration of any new sprinkler devices such as
water flow switches, tamper switches, etc. with base building fire alarm system and building
automation system for supervision, notification and fan shut down.
•
If Tenant’s occupancy is to be such as to require upgrades to the existing automatic sprinkler
system, sprinkler main or other component, Tenant shall be responsible for all costs of providing
the upgrading of the system to meet local code & insurance requirements.
•
Any damage to the Landlord’s sprinkler system caused by Tenant’s work will be repaired by
Landlord at Tenant’s expense.
•
The sprinkler supply piping for Tenant sprinkler system must be isolated from supplies for other
tenants and Landlord areas. The Tenant system will be inoperative during construction and must
not affect surrounding active systems.
•
Tenant shall provide a sprinkler water curtain parallel to the storefront with heads spaced at 6’-0”
at the Tenant side of the storefront(s). Provide additional sprinklers outside the storefront if the
existing, common area water curtain heads are more than 6’-0 from the Tenant storefront.
Water Tower Place
71
FIRE PROTECTION DESIGN CRITERIA
•
Tenant shall provide a sprinkler water curtain at all vertical openings such as atria, open
stairways, etc. regardless of the opening size or dimensions.
•
All ceilings having suspended elements, floating ceiling, ceiling openings, etc. shall have
sprinklers installed both at the finished ceiling and above the finished ceiling. Sprinklers shall be
installed in all display windows and accessible concealed spaces.
•
Sprinklers shall be omitted from all ComEd electric vaults, electrical switchgear rooms,
emergency generator rooms and electrical rooms containing equipment 600 volts or higher.
•
Tenant’s sprinkler system design shall be based on the City of Chicago Building Code. Class F
mercantile units, sprinklers shall provide a minimum of .20 GPM over the most remote 2,000 sq.
ft. Storage areas with ceiling heights greater than 14 feet shall provide .25 gpm over the most
remote 2,500 sq. ft. The maximum sprinkler spacing shall not exceed 130 sq. ft. per sprinkler.
Tenant’s sprinkler system shall be hydraulically calculated with flow pressure requirements shown
at Landlord’s connection point (see supplemental fire protection information).
•
The sprinkler hydraulic calculations shall include half the building standpipe demand. The total
standpipe and sprinkler demand does not need to exceed 1500 gpm.
•
Each Tenant’s Fire Protection Contractor shall size the sprinkler piping and then carry the friction
loss back down to the pump room and show the match between system demand and available
water supply at the pump room based on the pump curve plus 13 psi city suction. Allow 2 psi for
friction loss in the loop at 1000 gpm.
•
The Contractor is cautioned to adjust losses to actual take-off points on each floor, especially
where take-offs occur before offsets. The latter are counted in riser elbow for the floor on which
they occur.
•
The following Design Criteria Sheets indicate calculations, supply curves, riser locations and
profiles, etc. Consult the space layout drawings as issued for riser number to which the
Contractor is to connect as well as location of other piping take-offs between the Tenant’s cap
and the riser lateral at that floor.
Sprinkler Head Requirements
•
All sprinkler heads in public areas shall be concealed, standard coverage, standard response
type.
•
Sprinkler Identification Numbers (SIN) should be provided for the type(s) of sprinklers to be used
in the installation.
Material Requirements
•
All materials and equipment used shall be UL listed.
•
Piping: Black Steel, Schedule 40 on piping 2” and smaller. Schedule 10 pipe is permitted on
piping 2 ½” and larger and may only be joined with roll grooved fittings.
•
Fittings: steel screwed, or grooved, rated for system pressure.
•
All pipe, fittings and hangers shall be galvanized where moisture and corrosive conditions exist
and on preaction and dry sprinkler systems.
•
Installation: The complete installation is to be in strict accordance with Landlord’s design manual
requirements.
Water Tower Place
72
FIRE PROTECTION DESIGN CRITERIA
Drains and Valves
•
All inspector test drains must be piped to an open site drain. No inspector test drains will be
allowed to empty to slop sinks or mop receptors.
•
Auxiliary drain valves shall be provided at all low points in sprinkler piping. Identify low point with
a ceiling marker and provide access to all valve drains.
Special Fire Protection Systems
•
Cooking Hood Exhaust Fire Suppression: Fire protection above cooking equipment shall consist
of an automatic fire extinguishing system in accordance with NFPA and Chicago Building Code
requirements. Hood suppression system trouble and alarm points shall be tied to the Building Fire
Alarm System for supervision.
Special Storage Conditions
•
Tenant’s storage conditions may affect the design and installation of Tenant’s sprinkler system.
For areas where height of storage exceeds 12 feet, hydraulically calculated sprinklers shall be
provided in accordance with Chicago Building Code and Factory Mutual requirements. Details for
storage arrangements, types of racks, aisle widths, etc. shall be submitted to Landlord, Chicago
Fire Prevention Bureau and The Landlord’s risk consultant for review.
•
For double-decked storage areas (whether solid, slatted or open grated), automatic sprinklers
shall be provided for each level. Fire protection above rolling shelving units must also be provided
in accordance with all applicable requirements.
Dry Sprinkler Systems
Dry sprinkler systems shall be installed in areas subject to temperatures lower than 50° F.
Fire Protection Drawing Requirements
Tenant submittal drawings shall include complete plans, calculations and specifications for all sprinkler
work which shall consist of, but not be limited to the following:
•
General notes included on Tenant’s working drawings and information on the specifications which
define the sprinkler system design, material and installation requirements for Tenant’s space.
