g Dead Tank Circuit Breakers 72.5– 800kV — Advanced Technology in a Compact, Reliable Design with Primary Plus TM Pre-engineered solution set that digitizes XD|GE primary equipment and provides factory installed and configured protection, monitoring, diagnostics and communications. GE Digital Energy Dead Tank Circuit Breakers — 72.5–800kV 363kV Dead Tank SF6 Circuit Breaker 800kV Dead Tank SF6 Circuit Breaker Robust, High Quality and Reliable Breaker Technology For over a century, utilities around the world have relied on GE products and services to increase power system reliability and improve grid resiliency and responsiveness. As a global leader in grid infrastructure products and services, GE supports a broad set of utility applications ranging from transmission and substation automation to distribution networks and smart metering, enabling greater safety, connectivity and increased security. Through an alliance with XD Electric®, GE has extended its portfolio to include high and ultra high-voltage power equipment supporting the highest transmission voltage levels in the world. XD Electric is one of China’s largest primary equipment manufacturers dedicated to the research, application and development of high and ultra high-voltage power transmission equipment. XD Electric has a broad range of products to transform and direct the flow of power for industrial, commercial and residential users. 2 The XD|GE alliance provides end-to-end transmission solutions to meet the growing demand for electricity globally. The combined portfolios of GE and XD provide a comprehensive range of technology solutions for customers in the utility sector and energy intensive industries. The XD|GE breaker offerings are robust in design and are based on proven technology, yielding high quality products suitable for an extensive range of applications. XD|GE’s breakers are compact in design and construction with advanced arc extinguishing technology and self-blast interrupting capability which significantly reduces product size and improves reliability. Designed with a modular spring operated mechanism and an integrated hydromechanical operating mechanism, these circuit breakers improve product reliability, reduce costs, and minimize maintenance requirements. GEDigitalEnergy.com Dead Tank Circuit Breakers — 72.5–800kV Key Features & Benefits Reduced Footprint Current transformers equipped in the bushing insulators allow for reduced space and foundations required for installation. Compact Design and Construction Advanced arc extinguishing technology significantly reduces product size and improves reliability. Excellent Seismic Performance and Pollution-Resistant Capability The dead tank circuit breaker is well-suited for areas with frequent earthquakes, high elevation or severe pollution. Maintenance Free Design Modular spring operated mechanism and integrated hydromechanical operating mechanism improve product reliability, reduce costs, and minimize maintenance requirements. Primary Plus XD|GE offers Primary Plus™ for all its critical power delivery equipment. Primary Plus is a pre-engineered solution set that provides utilities and large industrial facilities with a means to reduce the time and labor associated with substation construction, expansion, and maintenance, while utilizing technologies and methodologies familiar to existing engineering resources. XD|GE’s factory installed and configured solutions include: • Digitized primary equipment by replacing labor-intensive, individually terminated copper wires with standardized physical interfaces and open communications protocols (IEC 61850) • Electrical protection systems optimized for each primary asset and application to monitor and react to fault conditions 72.5kV Dead Tank SF6 Circuit Breaker • Highly secure and ruggedized communication network equipment including industrial strength wireless, fiber optic multiplexers, and Ethernet switches for an advanced and reliable communications infrastructure 3 Dead Tank Circuit Breakers — 72.5–800kV 72.5kV SF6 Insulated Breaker 126/145/252kV SF6 Insulated Breaker The LW24-72.5 is an outdoor dead tank SF6 circuit breaker with self-blast interrupter technology and a spring operating mechanism. Type LW24-126/145/252/T outdoor dead tank SF6 circuit breaker product line incorporates world class