Super Vu-Tron® Supreme Types SJOOW/SOOW

advertisement
Rubber Cord
Cord & Cordset
Super Vu-Tron® Supreme Types SJOOW/SOOW
105ºC 300 and 600 Volt UL /CSA Portable Cord
N
PRO EW
DUC
T
Product Construction:
Conductors:
• 18 through 10 AWG. fully annealed
stranded tinned copper per ASTM B-174
Insulation:
• Premium-grade, color-coded, oil-resistant
105ºC EPDM
• Color Code: See chart below
TYPE SJOOW – 300 VOLT – UL/CSA
APPROX.
NO.
NET WT. COPPER
CATALOG OF AWG. COND. STRAND
CURRENT LBS/
WT.
STD.
†
NUMBER COND. SIZE STRAND O.D. INCHES mm INCHES mm AMPS
M' (S) LBS/M' CTN.
NOM. INS.
JACKET
THICKNESS NOMINAL O.D.
02601
02602
02603
2
3
4
18
18
18
41/34
41/34
41/34
.048" 0.030 0.76 0.310
.048" 0.030 0.76 0.320
.048" 0.030 0.76 0.345
7.87
8.13
8.76
10
10
7
60
70
85
10
15
20
1000'
1000'
250'
02604
02605
02606
2
3
4
16
16
16
65/34
65/34
65/34
.061" 0.030 0.76 0.315 8.00
.061" 0.030 0.76 0.335 8.51
.061" 0.030 0.76 0.370 9.40
13
13
10
67
83
100
16
24
32
1000'
250'
250'
02607
02608
02609
2
3
4
14 105/34 .078" 0.030 0.76 0.370 9.40
14 105/34 .078" 0.030 0.76 0.375 9.53
14 105/34 .078" 0.030 0.76 0.405 10.29
18
18
15
90
114
132
26
41
55
250'
250'
250'
TYPE SOOW – 600 VOLT – UL/CSA
NO.
CATALOG OF AWG. COND.
NUMBER COND. SIZE STRAND
NOM. INS.
THICKNESS
APPROX.
NET WT. COPPER
CURRENT LBS/
WT.
STD.
mm AMPS†
M' (S) LBS/M' CTN.
JACKET
NOMINAL O.D.
INCHES
mm
INCHES
02631*
02632
02633*
2
3
4
18
18
18
41/34
41/34
41/34
0.030
0.030
0.030
0.76
0.76
0.76
0.365
0.375
0.400
9.27
9.53
10.16
10
10
7
75
84
110
10
15
21
250'
250'
250'
02634
02635
02636
02621
2
3
4
5
16
16
16
16
65/34
65/34
65/34
65/34
0.030
0.030
0.030
0.030
0.76
0.76
0.76
0.76
0.370
9.40
0.395 10.03
0.425 10.80
0.515 13.08
13
13
10
8
86
105
127
181
16
24
32
40
250'
250'
250'
250'
02637*
02638
02639
02622*
2
3
4
5
14
14
14
14
105/34
105/34
105/34
105/34
0.045
0.045
0.045
0.045
1.14
1.14
1.14
1.14
0.510 12.95
0.525 13.34
0.575 14.61
0.675 17.15
18
18
15
12
155
176
218
285
26
41
55
66
250'
250'
250'
250'
02641*
02642
02643
02623*
2
3
4
5
12
12
12
12
168/34
168/34
168/34
168/34
0.045
0.045
0.045
0.045
1.14
1.14
1.14
1.14
0.590 14.99
0.600 15.24
0.650 16.51
0.730 18.54
25
25
20
16
200
243
295
315
41
67
90
103
250'
250'
250'
250'
02645
02646
02624*
3
4
5
10
10
10
259/34
259/34
259/34
0.045
0.045
0.045
1.14
1.14
1.14
*Non-stock item; minimum quantity purchase required.
†G reen conductor for grounding only. Ampacities based on
NEC table 400.5(A).
(S)
Actual shipping weight may vary.