•
Detailed information and drawings as required for special conditions including in-rack sprinkler
coverage if required.
•
Drawings shall include a sprinkler summary indicating material specifications, sprinkler type(s),
pressure and temperature ratings, and hydraulic calculations.
•
Welded, fabricated fittings used for joining sprinkler piping should be FM approved.
•
Should tenant configurations result in areas which cannot be reached by 30 feet of hose stream
being projected from a 75-foot long hose from existing Landlord fire hose connections, the Tenant
will be required to provide additional hose connections to meet local code requirements at Tenant
cost. Note that the Water Tower Place Fire Protection Program includes 1 1/2” fire hose
connections.
Water Tower Place
73
FIRE PROTECTION DESIGN CRITERIA
Sprinkler Shop Drawing Submittal Requirements
All Tenants shall have received approval of the Tenant sprinkler shop drawings and hydraulic calculations
from the Landlord’s risk consultant prior to the installation of the Tenant’s sprinkler system. Listed below is
a list of general submittal requirements. This list is not intended to be a complete listing; it is the Tenant’s
responsibility to contact the Landlord’s risk consultant with questions and concerns relating to their plan
review.
•
Submit three (3) sets of sprinkler protection plans and supporting hydro-calculations.
•
Shop drawing floor plans shall be drawn at 1/4”=1”-0” scale or larger, and shall indicate:
All new connections; locations of sprinklers, inspectors test valve, flushing drains, fire
extinguisher locations and fire hose valve locations.
Schedule and key of all sprinkler heads; sprinkler summary indicating material specifications,
pressure and temperature ratings.
Type and size of all piping and fittings, hanger locations and details, proper hydraulic nodes and
remote area outlined.
Locations of any structural components, mechanical equipment, service lines or fixtures that may
shield water spray.
•
Include reference drawings of adjacent systems or risers feeding the system being submitted.
•
Hydraulic calculations using equivalent lengths for fittings and approved K factors for sprinklers
and including any balancing of the overhead for rack systems.
•
Specifications/Cut sheets for materials being used such as sprinkler heads, sprinkler pipe, valves
and fittings and peripheral equipment (including tamper alarms, waterflow alarms, etc.).
•
Occupancy details – in order to review submitted plans to ensure adequate protection, accurate
occupancy details must be provided. These include, but are not limited to: materials being stored,
storage height, storage arrangement, processes present, etc.
•
For dry systems the valve house heating arrangements, piping slope and air supply details should
be included.
•
The Contractor’s Materials and Test Certificate Form No. 85 should be completed by the installing
contractor for all instructions and submitted to Global Risk Consultants for review and record.
Sprinkler Installation Requirements
•
The sprinkler system is to be de-activated during demolition and construction. The Contractor is
to schedule the installation of a blind flange to isolate the sprinkler system of the area under
construction.
The Contractor is to ensure that only the Tenant area under construction has a decommissioned
sprinkler system. The Contractor is responsible to perform any sprinkler modification work to
achieve this requirement.
Draining and capping of the sprinkler system is to be arranged with and performed by the Building
Engineer. Contractor shall give a minimum of forty eight hours notice and receive prior approval
from Johnson Controls prior to shutting off any sprinkler piping. The cost of this work shall be
charged to the Tenant’s Contractor.
Water Tower Place
74
FIRE PROTECTION DESIGN CRITERIA
•
All sprinkler heads are to be protected during construction. Protective caps & covers are to be
maintained on all sprinklers during the duration of the Tenant construction. Protective caps and
covers are only to be removed after all construction has been completed. Provide temporary
plugs and caps on all piping/fittings to keep out construction debris.
•
Automatic sprinklers must be handled and installed in accordance with the manufacturer’s
instructions to ensure reliable operation and to prevent premature operation. This typically
includes use of a designated sprinkler wrench specified for installation of the specific automatic
sprinkler, proper torquing or seating of the sprinkler into the fitting and inspection of the actuating
mechanism. Automatic sprinklers that are damaged or have their fusible element assembly
modified due to rough handling should be replaced with new, undamaged sprinklers of the same
type/design/temperature rating. Field adjustments of damaged sprinkler heads are not
acceptable.
•
The premises are to be kept free of combustible materials. Trash generated by construction
activity must be removed from the premises daily. Combustible enclosures for contractor’s tools
and storage are not permitted.
•
All fire protection materials installed shall be thoroughly clean upon completion of installation.
Heads, pipes, valves and fittings shall be completely clean of grease, metal cuttings and dirt, etc.
•
If any cutting or welding is to be done on any of the sprinkler piping in the field, all cut coupons
from modified pipes should be retained for examination by the Landlord’s risk consultant.
Fire Protection System Acceptance
•
Tenant sprinkler system shall not be put in service until the entire system within the demised
premises is pressure tested by a designated fire sprinkler contractor, witnessed by the Landlord’s
designated on-site representative and accepted by both the Landlord and an officer of the
Chicago Fire Department.
•
The Tenant shall not be allowed to bring any stock, furniture, fixtures, equipment, or other
combustible material to the premises until the entire sprinkler system and fire alarm system has
been approved and put into operation.