advanced technology at these kV ratings. Self-blast technology is well established and deployed throughout the industry. When interrupting a fault current, heat generated from arcing will compress the SF6 gas in the compression cylinder. As a result, highly pressurized gas travelling through the nozzle will extinguish the arc. Self-blast technology is more efficient and requires less operating energy than other arc extinguishing methods. Self-blast technology is used to reduce the operating energy and improve the interrupting reliability. With this advanced technology, the arc is extinguished by the highly pressured gas, which is a result of heat generated by the arc itself. Compared to traditional puffer technology, the operating energy of a self-blast circuit breaker could be reduced up to 50%. The operating mechanism used in this breaker, the CT20-II, is a spring driven technology. The advantages of this spring operated mechanism include improved stability and reliability, increased stability with ambient temperature changes, and minimal to zero maintenance given the lack of oil or gas component. The operating mechanism is a spring design, which makes the product simple in construction and light in weight with higher reliability and less noise in operation. The LW24-72.5 product has received independent KEMA® certification. To achieve certification, the product passed the back-to-back switching test as well as the shunt reactor switching test. This family of dead tank circuit breakers will have independent certifications from XIHARI, MHI, or KEMA depending on the rating class and design. This dead-tank breaker design is the most widely produced by XD|GE with over 2,000 units shipped and in service over the last few years. Normal Service Conditions Normal Service Conditions 2.1. Altitude 3000m 2.1. Altitude: ≤ 1000m (not more than 3000m in special condition) 2.2. Humidity monthly 90% 2.2. Humidity monthly 90% 2.3. Max. wind velocity 35m/s 2.3. Max. wind velocity 35m/s 2.4. Pollution class: IV class 2.4. Pollution class: III, IV class 2.5. Typical ambient temperature: -35°C to +40°C 2.5. Typical ambient temperature: -35°C to +40°C 2.6. Max. temperature difference daily: 25°C 2.6. Max. temperature difference daily: 25°C 2.7. Earthquake withstand density 9 degree 2.7. Earthquake withstand density 9 degree 2.8. Ice coating: ≤ 10mm 2.8. Ice coating: ≤ 10mm 2.9. Max. radiance from sun: 1000 W/m2 2.9. Max. radiance from sun: 1000 W/m2 72.5kV Dead Tank Circuit Breaker 4 126kV Dead Tank Circuit Breaker GEDigitalEnergy.com Dead Tank Circuit Breakers — 72.5–800kV 363/550/800kV SF6 Insulated Breaker The LW13A/23-363, LW13A-550, and LW13-800 family of products represent the technology platform for the highest kV rated XD|GE dead tank breakers. Single interrupting units per pole are utilized on breaker products from 363kV to 550kV without parallel capacitors and pre-insertion resistors. In addition, double interrupting unit designs are used for products from 363kV up to 800kV. Parallel capacitors and pre-insertion resistors are incorporated when double interrupting units per pole are used. Breakers from 363kV to 800kV can carry continuous current up to 5000A and have interrupting capability for short circuit at either 50kV or 63kA, per customer specification. Breakers above 363kV are equipped with the CYA8 hydromechanical mechanism. The fully integrated hydro-mechanical operating mechanisms are maintenance-free designs with long-term stability and reliability. 363kV - 800kV series dead tank breakers are tested and certified per IEC® standards by XIHARI®, the national HV lab in China. Normal Service Conditions 363kV Dead Tank SF6 Circuit Breaker 50kA 2.1. Altitude: ≤ 1000m (not more than 3000m in special condition) 2.2. Humidity monthly 90% 2.3. Max. wind velocity 35m/s 2.4. Pollution class: III, IV class 2.5.Typical ambient temperature: -35°C to +40°C 2.6. Max. temperature difference daily: 25°C 2.7. Earthquake withstand density 9 degree 2.8. Ice coating: ≤ 10mm 2.9. Max. radiance from sun: 1000 W/m2 550kV Dead Tank SF6 Circuit Breaker 550kV Dead Tank SF6 Circuit Breaker 800kV Dead Tank Circuit Breaker GEDigitalEnergy.com 5 Dead Tank Circuit Breakers — 72.5–800kV Technology lnner Construction Construction of Inner of Interrupter Interrupter 1. Interrupter The figure below