0.660 16.76
0.710 18.03
0.770 19.56
30
25
20
299
413
432
99
132
168
250'
250'
250'
COLOR CODE CHART
NO. OF
CONDUCTORS
COLOR
2
3
4
5
Black, White
Black, White, Green/Yellow
Black, White, Red, Green/Yellow
Black, White, Red, Orange, Green/Yellow
Jacket:
• Super Vu-Tron® Supreme, Yellow
• Temperature Range:
–50ºC to +105ºC UL/CSA
• Voltage rating:
300 volts Type SJOOW
600 volts Type SOOW
Jacket Marking:
• CAROL SUPER VU-TRON SUPREME
(SIZE) (mm2) 105C (UL) WATER RESISTANT
SJOOW (OR SOOW) CSA (–50C) FT-1
P-123-103 MSHA 300 (OR 600) VOLT
RoHS MADE IN USA
Applications:
• Machine tools
• Power tools
• Dockside power applications
• Motor leads
• Portable machinery
• Cranes
• Submersible pumps
• Where water immersion is required
• Severe OEM/MRO applications
Features:
• Yellow stripe on green conductor
• Sequential footage marks
• Excellent flexibility in cold temperatures
• Last longer in flex applications
• Integral Flexfill®
• Ozone- and weather-resistant
• UL Listed and CSA Certified for indoor and
outdoor use
• Water-resistant - can be immersed in water
• Safety-colored
• High heat and flame resistance
• Resistant to oils, acids and chemicals
• Excellent abrasion and cut resistance
• Class M stranding
• Tinned copper conductors - corrosion/
oxidation-resistant
• Sunlight- (UV) resistant
Industry Approvals:
• UL Flexible Cord - UL Subject 62
• CSA Flexible Cord - C22.2-49
• MSHA Approved
• RoHS Compliant
• CE Mark - Sizes 10 AWG and
12 AWG SOOW
• OSHA Acceptable
• JC580
Packaging:
• 250' (76.2 m), 500' (152.4 m),
1000' (304.8 m)
• Other put-ups available on special order
OSHA
Acceptable
Occupational Safety and Health
Administration
5
Rubber Cord
Cord & Cordset
AV
SPECAILABLE
THRIUAL ORDBEY
2008 R
!
Super Vu-Tron® III Types SJOOW/SOOW
105ºC 300 and 600 Volt UL /CSA Portable Cord
Product Construction:
Conductors:
• 18 through 10 AWG fully annealed
stranded bare copper per ASTM B-174
Insulation:
• Premium-grade, color-coded, oil-resistant
105ºC EPDM
• Color Code: See chart below
TYPE SJOOW – 300 VOLT – UL/CSA
Jacket:
• Super Vu-Tron® III, Yellow
• Temperature Range:
–50ºC to +105ºC UL/CSA
• Voltage rating:
300 volts Type SJOOW
600 volts Type SOOW
NOMINAL INS.
THICKNESS
CATALOG
NUMBER
NO. OF
COND.
Jacket Marking:
02001*
02002*
02003*
2
3
4
18
18
18
41/34
41/34
41/34
• CAROL SUPER VU-TRON III (SIZE)
105C (UL) WATER RESISTANT SJOOW
(OR SOOW) CSA (–50C) FT-1 P-123-103
MSHA 300 (OR 600) VOLT
02004*
02005*
02006*
2
3
4
16
16
16
02007*
02008*
02009*
2
3
4
14
14
14
Applications:
• Machine tools
• Power tools
• Dockside power applications
• Motor leads
• Portable machinery
• Cranes
• Submersible pumps
Features:
• Excellent flexibility in cold temperatures
• Last longer in flex applications
• Integral Flexfill®
• Ozone- and weather-resistant
• UL Listed and CSA Certified for indoor
and outdoor use
• Water-resistant, sunlight- (UV) resistant
• Safety-colored
• High heat and flame resistance
• Resistant to oils, acids and chemicals
• Excellent abrasion and cut resistance
Industry Approvals:
• UL Flexible Cord - UL Subject 62
• CSA Flexible Cord - C22.2-49
• MSHA Approved
• RoHS Compliant
Packaging:
• 250’ (76.2 m), 500’ (152.4 m),
1000’ (304.8 m)
• Other put-ups available on special order
COLOR CODE CHART
NO. OF
CONDUCTORS
COLOR
2
3
4
5
Black, White
Black, White, Green
Black, White, Red, Green
Black, White, Red, Orange, Green
6
AWG COND.