•
Upon completion of the work, signed copies of the appropriate contractor’s material and test
certificates found in NFPA 13, contractor’s “as-built” shop drawings and installation warranty,
shall be submitted to the Landlord for review and approval prior to occupancy of the premises.
Fire Extinguishers
•
Fire extinguisher for hand use shall be provided, located and installed by Tenant in accordance
with the NFPA-10 and Chicago Building Code Requirements.
•
Fire extinguishers located in finished areas shall be installed in recessed metal cabinets with solid
metal doors.
•
All fire extinguishers shall have signage visible from at least 50 feet away.
Water Tower Place
75
SPRINKLER DESIGN CRITERIA DETAILS
CALCULATIONS
Building Fire Riser Diagram
Water Tower Place
76
SPRINKLER DESIGN CRITERIA DETAILS
CALCULATIONS
Equivalent Lengths
Pump Room @ F-1 to Loop (8”)
30’ + G.V. (4) + ST (35) + L (18) =
87
Pump Room @ G-18 to Loop (8”)
17’ + G.V. (4) + ST (35) + L (18) =
74
Loop Sections
F-1 Pump to Riser 11
7-0’ + G.V. (4) + ST (35) =
46
Riser 11 to Riser 7
40 + 46 + 2T (0) =
86
Riser 7 to Riser 4 & 6
48 + 8 + 23 + 28 + 29 + 41 + G.V. (4) + 5T (0) + 2-45L(18) =
199
Riser 4 & 6 to Riser 3
23 + 62 + 8 + 28 + G.V. (4) + 4T (0) =
125
Riser 3 to G-18 Pump
26 + 36 + 1 + 4 + G.V. (4) + 2T (0) + L (18) + ST (35) =
124
G-18 Pump to Riser 2
27 + 87 + 33 + 1 + 36 + 30 + G.V. (4) + L (18) + 5T (0) =
236
Riser 2 to Riser 5
16 + 7 + 62 + 24 + G.V. (4) + 4T (0) =
113
Riser 5 to Riser 8 & 9
63 + 35 + 20 + 4 + 35 + 22 + 86 + 47 (0) + G.V. (4) + 2-45L (18) +
+ 2L (36) =
323
Riser 8 & 9 to Riser 10
8 + 31 + 15 + 3T (0) =
54
Riser 10 to F-1 Pump
1 + 81 + T (0) + L (18) + G.V. (4) =
104
Loop Friction Loss Calculations
Riser 1
F-1 Least Supply
L1 = 580
L2 = 830
Q
@ Qt = 1000
Q1 = 548
Q2 = 1 + § L2 · + .54
Q2 = 452
¨ ¸
© L1 ¹
Pf = 1.7 psi
Riser 2
L1 = 816
Q1 = 457
F-1 Least Supply
L2 = 594
Q2 = 543
Riser 3
L1 = 456
Q1 = 598
F-1 Least Supply
L2 = 954
Q2 = 402
Pf = 1.6 psi
Riser 4/6
L1 = 331
Q1 = 654
F-1 Least Supply
L2 = 1079
Q2 = 346
Pf = 1.3 psi
Pf = 1.7 psi
F-1 Least Supply
Riser 11
L2 = 876
L1 = 534
Pf = 1.7 psi
Q1 = 566
Q2 = 434
Clearly a loop loss of 2 psi @ 1000 gpm to any riser from any single pump is acceptable.
Water Tower Place
77
SPRINKLER DESIGN CRITERIA DETAILS
Riser 1
-3 G.V + L
6 G – 2-90L
CALCULATIONS
Straight
6” EQ. Length Values
45-7
90L – 14
T – 20
G.V. – 3
All risers are 6”
Riser 2
-3 G.V. = 22’ + L = 39
-2 17’ + 3(L)
-1 42’ + 4(L)
G (2L)
M 50 + 3L = ST
2 (2L)
8 (2L)
Riser 3
-3 23 + G.V. + L
-2
M 29 + 3L + ST
Riser 4
Riser 4B
-3 2 + L = 19
-1
M 20 = 3L
2
4
5
6
7 3 + 3L
8 6 + 2L + t
32 + T + 2L = 90
26 + 3L
7 + 2L
6 + 2L
6 + 2L
5 + 2L
Riser 5A
Riser 5B
-3 2’ + G.V. + L = 2T = (79)
-1 60’ + 4L
G 40 + 4L + ST
2 10 + 2L + ST
7 15 + 3L
8
80 + 4L
22 + 2L + T
Water Tower Place
78
SPRINKLER DESIGN CRITERIA DETAILS
CALCULATIONS
Riser 6
-3 81 + G.V. + L
G 28 + 2L
2 15 + 2L
3 19 + 31
Riser 7
Riser 7A
-3 22 + G.V. + L
DL 10 + 2L
G 2L
2 22 + 3L
95 + 4L + T
Riser 8
-3 4’ + G.V. + 2L
G 2’ + 2L
M 2“ = 2L
2 115 + 3L + ST
Riser 8A
50’ + 2L + ST
Riser 9
50’ + 2L + G.V.
BR 11 + 3L
2 117 + 3L + ST
7 3’ + 3L
Riser 10
-3 60 + 2L + G.V.
M 12 + 3L
Riser 11
-3 36 + 4L + G.V.
