ML-F-2x2 and 2x4 Type

advertisement
Med Lock Series
2x2 and 2x4 Recessed Flanged Luminaires for Surgical Suites
For Use in Continuous Row, Rectangle and Individual Layouts
ML04
Specifications:
Project:
Housing: Lapped and spot welded 20-gauge zinc coated CRS construction. All
seams of hole-free housing silicone sealed.
Fixture Type:
Door Frame: 20-gauge CRS or stainless steel channel door frame hinged to housing
with continuous stainless steel piano hinge. Secured with 2 captive stainless steel
fasteners.
Cross Section
Yoke
Gaskets: Neoprene, 100% pure, closed cell located at interface of door to housing and door to lens. See Option “GG” for SealPro™ NSF Listed closed cell
gasketing.
4.50”
Reflector: Full reflector panel designed to enhance asymmetric distribution. White
powder coat finished (minimum reflectivity 88%).
25.25”x 50.25”
To Table
Lens: One piece symmetric/asymmetric acrylic lens gasketed (closed cell 100% pure
neoprene) in channel door frame. RFI shielded lens ( .375" metallic silver grid)
complies with radiated emissions (RE101) of Military Standard 461E. Consult
factory for other lens options.
Ceiling Cutout
Lamps: See lamp options listed below. Lamps supplied by others.
Electrical: Standard ballasts - Electronic, less than 10% THD high performance
instant start universal voltage (120-277 volt). See options for other choices. Each
fixture is standard with one RFI line suppressor. Tested to surpass conducted
emissions (CE102) of Mil. Std. 461e See Options for additional selections for
ballasts and suppressor circuits.
24”
Finish: White DuPont Alesta™ using Agion® silver ion antimicrobial powder coat
finish standard. See option SSP for satin polished stainless steel doors.
49”
Installation: Yoke mounting standard. Flanges of adjoining fixtures are factory
removed to facilitate the installation in continuous rows mounting (CRM) without
overlapping flanges. Four .875" flattened and silicone sealed knockouts for wiring.
IP
64
Listings: UL and CUL Listed for Wet Location. IBEW Label. EMC tested and
labeled for Mil-Std 461E.
Ordering Information:
ML
- F
-
-
-
Size
-
Lamps
Material
ML
F = Flange
1 = CRS Hsg. & CRS Door
2 = CRS Hsg. & SS Door
2x2 = 2'x2' Housing
2, 3, 4 or 6/T8 = F17T8 17W T8 (G13)
1 or 2/T8U6 = F32T8/U/6 (6” U-Lamp, G13)
2 or 3/T8U1 = F31T8/U (1.625” U-Lamp, G13)
2, 3 or 4/BX = 40-Watt Biax (2G11)
2, 3, 4 or 6/T5HO = F24WT5 24W T5HO (G5)
2x4 = 2'x4' Housing
2, 3, 4 or 6/T8 = F32T8 32W T8 (G13)
2, 3, 4 or 6/T5 = F28WT5 28W T5 (G5)
2, 3, 4 or 6/T5HO = F54WT5 54W T5HO (G5)
Kurtzon Lighting / Quality Since 1898
IEC 60529
-
Series Installation Type
Many installations of these fixtures are in continuous rows. The ML series is
unique in that it is designed to be used in this manner though it is standard as
an individual fixture. Kurtzon provides a layout guide to facilitate the planning and installation of CRM option fixtures. See facing page.
WET LOCATION
Voltage
120V
277V
347V
UNV
Options
FF = Fuse & Holder
FD = Two Fuses & Holders
FT = Three Fuses & Holders
ESB = Magnetic Ballast (T8 32W only)
EBPRS= Program Rapid Start Ballast
DIM = Electronic Dimming Ballast**
1/EM = One Lamp Emergency Ballast (700 L)
2/EM = Two Lamp Emergency Ballast (1300 L)
F/EM= Two Lamp Emergency Ballast (3000L)†
2/CIR= Two RFI Protected Switched Circuits
3/CIR= Three RFI Protected Switched Circuits
GG = NSF listed SealPro™ Gasket
SSP= Satin Polished Stainless Steel Door
P12/RFI= Prismatic P12 Acrylic w/RFI Grid
PF= Plaster frame (For wet plaster ceilings)
GL2= Two Green 550nm T8 lamps
**Dimming ballasts are 0-10vdc type by manufacturer of our choice unless specified. Use DIM/(Model
Name) to specify a certain dimming system.
†Externally Mounted Emergency ballast is secured to
top of fixture housing.
Morris Kurtzon, Incorporated
1420 South Talman Avenue, Chicago, Illinois 60608
773/277-2121 FAX 773/277-9164
© 2010
Website - www.kurtzon.com
Med Lock Series
ML-F Operating Room Planning and Layout Guide
ML04
1. Layout
This guide is provided in order to help our users plan proper
installation of the complete Surgical lighting system.
The electrical plans contain information required to determine the configuration and quantity of each system component. Please provide the plan or complete this information
sheet and return it to the Kurtzon Customer Service Department.