shows the principle construction of the interrupter. The pressure of the gas in the puffer cylinder goes up when the gas is heated by the arc and then compressed by opening movement of the puffer cylinder. Fixed main contact Fixed arcing contact Moving main contact Piston This pressurized and compressed gas goes to the arc between the stationary contact and moving contact. The nozzle concentrates the gas flow to the arc for efficient cooling. Trip spring Trip spring Cam Cam Arc Nozzle Ratchet Ratchet Moving arcing contact Puffer cylinder LeverLever Ratchet Ratchet wheelwheel Closing-holding Closing-holding latchlatch 2. Spring Operating Mechanism The design of the spring operated mechanism provides the high performance required for reliable operation. The lever engaged with the locking device, which is released when the trip coil is energized, is rotated counterclockwise by the trip spring (Fig.1). Closing trigger Closing trigger Trip-holding Trip-holding the closing latch spring. The lever is rotated clockwise, compressing the trip spring latch Closing Closing coil coil by torque from the cam (Fig.2). As soon as the closing sequence is completed, the closing spring is charged interrupter interrupter openopen coil coil by the ratchet linked to the motor (Fig.3). The cam and the ratchet wheel engaged with the locking device, which is released when the closing coil is energized, are rotated counterclockwise by Cam Fixed Closing spring Closing spring finger Trip trigger Trip trigger Closed position Fig1.Fig1. Closed position (closing spring charged) (closing spring charged) Trip spring Ratchet Closing spring Lever Ratchet wheel Closing-holding latch Closing trigger Trip-holding latch Closing coil interrupter open coil Trip trigger Fig1. Closed position (closing spring charged) 6 Open position Fig2.Fig2. Open position (closing spring charged) (closing spring charged) GEDigitalEnergy.com Closed position Fig3.Fig3. Closed position (closing spring discharged) (closing spring discharged) Dead Tank Circuit Breakers — 72.5–800kV 3. Hydromechanical Operating Mechanism for Circuit Breakers The hydromechanical mechanism is built with its functional parts linked by integrated modules. To keep the operation as relaible as possible, “O”-rings are used at sealing points, disc-type springs are used to store energy, and two sets of respectively independent opening control valves are incorporated into Hydro-mechanical the design. This mechanism mechanism can be operated either in single phase or in three phase electrically, and can be gang-operated in Hydro-mechanical three phase mechanically. Hydro-mechanical mechanism a. Uncharged, open position b. Charged, open position 1. Low pressure oil tank a. Uncharged, 2. Oil lever indicator High pressure oil Low pressure oil open position 3. Operating piston rod 4. High pressure oil tank 5. Piston for charge 6. Support ring 7. Disk spring 8. Auxiliary switch High pressure oil 9. Oil-filling hole 10. Throttle of close 11. Electro-magnetic valve for close 12. Electro-magentic valve for open 13. Throttle of open 14. Oil drainage valve 15. Energy-store motor 16. Oil pump 17. Pressure release valve 18. Spring position switch c. Charged, closed position a. Uncharged, open position b. Charged, open position High pressure oil mechanism 1. Low pressure oil tank 2. Oil lever indicator 1. Low pressure oil tank 3. Operating piston rod 2. Oil lever indicator 4. High pressure oil tank 3. Operating piston rod 5. Piston for charge 4. High pressure oil tank 6. Support ring 5. Piston for charge 7. Disk spring 1. Low pressure oil tank 6. Support ring 8. Auxiliary switch 2. Oil lever indicator 7. Disk spring 9. Oil-filling hole 3. Operating piston rod 8. Auxiliary switch 10. Throttle of close 4. High pressure oil tank 9. Oil-filling hole 11. Electro-magnetic valve for close 5. Piston for charge 10. Throttle of close 12. Electro-magentic valve for open 6. Support ring 11. Electro-magnetic valve for close 13. Throttle of open 7. Disk spring 12. Electro-magentic valve for open 14. Oil drainage valve8. Auxiliary switch 13. Throttle of open 15. Energy-store motor 9. Oil-filling hole 14. Oil drainage valve 16. Oil pump 10. Throttle of close 15. Energy-store motor 17. Pressure release valve 11. Electro-magnetic valve for close 16. Oil pump 18. Spring position switch 