Water Tower Place
79
SPRINKLER DESIGN CRITERIA DETAILS
TENANT SPRINKLER
WATER SUPPLY DATA
Tenant Sprinkler Water Supply Data
Pump Room Floor: Elev. (31’2”)
Allow 2 psi Loop Loss @ 100% gpm
Add 20 psi for City Suction (F1)
13 psi (FPB)
Floor
1W
Ceiling Elev.
9’6”
17.6 psi
1E
9’6”
17.6 psi
M-W
23’6”
23.6 psi
M-E
23’6”
23.6 psi
2W
40’
30.8 psi
2E
40’
30.8 psi
3W
57’
51.5 psi
3E
57’
51.5 psi
4W
74’
45.4 psi
Number
5
4A
4B
7
10
8
5
4A
4B
7
11
10
8
3
4A
4B
5A
5B
6
7
11
8
8A
9/10
3
4A
4B
5A
5B
6
7
7A
8
8A
9
3
4a
4b
5a
5b
6
Riser
Location
C-10/B-10
G-11
G-10
E-5
C-2
C-4
B-10
G-11
G-10
E-5
E-1
C-2
D-4
E-15
E-11
G-10
B-10
A-11
D-12
E-5
E-1
E-4
C-5
A-7/C-2
E-15
E-11
G-10
B-10
A-11
D-12
E-6
F-4
E-7
C-5
A-7
e-15
e-11
g-10
b-10
a-11
e-12
Water Tower Place
Riser
Eq. Length
235
59
149
117
131
75
345
121
231
145
149
145
119
212
138
283
400
481
225
162
166
166
244
219/216
229
155
300
417
498
285
243
343
370
261
425
246
172
351
434
515
363
Friction Loss
At 1000 gpm
8.2
2.1
5.2
4.1
4.6
2.6
12.1
4.2
8.1
5.1
5.2
5.1
4.2
7.4
4.8
9.9
14.0
16.9
7.9
5.7
5.8
5.8
8.3
7.7/7.6
8.0
5.4
10.5
14.6
17.5
10.0
8.5
12.0
13.0
9.2
14.9
8.6
6.0
12.3
15.2
18.1
12.7
80
SPRINKLER DESIGN CRITERIA DETAILS
Floor
4E
Ceiling Elev.
74’
45.4 psi
5W
91’
52.9 psi
5E
91’
52.9 psi
6W
108’
60.2 psi
6E
106’
60.2 psi
7W
125’
67.6 psi
7E
125’
67.6 psi
8W
139’
73.7 psi
8E
139’
73.7 psi
Number
7
7A
8
8A
9
3
4A
4B
5A
5B
6
7
7A
8
8A
9
3
4A
4B
5A
5B
6
7
7A
8
8A
9
3
4A
4B
5A
5B
6
7
7A
8
8A
9
3
4A
5A
5B
6
1
2
7
7A
8
Riser
Location
E-6
F-4
E-7
C-5
A-7
H-15
H-11
G-10
B-10
A-11
E-12
H-6
P-4
E-7
C-5
A-7
H-15
H-11
G-10
B-10
A-11
E-12
H-6
P-4
E-7
C-5
A-7
H-15
H-11
G-10
B-10
A-11
E-12
H-6
P-4
E-7
C-5
A-7
E-15
E-11
B-9
A-11
E-12
F-16
A-15
H-6
F-4
E-7
Water Tower Place
TENANT SPRINKLER
WATER SUPPLY DATA
Riser
Eq. Length
260
360
387
278
442
263
189
402
451
532
380
277
377
404
295
459
280
206
452
468
549
397
294
394
421
312
476
297
268
469
542
566
414
311
41
438
329
493
311
346
556
660
428
201
401-170-572
325
425
452
Friction Loss
At 1000 gpm
9.1
12.6
13.6
9.8
15.5
9.2
6.6
14.1
15.8
18.7
13.3
9.7
13.2
14.2
10.4
16.1
9.8
7.2
15.7
16.4
19.3
13.9
10.3
13.8
14.8
1.0
16.7
10.4
9.5
16.5
19.0
19.9
14.5
10.9
14.4
1`5.4
11.5
17.3
10.9
12.1
19.5
23.2
15.0
7.1
20.0
11.4
14.9
15.9
81
SPRINKLER DESIGN CRITERIA DETAILS
Floor
9W
Ceiling Elev.
