JC71478 installation sheet

advertisement
Installation Sheet
a
company
Profile & Dimensions
Please read these instructions before
installation and retain for future reference
Important Information
SKYTILE® BASE EMERGENCY
Integral LED
32W
2800 lumens
88 LpcW
4200K
80
Installation Procedure
Read instructions and check you have all the tools and accessories required to complete the installation correctly.
Isolate power supply before starting the installation.
1.
2.
3.
4.
5.
240V~ 50Hz / Class I
Fig.1.
Blue
Neutral: Blue
Brown
Switched Live: Brown
Black
Unswitched Live: Black
6.
7.
8.
9. Remove the ceiling tile from the location where you wish to install the LED Panel.
Wire the Emergency Remote Pack to the mains supply. Refer to Fig.1 for details.
Plug the Red/Black cable into the receiving socket on the LED Panel, then plug the Blue/brown plug and
play wire into the receiving socket on the LED driver supplied. (Fig.2)
Disconnect and disregard the White mains cable supplied connected to the LED driver.
Connect the two core Blue/Brown cable from the remote pack into the mains input terminals of the Skytile
driver. (Fig.3)
Connect batteries inside the remote pack prior to completing the installation
Ensure the Green LED Charge indicator is located alongside the Skytile and is visible once the fitting is installed and operational.
View on inside of ceiling void showing LED Panel in position with Emergency Remote Pack
positioned on top of it.
Reconnect mains power supply, and test.
LED Driver
1A Fused Unswitched Live
Fig. 2
Mains
Supply
Plug & Play Connector - LED Panel
Red/Black
Ceiling Grid
Emergency
Remote Pack
Plug & Play Connector - LED Driver
Fig. 3
Black/Dash White
Suspension Mounting
JCC can also supply
a Wire Suspension Kit
for applications where
a ceiling grid is not
available
Ordering Code: JC71311
Ceiling Fix
Suspension
Wire
Panel Fixing
Bracket
LED
Panel
Surface Mounting
JCC can also supply a
Surface Mounting Tray.
Ordering Code: JC71262.
Note: DO NOT carry out insulation tests with the driver connected to the circuit. The external flexible cable cord of this
luminaire cannot be replaced: if the cord is damaged the luminaire should be decommissioned and destroyed.
Mains supply to LED Driver
All dimensions in millimetres
LED Panel
Black/Dash White
Blue/Brown
595
It may be necessary to uprate your MCBs to allow for increased inrush current. A 24 Hour charge period will be required
prior to any testing.
Emergency LED Panel
9.8
It is recommended that luminaires are installed by a qualified electrician to ensure that the installation complies with the
current IEE wiring regulations BS7671: 2008.
Any broken or damaged parts should be replaced as soon as possible.
JCC will not accept responsibility for any claims arising from sub-standard installations.
Installation Note
JC71478
Light source:
Total circuit Wattage:
Luminous flux:
Efficacy:
Colour temp:
Ra:
595
Important Warranty Information
Please ensure there
is adequate clearance
around the fitting to
allow access
to the panel.
This product has a 3 Year Extended Warranty, which must be registered on-line via the website address below.
RoHS
Compliant
IP20
BS EN ISO9001 - 2008
Registered Firm Certificate No. GB 1552
Drg No. JC71478-IS Issue: A - 26.11.15 - RCS
The installer will be asked to provide the following information which can be obtained from a label
attached to the rear of the luminaire chassis:
•
•
Product Code.
Batch Code.
jcc.co.uk
JCC Lighting Aftersales
Technical Support Helpline: 01243 838986
Customer Service Department: 01243 838999
Download