SIZE STRAND INCHES
NOMINAL O.D.
APPROX.
CURRENT NET WT.
AMPS† LBS/M1(S)
STD.
CTN.
mm
INCHES
mm
0.030
0.030
0.030
0.76
0.76
0.76
0.310
0.320
0.345
8.00
8.12
8.76
10
10
7
56
65
80
1000'
1000'
250'
65/34
65/34
65/34
0.030
0.030
0.030
0.76
0.76
0.76
0.315
0.335
0.370
8.00
8.51
9.40
13
13
10
68
80
95
1000'
250'
250'
41/30
41/30
41/30
0.030
0.030
0.030
0.76
0.76
0.76
0.370
0.375
0.405
9.40
9.52
10.29
18
18
15
90
110
130
250'
250'
250'
TYPE SOOW – 600 VOLT – UL/CSA
NOMINAL INS.
THICKNESS
NOMINAL O.D.
APPROX.
CURRENT NET WT.
AMPS† LBS/M1(S)
CATALOG
NUMBER
NO. OF
COND.
AWG
SIZE
COND.
STRAND
INCHES
mm
INCHES
mm
02031*
02032*
02033*
2
3
4
18
18
18
41/34
41/34
41/34
0.030
0.030
0.030
0.76
0.76
0.76
0.365
0.375
0.400
9.27
9.53
10.16
10
10
7
75
80
110
250'
250'
250'
02034*
02035*
02036*
02021*
2
3
4
5
16
16
16
16
65/34
65/34
65/34
65/34
0.030
0.030
0.030
0.030
0.76
0.76
0.76
0.76
0.370
0.395
0.425
0.515
9.40
10.80
10.80
13.08
13
13
10
8
75
100
120
150
250'
250'
250'
250'
02037*
02038*
02039*
02022*
2
3
4
5
14
14
14
14
41/30
41/30
41/30
41/30
0.045
0.045
0.045
0.045
1.14
1.14
1.14
1.14
0.510
0.525
0.575
0.675
12.95
13.34
14.61
17.15
18
18
15
12
155
165
215
285
250'
250'
250'
250'
02041*
02042*
02043*
02023*
2
3
4
5
12
12
12
12
65/30
65/30
65/30
65/30
0.045
0.045
0.045
0.045
1.14
1.14
1.14
1.14
0.590
0.600
0.650
0.730
14.99
15.24
16.51
18.54
25
25
20
16
200
250
280
315
250'
250'
250'
250'
02045*
02046*
02024*
3
4
5
10
10
10
104/30
104/30
104/30
0.045
0.045
0.045
1.14
1.14
1.14
0.660
0.710
0.770
16.76
18.03
19.56
30
25
20
320
375
432
250'
250'
250'
*Non-stock item available by special order; minimum quantity purchase required.
†G reen conductor for grounding only. Ampacities based on NEC table 400.5(A).
(S)
Actual shipping weight may vary.
STD.
CTN.
Rubber Cord
Cord & Cordset
Carolprene® Jacketed Type SOOW
105ºC 600 Volt UL /CSA Portable Cord
Product Construction:
Conductors:
• 16 through 10 AWG. fully annealed
stranded bare copper per ASTM B-174
Insulation:
• Premium-grade, color-coded 105ºC EPDM
• Color Code: See chart below
Jacket:
• Carolprene®, Yellow
• Temperature Range: -40ºC to +105ºC
TYPE SOOW – 600 VOLT – UL/CSA
CATALOG
NUMBER
NO. OF
COND.
16163
16164
16173
16174
16183
16184
16193
16194
3
4
3
4
3
4
3
4
NOMINAL INS.
THICKNESS
AWG. COND.
SIZE STRAND INCHES mm
16
16
14
14
12
12
10
10
26/30
26/30
41/30
41/30
65/30
65/30
104/30
104/30
0.030
0.030
0.045
0.045
0.045
0.045
0.045
0.045
0.76
0.76
1.14
1.14
1.14
1.14
1.14
1.14
NOMINAL O.D.
INCHES
mm
0.390
0.420
0.540
0.575
0.595
0.650
0.660
0.735
9.91
10.67
13.72
14.61
15.11
16.51
16.76
18.67
Cord furnished with UL and CSA labels.