152’
79.3 psi
152’
9E
Number
8A
9
10
3
4A
5A
5B
6
1
2
7
7A
8
8A
9
10
Riser
Location
C-5
A-7
C-2
E-15
E-11
B-9
A-11
E-12
F-16
A-15
H-6
F-4
E-7
C-5
A-7
C-2
Water Tower Place
TENANT SPRINKLER
WATER SUPPLY DATA
Riser
Eq. Length
343
507
315
324
359
569
673
441
214
585
338
428
455
356
520
328
Friction Loss
At 1000 gpm
12.0
17.8
11.1
11.4
12.6
20.0
23.6
15.5
7.5
20.5
11.9
15.4
16.3
12.5
18.3
11.5
82
SPRINKLER DESIGN CRITERIA DETAILS
TENANT SPRINKLER
WATER SUPPLY DATA
Efficiency/GPM Supply Curve
Water Tower Place
83
SPRINKLER DESIGN CRITERIA DETAILS
TENANT SPRINKLER
WATER SUPPLY DATA
Pressure/GPM Supply Curve
Water Tower Place
84
SPRINKLER DESIGN CRITERIA DETAILS
TENANT SPRINKLER
WATER SUPPLY DATA
Tenant Sprinkler Riser Diagram 1
Water Tower Place
85
SPRINKLER DESIGN CRITERIA DETAILS
TENANT SPRINKLER
WATER SUPPLY DATA
Tenant Sprinkler Riser Diagram 2
Water Tower Place
86
SPRINKLER DESIGN CRITERIA DETAILS
TENANT SPRINKLER
WATER SUPPLY DATA
Tenant Sprinkler Riser Diagram 3
Water Tower Place
87
SPRINKLER DESIGN CRITERIA DETAILS
TENANT SPRINKLER
WATER SUPPLY DATA
SPRINKLER RISER NUMBER FOR TENANT SPACES
This list indicates to what sprinkler riser the Tenant sprinkler connection is to be made. This information is
necessary for the submission of the hydraulic sprinkler calculations and shop drawings required of each
Tenant as set forth in the Exhibit B of the lease. See the Design Criteria K thru X for the necessary
sprinkler information as well as the space layout drawings which will indicate the cap size and location,
take-offs and pipe sizes between the Tenant’s cap and the riser, as well as the distance from the cap to
the riser. Please note however that the riser number (if any) indicated on the space layout drawing is to
be used if different from that given in this listing.
Tenant Space Number/Riser Number:
Ground Floor:
Third Floor:
G1/4B
3-1/3
G2/4B
3-2/3
G3/5A
3-3/7
G4/4B
3-4/7
G5/7
3-5/7
G6/10
3-6/7
Mezzanine Floor:
3-7/8A
M1/8
3-8/8A
M2/5A
3-9/9
M3/5A
3-10/7
M4/5A
3-11/5B
M5/10
3-12/5B
M6/7
3-13/5B
M7/5A M8/5A
3-14/3
Second Floor:
3-15/9
3-16/5B
2-2/3
3-17/3
2-4/3
3-18/3
2-5/3
3-19/5B
2-6/8A & 10
3-20/7
2-7/9
Fourth Floor:
2-8/9
4-1/4A
2-9/9
4-2/4A
2-10/3
4-4/4A
2-11/9
4-5/7
2-12/9
4-6/7
Water Tower Place
4-7/7
4-8/8
4-9/8A
4-10/8A
4-11/9
4-12/9
4-13/9
4-15/9
4-16/5B
4-17/5B
4-18/5B
4-20/5B
4-21/5B
4-22/9
Fifth Floor:
5-1/4A
5-2/4A
5-3/4A
5-4/4A
5-5/7
5-6/7
5-8/7
5-9/7
5-10/8A
5-11/9
5-12/9
5-13/9
5-14/9
5-15/9
5-16/5B
5-17/5B
5-18/5B
5-19/5B
5-20/5B
5-22/5B
5-23/9 5-24/4
Sixth Floor:
6-1/4A
6-2/4A
6-3/4A
6-4/7
6-5/7
6-6/7
6-7/7
6-8/8A
6-11/9
6-13/9
6-14/5B
88
FIRE ALARM SYSTEMS CRITERIA
Building Fire Alarm System
•
The Building alarm system consists of smoke detectors in building ductwork, flow alarms, tamper
switches and an emergency voice communication system.
Fire Alarm System
•
Tenants are required to provide system appliances within their premises and connect them to the
Building Fire Detection/Emergency Voice Communication System within their premises at Tenant
expense.
•
Required Tenant Fire Detection/Emergency Voice Communication System design must comply with:
NFPA 72 and Life Safety Code 101; Americans with Disabilities Act; the Chicago Building Code
section 9 (15-16); and the Chicago Electrical Code.
•
The Landlord shall provide a junction box with internally mounted terminal strips outside the Tenant’s
premises for connection to the Building Fire Detection/Emergency Voice Communication System.
These will generally be in service corridors near the Tenant premises.
•
The final connection of Tenant appliance wiring to the Building Fire Detection/Emergency Voice
Communication System, including programming and testing, will be performed by the Building Alarm
System Contractor at Tenant expense.
•
All Tenant sound systems must be interlocked with the Building Emergency Voice Communication
System so that the emergency system can override the Tenant system.
Fire Alarm Specifications
Tenant installation, appliances and wiring must match Building Alarm System specifications. Contact
Mark Eggerding of Johnson Controls at (708) 236-9701, to purchase devices and to request Building
alarm connection.
•
Device Manufacturer: GE Security/ EST.
•
Ceiling speaker/ strobes: GCFR-S7VM.
•
Wall mount speaker/ strobes: G4RF-S7VM.
•
Ceiling mount strobes: GCFR-VM.
•
Wall mount strobes: G4RF-VM.
•
Remote strobe power supplies: BPS6A; isolator modules will be part SIGA-IM.
•
Signaling line circuit wiring: 16 AWG Twisted pair cable FPLR Page Wire and Cable number 4731A
or equivalent.
•
Speaker circuit: 16 AWG Twisted pair cable FPLR Page Wire and Cable number 4731A or
equivalent.
•
Strobe circuit: 12 AWG Twisted pair cable FPLR Page Wire and Cable number 4720A or equivalent.
•
Provide 2 cables for Speaker circuit, 1 out to Tenant speakers and one return to Landlord terminal
box.
•
Conduit and junction boxes: Both to be red and boxes stenciled ‘FA’.