12. Electro-magentic valve for open 17. Pressure release valve 13. Throttle of open 18. Spring position switch 14. Oil drainage valve 15. Energy-store motor 16. Oil pump 17. Pressure release valve 18. Spring position switch b. Charged, open position c. Charged, closed position c. Charged, closed position Low pressure oil Low pressure oil 550kV Dead Tank SF6 Circuit Breaker GEDigitalEnergy.com 7 72.5Dead – 800kV Tank DeadTank Circuit Breakers Circuit — Breakers 72.5–800kV Innovative Facilities and Rigorous Quality Processes XD|GE’s technology portfolio is built in state-of-the-art manufacturing and testing facilities with robust quality processes which provide customers with products that meet the critical and demanding reliability and environmental challenges of transmission applications. Manufacturing Excellence XD|GE designs a broad range of switchgear in five specialized production facilities including machining, surface treatment, insulating, housing and casting. Additionally, there are two specialized facilities that produce both the spring and hydromechanical operating mechanisms. Final production is completed in three workshop assembly lines that total more than 50,000 square meters. Components such as aluminum enclosures, cast resin insulators, current and voltage transformers, and operating mechanisms are manufactured by XD|GE through a completely integrated manufacturing model. Advanced Test Facilities XIHARI®, the Xi’an High Voltage Apparatus Research Institute, is an integral part of the XD|GE alliance. XIHARI has extensive testing capabilities at its facility sites, which include a: High Power Laboratory, High Voltage Laboratory, Artificial Climate Laboratory, EMC Laboratory, and an Operational Test Circuit for HVDC Thyristor Valves. The testing hall meets all of the requirements of ISO/IEC® 17025 and houses some of the largest test equipment in the world, providing the capacity to test primary equipment as large as 1,100kV AC. The High Voltage Apparatus Laboratory in XIHARI is a government authorized national high-voltage apparatus quality supervision and inspection test center. It is an independent third-party laboratory for type tests, routine tests, performance tests and certificate tests for high-voltage apparatus. The testing facilities at XIHARI also include an extension environmental laboratory. Testing capabilities here include high altitude testing, high humidity testing, and temperature testing from -70° C up to +150° C. The switchgear facilities are ISO® 9001 certified, ISO 14001 certified for environmental management systems, as well as OSHA® 18001 certified for health and safety management systems. Exceptional Quality A focus on quality is an ongoing strategic initiative for XD|GE and that is evident throughout the manufacturing environment. The quality process begins with an incoming inspection of all materials to ensure the best possible inputs before manufacturing begins. Throughout the production and assembly process, there are multiple checkpoints, including both visual inspections as well as stopped flow inspections, all performed to documented test plans. The production facilities follow strict non-conforming procedures to identify, control and avoid the use and delivery of non-conforming products. Each production facility has developed strict environmental standards, including controls of cleanliness, temperature and humidity, and has controls in place to monitor and manage to the established standards. In addition, XD|GE has a dedicated measurment and inspection department with a certified full time inspector in each of its manufacturing sites. The measuring and inspection department provides a secondary cross-inspection for all work in process, as well as finished products, ensuring a high level of quality is achieved throughout the manufacturing process. First Pass Yield and Cost of Quality data is maintained and analyzed, per product family, in order to drive continual product and process improvements and higher product reliability. From raw materials acquisition and inspection to finished product, XD|GE’s breakers are designed to meet rigid quality processes so the installed product provides the highest level of reliability. 