*Non-stock item; minimum quantity purchase required.
†G reen conductor for grounding only. Ampacities based on NEC table 400.5(A).
(S)
Actual shipping weight may vary.
APPROX.
CURRENT NET WT.
AMPS† LBS/M' (S)
13
10
18
15
25
20
30
25
96
113
167
200
214
265
279
347
STD.
CTN.
250'
250'
250'
250'
250'
250'
250'
250'
Jacket Marking:
• CAROL (SIZE) (mm2) 105C (UL) WATER
RESISTANT SOOW CSA (-40C) FT-2
P-123-103 MSHA 600 VOLT RoHS
MADE IN USA
Applications:
• Portable tools and equipment
• Portable appliances
• Small motors and associated machinery
Features:
• Excellent resistance to oil and moisture
• Good tensile strength, elongation and
aging characteristics
• High flexibility
• Excellent abrasion resistance
• Water-resistant
• UL Listed and CSA certified for indoor
and outdoor use
Industry Approvals:
• UL Flexible Cord
• CSA Flexible Cord
• MSHA Approved
• RoHS Compliant
Packaging:
• 250' (76.2 m), 1000' (304.8 m)
• Other put-ups available on special order
COLOR CODE CHART
NO. OF
CONDUCTORS
3
4
COLOR
Black, White, Green
Black, White, Red, Green
7
Rubber Cord
Cord & Cordset
Carolprene® Jacketed Type SOOW
90ºC 600 Volt UL /CSA Portable Cord
Product Construction:
Conductors:
• 18 through 2 AWG. fully annealed
stranded bare copper per ASTM B-174
Insulation:
• Premium-grade, color-coded 90ºC EPDM
• Color Code: See chart below
Jacket:
• Carolprene®, Black
• Temperature Range: -40ºC to +90ºC
Jacket Marking:
• CAROL (SIZE) (mm ) 90C (UL) WATER
RESISTANT SOOW CSA (-40C) FT-2
P-7K-123033 MSHA 600 VOLT RoHS
MADE IN USA
2
Applications:
• Portable tools and equipment
• Portable appliances
• Small motors and associated machinery
Features:
• Excellent resistance to oil and moisture
• Good tensile strength, elongation and
aging characteristics
• High flexibility
• Excellent abrasion resistance
• Water-resistant
• UL Listed and CSA certified for indoor
and outdoor use
Industry Approvals:
• UL Flexible Cord - Subject 62
• CSA Flexible Cord - C22.2-49
• MSHA Approved
• RoHS Compliant
Packaging:
• 250' (76.2 m), 500' (152.4 m),
1000’ (304.8 m)
• Other put-ups available on special order
COLOR CODE CHART
NO. OF
CONDUCTORS
2
3
4
5
COLOR
Black, White
Black, White, Green
Black, White, Red, Green
Black, White, Red, Orange, Green
TYPE SOOW – 600 VOLT – UL/CSA
NOMINAL INS.
THICKNESS
AWG. COND.
SIZE STRAND INCHES mm
NOMINAL O.D.
NO. OF
COND.