Water Tower Place
89
CONSTRUCTION REQUIREMENTS
Contractors Guidelines
The following is a brief description of required items/procedures for Tenant construction.
Pre-Construction Meeting
Tenant and Tenant’s contractor shall not commence any work or deliver any materials to the building or
site without conducting a pre-construction meeting with the Landlord Operations Manager and supplying
all required pre-construction documents. Contact the Operations Manager to schedule the meeting.
Documents to be submitted at the meeting shall include but not be limited to:
x
Copy of the City Building Permit.
x
Certificate of Insurance.
x
Copy of Contractor’s City of Chicago Business License.
x
Tenant Contractor information form.
x
Contact list, including all subcontractors and a list of 24 hour emergency telephone numbers.
x
Construction schedule.
x
Contractor authorization for access form.
x
Proposed barricade plan & proposed barricade graphics.
x
Certified check for construction fee and deposit.
Documents to be brought to the meeting for review and discussion shall include the following:
x
Record permit drawing originals.
x
Landlord-approved design drawings.
Construction Fee and Deposit
The Tenant shall cause its General Contractor to deposit with the Operations Manager without liability for
interest, the sum of $5,000. Note that $2,500 will be applied to the fee for Landlord construction
administration. A $2,500 refundable deposit shall be applied to any costs incurred by General Growth in
fulfilling Tenant Contractor responsibilities which the Contractor fails to complete. This sum shall be
applied toward any costs incurred by Landlord or Landlord’s contractor to complete any part of Tenants’
work including but not limited to punch list items and damage caused to any portion of the mall which
Tenant or Tenant’s contractor fails to complete within the time period required by the lease. A certified
check made payable to Water Tower LLC; check must be submitted to the Operations Manager prior to
work start. All remaining funds will be fully refundable.
Quality Standards
All work by Tenant’s contractor, including repair work, shall be performed in a first-class, workmanlike
manner and shall be in good usable condition at completion. The Tenant shall require any person
performing work to guarantee that the work is free from any and all defects in workmanship and materials
for one year from the date of completion. The Tenant shall also require any such person to be
responsible for the replacement or repair, without additional charge, of work done or furnished by or
through such person, which shall become defective within one year after substantial completion of work.
Water Tower Place
90
CONSTRUCTION REQUIREMENTS
The correction of work shall include, without any additional charge, all expenses and damages in
connection with the removal, replacement, or repair of any part of work which may be damaged or
disturbed. All warranties or guarantees for material or workmanship on or regarding Tenant’s work shall
be contained in the contract or subcontract. The contract shall be written so that all warranties and
guarantees shall insure to the benefit of both Landlord and Tenant, as their respective interests appear,
and so that the correction can be directly enforced by either party.
Coordination
The Tenant’s work shall be coordinated with the Landlord and with other Tenants so that the Tenant’s
work will not interfere with the operation of the building. Provide not less than 96 hours' notice to the
Operations Manager for activities that will/may affect Landlord or Building Tenant’s operations.
Construction Barricade
The Tenant’s contractor shall erect a construction barricade to serve Tenant’s area.
x
The configuration shall be at the direction of the Operations Manager.
x
The barricade must cover the entire storefront width.
x
Barricade graphics are required; designs must be submitted to the Operations Manager for
review and approval prior to the erection of the barricade.
x
The barricade shall not be removed without Landlord approval.
Site Access
The Operations Manager will designate approved personnel entry point(s), loading docks and service
corridors, acceptable delivery/usage times, dumpster access, etc.
x
All construction access is through building service corridors if available. All materials and
workman access must be delivered to and brought into the building through designated loading
dock(s) and service corridors.
x
No materials, assemblies, deliveries or workman access is permitted through Tenant’s storefront
or in the common areas during mall operating hours.
x
Construction personnel must check-in at the building security office on Mies van der Rohe Way
and receive an adhesive, daily building pass. The pass must be worn throughout the work day.
Loading Dock
Deliveries are to be scheduled with the Building Dock Manager, (312) 440-3160. 45’-0 is the maximum
length vehicle that can be accommodated.
Freight Elevators
Freight elevators are available for use by the Contractor.
x
Elevators are to be kept free of trash, debris etc. at all times.
x
Contractors are to load and unload elevators in the most expedient way possible to minimize the
duration of use.
x
The Landlord may elect to provide an elevator operator at Tenant expense if the Contractor
utilizes the common freight elevator at the northeast corner of the building during construction.
Water Tower Place
91
CONSTRUCTION REQUIREMENTS
Construction Trash Removal
x
The Tenant and Tenant’s contractor(s) are responsible for all trash removal during construction,
fixturing and stocking. All trash removal shall be performed during the days and time designated
by the Landlord so as not to interfere with the operation of building tenants.
x
Trash hauling from the building loading dock shall be provided by the Landlord at the expense of
the Tenant. Contact the Dock Manager to order waste dumpsters.
x
Trash accumulation shall not be permitted overnight in the leased premises common areas or
service corridors.
Common Area Cleaning and Protection
x
Common areas are to be kept clean at all times, especially at public areas. Cleaning at public
areas is to be performed by a cleaning contractor. Daily cleaning work at public areas is to be
completed by 8:00 AM.
x
If Landlord removes Tenant's or Tenant's contractor's trash, the charge to the Tenant will be three
(3) times the Landlord's cost. Any material, whether trash or otherwise, placed outside of the
leased premises for more than 24 hours shall be subject to removal and disposal without notice.
x
The Landlord may require that temporary floor protection be provided for delivery and trash
removal using wheeled equipment. This is required at all carpeted areas.
