POWER FACTOR CORRECTION WWW.PDC.CO.NZ W H AT I S P O W E R FA C T O R ? Power Factor is the ratio of true power used (kW) to the apparent power (kVA) used in an electrical circuit. A poor power factor (0.95 PF or less) is caused when a circuit has a high level of inductive loads (predominantly electric motors) causing the circuit voltage and current waveforms to be out of phase and the resultant using more apparent power than is needed. HOW DOES IT AFFECT MY BUSINESS? WHAT CAN I DO TO PREVENT THIS? A poor power factor (less than 0.95 PF) may cause a tariff to be charged on your power bill, or an excess of kVA peak demand or both. It will increase your overall current loading and reduce spare capacity in your transformer, cables and electrical switchgear. By introducing Capacitors into the circuit, the Capacitive reactive power (in kVAr) balances the inductive reactive power to bring the Apparent power (kVA) closer to the true power (kW), the resultant being a PF of 0.95 or better or kW = kVA. This process is called Power Factor Correction and may take the form of individualised capacitors or an Automatic Power Factor Correction Unit (APFCU) depending on circuit requirements. HOW CAN PDC HELP? For overloaded sites Power Factor Correction is one of the quickest ways to reduce load and may help prevent costly infrastructure upgrades. PDC can partner with you to analyse, specify and supply the correct PFC unit for each unique site to remove the Power Factor tarriffs and reduce the kVA peak demand. Available system capacity is increased and costly electrical infrastructure upgrades can be avoided. CONTACT PDC FOR MORE INFORMATION AND SPECIALISED ADVICE ON POWER FACTOR CORRECTION. POWER-VAr P O W E R FAC T O R C O R R E C T I O N SYSTEM The POWER-VAr Power Factor Correction System by PDC is manufactured in New Zealand for industrial and commercial three phase 400/415V installations. To remove Power Factor tariffs, kVA peak demand, or free up supply capacity in electrical infrastructure, the PDC Power-VAR will be a champion in improving energy usage and reducing operational costs. Built on a solid electrical manufacturing pedigree, PDC has designed the Power-VAr to be robust, upgradable and serviceable ensuring a long service life history. Sourced components are of a high quality and are backed up by supplier and PDC quality assurance. With qualified maintenance, your PDC Power Factor Correction unit will give you outstanding service for many years achieving an excellent return on your investment. WWW.PDC.CO.NZ S P E C I F I C AT I O N Height ( typical) 2100mm (including plinth 100mm) Width 800mm Depth 600mm Colour RAL 7032 (Grey) Mounting Floor mounted Voltage 400/415V 3 phase Frequency 50 Hz Range 75 kVAr + Reactors 7% 3 Phase Harmonic Blocking Capacitors 3 Phase - IEC 60831 Environment Indoor, IP20, Oil Filled Ambient range limit + 40 Degrees C CT requirement 5A secondary (CT not supplied) Cooling Fan forced ventilation via thermostat Servicing Annual Contactors AC3 rated Cable entry Top or bottom. (Top standard) Integration (not fitted standard) Modbus, alarm contacts Alarm options (not fitted standard) Beacon, Sounder, O/P to BMS Step protection HRC (MCCB option available), System protection Overvoltage/Current/ Harmonic /temp cut out Capacitor protection Over pressure disconnect PA R T S L I S T Power Factor Capacitors 3 Phase Resin Impregnated Code PFC0140 PFC01540 PFC0240 Oil Impregnated 400/415V kVAr Dia (mm) Length (mm) Code 415V kVAr 440V kVAr Dia (mm) Length (mm) 1 55 165 PFC1052 6.25 7 85 190 1.5 55 165 PFC1252 8 9 85 190 2 55 165 PFC1244 10 12.5 85 265 PFC02540 2.5 55 165 PFC2052 12.5 14 85 265 PFC0340 3 65 205 PFC2552 15.5 17.5 85 265 PFC0440 4 65 205 PFC2044 17.8 20 85 265 PFC0540 5 65 205 PFC2244 20 22.5 85 265 PFC07540 7.5 75 208 PFC2544 22.5 25 85 265 PFC1040 10 85 208 PFC2844 25 28 85 265 PFC1240 12.5 85 208 Harmonic Filter Reactors 7% 189 Hz Code Power Factor Control Relay Code PFCR06 PFCR14 Contactor steps Size (mm) 6 144 x 144 14 144 x 144 kVAr @ 415V PFR06 6.25 PFR08 8.3 PFR12 12.5 PFR17 16.7 PFR25 25 PFR33 33 PFR50 50 PFR67 66.7 Power-VAr Power Factor Correction Systems by PDC Brought to you by: Size( H x W x D) mm Floor/ Wall n 800 x 600 x 300 Wall n 800 x 600 x 300 Wall 75 n 800 x 600 x 300 Wall PFCU75R 75 y 1600 x 800 x 600 Floor PFCU100R 100 y 1600 x 800 x 600 Floor PFCU125R 125 y 1600 x 800 x 600 Floor PFCU150R 150 y 2100 x 800 x 600 Floor PFCU200R 200 y 2100 x 800 x 600 Floor PFCU250R 250 y 2100 x 800 x 600 Floor PFCU300R 300 y 2100 x 800 x 600 Floor PFCU350R 350 y 2100 x 800 x 600 Floor PFCU380R 380 y 2100 x 800 x 600 Floor Code kVAr PFCU30 (mini) 30 PFCU45 (mini) 60 PFCU75 (mini) Reactors Christchurch Office PO Box 9022 388 - 396 Tuam St, Phillipstown, Christchurch 8011 New Zealand P +64 3 335 0366 F +64 3 335 0980 E switchboards@pdc.co.nz Northern Region/Auckland PO Box 12 249 30 Fairfax Ave, Penrose, Auckland 1061 New Zealand P +64 9 526 7881 F +64 9 579 8742 E switchboards@pdc.co.nz