02763
02769
02770
2
18
16/30
0.030
0.76
0.345
8.76
10
72
250'
3
18
16/30
0.030
0.76
0.365
9.27
10
84
250'
4
18
16/30
0.030
0.76
0.390
9.91
7
101
250'
02722
02765
02766
2
16
26/30
0.030
0.76
0.370
9.40
13
83
250'
3
16
26/30
0.030
0.76
0.390
9.91
13
103
250'
4
16
26/30
0.030
0.76
0.420
10.67
10
119
250'
02723
02762
02768
2
14
41/30
0.045
1.14
0.510
12.95
18
158
250'
3
14
41/30
0.045
1.14
0.535
13.59
18
172
250'
4
14
41/30
0.045
1.14
0.575
14.61
15
208
250'
02724
02725
02726
2
12
65/30
0.045
1.14
0.570
14.48
25
195
250'
3
12
65/30
0.045
1.14
0.595
15.11
25
229
250'
4
12
65/30
0.045
1.14
0.650
16.51
20
280
250'
02767
02728
02727
2
10
104/30
0.045
1.14
0.620
15.75
30
235
250'
3
10
104/30
0.045
1.14
0.660
16.76
30
295
250'
4
10
104/30
0.045
1.14
0.715
18.16
25
353
250'
16063
16064
16065
3
8
133/29
0.060
1.52
0.845
21.46
40
525
250'
4
8
133/29
0.060
1.52
0.960
24.38
35
676
250'
5
8
133/29
0.060
1.52
1.075
27.31
28
795
250'
16073
16074
16075
3
6
133/27
0.060
1.52
0.980
24.89
55
703
250'
4
6
133/27
0.060
1.52
1.080
27.43
45
891
250'
5
6
133/27
0.060
1.52
1.200
30.48
36
1123
250'
16083
16084
16085
3
4
133/25
0.060
1.52
1.140
28.96
70
1022
250'
4
4
133/25
0.060
1.52
1.260
32.00
60
1336
250'
5
4
133/25
0.060
1.52
1.365
34.67
48
1587
250'
16093
16094
16095*
3
2
133/23
0.060
1.52
1.330
33.78
95
1484
250'
4
2
133/23
0.060
1.52
1.460
37.08
80
1869
250'
5
2
133/23
0.060
1.52
1.580
40.13
64
2240
250'
INCHES
mm
Cord furnished with UL and CSA labels.
* Non-stock item; minimum quantity purchase required.
†G reen conductor for grounding only. Ampacities based on NEC table 400.5(A).
(S)
Actual shipping weight may vary.
8
APPROX.
CURRENT NET WT.
AMPS† LBS/M' (S)
CATALOG
NUMBER
STD.
CTN.
Rubber Cord
Cord & Cordset
Super Vu-Tron® Multi-Conductor Type SOOW
90ºC 600 Volt UL /CSA Portable Cord
Product Construction:
Conductors:
• 18 and 16 AWG. fully annealed stranded
bare copper per ASTM B-174
Insulation:
• Premium-grade, color-coded 90ºC EPDM
• Color Code: See chart below
Jacket:
• Super Vu-Tron® 90ºC, Black
• Temperature Range: -40ºC to +90ºC
TYPE S00W – 600 VOLT – UL/CSA
Jacket Marking:
• CAROL Super Vu-Tron (SIZE) (mm2)
90C (UL) WATER RESISTANT SOOW
CSA (-40C) FT-2 P-7K-123033 MSHA
600 VOLT RoHS MADE IN USA
CATALOG
NUMBER
09805
09806
09807
09808
09810
09812
09814
09816
09818*
09820
09822*
09824
09827*
09830*
Applications:
• Control circuits
• Tools
• Heavy industrial, processing and
construction equipment
Features:
• Extra-flexible stranding
• Abrasion-resistant
• Resists oils and solvents
• Flame-resistant
• Ozone-resistant
• 90ºC rated conductors and jacket
• Water-resistant
• UL Listed and CSA Certified for indoor
and outdoor use
Industry Approvals:
• UL Flexible Cord - UL Subject 62
• CSA Flexible Cord - C22.2-49
• MSHA Approved
• RoHS Compliant
09605
09606
09607
09608
09609
09610
09612
09614
09616
09618*
09620
09622*
09624
09626*
09630
Packaging:
• 5- through 8-conductor available on 250'
(76.2 m), 500' (152.4 m), and 1000'
(304.8 m) reels
• 9+ cond. available on long-length reels
• Other put-ups available on special order
COLOR CODE CHART
NO. OF
NO. OF
COND. COLOR TRACER COND. COLOR TRACER
1
2
3
4
5
6
7
8
9
10
11
14
Black
—
White
—
Red
—
Green
—
Orange
—
Blue
—
White
Black
Red
Black
Green
Black
Black
White
Red
White
Green
White
Blue
White
Black
Red
White
Red
Orange Black
12
13
14
15
16
17
18
19
20
21
Blue
Note: Colors repeat
after 21 conductors.
Black
Orange Red
Blue
Red
Red
Green
Orange Green
NO. OF
COND.
NOMINAL INS.
THICKNESS
NOMINAL O.D.
AWG.
SIZE
COND.