8 GEDigitalEnergy.com Dead Tank Circuit Breakers — 72.5–800kV Support and Service Global Project Engineering Services XD|GE is dedicated to helping its customers reach their system objectives and provides a suite of professional services to assist the successful deployment and maintainance of XD|GE products and solutions globally. From design to implementation to post-sales support, a team of technical and business experts are available to help customers effectively use the capabilities and product domain knowledge that are available from XD|GE. This support infrastructure covers the entire life cycle of the product. From the coordination of transportation logistics to the completion of site acceptance testing and warranty service, the highly qualified XD|GE team is available throughout the implementation. To ensure a high quality of service to meet the needs of each unique application, XD|GE has a global field service team of highly experienced and dedicated individuals. Coupled with a vast network of high voltage power equipment domain experts, XD|GE is able to support a broad range of applications in various environments. Finally, XD|GE offers a 24x7 global support service to address and direct any customer application and field questions. Specialized Installation and Commissioning • Logistics including coordination of ocean and inland transportation • Installation services include receiving, rigging, unloading and labor (mechanical and electrical) • Test commissioning • Site acceptance testing Post-Sales and Installation Support • 24x7 global customer service • Emergency response hotline • Several customer support access points available to ensure timely support (telephone, e-mail, fax, or web) • Global spare parts reserve • A global network of maintenance and repair facilities 4800kV/720 kJ Impulse Voltage Generator & ±2000kV 30mA DC Voltage Generator GEDigitalEnergy.com 9 Dead Tank Circuit Breakers — 72.5–800kV Primary Plus Pre-Engineering Secondary Equipment Primary Plus, XD|GE’s supplemental offering to its primary equipment, is a pre-engineered, factory installed solution set that allows utilities to reduce the time and labor associated with substation construction and commissioning. Primary Plus uses technologies and methodologies familiar to existing resources and skill sets. • Digitized primary equipment for replacing labor-intensive, individually terminated copper wires • Electrical protection solutions to monitor and react to fault conditions • Secure and ruggedized communications infrastructure devices including wireless radios, fiber optic multiplexers and Ethernet switches Digitized Substation MultilinTM HardFiber System Key Benefits • Using the Multilin HardFiber system, XD|GE can deliver primary equipment with digital communications. The Multilin HardFiber system digitizes analog signals from primary assets utilizing IEC 61850 communications, reducing total life costs of protection and control through labor and resource optimization. • Saves up to 50% of Protection & Control labor costs • This factory-installed solution reduces the amount of labor-intensive, individually terminated copper wire connections with pre-terminated copper and fiber optic cables with standard physical interfaces and open digital communications. • Eliminates the majority of copper wiring to better utilize resources for the design, building, commissioning, and maintenance of power system protection and control • Robust and simple architecture for deploying IEC 61850 process bus • Improves employee safety by leaving potentially dangerous high-energy signals in the switchyard • Reduces the chances for operational mistakes made during isolation and restoration after routine maintenance • Built as an extension of the Multilin Universal Relay (UR) family of products, suitable for a wide array of protection applications • Rugged, hardened, and secure switchyard interface enabling NERC/CIP compliance Electrical Protection & Control Advanced Relays for Primary Substation Equipment Primary Plus utilizes the Multilin C60 Breaker Protection system or Multilin F60 Feeder Protection system to provide primary protection of critical substation equipment. Multilin relays are substation hardened devices that provide comprehensive protection, control, automation, and monitoring of high voltage substation circuit breakers. With fast, deterministic execution of programmable automation logic, extensive I/O options, and integrated high-speed peer-to-peer communications, Multilin protection devices can receive and execute commands and at a fraction of the cost when compared to a traditional hard-wired configuration. 