There are three pieces of information needed before production of your order.
ML-F Series fixtures are designed to join together without
overlapping flanges and seams. For example; the end fixtures are flanged on one end and two sides; middle fixtures
are flanged on two sides. The complete housing is hole free,
silicone sealed and mates with adjoining housings using a
multi-point fastening and gasket system. This method creates
a sealed plenum.
The layouts below are the most common found within surgical suites. Please indicate which layout is used within your
plans. If a different design is required or none at all, please
specify your layout by sending us ceiling plan drawings or
sketches of your requirements. To assist you in your planning
we provide cad drawings from our website. This allows the
user to assemble nearly any layout selecting from eight different flange arrangements.
L
UA
VID
DI
IN
Center
Center
Center
Center
Center
Left Corner Right Corner
Left Corner
Center
Left End
Corner
Center
Right End
Left End
Corner
Center
Center
Center
Right End
Corner
Center
Right Corner
Right End
Center
Center
Left End
Left Corner Right Corner
Right End
Corner
Center
Left Corner
Left End
Right Corner
Individual
Individual
225 FC
Rectangular
Open Corner
245 FC
Rectangular
Closed Corner
Kurtzon Lighting / Quality Since 1898
250 FC
Square
225 FC
Modular
Morris Kurtzon, Incorporated
1420 South Talman Avenue, Chicago, Illinois 60608
773/277-2121 FAX 773/277-9164
© 2010
Website - www.kurtzon.com
Med Lock
ML-F Operating Room Planning and Layout Guide
ML04
2. Electrical
The electrical plans will indicate the number and configuration
of circuits controlling the fixture. A RFI filter is required per
switched circuit to comply with Mil Std. 461e. Please address
the following:
accommodate up to two circuits and a high lumen emergency
lighting ballast.
B. Emergency Lighting
Maintaining safe lighting levels in the surgical suite during a
power outage is possible using a self contained battery powered
emergency lighting ballast. Emergency lighting ballasts are
available in two general types. Standard NFPA 101 egress
lighting type and generator backup type. The two differ in the
amount of light generated and running time. The generator
backup type can drive up to three lamps at nearly full output
for a short duration, usually less than five minutes. Egress
lighting types will drive one or two lamps at a greatly reduced
output for 90 minutes. Please advise the type of emergency
lighting required for your project.
A. The number of switched circuits per fixture.
The standard fixture is provided with one switched circuit and
therefore one RFI. Additional switched circuits are specified
by the appropriate option suffix additions to the catalog number such as; 2/CIR or 3/CIR. Keep in mind; there is a physical limit to the number of ballasts RFI filters and emergency
lighting ballasts a fixture can contain. Our 2x4 fixture allows
up to four circuits or 3 circuits and one high lumen emergency
lighting ballast without modifications. Consult factory for
arrangements in excess of this. The smaller 2x2 fixture can
Left Corner
Right Corner
Arrow indicates maximum
candlepower direction or aim.
(see label in fixture)
FA
Center
Center
W1
Center
FA
4a
4b
F
Right Corner
3b
3. Ceiling Cutout
This series is intended for recessed installation in a plaster or
drywall (GWB) ceiling system. The sizing of the ceiling finished
opening or "cutout" is important to a successful installation. We
provide detailed drawings showing the ceiling cutout size with
each order. Also available are cad drawings showing examples
and templates in 2D and 3D on our website. If you still need
to calculate your own finished ceiling openings please consider
the following. The ceiling cutout is always spaced 0.50 inches
from the housing body. This gives proper spacing and tolerance
to create a cutout and seal the plenum. Cutouts are calculated
using the following formulas.
Row Cutout Formulas:
#1(L1 x Qty in Row) +1= CL
#2 W1 +1= CW
L1
Left Corner
3a
Center
FA1
Ceiling cutout
L2
c
W2
Dimensions (inches)
2x2
2x4
L1
Housing body (L) (along lamps)
24.0
48.0
W1
Housing body (W) (across lamps)
23.0
23.0
L2
Housing with two flanges (L) O.A.
26.25
50.25
W2
Housing with two flanges (W) O.A.
25.25
25.25
F
Flange extension from body
1.125
1.125
25 x 24
49 x 24
C /C
L
W
Ceiling Cutout (L1 +1") x (W1 +1")
Rectangle / Square Cutout Formulas:
#3a. (L1 x Qty in Row) + 2(W1) +1= CL1 = 143"*
#3b. (L1 x Qty in Row) +1= CL2= 97"*
#4a. CL1 -2(W1)-2 = CW1 = 95*
#4b. CL2-2(W1)-2 = CW2 =49"*
When calculating the cutout for a rectangle with closed corners you must determine
the row length CL in both directions and offset the cutout by the result of W1+1 to
obtain result CW1 & CW2 dimension.
Kurtzon Lighting / Quality Since 1898
Morris Kurtzon, Incorporated
1420 South Talman Avenue, Chicago, Illinois 60608
773/277-2121 FAX 773/277-9164
© 2010
Website - www.kurtzon.com