Demolition
The Contractor shall remove all uncovered, unused utilities and equipment, including but limited to the
following: ductwork, VAV boxes and grilles; electrical conduit, wiring and light fixtures; plumbing fixtures,
domestic water piping, vent piping and waste piping.
This includes electrical and plumbing utilities in the space below the Tenant floor level.
Existing Utility Interruptions
Do not interrupt utilities serving occupied areas unless permitted under the following conditions and then
only after arranging to provide temporary utility services according to requirements indicated:
x
Contractor shall be responsible to verify location of existing utilities, including utilities that pass
through the space serving other areas. Any effects of existing utilities on proposed construction
will be coordinated by the Contractor at no additional expense to the Landlord.
x
Notify the Operations Manager not less than seven days in advance of proposed utility
interruptions.
x
Do not proceed with utility interruptions without the Operations Manager’s written permission.
Structure
Structural modifications and coring through floor slabs require an engineering analysis and design. The
Tenant shall perform analyses and submit them for review by the Landlord’s structural engineer; review
shall be performed at the Tenant’s expense.
x
Supplemental structural support framing shall be installed by the Tenant to adequately support
suspended equipment within the premises. Where unusually heavy loads are applied to either the
Water Tower Place
92
CONSTRUCTION REQUIREMENTS
structural floor slab or to the building’s structural deck, specific details must be developed by the
Tenant and submitted for Landlord review and approval.
•
All storefront construction shall be floor supported only with an appropriate structural system,
with appropriate lateral bracing back to the building structure as required. No vertical load shall be
suspended from the Landlord’s storefront bulkhead system.
•
Coring may be permitted for installing piping and conduit through the slab, with concrete repairs
installed in accordance with building requirements.
A drawing submittal must be made to the Operations Manager prior to any slab penetrations
being made. Non-Destructive Testing is to be performed to locate existing reinforcing; results are
to be shown on the submittal. Proposed cores must be located within existing reinforcing.
Drawing is to be dimensioned and to scale. Note that X-Raying is not permitted.
Allow ten business days for the review of the coring submittal. No coring work is to be performed
without approval from the Operations Manager.
General Contractor Requirements
•
Tenant shall ensure that all Tenant contractors are bondable and licensed in the State of Illinois
and City of Chicago. Landlord shall have the right to approve Tenant’s contractors and
subcontractors; however, such approval shall not constitute the assumption of any responsibility
or liability by Landlord for the actions of Tenant’s contractors or subcontractors or the quality or
sufficiency of Tenant’s work.
•
The Contractor shall comply with all rules and regulations of the Federal and State Governments
and Chicago Health Department.
•
All work performed by Tenant’s contractor shall be performed in strict accordance with the final
plans approved by the Landlord.
•
Tenant’s contractor(s) may perform “noisy” construction, such as jack-hammering, saw cutting,
core drilling etc., only during hours designated by the Operations Manager. This is generally from
9:00 PM and 9:00 AM.
•
Work in public common areas visible to the public (such as barricade assembly & finishing) will
take place between 9:00 PM and 9:00 AM.
•
Tools, supplies, materials, store fixtures, etc. must be confined to the Tenant space. Nothing may
be left in common areas from 9:00 AM and 9:00 PM.
•
Tenant’s contractor shall obtain Landlord’s prior written approval for all drilling, welding, or other
attachment to Landlord’s structural system.
•
Tenant’s contractor’s work shall be subject to inspection by Landlord during the course of
construction for the purpose of determining the quality of workmanship and adherence to
Landlord requirements. Tenant’s contractor(s) is required to cooperate with the Operations
Manager and correct any deficiencies noted within (10) days.
•
The Contractor is responsible for vehicular parking for all employees and subcontractor
employees. No discount is available for utilizing the building parking garage; note that headroom
there is at 6’-4. No parking is available in the building loading dock.
•
No gasoline, flammable oils, or other highly combustible materials are to be stored at the site.
•
Provide separate, rodent-proof containers for food waste. No food waste is to be deposited in
construction waste containers prior to the immediate removal of the containers from the site.
Water Tower Place
93
CONSTRUCTION REQUIREMENTS
x
The Contractor shall notify the Operations Manager or Building Security within 24 hours of
receipt, of any complaints, fines, citations, violations or issues, by any governmental body or
regulatory agency against the Contractor relating to the Project. The Contractor will subsequently
provide evidence to the Landlord that these issues have been satisfactorily addressed and
resolved.
x
Floors areas where water is present shall receive a waterproof membrane extending a minimum
of 6” up adjoining partitions. The Tenant’s Contractor will be required to provide a flood test of
waterproofed areas prior to finishes being applied; the test is to be observed by the Operations
Manager.
HVAC Requirements
x
Contractor is to provide a filter at air returns for the duration of demolition and construction.
x
All work involving medium-pressure ductwork must be done between 12:00 AM and 8:30 AM.
x
Air balance reports are to be submitted prior to the store opening.
Temporary Power Requirements
x
The Tenant shall provide its own temporary lighting and power distribution.
x
In the event Landlord provides temporary electrical utility service, Tenant shall pay Landlord a
single charge equal to the greater of $750.00 or $0.75 per square foot of the leased premises.