10 Key Benefits • Advanced circuit breaker monitoring and control in a single platform • Complete IEC 61850 Process Bus solution providing resource optimization and minimizing total protection & control lifecycle costs • Modular hardware architecture allow for device configuration flexibility, meeting the needs of most circuit breaker applications • Advanced fault and disturbance recording, including internal device health monitoring, eliminating the need for external devices and maximizing asset life • Robust network security enabling critical infrastructure Protection and NERC/CIP compliance • Advanced automation capabilities for customized protection and control systems • Simplified system integration and access to information through the use of multiple communication options and protocols, including native support for IEC 61850 GEDigitalEnergy.com Dead Tank Circuit Breakers — 72.5–800kV Dimensions and Foundation 72.5kV SF6 Breaker LW24-72.5 LW24-72.5 2530 2320 10° 2115 10° 1160 30° 30° 2806 Grounding Terminal 32 56 300 885 981 2×4-M10 120 920 120 32 56 1280 M20 85 2363 3650 1360 920 280 150 392 500 500 1280 940 400 80 16 R6 All measurements are in millimeters (mm) GEDigitalEnergy.com 11 Dead Tank Circuit Breakers — 72.5–800kV 126-145kV SF6 Breaker LW24-126 LW24-126/LW24-145 2030 1560 251 3200 1510 1510 C 2 N1 10 M 2- 14 22x2.4 100 530 225 45 370 175 175 180 1000 6-ø12 180 120 34 610 120x200 200 R7 120 50 85 50 R7 200 630 100 250 370 GEDigitalEnergy.com (865) 2070 650 250 38 220 280 610 100 650 1300 1800 250 100 1205 120 38 1300 100 1500 1000 500 500 12 2*4-M10 50 1670 2300 3820 3900 1070 1750 1000 1530 1000 45 30 102 40 4-ф 3820 40 800 Dead Tank Circuit Breakers — 72.5–800kV 252kV SF6 Breaker LW24-252 outline and foundation drawing LW24-252 3000 - 4000 3000 - 4000 (2860) P2 591 (2511) (5165) P1 1320 1220 Phase B Phase C P1 P1 P1 t22 Aluminum Alloy Plate 9-φ18 2860 45 45 A-A 145 Phase A .5 R9 A A 45 45 45 10 P2 Grounding Block P2 10 0° 0° 800 P2 10 800 0° Terminal Pad 800 924 Cement Foundation A-A 70 320 E E 245 Grounding Position (2 places) A E 320 C E 500 300 E E 220 1380 1380 245 1220 A Anchor Bolt M30*800 145 All measurements are in millimeters (mm) C 373 GEDigitalEnergy.com 13 Dead Tank Circuit Breakers — 72.5–800kV 363kV SF6 Breaker LW23-363/ Y 363kV DTB with single-breaker LW23-363 4000-5000 4000-5000 873 510 700 920 1500 6534 (3463) (1438) 14 GEDigitalEnergy.com Dead Tank Circuit Breakers — 72.5–800kV 363kV SF6 Breaker LW13-363/Y Outline Drawing of 363kV DTB with double-breakers LW13A-363 5000 200 2200 2180 5000 1000 1120 5 84 1100 4620 800 820 800 80 Anchor Bolt M30X800 1800 3325 7300 2500 All measurements are in millimeters (mm) 125 GEDigitalEnergy.com 15 Dead Tank Circuit Breakers — 72.5–800kV LW13A-550/Y 550kV DTB Outline Drawing 550kV SF6 Breaker LW13A-550 Phase C Phase B Phase A 8000 2850 2450 8000 80 I (1000) (1180) 0 80 1100 800 5 R=84 0 30 150 125 800 16 Anchor Bolt M30X1000 1000 1000 105 1600 3195 2150 8395 1500 6190 GEDigitalEnergy.com All measurements are in millimeters (mm) Dead Tank Circuit Breakers — 72.5–800kV 800kV SF6 Breaker LW13-800 General Assembly Drawing LW13-800 DTB 11000 10249 11000 7607 500 P1 3820 2000 13146 500 630 1460 1580 800 Ground Grounding Block 190 LCP 1680 560 3864 4239 3820 3000 12966 12108 4681 4523 5620 P1 P1 36 Terminal Pad LCP 9-Ø24 65 65 65 65 65 220 R900 Aluminum Alloy Plate P2 Size of Grounding Block 70 15 GEDigitalEnergy.com 70 Copper Soldering 70*70 100 130 15 P2 40 P2 17 Dead Tank Circuit Breakers — 72.5–800kV Technical Specifications Main Technical Data of 72.5kV-800kV Dead Tank Circuit Breaker* PRODUCT TYPE LW24-72.5 LW24-126 LW24- 145 LW24-252 LW23-363 LW13A-363 LW13A-550 LW13-800 1. Electrical Parameters 1. 1 Rated voltage (kV) 72.5 126 145 252 363 363 550 800 1. 2 Rated frequency (Hz) 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 1. 3 Rated continuous current (A) 3150 3150 3150 4000 3150/4000/ 3150/4000/ 5000 5000 5000 1. 4 Rated short circuit breaking current (kA) 40 40 31.5/40 50/63 50 50/63 50/63 50/63 1. 5 Making current (kA) 100 100 80 125 125 125/160 135/171 135/171 1. 