STRAND
INCHES
mm
INCHES
mm
5
18
16/30
0.030
0.76
0.465
11.81
6
18
16/30
0.030
0.76
0.495
7
18
16/30
0.030
0.76
0.520
8
18
16/30
0.030
0.76
0.530
13.46
10
18
16/30
0.030
0.76
0.595
12
18
16/30
0.030
0.76
0.600
APPROX.
CURRENT NET WT.
(1)
AMPS
LBS/M' (S)
5.6
141
12.57
5.6
152
13.21
5.6
172
4.9
177
15.11
4.9
225
15.24
3.5
240
265
14
18
16/30
0.030
0.76
0.630
16.00
3.5
16
18
16/30
0.030
0.76
0.700
17.78
3.5
310
18
18
16/30
0.030
0.76
0.760
19.30
3.5
345
20
18
16/30
0.030
0.76
0.795
20.19
3.5
382
22
18
16/30
0.030
0.76
0.805
20.45
3.1
400
24
18
16/30
0.030
0.76
0.850
21.59
3.1
451
27
18
16/30
0.030
0.76
0.865
21.97
3.1
475
30
18
16/30
0.030
0.76
0.915
23.24
3.1
533
5
16
26/30
0.030
0.76
0.495
12.57
8.0
167
6
16
26/30
0.030
0.76
0.520
13.21
8.0
182
7
16
26/30
0.030
0.76
0.540
13.72
8.0
194
8
16
26/30
0.030
0.76
0.575
14.61
7.0
218
9
16
26/30
0.030
0.76
0.600
15.24
7.0
243
10
16
26/30
0.030
0.76
0.620
15.75
5.0
255
12
16
26/30
0.030
0.76
0.660
16.76
5.0
296
14
16
26/30
0.030
0.76
0.730
18.54
5.0
352
383
16
16
26/30
0.030
0.76
0.740
18.80
5.0
18
16
26/30
0.030
0.76
0.770
19.56
5.0
417
20
16
26/30
0.030
0.76
0.810
20.57
5.0
457
22
16
26/30
0.030
0.76
0.900
22.86
4.5
510
24
16
26/30
0.030
0.76
0.925
23.50
4.5
563
26
16
26/30
0.030
0.76
0.965
24.51
4.5
611
30
16
26/30
0.030
0.76
1.010
25.65
4.5
767
Values shown are for current-carrying conductors. A grounding conductor, or one which carries only the unbalance
current from other conductors, is NOT counted in determining current carrying capacity. Ampacities based on
NEC table 400.5(A).
* Non-stock item; minimum quantity purchase required.
(S)
Actual shipping weight may vary.
(1)
Rubber Cord
Cord & Cordset
Super Vu-Tron® Multi-Conductor Type SOOW
90ºC 600 Volt UL /CSA Portable Cord
Product Construction:
Conductors:
• 14 through 10 AWG. fully annealed
stranded bare copper per ASTM B-174
Insulation:
• Premium-grade, color-coded 90ºC EPDM
• Color Code: See chart below
Jacket:
• Super Vu-Tron® 90ºC, Black
• Temperature Range: -40ºC to +90ºC
TYPE S00W – 600 VOLT – UL/CSA
CATALOG
NUMBER
NO. OF
COND.
AWG.
SIZE
09405
09406
09407
09408
09409*
09410
09412
09414
09416
09418*
09420
09424
09428*
09430*
5
6
7
8
9
10
12
14
16
18
20
24
28
30
09205
09206
09207
09208
09209
09210
09212
09214
09216
09218*
09220
09224
09226
09227*
09228*
09230
5
6
7
8
9
10
12
14
16
18
20
24
26
27
28
30
09005
09006
09007
09008*
09010
09012
09016*
09020*
5
6
7
8
10
12
16
20
NOMINAL INS.
THICKNESS
mm
CURRENT
AMPS (1)
APPROX.
NET WT.