Plumbing Requirements
x
A drawing submittal must be made to the Operations Manager prior to any horizontal slab
penetrations being made. Sonar investigations (X-Raying is not allowed) must be performed to
locate existing reinforcing and a drawing prepared; then proposed cores must be located within
the reinforcing. Drawing is to be dimensioned and to scale.
x
Allow ten business days for the review of the coring submittal. No coring work is to be performed
without approval from the Operations Manager.
x
Tenant’s contractor(s) may perform core drilling from 12:00 AM and 8:30 AM.
Fire Protection Requirements During Construction
x
The Tenant sprinkler is to remain inoperative during demolition and construction.
x
The initial drain down of the system will be performed at Landlord expense. Subsequent drain
downs will be at Contractor cost.
x
The valve test drain shall be piped to an open site drain.
x
The sprinkler system shall be pressure tested at 200 PSI for two hours and must be witnessed by
the Building Engineer.
x
Provide at least one Class ABC, 10 pound dry chemical fire extinguisher per 3,000 SF of area
under construction. Maximum separation between extinguishers is 75’-0.
Water Tower Place
94
INSURANCE
Insurance
The Tenant’s Contractor(s) must fulfill the following insurance requirements and shall maintain at no
expense to the Landlord.
x An insurance certificate shall be submitted to the Operations Manager prior to the start of
construction. Please reference the Store/Brand Name and Store Number for identification
purposes. Memorandums of Insurance and certificates sent via fax will not be accepted.
x
Insurance carriers shall have an AM Best's rating of A-VII or better, and shall be registered or
authorized to do business in the state in which the Shopping Center is located.
Certificate Holder
Water Tower LLC
Suite 987W, 845 N Michigan Ave
Chicago, IL 60611
Additional Insureds/ Loss Payee
Water Tower LLC, Rouse Property Management, Inc. and its direct and indirect parents and subsidiaries,
any of their affiliated entities, successors and assigns and any current of future director, officer employee,
partner, member or agent of any of them.
Required Coverage’s
General Liability
$1,000,000 Occurrence/ $3,000,000 Aggregate
$3,000,000 Products Comp/Op Aggregate
$1,000,000 Personal & Advertising Injury
$50,000 Fire Legal Liability
Include Waiver of Subrogation
Automobile Liability
$1,000,000 Combined Single Limit
Worker’s Compensation
Statutory
Employer’s Liability
$1,000,000 Each Accident
$1,000,000 Disease, Policy Limit
$1,000,000 Disease, Each Employee
Property
Special From Perils (“All Risk”)
Improvements & Betterments
Business Income
Replacement Cost
Include Waiver of Subrogation
Certification Clause
30 Days Notice
The following must be stricken from the cancellation wording: “Endeavor to...but failure to mail such
notice shall impose no obligation or liability of any kind upon the company, its agents, or representatives.”
OR
If this is not possible, an Additional Insured Endorsement specifically naming the above entities and
additional language must be provided.
Water Tower Place
95
LANDLORD PUNCH LIST
General Growth
Johnson Controls
A. City Certificate of Occupancy has been issued
(if required).
1. HVAC Air Balance report received.
B. Payment for Landlord work and materials has
been received.
C. Construction
documents.
conforms
to
approved
2. Abandoned utilities have been removed from
the space, including below the structural slab.
3. VAV Boxes, controllers and thermostats
conform to Building specified models.
4. Conduit for the future Building
Management System is installed.
D. Common areas are clean.
E. Flooring is completed outside the Tenant
Storefront and is flush with the public area
floor.
F. No storefront elements or signage cross the
lease line.
Energy
5. Thermostat set points conform to Building
requirements.
6. Nighttime heating is installed (at spaces with
exterior exposure).
H. Service corridor penetrations are firestopped.
7. Fire protection material and test certificates,
“as-built” shop drawings and installation
warranty received.
I.
Service door graphics have been installed.
8. Sprinkler drain line is hard-piped to a drain.
J.
Display Zone lighting types and installation are
acceptable.
9. Sprinkler heads at 6’-0 spacing at storefronts.
G. Service corridor finishes are completed.
K. Blade sign is installed (if applicable).
L. No light fixtures are aimed into common areas.
M. Tenant sound system is not audible outside
the space (if applicable).
N. Tenant security
system
requirements (if applicable).
conforms
to
O. Approval of the fire protection system has
been issued by the Landlord’s risk consultant.
10. Sprinkler heads at 6’-0 spacing around floor
openings.
11. Drain pan installed under water heater and
piped to open site drain (if heater required).
12. Water meter installed (if required).
13. 4-inch clean-outs accessible from the Tenant
space installed (if applicable).
14. Wet area waterproofing tested (if applicable).
15. BTU meter is installed (if required).
16. Signs and Display Zone lighting are connected
to timer; timer is set to correct time periods.
17. Electrical load phases balanced within 7%.
18. Electrical disconnect installed in space.
19. Electric meter reads entire electrical load.
20. Electrical system is fused properly.
21. Emergency and exit lighting fused properly.
22. Circuit breaker panel labeled properly.
23. Conduit connections are compression type.
24. Alarm conduit and junction box covers are red.
25. Tenant Fire Detection/ Emergency Voice
Communication system has been tested.
26. Override of Tenant sound system by the
Building Emergency Voice Communication is
operational (if applicable).
Water Tower Place
96