6 Rated peak withstand current (kA) 100 100 80 125 125 125/160 135/171 135/171 1. 7 Specific creepage distance (mm/kV) 25/31 25/31 25/31 25/31 25/31 25/31 25 25 1. 8 Short line fault breaking current (kA) 36/30 36/30 28.35/23.63 45/37.5 45/37.5(50kA); 56.7/47.25(63kA) 1. 9 Out of phase breaking current (kA) 10 10 7.875 12.5 12.5(50kA)/15.75(63kA) 1. 10 Rated short-time power-frequence withstand voltage (kV): To earth 160 230 275 460 510 510 740 960 1. 11 Rated lightning impulse withstand voltage (kV): To earth 350 550 650 1050 1300 1300 1675 2100 1.12 Last pole to clear factor 1.5 1.5 1.5 1.3 1.3 1.3 1.3 1.3 4 4 3 3 3 3 3 3 LW24-72.5 LW24-126 LW24- 145 LW24-252 LW23-363 LW13A-363 LW13A-550 LW13-800 2. 1 Type of mechanism Spring Spring Spring Spring/ Hydro-mechanical Spring/ Hydro-mechanical Spring/ Hydro-mechanical 2. 2 Mechanical endurance (times) ≥ 5000 ≥ 5000 ≥ 5000 ≥ 5000 ≥ 5000 ≥ 5000 ≥ 5000 ≥ 5000 1.13 Rated short-time withstand duration(s) PRODUCT TYPE 2. Mechanical Parameters 2. 3 Rated operating sequence Hydro-mechanical O-0.3s-CO-180s-CO 2. 4 Close time (ms) ≤100 ≤100 ≤100 ≤110 ≤100 ≤100 ≤100 ≤100 2. 5 Open time (ms) ≤30 ≤30 ≤30 ≤30 ≤20 ≤20 ≤20 ≤20 2. 6 Breaking time (ms) ≤60 ≤60 ≤60 ≤60 ≤40 ≤40 ≤40 ≤40 40-50 40-50 40-50 50-70 40-50 40-50 40-50 40-50 ≤3 ≤4 ≤3 ≤5 ≤3 ≤4 ≤3 ≤4 ≤3 ≤5 ≤2 ≤3 ≤2 ≤3 ≤2 ≤3 ≤2 ≤3 2. 7 Close-open time (ms) 2. 8 Operating asynchronism (ms) Between poles Open Close ≤2 ≤4 2. 9 Operating asynchronism (ms) Across break Open Close 2. 10 Number of breaks per pole 1 1 1 1 1 2 2/1 2 2. 11 Three phase operation/ single phase 3p 3p 3p 3p/1p 1p 1p 1p 1p 0.4/0.5 0.5 0.5 0.6 0.5 0.5 0.5/0.6 0.6 2. 12 Rated SF6 gas pressure (Mpa) 2. 13 Leakage of SF6 gas per year (%) ≤0.5 ≤0.5 ≤0.5 ≤0.5 ≤0.5 ≤0.5 ≤0.5 ≤0.5 2. 14 Weight (kg) 1550 3400 3400 9000 10000 18000 18000/15000 60000 * Additional products available - see product ordering page for complete listing. 18 GEDigitalEnergy.com Dead Tank Circuit Breakers — 72.5–800kV Ordering LW SF6 Circuit Breaker Outdoor Design Sequence No. - * * / * * - * LW 24 13/ 13A 23 Rated Voltage 72.5 126 145 252 363 550 800 Operating System: T: Spring Mechanism Y: Hydro-mechanical Mechanism Rated Current (A) T Y 1250 2000 3150 4000 5000 Rated Interrupting Current (kA) 31.5 40 50 63 Dead Tank Circuit Breaker Product Line With Spring Mechanism: Dead Tank Circuit Breaker Product Line With Hydro-mechanical Mechanism: LW24-72.5/T1250-31.5 LW24-252/Y4000-63 LW24-72.5/T2000-31.5 LW23-363/Y3150-50 LW24-72.5/T2500-31.5 LW23-363/Y4000-50 LW24-72.5/T3150-40 LW13A-363/Y3150-50 LW24-126/T3150-40 LW13A-363/Y4000-50 LW24-145/T3150-31.5 LW13A-363/Y5000-50 LW24-145/T3150-40 LW13A-363/Y3150-63 LW24-252/T4000-50 LW13A-363/Y4000-63 LW13A-363/Y5000-63 LW13A-550/Y5000-63 LW13-800/Y5000-63 Ordering Notes: Please provide the following information when ordering: 1. Type, description of product, and type of mechanism. 2. Rated voltage, rated current, short circuit breaking current. 3. Current ratio, accuracy class and quantity, rated output capacity. 4. Pollution class: class III or class IV. 5. Control voltage of mechanism: DC220V or DC110V. 6. Voltage of energy-store motor: AC380V or AC/DC 220V or AC/DC 110V. GEDigitalEnergy.com Toll Free: 1.877.605.6777 Direct: 678.844.3777 gedigitalenergy@ge.com 2018 Powers Ferry Road, Atlanta, GA 30339 19 GEDigitalEnergy.com Digital Energy Toll Free: 1.877.605.6777 Direct: 678-844-6777 gedigitalenergy@ge.com 2018 Powers Ferry Road, Atlanta, GA 30339 GE, the GE monogram, Primary Plus and Multilin are trademarks of the General Electric Company. g XD Electric is a registered trademark of China XD Electric Group. XIHARI is a registered trademark of the Xi’an High Voltage Apparatus Research Institute Co., Ltd. IEC is a registered trademark of Commission Electrotechnique Internationale. IEEE is a registered trademark of the Institute of Electrical Electronics Engineers, Inc. ISO is a registered trademark of the International Organization for Standardization. OSHA is a registered trademark of the U.S. Department of Labor. KEMA is a registered trademark of DNV. GE Digital Energy reserves the right to make changes to specifications of products described at any time without notice and without obligation to notify any person of such changes. Copyright 2013, General Electric Company. GEA-12723B(E) English 131220