LBS/M'(S)
0.645
0.710
0.710
0.760
0.830
0.820
0.855
1.000
1.030
1.100
1.120
1.260
1.330
1.335
16.38
18.03
18.03
19.30
21.08
20.83
21.72
25.40
26.16
27.94
28.45
32.00
33.78
33.91
12.0
12.0
12.0
10.5
10.5
10.5
7.5
7.5
7.5
7.5
7.5
6.7
6.7
6.0
269
317
347
430
417
427
493
601
678
720
806
1003
1080
1153
0.715
0.740
0.790
0.825
0.900
1.000
1.010
1.020
1.135
1.175
1.170
1.435
1.380
1.455
1.500
1.455
18.16
18.80
20.07
20.96
22.86
25.40
25.65
25.91
28.83
29.85
29.72
36.45
35.05
37.72
38.10
36.96
16.0
16.0
16.0
14.0
14.0
14.0
10.0
10.0
10.0
10.0
10.0
9.0
9.0
9.0
9.0
9.0
333
412
465
526
517
649
669
731
933
920
989
1273
1324
1325
1355
1492
NOMINAL O.D.
COND.
STRAND
inCHES
mm
inCHES
14
14
14
14
14
14
14
14
14
14
14
14
14
14
41/30
41/30
41/30
41/30
41/30
41/30
41/30
41/30
41/30
41/30
41/30
41/30
41/30
41/30
0.045
0.045
0.045
0.045
0.045
0.045
0.045
0.045
0.045
0.045
0.045
0.045
0.045
0.045
1.14
1.14
1.14
1.14
1.14
1.14
1.14
1.14
1.14
1.14
1.14
1.14
1.14
1.14
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
65/30
65/30
65/30
65/30
65/30
65/30
65/30
65/30
65/30
65/30
65/30
65/30
65/30
65/30
65/30
65/30
0.045
0.045
0.045
0.045
0.045
0.045
0.045
0.045
0.045
0.045
0.045
0.045
0.045
0.045
0.045
0.045
1.14
1.14
1.14
1.14
1.14
1.14
1.14
1.14
1.14
1.14
1.14
1.14
1.14
1.14
1.14
1.14
10
10
10
10
10
10
10
10
104/30
104/30
104/30
104/30
104/30
104/30
104/30
104/30
0.045
0.045
0.045
0.045
0.045
0.045
0.045
0.045
1.14
1.14
1.14
1.14
1.14
1.14
1.14
1.14
0.770
0.875
0.900
0.935
1.020
1.070
1.230
1.325
19.56
22.23
22.86
23.75
25.91
27.18
31.24
33.66
20.0
20.0
20.0
17.5
17.5
12.5
12.5
12.5
472
565
552
682
758
871
1147
1445
Values shown are for current-carrying conductors. A grounding conductor, or one which carries only the unbalance
current from other conductors, is NOT counted in determining current carrying capacity. Ampacities based on
NEC table 400.5(A).
* Non-stock item; minimum quantity purchase required.
(S)
Actual shipping weight may vary.
(1)
Jacket Marking:
• CAROL Super Vu-Tron (SIZE) (mm2)
90C (UL) WATER RESISTANT SOOW
CSA (-40C) FT-2 P-7K-123033 MSHA
600 VOLT RoHS MADE IN USA
Applications:
• Control circuits
• Tools
• Heavy industrial, processing and
construction equipment
Features:
• Extra-flexible stranding
• Abrasion-resistant
• Resists oils and solvents
• Flame-resistant
• Ozone-resistant
• 90ºC rated conductors and jacket
• Water-resistant
• UL Listed and CSA Certified for indoor
and outdoor use
Industry Approvals:
• UL Flexible Cord - UL Subject 62
• CSA Flexible Cord - C22.2-49
• MSHA Approved
• RoHS Compliant
Packaging:
• 5- through 8-conductor available on 250'
(76.2 m), 500' (152.4 m), and 1000' (304.8
m) reels
• 9+ cond. available on long-length reels
• Other put-ups available on special order
COLOR CODE CHART
NO. OF
NO. OF
COND. COLOR TRACER COND. COLOR TRACER
1
2
3
4
5
6
7
8
9
10
11
Black
—
White
—
Red
—
Green
—
Orange
—
Blue
—
White
Black
Red
Black
Green
Black
Black
White
Red
White
Orange Black
12
13
14
15
16
17
18
19
20
21
Blue
Note: Colors repeat
after 21 conductors.
Black
Green White
Blue
White
Black
Red
White
Red
Orange Red
Blue
Red
Red
Green
Orange Green
15
Download